Documente Academic
Documente Profesional
Documente Cultură
I.S. Isolators
I.S. Isolators (DIN Rail Mounting) Switching Repeater Type 9350 Intrinsically safe input [EEx ia] IIC Power supply 18...35 V DC Galvanic isolation between input, output and power supply Open-circuit and short-circuit monitoring (disconnectable) 1 and 2 channels Operating mode can be set Transmission frequency up to 10 kHz Active or passive inputs Installation in Zone 2 (Div 2) possible EMC tested, CE marking
LED indication switching state and open-circuit / short-circuit channel 1 LED indication power supply Switches for setting operating mode LED indication switching state and open-circuit / short-circuit channel 2
Basic function: binary/digital input, 1 and 2 channels The switching repeaters are suitable typically for intrinsically safe operation of contacts, proximity switches to DIN 19234 (NAMUR), optocoupler outputs, etc. They are also suitable for pulsed signals.
Hazardous area
3 1 7 (+) 9 (-) 4 1 Outputs see page 3/38 channel 2 (only types 9350/2...) Load 2 Supply Digital input 2 5 6 7
I.S.
8 (+)
9 L+ 24 V DC L-
3/36
Safety data for input Certifications Marking Classification BVS (Europe, CENELEC), CSA (Canada), SEV (Switzerland), FTZU (Czech Republic), EVPU (Slovakia), BKI (Hungary), KDB (Poland), VNIIEF (Russia), FM (USA) [EEx ia] IIC/IIB according to CENELEC associated electrical apparatus
Safe maximum values (CENELEC) per input Types Max. voltage Um Max. current lm Max power Pm Max. capacitance Ca for [EEx ia] IIC/IIB Max. inductance La for [EEx ia] IIC/IIB 9350/.0-1.-10 10.6 V 29.7 mA 79 mW 2.5 F / 15 F 40 mH / 150 mH 9350/10-24-10*) 10.6 V 1.1 mA 3 mW 2.5 /15 F, Cint 3nF 1H/1H
*) Type 9350/10-24-10 (passive input): only for connection to certified intrinsically safe circuits with Um 28 V Further information and combinations of values, see certifications
3/37
24 V DC 18..35 V DC 9350/20-11-10 9350/20-14-10 9350/10-11-10 9350/10-14-10 9350/10-24-10 9350/10-15-10 9350/20-12-10 9350/10-12-10 42 mA 1.0 W yes 38 mA 0.91 W yes 32 mA 0.77 W yes 24 mA 0.58 W yes 24 mA 0.58 W yes 36 mA 0.86 W yes
9350/20-14-10
9350/10-11-10 9350/10-12-10
1 5 2 3 3 1 5
9350/10-14-10 9350/10-24-10
1 5
9350/10-15-10
1 5
2 3
Open-circuit and/or short-circuit Output behavior on open-circuit or short-circuit Monitoring disconnectable OFF
Dimensions (Casing type A), mechanical data, ambient conditions and accessories see page 3/58f.
We reserve the right to make alterations to the technical data, weights, dimensions, designs and products available without notice. The illustrations cannot be considered binding.
3/38
3/39