Sunteți pe pagina 1din 6

2X500 MW Sagardighi Thermal Power Plant (Unit-3 4)- Coal Handling Plant Package,

at Sagardighi, WestBengal for West Bengal Power Development Corporation Ltd.

ANNEXURE-A
Maximum Demand Calculation of LT (415 V) Switchgear near Track Hopper & Wagon Tippler Complex :Source of supply: 11KV HT Swichgear located near Crusher House
Sl.
No.

1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
10.0
11.0
12.0
13.0
14.0
15.0
16.0
17.0
18.0
19.0
20.0
21.0
22.0
23.0
24.0
25.0
26.0
27.0
28.0
29.0
30.0
31.0
32.0
33.0
34.0

Nameplate
Rating kW

No. of Equipment
Description of Loads

WT Pump Motor-1 for Tilting Hydraulic Drive


WT Pump Motor-2 for Tilting Hydraulic Drive
WT Pump Motor for Clamping Hydraulic Drive
Oil Cooler for Pump Motor for Tilting Hydraulic Drive
Brake Release motor for Tilting Hydraulic Drive
Oil Cooler for Pump Motor for Clamping Hydraulic Drive
Oil Circulation for WT Tilting Hydraulic Drive
SAC Pump Motor-1 for Hydraulic Drive
SAC Pump Motor-2 for Hydraulic Drive
Oil Cooler for Pump Motor-1 for SAC Hydraulic Drive
Oil Cooler for Pump Motor-2 for SAC Hydraulic Drive
Oil Circulation for SAC Hydraulic Drive
Lubrication Panel for Wagon Tippler
In Motion Weigh Bridge for Wagon Tippler
Dribble Conveyor DC-1
Paddle Feeder PF-1, PF-2, PF-3 & PF-4
Belt Conveyor 11A & 11B
Suspended Magnet SM-1 & SM-2
Compressor for BOBR Wagon Loading System CASC-1A & 1B
Sump Pump at Track Hopper SPDW-1, 2, 3, 4, 5, 6, 7 & 8
Sump Pump at Wagon Tippler SPDW-11 & 12
Sump Pump at TP-11 & TP-12 SPDW-9 & 10
Ventilation Supply Fan for TRH VSF-1, 2, 3, 4, 5, 6, 7 & 8
Ventilation Supply Fan for TP-12 VSF-9
Ventilation Supply Fan for WT-2, TP-11 & TP-12 VSF-10
Ventilation Supply Fan for Conveyor 12A & 12B VSF-11
Ventilation Axial Fan for TRH & TP-12 VEF-1, 2, 3, 4, 5 & 6
Ventilation Axial Fan for WT-2, TP-11 & TP-12 VEF-7
Ventilation Axial Fan for Conveyor 12A & 12B VEF-8
Ventilation Supply Fan for TRH MCC VSF-14
Pump for Ventilation System for TRH MCC VSP-3A & 3B
UPS
MLDB
ACDB (For all Others Load like SOV, Space Heater, CBS, ZSS etc.)

Working

Standby

Total

(kW)

(kW)

(a)

(b)

c=(a)+(b)

(d1)

(d2)

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
1
4
1
1
8
1
1
1
6
1
1
1
1
1
1
1

0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
3
1
0
1
4
1
1
0
0
0
0
0
0
0
0
1
0
0
0

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
4
2
2
2
8
2
2
8
1
1
1
6
1
1
1
2
1
1
1

110
110
75
5.5
2.2
5.5
3.7
160
160
5.5
5.5
2.2
1.5
2
15
93
160
11
37
22
15
22
22
15
22
30
9.3
11
11
11
5.5
10.75
90
27

99
99
67.5
4.95
1.98
4.95
3.33
144
144
4.95
4.95
1.98
1.35
1.8
13.5
74.6
119
9.3
30.8
18.7
11.24
18.7
18.3
12.5
18.2
24
7
9.0
9.0
9.8
4.5
10.8
90.0
27.0

Transformer Sizing
Net Load (KW)
Total Load (KVA)
Required Transformer Capacity(kVA) with 20% margin
Selected Transformer Capacity (kVA) {after considering voltage dip while starting any drive does not
exceeding the limit acceptable for equipment concerned but not exceeding 15% at the cable terminal}
Incomer selected (A)
Bus coupler selected (A)

Brake kW

Voltage
(V)

415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415

Duty Category
C= Continuous
I= Intermittent

Efficiency

Power
Factor

(e)

(h)

(i)

C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C

95.2%
95.2%
90.5%
82.0%
86.4%
75.0%
88.3%
95.8%
95.8%
82.0%
82.0%
86.4%
75.0%
75.0%
91.8%
89.0%
95.8%
91.0%
93.6%
92.6%
91.8%
92.6%
92.6%
91.8%
92.6%
93.2%
90.5%
91.0%
91.0%
91.0%
89.0%
100.0%
100.0%
100.0%

0.92
0.92
0.78
0.8
0.72
0.68
0.8
0.91
0.91
0.8
0.8
0.72
0.68
0.68
0.88
0.84
0.91
0.85
0.81
0.85
0.88
0.85
0.85
0.88
0.85
0.88
0.85
0.85
0.85
0.85
0.84
0.9
0.9
0.9

Nett Demand
Remarks
(kW)

(KVA)

(j)=(a)x(d2)/
(k)=(j)/(i)
(h)
103.99
113.03
103.99
113.03
74.59
95.62
6.04
7.55
2.29
3.18
6.60
9.71
3.77
4.71
150.31
165.18
150.31
165.18
6.04
7.55
6.04
7.55
2.29
3.18
1.80
2.65
2.40
3.53
14.71
16.71
83.82
99.79
124.22
136.50
20.44
24.05
32.91
40.62
80.78
95.03
12.24
13.91
20.19
23.76
158.10
186.00
13.62
15.47
19.65
23.12
25.75
29.26
46.41
54.60
9.89
11.64
9.89
11.64
10.77
12.67
5.06
6.02
10.75
11.94
90.00
100.00
27.00
30.00

1436.65
1644.39
1973.26
2 Nos. 2000 KVA
(100% Stand By)
3200
3200

Hence selected Transformer 2000 KVA, 11/0.433 KV, DYN11, ONAN


McNally Bharat Engineering Co. Ltd.
Drawing No.-2-PM07-DC00-3-0003 (Rev. No.-0)

Page 1 of 6

2X500 MW Sagardighi Thermal Power Plant (Unit-3 4)- Coal Handling Plant Package,
at Sagardighi, WestBengal for West Bengal Power Development Corporation Ltd.

ANNEXURE-B
Maximum Demand Calculation of LT (415 V) Switchgear (Bus-1) near Crusher House :Source of supply: 11KV HT Swichgear located near Crusher House
Sl.
No.

1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
10.0
11.0
12.0
13.0
14.0
15.0
16.0

In Line Magnetic Separator ILMS-1


Rack & Pinion Gate RPG-1 & 2
Drive of Roller Screen RS-1 & 2
Reversible Belt Feeder RBF-1
Coal Sampling unit CSU-1
Passenger cum Goods Elevator EL-1
Belt Conveyor 14A
Dust Suppression Pump DSP-1A & 1B
Drinking Water Pump DW-1A & 1B
Dust Suppression Pump DSP-10A & 10B
DEF-1 Centrifugal Fan for Bag Filter-1
RAL for Bag Filter-1
Screw Conveyor for Bag Filter-1
Motorized Damper for Bag Filter-1
MLDB
ACDB (For all Others Load like SOV, Space Heater, CBS, ZSS etc.)
Transformer Sizing
Net Load (KW)
Total Load (KVA)
Required Transformer Capacity(kVA) with 20% margin

McNally Bharat Engineering Co. Ltd.


Drawing No.-2-PM07-DC00-3-0003 (Rev. No.-0)

Nameplate
Rating kW

No. of Equipment
Description of Loads

Brake kW

Working

Standby

Total

(kW)

(kW)

(a)

(b)

c=(a)+(b)

(d1)

(d2)

1
0
4
1
1
1
1
1
1
1
1
1
1
4
1
1

0
2
0
0
0
0
0
1
1
1
0
0
0
0
0
0

1
2
4
1
1
1
1
2
2
2
1
1
1
4
1
1

26
2.2
37
45
75
15
180
45
18.5
18.5
75
0.55
1.5
0.22
180
18

23
1.76
32
43
60
13
170
37
15.4
15.4
62
0.495
1.35
0.198
180.0
18.0

Voltage

Duty Category

(V)

C= Continuous
I= Intermittent

415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415

Efficiency

Power
Factor

(e)

(h)

(i)

C
I
C
C
C
C
C
C
C
C
C
C
C
C
C
C

92.5%
86.4%
93.6%
93.9%
92.3%
91.8%
95.8%
93.9%
92.2%
92.2%
94.7%
70.0%
75.0%
70.0%
100.0%
100.0%

0.82
0.84
0.81
0.82
0.84
0.88
0.91
0.82
0.85
0.85
0.9
0.6
0.7
0.6
0.9
0.9

Nett Demand
Remarks
(kW)

(KVA)

(j)=(a)x(d2)/(
(k)=(j)/(i)
h)
24.86
30.32
0.00
0.00
136.75
168.83
45.79
55.85
65.01
77.39
14.16
16.09
177.45
195.00
39.40
48.05
16.70
19.65
16.70
19.65
65.47
72.74
0.71
1.18
1.80
2.57
1.13
1.89
180.00
200.00
18.00
20.00

803.95
929.22
1115.06

Page 2 of 6

2X500 MW Sagardighi Thermal Power Plant (Unit-3 4)- Coal Handling Plant Package,
at Sagardighi, WestBengal for West Bengal Power Development Corporation Ltd.

ANNEXURE-B
Maximum Demand Calculation of LT (415 V) Switchgear (Bus-3) near Crusher House :Source of supply: 11KV HT Swichgear located near Crusher House

1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
10.0
11.0
12.0
13.0
14.0
15.0

Nameplate
Rating kW

No. of Equipment

Sl.
No.

Description of Loads

In Line Magnetic Separator ILMS-2


Rack & Pinion Gate RPG-3 & 4
Drive of Roller Screen RS-3 & 4
Reversible Belt Feeder RBF-2
Belt Conveyor 13C
Belt Conveyor 14B
DFDS Pump DFDSP-1A & 1B
Dust Suppression Pump DSP-2A & 2B
Dust Suppression Pump DSP-3A & 3B
DFDS Compressor DFDSC-1A, 1B, 1C & 1D
Dust Suppression Pump DSP-11A & 11B
Ventilation Supply Fan for Crusher House MCC VSF-13
Pump for Ventilation System for Crusher House MCC VSP-1A & 1B
UPS
Battery Charger

Working

Standby

Total

(kW)

(kW)

(a)

(b)

c=(a)+(b)

(d1)

(d2)

1
0
4
1
1
1
1
1
1
2
1
1
1
1
1

0
2
0
0
0
0
1
1
1
2
1
0
1
0
0

1
2
4
1
1
1
2
2
2
4
2
1
2
1
1

26
2.2
37
45
160
180
22
22
75
75
37
18.5
7.5
18
54

23
1.76
32
43
68
170
18.2
18.1
62
62.5
29
16.3
6.2
18.0
54.0

Transformer Sizing
Net Load (KW)
Total Load (KVA)
Required Transformer Capacity(kVA) with 20% margin
Nett Load for PMCC-2 (for both Bus=1 & Bus-3) [KW]
Total Load for PMCC-2 (for both Bus=1 & Bus-3) [KW]
Selected Transformer Capacity (kVA) {after considering voltage dip while starting any drive does not
exceeding the limit acceptable for equipment concerned but not exceeding 15% at the cable terminal}
Incomer selected (A)
Bus coupler selected (A)

Brake kW

Voltage

Duty Category

(V)

C= Continuous
I= Intermittent

415
415
415
415
415
415
415
415
415
415
415
415
415
415
415

Efficiency

Power
Factor

(e)

(h)

(i)

C
I
C
C
C
C
C
C
C
C
C
C
C
C
C

92.5%
86.4%
93.6%
93.9%
95.8%
95.8%
92.6%
92.6%
94.7%
94.7%
93.6%
92.2%
90.1%
100.0%
100.0%

0.82
0.84
0.81
0.82
0.91
0.91
0.85
0.85
0.9
0.9
0.81
0.85
0.82
0.9
0.9

Nett Demand
Remarks
(kW)

(KVA)

(j)=(a)x(d2)/(
(k)=(j)/(i)
h)
24.86
30.32
0.00
0.00
136.75
168.83
45.79
55.85
70.98
78.00
177.45
195.00
19.65
23.12
19.55
23.00
65.47
72.74
132.00
146.66
30.98
38.25
17.72
20.85
6.88
8.39
18.00
20.00
54.00
60.00

820.10
941.02
1129.22
1624.05
1870.24
3 Nos. 1600 KVA
(3 X 50 %)
2500
2500

Hence selected Transformer 1600 KVA, 11/0.433 KV, DYN11, ONAN

McNally Bharat Engineering Co. Ltd.


Drawing No.-2-PM07-DC00-3-0003 (Rev. No.-0)

Page 3 of 6

2X500 MW Sagardighi Thermal Power Plant (Unit-3 4)- Coal Handling Plant Package,
at Sagardighi, WestBengal for West Bengal Power Development Corporation Ltd.

ANNEXURE-C
Maximum Demand Calculation of LT (415 V) Switchgear located at TP-17 :Source of supply: 11KV HT Swichgear located near Crusher House
Sl.
No.

1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
10.0
11.0
12.0
13.0
14.0
15.0
16.0
17.0
18.0
19.0
20.0
21.0
22.0
23.0
24.0
25.0
26.0
27.0
28.0
29.0
30.0
31.0
32.0
33.0
34.0
35.0
36.0
38.0
39.0

McNally Bharat Engineering Co. Ltd.


Drawing No.-2-PM07-DC00-3-0003 (Rev. No.-0)

Nameplate
Rating kW

No. of Equipment
Description of Loads

In Line Magnetic Separator ILMS-3 & ILMS-4


Coal Sampling unit CSU-2
Passenger cum Goods Elevator EL-2 & El-3
Rack & Pinion Gate RPG-5 & 6
Belt Conveyor 18, 19, 20 & 21
Drive of Travelling Tripper FTR-1, 2, 3 & 4
Brake of Travelling Tripper
Rail Clamp of Travelling Tripper
Flap Gate for Travelling Tripper
DEF-2 Centrifugal Fan for Bag Filter-2 at TP-16
RAL for Bag Filter-2 at TP-16
Motorized Damper for Bag Filter-2 at TP-16
DEF-3 Centrifugal Fan for Bag Filter-3 at TP-17
RAL for Bag Filter-3 at TP-17
Motorized Damper for Bag Filter-3 at TP-17
DEF-4 Centrifugal Fan for Bag Filter-4 at TP-18
RAL for Bag Filter-4 at TP-18
Motorized Damper for Bag Filter-4 at TP-18
DEF-5 Centrifugal Fan for Bag Filter-5 at TP-19
RAL for Bag Filter-5 at TP-19
Motorized Damper for Bag Filter-5 at TP-19
DEF-6 Centrifugal Fan for Bag Filter-6 at Roof of Bunker-3
RAL for Bag Filter-6 at Roof of Bunker-3
DEF-7 Centrifugal Fan for Bag Filter-7 at Roof of Bunker-3
RAL for Bag Filter-7 at Roof of Bunker-3
DEF-8 Centrifugal Fan for Bag Filter-8 at Roof of Bunker-4
RAL for Bag Filter-8 at Roof of Bunker-4
DEF-9 Centrifugal Fan for Bag Filter-9 at Roof of Bunker-4
RAL for Bag Filter-9 at Roof of Bunker-4
Ventilation Axial Fan for Bunker-1 of Unit-3 VEF-16 to 25
Ventilation Axial Fan for Bunker-2 of Unit-3 VEF-26 to 35
Ventilation Axial Fan for Bunker-1 of Unit-4 VEF-16 to 27
Ventilation Axial Fan for Bunker-2 of Unit-4 VEF-16 to 28
Ventilation Supply Fan for TP-17 MCC VSF-14
Pump for Ventilation System for TP-17 MCC VSP-2A & 2B
UPS
MLDB
ACDB (For all Others Load like SOV, Space Heater, CBS, ZSS etc.)

Brake kW

Working

Standby

Total

(kW)

(kW)

(a)

(b)

c=(a)+(b)

(d1)

(d2)

2
1
2
0
2
8
4
8
0
1
1
6
1
1
6
1
1
6
1
1
4
1
1
1
1
1
1
1
1
10
10
10
10
1
1
1
1
1

0
0
0
2
2
0
0
0
8
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
0
0
0

2
1
2
2
4
8
4
8
8
1
1
6
1
1
6
1
1
6
1
1
4
1
1
1
1
1
1
1
1
10
10
10
10
1
2
1
1
1

26
75
15
2.2
160
5.5
0.2
0.3
5.5
15
0.55
0.22
15
0.55
0.22
15
0.55
0.22
15
0.55
0.22
45
0.55
45
0.55
45
0.55
45
0.55
0.55
0.55
0.55
0.55
11
5.5
9
135
27

23
64
13
1.76
156
4.7
0.18
0.27
4.7
12
0.495
0.198
12
0.495
0.198
12
0.495
0.198
12
0.495
0.198
37
0.495
37
0.495
37
0.495
37
0.495
0.41
0.41
0.41
0.41
9.8
4.5
9.0
135.0
27.0

Voltage

Duty Category

(V)

C= Continuous
I= Intermittent

415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415

Efficiency

Power
Factor

(e)

(h)

(i)

C
C
C
I
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C

92.5%
92.3%
90.1%
86.4%
95.8%
89.2%
60.0%
60.0%
89.2%
91.8%
70.0%
70.0%
91.8%
70.0%
70.0%
91.8%
70.0%
70.0%
91.8%
70.0%
70.0%
93.9%
70.0%
93.9%
70.0%
93.9%
70.0%
93.9%
70.0%
60.0%
60.0%
60.0%
60.0%
91.0%
89.2%
100.0%
100.0%
100.0%

0.82
0.84
0.84
0.84
0.91
0.8
0.6
0.6
0.8
0.88
0.6
0.6
0.88
0.6
0.6
0.88
0.6
0.6
0.88
0.6
0.6
0.82
0.6
0.82
0.6
0.82
0.6
0.82
0.6
0.6
0.6
0.6
0.6
0.85
0.8
0.9
0.9
0.9

Nett Demand
Remarks
(kW)

(KVA)

(j)=(a)x(d2)/(
(k)=(j)/(i)
h)
49.73
60.65
69.34
82.55
28.86
34.35
0.00
0.00
325.68
357.89
42.15
52.69
1.20
2.00
3.60
6.00
0.00
0.00
13.07
14.85
0.71
1.18
1.70
2.83
13.07
14.85
0.71
1.18
1.70
2.83
13.07
14.85
0.71
1.18
1.70
2.83
13.07
14.85
0.71
1.18
1.13
1.89
39.40
48.05
0.71
1.18
39.40
48.05
0.71
1.18
39.40
48.05
0.71
1.18
39.40
48.05
0.71
1.18
6.83
11.39
6.83
11.39
6.83
11.39
6.83
11.39
10.77
12.67
5.04
6.31
9.00
10.00
135.00
150.00
27.00
30.00

Page 4 of 6

2X500 MW Sagardighi Thermal Power Plant (Unit-3 4)- Coal Handling Plant Package,
at Sagardighi, WestBengal for West Bengal Power Development Corporation Ltd.

Transformer Sizing
Net Load (KW)
Total Load (KVA)
Required Transformer Capacity(kVA) with 20% margin
Selected Transformer Capacity (kVA) {after considering voltage dip while starting any drive does not
exceeding the limit acceptable for equipment concerned but not exceeding 15% at the cable terminal}
Incomer selected (A)
Bus coupler selected (A)

956.49
1122.09
1346.50
2 Nos. 1600 KVA
(100% Stand By)
2500
2500

Hence selected Transformer 1600 KVA, 11/0.433 KV, DYN11, ONAN

McNally Bharat Engineering Co. Ltd.


Drawing No.-2-PM07-DC00-3-0003 (Rev. No.-0)

Page 5 of 6

2X500 MW Sagardighi Thermal Power Plant (Unit-3 4)- Coal Handling Plant Package,
at Sagardighi, WestBengal for West Bengal Power Development Corporation Ltd.

ANNEXURE-D
Maximum Demand Calculation of MV (3300 kV) Switchgear located near Crusher House :Source of supply: 11KV HT Swichgear located near Crusher House
No. of Equipment

Sl.
No.

1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0

Description of Loads

Apron Feeder AFD-2


Belt Conveyor 12A & 12B
Ring Granulator Crusher CR-1, CR-2, CR-3 & CR-4
Reversible Belt Conveyor 22A
Reversible Belt Conveyor 22B
Belt Conveyor 13A & 13B
Belt Conveyor 15A & 15B
Belt Conveyor 16A & 16B
Belt Conveyor 17A & 17B

Nameplate
Rating kW

Brake kW

Working

Standby

Total

(kW)

(kW)

(a)

(b)

c=(a)+(b)

(d1)

(d2)

1
4
4
1
0
2
4
2
2

0
0
0
1
2
0
0
0
0

1
4
4
2
2
2
4
2
2

340
340
850
340
340
340
340
340
340

255
325
630
331
267
240
335
252
244

Transformer Sizing
Net Load (KW)
Total Load (KVA)
Required Transformer Capacity(kVA) with 10% margin

Voltage
(V)

415
415
415
415
415
415
415
415
415

Duty Category
C= Continuous
I= Intermittent

Efficiency

Power
Factor

(e)

(h)

(i)

C
C
C
C
C
C
C
C
C

95.0%
95.0%
94.0%
95.0%
95.0%
95.0%
95.0%
95.0%
95.0%

0.85
0.85
0.79
0.85
0.85
0.85
0.85
0.85
0.85

Nett Demand
Remarks
(kW)

(KVA)

(j)=(a)x(d2)/
(k)=(j)/(i)
(h)
268.42
315.79
1368.42
1609.91
2680.85
3393.48
348.42
409.91
0.00
0.00
505.26
594.43
1410.53
1659.44
530.53
624.15
513.68
604.33

7626.11
9211.44
10132.58

Selected Transformer Capacity (kVA) {after considering voltage dip while starting any drive does not
exceeding the limit acceptable for equipment concerned but not exceeding 15% at the cable terminal}

10200

Incomer selected (A)


Bus coupler selected (A)

2500
2500

Hence selected Transformer 10600 KVA, 11/3.45KV, DYN1, ONAN

McNally Bharat Engineering Co. Ltd.


Drawing No.-2-PM07-DC00-3-0003 (Rev. No.-0)

Page 6 of 6

S-ar putea să vă placă și