Sunteți pe pagina 1din 4

3

I.S. Isolators
I.S. Isolators (DIN Rail Mounting) Switching Repeater Type 9350 Intrinsically safe input [EEx ia] IIC Power supply 18...35 V DC Galvanic isolation between input, output and power supply Open-circuit and short-circuit monitoring (disconnectable) 1 and 2 channels Operating mode can be set Transmission frequency up to 10 kHz Active or passive inputs Installation in Zone 2 (Div 2) possible EMC tested, CE marking

LED indication switching state and open-circuit / short-circuit channel 1 LED indication power supply Switches for setting operating mode LED indication switching state and open-circuit / short-circuit channel 2

Basic function: binary/digital input, 1 and 2 channels The switching repeaters are suitable typically for intrinsically safe operation of contacts, proximity switches to DIN 19234 (NAMUR), optocoupler outputs, etc. They are also suitable for pulsed signals.
Hazardous area
3 1 7 (+) 9 (-) 4 1 Outputs see page 3/38 channel 2 (only types 9350/2...) Load 2 Supply Digital input 2 5 6 7

I.S.

8 (+)

9 L+ 24 V DC L-

3/36

I.S. Isolators (DIN Rail Mounting) Switching Repeater Type 9350


Selection table Version 2 channels 2 channels 2 channels 1 channel 1 channel 1 channel 1 channel 1 channel Output signal contact power contact electronic signal contact power contact electronic electronic + signal contact electronic Input NAMUR NAMUR NAMUR NAMUR NAMUR NAMUR NAMUR for voltage pulses Ordering code 9350/20-11-10 9350/20-12-10 9350/20-14-10 9350/10-11-10 9350/10-12-10 9350/10-14-10 9350/10-15-10 9350/10-24-10

Safety data for input Certifications Marking Classification BVS (Europe, CENELEC), CSA (Canada), SEV (Switzerland), FTZU (Czech Republic), EVPU (Slovakia), BKI (Hungary), KDB (Poland), VNIIEF (Russia), FM (USA) [EEx ia] IIC/IIB according to CENELEC associated electrical apparatus

Safe maximum values (CENELEC) per input Types Max. voltage Um Max. current lm Max power Pm Max. capacitance Ca for [EEx ia] IIC/IIB Max. inductance La for [EEx ia] IIC/IIB 9350/.0-1.-10 10.6 V 29.7 mA 79 mW 2.5 F / 15 F 40 mH / 150 mH 9350/10-24-10*) 10.6 V 1.1 mA 3 mW 2.5 /15 F, Cint 3nF 1H/1H

*) Type 9350/10-24-10 (passive input): only for connection to certified intrinsically safe circuits with Um 28 V Further information and combinations of values, see certifications

3/37

I.S. Isolators (DIN Rail Mounting) Switching Repeater Type 9350


Technical data Power supply Rated voltage UN Voltage range Types Rated current (for UN) IN Max. power consumption Polarity reversal protection Input Types 9350/.0-1.-10: to DIN 19234 (NAMUR) Type 9350/10-24-10: for active sources/pulses voltage for ON voltage for OFF Output Types Contact rating Max. switching voltage Max. switching current Max. switching power Min. contact load (guideline) Max. switching frequency Electronic output (short-circuit proof): Rated voltage Rated current Switching frequency Overview Types 9350/20-11-10 9350/20-12-10
1 5 2 2

24 V DC 18..35 V DC 9350/20-11-10 9350/20-14-10 9350/10-11-10 9350/10-14-10 9350/10-24-10 9350/10-15-10 9350/20-12-10 9350/10-12-10 42 mA 1.0 W yes 38 mA 0.91 W yes 32 mA 0.77 W yes 24 mA 0.58 W yes 24 mA 0.58 W yes 36 mA 0.86 W yes

6.5 V 7.5 V..24 V

9350/.0-11-10 AC 125 V 0.5 A 50 VA DC 150 V 0.5 A 25 W 1 V, 100 A 15 Hz 35 V 50 mA 10 kHz AC 250 V 2A 100 VA

9350/.0-12-10 DC 250 V 2A 50 W 12 V, 100 mA 15 Hz

9350/20-14-10

9350/10-11-10 9350/10-12-10
1 5 2 3 3 1 5

9350/10-14-10 9350/10-24-10
1 5

9350/10-15-10

1 5

2 3

Open-circuit and/or short-circuit Output behavior on open-circuit or short-circuit Monitoring disconnectable OFF

Dimensions (Casing type A), mechanical data, ambient conditions and accessories see page 3/58f.

We reserve the right to make alterations to the technical data, weights, dimensions, designs and products available without notice. The illustrations cannot be considered binding.

3/38

I.S. Isolators (DIN Rail Mounting) Switching Repeater Type 9350

3/39