Pulsar
700 1000 1500 1000 RT2U 1500 RT2U EXB 1000/1500 EXB 1000/1500 RT2U Installation and User Manual Manuel dinstallation et dutilisation Manual de instalacin y de usuario Manual de instalao e do usurio

Downloaded from www.Manualslib.com manuals search engine

Downloaded from www.Manualslib.com manuals search engine

E N G L I S H

Installation and User Manual

Pulsar
Installation and User Manual

Revision History
Pulsar Installation and User Manual, 86-86700-00 Revision: A01 ECN#: 005282 5/2007

Copyright 2007 MGE Office Protection Systems All rights reserved. Printed in U.S.A. MGE Office Protection Systems 13 Whatney, Suite #101 Irvine, CA 92618
(949) 268-2800

For Technical Support, Customer Care Center, or Customer FAQ, please visit our website: www.mgeops.com or call (800) 279-7776

86-86700-00 A01
Downloaded from www.Manualslib.com manuals search engine

Pulsar

E N G L I S H

86-86700 A01
Downloaded from www.Manualslib.com manuals search engine

E N G L I S H

Contents

Introduction ..........................................................................................................................................1 Symbol Usage ....................................................................................................................................3

1. Presentation
1.1 1.2 1.3 Standard Positions..........................................................................................................1 1 Rear Panels ....................................................................................................................1 2 Control Panel ..................................................................................................................1 3

2. Installation
2.1 2.2 2.3 2.4 2.5 2.6 2.7 Unpacking and Contents Check ....................................................................................2 1 Installation of the RT Model in Tower Position ..............................................................2 2 Installation of the RT Model in a Rack ..........................................................................2 2 Communication Ports ....................................................................................................2 3 Connection to the Communication Port by Contact (2)..................................................2 4 Connections with a FlexPDU module ............................................................................2 5 UPS Connection ............................................................................................................2 5

3. Operation
3.1 3.2 3.3 3.4 3.5 Start-Up and Normal Operation......................................................................................3 1 Operation on Battery Power ..........................................................................................3 1 Return of AC Power........................................................................................................3 2 UPS Shutdown ..............................................................................................................3 2 Using the UPS Remote Control Functions ....................................................................3 2

4. Access to Measurements and Personalization Data


4.1 4.2 4.3 4.4 Display Menus Arrangement ..........................................................................................4 1 Access to Measurements ..............................................................................................4 1 Personalization Using the Control Panel........................................................................4 1 Personalization Using External Software ......................................................................4 2

5. Maintenance
5.1 5.2 Troubleshooting ..............................................................................................................5 1 Battery-module Replacement ........................................................................................5 2

Appendices
6.1 6.2 Technical Specifications ................................................................................................A 1 Programming the Programmable Outlets ......................................................................A 2 MGE Office Protection Systems Customer Care Center ..............................................A 4 Glossary ........................................................................................................................G 1

86-86700-00 A01
Downloaded from www.Manualslib.com manuals search engine

Contents

ci

Pulsar

E N G L I S H

86-86700-00 A01
Downloaded from www.Manualslib.com manuals search engine

E N G L I S H

Introduction

Thank you for selecting an MGE Office Protection Systems product to protect your electrical equipment. Pulsar has been designed with the utmost care. We recommend that you take the time to read this manual to take full advantage of the many features of your UPS (Uninterruptible Power System). Before installing Pulsar, please read the booklet on the required safety instructions. Then follow the indications in this manual. To discover the entire range of MGE Office Protection Systems products and the options available for the Pulsar range, we invite you to visit our web site at www.mgeops.com or contact your MGE Office Protection Systems representative.

Environmental protection
MGE Office Protection Systems has implemented an environmental-protection policy. Products are developed according to an eco-design approach.

Substances
This product does not contain CFCs, HCFCs, or asbestos.

Packing
To improve waste treatment and facilitate recycling, separate the various packing components. The cardboard we use comprises over 50% of recycled cardboard. Sacks and bags are made of polyethylene. 01 Packing materials are recyclable and bear the appropriate identification symbol.
PET

Material Polyethylene terephthalate High-density polyethylene Polyvinyl chloride Low-density polyethylene Polypropylene Polystyrene

Abbreviation PET HDPE PVC LDPE PP PS

Symbol number 01 02 03 04 05 06

01
PET

Follow all local regulations for the disposal of packing materials.

End of life
MGE Office Protection Systems will process products at the end of their service life in compliance with local regulations. MGE Office Protection Systems works with companies in charge of collecting and eliminating our products at the end of their service life.

Product The product is made up of recyclable materials. Dismantling and destruction must take place in compliance with all local regulations concerning waste. At the end of its service life, the product must be transported to a processing center for electrical and electronic waste. Battery The product contains lead-acid batteries that must be processed according to applicable local regulations concerning batteries. The battery may be removed and disposed of in compliance with correct local disposal regulations. The "Material Safety Data Sheets" (MSDS) for the batteries are available on our web site*. (*) For more information or to contact the Product Environmental manager, please visit our website: www.mgeops.com.

86-86700-00 A01
Downloaded from www.Manualslib.com manuals search engine

Introduction

Pulsar

E N G L I S H

Federal Communication Commission (FCC) statement


NOTE: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense

Symbol Usage

Important instructions that must always be followed

Information, advice, help

Visual indication

Action

Audible signal

LED off

LED on

2
Downloaded from www.Manualslib.com manuals search engine

Introduction

86-86700-00 A01

E N G L I S H

Presentation

1.1

Standard Positions
Tower Position
Dimensions (H x W x D) in mm / inches Pulsar 700 Pulsar 1000 Pulsar 1000 RT2U Pulsar 1500 Pulsar 1500 RT2U Pulsar EXB 1000/1500 Pulsar EXB 1000/1500 RT2U 242 x 158 x 400 / 9.52 x 6.22 x 15.74 242 x 158 x 400 / 9.52 x 6.22 x 15.74 438 x 86.5 x 480 / 17.24 x 3.4 x 18.9 242 x 158 x 450 / 9.52 x 6.22 x 17.71 438 x 86.5 x 480 / 17.24 x 3.4 x 18.9 242 x 158 x 400 / 9.52 x 6.22 x 15.74 440 x 86.5 x 480 / 17.32 x 3.4 x 18.9

Rack Position
Weights in kg / lbs Pulsar 700 Pulsar 1000 Pulsar 1000 RT2U Pulsar 1500 Pulsar 1500 RT2U Pulsar EXB 1000/1500 Pulsar EXB 1000/1500 RT2U 12.5 / 27.55 15 / 33 18 / 39.68 18 / 39.68 20.5 / 45.2 21 / 46.3 24.5 / 54

86-86700-00 A01
Downloaded from www.Manualslib.com manuals search engine

Contents

11

Pulsar

E N G L I S H

1.2

Rear Panels
Pulsar 700 / 1000 / 1500
(1) USB communication port
4 2

(2) RS232 and dry contacts communication port (3) Connector for automatic recognition of a battery EXB module (except on Pulsar 700) (4) Slot for optional communication card (5) Connector for remote ON/OFF and RPO (Remote Power Off) control (6) Connector for battery EXB module, except on Pulsar 700

1 8

5 3 6 7 10 9

(7) Group of programmable outlets for connection of equipment (8) Group of outlets for connection of equipment (9) Input power plug for connection to AC-power source (10) LED (SWF) indicating distribution system phase/neutral reversal

Pulsar 1000 RT2U / 1500 RT2U


1 2 5 10 3 6 4 8 9

Pulsar EXB 1000/1500 (optional battery module)


(11) Connectors for battery modules (to the UPS or to the other battery modules) (12) Connectors for automatic recognition of battery modules

12
Downloaded from www.Manualslib.com manuals search engine

Presentation

86-86700-00 A01

E N G L I S H

Installation and User Manual

Pulsar EXB 1000/1500 RT2U (optional battery module)

1.3

Control Panel

(20) Load protected LED (21) Downgraded operation LED (22) Load not protected LED (23) Alphanumeric display (24) Escape (cancel) button (25) Scroll button (26) Enter (confirm) button (27) ON/OFF button for UPS and outlets

86-86700-00 A01
Downloaded from www.Manualslib.com manuals search engine

Presentation

13

Pulsar

E N G L I S H

(This page left blank intentionally)

14
Downloaded from www.Manualslib.com manuals search engine

86-86700-00 A01

E N G L I S H

Installation

2.1

Unpacking and Contents Check

(30) (31) (33) (34) (36)

Pulsar 700, 1000, 1500 Pulsar 1000 RT2U, 1500 RT2U RS232 communication cable USB communication cable Solution-Pac CD-ROM and documentation Elements supplied depending on the version or option

(37) Mounting kit for 19-inch bays (38) 2 supports for the upright position (RT model only) (41) NMC communication card (optional)

Packing materials must be disposed of in compliance with all local regulations concerning waste. Recycling symbols are printed on the packing materials to facilitate sorting.

86-86700-00 A01
Downloaded from www.Manualslib.com manuals search engine

Installation

21

Pulsar

E N G L I S H

2.2

Installation of the RT Model in Tower Position

2.3

Installation of the RT Model in a Rack


It is advised to install the battery EXB module(s) at the lowest position in the rack, then install the UPS above. Follow steps 1 to 4 for module mounting on the rails.

The rails and necessary hardware (37) are supplied by MGE Office Protection Systems.

22
Downloaded from www.Manualslib.com manuals search engine

Installation

86-86700-00 A01

E N G L I S H

Installation and User Manual

2.4

Communication Ports
Connection of RS232 or USB communication port (optional)
The RS232 and USB communication ports cannot operate simultaneously.

Tower model
1. Connect the RS232 (33) or USB (34) communication cable to the serial or USB port on the computer equipment. 2. Connect the other end of the communication cable (33) or (34) to the USB (1) or RS232 (2) communication port on the UPS. The UPS can now communicate with MGE Office Protection Systems power management software.

RT model

86-86700-00 A01
Downloaded from www.Manualslib.com manuals search engine

Installation

23

Pulsar

E N G L I S H

Installation of optional communication cards (optional)


Tower model RT model
It is not necessary to shutdown the UPS before installing a communication card. (4): Slot, with restricted access, for the communicationscard. 1. Remove the UPS cover (4) secured by screws. 2. Insert the communication card in the slot. 3. Put the UPS cover back in place using the screws.

2.5

Connection to the Communication Port by Contact


Pin 2, 3, 5 and 6: not used, Pin 1: operation on automatic by-pass, Pin 4: user common, Pin 7: low battery, Pin 8: load protected,
n.o. n.o. n.o.

Pin 9: operation on battery. n.o.: contact normally open.

When the status is active, the contact between the common (Pin 4) and the relevant information pin is closed. Contact characteristics (optocoupler) Voltage: 48Vdc max Current: 25mA max per contact Power: 1.2W

24
Downloaded from www.Manualslib.com manuals search engine

Installation

86-86700-00 A01

E N G L I S H

Installation and User Manual

2.6

Connections with a FlexPDU (Power Distribution Unit) module (optional)


1. Connect the UPS socket (9) to the AC-power source using the power cable from the equipments to be protected. 2. Connect the input socket on the FlexPDU module (48) to the UPS outlet (7) or (8). The cable and the connectors are marked in red.
7 8 9

3. Connect the equipment to the outlets (45) and (46) on the FlexPDU module. These outlets differ, depending on the version of the FlexPDU module. 4. Fit the connection securing system that prevents the plugs from being pulled out accidentally.

45

46

48

2.7

UPS Connection
Check that the indications on the name plate located on the back of the UPS correspond to the AC-power source and the true electrical consumption of the total load.

Tower model
1. Connect the UPS socket (9) to the AC power source using the power cable from the equipments to be protected. 2. Connect the loads to the UPS. It is preferable to connect the priority loads to the outlets marked (8) and the non-priority loads to the outlets marked (7) that can be programmed in pairs (1 and 2). To program the outlets, the MGE Office Protection Systems communications software is required.

RT model

Note. The UPS charges the battery as soon as it is connected to the AC-power source, even if button (27) is not pressed. Once the UPS is connected to the AC-power source, eight hours of charging are required before the battery can supply the rated backup time.

86-86700-00 A01
Downloaded from www.Manualslib.com manuals search engine

Installation

25

Pulsar

E N G L I S H

(This page left blank intentionally)

26
Downloaded from www.Manualslib.com manuals search engine

86-86700-00 A01

E N G L I S H

Operation
3.1 Start-Up and Normal Operation
For the initial start, AC power must be present to detect any wiring errors. Subsequently, the UPS can start even if AC power is not present.

Press button (27) for approximately 1 second. The connected devices are protected by the UPS. LED (20) is ON. If LED (22) is ON, a fault has occurred (see the "Troubleshooting" section). During normal operation, the scroll button (25) may be used to read UPS measurements (AC input voltage, operating mode, battery capacity and UPS serial number)

UPS personalization If UPS personalization is desired, it is advised to enter the personalization mode at this time. This mode may be entered using the buttons on the control panel or the Personal Solution-Pac software (Windows) included on the Solution-Pac CDROM provided by MGE Office Protection Systems.

3.2

Operation on Battery Power


Transfer battery power Transfer to to battery power

The connected devices continue to be supplied by the UPS when AC power is no longer available. The necessary energy is provided by the battery. LEDs (20) and (21) go ON. The audio alarm beeps every ten seconds. The connected devices are supplied by the battery. The display indicates the remaining backup time.

Low-battery warning

LEDs (20) and (21) go ON. The audio alarm beeps every three seconds.

The remaining battery power is low. Shut down all applications on the connected equipment because automatic UPS shutdown is imminent.

86-86700-00 A01
Downloaded from www.Manualslib.com manuals search engine

Operation

31

Pulsar

E N G L I S H

End of battery backup time All the LEDs go OFF. The audio alarms stops.

The UPS is completely shut down.

3.3

Return of AC Power
Following an outage, the UPS restarts automatically when AC power returns (unless the restart function was disabled via UPS personalization) and the load is again supplied.

3.4

UPS Shutdown
Press button (27) for approximately 1 second. The devices connected to the UPS are no longer supplied.

3.5

Using the UPS Remote Control Functions


Pulsar has the choice of two remote control options. RPO: Remote Power Off allows a remote contact to be used to disconnect all the equipment connected to the UPS from the power supply. Restarting the UPS requires manual intervention. ROO: Remote ON/OFF allows remote action of button (27). These functions are obtained by opening a contact connected between the appropriate pins of connector (5) on the rear panel of the UPS (see diagram on following page).

RT m odel

Tower m odel

32
Downloaded from www.Manualslib.com manuals search engine

Operation

86-86700-00 A01

E N G L I S H

Installation and User Manual

Remote control connection and test


1. 2. 3. Check the UPS is shut down and the electrical supply network disconnected. Remove connector (5) by unfitting the screws. Connect a normally closed volt-free contact (60 Vdc / 30 Vac max, 20 mA max, 0.75mm 2 cable cross section) between the two pins of connector (5), see diagram.

Contact open: shut down of UPS Contact closed: start-up of UPS (UPS connected to the network and network energized) Note: local On/Off control via button (27) has priority over the remote control order. Contact open: shut down of UPS To return to normal operation, deactivate the external remote shut down contact and restart the UPS using button (27).

4. 5. 6.

Plug connector (5) into the back of the UPS. Connect and restart the UPS according to the previously described procedures. Activate the external remote shut down contact to test the function.

Warning: This connector must only be connected to SELV (Safety Extra Low Voltage) circuits.

86-86700-00 A01
Downloaded from www.Manualslib.com manuals search engine

Operation

33

Pulsar

E N G L I S H

(This page left blank intentionally)

34
Downloaded from www.Manualslib.com manuals search engine

86-86700-00 A01

E N G L I S H

Access to Maintenance and Personalization Data

4.1

Display Menus Arrangement

4.2

Access to Measurements
Press the scroll button (25) to access any status conditions and alarms, then the measurements for voltage, current, frequency, power output and battery backup time.

4.3

Personalization Using the Control Panel


Press the scroll button (25) several times until the personalization menu is reached. Press the Enter button (26) to access the different possibilities. Finally, confirm the selection by pressing the Enter button (26) again.

Local personalization Function Language Audio alarm Factory setting English Enabled Other available settings French, Spanish, Portuguese Disabled

86-86700-00 A01
Downloaded from www.Manualslib.com manuals search engine

Contents

41

Pulsar

E N G L I S H

Output personalization
Function Output voltage Frequency converter (1) Output frequency Transfer to the bypass AC input Overload level
(1) (1) (1)

Factory Setting 120 Volts AC Disabled Automatic selection Bypass AC power must be within tolerances 100%

Other available settings 100 to 127 Volts AC Enabled 50 or 60 Hz Bypass AC power may be outside tolerances 30 / 50 / 70%

Comments

The connected devices are never transferred to the bypass. User selectable only if the frequencyconverter function is enabled.

(1)

Alarm if threshold is overrun.

(1) These parameters may be modified only when the UPS is OFF. Detailed comments are available in the Personal Solution-Pac software.

ON/OFF personalization
Function Factory Setting Other available settings Disabled Disabled Enabled The UPS restarts automatically when AC power returns. When function enabled, battery shuts down when power drops to <5%. Neutral inversion (SWF) When function enabled, the UPS remains OFF if the system detects phase/neutral inversion. Comments

Start on battery power Enabled Automatic restart Energy savings Detection of phase/ neutral inversion (SWF) Enabled Disabled

Enabled

Disabled

Battery personalization
Function Battery test Low-battery warning Selection of the backup time Battery protection against excessive discharges Factory Setting Weekly test 20% Automatic detection of number of battery modules Enabled Other available settings No test / daily test / monthly test 0 to 100% 13 to 200 Ah Excessive discharges when function disabled, MGE Office Protection Systems warranty no longer applies. Adjustable in 1% steps. Comments

Disabled

4.4

Personalization using external software


Insert the Solution-Pac CD-ROM in the drive. On the first navigation screen, select "Point to Point solution" and follow the instructions on how to install the Personal Solution-Pac software. Then select "Settings", "Advanced settings" and "UPS settings". Note that the Linux/Unix/MacOS versions of the Personal Solution-Pac software do not offer this possibility.

42

Access to Maintenance and Personalization Data

86-86700-00 A01

Downloaded from www.Manualslib.com manuals search engine

E N G L I S H

Troubleshooting
5.1 Troubleshooting
If LED (21) or (22) is ON, a fault or an alarm has occurred. Use the escape button (24) to stop the audio alarm.

Display The UPS does not start, the alphanumeric display indicates: COLD START NOK CHECK AC WIRING

Description The AC input power is not connected or is connected to the UPS output.

Corrective Action Check the UPS is correctly connected to the AC input power.

LED (22) is ON, the SWF LED Phase inversion on AC input (11) at the rear of the UPS is ON. power. The UPS does not start. The alphanumeric display indicates: SITE WIR. FAULT CHECK AC WIRING

In an earthed-neutreal system, to correct the wiring, call an electrician to modify the connections. For all other types of system, disable the detection function.

LED (22) is ON, the alphanumeric The battery is incorrectly display indicates: NO BATTERY connected. CHECK CONNECTION LED (22) is ON, the alphanumeric A fault is detected on the battery. display indicates: BATTERY FAULT SERV REQUIRED LED (21) is ON, the alphanumeric The load level exceeds the prodisplay indicates: OVERLOAD grammed overload level or UPS ALARM REDUCE LOAD capacity. LED (22) is ON, the alphanumeric The UPS is overloaded. Devices display indicates: LOAD UNPRO- connected to the UPS are fed TECTED OUTPUT OVERLOAD directly by the electrical network via the By-pass. LED (22) is ON, the alphanumeric After repetitive overloads, the display indicates: REDUCE UPS is locked in the By-pass LOAD RESTART UPS position. Devices connected to the UPS are fed directly by the electrical network.

Check battery connections (see Section 5.2, Battery-Module Replacement). Replace the battery (see Section 5.2, Battery-Module Replacement). Call the after-sales support Check the power drawn by the connected devices and disconnect any non-priority devices. Check the programmed overload level. Check the power drawn by the connected devices and disconnect any non-priority devices. Check the power drawn by the connected devices and disconnect any non-priority devices. Shut down and restart the UPS to return to normal operation.

LED (22) is ON, the alphanumeric The UPS shut down automatically Check the power drawn by the condisplay indicates: OVERLOAD because of overload at the UPS nected devices and disconnect any FAULT REDUCE LOAD output. non-priority devices. LED (22) is ON, the alphanumeric The UPS shut down automatically Check the installation at the UPS outdisplay indicates: LOAD SHORT- because of a short-circuit at the put (wiring, fault equipment). CIRCU CHECK WIRING UPS output. LED (22) is ON, the alphanumeric A UPS internal fault has occurred. Call the after-sales support departdisplay indicates: INTERNAL There are two possible situations: ment. FAULT SERV REQUIRED The load is still supplied, but directly with AC power via the bypass, The load is no longer supplied. The alphanumeric display indicates: REMOTE POWER OFF RPO Switching of the Remote Power Off (RPO) has led to the shut down of the UPS. Replace the contact in the normal position, and press the ON/OFF button to restart.

10

11

86-86700-00 A01
Downloaded from www.Manualslib.com manuals search engine

Troubleshooting

51

Pulsar

E N G L I S H

5.2

Battery-Module Replacement
Safety recommendations
The battery can cause electrocution and high short-circuit currents. The following safety cautions are required before servicing the battery components: Remove watches, rings, bracelets and all other metal objects from the hands and arms. Use tools with an insulated handle.

Battery-module removal
RT m odel
A Unscrew the left-hand side of the front panel (two screws). B Remove the part.

C Disconnect the battery block by separating the two connectors (never pull on the wires).

D Remove the metal protection cover in front of the battery (two screws). E Turn the connector. F Pass the connector through the hole.

D E

52
Downloaded from www.Manualslib.com manuals search engine

Troubleshooting

86-86700-00 A01

E N G L I S H

Installation and User Manual

G Pull the plastic tab to remove the battery block and replace it.

Tower m odel

A Put the front panel near the UPS.

B Disconnect the battery block by separating the two connectors (never pull on the wires).

C Remove the 4 fixing screws on the metal protection cover of the battery.

86-86700-00 A01
Downloaded from www.Manualslib.com manuals search engine

Troubleshooting

53

Pulsar

E N G L I S H

D Remove the metal protection cover of the battery.

E Pull the plastic tab to remove the battery block and replace it.

Mounting the new battery module


Carry out the above instructions in reverse order. To ensure safety and high performance, use only batteries supplied by MGE Office Protection Systems. Take care to firmly press together the two parts of the connector during remounting.

54
Downloaded from www.Manualslib.com manuals search engine

Troubleshooting

86-86700-00 A01

E N G L I S H

Appendix
Technical Specifications

Pulsar 700

Pulsar 1000 Pulsar 1000 RT2U 1000VA /900 W


(3)

Pulsar 1500 Pulsar 1500 RT2U 1500VA /1290 W


(4)

Pulsar EXB 1000/1500 (1) Pulsar EXB 1000/1500 RT2U (2)

Output power AC input power Voltage Frequency Power factor Load output Voltage Frequency Harmonic distortion Overload capacity Current Battery, sealed lead acid, maintenance free Environment Operating temperature range Relative humidity Leakage current Storage temperature range Altitude Standards and certification Safety EMC Surge suppressor

700VA / 630W

Single phase 60 / 70 / 80V to 142V (5) 50/60 Hz autoselect > 0.95

Single phase 120V 3% (6) 50/60 Hz 0.5% (7) < 4% for linear load, < 6% for nonlinear load 102% continuous, 130% 12s, > 130% 2s 5.8A (8) 2x12V 7Ah 8.3A (8) 3x12V 7Ah 12.5A (8) 3x12V 9Ah Two string of 3x12V -9Ah

0C to 40C 20% to 90% (without condensation) < 1.1mA -25C to 40C 1000 m

UL 1778 (4th edition), CSA C22.2 No 107.3-05 FCC Subpart B, class A IEEE/ANSI 62.41

(1) EXB Module for Pulsar 1000 and Pulsar 1500 (2) EXB RT2U Module for Pulsar 1000 RT2U and Pulsar 1500 RT2U. (3) 900W, in standard configuration, 800W with at least 1 EXB connected (4) 1290W in standard configuration, 1200W with at least 1 EXB connected (5) Values for 33% / 66% / 100% of nominal power rating (6) Adjustable from 100V to 127V using the UPS Config software (7) Frequency-converter mode is programmable using the UPS Config software (8) Nominal, for 120V output voltage

86-86700-00 A01
Downloaded from www.Manualslib.com manuals search engine

Appendix

A1

Pulsar

6.2

Programming the Programmable Outlets


1. To open the Setting window, left-click on Start Menu / Programs / MGE UPS Systems / Personal Solution Pac / Settings, or right-click on the PSP power plug located in the SYS Tray. Click on the + symbol next to UPS Settings to expand the UPS Settings section.

2.

3.

Click on Startup Timer and change the The group of outlets restarts after to 0 to have powershare outlet provide power at the same time the as main outlets.

A2
Downloaded from www.Manualslib.com manuals search engine

Appendix

86-86700-00 A01

Installation and User Manual

4. 5.

Repeat step 3 for each programmable outlet. After making the changes,s click on the Apply button.

The section entitled Shutdown timer allows the user to define how long the powershare outlet should provide power after a power loss. To configure the powershare to power off at the same time as the main outlets: 6. Set the The group of outlet is powered OFF after to 65535.

86-86700-00 A01
Downloaded from www.Manualslib.com manuals search engine

Appendix

A3

Pulsar

E N G L I S H

MGE Office Protection Systems Customer Care Center

Technical Support and Product Services

Technical questions? If you encounter a problem while following the instructions in this manual, or have questions about the operation, repair, or servicing of your equipment, please visit our web site www.mgeops.com for complete service information.

To insure that your questions are correctly answered, please obtain the part number, assembly number, and serial number of the unit and include them in any discussions or correspondence. Part Number: ________________________________________________________________________________________ Assembly Number: __________________________________________________________________________________ Serial number: ______________________________________________________________________________________

Who To Contact
For Technical Support, Customer Care Center, Customer FAQ please visit our website: www.mgeops.com or call (800) 279-7776.

Scheduling Field Service Engineer Support


Scheduling of the MGE Office Protection Systems Field Service Engineers typically should be done 7 to 10 days before they are required on-site. If the startup of the UPS is critical to maintaining your schedule, please contact MGE Office Protection Systems, to insure a safe installation and start-up that will maintain the MGE Office Protection Systems warranty and insure smooth performance.

Return Policy for Single Phase Products (RMA)


Should you require factory service for your equipment, contact MGE Office Protection Systems Customer Care Center and obtain a Return Materials Authorization (RMA) prior to shipping your unit. Never ship equipment to MGE Office Protection Systems without first obtaining an RMA number. For further details please visit our website: www.mgeops.com Date: ______________________________________________________________________________________________ RMA Number: ______________________________________________________________________________________ Contact Name: ______________________________________________________________________________________

A4
Downloaded from www.Manualslib.com manuals search engine

Appendix

86-86700-00 A01

E N G L I S H

Glossary

Bypass AC

input Bypass line from the AC-power source, controlled by the UPS, used to directly supply the load if an overload or a malfunction occurs on the UPS. Time during which the load can be supplied by the UPS operating on battery power. Internal UPS test to check battery status. Devices connected to the UPS output. Battery discharge beyond the permissible limit, resulting in irreversible damage to the battery. Module with UPS outlets for installation in a bay. There are different modules with different types of outlets. Operating mode used to convert the AC-power frequency between the UPS input and output (50 Hz -> 60 Hz or 60 Hz -> 50 Hz). UPS manual-bypass module for maintenance. There are different modules with different types of outlets. This is a battery-voltage level indicating that battery power is low and that the user must take action in light of the imminent break in the supply of power to the load. The AC-power line supplying the UPS under normal conditions. Ratio of the power effectively drawn by the load to the maximum output of the UPS. It is possible to modify certain UPS parameters set in the factory. Certain UPS functions can also be modified by the Personal Solution-Pac software to better suit user needs. These outlets can be automatically shut down during operation on battery power (shutdown time delays can be programmed with the Personal Solution Pac software). The UPS has two sets of two and one programmable outlets. The devices connected to the UPS can be started even when AC power is not available. The UPS operates only on battery power. Uninterruptible Power Supply. This function enables or disables UPS ON/OFF control sequences by computer power management software.

Backup time Battery test Equipments Excessive discharge FlexPDU

Frequency converter

HotSwap MBP

Low-battery warning

Normal AC input Percent load Personalization

Programmable outlets

Start on battery power

UPS UPS ON/OFF controlled by software

86-86700-00 A01
Downloaded from www.Manualslib.com manuals search engine

Glossary

G1

Downloaded from www.Manualslib.com manuals search engine

F R A N A I S

Manuel dinstallation et dutilisation

Pulsar
Manuel dinstallation et dutilisation

Historique des rvisions


Pulsar Manuel dinstallation et dutilisation, 86-86700-00 Rvision : A01 N NCE : 005282 5/2007

Copyright 2007 MGE Office Protection Systems All rights reserved. Printed in U.S.A. MGE Office Protection Systems 13 Whatney, Suite #101 Irvine, CA 92618
(949) 268-2800

For Technical Support, Customer Care Center, or Customer FAQ, please visit our website: www.mgeops.com or call (800) 279-7776

86-86700-00 A01
Downloaded from www.Manualslib.com manuals search engine

Pulsar

F R A N A I S

86-86700-00 A01
Downloaded from www.Manualslib.com manuals search engine

F R A N A I S

Table des matires

Introduction ........................................................................................................................................1 Symboles utiliss ................................................................................................................................3

1. Prsentation
1.1 1.2 1.3 Positions standard ..........................................................................................................1 1 Panneaux arrire ............................................................................................................1 2 Panneau de commande ................................................................................................1 3

2. Installation
2.1 2.2 2.3 2.4 2.5 2.6 Dballage et vrification du contenu ..............................................................................2 1 Installation du modle RT en position tour ....................................................................2 2 Installation du modle RT en mode modulaire ..............................................................2 2 Ports de communication ................................................................................................2 3 Contacts de connexion au port de communication (2) ..................................................2 4 Branchement de lUPS ..................................................................................................2 5

3. Fonctionnement
3.1 3.2 3.3 3.4 3.5 Dmarrage et fonctionnement normal ..........................................................................3 1 Fonctionnement avec alimentation par pile....................................................................3 1 Retour de lalimentation c.a. ..........................................................................................3 2 Mise hors service de lUPS ............................................................................................3 2 Utilisation des fonctions de commande distance de lUPS ........................................3 2

4. Accs aux mesures et aux donnes de personnalisation


4.1 4.2 4.3 4.4 Configuration des menus daffichage ............................................................................4 1 Accs aux mesures ........................................................................................................4 1 Personnalisation par le panneau de commande ............................................................4 1 Personnalisation par un logiciel externe ........................................................................4 2

5. Entretien
5.1 5.2 Dpannage ....................................................................................................................5 1 Remplacement de la pile ................................................................................................5 2

Annexes
Caractristiques techniques ........................................................................................................A 1 Glossaire ....................................................................................................................................G 1

86-86700-00 A01
Downloaded from www.Manualslib.com manuals search engine

Table des matires

ci

Pulsar

F R A N A I S

(Page laisse vierge volontairement)

86-86700-00 A01
Downloaded from www.Manualslib.com manuals search engine

Introduction

Merci davoir choisi un produit de MGE Office Protection Systems pour protger votre quipement lectrique. Les UPS Pulsar on t conus avec le plus grand soin. Nous vous recommandons de prendre le temps de lire le prsent manuel afin de profiter pleinement de toutes les fonctions de votre UPS (Uninterruptible Power System alimentation sans coupure). Avant dinstaller votre UPS Pulsar, veuillez lire la brochure sur les instructions de scurit obligatoires. Suivez ensuite les indications dans le prsent manuel. Pour connatre tous les produits de MGE Office Protection Systems, ainsi que les options offertes pour la gamme Pulsar, nous vous invitons consulter notre site Web au www.mgeops.com ou communiquer avec votre reprsentant de MGE Office Protection Systems.

Protection environnementale
MGE Office Protection Systems a mis en uvre une politique de protection environnementale. Nos produits sont conus en adoptant une approche cologique.

Substances
Ce produit ne contient pas de CFC, de HCFC ou damiante.

Emballage
Pour amliorer le traitement des dchets et faciliter le recyclage, triez les divers matriaux demballage. Le carton utilis est compos 50 % de carton recycl. Les sacs sont faits de polythylne. 01 Les matriaux demballages sont recyclables et affichent le symbole didentification appropri.
PET

Matriau Polytrphtalate dthylne Polythylne haute densit Polychlorure de vinyle Polythylne basse densit Polypropylne Polystyrne

Abrviation PTE PEHD PVC PEBD PP PS

Numro de symbole 01 02 03 04 05 06

01
PET

Au moment dliminer les matriaux demballage, respectez les rglements locaux.

Fin de vie
MGE Office Protection Systems traitera les produits en fin de vie de service conformment aux rglements locaux. MGE Office Protection Systems collabore avec les entreprises responsables de recueillir et dliminer nos produits en fin de vie de service.

Produit Ce produit est fait de matriaux recyclables. Il faut dsassembler et dtruire le produit conformment tous les rglements locaux sur les dchets. Lorsque le produit atteint la fin de sa vie de service, il faut le transporter dans un centre de traitement des dchets lectriques et lectroniques. Pile Ce produit contient des piles au plomb qui doivent tre traites conformment aux rglements locaux sur les piles. Il est possible denlever la pile et de lliminer conformment la rglementation locale relative llimination. La fiche signaltique des piles est accessible dans notre site Web.* (*) Pour obtenir de plus amples renseignements ou pour communiquer avec le directeur de la politique environnementale du produit, utilisez le formulaire environnemental dans notre site : www.mgeops.com -> propos -> Environnement.

86-86700-00 A01
Downloaded from www.Manualslib.com manuals search engine

Introduction

Pulsar

F R A N A I S

Symboles utiliss

Instructions importantes quil faut toujours suivre.

Information, conseil, aide.

Aide visuel.

Action

Signal sonore.

Voyant teint

Voyant allum.

nonc de la Federal Communication Commission (FCC)


Remarque : Cet quipement a t test et dclar conforme aux limites dfinies pour les dispositifs numriques de classe A, telles qu'nonces dans la section 15 de la rglementation de la FCC. Ces limites ont pour but de garantir un niveau de protection raisonnable contre les interfrences dangereuses lorsque cet quipement est utilis dans un environnement commercial. Cet quipement gnre, utilise et met des ondes radiolectriques qui peuvent, s'il n'est pas install et exploit conformment aux directives indiques dans le manuel dinstructions fourni, crer des interfrences nfastes avec les transmissions radio. Lutilisation de cet quipement dans une zone rsidentiel causera certainement des interfrences nuisibles, dans lequel cas, lutilisateur doit veiller lui-mme liminer ces interfrences.

2
Downloaded from www.Manualslib.com manuals search engine

86-86700-00 A01

F R A N A I S

Prsentation

1.1

Positions standard
Position tour
Dimensions (H x L x P) en mm / pouces Pulsar 700 Pulsar 1000 Pulsar 1000 RT2U Pulsar 1500 Pulsar 1500 RT2U Pulsar EXB 1000/1500 Pulsar EXB 1000/1500 RT2U 242 x 158 x 400 / 9,52 x 6,22 x 15,74 242 x 158 x 400 / 9,52 x 6,22 x 15,74 438 x 86.5 x 480 / 17,24 x 3,4 x 18,9 242 x 158 x 450 / 9,52 x 6,22 x 17,71 438 x 86.5 x 480 / 17,24 x 3,4 x 18,9 242 x 158 x 400 / 9,52 x 6,22 x 15,74 440 x 86.5 x 480 / 17,32 x 3,4 x 18,9

Position modulaire
Poids en kg / lb Pulsar 700 Pulsar 1000 Pulsar 1000 RT 2U Pulsar 1500 Pulsar 1500 RT 2U Pulsar EXB 1000/1500 Pulsar EXB 1000/1500 RT2U 12,5 / 27,55 15 / 33 18 / 39,68 18 / 39,68 20,5 / 45,2 21 / 46,3 24,5 / 54

86-86700-00 A01
Downloaded from www.Manualslib.com manuals search engine

Prsentation

11

Pulsar

F R A N A I S

1.2

Panneaux arrire
Pulsar 700 / 1000 / 1500
(1) Port de communication USB
4 2

(2) Port de communication RS232 et contacts secs (3) Connecteur de reconnaissance automatique de lajout dun module pile EXB (sauf pour le Pulsar 700) (4) Fente pour carte de communication facultative (5) Connecteur de commande de marche-arrt distance et ADD (dsactivation distance) (6) Connecteur pour module de pile EXB exception pour le Pulsar 700

1 8

5 3 6 7 10 9

(7) Groupe de prises programmables pour le branchement dquipement (8) Groupe de prises pour le branchement dquipement (9) Prise dentre pour brancher lUPS une source dalimentation c.a. (10) Voyant (SWF) indiquant le systme en phase neutre ou inverse

Pulsar 1000 RT2U / 1500 RT2U


1 2 5 10 3 6 4 8 9

Pulsar EXB 1000/1500 (pile facultative)


(11) Connecteurs de module de pile (vers lUPS ou les autres modules de piles) (12) Connecteur de reconnaissance automatique des modules de pile

12
Downloaded from www.Manualslib.com manuals search engine

Prsentation

86-86700-00 A01

F R A N A I S

Manuel dinstallation et dutilisation

Pulsar EXB 1000/1500 RT2U (pile facultative)

1.3

Panneau de commande

(20) Voyant de charge protge (21) Voyant de fonctionnement dgrad (22) Voyant de charge protge (23) Affichage alphanumrique (24) Bouton ESC (annuler) (25) Bouton de dfilement (26) Bouton dentre (confirmer) (27) Bouton darrt mise en marche de lUPS et des prises

86-86700-00 A01
Downloaded from www.Manualslib.com manuals search engine

Prsentation

13

Pulsar

F R A N A I S

(Page laisse vierge volontairement)

14
Downloaded from www.Manualslib.com manuals search engine

86-86700-00 A01

F R A N A I S

Manuel dinstallation et dutilisation

Installation

2.1

Dballage et vrification du contenu

(30) (31) (33) (34) (36)

Pulsar 700, 1000, 1500 Pulsar 1000 RT2U, 1500 RT2U Cble de communication RS232 Cble de communication USB CD-ROM Solution-Pac et documentation fournie selon la version et les options choisies

(37) Trousse dinstallation pour les btis de 19 pouces (38) Deux supports dinstallation la verticale (modle RT seulement) (41) Carte de communication NMC (facultative)

Il faut liminer les matriaux demballage conformment tous les rglements locaux sur les dchets. Les symboles de recyclage sont imprims sur les matriaux demballage pour en faciliter le triage.

86-86700-00 A01
Downloaded from www.Manualslib.com manuals search engine

Installation

21

Pulsar

F R A N A I S

2.2

Installation du modle RT en position tour

2.3

Installation du modle RT en module


Il est recommand dinstaller le(s) module(s) de pile EXB la position la plus basse du bti, puis dinstaller lUPS par-dessus. Suivez les tapes 1 4 pour installer le module sur des rails.

Les rails et la quincaillerie ncessarire (37) sont fournis par MGE Office Protection Systems.

22
Downloaded from www.Manualslib.com manuals search engine

Installation

86-86700-00 A01

F R A N A I S

Manuel dinstallation et dutilisation

2.4

Ports de communication
Raccordement du port de communication RS232 ou USB (facultatif)
Les ports de communication RS232 et USB ne peuvent pas fonctionner simultanment.

Modle tour
1. Branchez le cble de communication RS232 (33) ou USB (34) au port srie ou USB de lordinateur. 2. Branchez lautre extrmit du cble de communication (33) ou (34) dans le port de communication USB (1) ou RS232 (2) de lUPS. LUPS peut maintenant communiquer avec le logiciel de gestion de lalimentation de MGE Office Protection Systems.

Modle RT

86-86700-00 A01
Downloaded from www.Manualslib.com manuals search engine

Installation

23

Pulsar

F R A N A I S

Installation des cartes de communication (facultatives)


Tower model RT model
Il nest pas ncessaire de mettre lUPS hors tension avant dinsrer une carte de communication. (4) : Fente accs retreint de la carte de communication. 1. Enlevez le couvercle de lUPS (4) maintenu en place par des vis. 2. Insrez la carte de communication dans la fente. 3. Replacez le couvercle de lUPS laide des vis.

2.5

Contacts de connexion au port de communication


Broches 2, 5, 3 et 6 : pas utilises Broche 1 : fonctionnement en mode de drivation automatique, Broche 4 : commun (utilisateur), Broche 7 : pile faible, Broche 8 : protection de charge,
n.o. n.o. n.o.

Broche 9 : fonctionnement avec alimentation par pile. n.o. : contact normalement ouvert.

Lorsque le statut est actif, le contact entre le signal commun (broche 4) et la broche de linformation pertinente est coup. Caractristiques des contacts (optocoupler) Tension: Max de 48 V c.c. Courant: Max de 25mA par contact Puissance: 1,2 W

24
Downloaded from www.Manualslib.com manuals search engine

Installation

86-86700-00 A01

F R A N A I S

Manuel dinstallation et dutilisation

2.6

Branchement de lUPS
Assurez-vous que les indications de la plaque signaltique larrire de lUPS correspondent lalimentation c.a. et la consommation lectrique relle de la charge totale.

Tower model
1. Branchez la prise de lUPS (9) dans la source dalimentation c.a. laide du cble dalimentation. 2. Branchez les dispositifs dans lUPS. Il est prfrable de brancher les charges prioritaires dans les prises (8) et les charges non prioritaires, dans les prises (7), qui peuvent tre programmes en paires. Pour programmer les prises, il faut avoir le logiciel de communication MGE Office Protection Systems.

RT model

Note : LUPS commence charger sa pile aussitt quil est branch dans une source dalimentation c.a., mme si le bouton (27) na pas t enfonc. Une fois lUPS branch une source dalimentation c.a., celui-ci prend huit heures avant que sa pile puisse offrir le rendement nominal indiqu.

86-86700-00 A01
Downloaded from www.Manualslib.com manuals search engine

Installation

25

Pulsar

(Page laisse vierge volontairement)

26
Downloaded from www.Manualslib.com manuals search engine

Installation

86-86700-00 A01

F R A N A I S

Fonctionnement
3.1 Dmarrage et fonctionnement normal
Au moment du dmarrage initial, lappareil doit tre sous alimentation c.a. afin de dtecter les erreurs de cblage. Ensuite, lappareil peut dmarrer mme sil nest pas aliment par courant c.a.

Appuyez sur le bouton (27) pendant environ 1 secondes. Les dispositifs branchs sont protgs par lUPS. Le voyant (20) sallume. Si le voyant (22) est allum, une faute sest produite (voir la section Dpannage ). Durant le fonctionnement normal, vous pouvez utiliser le bouton de dfilement (25) pour lire les mesures de lUPS (tension dentre c.a., mode de fonctionnement, capacit de la pile et numro de srie de lUPS). Personnalisation des options de lUPS Si vous dsirez personnaliser les options de lUPS il est recommand dacceder au mode de personnalisation maintenant. On accde ce mode laide des boutons du panneau de commande ou du logiciel Personal Solution-Pac (Windows) inclus dans le CD-ROM Solution-Pac fourni avec le systme MGE Office Protection Systems.

3.2

Fonctionnement avec alimentation par pile


Transfer battery power Transfer to to battery power

Les dispositifs branchs demeurent protgs par lUPS lorsque lalimentation c.a. nest plus fonctionnelle. Lnergie ncessaire est fournie par la pile. Les voyants (20) et (21) sallument. Lavertisseur sonore met un bip toutes les dix secondes. Les dispositifs branchs sont aliments par la pile. Laffichage indique la dure restante de lalimentation par pile.

Low-battery warning
Les voyants (20) et (21) sallument. Lavertisseur sonore met un bip toutes les trois secondes.

La charge de la pile est faible. Fermez tous les dispositifs branchs dans lUPS, car celui-ci sera bientt hors-fonction.

86-86700-00 A01
Downloaded from www.Manualslib.com manuals search engine

Fonctionnement

31

Pulsar

F R A N A I S

Fin de la priode dlimentation par pile Tous les voyants seteignent. Lavertisseur sonore sarrte.

LUPS est entirement hors tension.

3.3

Retour de lalimentation c.a.


la suite dune panne, lUPS redmarre automatiquement lorsque lalimentation c.a. fonctionne de nouveau ( moins que la fonction de redmarrage automatique a t dsactive en personnalisant les options de lUPS); la charge est alors nouveau alimente.

3.4

Mise hors service de lUPS


Appuyez sur le bouton (27) pendant environ 1 secondes. Les dispositifs branchs lUPS ne sont plus aliments.

3.5

Utilisation des fonctions de commande distance de lUPS


La gamme de modles Pulsar offre deux options de commande distance. MHTD : La mise hors tension distance permet dutiliser un contact distance pour couper lalimentation de tous les dispositifs branchs lUPS. Il faut ensuite redmarrer lUPS manuellement. ADD : Larrt mise en marche distance permet dutiliser distance le bouton (27). Ces fonctions sont accessibles en ouvrant le contact entre les broches appropries du connecteur (5) > du panneau arrire de lUPS (voir la figure la page suivante).

RT m odel

Tower m odel

32
Downloaded from www.Manualslib.com manuals search engine

Fonctionnement

86-86700-00 A01

F R A N A I S

Manuel dinstallation et dutilisation

Connexion et essai de commande distance


1. 2. 3. Assurez-vous que lUPS est hors service et que lalimentation lectrique est coupe. Dbranchez le connecteur (5) aprs avoir retir les vis. Branchez un contact normalement ferm sans tension (maximum de 60 V c.c. / 30 V c.a., maximum de 20 mA, section transversale de 0,75 mm de 2 cbles) entre les deux broches du connecteur (5), voir le diagramme. Contact ouvert : Mise hors tension de lUPS Contact ferm : Mise sous tension de lUPS (lUPS est raccord un rseau et celui-ci est activ) Note : La commande dactivation/dsactivation locale, laide du bouton (27), supplante la fonction distance. Contact ouvert : Mise hors tension de lUPS Pour retourner en fonctionnement normal, dsactivez le contact distance et appuyez sur le bouton (27) pour redmarrer lUPS.

4. 5. 6.

Branchez le connecteur (5) larrire de lUPS. UPS sous tension en suivant les procdures prcdemment dcrites. Activez le contact de mise hors tension distance pour tester la fonction.

Avertissement : Il faut brancher ce connecteur un circuit TBTS (trs basse tension de scurit).

86-86700-00 A01
Downloaded from www.Manualslib.com manuals search engine

Fonctionnement

33

Pulsar

F R A N A I S

(Page laisse vierge volontairement)

34
Downloaded from www.Manualslib.com manuals search engine

86-86700-00 A01

F R A N A I S

Accs aux mesures et aux donnes de personnalisation

4.1

Configuration des menus daffichage

4.2

Accs aux mesures


Appuyez sur le bouton de dfilement (25) pour afficher tous les statuts et toutes les alarmes, puis les mesures de tension, de courant, de frquence, de puissance de sortie et de dure dalimentation par pile.

4.3

Personnalisation par le panneau de commande


Appuyez plusieurs fois sur le bouton de dfilement (25) pour atteindre le menu de personnalisation. Appuyez sur le bouton dentre (26) pour accder aux diffrentes options. Finalement, appuyez de nouveau sur le bouton dentre (26) pour confirmer votre slection.

Personnalisation locale Fonction Langue Avertisseur sonore Rglage lusine Anglais Activ Autres rglages possibles Franais, Espagnol, Portugais Dsactiv

86-86700-00 A01

Accs aux mesures et aux donnes de personnalisation

41

Downloaded from www.Manualslib.com manuals search engine

Pulsar

F R A N A I S

Personnalisation des options de la sortie principale


Fonction Tension de sortie Convertisseur de frquences
(1) (1)

Rglage lusine 120 Volts c.a. Dsactiv

Autres rglages possibles 100 127 Volts c.a. Activ

Commentaires

Les dispositifs branchs ne sont jamais transfrs au circuit de drivation. Slectionn par lutilisateur seulement si la fonction de convertisseur de frquence est active.

Frquence de sortie

(1)

Slection automatique 50 ou 60 Hz Lalimentation c.a. de Lalimentation c.a. de drivation doit drivation peut ne pas respecter la tolrance respecter la tolrance 30 / 50 / 70%

Transfer lentre c.a. de drivation (1)

Niveau de surcharge (1) 100%

Alarme en cas de dpassement de seuil.

(1) Ces paramtres peuvent tre modifis uniquement lorsque lUPS est arrt. Les dtails sur la faon de procder sont indiqus dans le logiciel Personal Solution-Pac.

Personnalisation des options de mise en marche/arrt


Fonction Rglage lusine Autres rglages possibles Dsactiv Dsactiv Activ LUPS redmarre automatiquement lorsque lalimentation c.a. est rtablie. Lorsque cette fonction est active, lalimentation par pile steint lorsque la capacit atteint moins de 5%. Inversion de la phase neutre (SWF) Lorsque cette fonction est active, lUPS demeure hors fonction si le systme dtecte une inversion de la phase neutre. Commentaires

Dmarrage en mode Activ dalimentation par pile Redmarrage automatique conomie dnergie Dtection de phase/ inversion de la phase neutre (SWF) Activ Dsactiv

Activ

Dsactiv

Personnalisation des options de la pile


Fonction Tests de pile Rglage lusine Test hebdomadaire Autres rglages possibles Aucun test / test quotidien / test mensuel 0 100 % Rglable par incrment de 1 %. Commentaires

Avertissement de pile faible 20% Slection de la dure de lalimentation par pile Protection de la pile contre les dcharges excessives

Dtection automatique du nombre de 13 200 Ah modules de pile En cas de dcharge excessive lorsque cette fonction est dsactive, MGE Office Protection Systems annule la garantie de lappareil.

Activ

Dsactiv

4.4

Personnalisation par un logiciel externe


Insrez le CD-ROM Solution-Pac dans le lecteur. Dans le premier cran de navigation, slectionnez Solution Point point , puis suivez les instructions sur la faon dinstaller le logiciel Personal Solution-Pac. Slectionnez ensuite Configuration , Configuration avance et Configuration UPS . Veuillez noter que les versions de Personal Solution-Pac pour Linux/Unix/MacOS noffrent pas cette option.

42

Accs aux mesures et aux donnes de personnalisation

86-86700-00 A01

Downloaded from www.Manualslib.com manuals search engine

F R A N A I S

Dpannage

5.1

Dpannage
Si le voyant (21) ou (22) est allum, il sest produit une dfaillance ou une alarme. Appuyez sur le bouton ESC (24) pour arrter lalarme sonore.

Affichage LUPS ne se met pas en marche et laffichage indique : COLD START NOK CHECK AC WIRING (problme de dmarrage, vrifiez lalimentation c.a.) Le voyant (22) est allum, le voyant SWF (11) larrire de lUPS est allum. Laffichage indique : SITE WIR. FAULT CHECK AC WIRING (erreur de filage; vrifiez le filage de lalimentation c.a.)

Description Lalimentation c.a. nest pas branche ou est branche dans la sortie de lUPS.

Mesure corrective Assurez-vous que lUPS est branch correctement dans la prise dentre c.a.

Inversion de phase dans lalimentation dentre c.a. LUPS ne se met pas en marche.

Dans un systme neutre, mis la terre, il faut communiquer avec un lectricien pour modifier les connexions. Pour tous les autres types de systme, dsactivez la foction de dtection. Vrifiez la connexion des piles (voir la section 5.2, Remplacement du module de pile).

Le voyant (22) est allum, laffichage indique : NO BATTERY CHECK CONNECTION (pas de pile, vrifiez la connexion) Le voyant (22) est allum, laffichage indique : BATTERY FAULT SERV REQUIRED (Dfaut de pile : rparation ncessaire.)

La pile est mal branche.

Un dfaut de pile a t dtect.

Remplacez la pile (voir la section 5.2, Remplacement du module de pile). Communiquez avec le service du soutien aprs-vente. Vrifiez la puissance de la charge des dispositifs branchs et dbranchez tout dispositif non prioritaire. Vrifiez le rglage de niveau de surcharge. Vrifiez la puissance de la charge des dispositifs branchs et dbranchez tout dispositif non prioritaire.

Le voyant (21) est allum, laffichage Le pourcentage de charge est suprieur indique : OVERLOAD ALARM REDUCE au niveau de surcharge ou la capacit LOAD (Alarme de surcharge; diminuez la rgle de lUPS. charge.) Le voyant (22) est allum, laffichage indique : LOAD UNPROTECTED OUTPUT OVERLOAD (Surcharge de sortie : la charge nest pas protge.) Le voyant (22) est allum, laffichage indique : REDUCE LOAD RESTART UPS (Rduisez la charge et redmarrez lUPS.) Le voyant (22) est allum, laffichage indique : OVERLOAD FAULT REDUCE LOAD (DFAUT DE SURCHARGE; DIMINUEZ LA CHARGE.) LUPS est en surcharge. Les dispositifs qui y sont branchs reoivent lalimentation directement de votre rseau lectrique par le circuit de drivation. Aprs des surcharges rptes, lUPS est verrouill en mode de drivation. Les dispositifs qui y sont branchs reoivent lalimentation directement de votre rseau lectrique. LUPS s'teint automatiquement en raison d'une surcharge la sortie.

Vrifiez la puissance de la charge des dispositifs branchs et dbranchez tout dispositif non prioritaire. Fermez lUPS et redmarrez-le; il sera alors en mode normal. Vrifiez la puissance de la charge des dispositifs branchs et dbranchez tout dispositif non prioritaire. Vrifiez les branchements la sortie de lUPS (cble, quipement dfectueux).

Le voyant (22) est allum, laffichage LUPS steint automatiquement en indique : LOAD SHORT-CIRCU CHECK raison d'un court-circuit la sortie. WIRING (Court-circuit de charge; vrifiez les cbles.) Le voyant (22) est allum, laffichage indique : INTERNAL FAULT SERV REQUIRED (Dfaut interne : rparation ncessaire.) Un dfaut interne sest produit dans lUPS. Deux situations peuvent stre produites : La charge est toujours alimente, mais directement du circuit de drivation c.a., La charge nest plus alimente. Le fait de dsactiver la fonction de dsactivation distance a entran la fermeture de lUPS.

Communiquez avec le service du soutien aprs-vente.

10

11

Laffichage indique : REMOTE POWER OFF RPO (Dsactivation distance)

Replacez le contact la position normale et appuyez sur le bouton marche-arrt pour redmarrer lUPS.

86-86700-00 A01
Downloaded from www.Manualslib.com manuals search engine

Dpannage

51

Pulsar

F R A N A I S

5.2

Remplacement de la pile
Recommandations de scurit
La pile peut causer des lectrocutions et des courants levs en court-circuit. Il faut observer les prcautions de scurit suivantes avant de faire lentretien du compartiment de la pile : Enlevez montre, bagues, bracelet et autres objets de mtal sur les mains et les bras. Utilisez les outils avec des poignes isoles.

Enlvement de la pile
RT m odel
A Enlevez les deux vis du ct gauche du panneau avant. B Enlevez la pice.

C Tirez sur les deux connecteurs pour dbrancher la pile (ne tirez pas sur les fils).

D Enlevez le couvercle de protection mtallique devant la pile en dvissant les deux vis. E Tournez le connecteur. F Enfilez le connecteur dans louverture.

D E

52
Downloaded from www.Manualslib.com manuals search engine

Dpannage

86-86700-00 A01

F R A N A I S

Manuel dinstallation et dutilisation

G Tirez sur la languette de plastique pour enlever la pile et remplacez-la.

Tower m odel

A Placez le panneau avant prs de lUPS.

B Tirez sur les deux connecteurs pour dbrancher la pile (ne tirez pas sur les fils).

C Enlevez les quatre vis qui fixent le couvercle de protection mtallique de la pile.

86-86700-00 A01
Downloaded from www.Manualslib.com manuals search engine

Dpannage

53

Pulsar

F R A N A I S

D Enlevez le couvercle de protection mtallique de la pile.

E Tirez sur la languette de plastique pour enlever la pile et remplacez-la.

Installation de la nouvelle pile


Excutez les instructions ci-dessus dans lordre inverse. Pour assurer la scurit et un rendement optimal, utilisez seulement les piles fournies par MGE Office Protection Systems. Durant linstallation de la nouvelle pile, assurez-vous dappuyer fermement lune contre lautre les deux parties du connecteur.

54
Downloaded from www.Manualslib.com manuals search engine

Dpannage

86-86700-00 A01

F R A N A I S

Annexe
Caractristiques techniques

Pulsar 700

Pulsar 1000 Pulsar 1000 RT2U 1000 VA / 900 W


(3)

Pulsar 1500 Pulsar 1500 RT2U 1500 VA / 1290 W


(4)

Pulsar EXB 1000/1500 (1) Pulsar EXB 1000/1500 RT2U (2)

Puissance de sortie Puissance de sortie c.a. Tension Frquence Facteur de puissance Charge de sortie Tension Frquence Distorsion harmonique Capacit de surcharge Courant Pile scelle, acide de plomb, sans entretien Environnement Plage de temp. de fonctionnement Humidit relative Courant de fuite Plage de temp. dentreposage Altitude Normes et certification Scurit CEM Parasurtenseur (1) (2) (3) (4) (5) (6) (7) (8)

700 VA / 630 W

Simple phase 60 / 70 / 80 V 142 V (5) 50/60 Hz slectionn automatiquement > 0,95 Simple phase 120V 3 % (6) 50/60 Hz 0,5 % (7) < 4 % pour des charges linaires, < 6 % pour des charges non linaires 102 % continue, 130 % 12 s, > 130 % 2 s 5,8 A (8) 8,3 A (8) 12,5 A (8) 2x12 V 7 Ah 3x12 V 7 Ah 3x12 V 9 Ah Deux chanes de 3x12 V -9 Ah

0 C 40 C 20 % 90 % (sans condensation) < 1,1 mA -25 C 40 C 1000 m

UL 1778 (4e dition), CSA C22.2 No 107.3-05 FCC sous-partie B, classe A IEEE/ANSI 62.41

Module EXB pour les modles Pulsar 1000 et Pulsar 1500 Module EXB RT2U pour les modles Pulsar 1000 RT2U et Pulsar 1500 RT2U. 900W, dans une configuration standard, 800 W et au moins un module EXB raccord 1290W dans une configuration standard, 1200 W et au moins un module EXB raccord Valeurs nominales de puissance de 33 % / 66 % / 100 % Rglable de 100 V 127 V laide du logiciel de configuration de lUPS Le mode de convertisseur de frquence est programmable laide du logiciel de configuration de lUPS Valeur nominale pour une tension de sortie de 120 V

86-86700-00 A01
Downloaded from www.Manualslib.com manuals search engine

Annexe

A1

Pulsar

F R A N A I S

Service la clientle de MGE Office Protection Systems

Soutien technique et service des produits

Vous avez des questions dordre technique? Si vous prouvez des problmes avec les instructions contenues dans le prsent manuel ou si vous avez des questions sur lutilisation, la rparation ou lentretien de votre quipement, veuillez communiquer avec le service la clientle de MGE Office Protection Systemsou visitez notre site Web, au www.mgeops.com pour obtenir de linformation complte sur lentretien des appareils.

Pour vous assurer dobtenir une rponse satisfaisante, veuillez avoir porte de main le numro de pice, le numro dassemblage et le numro de srie de lappareil et incluez ces renseignements dans toute discussion ou toute correspondance. Numro de pice : Numro dassemblage : Numro de srie : _____________________________________________________________________ _____________________________________________________________________ _____________________________________________________________________

Ressources :
Pour l'appui technique, le centre de soin de client, FAQ de client visitent svp notre site Web : www.mgeops.com ou appel

Planifier le soutien dun ingnieur sur le terrain


Il faut habituellement planifier le soutien dun ingnieur de service sur le terrain de MGE de sept dix jours avant la date prvue du service sur place. Si la mise en fonction de lUPS est essentiel au respect de votre calendrier, veuillez communiquer avec MGE au numro sans frais 1 800 438-7373, pour assurer une mise en fonction sre, respectant la garantie et assurant un rendement optimal.

Politique de retour des produits simple phase (NARM)


Si votre quipement exige un service en usine, communiquez avec le service la clientle de MGE pour obtenir un numro dautorisation de retour de matriel (NARM) avant denvoyer lappareil. Nexpdiez jamais de lquipement MGE sans avoir pralablement obtenir un NARM. Pour d'autres dtails veuillez la visite notre site Web : www.mgeops.com

Date : NARM :

______________________________________________________ ______________________________________________________

Personne-ressource : ______________________________________________________

A2
Downloaded from www.Manualslib.com manuals search engine

Annexe

86-86700-00 A01

F R A N A I S

Glossaire

Entre c.a. de drivation

Ligne de drivation de la source c.a., commande par lUPS, utilise pour alimenter la charge en cas de surcharge ou de dfaillance de lUPS. Le temps durant lequel la charge est alimente par la pile de lUPS. Test interne de lUPS pour vrifier le statut de la pile. Les dispositifs branchs aux sorties de lUPS. Dcharge de la pile au-del de la limite permise, entranant des dommages irrversibles celle-ci. Module comportant des sorties dUPS sinstallant dans un bti. Il existe diffrents modules comportant diffrents types de sorties. Mode de fonctionnement utilis pour convertir la frquence dalimentation c.a. entre lentre de lUPS et sa sortie (50 Hz -> 60 Hz ou 60 Hz -> 50 Hz). Module de drivation manuelle de lUPS servant lentretien. Il existe diffrents modules comportant diffrents types de sorties. Un niveau de tension de la pile indiquant que celle-ci est faible et que lutilisateur doit prendre des mesures, car lalimentation de la charge sera bientt interrompue. La ligne de courant c.a. alimentant lUPS dans des conditions normales. Le ratio de la puissance utilise par la charge comparativement la puissance maximale de lUPS. Il est possible de personnaliser certains paramtres de lUPS configurs en usine. Certaines fonctions de lUPS peuvent galement tre modifies laide du logiciel Personal SolutionPac pour mieux satisfaire vos besoins. Ces sorties peuvent tre programmes pour se dsactiver automatiquement lorsque lUPS fonctionne en mode pile (il est possible de programmer le dlai de fermeture laide du logiciel Personal Solution Pac). LUPS comporte deux ensembles de deux et une sortie programmables. Il est possible de dmarrer les dispositifs branchs dans lUPS mme en labsence dalimentation c.a. LUPS fonctionne uniquement laide de la pile. Systme dalimentation sans coupure. Cette fonction, commande par le logiciel de personnalisation, active ou dsactive la squence de commande de mise en marche ou darrt de lUPS par lordinateur.

Temps dalimentation de secours Test de pile quipement Dcharge excessive

FlexPDU

Covertisseur de frquences HotSwap MBP

Avertissement de pile faible Entre c.a. normale Pourcentage de charge

Personnalisation

Sorties programmables

Dmarrage en mode dalimentation par pile UPS Mise en marche/arrt de lUPS

86-86700-00 A01
Downloaded from www.Manualslib.com manuals search engine

Glossaire

G 1

Downloaded from www.Manualslib.com manuals search engine

E S P A O L

Manual de instalacin y de usuario

Pulsar
Manual de instalacin y de usuario

Historial de revisiones
Manual de instalacin y de usuario del Pulsar, 86-86700-00 Revisin: A01 ECN#: 005282 5/2007

Copyright 2007 MGE Office Protection Systems All rights reserved. Printed in U.S.A. MGE Office Protection Systems 13 Whatney, Suite #101 Irvine, CA 92618
(949) 268-2800

For Technical Support, Customer Care Center, or Customer FAQ, please visit our website: www.mgeops.com or call (800) 279-7776

86-86700-00 A01
Downloaded from www.Manualslib.com manuals search engine

Pulsar

E S P A O L

86-86700-00 A01
Downloaded from www.Manualslib.com manuals search engine

E S P A O L

Contenido

Introduccin ........................................................................................................................................1 Uso de smbolos..................................................................................................................................3

1. Presentacin
1.1 1.2 1.3 Posiciones estndar ......................................................................................................1 1 Paneles posteriores ........................................................................................................1 2 Panel de control..............................................................................................................1 3

2. Instalacin
2.1 2.2 2.3 2.4 2.5 2.6 Desembalado y control del contenido ............................................................................2 1 Instalacin del Modelo RT en posicin vertical ..............................................................2 2 Instalacin del Modelo RT en un bastidor ......................................................................2 2 Puertos de comunicacin ..............................................................................................2 3 Conexin al Puerto de comunicacin utilizando un Contacto (2) ..................................2 4 Conexin de la UPS ......................................................................................................2 5

3. Funcionamiento
3.1 3.2 3.3 3.4 3.5 Arranque y Funcionamiento normal ..............................................................................3 1 Funcionamiento con alimentacin de batera ................................................................3 1 Retorno a alimentacin de CA ......................................................................................3 2 Apagado de la UPS ........................................................................................................3 2 Uso de las Funciones de control remoto de la UPS ......................................................3 2

4. Acceso a los datos de mantenimiento y de personalizacin


4.1 4.2 4.3 4.4 Disposicin de los mens en pantalla ............................................................................4 1 Acceso a Mediciones......................................................................................................4 1 Personalizacin utilizando el Panel de control ..............................................................4 1 Personalizacin utilizando software externo ..................................................................4 2

5. Mantenimiento
5.1 5.2 Solucin de inconvenientes............................................................................................5 1 Reemplazo del mdulo de la batera..............................................................................5 2

6. Apndices
Especificaciones tcnicas............................................................................................................A 1 Glosario......................................................................................................................................G 1

86-86700-00 A01
Downloaded from www.Manualslib.com manuals search engine

Contenido

ci

Pulsar

E S P A O L

(Esta pgina ha sido dejada intencionadamente en blanco)

86-86700-00 A01
Downloaded from www.Manualslib.com manuals search engine

E S P A O L

Introduccin

Le agradecemos haber elegido un producto de MGE Office Protection Systems para proteger su equipo elctrico. El Pulsar ha sido diseado con el mayor cuidado. Le recomendamos tomarse un tiempo para leer este manual y as poder obtener el mximo beneficio de las muchas caractersticas de su UPS (Uninterruptible Power System - sistema de alimentacin ininterrumpible, por sus siglas en ingls). Antes de instalar una Pulsar, lea atentamente el folleto sobre las instrucciones de seguridad requeridas. Luego siga las indicaciones en este manual. Para descubrir toda la gama de los productos MGE Office Protection Systems y las dems opciones disponibles para la gama Pulsar, le invitamos a visitar nuestro sitio en www.mgeops.com o a ponerse en contacto con su representante de MGE Office Protection Systems.

Proteccin ambiental
MGE Office Protection Systems ha implementado una poltica de proteccin ambiental. Los productos son desarrollados utilizando un enfoque ecolgico en el diseo.

Sustancias
Este producto no contiene CFC, HCFC o amianto.

Embalaje
Para mejorar el tratamiento de los residuos y facilitar el reciclaje, separe los diferentes componentes del embalaje. El cartn que utilizamos incluye ms del 50% de cartn reciclado. Los sacos y bolsas estn hechos de polietileno. 01 Los materiales del embalaje son reciclables y presentan el smbolo de identificacin correspondiente.
PET

Material Tereftalato de polietileno Polietileno de alta densidad Cloruro de polivinilo Polietileno de baja densidad Polipropileno Poliestireno

Abreviatura PET HDPE PVC LDPE PP PS

Nm. de Smbolo 01 02 03 04 05 06

01
PET

Siga las reglamentaciones locales correspondientes a la disposicin de materiales de embalaje.

Final de vida
MGE Office Protection Systems procesar los productos que estn al final de su vida til en cumplimiento de las reglamentaciones locales. MGE Office Protection Systems trabaja con empresas encargadas de la recoleccin y eliminacin de nuestros productos al final de su vida de servicio.

Producto El producto est fabricado con materiales reciclables. El desarmado y la destruccin deben ser realizados en cumplimiento con todas las reglamentaciones locales correspondientes a los desechos. Al final de la vida de servicio, el producto debe ser transportado a un centro de procesamiento para desechos elctricos y electrnicos. Batera Este producto contiene bateras de plomo / cido, las que deben ser procesadas cumpliendo con las reglamentaciones locales sobre bateras. La batera puede ser retirada y dispuesta en cumplimiento con las correspondientes reglamentaciones locales. En nuestro sitio internet est disponible la Material Safety Data Sheets - Planilla de datos de seguridad del material (MSDS, por sus siglas en ingls) correspondiente a las bateras*. (*) Para obtener ms informacin o ponerse en contacto con el Gerente ambiental del producto, use el Formulario ambiental (Environmental Form) disponible en el sitio: www.mgeops.com -> About us -> Environment.

86-86700-00 A01
Downloaded from www.Manualslib.com manuals search engine

Introduccin

Pulsar

E S P A O L

Uso de smbolos

Importantes instrucciones que deben ser siempre obedecidas

Informacin, recomendaciones, ayuda

Indicacin visual

Accin

Seal audible

LED apagado

LED encendido

Declaracin de la Comisin Federal de Comunicaciones (FCC)


NOTA: Este equipo ha sido evaluado y se ha determinado que cumple con los lmites para un dispositivo digital Clase A, conforme a la Parte 15 de las Reglas de la FCC. Estos lmites estn diseados para brindar una proteccin razonable contra interferencia daina cuando el equipo es utilizado en un ambiente comercial. Este equipo genera, utiliza y puede irradiar energa en frecuencia radial, y en caso que no sea instalado y utilizado conforme al manual de instrucciones, puede ocasionar interferencia daina a las comunicaciones por radio. El empleo de este equipo en una zona residencial puede causar interferencia daina, en cuyo caso el usuario deber solventar los gastos para corregir la interferencia.

2
Downloaded from www.Manualslib.com manuals search engine

86-86700-00 A01

E S P A O L

Presentacin

1.1

Posiciones estndar
Posicin vertical
Medidas (A x A x P) en mm / pulgadas Pulsar 700 Pulsar 1000 Pulsar 1000 RT2U Pulsar 1500 Pulsar 1500 RT2U Pulsar EXB 1000/1500 Pulsar EXB 1000/1500 RT2U 242 x 158 x 400 / 9,52 x 6,22 x 15,74 242 x 158 x 400 / 9,52 x 6,22 x 15,74 438 x 86.5 x 480 / 17,24 x 3,4 x 18,9 242 x 158 x 450 / 9,52 x 6,22 x 17,71 438 x 86.5 x 480 / 17,24 x 3,4 x 18,9 242 x 158 x 400 / 9,52 x 6,22 x 15,74 440 x 86.5 x 480 / 17,32 x 3,4 x 18,9

Posicin en bastidor
Peso en kg / lbs Pulsar 700 Pulsar 1000 Pulsar 1000 RT2U Pulsar 1500 Pulsar 1500 RT2U Pulsar EXB 1000/1500 Pulsar EXB 1000/1500 RT2U 12,5 / 27,55 15 / 33 18 / 39,68 18 / 39,68 20,5 / 45,2 21 / 46,3 24,5 / 54

86-86700-00 A01
Downloaded from www.Manualslib.com manuals search engine

Presentacin

11

Pulsar

E S P A O L

1.2

Paneles posteriores
Pulsar 700 / 1000 / 1500
(1) Puerto de comunicacin USB
4 2

(2) Puerto de comunicacin y de contactos secos RS232 (3) Conector para reconocimiento automtico de un mdulo de batera EXB (excepto en el Pulsar 700) (4) Ranura para tarjeta opcional de comunicacin (5) Conector control de encendido/apagado (ON/OFF) y RPO remoto (Apagado remoto) (6) Conector para mdulo de batera EXB con la excepcion de Pulsar 700

1 8

5 3 6 7 10 9

(7) Grupo de salidas programables para conexin de equipo (8) Grupo de salidas para conexin de equipo (9) Entrada para enchufe de alimentacin para conexin a una fuente de CA (10) El LED (SWF) indica la fase del sistema de distribucin / inversin del neutro

Pulsar 1000 RT2U / 1500 RT2U


1 2 5 10 3 6 4 8 9

Pulsar EXB 1000/1500 (mdulo opcional de batera)


(11) Conectores para los mdulos de batera (a la UPS o a los otros mdulos de batera) (12) Conectores para reconocimiento automtico de mdulos de batera

12
Downloaded from www.Manualslib.com manuals search engine

Presentacin

86-86700-00 A01

E S P A O L

Manual de instalacin y de usuario

Pulsar EXB 1000/1500 RT2U (mdulo opcional de batera)

1.3

Panel de control

(20) LED de carga protegida (21) LED de funcionamiento disminuido (22) LED de carga no protegida (23) Pantalla alfanumrica (24) Botn Escape (cancelacin) (25) Botn de desplazamiento (26) Botn Enter (confirmacin) (27) Botn de encendido (ON/OFF) para la UPS y las salidas

86-86700-00 A01
Downloaded from www.Manualslib.com manuals search engine

Presentacin

13

Pulsar

E S P A O L

(Esta pgina ha sido dejada intencionadamente en blanco)

14
Downloaded from www.Manualslib.com manuals search engine

86-86700-00 A01

E S P A O L

Manual de instalacin y de usuario

Instalacin

2.1

Desembalado y control del contenido

(30) (31) (33) (34) (36)

Pulsar 700, 1000, 1500 (37) Kit de montaje para bahas de 19 pulg Pulsar 1000 RT2U, 1500 RT2U (38) 2 soportes para la posicin vertical (slo para el modelo RT) Cable de comunicacin RS232 (41) Plaqueta de comunicacin NMC (opcional) Cable de comunicacin USB CD-ROM del Solution-Pac y Elementos de documentacin provistos, dependiendo de la versin o de la opcin

Los materiales del embalaje deben ser desechados en cumplimiento con todas las reglamentaciones locales correspondientes a los desechos. Los smbolos de reciclaje aparecen impresos en los materiales del embalaje para facilitar su clasificacin.

86-86700-00 A01
Downloaded from www.Manualslib.com manuals search engine

Instalacin

21

Pulsar

E S P A O L

2.2

Instalacin del Modelo RT en posicin vertical

2.3

Instalacin del Modelo RT en un bastidor


Se recomienda instalar el/los mdulo/s EXB de batera en la posicin ms baja del bastidor para luego colocar la UPS arriba. Siga los pasos 1 al 4 para montar los mdulos en los rieles.

Los rieles y los herrajes necesarios (37) son provistos por MGE Office Protection Systems.

22
Downloaded from www.Manualslib.com manuals search engine

Instalacin

86-86700-00 A01

E S P A O L

Manual de instalacin y de usuario

2.4

Puertos de comunicacin
Conexin de un puerto de comunicacin RS232 o USB (opcional)
Los puertos de comunicacin RS232 y USB no pueden funcionar simultneamente.

Modelo vertical
1. Conecte el cable de comunicacin RS232 (33) o el USB (34) al puerto serial o USB de la computadora. 2. Conecte el otro extremo del cable de comunicacin (33) o (34) al puerto de comunicacin USB (1) o RS232 (2) de la UPS. La UPS podr entonces comunicarse con el software de gestin de alimentacin MGE Office Protection Systems.

Modelo RT

86-86700-00 A01
Downloaded from www.Manualslib.com manuals search engine

Instalacin

23

Pulsar

E S P A O L

Instalacin de las plaquetas opcionales de comunicacin (opcional)


Tower model RT model
No es necesario apagar la UPS antes de instalar una plaqueta de comunicacin. (4): Ranura con acceso restringido para la tarjeta de comunicacin. 1. Retire la tapa de la UPS (4) que est fijada con tornillos. 2. Coloque la plaqueta de comunicacin en la ranura. 3. Coloque nuevamente la tapa de la UPS y fjela utilizando los tornillos.

2.5

Conexin al puerto de comunicacin utilizando un contacto


Clavijas 2, 3, 5 y 6: no utilizadas, Clavija 1: funcionamiento en derivacin automtica, Clavija 4: en comn, Clavija 7: batera baja, Clavija 8: carga protegida,
n.o. n.o. n.o.

Clavija 9: funcionamiento con batera. n.o.: contacto normalmente abierto.

Cuando el estado sea activo, el contacto entre la clavija comn (Clavija 4) y la clavija de informacin pertinente est cerrado. Caractersticas del contacto (optoacoplador) Voltaje: 48 VCA mx. Corriente: 25mA mx. por contacto Alimentacin: 1,2W

24
Downloaded from www.Manualslib.com manuals search engine

Instalacin

86-86700-00 A01

E S P A O L

Manual de instalacin y de usuario

2.6

Conexin de la UPS
Controle que las indicaciones en la placa de identificacin ubicada en la parte posterior de la UPS coincida con la fuente de alimentacin de CA y con el consumo elctrico verdadero de la carga total.

Tower model
1. Conecte la toma de corriente de la UPS (9) a la fuente de alimentacin de CA utilizando el cable de alimentacin del equipo a proteger. 2. Conecte las cargas a la UPS. Es preferible conectar las cargas prioritarias a las tomas de corriente marcadas (8) y las cargas no prioritarias a las tomas de corriente marcadas (7) de manera que puedan ser programadas en pares (1 y 2). Para programar las salidas se necesita del software de comunicacin MGE Office Protection Systems.

RT model

Nota: La UPS carga la batera tan pronto como se la conecta a la fuente de CA, aunque no se haya presionado el botn (27). Una vez que la UPS est conectada a la fuente de alimentacin de CA, se necesita de ocho horas de carga antes que la batera pueda alimentar el tiempo nominal de respaldo.

86-86700-00 A01
Downloaded from www.Manualslib.com manuals search engine

Instalacin

25

Pulsar

E S P A O L

(Esta pgina ha sido dejada intencionadamente en blanco)

26
Downloaded from www.Manualslib.com manuals search engine

86-86700-00 A01

E S P A O L

Funcionamiento
3.1 Arranque y Funcionamiento normal
Para el encendido inicial, deber existir alimentacin de CA para detectar cualquier error de cableado. Es por ello que la UPS puede arrancar inclusive si no hay alimentacin de CA

Oprima el botn (27) por aproximadamente 1 segundo. Los dispositivos conectados son protegidos por la UPS. Se enciende el LED (20). En caso que el LED (22) est encendido, se ha producido una falla (consulte la seccin Solucin de inconvenientes). Durante el funcionamiento normal, se puede utilizar el botn de desplazamiento (25) para leer mas mediciones de la UPS (voltaje de entrada de CA, modo de funcionamiento, capacidad de la batera y nmero de serie de la UPS) Personalizacin de la UPS En caso que se desee personalizar la UPS, se recomienda entrar en el modo personalizacin en este momento. Se puede ingresar en este modo utilizando los botones en el panel de control o utilizando el software Personal Solution-Pac (para Windows) incluido en el CD-ROM de Solution-Pac provisto por MGE Office Protection Systems.

3.2

Funcionamiento con alimentacin de batera


Transfer to battery power

Los dispositivos conectados continan siendo alimentados por la UPS cuando ya no est disponible la alimentacin de CA. La energa necesaria es provista por la batera. Se encienden los LED (20) y (21). La alarma de audio suena cada diez segundos. Los dispositivos conectados son alimentados por la UPS. La pantalla muestra el tiempo remanente.

Low-battery warning

Se encienden los LED (20) y (21). La alarma de audio suena cada tres segundos.

La reserva de la batera est baja. Apague todos los equipos conectados a la UPS ya que su apagado automtico es inminente.

86-86700-00 A01
Downloaded from www.Manualslib.com manuals search engine

Funcionamiento

31

Pulsar

E S P A O L

Indique el tiempo de respaldo de la batera Se apagan todos los LED. Se detiene la alarma sonora.

La UPS est completamente apagada.

3.3

Retorno a alimentacin de CA
Luego de un corte de alimentacin, la UPS se enciende automticamente cuando retorna la alimentacin de CA (excepto la funcin de reencendido haya sido deshabilitada por medio de la personalizacin de la UPS) y se alimenta nuevamente la carga.

3.4

Apagado de la UPS
Oprima el botn (27) por aproximadamente 1 segundo. Los dispositivos conectados a la UPS ya no reciben alimentacin.

3.5

Uso de las Funciones de control remoto de la UPS


Pulsar cuenta con dos opciones de control remoto. RPO: El Remote Power Off (Apagado remoto) permite utilizar un contacto remoto para desconectar todo el equipo conectado a la UPS de la fuente de alimentacin. El reencendido de la UPS necesita de intervencin manual. ROO: El apagado remoto (Remote ON/OFF) permite el funcionamiento remoto del botn (27). Estas funciones se obtienen abriendo un contacto entre las clavijas correspondientes del conector (5) en el panel posterior de la UPS (consulte el diagrama que aparece en la prxima pgina).

RT m odel

Tower m odel

32
Downloaded from www.Manualslib.com manuals search engine

Funcionamiento

86-86700-00 A01

E S P A O L

Manual de instalacin y de usuario

Conexin y prueba del control remoto


1. 2. 3. Controle que la UPS est apagada y que toda la red de alimentacin elctrica est desconectada. Retire el conector (5) destornillando los tornillos. Conecte un contacto normal cerrado libre de tensin (60 VCC / 30 VCA mx., 20 mA mx., cable de 0,75 mm 2 de seccin) entre las dos clavijas del conector (5), consulte el diagrama. Contacto abierto: apagado de la UPS Contacto cerrado: arranque de la UPS (UPS conectada a la red y red activada) Nota: el control de encendido utilizando el botn (27) tiene prioridad sobre la orden del control remoto. Contacto abierto: apagado de la UPS Para volver al funcionamiento normal, desactive el contacto de apagado remoto y encienda nuevamente la UPS utilizando el botn (27). 4. 5. 6. Enchufe el conector (5) en la parte posterior de la UPS. Conecte y encienda nuevamente la UPS utilizando los procedimientos descriptos anteriormente. Active el contacto de apagado remoto externo para comprobar el funcionamiento.

Advertencia: Este conector slo debe ser conectado a circuitos SELV (muy baja tensin de seguridad, por sus siglas en ingls).

86-86700-00 A01
Downloaded from www.Manualslib.com manuals search engine

Funcionamiento

33

Pulsar

E S P A O L

(Esta pgina ha sido dejada intencionadamente en blanco)

34
Downloaded from www.Manualslib.com manuals search engine

86-86700-00 A01

E S P A O L

Acceso a los datos de mantenimiento y de personalizacin

4.1

Disposicin de los mens en pantalla

4.2

Acceso a Mediciones
Oprima el botn de desplazamiento (25) para ingresar a cualquier estado de situacin y alarmas, luego a las mediciones de voltaje, corriente, frecuencia, potencia de salida y tiempo restante de respaldo.

4.3

Personalizacin utilizando el Panel de control


Oprima el botn de desplazamiento (25) varias veces hasta alcanzar el men de personalizacin. Oprima el botn Enter (26) para acceder a las diferentes posibilidades. Finalmente confirme la seleccin oprimiendo nuevamente el botn Enter (26).

Personalizacin local Funcin Idioma Alarma sonora Configuracin de fbrica Ingls Habilitada Otras configuraciones disponibles Francs, Espaol, Portugus Deshabilitada

86-86700-00 A01

Acceso a los datos de mantenimiento y de personalizacin

41

Downloaded from www.Manualslib.com manuals search engine

Pulsar

E S P A O L

Personalizacin de salida
Funcin Voltaje de salida Convertidor de frecuencia(1)
(1)

Configuracin de fbrica 120 Voltios CA Deshabilitada

Otras configuraciones disponibles 100 a 127 Voltios CA Habilitada

Comentarios

Los dispositivos conectados nunca son transferidos a la derivacin. Slo pueden ser seleccionadas por el usuario en caso que est activada la funcin de conversin de frecuencia.

Frecuencia de salida (1) Seleccin automtica

50 60 Hz

La alimentacin de CA La alimentacin de CA Transferir a la entrada derivada puede estar (1) derivada debe estar de derivacin de CA dentro de las tolerancias fuera de las tolerancias Nivel de sobrecarga
(1)

100%

30 / 50 / 70%

Activar alarma si se sobrepasa el umbral.

(1) Estos parmetros slo pueden ser modificados cuando la UPS est apagada. Podr encontrar comentarios detallados en el software Personal Solution-Pac.

Personalizacin de encendido / apagado


Funcin Arranque con alimentacin de batera Reencendido automtico Ahorro de energa Deteccin de fase / inversin del neutro (SWF) Configuracin de fbrica Habilitada Otras configuraciones disponibles Deshabilitada La UPS arranca nuevamente de manera automtica cuando retorna la alimentacin de CA. Cuando se habilita esta funcin, la batera se apaga cuando la potencia baja al <5%. Inversin del neutro (SWF) Cuando se habilita la funcin, la UPS se mantiene apagada si el sistema detecta la inversin de una fase/del neutro. Comentarios

Habilitado

Deshabilitado

Deshabilitado

Habilitado

Habilitado

Deshabilitado

Personalizacin de batera
Funcin Prueba de batera Configuracin de fbrica Prueba semanal Otras configuraciones disponibles Sin prueba / diaria / mensual 0 al 100% Ajustable en pasos del 1%. Comentarios

Advertencia de batera 20% baja Seleccin del tiempo de respaldo La batera brinda proteccin contra descargas excesivas

Deteccin automtica 13 a 200 Ah de la cantidad de mdulos de batera En caso que se produzcan excesivas descargas mientras la funcin est deshabilitada, ya no se contar con la garanta MGE Office Protection Systems.

Habilitado

Deshabilitado

4.4

Personalizacin utilizando software externo


Coloque el CD-ROM del Solution-Pac en la lectora. En la primera pantalla de navegacin, seleccione Point to Point solution (Solucin punto a punto) y siga las instrucciones de instalacin del software Personal Solution-Pac. Luego seleccione Settings (Configuracin), Advanced settings (Configuracin avanzada) y UPS settings (Configuracin de la UPS). Observe que las versiones para Linux/Unix/MacOS del software Personal SolutionPac no ofrecen esta posibilidad.

42

Acceso a los datos de mantenimiento y de personalizacin

86-86700-00 A01

Downloaded from www.Manualslib.com manuals search engine

E S P A O L

Solucin de inconvenientes
5.1 Solucin de inconvenientes
En caso que se encienda el LED (21) o (22), se ha producido una falla o una alarma. Utilice el botn de escape (24) para silenciar la alarma sonora. Pantalla Descripcin Accin correctiva

En caso que la UPS no se La alimentacin de CA no est Controle que la UPS est encienda, la pantalla conectada o lo est a la salida de correctamente conectada a la entrada alfanumrica muestra: COLD la UPS. de CA. START NOK CHECK AC WIRING El LED (22) est encendido, el Inversin de fase en la entrada LED SWF (11) ubicado en la de alimentacin de CA. La UPS parte posterior de la UPS est no enciende. encendido. La pantalla alfanumrica muestra: SITE WIR. FAULT CHECK AC WIRING Cuando el LED (22) est encendido, la pantalla alfanumrica indica: BATTERY FAULT SERV REQUIRED La batera est conectada incorrectamente. Para corregir el cableado en un sistema con neutro puesto a tierra, llame a un electricista para que modifique las conexiones. Para todos los dems tipos de sistemas, deshabilite la funcin de deteccin. Controle las conexiones de la batera (consulte la Seccin 5.2, Reemplazo del mdulo de la batera). Sustituya la batera (consulte la Seccin 5.2, Reemplazo del mdulo de la batera). Luego llame a soporte postventa. Controle la potencia erogada por los dispositivos conectados y desconecte aquellos dispositivos no prioritarios. Controle el nivel de sobrecarga programado.

LED (22) is ON, the alphanumeric Se ha detectado una falla en la display indicates: BATTERY batera. FAULT SERV REQUIRED Cuando el LED (21) est encendido, la pantalla alfanumrica indica: OVERLOAD ALARM REDUCE LOAD Cuando el LED (22) est encendido, la pantalla alfanumrica indica: LOAD UNPROTECTED OUTPUT OVERLOAD Cuando el LED (22) est encendido, la pantalla alfanumrica indica: REDUCE LOAD RESTART UPS El nivel de carga supera el nivel programado de sobrecarga o la capacidad de la UPS.

La UPS est sobrecargada. Los Controle la potencia erogada por los dispositivos conectados a la UPS son dispositivos conectados y desconecte alimentados directamente por la red aquellos dispositivos no prioritarios. elctrica por medio de la derivacin. Luego de una repeticin de sobrecargas, la UPS queda bloqueada en posicin de derivacin. Los dispositivos conectados a la UPS son alimentados directamente por la red elctrica. Controle la potencia erogada por los dispositivos conectados y desconecte aquellos dispositivos no prioritarios. Apague y encienda la UPS para retornar al funcionamiento normal. Controle la potencia erogada por los dispositivos conectados y desconecte aquellos dispositivos no prioritarios. Controle la instalacin de la salida de la UPS (cableado, equipo con fallas). Llame al departamento de soporte postventa.

Cuando el LED (22) est encendido, La UPS se apaga automticala pantalla alfanumrica indica: mente debido a una sobrecarga OVERLOAD FAULT REDUCE LOAD en la salida de la UPS. Cuando el LED (22) est encendido, la pantalla alfanumrica indica: LOAD SHORT-CIRCU CHECK WIRING Cuando el LED (22) est encendido, la pantalla alfanumrica indica: INTERNAL FAULT SERV REQUIRED La UPS se apaga automticamente debido a un cortocircuito en la salida de la UPS. Se ha producido una falla interna en la UPS. Existen dos situaciones posibles: Todava se alimenta la carga, pero de manera directa desde la red de CA a travs de la derivacin, Ya no se alimenta la carga.

10

11

La pantalla alfanumrica muestra: El cambio del Apagado remoto Reemplace el contacto en la posicin REMOTE POWER OFF RPO (RPO) ha causado el apagado de normal y oprima el botn ON/OFF la UPS. para encenderla nuevamente.

86-86700-00 A01
Downloaded from www.Manualslib.com manuals search engine

Solucin de inconvenientes

51

Pulsar

E S P A O L

5.2

Reemplazo del mdulo de la batera


Recomendaciones de seguridad
La batera puede causar la electrocucin y generar fuertes corrientes de cortocircuito. Se deben seguir las siguientes precauciones de seguridad antes de trabajar con los componentes de la batera: Qutese relojes, anillos, pulseras y cualquier otro objeto metlico de manos y brazos. Use herramientas con mangos aislados.

Extraccin del mdulo de la batera


RT m odel
A Destornille el lateral izquierdo del panel delantero (dos tornillos) B Retire la pieza.

C Desconecte el bloque de la batera separando los dos conectores (nunca tire de los cables).

D Retire la tapa metlica de proteccin adelante de la batera (dos tornillos). E Haga girar el conector. F Pase el conector a travs del orificio.

D E

52
Downloaded from www.Manualslib.com manuals search engine

Solucin de inconvenientes

86-86700-00 A01

E S P A O L

Manual de instalacin y de usuario

G Retire la lengeta plstica para retirar el bloque de la batera y reemplcela.

Tower m odel

A Coloque el panel delantero cerca de la UPS.

B Desconecte el bloque de la batera separando los dos conectores (nunca tire de los cables).

C Retire los 4 tornillos de fijacin ubicados sobre la tapa metlica de proteccin de la batera.

86-86700-00 A01
Downloaded from www.Manualslib.com manuals search engine

Solucin de inconvenientes

53

Pulsar

E S P A O L

D Retire la tapa metlica de proteccin de la batera.

E Retire la lengeta plstica para retirar el bloque de la batera y reemplcela.

Colocacin del nuevo mdulo de la batera


Siga las instrucciones anteriormente descriptas en orden inverso. Para garantizar la seguridad y el alto rendimiento, use solamente bateras provistas por MGE Office Protection Systems. Apriete firmemente las dos partes del conector durante el montaje

54
Downloaded from www.Manualslib.com manuals search engine

Solucin de inconvenientes

86-86700-00 A01

E S P A O L

Apndice
Especificaciones tcnicas

Pulsar 700

Pulsar 1000 Pulsar 1000 RT2U 1000VA /900 W


(3)

Pulsar 1500 Pulsar 1500 RT2U 1500VA /1290 W


(4)

Pulsar EXB 1000/1500 (1) Pulsar EXB 1000/1500 RT2U (2)

Potencia de salida Potencia de entrada de CA Voltaje Frecuencia Factor de potencia Salida de carga Voltaje Frecuencia Distorsin armnica Capacidad de sobrecarga Corriente Batera sellada de plomo cido libre de mantenimiento Ambiente Temperatura operativa Humedad relativa Corriente de fuga Temperatura almacenamiento Altitud Normas y certificacin Seguridad EMC Supresor de sobrecargas

700VA / 630W

60 / 70 / 80V monofsica a 142V (5) 50/60 Hz autoseleccionable > 0,95

120V monofsica 3% (6) 50/60 Hz 0,5% (7) < 4% para una carga linear, < 6% para una carga linear 102% continuos, 130% 12 seg, > 130% 2 seg 5,8A (8) 2x12V 7Ah 8,3A (8) 3x12V 7Ah 12,5A (8) 3x12V 9Ah Dos hileras de 3x12V -9Ah

0C a 40C 20% al 90% (sin condensacin) < 1,1mA -25C a 40C 1000 m

UL 1778 (4 edicin), CSA C22.2 N 107.3-05 FCC Subparte B, clase A IEEE/ANSI 62.41

(1) Mdulo EXB para la Pulsar 1000 y la Pulsar 1500 (2) Mdulo EXB RT2U para la Pulsar 1000 RT2U y la Pulsar 1500 RT2U. (3) 900W, en la configuracin estndar, 800W con al menos 1 EXB conectado (4) 1290W en la configuracin estndar, 1200W con al menos 1 EXB conectado (5) Valores para el 33% / 66% / 100% de la capacidad nominal de potencia (6) Ajustable de 100V a 127V utilizando el software de configuracin de la UPS (7) El modo de conversin de frecuencia se programa utilizando el software de configuracin de la UPS (8) Nominal, para un voltaje de salida de 120V

86-86700-00 A01
Downloaded from www.Manualslib.com manuals search engine

Apndice

A1

Pulsar

E S P A O L

Centro de atencin al cliente de MGE Office Protection Systems

Soporte tcnico y servicios para los productos


Tiene preguntas tcnicas? En caso que encuentre un problema al seguir las instrucciones de este manual o tenga preguntas sobre el funcionamiento, reparacin o servicio de su equipo, consulte directamente al Centro de atencin al cliente de MGE Office Protection Systems o visite nuestro sitio en internet: www.mgeops.com para obtener una completa informacin para servicio.

Para garantizar que su consulta sea respondida adecuadamente, obtenga el nmero de la pieza, el nmero del conjunto y el nmero de serie de la unidad e inclyalos en cualquier consulta o correspondencia. Nmero de pieza: _____________________________________________________________________

Nmero de conjunto: _____________________________________________________________________ Nmero de serie: _____________________________________________________________________

Personas a quienes consultar


Para la ayuda tcnica, el centro del cuidado del cliente, FAQ del cliente visita por favor nuestro Web site: www.mgeops.com o llamada (800) 279-7776.

Programacin para la visita de un ingeniero de servicio en campo


La Programacin para la visita de un Ingeniero de servicio en campo de MGE debe ser hecha habitualmente entre 7 a 10 das antes de la fecha deseada para la visita. En caso que la puesta en servicio de la UPS sea de gran importancia en su cronograma, llame al nmero gratuito de MGE: 1-800-438-7373, para asegurarse realizar una instalacin y encendido seguros que le permitirn mantener la garanta de MGE y asegurarse un buen funcionamiento.

Poltica de devolucin para productos monofsicos (RMA)


En caso que necesite de servicio en fbrica para su equipo, pngase en contacto con el Centro de atencin al cliente de MGE y obtenga una Autorizacin para devolucin de materiales (RMA, por sus siglas en ingls) antes de enviar su unidad. Nunca enve equipo a MGE sin haber conseguido antes el nmero de la RMA. Para otros detalles satisfaga la visita nuestro Web site: www.mgeops.com

Fecha: Nmero de RMA: Nombre del contacto:

______________________________________________________ ______________________________________________________ ______________________________________________________

A2
Downloaded from www.Manualslib.com manuals search engine

Apndice

86-86700-00 A01

E S P A O L

Glosario

Derivacin de CA

Entrada de lnea de Derivacin proveniente de una fuente de CA, controlada por la UPS, utilizada para alimentar directamente la carga en caso que la UPS sufra una sobrecarga o una falla. Tiempo durante el cual la carga puede ser alimentada con la batera de la UPS. Prueba interna de la UPS que se utiliza para controlar el estado de la batera. Dispositivos conectados a la salida de la UPS. Descarga de la batera ms all del lmite admisible, lo que causa un dao irreversible a la batera. Mdulo con salidas de UPS para ser instalado en una baha. Existen diferentes mdulos para diferentes tipos de tomacorrientes.

Tiempo de respaldo Prueba de batera Equipo Descarga excesiva

FlexPDU

Convertidor de frecuencia Modo de funcionamiento utilizado para convertir la frecuencia de alimentacin de CA entre la entrada y la salida de la UPS (50 Hz -> 60 Hz o 60 Hz -> 50 Hz). HotSwap MBP Mdulo de derivacin manual de la UPS utilizado para realizar mantenimiento. Existen diferentes mdulos para diferentes tipos de tomacorrientes.

Advertencia de batera baja Este es un nivel de voltaje de la batera que indica que la reserva de la batera est baja y que el usuario deber tomar medidas debido a una inminente interrupcin de alimentacin a la carga. Entrada normal de CA Porcentaje de carga Personalizacin La lnea de alimentacin de CA que alimenta la UPS bajo condiciones normales. Proporcin de la potencia realmente entregada a la carga y la mxima salida de la UPS. Es posible modificar ciertos parmetros de la UPS programados en fbrica. Ciertas funciones de la UPS tambin pueden ser modificadas por medio del software Personal Solution-Pac para ajustarlos mejor a las necesidades del usuario. Estas salidas pueden ser apagadas automticamente durante el funcionamiento con alimentacin de batera (los retardos de apagado pueden ser programados con el software Personal Solution Pac). La UPS cuenta con dos conjuntos de una y dos salidas programables. Los dispositivos conectados a la UPS pueden ser encendidos incluso si no hay alimentacin de CA disponible. La UPS funciona solamente con la alimentacin de su batera. Sistema de alimentacin ininterrumpible, por sus siglas en ingls. Esta funcin habilita o deshabilita el control de las secuencias de encendido y apagado de la UPS por medio de una computadora.

Salidas programables

Arranque con alimentacin de batera UPS Encendido/Apagado de la UPS controlado por software

86-86700-00 A01
Downloaded from www.Manualslib.com manuals search engine

Glosario

G1

Downloaded from www.Manualslib.com manuals search engine

P O R T U G U E S E

Manual de instalao e do usurio

Pulsar
Manual de instalao e do usurio

Histrico de reviso
Manual de instalao e do usurio do Pulsar, 86-86700-00 Reviso: A01 ECN#: 005282 5/2007

Copyright 2007 MGE Office Protection Systems All rights reserved. Printed in U.S.A. MGE Office Protection Systems 13 Whatney, Suite #101 Irvine, CA 92618
(949) 268-2800

For Technical Support, Customer Care Center, or Customer FAQ, please visit our website: www.mgeops.com or call (800) 279-7776

86-86700-00 A01
Downloaded from www.Manualslib.com manuals search engine

Pulsar

P O R T U G U E S E

86-86700-00 A01
Downloaded from www.Manualslib.com manuals search engine

P O R T U G U E S E

ndice

Introduo............................................................................................................................................1 Uso de smbolos..................................................................................................................................3

1. Apresentao
1.1 1.2 1.3 Posies padro ............................................................................................................1 1 Painis traseiros ............................................................................................................1 2 Painel de controle ..........................................................................................................1 3

2. Instalao
2.1 2.2 2.3 2.4 2.5 2.6 Como desembalar e verificao de contedo ................................................................2 1 Instalao do modelo RT em posio de torre ..............................................................2 2 Instalao do modelo RT em um bastidor......................................................................2 2 Portas de comunicao ..................................................................................................2 3 Conexo porta de comunicao por contato (2) ........................................................2 4 Conexo UPS ................................................................................................................2 5

3. Operao
3.1 3.2 3.3 3.4 3.5 Inicializao e operao normal ....................................................................................3 1 Operao com bateria ....................................................................................................3 1 Retorno de energia por entrada de CA ..........................................................................3 2 Desligamento do UPS ....................................................................................................3 2 Uso das funes de controle remoto do UPS ................................................................3 2

4. Acesso a medidas e a dados de personalizao


4.1 4.2 4.3 4.4 Organizao dos menus de exibio ............................................................................4 1 Acesso a medidas ..........................................................................................................4 1 Personalizao usando o painel de controle..................................................................4 1 Personalizao usando software externo ......................................................................4 2

5. Manuteno
5.1 5.2 Soluo de problemas ..................................................................................................5 1 Substituio do mdulo da bateria ................................................................................5 2

Apndices
Especificaes tcnicas ..............................................................................................................A 1 Glossrio ....................................................................................................................................G 1

86-86700-00 A01
Downloaded from www.Manualslib.com manuals search engine

ndice

ci

Pulsar

P O R T U G U E S E

(Esta pgina foi deixa intencionalmente em branco)

c ii
Downloaded from www.Manualslib.com manuals search engine

ndice

86-86700-00 A01

P O R T U G U E S E

Introduo

Obrigado por selecionar um produto MGE Office Protection Systems para proteger seu equipamento eltrico. Pulsar foi criado com o maior cuidado. Recomendamos que voc leia este manual para aproveitar completamente os vrios recursos do seu UPS (Uninterruptible Power System, Sistema de alimentao ininterrupta). Antes de instalar o Pulsar, leia o folheto sobre as instrues de segurana necessrias. Em seguida, siga as indicaes neste manual. Para descobrir toda a gama de produtos MGE Office Protection Systems e as opes disponveis para a linha Pulsar, o convidamos a visitar nosso site na Web em www.mgeops.com ou entre em contato com o representante da MGE Office Protection Systems.

Proteo ambiental
A MGE Office Protection Systems implementou uma poltica de proteo ambiental. Os produtos so desenvolvidos de acordo com a abordagem de projeto ecologicamente correto.

Substncias
Este produto no contm CFCs, HCFCs ou asbestos.

Embalagem
Para melhorar o tratamento de resduos e facilitar a reciclagem, separe os vrios componentes da embalagem. A caixa que usamos composta de mais de 50% de papelo. Sacos e sacolas so feitos de polietileno. 01 Os materiais da embalagem so reciclveis e contm o smbolo de identificao adequado.
PET

Material Tereptalato de polietileno Polietileno de alta densidade Cloreto de polivinil Polietileno de baixa densidade Polipropileno Poliestireno

Abreviao PET HDPE PVC LDPE PP PS

Smbolo nmero 01 02 03 04 05 06

01
PET

Siga todas as regulamentaes locais para o descarte de materiais de embalagem.

Fim de vida
A MGE Office Protection Systems processar produtos no fim de sua vida de servio em conformidade com as regulamentaes locais. A MGE Office Protection Systems trabalha com empresas encarregadas de coletar e eliminar nossos produtos no fim de sua vida de servio.

Produto O produto feito de materiais reciclveis. A desmontagem e a destruio devem ocorrer em conformidade com todas as regulamentaes locais relacionadas aos resduos. No fim de sua vida til, o produto dever ser transportado para um centro de processamentos para resduos eltricos e eletrnicos. Bateria O produto contm baterias de cido-chumbo que devem ser processadas de acordo com as regulamentaes locais aplicveis relacionadas s baterias. A bateria pode ser removida e descartada em conformidade com as regulamentaes de descarte local correto. As Fichas tcnicas de segurana de material (MSDS) para as baterias esto disponveis no nosso site*. (*) Para obter mais informaes ou para entrar em contato com o gerente ambiental do produto, consulte Environmental Form (Formulrio ambiental) no site: www.mgeops.com -> About us -> Environment (Sobre ns -> Ambiente).

86-86700-00 A01
Downloaded from www.Manualslib.com manuals search engine

Introduo

Pulsar

P O R T U G U E S E

Uso de smbolos

Instrues importantes que devem ser sempre seguidas

Informao, notcia, ajuda

Indicao visual

Ao

Sinal audvel

LED desligado

LED ligado

Declarao da Federal Communication Commission (FCC)


OBSERVAO: Este equipamento foi testado e est de acordo com os limites para um dispositivo digital Classe A, de acordo com a Parte 15 das regras da FCC. Esses limites foram criados para fornecer proteo razovel contra interferncia danosa quando o equipamento for operado em um ambiente comercial. Este equipamento gera, usa e pode radiar energia de freqncia de rdio e, se no for instalado e usado de acordo com o manual de instrues, pode provocar interferncia danosa a comunicaes de rdio. A operao desse equipamento na rea residencial pode provocar interferncia danosa e nesse caso o usurio precisar corrigir a interferncia a sua prpria custa.

2
Downloaded from www.Manualslib.com manuals search engine

86-86700-00 A01

P O R T U G U E S E

Apresentao

1.1

Posies padro
Posio de torre
Dimenses (H x W x D) em mm / polegadas Pulsar 700 Pulsar 1000 Pulsar 1000 RT2U Pulsar 1500 Pulsar 1500 RT2U Pulsar EXB 1000/1500 Pulsar EXB 1000/1500 RT2U 242 x 158 x 400 / 9,52 x 6,22 x 15,74 242 x 158 x 400 / 9,52 x 6,22 x 15,74 438 x 86.5 x 480 / 17,24 x 3,4 x 18,9 242 x 158 x 450 / 9,52 x 6,22 x 17,71 438 x 86.5 x 480 / 17,24 x 3,4 x 18,9 242 x 158 x 400 / 9,52 x 6,22 x 15,74 440 x 86.5 x 480 / 17,32 x 3,4 x 18,9

Posio de bastidor
Pesos em kg / lbs Pulsar 700 Pulsar 1000 Pulsar 1000 RT2U Pulsar 1500 Pulsar 1500 RT2U 12,5 / 27,55 15 / 33 18 / 39,68 18 / 39,68 20,5 / 45,2

Pulsar EXB1000/1500 21 / 46,3 Pulsar EXB 1000/1500 RT2U 24,5 / 54

86-86700-00 A01
Downloaded from www.Manualslib.com manuals search engine

Apresentao

11

Pulsar

P O R T U G U E S E

1.2

Painis traseiros
Pulsar 700 / 1000 / 1500
(1) Porta de comunicao USB
4 2

(2) Porta de comunicao RS232 e de contatos secos (3) Conector para reconhecimento automtico de um mdulo EXB de bateria (exceto no Pulsar 700)

1 8

(4) Slot para placa de comunicao opcional (5) Conector para controle ROO (LIGAR/DESLIGAR remoto) e RPO (Desligamento remoto) (6) Conector para mdulo EXB de bateria exceto o Pulsar 700

5 3 6 7 10 9

(7) Grupo de tomadas programveis para conexo do equipamento (8) Grupo de tomadas para conexo do equipamento (9) Plugue de energia de entrada para conexo com fonte de alimentao CA (10) LED (SWF) indicando inverso fase/neutro do sistema de distribuio

Pulsar 1000 RT2U / 1500 RT2U


1 2 5 10 3 6 4 8 9

Pulsar EXB 1000/1500 (mdulo de bateria opcional)


(11) Conectores para mdulos de bateria (para o UPS ou para os outros mdulos de bateria) (12) Conectores para reconhecimento automtico de mdulos de bateria

12
Downloaded from www.Manualslib.com manuals search engine

Apresentao

86-86700-00 A01

P O R T U G U E S E

Manual de instalao e do usurio

Pulsar EXB 1000/1500 RT2U (mdulo debateria opcional)

1.3

Painel de controle

(20) LED protegido contra carga (21) LED de funcionamento reduzido (22) LED no protegido contra carga (23) Exibio alfanumrica (24) Boto Escape (cancelar) (25) Boto Rolar (26) Boto Enter (confirmar) (27) Boto LIGAR/DESLIGAR para o UPS e tomadas

86-86700-00 A01
Downloaded from www.Manualslib.com manuals search engine

Apresentao

13

Pulsar

P O R T U G U E S E

(Esta pgina foi deixa intencionalmente em branco)

14
Downloaded from www.Manualslib.com manuals search engine

86-86700-00 A01

P O R T U G U E S E

Manual de instalao e do usurio

Instalao

2.1

Como desembalar e verificao de contedo

(30) (31) (33) (34) (36)

Pulsar 700, 1000, 1500 Pulsar 1000 RT2U, 1500 RT2U Cabo de comunicao RS232 Cabo de comunicao RS232 CD-ROM Solution-Pac e elementos de documentao fornecidos dependendo da verso ou opo

(37) Kit de montagem para compartimentos de 19 polegadas (38) 2 suportes para a posio vertical (somente para modelo RT) (41) Placa de comunicao NMC (opcional)

Os materiais da embalagem da UPS devem ser reciclados em conformidade com os regulamentos aplicveis resduos. Os smbolos de reciclagem esto impressos nos materiais de embalagem, para facilitar a separao.

86-86700-00 A01
Downloaded from www.Manualslib.com manuals search engine

Instalao

21

Pulsar

P O R T U G U E S E

2.2

Instalao do modelo RT em posio de torre

2.3

Instalao do modelo RT em um bastidor


Aconselhamos a instalao do mdulo EXB de bateria na posio mais baixa do bastidor e, em seguida, instalar o UPS acima. Siga as etapas 1 a 4, para a montagem do mdulo nos trilhos.

Os trilhos e o hardware necessrio (37) so fornecidos pela MGE Office Protection Systems.

22
Downloaded from www.Manualslib.com manuals search engine

Instalao

86-86700-00 A01

P O R T U G U E S E

Manual de instalao e do usurio

2.4

Portas de comunicao
Conexo da porta de comunicao RS232 ou USB (opcional)
As portas de comunicao RS232 e USB no podem funcionar simultaneamente.

Modelo tipo torre


1. Conecte o cabo de comunicao RS232 (33) ou USB (34) porta serial ou USB no equipamento do computador. 2. Conecte a outra extremidade do cabo de comunicao (33) ou (34) porta de comunicao USB (1) ou RS232 (2) ao UPS. Agora a UPS pode se comunicar com o software de gerenciamento de energia da MGE Office Protection Systems.

Modelo RT

86-86700-00 A01
Downloaded from www.Manualslib.com manuals search engine

Instalao

23

Pulsar

P O R T U G U E S E

Instalao de placas de comunicao opcionais (opcional)


Tower model RT model
No necessrio desligar a UPS antes de instalar a placa de comunicao. (4): Slot, com acesso restrito, para a placa de comunicao. 1. Retire a tampa do UPS (4) presa por parafusos. 2. Insira a placa de comunicao no encaixe. 3. Coloque a tampa do UPS novamente usando os parafusos.

2.5

Conexo porta de comunicao por contato


Pino 2, 3, 5 e 6: no usados, Pino 1: operao em derivao automtica, Pino 4: usurio comum, Pino 7: bateria fraca, Pino 8: protegido contra carga,
n.o. n.o. n.o.

Pino 9: operao com bateria. n.ligado: contato normalmente aberto.

Quando o status for ativo, o contato entre o pino comum (Pin 4) e o pino de informaes relevantes ser fechado. Caractersticas do contato (isolador ptico) Voltagem: 48Vdc max Corrente: 25mA mx por contato Potncia: 1.2W

24
Downloaded from www.Manualslib.com manuals search engine

Instalao

86-86700-00 A01

P O R T U G U E S E

Manual de instalao e do usurio

2.6

Conexo UPS
Verifique se as indicaes da plaqueta de identificao localizada na traseira do UPS correspondem s especificaes da fonte de alimentao e do real consumo de eletricidade na carga total.

Tower model
1. Conecte o soquete do UPS (9) fonte de alimentao CA usando o cabo de alimentao dos equipamentos a serem protegidos. 2. Conecte as cargas UPS. prefervel conectar as cargas prioritrias s tomadas marcadas (8) e as cargas no prioritrias s tomadas marcadas (7) que podem ser programadas em pares (1 e 2). Para programar as tomadas, o software de comunicao da MGE Office Protection Systems necessrio.

RT model

Nota. O UPS carrega a bateria assim que conectado fonte de alimentao CA, mesmo se o boto (27) no estiver pressionado. Depois de o UPS ter sido conectado fonte de alimentao CA, oito horas de carregamento so necessrias antes que a bateria possa fornecer o tempo de carga nominal.

86-86700-00 A01
Downloaded from www.Manualslib.com manuals search engine

Instalao

25

Pulsar

(Esta pgina foi deixa intencionalmente em branco)

26
Downloaded from www.Manualslib.com manuals search engine

86-86700-00 A01

P O R T U G U E S E

Operao
3.1 Inicializao e operao normal
Ao ser iniciado pela primeira vez, a alimentao CA dever estar presente para detectar quaisquer erros de fiao. Posteriormente, o UPS poder ser iniciado, mesmo se a alimentao CA no estiver presente.

Pressione o boto (27) por cerca de um segundo. Os dispositivos conectados so protegidos pela UPS. LED (20) est LIGADO. Se o LED (22) estiver LIGADO, ocorreu uma falha (consulte a seo "Soluo de problemas"). Durante a operao normal, o boto de rolagem (25) pode ser usado para ler medidas do UPS (voltagem de entrada CA, modo operacional, capacidade da bateria e nmero de srie do UPS). Personalizao do UPS Se a personalizao do UPS for desejada, aconselhamos entrar no modo de personalizao neste momento. possvel entrar nesse modo usando os botes no painel de controle no o software Solution-Pac (Windows) includo no CD-ROM do Solution-Pac fornecido pela MGE Office Protection Systems.

3.2

Operao com bateria


Transfer battery power Transfer to to battery power

Os dispositivos conectados continuam a receber energia do UPS se a energia da fonte de alimentao CA no estiver mais disponvel. A energia necessria fornecida pela bateria. LEDs (20) e (21) esto LIGADOS. O alarme de udio soa a cada dez segundos. Os dispositivos conectados recebem energia da bateria. A tela indica o tempo de bateria restante.

Low-battery warning

LEDs (20) e (21) esto LIGADOS. O alarme de udio soa a cada trs segundos.

A carga restante da bateria est baixa. Desligue todos os aplicativos dos equipamentos conectados porque o desligamento da UPS iminente.

86-86700-00 A01
Downloaded from www.Manualslib.com manuals search engine

Operao

31

Pulsar

P O R T U G U E S E

Fim do tempo de durao da bateria Todos os LEDs se apagam. Os alarmes de udio param.

O UPS completamente desligado.

3.3

Retorno de energia por entrada de CA


Depois de uma interrupo de energia, o UPS automaticamente reinicializada quando a energia de alimentao CA retorna (a menos que a funo de reinicializao tenha sido desativada por meio de personalizao do UPS) e a carga passar a ser fornecida novamente.

3.4

Desligamento do UPS
Pressione o boto (27) por cerca de um segundo. Os dispositivos conectados UPS no mais recebem energia.

3.5

Uso das funes de controle remoto do UPS


Pulsar tem a escolha de duas opes de controle remoto. RPO: O desligamento remoto permite que se use um contato remoto para desconectar todos os equipamentos conectados ao UPS por meio de uma fonte de alimentao. A reinicializao da UPS exige interveno manual. ROO: LIGAR/DESLIGAR remoto permite a ao remota do boto (27). Essas funes so obtidas abrindo-se o contacto conectado entre os pinos apropriados do conector (5) no painel traseiro do UPS (consulte o diagrama na pgina a seguir).

RT m odel

Tower m odel

32
Downloaded from www.Manualslib.com manuals search engine

Operao

86-86700-00 A01

P O R T U G U E S E

Manual de instalao e do usurio

Conexo e teste por controle remoto


1. 2. 3. Verifique se o UPS est desligado e se a rede de fonte de alimentao est desconectada. Retire o conector (5) aps soltar os parafusos. Conecte um contato sem voltagem normalmente fechado (60 Vdc / 30 Vac mx., 20 mA mx., seo transversal do cabo de 0,75mm 2) entre os dois pinos do conector (5), (consulte o diagrama). Contacto aberto: desligamento do UPS Contato fechado: inicializao do UPS (UPS conectado rede e energizado pela rede). Nota: Controle LIGAR/DESLIGAR por meio do boto (27) em prioridade em relao ordem do controle remoto. Contacto aberto: desligamento do UPS Para retornar operao normal, desative o contato de desligamento remoto externo e reinicie o UPS usando o boto (27).

4. 5. 6.

Ligue o plugue (5) na parte traseira da UPS. Conecte e reinicie o UPS, conforme os procedimentos descritos anteriormente. Ative o contato externo de desligamento remoto, para testar a funo.

Aviso: Esse conector deve ser conectado somente a circuitos SELV (Voltagem segura extra-baixa).

86-86700-00 A01
Downloaded from www.Manualslib.com manuals search engine

Operao

33

Pulsar

P O R T U G U E S E

(Esta pgina foi deixa intencionalmente em branco)

34
Downloaded from www.Manualslib.com manuals search engine

86-86700-00 A01

P O R T U G U E S E

Acesso a dados de manuteno e de personalizao

4.1

Organizao dos menus de exibio

4.2

Acesso a medidas
Pressione o boto de rolagem (25) para acessar quaisquer condies e alarmes de status e, em seguida, as medidas para voltagem, corrente, freqncia, sada de energia e tempo de durao da bateria.

4.3

Personalizao usando o painel de controle


Pressione o boto de rolagem (25) vrias vezes, at que o menu de personalizao seja exibido. Pressione o boto Enter (26) para acessar as diferentes possibilidades. Finalmente, confirme a seleo pressionando o boto Enter (26) novamente.

Personalizao local Funo Idioma Alarme de udio Configurao de fbrica Ingls Ativada Outras configuraes disponveis Francs, Espanhol, Portugus Desativada

86-86700-00 A01
Downloaded from www.Manualslib.com manuals search engine

Acesso a dados de manuteno e de personalizao

41

Pulsar

P O R T U G U E S E

Personalizao de sada
Funo Voltagem de sada Freqncia conversor (1)
(1)

Configurao de fbrica 120 Volts CA Desativada

Outras configuraes disponveis 100 a 127 Volts CA Ativada 50 ou 60 Hz

Comentrios

Os dispositivos conectados nunca so transferidos para a derivao. Selecionvel pelo usurio apenas se a funo de conversor de freqncia estiver ativada..

Freqncia de sada(1) Seleo automtica Transferncia para a entrada CA de derivao (1) Nvel de sobrecarga
(1)

A derivao de energia A derivao da energia CA deve estar dentro CA pode estar fora dos dos nveis de tolerncia nveis de tolerncia 100% 30 / 50 / 70% Alarme se o limite for ultrapassado.

(1) Esses parmetros podem ser modificados apenas quando o UPS est DESLIGADO. Cometrios detalhados esto disponveis no software Personal Solution-Pac.

Personalizao de LIGAR/DESLIGAR
Funo Inicie com energia da bateria Reinicializao automtica Economia de energia Configurao de fbrica Ativada Ativada Desativada Outras configuraes disponveis Desativada Desativada Ativada O UPS reiniciado automaticamente quando a energia CA retorna. Quando a funo est ativada, a bateria desligada quando a energia cai para <5%. Inverso neutra (SWF) Quando a funo estiver ativada, o UPS permanecer DESLIGADO se o sistema detectar inverso fase/neutro. Comentrios

Deteco de inverso Ativada fase/neutro (SWF)

Desativada

Personalizao da bateria
Funo Teste de bateria Configurao de fbrica Teste semanal Outras configuraes disponveis Sem testes / teste dirio / teste mensal 0 a 100% 13 a 200 Ah Descargas excessivas quando a funo est desativada, a garantia da MGE Office Protection Systems no se aplica mais. Ajustvel em 1% etapas. Comentrios

Aviso de bateria fraca 20% Seleo do tempo de durao da bateria Proteo da bateria contra descargas excessivas Deteco automtica do nmero de mdulos de bateria Ativada

Desativada

4.4

Personalizao usando software externo


Insira o CD-ROM do Solution-Pac na unidade. Na primeira tela de navegao, escolha a opo "Soluo ponto a ponto" e siga as instrues sobre como instalar o software software Personal Solution-Pac. A seguir selecione a opo "Configuraes", "Configuraes avanadas" e "Configuraes da UPS". Observe que as verses do software Personal Solution-Pac para o Linux/Unix/MacOS no oferecem essa possibilidade.

42

Acesso a dados de manuteno e de personalizao

86-86700-00 A01

Downloaded from www.Manualslib.com manuals search engine

P O R T U G U E S E

Soluo de problemas
5.1 Soluo de problemas
Se o LED (21) ou (22) estiver LIGADO, uma falha ou alarme ocorreu. Use o boto ESCAPE (24) para parar o alarme de udio.

Tela

Descrio

Ao corretiva Verifique se o UPS est corretamente conectado energia de entrada CA..

O UPS no inicia e o monitor A energia de entrada CA no alfanumrico indica: COLD est conectada ou est conectaSTART NOK CHECK AC WIRING da sada do UPS. LED (22) est LIGADO, o LED SWF (11) na prte traseira do UPS est LIGADO. O monitor alfanumrico indica: SITE WIR. FAULT CHECK AC WIRING Inverso de fase na energia de entrada CA. O UPS no inicia.

Em um sistema terra-neutro, para corrigir a fiao, chame um eletricista para modificar as conexes. Para todos os outros tipos de sistema, desative a funo de deteco.

O LED (22) est LIGADO, o monitor alfanumrico indica: NO BATTERY CHECK CONNECTION

A bateria est conectada de maneira incorreta.

Verifique as conexes da bateria (consulte Seo 5.2, Substituio do mdulo da bateria). Substitua a bateria (consulte a Seo 5.2, Substituio do mdulo da bateria). Ligue para o suporte ps-vendas. Verifique a energia retirada pelos dispositivos conectados e desconecte todos os dispositivos no prioritrios. Verifique o nvel de sobrecarga programado. Verifique a energia retirada pelos dispositivos conectados e desconecte todos os dispositivos no prioritrios. Verifique a energia retirada pelos dispositivos conectados e desconecte todos os dispositivos no prioritrios. Desligue e reinicie o UPS para retornar operao normal. Verifique a energia retirada pelos dispositivos conectados e desconecte todos os dispositivos no prioritrios. Verifique a instalao na sada do UPS (fiao, equipamento com falha).

O LED (22) est LIGADO, o Uma falha detectada na batemonitor alfanumrico indica: ria. BATTERY FAULT SERV REQUIRED O LED (21) est LIGADO, o monitor alfanumrico indica: OVERLOAD ALARM REDUCE LOAD O LED (22) est LIGADO, o monitor alfanumrico indica: LOAD UNPROTECTED OUTPUT OVERLOAD O LED (22) est LIGADO, o monitor alfanumrico indica: REDUCE LOAD RESTART UPS O nvel da carga excede o nvel de sobrecarga programada ou a capacidade do UPS. O UPS est sobrecarregado. Os dispositivos conectados ao UPS so alimentados diretamente pela rede eltrica por meio do By-pass. Depois das sobrecargas repetitivas, o UPS est bloqueado na posio By-pass. Os dispositivos conectados ao UPS so alimentados diretamente pela rede eltrica.

O LED (22) est LIGADO, o O UPS desligado automaticamonitor alfanumrico indica: OVER- mente por causa de sobrecarga LOAD FAULT REDUCE LOAD na sada do UPS. O LED (22) est LIGADO, o O UPS desligado automaticamonitor alfanumrico indica: LOAD mente por causa de um curto-cirSHORT-CIRCU CHECK WIRING cuito na sada do UPS. O LED (22) est LIGADO, o monitor alfanumrico indica: INTERNAL FAULT SERV REQUIRED

10

Ocorreu uma falha interna no UPS. Ligue para o departamento de suporte H duas situaes possveis: ps-vendas. A carga ainda fornecida, mas diretamente, com energia CA por meio da derivao, A carga no mais fornecida. O desligamento da energia (RPO) levou ao desligamento do UPS. Retorne o contato para a posio normal e pressione o boto LIGAR/DESLIGAR para reiniciar.

11

O modelo alfanumrico indica: REMOTE POWER OFF RPO

86-86700-00 A01
Downloaded from www.Manualslib.com manuals search engine

Soluo de problemas

51

Pulsar

P O R T U G U E S E

5.2

Substituilo do mdulo da bateria


Recomendaes de segurana
A bateria pode causar choques e correntes de curto-circuito. As seguintes precaues de segurana devem ser seguidas antes de qualquer manuteno nos componentes da bateria: Retire relgios, anis, braceletes e quaisquer outros objetos de metal das mos e dos braos. Use ferramentas com cabos isolados.

Retirada do mdulo da bateria


RT m odel
A Retire os dois parafusos do lado esquerdo do painel frontal (dois parafusos). B Retire a pea.

C Desconecte o bloco da bateria, separando os dois conectores (nunca puxe pelos fios).

D Retire a tampa de proteo de metal na parte da frente da bateria (dois parafusos). E Gire o conector. F Passe o conector pelo orifcio.

D E

52
Downloaded from www.Manualslib.com manuals search engine

Soluo de problemas

86-86700-00 A01

P O R T U G U E S E

Manual de instalao e do usurio

G Puxe a guia plstica para retirar o bloco da bateria e o substitua.

Tower m odel

A Coloque o painel frontal prximo ao UPS.

B Desconecte o bloco da bateria, separando os dois conectores (nunca puxe pelos fios).

C Retire os 4 parafusos de fixao da tampa de proteo de metal da bateria.

86-86700-00 A01
Downloaded from www.Manualslib.com manuals search engine

Soluo de problemas

53

Pulsar

P O R T U G U E S E

D Retire a tampa de proteo de metal da bateria.

E Puxe a guia plstica para retirar o bloco da bateria e o substitua.

Montagem do novo mdulo da bateria


Siga as instrues acima na ordem inversa. Para garantir segurana e alto desempenho, use somente baterias fornecidas pela MGE Office Protection Systems. Cuide de pressionar firmemente as duas partes do conector entre si durante a remontagem.

54
Downloaded from www.Manualslib.com manuals search engine

Soluo de problemas

86-86700-00 A01

P O R T U G U E S E

Appendix
Especificaes tcnicas

Pulsar 700

Pulsar 1000 Pulsar 1000 RT2U 1000VA /900 W


(3)

Pulsar 1500 Pulsar 1500 RT2U 1500VA /1290 W


(4)

Pulsar EXB 1000/1500 (1) Pulsar EXB 1000/1500 RT2U (2)

Energia de sada Fonte de alimentao CA Voltagem Freqncia Fator de potncia Sada de carga Voltagem Freqncia Distoro harmnica Capacidade de sobrecarga Corrente Bateria, cido chumbo lacrada, sem manuteno Ambiente
Faixa de temperatura operacional Umidade relativa Corrente de vazamento Faixa de temp. de armazenamento Altitude

700VA / 630W

Fase nica 60 / 70 / 80V a 142V (5) 50/60 Hz de seleo automtica > 0,95

Fase nica 120V 3% (6) 50/60 Hz 0,5% (7) < 4% para carga linear, < 6% para carga no linear 102% contnuo, 130% 12s, > 130% 2s 5,8A (8) 2x12V 7Ah 8,3A (8) 3x12V 7Ah 12,5A (8) 3x12V 9Ah Duas strings de 3x12V -9Ah

0C a 40C 20% to 90% (sem condensao) < 1,1mA -25C a 40C 1000 m

Padres e certificao Segurana EMC Supressor de sobrecarga UL 1778 (4a edio), CSA C22.2 No 107.3-05 FCC Subparte B, classe A IEEE/ANSI 62.41

(1) Mdulo EXB para Pulsar 1000 e Pulsar 1500 (2) Mdulo EXB RT2U para Pulsar 1000 RT2U e Pulsar 1500 RT2U. (3) 900W, na configurao padro, 800W com pelo menos 1 EXB conectado (4) 1290W na configurao padro, 1200W com pelo menos 1 EXB conectado (5) Valores para 33% / 66% / 100% da taxa de alimentao nominal (6) Ajustvel de 100V a 127V usando o software UPS Config (7) O modo de conversor de freqncia programvel usando o software UPS Config (8) Nominal, para voltagem de sada de 120V

86-86700-00 A01
Downloaded from www.Manualslib.com manuals search engine

Apndice

A1

Pulsar

P O R T U G U E S E

Centro de atendimento ao cliente da MGE Office Protection Systems

Suporte tcnico e servios de produtos

Perguntas tcnicas? Se voc encontrar um problema ao seguir as instrues deste manual ou tiver perguntas sobre a operao, o reparo ou a manuteno do equipamento, ligue para o centro de atendimento ao cliente da MGE Office Protection Systems ou visite nosso site em www.mgeops.com para informaes completas de assistncia.

Para garantir que suas perguntas sejam corretamente respondidas, obtenha o nmero da pea, o nmero da montagem e o nmero de srie da unidade e os inclua em quaisquer discusses ou correspondncia. Nmero da pea: Nmero da montagem: Nmero de srie: _____________________________________________________________________ _____________________________________________________________________ _____________________________________________________________________

Quem contactar
Para a sustentao tcnica, o centro do cuidado do cliente, FAQ do cliente visita por favor nosso Web site: www.mgeops.com ou chamada (800) 279-7776.

Agendamento do suporte do engenheiro de servio em campo


O agendamento dos engenheiros de servio em campo da MGE deve ser feito, normalmente, de 7 a 10 dias antes de eles serem necessrios no local. Se a inicializao do UPS for vital para a manuteno da sua programao, ligue para o 0800 da MGE (nos EUA) 1-800-438-7373, para garantir instalao e inicializao seguras que iro manter a garantia da MGE e garantir desempenho sem problemas.

Poltica de devoluo para produtos de fase nica (RMA)


Se voc precisar de assistncia da fbrica para seu equipamento, entre em contato com o Centro de atendimento ao cliente da MGE e obtenha uma autorizao de materiais de devoluo (RMA) antes de enviar sua unidade. Nunca envie equipamento para a MGE sem primeiro obter um nmero de RMA. Para uns detalhes mais adicionais satisfaa a visita nosso Web site: www.mgeops.com

Data: Nmero de RMA:

______________________________________________________ ______________________________________________________

Nome de contato: ______________________________________________________

A2
Downloaded from www.Manualslib.com manuals search engine

Apndice

86-86700-00 A01

P O R T U G U E S E

Glossrio

CA de derivao

Linha de derivao de entrada da fonte de alimentao CA, controlada pelo UPS, usada para fornecer diretamente a carga se ocorrer sobrecarga ou falha no UPS. Tempo durante o qual a carga pode ser fornecida pelo UPS operando com bateria. Teste interno do UPS para verificar o status da bateria. Dispositivos conectados sada do UPS. Descarga da bateria alm do limite permitido, resultando em dano irreversvel bateria. Mdulo com tomadas UPS para instalao em um compartimento. H diferentes mdulos com diferentes tipos de tomadas.

Tempo de durao da bateria Teste de bateria Equipamento Descarga excessivae FlexPDU

Conversor de freqncia Modo de operao usado para converter a freqncia de energia CA entre a entrada e a sada do UPS (50 Hz -> 60 ou 60 Hz -> 50 Hz). HotSwap MBP UPS mdulo de derivao manual do UPS para manuteno. H diferentes mdulos com diferentes tipos de tomadas. um indicador de nvel baixo da voltagem da bateria, indicando que a carga da bateria est baixa e que o usurio deve agir rapidamente devido a risco iminente de interrupo de energia da carga da bateria. A fonte de alimentao CA que alimenta o UPS sob condies normais. Proporo da energia efetivamente puxada pela carga na sada mxima do UPS. possvel modificar certos parmetros da UPS definidos de fbrica. Certas funes da UPS tambm podem ser modificadas pelo software Personal Solution-Pac para melhor se adaptar s necessidades dos usurios. Essas tomadas podem ser automaticamente fechadas durante a operao com bateria (atrasos na hora do desligamento podem ser programados com o software Personal Solution Pac). O UPS tem dois conjuntos de duas e de uma tomada programvel. Os dispositivos conectados ao UPS podem ser iniciados mesmo se a energia da fonte de alimentao CA no estiver disponvel. O UPS funciona apenas com a energia suprida pela bateria. Sistema de alimentao ininterrupta. Esta funo ativa ou desativa a inicializao das seqncias de controle LIGAR/DESLIGAR da UPS ON/OFF pelo computador software de gerenciamento de energia.

Aviso de bateria fraca

Entrada normal CA Porcentagem de carga Personalizao

Tomadas programveis

Iniciar com bateria

UPS LIGAR/DESLIGAR da UPS controlado pelo software

86-86700-00 A01
Downloaded from www.Manualslib.com manuals search engine

Glossrio

G1

Pulsar

P O R T U G U E S E

Notas:

86-86700-00 A01
Downloaded from www.Manualslib.com manuals search engine

Downloaded from www.Manualslib.com manuals search engine