14 GW4-27.5DW Single Grounding Once-through Operation Disconnector 15 GW4-110DW Three-phase Coupled Remodeling Disconnector 16 GW5-110D (W)/630/1250 Outdoor Triple Pole Mounted Disconnector 17 Medium Voltage Switch 23 VBP Indoor Solid-sealed Pole Vacuum Circuit Breaker 32 VK Vacuum Circuit Breaker (Designated Sales Region) 44 VY Vacuum Circuit Breaker (Designated Sales Region) 53 ZN85-40.5 Indoor AC High Voltage Vacuum Circuit Breaker 60 VS1-BYE Indoor High Voltage Vacuum Circuit Breaker 66 VW Single-phase Vacuum Circuit Breaker (Designated Sales Region) 67 UVA Vacuum Contactor - Fuse Combination 70 BYEW1 Series Air Circuit Breaker 71 BYEM1 Series Molded Case Circuit Breaker 75 BYEM1LE Series MCCB with Residual Current Protection 79 BYEM2Z Molded Case Circuit Breaker 81 BYEM6, BYEM6LE Series Miniature Circuit Breaker 83 BYQ2 Series Dual Power Supply Automatic Transfer Switch 86 BYES9 Series Dual Power Supply Automatic Transfer Switch 88 Vacuum interrupter

Overview

Product Category

Overview
Engage in the manufacturing, distribution, design and installation of various high, medium and low voltage switch assemblies of complete specifications and varieties. Products include vacuum circuit breaker and contactor, vacuum interrupter, SF6 MV gas insulated switchgear, high voltage disconnector, various low voltage circuit breakers and switches. Toshiba Baiyun Vacuum Interrupters (Jinzhou) Co., Ltd. is a joint venture engaged in the manufacturing of vacuum interrupters established jointly by Japan Toshiba K.K., Guangzhou Baiyun Electric Group Co., Ltd. and Toshiba (China) Co., Ltd. with its controlling shares held by Toshiba Group. It's the manufacturing base of vacuum switch tubes. It sticks to the strategy of dual brands, namely, Toshiba vacuum interrupter and Liaoju vacuum interrupter. Its Liaoju vacuum interrupter is one of the top four famous brands in China. Nanjing Electric (Group) Co., Ltd. (the former name: Nanjing Electro-Ceramic Factory) was established in 1936. Through merger and acquisition, now it's the wholly owned subsidiary of Baiyun Electric Group; it's the manufacturing base of high voltage disconnectors; and its Thunder brand registered in 1937 is famous at home and abroad. Descriptive trademark is Guangzhou Famous Brand and than 100 million yuan. It respectively introduced more than 50 (sets) world advanced NC presses, NC shearers, NC benders, mechanical machining centers, bus bar machining centers, multi-purpose welding equipment and automatic spraying production lines etc. from Japan, Switzerland, U.S., Britain, Italy, Germany etc., and formed multi-functional metal plate and mechanical processing and production lines; its production technology and production capacity can represent the highest achievement in the fellow sector at home; its annual production capacity of high and medium voltage switchgear assemblies is 6000. Its products are mainly used by the key customers in eight industries including power grid, rail transportation, power plant, petroleum and petrochemical and its market share in the construction of Southern Power Grid is 50%. So far, the company has participated in 15 provincial level power grid construction projects, the construction of more than 80 power plants, as well as Beijing Metro and Guangzhou Metro, becoming one of the 13 qualified suppliers of PetroChina and Sinopec. It introduces and sets up various management methods and systems, including ISO9001, ISO14001, OHSAS18001, 6S, ERP, CRM, PLM, JIT, MBO, CEMS etc., which provide high-quality guarantee for its products. The company has Corporate Technical Center approved by Guangdong Province and state approved corporate technical center high and low voltage switchgear assemblies research sub-center, sets up eight multi-functional research labs in the area of switchgear assemblies, has top high and low voltage electrical products development and test techniques, and possesses more than 80 test and detection equipment with the highest level of the industry, and its metering center has been approved as State Intermediate Metering enterprise.

Product Category
LW41-126/T4000-40 High Voltage SF6 Circuit Breaker
Overview
LW41-126/T4000-40 SF6 Circuit Breaker is outdoor live tank circuit breaker, 3 phase, 50Hz, used in 126kV power system for cutting off load current, fault current and switching circuit. It is capable of 3 phase O/C and auto-reclosing, used to operate, control ans protect power system. This type of SF6 circuit breaker is self-developed product by our company, using SF6 as insulation and arc extinction medium. It adopts the latest self-energy arc extinguishing technology in the word, with the technical performance reaching international advanced level and leading position in China. It is featured with reasonable design, compact structure and low operating power. Spring mechanism is superior to hydraulic one for no leakage of oil and nitrogen. This kind of SF6 circuit breaker is the replacement product of SF6 puffer circuit breaker, having the advantage of low noise, reliable operation, fast installation and easy maintenance.

Working condition
No.
1 2 3 4 5 6 7 8 Ambient temperature Wind pressure Altitude Seismic intensity Pollution degree of external insulation Static tensile force of horizontal longitudinal terminal Static tensile force of transverse horizontal terminal Static tensile force of vertical terminal

Item

Unit
0

Data
-30 ~ 50 700 1000 9 II, III, IV 1250 750 1000

Guangdong Province Famous Brand. High, medium and low voltage switchgear assembly is Guangdong Famous Brand. Besides its proprietary brands, it also manufactures many products with joint venture brands. It successively established three joint ventures with Toshiba and Mitsubishi, and cooperated with Germany Siemens, France Schneider and Switzerland ABB for more than 20 technologies, and introduced the world advanced critical technologies including 8PT, VK and OKKEN products. For a number of years, the company has invested for more

Pa m Degree Class N N N

02

High & Low Voltage Switch

03

Product Category

Product Category

Technical data of circuit breaker


No.
1 2

SF6 management
Item Unit
kV Hz Phase to phase, phase to earth Across the isolating distance Phase to phase, phase to earth Across the isolating distance kV kV A kA kA s kA kA kA kA A time(s) time(s) % ppm

Data
126 50 230 265 550 630 4000 40 1.5 40 4 100 100 0-0.3s-CO-180s-CO 36; 30 10 31.5 16 3000 1 150

No.
1 2 3 4 5 6 7 Rated working pressure

Item
Gas supplement alarm pressure Lock pressure SF6 charge pressure during package and transportation Annual leakage ratio (SF6) Water content in SF6 (V/V) Gas filling quantity

Unit
MPa MPa MPa MPa % ppm kg

Technical data
0.60
0.52 0.50

Rated voltage Rated frequency Rated short time power frequency withstand voltage (wet, dry) Rated lightning impulse withstand voltage (positive, negative)

Insulation

0.02 ~ 0.03 1 150 8

4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Rated current Rated short-circuit breaking current First-pole-to-clear factor Rated short time withstand current Rated duration of short-circuit Rated peak withstand current Rated short-circuit making current Rated operating sequence Short-line fault breaking current Rated out-of-phase breaking current Rated line-charging breaking current Electrical interruptive life of rated short-circuit current Mechanical life Annual leakage ratio (SF6) Water content in SF6

Structure
Circuit breaker is composed of three poles, cross-beam, column and spring operating mechanism (outline and dimension shown in drawing 1). Three poles are on top of the crossbeam, and the spring operating mechanism is right below the cross-beam. The three poles are mechanical connection, with each pole filled with SF6 as insulation and arc-extinction medium, connected by pipeline to form a gas circuit system, and monitored by pressure pointer type density relay. Electrical control system is placed in the spring mechanism box.

chamber to mix with SF6 inside to lower the temperature of the gas, and leave one-way valve (12) tightly closed due to pressure rise in the thermal expansion chamber. When spout laryngeal departs with static arcing contact and the current becomes zero, the high pressure SF6 in the chamber will burst out from the laryngeals of spout and moving arcing contact ( see drawing 2-a ) . Starting from opening operation, piston (13) will move downward together with the thermal expansion chamber to compress SF6 in the pressure chamber. When the pressure gradually increases to a certain value, elastic relief valve is opened. Piston compresses and the relief valve exhausts. As the reaction force to block downward movement decrease, the operating power required is reduced. When breaking low current, mall power generated by the arc and low pressure in the thermal expansion chamber cant provide enough arc-blown pressure, and piston continues to go downward to press SF6 in the chamber to increase the pressure. Difference between the upper and lower air pressure actions to open up the one-way valve (12), and SF6 gas flows through thermal expansion chamber vent to blow out the arc. (See drawing 2-c).

Mechanical property
No.
1 2 3 4 5 6 7 Opening time Closing time Open-close time Close-open time Opening simultaneity Closing simultaneity Switch off time

Arc-quenching principle
During the opening operation, when the static main contact Item Unit
ms ms ms ms ms ms ms

Technical data
322 605 300 805 2 3 60

(3) and moving contact (4) separates, the current will transfer to static arcing contact (10) and moving arc contact (11) for continued flow, and the moving contact will keep up the opening operation. When breaking high current: during breaking operation, SF6 turns into high temperature and pressure gas by the arc generated by the separation action of moving arcing contact and static arcing contact (10). Before spout (9) laryngeal departs with static arcing contact, the gas flows into thermal expansion

Spring mechanism
No.
1 2 3 4 5 6 Control circuit voltage Rated voltage / power of energy storage motor Energy storage time at 85-110% rated voltage Voltage of automatic anti-condensation device and heater Power frequency withstand voltage of mechanical aux. circuit

Item
Tripping and closing coil voltage/current

Unit
V/A V V/kW s V V

Technical data
DC 220/2 DC 220 AC, DC 220/0.8 <30 AC 220 2000

04

High & Low Voltage Switch

05

Distance from the live parts to ground 3230

Product Category
8-M36-4 embedded anchor bolts (Provided by Baiyun) 150 cable hole

Product Category

1. Pole

2 . Cross-arm

3 . Column

4 . Spring operating mechanism 6. Terminal block 7. Mechanism chamber

5. ON-OFF indicator and density relay

Terminal block

Drawing 1 LW-126/T4000-40 AC SF6 Circuit Breaker

Drawing 3 Circuit breaker installation foundation

Force to foundation, weight and dimension


No.
1 2 3 4
a. ON position
1. Porcelain sleeve 6. Pressure chamber

Item
Opening force (downward) Closing force (upward) Total weight including mechanism and gas Dimension (L*W*H)

Unit
N N kg mm

Data
21000 15000 1400 3900*710*4884

b. Break high current

c. Break small current


4. Moving main contact 14. Pressure relief valve

d. OFF position
5. Thermal expansion chamber 10. Static arcing contact

2. Static main contact pedestal 3. Static main contact 7. Intake valve 13. Piston

8. Moving main contact pedestal 9. Spout

11. Moving arcing contact 12. One way valve

Drawing 2 Principle of self-energized arc-extinguishing

06

High & Low Voltage Switch

07

Product Category

High & Low Voltage Switch

Secondary control schematic for LW-126/T4000-40 AC high voltage SF6 circuit breaker

Product Category

08 09

Product Category

Product Category

Order instruction
Please clearly state the following items when ordering:
1. Type, name, quality of circuit breaker; 2. Rated voltage, rated current, rated short circuit breaking current and rated insulation level; 3. External insulation pollution degree (or specific creepage distance); 4. Primary wiring diagram; 5. Voltage of control circuit, now only DC 220V available; 6. Voltage of energy storage motor, AC/DC 220V motor available; 7. If gas processing equipment, SF6 leakage detector, micro-moisture meter required; 8. Spare parts list: name and quantity.

10

High & Low Voltage Switch

11

Product Category

Product Category

High Voltage Disconnector


Overview
Nanjing Electric (Group) Co., Ltd. was restructured and became the wholly owned subsidiary of Baiyun Electric Group and now is the manufacture base of high voltage disconnectors. Nanjing Electric (Group) Co., Ltd. (Nanjing Electro-Ceramic Factory) has been producing high voltage disconnectors for more than 40 years; it's one of the important manufacturers of high voltage disconnector in our country. Products used for electrification railway network system and signal indication include GW4, GW5 and FWZ series of outdoor high voltage disconnector, isolation load switch and equipped electric mechanism and manual mechanism. Rated voltages of products range from 10kV to 220kV, rated current includes 630A, 1250A, 1600A, 2000A, 2500A, and 3150A, specific creepage distance has 16mm/kV, 20mm/kV, 25mm/kV, and 31mm/kV, which is of complete range of types and specifications. The high voltage disconnector has high performance and has passed the test by state or provincial test center. Now it has tens of thousands machine units running in the state power system, among which GW4 series are well recognized by users to have reliable structure, flexible machine driven system, convenient operation, stable contact resistance etc. At present, its products have been sold to all Railway Bureaus of the Ministry of Railways. In recent years, its metal accessories including rod insulator cap, pedestal switch base frame etc. all employ hot galvanizing technology, which greatly improves the metalwork's ability to resist tarnishing. The company's disconnector and load switches have been successfully used in the railway projects including Beijing Kowloon Railway, Beijing Shenyang Passenger Railway, Guanghan High-speed Rail, Shanghai-Nanjing Intercity High-speed Rail, Guangdong-Hainan Cross-sea Railway, Datong-Qinhuangdao Railway, KowloonCanton Railway etc. The product obtains ISO9001 Quality System Authentication.

Working conditions
1. 2000m or less than 3000m (3000m inclusive) above sea level 2. Surrounding ambient temperature is not higher than +40C or lower than -30C, and not lower than -40C in severe cold districts. 3. Seismic intensity does not exceed grade 8. 4. Wind pressure for outdoor products shall not exceed 700Pa (equivalent to 31m/s). 5. Ice coating thickness shall not exceed 1mm in general districts and not exceed 10mm and 20mm in heavy ice coating districts. 6. Indoor product temperature: relative temperature: daily average value shall not be greater than 95% and monthly mean shall not be greater than 90%. Saturated vapor pressure: daily average value shall not be greater than 2.210-1MPa, and monthly mean value shall not be greater than 1.810-1MPa; when temperature drops sharply in the periods with high humidity, it may condense. Voltage Switchgear and Control Standards 5. GB311.1 Insulation Coordination for High Voltage Power Transmission and Distribution Equipment 6. GB311.2-311.6 High-voltage Test Techniques 7. GB3309 Mechanical Test at Ambient Temperature for High Voltage Switchgear 8. GB5582 External Insulation Pollution Class of High Voltage Electric Power Equipment 9. GB5273 Terminals for Transformers, High Voltage Apparatuses and Bushings 10. GB3804-3.6kV-40.5kV High-voltage Alternating Current Switch for Rated Voltage range from 3.6kV to 40.5kV 11. TB/T3150 High Voltage AC Disconnectors and Earthing Switch for Electrification Railway 12. TB/T3151 High Voltage AC Load Switches for Electrification Railway 7. The product is not applicable in the following places: Places with fire or explosion; Places with sharp swings, shakes or impacts Places filled with chemical gases that can easily corrode metals and insulation materials 8. Air pollution classes: no obvious pollution for the use of indoor products; pollution classes for operating ambient of outdoor products include class 0 (clear area), class I, class II, class III, and class IV, which shall be specified by the technical requirements.

Note:
According to the regulations of GB5582-85 External Insulation Pollution Class of High Voltage Electric Power Equipment, the minimum nominal specific creepage distance is 14.8mm/kV, 16mm/kV for class I, 20mm/ kV for class II, 25mm/kV for class III and 31mm/kV for class IV. Specific creepage distance is the ratio of external insulation creepage distance and equipment maximum voltage. If the uses requirements are beyond the above standard service conditions, please contact with relevant departments of the company (factory).

Use
It can be used for the switch of HV electrification railway contact network system without carrying current and electrical isolation between the electrical equipment under maintenance such as primary busbar and breaker and the energized high voltage line. Load switch can open the rated current and cut off shortcircuit current, and has obvious break distance.

Order instructions
1. Product model, name, rated voltage and rated current 2. Thermal stable current of the disconnector and grounding disconnector 3. Grounding disconnector: ungrounded, grounded on the right, grounded on the left, grounded on both sides 4. Creepage distance 5. Model and name of operating mechanism, working voltage of power, number of contactors for auxiliary switches, with electromagnetic lock or not 6. Operation mode: triple-pole interlock or single-pole operation, single-pole, double-pole interlocking or triple-pole 7. Special inclination installation shall be indicated in an order (GW5).

Standards
1. GB1985 Alternating Current High-voltage Disconnectors and Earthing Switches 2. GB11022 Common Technical Requirements for High Voltage Switchgear 3. Equivalent IEC-129 (1984) publication Alternate Current Disconnectors and Earthing Switches by equivalent 4. Equivalent IEC-694 (1980) General Specifications for High

12

High & Low Voltage Switch

13

about

Product Category

Product Category

GW4-27.5DW Single Grounding Once-through Operation Disconnector


Overview
GW4-27.5DW outdoor AC high voltage disconnector for electrification railway is 50HZ outdoor HV electrical equipment. It can be used for the switch of alternate current 27.5kV contact network with voltage and without load as well as the electrical isolation between the electrical equipment under maintenance such as HV busbar and circuit breaker and the energized high voltage line. It can also be used for breaking and making of low capacitance current and inductive current.

GW4-110DW Three-phase Coupled Remodeling Disconnector


Overview
GW4 series high voltage disconnector is single-phase dual column horizontal open circuit structure; it's mainly composed of base frame, rod support insulator, current-carrying part and electric Operating device. Each phase has two support insulators, which are respectively fixed to the bearing chock on both sides of the base frame; they are connected by cross member and can rotate horizontally; their intersection angle is 90. The conduction knife switch is split into halves, which are fixed to the support insulator respectively; contact point of the contactor is in between two support insulators. The terminal GW4-126 high voltage disconnector can also be used for highprofile layout (namely, operated with the control mechanism drawn out). Parts and components for the intermediate driving section will be provided along with the disconnector. GW4-126 series can be furnished with CS14G manual control mechanism or CJ11 electric control mechanism; the earthing switch is furnished with CS14G manual control mechanism; the manual control mechanism can also be used with DSW4 electromagnetic lock. It uses slot aluminum as the main conductor; it has large area of dissipation, high intensity and is safe and reliable; the earthing switch uses flexible configuration and can turn right and left conveniently.

Overall Dimension Drawing


about

about

employs flexible connection, with simple structure, reliable contact and is convenient for repair.

Overall dimension drawing

1. GW4- 27.5DW single pole disconnector 5. CJ11A-G electric-operated mechanism

2. Upper hoop joint

3. 32 water gas pipelines (prepared by users)

4. Lower hoop joint

GW4-27.5DW Single Pole Multipack Figure of Single Pole Grounded Once-through Operation Disconnector (matched with CJ11A-G electric mechanism) GW4- 110DW three-phase interlock remodeling structure

Main technical parameters


Item
Rated voltage Rated current Rated withstand current Rated peak withstand current Rated short-circuit period Short-time power frequency withstand voltage Rated lightning impulse withstand voltage Static tension of terminal Creepage distance Mechanical life Fitted device Grounded Fracture Grounded Fracture Horizontal Transverse Vertical

Main technical parameters


Unit
kV A kA kA s kV kV N

GW4-27.5DW
27.5 1250~3150 31.5~40 80~100 4 80 90 185 215 750 750 500 1200 10000 CJ11 CS14 Rated voltage Rated current Rated short time withstand current Rated peak withstand current Rated short-circuit period

Item

Unit
kV A kA kA s Grounded distance Fracture Grounded distance Fracture Horizontal Lateral Vertical kV kV N mm time(s) Disconnector Earthing switch

GW4-40.5DW
40.5 1250~3150 31.5~40 80~100 4 80 90 185 215 750 750 500 1020~1260 10000 CJ11 CS14

GW4-126DW
126 1250~3150 31.5~50 80~100 4 230 300 550 650 1250 750 1000 3150~3910 10000 CJ11 CS14

Short-duration power-frequency withstand voltage Rated lightning impulse withstand voltage Static tension of terminal Creepage distance Mechanical endurance Supplementary device

time(s) Disconnector Earthing switch

14

High & Low Voltage Switch

15

not less than 2m

not less than 1m

Product Category

Product Category

GW5-110D (W)/630/1250 Outdoor Triple Pole Mounted Disconnector


Overview
GW5-126II(DW) series disconnector is mainly composed of three single poles; each pole is composed of base frame, support insulator, right and left contactors, grounded knife switch, electric Operating device etc. Two support insulators are respectively fixed to the rotary bearings of the pedestal, in V type. Intersection angle of axial lines is 50; bevel gear joggle is under two bearing chocks; the right and left contactors are fixed to the top of support insulator; rotation of the bearing chock will drive the synchronous rotation of the support insulator, thereby to open and close two contactors; three single poles can be interlocked by the interlocking drawbar. This series of disconnector can be grounded on one side, on both sides or ungrounded. CS17F and CS17D manual control mechanism with the angle of rotation being 90are used respectively for it. There is mechanical interlocking and electromagnetic lock on the control mechanism to make sure the operating sequence is right. In order to meet user needs, this series of products can be installed in five different ways, namely, horizontal installation, inclined for 25, inclined for 50, side installation (inclined for 90 and upside down installation.

Medium Voltage Switch


VB Vacuum Circuit Breaker
Places without fire, inflammables, explosion hazards, chemical corrosion and sharp vibration; Seismic intensity: not exceeding grade 8; For special operating ambient, please contact with the manufacturer.

Type specification

Structural feature

Overview
Application environmental conditions
Ambient temperature: upper limit +40C, lower limit -10C; Elevation: not exceeding 1000m;

vacuum: with VEZ A: with KYN B: special 25: 25kA 32: 31.5kA 40: 40kA 50: 50kA 06: 630A 12: 1250A 16: 1600A 20: 2000A 25: 2500A 32: 3150A 40: 4000A 12kV

Rated breaking current

Overall dimension drawing


Earthing switch shalf

Direction A

Type series Rated current

(Installatin hole)

Relative humidity: daily average value shall not be greater than 95%; monthly average value shall not be greater than 90%;
Rated voltage

Earthing knife

Technical parameters
2. Universal joint; 8. Joint; 12. Oscillating arm; 16. Split pin; 3. Pin with hole; 9. Link rod assembly; 13. Bushing; 4. water gas pipe (prepared by user); 10. Water gas pipe (prepared by user); 14.M6 fastening screw;

Product line

VB vacuum circuit breaker

1. Single pole assembly; 5. Locking ring; 11. Supporting rack (prepared by user); 15. Grounded knife switch;

Electric parameters
No.
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

Name (unit)
Rated voltage (kV ) Rated current (A) Frequency (Hz) Rated short-circuit breaking current (kA) Rated short-circuit making current (kA) 4s rated short time withstand current (kA) Rated peak withstand current (kA) Single capacitor bank current (A) Rated O/C current Back to back capacitor bank current (A) 1min power frequency withstand voltage (kV) Impulse withstand voltage (kV) Rated operating procedure Rated short-circuit current operation time(s) Mechanical endurance (times) Rated breaking time (ms) Trip time (ms) Making time (ms) Rated operating voltage (V) Rated operating current (A ) Single-phase major loop resistance (without primary plug)

Technical parameters
12 630, 1250, 1600 50 25, 31 .5. 40 63, 80, 100 25. 31 .5. 40 63, 80. 100 630 40. 50 100, 125 40. 50 100. 125 800 2000, 2500, 3150, 4000

17.CS17 manual control mechanism;

GW5-110IID (W)/630,1250 (90transmission) Triple Pole Multipack Figure of Outdoor Disconnector

Main technical parameters


Item
Rated voltage Rated current Rated short time withstand current Rated peak withstand current Rated short-circuit period Short-duration power-frequency withstand voltage Rated lightning impulse withstand voltage Static tension of terminal Creepage distance Mechanical endurance Supplementary device Grounded distance Fracture Grounded distance Fracture Horizontal Lateral Vertical

Unit
kV A kA kA S kV kV N mm time(s) Disconnector Earthing switch

GW5-40.5DW
40.5 1250~3150 31.5~40 80~100 4 80 90 185 215 750 750 500 1020~1260 10000 CJ11 CS14

GW5-126DW
126 1250~3150 31.5~50 80~100 4 230 300 550 650 1250 750 1000 3150~3910 10000 CJ11 CS14

400 42 (Fracture: 48) 75 (Fracture: 85) O-0, 3s-CO-180s-CO (40, 50kA is O-180s-CO-180s-CO) 50 30000 20000 60 30 45 AC/DC 220V/110V 2.0/4.0 1N=630A 1N=1250A 1600a1N2000A 1N2500A R65 R40 R30 R25

16

High & Low Voltage Switch

17

Product Category
Mechanical parameters
Serial No.
1 2 3 4 5 6

Product Category

Overall dimension
Name (unit) Characteristic parameters Breaking current 40KA Breaking current = 50kA
8.01 30.5 0.4-0.8 0.8-2.0 2 2 9.01

Low current

Contactor torque (mm) Contacting travel (mm) Average closing speed (m/s) Average trip speed (m/s) Jump time of contactor closing (ms) Three-phase asynchronization (ms)

Structure
Main elements of VB vacuum circuit breaker include the operating device, driven gear, insulating boot, vacuum interrupter

Insulating boot Housing Vacuum interrupter Operating device Closing spring

Hoisting hook

Fluctuation conductor

Vacuum interrupter 1. Primary plug ; Trip spring Flexible connection 2. Vacuum interrupter ; 3. Handle ; 4. Counter ; 5. Closing and trip indication ; 6. Inserting hole of charging handle ;

Insulation cover Primary plug

Contactor spring

Driven gear Chassis

Valve press plate

Lever Chassis Insulation drawbar

7. Secondary plug ; 8. Spring charging indication ; 9. Closing button ; 10. Trip knob

Figure 3.1 Sectional View of Disconnector

Trip paddle Trip fanning strip Rachet Manual charging gear Closing half shaft Charging motor and gear box Trip half shaft Excitation switch Charging camshaft Main shaft Counter Contactor spring Trip fanning strip Closing spring Trip knob Closing button Closing releasing slab Closing coil

Trip coil Vacuum interrupter

Figure 4.1.1 Outline Drawing of Low Current Breaker

Chassis

Charging motor and gear box Trip spring

Closing wedge

Contactor spring

Figure 3.2 Device Module View

Figure 3.3 Device Module View Figure 4.1.2 Chassis Mechanism

18

High & Low Voltage Switch

19

1. Primary plug ; 2. Vacuum interrupter ; 3. Handle ; 4. Counter ; 5. Closing and trip indication ; 6. Inserting hole of charging handle 7. Secondary plug ; 8. Spring charging indication ; 9. Closing button ; 10. Trip knob

Figure 4.1.3 Outline Drawing of Heavy Current Breaker

Test position

Work position

20

Note: the anti-trip circuit can be cancelled according to customer requirements

TC: (trip coil) CC: (closing coil) M: (charging motor) LS1~LS5, s8, s: (limit switch) a1~a8: (Auxilisry contact) b1~b8: (Auxiliary contact)

Y: (auxiliary relay) X: (Control relay) F: (Fuse) C: (capacitor) R1~R4: (resistor) D1~D6:(Diode)

Product Category
Heavy current Secondary schematic diagram

Product Category

High & Low Voltage Switch

21

Product Category
Product lectotype
VB-12 No. Width of Operating Main model Series auxiliary voltage A cabinet VB-1206B25 VB-1212B25 VB-1206B25 VB-1212B25 VB-1206B32 VB-1212B32 VB-1216B32 VB-1220B32 VB-1212B40 VB-1216B40 VB-1220B40 VB-1225B40 VB-1232B40 VB-1240B40 VB-1212B50 VB-1232B50 VB-1240B50 W1000 880 852 836 840 587 637 350 746 700 109 310 296 85 86 343 262 275 70 25 262 109 A W800 AC/DC 110 220 598 648 436 76 78 294 685 652 638 638 637 275 280 322 210 49 28 261 (608) (658) (443) (81) (71) (304) 35 W650 528 502 494 494 ------------------------------------Main dimensions B C1 C2 D E F G H J K L M N P W X 35 OverAnti- Tripping Rock- Output Earthing current trip closure in contact mode Y release

Product Category

VBP Indoor Solid-sealed Pole Vacuum Circuit Breaker


Firmer structure
Epoxy medium can protect the vacuum interrupter better, and protect it from accident mechanical damages during assembling and transportation.

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17

598 648 436 76 78 294 637 275 280 322 150 20 189 (608) (658) (443) (81) (71) (304) 49

Miniaturization
The use of epoxy as insulating medium can greatly shorten the
0: No 0: No 1: 1: Yes Yes 3:3a3b 0: No 0: No 5:5a5b 1: Yes 1: Yes 8:8a8b 0: both sides 1: bottom

phase spacing, and reduce the volume of the vacuum breaker and its auxiliary switch cabinet.

70

Free of maintenance
The entire polar pole is poured to an integral unit, so the

Overview
VBP indoor solid-sealed pole vacuum circuit breaker is 12kV24kV three-phase alternating current 50Hz indoor high voltage switchgear; it's applicable to the control and protective cable, overhead line, transformer, current motor, current generator and capacitor bank in power transformation and distribution station, and can be widely used in power plant, power grid, metallurgy, petrochemical, and urban infrastructure construction projects

vacuum interrupter can be better protected; the maintenance free feature of vacuum interrupter enables the breaker to be maintenance free.

e.g. VB-1212B32A/W800 DC220V 100500

Note: 1. Number in the brackets means special models 2. Please contact with the manufacturer for other special models needed

Product Lectotype Information Sheet


Procurement company Company Add. Proposing Dept. End customer Model required Model Rated voltage Rated current Type Rated breaking Structural series current feature 25: 25kA 32: 31.5kA 40: 40kA 50: 50kA Vacuum: with VEZ / A: with KYN B: special / Quantity Auxiliary Operational Anti- Closing Rocking-in Output Over-current Earthing cabinet width power supply trip closure closure contact release form W650 W800 W1000 AC220V AC110V DC220V DC110V 3: 3A3B 5: 5A5B 8: 8A8B 0: both sides 1: bottom Promoter Tel:

such as airports, buildings, metros etc.

Characteristics
High reliability
Compared with traditional integral type breaker, the number of solid-sealed polar pole breaker's parts and components, conductor faying surface, and connecting fasteners is greatly reduced, which simplifies the assembling of major loop, reduces the loop resistance, and greatly improves the reliability of connection of major galvanic circle.
B 1. Dynamic conducting rod 2. Guide sleeve 3. Corrugated tube 4. Dynamic cover board 5. Shield cover of corrugated tube 6. Ceramic package 7. Shield tube 8. Contactor system 9. Static conducting rod 10. Static cover board

Reference value

VB

06: 630A 12:1250A 20:2000A - 12:12kV 25:2500A 32:3150A 40:4000A 12

0: No 1: Yes

0: No 1: Yes

0: No 1: Yes

0: No 1: Yes

VB

Stable insulating property


Surface of vacuum interrupter is poured with epoxy, so the
Note: 1. Standard configuration: rocking handle, charging handle (1 set for every 3 switches) 2. Please fill in the following column for other configuration or special requirements. Other special requirements

impact of polar pole's external environment on vacuum interrupter is reduced to the minimum; its insulating ability can protect the breaker from being affected by dust, moisture, beasties, dews and pollution, so it can fully meet the creeping distance requirements of class 2 polluted districts specified in GB/DL.

22

High & Low Voltage Switch

23

Product Category
More environment friendly
Solid-sealed polar pole breaker can to a certain degree replace SF6 gas as protective insulation, so it's more environment friendly. For other special requirements beyond the above stated application ambient conditions, please contact with the manufacturer. No.
1 2 3 4 5 6

Product Category

Table 2 Mechanical Parameters

Item
Contactor torque Contactor overtravel Average closing speed Average trip speed Closing bounce time Asynchronization of closing and trip

Unit
mm m/s ms

Characteristic parameters Rated voltage 12kV Rated voltage 24kV


91 3.5 0.5 0.4~0.8 1.0~1.8 2 2 131 3 0.5 0.6~1.0 1.3~1.7

Model description

Satisfaction of different standards


VBP indoor solid-sealed pole vacuum breaker can satisfy different GB, DL standards.
Rated short-circuit breaking current 25: 25kA;32:31.5kA; 40:40kA Product series Rated current 06: 63A; 12:1250A; Rated voltage: 12:12KV; 24:24KV; Solid-sealed polar pole

Working condition
Ambient temperature: upper limit +40C, lower limit -15C; Elevation: not exceeding 3000m Relative humidity: daily average value shall not be greater than

Circuit breaker outside view


Low current breaker of rated voltage 12kV Heavy current breaker of rated voltage 12kV

95%; monthly average value shall not be greater than 90%


Places:

Secondary plug

Upper contact arm Solid-sealed polar pole

Secondary plug

Cooling grid Primary plug Upper contact arm Solid-sealed polar pole

indoor, without fire, inflammables, explosion hazards,

Counter

chemical corrosion and sharp vibration


Seismic intensity: not exceeding grade 8;

Design serial number Vacuum circuit breaker

Tripping button Closing and trip indication Specification

Primary plug Lower contact arm Inserting hole of charging handle Closing button Spring charging indication Inserting hole of crank handle

Tripping button Closing and trip indication Specification

Counter Lower contact arm Inserting hole of charging handle Closing button Spring charging indication Inserting hole of crank handle

Technical parameters
Table 1 Electric Parameters

Low current breaker of rated voltage 24kV


Technical parameters
12, 24

Heavy current breaker of rated voltage 24kV

No
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Item

Unit

Rated voltage kV Lightning impulse withstand voltage Rated kV insulation level 1min power frequency withstand voltage Rated frequency Hz Rated current A Rated short-circuit breaking current Rated short-circuit making current (peak value) kA Rated peak withstand current Rated short time withstand current/ duration kA/s Single capacitor bank current Rated O/C A current Back to back capacitor bank current Trip time ms Making time Mechanical endurance time(s) Rated breaking time ms Rated operating voltage V Rated operating current A Rated operating sequence Major loop resistance (20C) M0

To ground 75 (fracture 85), to ground 125 (fracture 145)


Secondary plug

Primary plug Upper contact arm Solid-sealed polar pole

Secondary plug

Cooling grid Primary plug Upper contact arm Solid-sealed polar pole Lower contact arm Counter Inserting hole of charging handle Closing button Spring charging indication Inserting hole of crank handle

To ground 42 (fracture 48), to ground 65 (fracture 79) 50 630, 1250, 1600 25, 31.5, 40 63, 80, 100 63, 80, 100 25/4, 31.5/4, 40/4 630 2000, 3150, 4000 40 100 100 40/4 800 400 30 45 20000 60 AC/DC 220V/110V 2.0/4.0 O-0.3s - CO - 180s-CO ln=630A60 ln=1250A 40 1600=Sln=s2000A30 3150A=Sln=S4000A25
Counter Tripping button Closing and trip indication Specification

Lower contact arm Inserting hole of charging handle Trip button Closing button Closing and trip indication Spring charging indication
Specification

Inserting hole of crank handle

24

High & Low Voltage Switch

25

Product Category

Product Category

Internal structure of circuit breaker

Overall dimension of rated voltage 24kV heavy current breaker

1 . Trip button ;

Circuit board Trip coil Trip spring Main shaft Closing coil Rocking-in closure

Closing spring Auxiliary switch Spring device

2 . Closing button ; 3 . Closing and trip indication ; 4 . Secondary plug ; 5 . Counter ; 6 . Inserting hole of charging handle ; 7 . Spring charging indication ; 8 . Handle ; 9 . Primary plug ; 10 . Upper contact arm ; 11 . Solid-sealed polar pole ; 12 . Lower contact arm

Draft gear Inserting mouth of crank handle

Overall dimension of circuit breake


Overall dimension low current breaker of rated voltage 12kV Overall dimension heavy current breaker of rated voltage 12kV

Overall dimension of rated voltage 24kV low current breaker

1 . Trip button ; 2 . Closing button ; 3 . Closing and trip indication ; 4 . Secondary plug ; 5 . Counter ; 6 . Inserting hole of charging handle ; 7 . Spring charging indication ; 8 . Handle ; 9 . Primary plug ; 10 . Upper contact arm ; 11 . Solid-sealed polar pole ; 12 . Lower contact arm

Product selection sheet


Main dimensions Width Operating of Main model auxiliary voltage A B C D E F G H J cabinet VBP-1206B25 VBP-1212B25 VBP-1212B32 VBP-1212B40 W800 685 652 638 608 436 641 280 275 76 VBP-1216B32 VBP-1216B40 VBP-1220B32 DC/AC VBP-1220B40 110 VBP-1232B40 220 840 587 350 700 296 310 85 VBP-1240B40 VBP-2406B25 VBP-2412B25 W1000 885 842 VBP-2412B32 838 747 447 775 326 310 71 VBP-2416B32 VBP-2420B32 VBP-2432B32 373 447 775 346 310 71 VBP-2432B32/W1000 DC220V 100500 OverEarthing Anti- Closing Rock-in Output current N trip closure closure contact release mode

No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 e.g.

78 210

304

86 275

0: No 0: No 1: 1: Yes Yes 294

0: No 1: Yes

3:3a3b 5:5a5b 8:8a8b

0: No 1: Yes

0: both sides 1: bottom

126 275 336 454

1. Primary plug ; 2. Upper conducting rod ; 3. Solid-sealed polar pole ; 4. Lower conducting rod ; 5. Secondary plug ; 6. Counter ; 7. Trip button ; 8. Closing and trip indication ; 9. Handle ; 10. Inserting hole of charging handle ; 11. Closing button ; 12. Spring charging indication

1. Trip button ; 2 . Closing button ; 3 . Closing and trip indication ; 4 . Secondary plug ; 5 . Counter ; 6 . Inserting hole of charging handle ; 7 . Spring charging indication ; 8. Handle ; 9. Primary plug ; 10. Upper contact arm ; 11. Solid-sealed polar pole ; 12. Lower contact arm

126 275 336 443

26

High & Low Voltage Switch

27

M: charging motor CC: closing electromagnet TC: trip electromagnet 1WK1-5: limit switch FK: auxiliary switch Kj: control relay C1-C2: capacitor Rd: fuse R1-R4: resistor S8 - S9: auxiliary switch (contained by the chassis) D1 - D6: diode Fj: auxiliary relay

Product Category

Product Category

Schematic diagram of control loop

Installation and commissioning


Inspection before installation
After unpacking the circuit breaker, check whether the assemblies are complete according to the packing list; confirm there are no damages in its appearance, no water log or impurities; make sure the screws are tightened, the major loop is firmly fastened and the product can run normally. After the inspection, clean the dust on the surface. Check the degree of vacuum of the vacuum interrupter using power frequency withstand voltage method (trip the breaker and impose powerfrequency voltage to the fracture).Install the machine after it's qualified in inspection.

Check whether the connecting line is broken; Check whether the breaker is damaged mechanically; Conduct power frequency withstand voltage test to the breaker to check its insulation level.

Manual closing and trip


Manual charging: insert the charging handle from the inserting hole of charging handle on the panel to store energy; when the device ticktocks, and the charging sign points to the charging position, it shows the spring device has finished charging. Manual closing: press the closing button on the panel, the closing-trip sign will show the closed position, meaning that it's closed. Manual trip: press the trip knob on the panel, the closing-trip sign will show the tripping position, meaning that it's tripping.

Commissioning
Products which are in good condition after unpacking inspection need no commissioning; only the breakers which do not meet the technical requirements or whose parts and components are changed need commissioning. (Commissioning shall be conducted with the help of the company's technicians; if detailed product information is required, please contact with our company directly) First of all, adjust the adjusting nut at the lower end of the dynamic conducting rod of vacuum interrupter, so that the vacuum interrupter's contactor torque and contactor overtravel can reach the specified value of the specification; Then check whether all parts of the shaft are correctly connected and whether the oil bumper is normal; Finally, adjust the device so that it can operate normally; there is be no clamping stagnation in manual operation, electro control, charging, closing and tripping. After commissioning of the entire breaker, it shall meet the requirements of parameters list in table 2.

Electric closing and trip


Charging operation: connect the control loop of the breaker, power on and after the charging signal is sent out, the breaker's control wiring is powered on; the motor will be powered on through the control loop and then it rotates and drives the closing spring to store energy. After the closing spring finishes charging, the limit switch will cut off the motor power and the charging sign will point to the charging position. Closing operation: after the closing instruction is given out, the closing coil excites and the iron core moves to hit the closing interlocking; the closing spring releases energy and the breaker will be switched on; after the closing operation, the closing-trip sign will show the closed position, and under such circumstances the charging device is in free state. Tripping operation: after the tripping instruction is given out, the trip coil excites and the iron core moves to separate the tripping interlocking; the tripping spring releases energy and the breaker will be switched off; after the tripping operation, the closing-trip sign will show the switch-off state.

Operation and maintenance


Operational readiness inspection
Check whether the installed base of breaker is level and whether the fundamental plane can bear the weight of switch and relevant electrical force;

Test position

Working condition

28

High & Low Voltage Switch

29

Product Category
Maintenance and repair
The maintenance intervals and contents are changing along with the service conditions, on/off times and the level of breaking current. Normally running breaker shall be maintained regularly; clean the dust on the insulation surface, and all moving parts shall be poured with lubricating oil regularly; Check whether the screws are loosened after operating for 2000 times; if screws are loosened, tighten them timely; Check immediately when there are closing or tripping faults; During maintenance, the vacuum interrupter shall not be hit with hard objects (such as tools); Mechanical features testing and adjustment of the breaker shall only be conducted by professionals. variation in temperature may cause frosting, which may reduce the performance or cause defects). No.
1 2 3

Product Category

List of accessories
Name
Manual charging handle Rocking handle of breaker 58-core air socket

Use
For manual charging of breaker Rocking in and out of breaker Plug match between secondary socket and vacuum circuit breaker

Attachment paper
Quality certificate Factory inspection report Checklist of attachment spares, parts and accessories Packing list Installation and instruction manual Other relevant documents

Product Lectotype Information Sheet


Procurement company Company Add. Proposing Dept. End customer Model required Model Rated voltage Rated Type Rated current series breaking current Structural feature Auxiliary Operatio- Anti- Closing Rock-in Output Overcabinet nal power trip closure closure contact current width supply release Earthing mode Tel:

Ordering instructions
Type and name of breaker Rated voltage (kv) Rated current (A) Rated short-circuit breaking current ( kA) Quantity Operating device voltage (AC/DC) Accessories If users have other special requirements (such as elevation, temperature etc.), please make notes before placing orders.

Storage
The breaker shall be placed in the room that is dry, ventilated, damp proof and has no noxious gas; pay attention to the following notes and remember to fix the dust-proof cover. The storage place shall be dry and kept out of the sun; Avoid corrosive gas and dust; Avoid places with sharp variation in temperature (sharp

06:630A 12:1250A Reference VBP - 12:12kV 16:1600A 20:2000A value 25:2500A 32:3150A 40:4000A VBP 12

with W650 25:25kA Vacuum: VEZ 32:31.5kA A: with KYN W800 40:40kA B: special W1000

AC220V AC110V 0: No 0: No DC220V 1: Yes 1: Yes DC110V

0: No 1: Yes

0: No 0: both sides 1: Yes 1: bottom

Note: Standard configuration: rocking handle, charging handle (1 set for every 3 switches) Please fill in the following column for other configuration or special requirements. Other special requirements

30

High & Low Voltage Switch

31

Product Category

Product Category

VK Vacuum Circuit Breaker (Designated Sales Region)


Overview
Product overview
VK vacuum circuit breaker is produced by Guangzhou Toshiba Baiyun Electric Equipment Co., Ltd. through introducing the improved technology of Toshiba. The product is of omniseal handcart type; its general layout is suspension type; it adopts the three-phase integral insulating boot and is used for interphase and phase-ground insulation and fixed interrupter; It uses the charging spring device, has the functions of manual charging and electric charging, and has anti-bouncer. The operating device has mechanical and electric interlock which

Miniaturization design
It adopts three-phase insulating boot which can be used for inter-phase and phase-ground insulation and support of interrupter; it's delicate in appearance, compact in structure, small in size and light in weight. Rear part of the insulating boot has insulation cap which can realize the omniseal of breaker; it can be furnished with a 650 mm wide cabinet.

Satisfaction of different standards


VK vacuum circuit breaker can meet GB, DL, IEC, and JEC standards.

Working condition
Ambient temperature: upper limit +40C, lower limit -15C; Elevation: not exceeding 1000m; Relative humidity: daily average value shall not be greater than 95%; monthly average value shall not be greater than 90%; Places without fire, inflammables, explosion hazards, chemical corrosion and sharp vibration; Seismic intensity: not exceeding grade 8; For special operating ambient, please contact with the manufacturer.

Large creeping distance vacuum interrupter


Surface creeping distance of the corrugated pipe interrupter produced by Toshiba Corporation exceeds 240mm, making it safer and more reliable in use.

Reliable vacuum circuit breaker


With the technical support of Toshiba which is most experienced in the manufacturing of vacuum equipment and the introduction of Toshiba's advanced manufacture and monitoring equipment, Guangzhou Toshiba Baiyun Electric Equipment Co., Ltd. will provide good quality and highly reliable vacuum circuit breakers to the vast customers.

can prevent maloperation. At its bottom there is chassis for closed operation. VK type vacuum circuit breaker is 3.6 ~ 12kV three-phase alternating current 50Hz indoor high voltage switchgear; it can be used for the control or protection of power transmission and distribution system in power plants, substations and industrial and mining companies, especially for opening circuit in places with vital power load and frequent operations.

Closed operation
Bottom of the breaker has a chassis and the use of cabinet can realize closed operation, making it safer and more convenient.

High reliability
From design to production, VK type vacuum circuit breaker is under strict quality control system.

Model description

Toshiba world leading vacuum technique


Toshiba has been dedicated to improving and developing vacuum technique since 1962. Now its annual output exceeds 300 million, which is leading in the world The product has large surface creeping distance and strong pollution resistance ability, which can meet the market demands in China Patented technology of longitudinal magnetic field, strong ability in opening circuit More than 40 years' experience in manufacturing and operation, high reliability

Characteristics Reliable breaking performance


VK type vacuum circuit breaker adopts the high-performance vacuum interrupter produced by Toshiba Corporation; during breaking, the electric arc in the vacuum can diffuse at a high speed, which can realize arc quenching when the current reaches zero for the first time.

Less maintenance
VK vacuum circuit breaker needs no special maintenance; besides, with special structural design, it's easy to operate and repair.

Structural feature Rated breaking current Type series

Vacuum: with VEZ A: with KYN B: special 25:25kA ; 32:31.5kA 40:40kA ; 50:50kA

Rated current 06:630A

Long service life


Mechanical endurance of Vk vacuum circuit breaker is >20000 times, and rated short-circuit current opening is >50 times.

12:1250A 16:1600A 20:2500A 32:3150A 40:4000A

Rated voltage 12kV Product series VK vacuum circuit breaker

Safe and reliable


Vacuum circuit breaker takes vacuum as the arc-extinguishing medium which will generate no explosion and fire during breaking.

No pollution to environment
Vacuum circuit breaker has no decomposed product and will generate no pollution to environment; there is little noise during its operation.

32

High & Low Voltage Switch

33

Product Category

Product Category

Technical parameters
Electric parameters
No.
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 Rated O/C current

Sectional view
Insulating boot Hoisting hook Closing spring vacuum interrupter Flexible connection Fluctuation conductor

Name (unit)
Rated voltage(kv) Rated current(A) Frequency (Hz) Rated short-circuit breaking current( kA) Rated short-circuit making current ( kA) 4s rated short time withstand current ( kA) Rated peak withstand current ( kA) Single capacitor bank current (A) Back to back capacitor bank current (A) Impulse withstand voltage ( kV) Rated operating procedure Rated short-circuit current operation times Mechanical endurance (times) Rated open circuit time (ms) Trip time(ms) Making time(ms) Rated operating voltage(V) Rated operating current(A) Single-phase major loop resistance (without primary plug) In=630A R60na 30000 25, 31 .5. 40 63, 80, 100 25. 31 .5. 40 63, 80. 100 630

Technical parameters
12 630, 1250, 1600 50 40. 50 100, 125 40. 50 100. 125 800 400 42 (fracture: 48) 75 (fracture: 85) O-0.3s-CO-180s-CO (40, 50kA^jO-180s-CO-180s-CO) 50 20000 60 30 45 AC/DC 220V/110V 2.0/4.0 In=1250A R40na 1600AIn2000A R30nD In2500A 2000, 2500, 3150, 4000

Housing vacuum interrupter

Operating device

Insulation cover Trip spring Primary plug Contactor spring Valve press plate Lever Chassis

1min power frequency withstand voltage(kV)

Driven gear Chassis

Insulation drawbar

Outline view

Secondary plug of control loop Trip button Inserting hole of charging handle Closing button (underneath the interlocking cover board; the cover board is optional)

Closing/trip indication (closing: red; trip: green) Counter Specification Inserting hole of crank handle

Mechanical parameters
No.
1 2 3 4 5 6

Name (unit)
Open contact clearance (mm) Contacting travel (mm) Average closing speed (m/s) Average trip speed (m/s) Jump time of contactor closing (ms) Three-phase asynchronization (ms)

Characteristic parameters Breaking current40KA


8.01 30.5 0.4-0.8 0.8-2.0 <2 <2

Charging indication (white: discharged; yellow: charged)

Breaking current = 50kA


9.01

Primary plug

Insulating boot vacuum interrupter

Structure and functions


Overall structure
Main elements of VK vacuum interrupter include the operating device, driven gear, insulating boot, vacuum interrupter, conductor, housing and chassis.
Insulation drawbar

Insulation cover

Figure 3.2 Outline view of low circuit breaker(630-2000A)

34

High & Low Voltage Switch

35

Product Category
Tripping fanning strip Secondary plug of control loop Trip button Rachet Manual charging gear Inserting hole of charging handle Closing button (underneath the interlocking cover board; the cover board is optional) Closing half shaft Trip half shaft Limit switch Charging camshaft Main shaft Charging motor and gear box Closing/trip indication (closing: red; trip: green) Charging indication (white: discharged; yellow: charged) Counter Contactor spring Counter Inserting hole of crank handle Specification Trip paddle Tripping fanning strip Primary plug

Product Category

Figure 3.5 Device Module View


Trip coil Vacuum interrupter

Closing spring Vacuum interrupter

Trip button Closing button

Charging motor and gear box

Insulation cover Insulating boot

Closing releasing slab Closing coil

Trip spring

Closing wedge

Contactor spring

Figure 3.3 Outline drawing of heavy current breaker(2500-4000A)

Figure 3.6 Device Module View

Load characteristics Structure of the operating device Operating device


The operating device adopts four-bar structure. During closing, the closing spring drives the closing camshaft to rotate, and rotation of cam will press the four bars to drive the main shaft to close. During tripping, the tripping fanning strip rotates and drives the connecting rod to activate the four bars, so that the four bars lose balance; the quick moving of four bars will drive the rotation of the main shaft to open. On the device there is a line indicating the abrasion state of contactor and the abrasion of contactor can be observed from its front side. For details, please refer to the validation of contactor abrasion in the maintenance and repair part.
Device interlock Contactor abrasion mark Electric chassis operation motor (optional) Rocking in interlock electromagnet Rocking-in closure Closing spring Circuit board Trip coil

During closing of vacuum circuit breaker, the closing spring release energy and draw and press the trip and contractor spring respectively; the trip and contactor spring store energy.

During tripping, the trip and contactor spring release energy and act together to separate the dynamic & static contactors of the vacuum interrupter quickly.

Auxiliary switch Closing coil

Trip spring Main shaft Contactor spring Draft gear

Figure 3.4 View of device on the breaker

Comparison between VK device and like products : The most proper load characteristics Higher calorie running Low fusion welding rate of vacuum interrupter contactor Figure 3.7 Load characteristics of the device

36

High & Low Voltage Switch

37

Product Category
Structure and principle of vacuum interrupter
The interrupter adopts the longitudinal magnetic field electrode technology and controls the electric arc through the magnetic field to realize fast arc extinction. With the action of the current flowing through the electrode, there is longitudinal magnetic field generated between the contactors. With the action of the longitudinal magnetic field, the electric arc rotates on the electrode surface and diffuse to the electrode surface fast, so arc voltage is low and stable and there is little contact loss, so that the contactor of interrupter can work for a longer time.
Static contactor Shield cover A Current and magnetic field

Product Category

Tripping operation
Press the trip button and the breaker opens. Then, the closing and trip indication shows "open". The following operations may cause breaker defects:

circumstances, if the closing instruction is given out (impose pressure on +HM-N1 point), the breaker will close when the closing coil CC excites (about 40ms). When the breaker closes, the auxiliary switches b5 and b6 switch and closing coil CC terminates excitation. Then the stabilizer Y excites and forms the protective circuit of closing and tripping circuit. Charging action When the breaker closes, the limit switch closes at the same time; the control relay X excites and starts the charging function. After the control relay excites, the charging circuit is switched on; the current motor M rotates and drives the spring to charge; after the spring finishes charging (about 4s), the limit switch LS1LS2 breaks, and control relay X terminates excitation. Tripping action Only a1, a2 and TC are related to breaker tripping; when conditions allow, if the tripping instruction is given out (impose pressure on +FM-N2 point), the breaker will open when the trip coil excites (about 25ms). When the breaker opens, auxiliary switches a1 and a2 switch and trip coil TC terminates excitation. Note: refer to section 5.3 Secondary Schematic Diagram for all contact points.

Warning

Press the closing button under closed position. Press the closing button while pressing the trip button.

Electric operation Charging operation


Connect the control loop of the breaker and power on, the current motor will rotate and the closing spring begins charging. When the charging indication changes from "white"

Ceramic package

(discharged) to "yellow" (charged), it means the closing spring


Dynamic contactor

has finished charging.

Metal bellows

Closing operation
After the closing instruction is given out, the closing coil excites and breaker is closed. After it's closed, the current motor continues rotating, till the closing spring finishes charging.
B Internal structure C Conditions at the arc

The closing and trip indication will show "closed". The closing spring's charging indication shows "yellow" (charged).

Figure 3.8 Structure of vacuum interrupter and drawing of arc extinction principle

Operational method and action specification


Manual operation Charging operation
See figure 4.1-4.2: insert the charging handle, and shake it several times (about 7 times) and it will click. Then the closing spring charging indication changes from white (discharged) to yellow (charged), showing that it has entered to the charged state.
Figure 4.1 Manual operation drawing
Inserting hole of charging handle

Tripping operation
After the tripping instruction is given out, the trip coil excites and breaker is open. Then, the closing and trip indication shows "open".

Dangerous

Please keep off, for fear of casualties due to electric shock.

Action specification Action of control loop


Do not operate the breaker when the panel

Note
Trip button Closing button

is discharged, in case there are damages and accidents.

Closing operation
Press the closing button and the breaker closes. Then, the closing and trip indication shows "closed"; closing charging indication shows "white" (discharged).

Closing action
Closing and trip indication Charging indication

1. When the limit switch LS closes, the closing spring begins charging 2. When the limit switch LS opens, the closing spring finishes charging 3. Closing instruction ; 4. The closing action begins (the trip spring begins charging) 5. Tripping instruction ; 6. Tripping action begins ; 7. Breaker closes ; 8. Breaker opens

After the closing spring finishes charging, if the breaker is in open status and meet the requirements for closing of the breaker, its control loop is shown in figure 4.3. Under such

Figure 4.2 Manual operation indication

Figure 4.3 Control Loop Operation

38

High & Low Voltage Switch

39

Product Category
Device action Note
Keep your hands or any part of your body from the device, for fear of jammed injuries. Charging action The breaker is kept at the closed postion as shown in figure 4.4 (B); drive the charging crank handle electrically or manually to Closing action Figure 4.4 (A) is the illustrative drawing showing the open status of the breaker, when the closing spring is charging (waiting for closing). Under such circumstances, press the closing button or drive the closing wedge through the closing coil, so that the cam can rotate fast as shown in figure 4.4 (B), that's the closed position. rotate the closing cam and start the charging function. When the roller on the closing cam touches the closing wedge, it finishes charging. Tripping action Press the trip button or drive the trip axis through the trip coil and the device will return to the open status as shown in figure 4.4 (A).

Product Category

Overall dimension
Low current

1 Primary plug 2 Vacuum interrupter 3 Handle 4 Counter 5 Closing and trip indication 6 Inserting hole of charging handle 7 Secondary plug 8 Spring charging indication 9 Closing button 10 Trip button

A Figure 4.4 Operation of Device

Figure 5.1 Outline Drawing of Low Circuit Breaker

40

High & Low Voltage Switch

41

Product Category
Chassis
Grounding busbar

Product Category

Product selection sheet


------------------------------------ ReW. of Main dimensions No. Main Anti- Closing Rack-in Output OC. Earthing Electric mark Series aux. Un model A B C1 C2 D E F G H J K L M N P W X Y trip closure closure contact trip mode chassis cabinet VK1 35 1206B25 W650 528502494494 608 658 443 637298289 81 71 322 304 165 20189 VK2 49 1212B25 VK3 35 1206B25 VK4 1212B25 VK5 49 1212B32 W800 685652638638 608 658 443 637298289 81 71 322 304 200 38261 VK6 1212B40 VK7 1216B40 70 VK8 1220B40 VK9 1225B40 VK10 109 1232B40 VK11 1240B40 W1000 880 852836840 712 762 472 746375284 83 86 343 387 275 25362 VK12 70 1212B50 VK13 1232B50 109 VKAC/ 0: 0: both 14 0: No 1240B50 DC 0: No 0: No No sides 0: No 1: 110 1: Yes 1: Yes 1: 1: 1: Yes VKYes 15 35 220 Yes bottom 1206B25 598 648 436 76 78 294 W650 528502494494 637275280 322 150 20189 (608) (658)(443) (81) (71) (304) VK16 49 1212B25 VK17 35 1206B25 VK18 1212B25 VK19 49 1212B32 598 648 436 76 78 294 W800 685652638638 637275280 322 210 28261 (608) (658)(443) (81) (71) (304) VK20 1212B40 VK21 1216B40 70 A VK22 1220B40 VK23 1225B40 VK24 700 109 1232B40 VK25 1240B40 W1000 880852836840 587 637 350 310296 85 86 343 262 275 25362 VK26 70 1212B50 VK27 746 1232B50 109 VK28 1240B50 e.g. With Toshiba VEN cabinet with KYN28/KYN44 cabinet
Note: 1. Number in the brackets means special models 2. For other models, please contact with the manufacturer

Grounding clamps at two sides interlock plate

Note 1: Choose one from the two grounding modes

Figure 5.2 Chassis Mechanism

Heavy current

1 Primary plug 2 Vacuum interrupter 3 Handle 4 Counter 5 Closing and trip indication 6 Inserting hole of charging handle 7 Secondary plug 8 Spring charging indication 9 Closing button 10 Trip button

Figure 5.3 Outline Drawing of Heavy Current Breaker

42

High & Low Voltage Switch

43

Product Category

Product Category

VY Vacuum Circuit Breaker (Designated Sales Region)


Simple spring control mechanism; 10000 times of maintenance free operation; It adopts the lead screw propelling device, making it labor saving, stable, and have good self-locking performance.

connection, which has high reliability. The loop resistance of vacuum interrupter under rated contact pressure is less than 50u. : The control device adopts the spring control mechanism especially designed for such new style breaker and is fixed inside the framework. Its design characteristics are more suitable for such vertical arrangement of the breaker, making it become an inseparable part of the entire structure of the breaker. The device is simply designed and its output curve can well meet

the requirements of the interrupter. Its performance can better fit the characteristics and requirements of 40.5kV vacuum circuit breaker. The breaker is generally reasonable in overall arrangement, delicate in appearance and simple and flexible in operation; it's characterized by reliable electric property, long service life, convenient repair and the maintenance free feature. It's suitable for various places and can be used in the places with harsh operating conditions.

Working condition
Ambient temperature: upper limit +40C, lower limit -15C; Elevation: not exceeding 1000m; Relative humidity: daily average value shall not be greater than 95%; monthly average value shall not be greater than 90%; Places: indoor, without fire, inflammables, explosion hazards, chemical corrosion and sharp vibration Seismic intensity: not exceeding grade 8;

Circuit breaker outside view

Charging indication

Overview
VY-40 indoor AC high voltage vacuum circuit breaker is mainly used in three-phase alternating current 50Hz, 40.5kV power system for opening and closing load current, overload and short-circuit current; it can be used in the places with frequent operation, and is suitable for the control and protection in power plants, transformer substations, power equipment and power lines. The breaker adopts spring charging control mechanism and the operational power supply can be DC or AC, which is very convenient; the product is characterized by good performance, high reliability, convenience in repair and maintenance, and long maintenance interval.

Special requirements can be made in orders.

Model description

Counter Closing button Trip button Inserting hole of charging handle Design series number Rated short-circuit breaking current (kA): 25, 31.5 Rated current(A):J:630,M:1250,N:1600, P:2000 Rated voltage: 40.5kV Product series Vacuum circuit breaker Tripping indication

Figure 1 Panel Appearance

Introduction of structural function


Structure
VY - 40 indoor AC high voltage vacuum circuit breaker (breaker for short hereinafter) adopts the vertical arrangement structure, which effectively reduces the depth of breaker. The breaker adopts compound insulation structure; the three-phase interrupter and conductors are separated by three independent epoxy insulating cylinders. Compound insulation reduces the size of breaker. With the use of compound insulation structure, the breaker can meet the requirements of air insulation distance and creeping distance in normal operation. The main galvanic circle's vacuum interrupter and conductor are installed in the insulating cylinder, so the inter-phase distance is only 300mm. Electrical connection of the major loop adopts fixed type
Figure 2 Circuit Breaker Appearance
Specification Secondary plug of control loop Handle Inserting hole of handle Operating instruction for propelling device Emergency trip button Earthing interlock handle Opening part Primary plug Contact arm

Characteristics
The breaker adopts the integral arrangement structure with the vacuum interrupter on the top and the device at the bottom, which is convenient for commissioning; It adopts the compound insulation structure with air and epoxy material, which is compact in design and light in weight; The interrupter adopts longitudinal magnetic field arc extinction, which is of low closure property and fine asymmetric breaking performance;

Screw rod

44

High & Low Voltage Switch

45

Product Category

Product Category

Operating principle
Arc extinction principle
The vacuum interrupter for the breaker has high degree of vacuum. When the dynamic and static contactors are charged and open when driven by the operating device, vacuum arc will be produced between the two contactors. Besides, due to the special structure of contactor, there may be proper longitudinal magnetic field generated between two contactors. As a result, the vacuum arc will be diffused and spread uniformly on the surface of the contactor to be combusted, thereby to maintain very low arc voltage. When the current reaches zero naturally, residual ions, electronics and metallic vapor will be compounded or condensed on the contactor surface and shield cover within microseconds to extinct the arc; insulation strength of the medium at the interrupter fracture will be restored fast to realize breaking. The vacuum circuit breaker uses longitudinal magnetic field to control the vacuum arc, so it has powerful and strong ability for breaking current.

c) Closing operation
After the device closing spring is charged, such state will be kept due to the pressure of the wedge. Gusset of the wedge tends to move in the direction of tripping under the driving force of the cam roller. Now rotate the closing half shaft clockwise to the release position (about 20) and the gusset of wedge that keeps the charging state will run fast clockwise; the charging state will terminate, and closing spring releases energy fast and drives the cam to rotate anticlockwise. Meanwhile, the linkage gear will run to the closing position as driven by the cam to close the device. Then the travel switch will reset; the motor powers on and drives the closing spring to charge again, so that the device
Static contactor Shield cover

Charging action
When the breaker closes, the limit switch LS1 -LS2 closes at the same time; the control relay X excites and starts the charging function. After the control relay excites, the charging circuit is switched on; the current motor M rotates and drives the spring to charge; after the spring finishes charging (about 4s), the limit switch LS1-LS2 breaks, and control relay X terminates excitation.

Tripping action
Only a1, a2 and TC are related to breaker tripping; when conditions allow, if the tripping instruction is given out (impose pressure on +FM-N2 point), the breaker will open when the trip coil excites (about 25ms). When the breaker opens, auxiliary switches a1 and a2 switch and trip coil TC terminates excitation.

is closed and charged.

Ceramic package Dynamic contactor Metal bellows

d) Tripping operation
The closed state of device is kept by the gusset and half shaft of linkage gear. The gusset tends to move along the release direction under the load of breaker; at such time if the tripping half shaft is rotated to the release position anticlockwise (about 20), the gusset will run fast anticlockwise, and thus the balanced state of linkage gear will be terminated. It will move to the tripping positin under load and the device is open.

Note: refer to the device wiring diagram for the contact points

Dangerous

Please keep off, for fear of casualties due to electric shock.

Action of control loop

A Current and magnetic field

B Internal structure

C Conditions at the arc

Action a) Motor charging operation


Connect the control loop of the breaker; power on and the motor will start running. When the discharged and charged indication changes from "discharged" to "charged", the motor stops. Then the closing spring is charged.

e) Action specification
Do not operate the breaker when the panel

Warning

is discharged, in case there are damages and accidents.

Action of control loop


Closing action
After the closing spring finishes charging, if the breaker is in open status and meets the requirements for closing of the breaker, its control loop is shown in figure 4.3. Under such
Inserting hole of charging handle

b) Manual charging operation


Take the baffle of the handle inserting hole and insert the manual charging handle (about 280mm, accessory) to the inserting hole; shake the charging handle several times (about seven times) and it will snap and become charged. Note) Times of action of the operating handle will change along with the change of action angles. After the device is charged, the breaker will close as long as it receives the closing instruction at any time.
Figure 3 Manual Operation Drawing

circumstances, if the closing instruction is given out (impose pressure on +HM-N1 point), the breaker will close when the closing coil CC excites (about 40ms). When the breaker closes, the auxiliary switches b5 and b6 switch and closing coil CC terminates excitation. Then the stabilizer Y excites and forms the protective circuit of closing and tripping circuit.

1. 2. 3. 4. 5. 6. 7. 8.

When the limit switch LS closes, the closing spring begins charging When the limit switch LS opens, the closing spring finishes charging Closing instruction The closing action begins (the trip spring begins charging) Tripping instruction Tripping action begins Breaker closes Breaker opens

46

High & Low Voltage Switch

47

Product Category

Product Category

Technical parameters
No.
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Rated insulation level

Mechanical features parameters


Unit
kV Hz A kA

Item
Rated voltage 1min power frequency withstand voltage (effective value) Lightning impulse withstand voltage (peak value) Rated frequency Rated current 4s rated short time withstand current Rated peak withstand current Rated short-circuit breaking current Rated short-circuit making current Rated operating sequence Breaking time Breaking times of rated short-circuit breaking current Breaking current of single capacitor bank Breaking current of back to back capacitor bank Rated operating voltage Mechanical endurance

Parameter value
40.5 95 185 50 630 1250 1600 2000 25, 31.5 63, 80 25, 31.5 63, 80 O-0.3s-CO-180s-CO

No.
1 2 3 4 5 6 7 8 9 10 11 12

Item
Contactor torque Contactor overtravel Allowable abrasion thickness of overtravel contactor Average closing speed Average trip speed Making time Trip time Contactor closing bounce time Closing asynchronization of three-phase contactor Trip asynchronization of three-phase contactor Cushion stroke of buffer Loop resistance of all phases (excluding contact arm)

Unit
mm mm m/s

Parameter value
21 1 4 0.5 3 0.8~1.2 1.2~17 35-65 15~22

ms

^5 2 2

ms time(s) A V time(s)

60 20 630 400 AC110/220, DC 110/220 10000

mm

71 40

Technical parameters for charging motor of control mechanism


Rated voltage (V)
DC110/AC110 DC220/AC220

Rated output power (W)


70

Normal working voltage


85%~110% Rated voltage

Product overall dimension Technical parameters for closing and trip coil
Rated working voltage (V) Coil ohmic value at 20C () Coil turns Rated operating current (A) Normal working voltage range
DC110 27.7 10% 1700 4 DC220 126 10% 3880 2

Reliable tripping at 65%-120% rated working voltage; no tripping lower than 30% rated working voltage

List of accessories
No.
1 2 3

Name
Manual charging handle Rocking handle of breaker Air socket

Use
For manual charging of breaker Rocking in and out of breaker Connection of the secondary loop of breaker

1. Primary plug ; 2. Vacuum interrupter ; 3. Handle ; 4. Counter, charging, closing and tripping indication ; 5. Earthing interlock handle 6. Inserting hole of charging handle ; 7. Emergent trip button ; 8. Inserting mouth of crank handle ; 9. Closing and trip button ; 10. Specification

48

High & Low Voltage Switch

49

Welding panel of printed circuit

Wiring diagram of the device

Product Category

Product Category

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

LX R4 R3 R2 R1 RD C2 C1 D1~D5 FJ KJ FK 1WK1~3 HQ, FQ D

Limit switch Resistor Resistor Resistor Resistor Fuse Capacitor Capacitor Diode Auxiliary relay Control relay Auxiliary switch Limit switch Closing and trip electromagnet Charging motor

LXW18-11 RJ-2W-24KQ/6.8KQ RJ-2W-3KD.750Q RJ-2W-12KQ/3KQ R - 2W -1 BGXP 250V 2A/4A CL11-600V0.1 m F/400V0.1 [iF CL11-400V 0.1 M F/200V 0.22 u F 1N5407 800V 3A JQX-13F2 DC110V/48V JQX-13F4DC110V/48V F10-10II/W2 10a10b LXW16-11 DC220V 16A MFH-10 DC220V/110V ZYJ55-1A DC220V/110V rev 10r/min torque 24.5NM

1 2 1 2 2 1 1 1 5 1 1 1 3 2 1

Packing, transport, acceptance check and storage


Packing and transport
VY-40 indoor vacuum circuit breaker is independently packed. It's fixed to a wooden stand and covered with plastic paper to prevent penetration of water. During packing and transporting, the breaker shall be open and the product can't be turned over or rolled.

Installation and commissioning


Inspection before installation
Afther unpacking, check whether the parts and components of breaker are complete according to the packing list; check whether the breaker is wetted and damaged and whether it can run normally. After the inspection, clean the dust on the surface. Check the degree of vacuum of the vacuum interrupter using power frequency withstand voltage method (trip the breaker and impose power-frequency voltage to the fracture at 95kV/ min). Install the machine after it's qualified in inspection.

Acceptance check upon reception


Check whether the packing is in good condition; Consult the packing list and check whether the documents, accessories, and spare parts are complete; Check whether the technical parameters on the nameplate of breaker and quality certificate meet the requirements of ordering.

Commissioning
Products which are in good condition after unpacking inspection need no commissioning; only the breakers which do not meet the technical requirements or whose parts and components are changed need commissioning First of all, adjust the height of knuckle bearing and oil bumper at the lower end of the dynamic conducting rod of vacuum interrupter, so that the vacuum interrupter's contactor torque can reach the specified value of the specification; Adjust the nuts on the contactor spring properly so that the contactor over travel can reach the value specified in the technical specification; Then check whether all parts of the shaft are

Storage
The breaker shall be placed in the room that is dry, ventilated, damp proof, shock-resistant and noxious gas proof. If it's placed for a long time, spread lubricating oil to the transmission parts and check whether the environment meets the requirements regularly.

50

High & Low Voltage Switch

51

Product Category
correctly connected and whether the oil bumper is normal. Finally, adjust the device so that it can operate normally; make sure there is be no clamping stagnation in manual operation, electro control, energy storage, closing and tripping. After commissioning of the entire breaker, it shall comply with the parameters listed in table 2.

Product Category

ZN85-40.5 Indoor AC High Voltage Vacuum Circuit Breaker


longitudinal magnetic field arc extinction, which is of low closure property and fine asymmetric breaking performance; Simple spring control mechanism; 10000 times of maintenance free operation; It adopts the lead screw propelling device, making it labor saving, stable, and have good self-locking performance.

Attachment paper
Quality certificate Factory inspection report Checklist of attachment spares, parts and accessories Packing list Installation and instruction manual Other relevant documents

Ordering instructions
Type of breaker Quantity Rated voltage (kv) Operating voltage (AC / DC) Rated current (A) Accessories Rated short-circuit breaking current ( kA)

Working condition
Ambient temperature: upper limit +40C, lower limit -15C; Elevation: not exceeding 1000m; Relative humidity: daily average value shall not be greater than 95%; monthly average value shall not be greater than 90%; Places: indoor, without fire, inflammables, explosion hazards,

Overview
ZN85-40.5 indoor AC high voltage vacuum circuit breaker is mainly used in three-phase alternating current 50Hz, 40.5kV power system for opening and closing load current, overload and short-circuit current; it can be used in the places with frequent operations, and is suitable for the control and protection in power plants, transformer substations, power equipment and power lines. The breaker adopts spring charging control mechanism and the operational power supply can be DC or AC, which is very convenient; the product is characterized by good performance, high reliability, convenience in repair and maintenance, and long maintenance interval.

chemical corrosion and sharp vibration Seismic intensity: not exceeding grade 8; Special requirements can be made in orders.

Model description
Rated short-circuit breaking current (Ka): 25, 31.5 Rated current (A): 630, 1250, 1600, 2000 Rated voltage: 40.5kV Design serial number Indoor Vacuum circuit breaker

Characteristics
The breaker adopts the integral arrangement structure with the vacuum interrupter on the top and the device at the bottom, which is convenient for commissioning; It adopts the compound insulation structure with air and epoxy material, which is compact in design and light in weight; It can be matched with both imported vacuum interrupter and home-made vacuum quenching pot. Both of them adopt

Introduction of structural function


Structure
ZN85-40.5 indoor AC high voltage vacuum circuit breaker(breaker for short hereinafter) adopts the vertical arrangement structure, which effectively reduces the depth of breaker. The breaker adopts compound insulation structure; the three-phase interrupter and conjoint charged body are

52

High & Low Voltage Switch

53

Product Category
separated by three independent epoxy insulating boots. Compound insulation reduces the size of breaker. With the use of compound insulation structure, the breaker can meet the requirements of air insulation distance and creeping distance in normal operation. The main galvanic circle's vacuum interrupter is connected with the dynamic & static conductors and installed in the insulating cylinder, so the inter-phase distance is only 300mm. Electrical connection of the major loop adopts fixed type connection, which has high reliability. This breaker can be furnished with both imported vacuum interrupter and home-made vacuum interrupter. The degree of vacuum inside the vacuum interrupter is lower than 1.33x10-3Pa; the loop resistance of vacuum interrupter under rated contact pressure is less than 25 u. The control device adopts the spring device especially designed for such new style breaker and is fixed inside the framework. Its design characteristics are more suitable for such vertical arrangment of the breaker, making it become an inseparable part of the entire structure of the breaker. The device is simply designed and its output curve can well meet the requirements of the interrupter. Its performance can better fit the characteristics and requirements of 40.5kV vacuum circuit breaker. The breaker is generally reasonable in overall arrangement, delicate in appearance and simple and flexible in operation; it's characterized by reliable electric property, long service life, convenient repair and the maintenance free feature. It's suitable for various places and can be used in the places with harsh operating conditions. b) Manual charging operation Insert the manual charging handle (about 420mm long, accessory) to the inserting hole of charging rocking arm; then sway it from side to side (about 60); the unidirectional bearing can drive the charging shaft to rotate so that the closing spring can charge. After the device is charged, the breaker will close as long as it receives the closing instruction at any time. c) Closing operation After the device closing spring is charged, such state will be kept due to the pressure of the wedge. Gusset of the wedge tends to move in the direction of tripping under the driving force of the cam roller. Now rotate the closing half shaft clockwise to the release position (about 20) and the gusset of wedge that keeps the charging state will run fast clockwise; the charging state will terminate, and closing spring releases energy fast and No.
1 2 3 4 5 6 7 8 9 10 11

Product Category

on the surface of the contactor to be combusted, thereby to maintain very low arc voltage. When the current reaches zero naturally, residual ions, electronics and metallic vapor will be compounded or condensed on the contactor surface and shield cover within microseconds to extinc the arc; insulation strength of the medium at the interrupter fracture will be restored fast to realize breaking. The vacuum circuit breaker uses longitudinal magnetic field to control the vacuum arc, so it has powerful and strong ability for breaking current.

drives the cam to the closing position, so that the device can be closed. Then the travel switch will reset; the motor powers on and drives the closing spring to charge again, so that the device is closed and charged. d) Tripping operation The closed state of device is kept by the gusset and half shaft of linkage gear. The gusset tends to move along the release

direction under the load of breaker; at such time if the tripping half shaft is rotated to the release position anticlockwise (about 20), the gusset will run fast anticlockwise, and thus the balanced state of linkage gear will be terminated. It will move to the tripping positin under the force of trip spring so that the device will be open.

Charging principle of the device


a) Motor charging operation The device charging unit uses single reduction gear unit; the motor inputs power from one end of the small chain wheel spindle and drives the big chain wheel through roller chain. The large chain wheel rotates and at the same time drives the driving pawl which will mesh with the driving block during operation, so that the closing spring can charge. After the spring charging has finished, the travel switch is pushed to cut off the motor power. Meanwhile, the clutch pusher will lift the driving pawl away from the driving block to make sure the charging system won't be damaged under inertia force. No.
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Rated insulation level

Technical parameters
Item
Rated voltage 1min power frequency withstand voltage(effective value) Lightning impulse withstand voltage (peak value) Rated frequency Rated current 4s rated short time withstand current Rated peak withstand current Rated short-circuit breaking current Rated short-circuit making current Rated operating sequence Breaking time Breaking times of rated short-circuit breaking current Breaking current of single capacitor bank Breaking current of back to back capacitor bank Rated operating voltage Mechanical endurance ms time(s) A V time(s) kA Hz A kV

Unit

Parameter value
40.5 95 185 50 630, 1250, 1600, 2000 25, 31.5 63, 80 25, 31.5 63. 80 O-0.3s-CO-180s-CO 80 20 630 400 DC/AC 110/220 10000

Mechanical features parameters


Item
Contactor torque Contactor overtravel Allowable abrasion thickness of contactor Average closing speed (12mm just before the contactor closes) Average trip speed (12mm just before the contactor opens) Making time Trip time Contactor closing bounce time Closing asynchronization of three-phase contactor Trip asynchronization of three-phase contactor Loop resistance of all phases(excluding contact arm) ms m/s mm

Unit

Parameter value
21 2 7.51.5 3 0.8-1.2 1.70.3 100 60 3 2 2 50

Operating principle Arc extinction principle


The vacuum interrupter for the breaker has high degree of vacuum. When the dynamic and static contactors are charged and open when driven by the operating device, vacuum arc will be produced between the two contactors. Besides, due to the special structure of contactor, there may be proper longitudinal magnetic field generated between two contactors. As a result, the vacuum arc will be diffused and spread uniformly

54

High & Low Voltage Switch

55

Product Category

Product Category

Technical parameters for the charging motor of control mechanism


Model
ZYJ110-66

Wiring diagram of the device

Rated voltage (V)


DC/AC 110/220

Rated output pwoer(W)


<230

Normal working voltage


85% - 110% rated voltage

Technical parameters for closing and trip coil


Rated working voltage(V) Coil ohmic value at 20C (Q ) Coil turns Rated operating current(A) Normal working voltage range
DC110 10510% 4860 1.05 DC220 230 10% 5430 0.96

Anti-trip circuit

Closing and tripping circuit

Reliable tripping at 65%-120% rated working voltage; no tripping lower than 30% rated working voltage

List of accessories
No.
1 2 3

Tripping circuit
Use
For manual charging of breaker Rocking in and out of breaker Connection of the secondary loop of breaker

Name
Manual charging handle Rocking handle of breaker Air socket

Charging motor Charging signal

Product overall dimension


Charging signal

Operating instructions for tripping prevention


CZ and outgoing feeders are connected to the adjacent terminals on the cabinet; Need anti-trip circuit: short circuit of these two points (use connection strap); Need no anti-trip circuit: no short circuit of these two points
K0 JX HQ TQ LX D
1. Primary plug 2. Vacuum interrupter 3. Handle 4. Counter, charging, closing and tripping indication 5. Earthing interlock handle 6. Inserting hole of charging handle 7. Emergent trip button 8. Inserting mouth of crank handle 9. Closing and trip button 10. Specification

Auxiliary relay Transition terminal Closing electromagnet Tripping electromagnet Interlocking limit switch Charging motor Air socket Charging limit switch Auxiliary switch Name

CZ CK DL Code

56

High & Low Voltage Switch

57

Product Category

Product Category

Packing, transport, acceptance check and storage


Packing and transport
ZN85-40.5 indoor vacuum circuit breaker shall be independently packed. It's fixed to a wooden stand and covered with plastic paper to prevent penetration of water. During packing and transporting, the breaker shall be open and the product can't be turned over or rolled.

components are changed need commissioning. First of all, adjust the height of knuckle bearing and oil bumper at the lower end of the dynamic conducting rod of vacuum interrupter, so that the vacuum interrupter's contactor torque can reach the specified value of the specification; Adjust the nuts on the contactor spring properly so that the contactor overtravel can reach the value specified in the technical specification; Then check whether all parts of the shaft are correctly connected and whether the oil bumper is normal; Finally, adjust the device so that it can operate normally; make sure there is be no clamping stagnation in manual operation, electro control, energy storage, closing and tripping. After commissioning of the entire breaker, it shall comply with the parameters list in table 2.

Check the degree of vacuum of the vacuum interrupter; Check whether the overtravel and contactor torque meet the requirements; Check whether the fasteners are loosened; Check whether the breaker is dry and clean; Check whether the contact of auxiliary switch is burnt. C) If the breaker is found to be wet, check all the insulation pieces timely; dry the wet parts at 70C- 80C oven for 48 hours and then assemble and debug it again, till it complies with the parameters in table 2. D)Check all the parts of the device after 2000 times of operations and take corrective measures if there is looseness and lubricant starvation. E)During use and maintenance, enclosure of the vacuum interrupter shall not be hit with hard objects (such as tools); F)After the interrupter opens circuit for 20 times, check the degree of vacuum of the interrupter and erosion of contactor; if it can't meet the requirements, change the interrupter immediately.

Attachment paper
Quality certificate Checklist of attachment spares, parts and accessories Installation and instruction manual Factory inspection report Packing list Other relevant documents

Acceptance check upon reception


Check whether the packing is in good condition; Consult the packing list and check whether the documents, accessories, and spare parts are complete; Check whether the technical parameters on the nameplate of breaker and quality certificate meet the requirements of ordering.

Ordering instructions
Type of breaker Rated voltage(kv) Rated current(A) Rated short-circuit breaking current( kA) Quantity Operating voltage(AC / DC) Charging motor voltage(V) Closing and trip coil voltage(V) Accessories

Rated operating sequence of the breaker


Proper operating sequence of this breaker is: open-0.3s-close and open-180s-close and open Closing and trip of the breaker can be operated in two ways: electric operation and manual operation.

Storage
The breaker shall be placed in the room that is dry, ventilated, damp proof, shock-resistant and noxious gas proof. If it's placed for a long time, spread lubricating oil to the transmission parts and check whether the environment meets the requirements regularly.

a) Electric operation
When the breaker's secondary plug is well connected to the external control circuit, it can be operated electrically through the closing and trip coil.

Installation and commissioning


Inspection before installation
After unpacking, check whether the parts and components of breaker are complete according to the packing list; check whether the breaker is wetted and damaged and whether it can run normally. After the inspection, clean the dust on the surface. Check the degree of vacuum of the vacuum interrupter using power frequency withstand voltage method (trip the breaker and impose power-frequency voltage to the fracture at 95kV/ min). Install the machine after it's qualified in inspection.

b) Manual operation
Insert the charging handle to the device's charging block and then charge manually; press the closing button on the panel for closing operation; press the trip button for trip operation.

Operation and maintenance


A) Before the breaker is put into service, check whether the rated voltage and rated current of the operating elements are in coincidence with the practical situations; then conduct manual charging, electric charging, closing operation and tripping operation to the device and check whether all the indicators are qualified. B) The breaker in service shall be inspected regularly; main contents include:

commissioning
Products which are in good condition after unpacking inspection need no commissioning; only the breakers which do not meet the technical requirements or whose parts and

58

High & Low Voltage Switch

59

Product Category

Product Category

VS1-BYE Indoor High Voltage Vacuum Circuit Breaker

Technical parameter
Technical parameters of breaker

Parameter No. Name Unit 1250-31.5 1600-40 VS1- 3150-40 VS1- 630-25 VS1- 1600-31.5 VS12000-40 BYE-12/T 4000-40 BYE-12/T 1250-25 BYE-12/T 2000-31.5 BYE-12/T 2500-40 2500-31.5
12 KV (inter-phase, phase to ground) 75, (fracture) 85 (inter-phase, phase to ground) 42, (fracture) 48 Hz 630 1250 A 630/400 25 25 63 63 31.5 31.5 80 80 800/400 40 40 100 100 1250 1600 2000 2500 1600 2000 2500 3150 4000

Rated voltage Lightning impulse withstand voltage (full wave) 1min power frequency withstand voltage

insulation 2 Ratedlevel 3 4

Rated frequency Rated current

Overview
VS1-BYE indoor high voltage vacuum circuit breaker is 12kv three-phase alternating current 50Hz indoor high voltage switchgear which can be used for the control and protection of electrical equipment in mines, companies, power plants and transformer substations. It can be placed in hand cart type switch cabinet or fixed type switch cabinet. It has the strengths like long service life, simple maintenance, no pollution and explosion hazards, and low noise. It can be used in the places with frequent operations, such as the power transformation and distribution stations and closing and trip capacitor banks which require small placing area, no oil and high safety and reliability.

Places without fire, explosion hazards, severe pollution, chemical corrosion and sharp vibration; Seismic intensity: not exceeding grade 8; Note: for other service conditions not included in the above stated ones, users can contact with the manufacturer.

Rated O/C single capacitor bank current 5 / Rated O/C back to back capacitor bank current 6 7 8 9 10 11 12 13 14 Rated short-circuit breaking current 4s rated short time withstand current Rated peak withstand current Rated short-circuit making current Rated operating sequence Rated operating voltage Mechanical endurance Breaking times of rated short-circuit breaking current Accumulative allowable abrasion thickness of dynamic and static contactors

Applicable standards
GBI984-2003 Alternate Current High-voltage Circuit Breaker JB 3855-1996 3.6~40.5kV Indoor Alternate Current High Voltage Vacuum Circuit Breaker for Rated Voltage above 3.6kV and below 40.5kV DL/T403-2000 12kV~40.5kV Ordering Specifications for HV Vacuum Circuit Breaker for Rated Voltage from 12kV to 40.5kV

trip-180s-closing and Trip-0.3s-closing and trip-108s-closing and trip Trip-180s-closing and trip 220/110 10000 time(s) 30 3

Adjustment parameters of breaker

Working condition
Ambient temperature: upper limit +40C, lower limit -10C; Elevation: not exceeding 1000m; Relative humidity: daily average value shall not be greater than 95%; monthly average value shall not be greater than 90%; Saturated vapor pressure: daily average value shall not be greater than 2.2X10 - 3MPa; monthly average value shall not be greater than 1.8X10 - 3MPa;

Type specification

No.
1 2 3 4

Name
Contactor torque Contacting travel Interphase center distance Average trip speed Average closing speed Trip time Maximum/rated Minimum Making time Closing asynchronization of three-phase contactor Trip asynchronization of three-phase contactor Contactor closing bounce time Major loop resistance

Unit
mm 2100.5 m/s

Parameter
111 30.5 2750.5 1.10.2 0.60.2 20~50 25~60 30~65 2 2 2

Vacuum circuit breaker Indoor Code of Baiyun electric appliance Rated voltage (kV)

Rated short-circuit breaking current( kA) Rated current(A) Spring operating device

5 6 7 8 9 10 11

ms

40

30

25

20

60

High & Low Voltage Switch

61

Product Category

Product Category

Appearance and operating principle Product structure


General layout
VS1-BYE indoor high voltage vacuum circuit breaker's interrupter and operating device are fixed to the same framework, one in the front and the other at the back, namely the integral layout. With such structural design, operation of the operating device can better fit with the performance required by the closing and trip of interrupter, which can reduce the unnecessary intermediate transmission links, reduce energy consumption and noise, and make the operating characteristics of breaker more reliable. The major galvanic circle is of three-phase floor-type structure. The vacuum interrupter is installed inside the insulating tube vertically; the insulating cylinder is made by epoxy with APG technology, so it can resist creepage well. Such structural design can greatly reduce the accumulation of dust on the surface of interrupter; it not only can protect the vacuum interrupter from the influence of external factors, but also can take on highimpedance state to the voltage effect even in moisted and severely polluted environment. The operating device is of horizontal spring charging type which can charge manually or electrically. The operating device is placed inside the cabinet of the interrupter; the breaker's cabinet can double as the bracket of operating device. The cabinet is divided into five assembly space by four boards to hold the charging part, transmission part, release part and cushion part of the operating device. The operating device also has interlocking functions: a. The breaker can't be closed before the device finishes charging; b. The breaker can only be rocked in and out of the switch cabinet in tripping status; c. The breaker can only be closed or open when it's in the working position or testing position inside the switch cabinet; d. When the breaker is closed for charging, the closing button is locked and can't be pressed. On the panel of the breaker, there is closing and trip indication of breaker, and the charging indication of closing spring, as well as the inserting holes for manual closing and trip button and manual charging handle; the panel can also show the times of breaker operations.
Figure 2 Outline drawing of breaker with the rated current from 1600A to 4000A (phase distance 275mm)
1. Secondary plug ; 2. Charging sign ; 3. Closing button ; 4. Charging handle hole ; 5. Closing-trip sign ; 6. Counter ; 7. Trip button

Schematic wiring diagram


According to customer requirements, we can cancel the tripping prevention coil, add over-current release coil and closing blocking coil. Manual tripping: press the trip button on the faceplate, the closing-trip sign will show the tripping position, meaning that it's open. Electric closing and trip operation After the charging signal is given out, the switch control wiring powers on; after the motor powers on through the control loop, it rotates and drives the extension spring to charge. After the closing spring stores appropriate energy, the limit switch will cut off the motor power and the charging indication will point at the charged position. Closing operation: after the closing coil powers on, the iron core moves to hit the closing interlocking; the closing spring releases energy and the switch will be off; after the closing operation, the closing-trip sign will show the closed position, and under such circumstances the charging device is in free state. Tripping operation: the switch is on; to open it, power on the trip coil; the iron core of coil moves to separate the tripping interlocking; the trip spring releases energy and the switch will be off; after the tripping operation, the closing-trip sign will show the open state.

Use
Operational readiness inspection Check whether the installed base of switch is level and whether the fundamental plane can bear the weight of switch and relevant electrical force; Check whether the connecting line is broken Check whether the switch is mechanically damaged Conduct power frequency withstand voltage test to the switch to check its insulation level. Manual closing and trip operation Manual charging: insert the charging handle from the insert hole of charging handle on the panel to store energy; when the device ticktocks, and the charging sign points to the charging position, it shows the spring device has finished charging.

Product installation and assembly dimension and arrangement of panel

1. Secondary plug ; 2. Charging sign ; 3. Closing button ; 4. Charging handle hole ; 5. Closing-trip sign ; 6. Counter ; 7. Trip button

Manual closing: press the closing button on the panel, the closingtrip sign will show the closed position, meaning that it's closed.

Figure 1 Outline drawing of breaker with the rated current from 630A to 1250A (phase distance 210mm)

62

High & Low Voltage Switch

63

Figure 3 Schematic Wiring Diagram of Control Loop

Schematic wiring diagram

HQ closing electromagnet ; 6. TQ tripping electromagnet ; 7. V1 - V3 rectifier ; 8. CZ air socket ; 9. KO auxiliary relay ;

1. S1 - S4 limit switch ; 2. HK auxiliary switch ; 3. S8, S9 test and working position switch ; 4. M charging motor ; 5.

64

10. R1 divider resistance ; 11. JX line bank

Product Category

Product Category

Maintenance & management


Normally running breaker shall be maintained regularly; clean the dust on the insulation surface, and all moving parts shall be poured with lubricating oil regularly; Check whether the screws are loosened after operating for 2000 times; if screws are loosened, tighten them timely; Check immediately when there are closing or tripping faults; Mechanical features testing and adjustment of the switch shall only be conducted by professionals.

Attachment paper and accessories


Quality certificate Installation and instruction manual Packing list Charging handle, rocking handle (provided according to the amount on order and customer requirements)

Ordering instructions
Please indicate the following items when orders are placed: Model, name and quantity of breaker; Rated operating voltage; Name and quantity of spare parts

Storage
The breaker shall be placed in the room that is dry, ventilated, damp proof, noxious gas proof. If it's placed for a long time, spread lubricating oil to the transmission parts and check whether the environment meets the requirements regularly. The permissible storage period of vacuum interrupter is 20 years.

High & Low Voltage Switch

65

Product Category

Product Category

VW Single-phase Vacuum Circuit Breaker (Designated Sales Region)


Technical parameters
No.
1 2 3 4 5 6 7 8

UVA Vacuum Contactor - Fuse Combination


surge protection. The control equipment is of IC return circuit design which is

Name
Rated voltage Rated current Rated short-circuit breaking current Rated short-circuit making current 1min power frequency withstand voltage Impulse withstand voltage Rated short-circuit current operation times Mechanical endurance

Unit
kV A kA kA kV kV time(s) time(s)

Technical parameters
27.5 630, 1250 25 63 95 200 20 10000

low in power consumption. It meets IEC, BS, AS, JEM and GB standards and is widely used in the world.

Use
It's mainly used in three-phase alternating current 50Hz, 3.6 ~ 12kV power system for start of motor, and closing and open of

Characteristics
The product is developed with the advanced technology of Toshiba K.K. Simple and portable; double-layer structure which can save much more space; With original CV vacuum contactor to realize excellent breaking performance; The contactor is made from special material which can reduce the interception value to the minimum and needs no

transformers and capacitors.

Type specification
Model of UVA high voltage vacuum contactor - fuse combinations
Excitation mode: unsigned: electric maintenance L: mechanical maintenance Operation type: B: rocking in Design serial number: A Rated current: G - 200A; H - 400A Rated voltage: 10: 12kV Design serial number: A Vacuum contactor- fuse combinations

Characteristics
The product is developed with the advanced technology of Toshiba K.K. It adopts high-strength insulation supporters and has large creeping distance; it uses compound insulation technology and the vacuum interrupter is installed inside the insulating boot, and thus it has good insulating property and small size; The major loop system is in T type supporting structure with high intensity. Its vacuum interrupter adopts longitudinal magnetic field arc extinction, and has reliable breaking performance. It's of handcart rocking-in structure and a spring control device

is installed inside; it has both manual charging function and electric charging function, and has stable performance and long service life. There is little noise during the operation of device; during operation, there is no decomposed product and will generate no pollution to environment; It adopts the reliable "Five-Prevention" equipment, and has both mechanical interlocking and electrical interlocking.

Technical parameters
No.
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

Use
It's mainly used in single-phase alternating current 50Hz and 27.5kV railway system for opening and closing load current, overload and short-circuit current.

Item
Rated voltage Rated frequency Rated current of vacuum contactor Rated current of the combinations (fuse) Rated short-circuit breaking current and making current (fuse) Closing Nominal control voltage Trip Allowable fluctuation range of control voltage Closing Operating current (at 100V) Maintenance /trip Making time Trip time Auxiliary contact Parameter of auxiliary contact Operating voltage Thermal current Parameter of auxiliary contact D.C. capacity Motor Maximum load Transformer Weight Applied standard

Unit
kV Hz A A kA V A ms V A W kW kVA kg

Parameters
12 50 400 200 50/125 100-240AC/100-220DC 100 -110,200-220DC 85%~110%85%-110% of nominal control voltage 6 (peak value) 0.13 (average)/4 (peak value) 50-200 20~50 5NO-5NC 48-480 10 60(L/R150ms) 3500 4500 85 IEC62271-106:2003 GB/T 14808-2001

66

High & Low Voltage Switch

67

Product Category
Model description
Operating device: L with closure "In", "out" mode: D: warpping in; M: pushing in Design serial number: A Rated current: G - 200A; H - 400A Rated voltage: 3:3.6Kv, 6:7.2KV Design serial number: A Vacuum contactor- fuse combinations

Product Category

Appearance of UVA Vacuum Contactor- Fuse Combinations

Secondary plug of control loop

UVA-3GAM(L) No. 1 2 3 4 5 6 7 8 9 10 Rated voltage Lightning impulse withstand voltage Rated insulation level 1min power frequency withstand voltage Rated frequency Rated operating current Rated breaking current(fuse) Nominal control voltage Allowable range of control voltage Closing Operating current (100V) Maintemance/trip Making time Trip time Unit UVA-3GAD(L)

UVA-3HAM(L) UVA-3HAD(L)

UVA-6GAM(L) UVA-6GAD(L)

UVA-6HAM(L) UVA-6HAD(L)
Emergency tripping hole

Hz A kA V A Ms

50/60 200 400 200 400 40, 50 AC/DC 110/220 85% - 110% nominal control voltage 4.5 0.1(average)/4.0(trip) 65-80 20-30

Closing and trip indication Counter

Specification

Overall dimension of UVA vacuum contactor - fuse combinations

Insulating cylinder

Primary plug

Contactor (CV)

1. Release 2. Fuse 3. Vacuum interrupter 4. Primary plug 5. Vacuum contactor (CV) 6. Secondary plug 7. Emergent tripping hole 8. Counter 9. Closing and trip indication Figure 6 Overall Dimension Drawing of UVA Vacuum Contactor- Fuse Combinations

68

High & Low Voltage Switch

69

Product Category

Product Category

Low Voltage Switch BYEW1 Series Air Circuit Breaker


Overview

BYEM1 Series Molded Case Circuit Breaker


Overview
electric energy, protect lines and protect the power supply equipment against overload, short circuit and under voltage. Meanwhile, the circuit breaker up to 630A can also be used protect electric motors against infrequent start, overload, short circuit and under voltage. The products comply with GB14048.2, IEC60947-2 standards. The products have such advantages as compact size, high breaking capacity and short flashover (no flashover), which makes them one of the ideal products for the users. The products are applicable in the power distribution network They are applicable in the following working conditions: Temperature is between -5C~+40C, and the altitude of the installation site does not exceed 2000m.

The product is applicable to distribution grid at AC 50Hz, up to rated voltage 380V, 660V and rated current 6300A, to distribute electric energy and protect lines as well as protect power supply equipment from overload, under voltage, short circuit and single phase earthing fault. The product complies with GB14048.2, IEC60947-2 standards. The circuit breaker is compact and small. The main part of the circuit breaker consists of insulation housing, contact system, smart controller, actuating mechanism, motor-driven energy storage mechanism. They are applicable to the following working conditions: Temperature is between -5C~+40C and the altitude of the installation site does not exceed 2000m.
Number of poles

at rated insulation voltage 690V, AC 50Hz, rated working voltage 660V and rated working current up to 800A, so as to distribute

Overall & mounting dimensions for BYEM1-63L, M connections before the barrier (3-pole, 4-pole)

Model description
The dimensions of 3-pole M type or 4-pole type are in bracket

Hole sizes for mounting plate

They are installed in the sites where there are no explosive hazards, conductive dust, metal corrosion and insulation damage possibilities. Frame rated current Inm (A)
2000 3200 6300

Frame rated current Design number Universal circuit breaker Enterprise code

Overall & mounting dimensions for BYEM1-100L, M, H connections before the barrier (3-pole, 4-pole)
Connection terminal blocks before the barrier (options)

Rated current In (A)


630, 800, 1000, 1250, 1600, 2000 2000, 2500, 3200, 4000 4000, 5000, 6300

Rated limit short-circuit breaking capacity Icu (kA) 380V


80 cos=0.2 100 cos=0.2 120 cos=0.2

Rated operating short-circuit Rated short-time withstand breaking capacity Ics (kA) current Icw (kA/s) 380V
65 cos=0.2 80 cos=0.2 100 cos=0.2

690V
50 cos=0.25 65 cos=0.2 ---

690V
50 cos=0.25 50 cos=0.25 ---

380V
50 cos=0.25 80 cos=0.2 100 cos=0.2

690V
40 cos=0.25 50 cos=0.25 --68 for L type 86 for M, H type 86 for L type 104 for M, H type

The height of 4-pole type is equal to that of 3-pole M, H types

Hole sizes for mounting plate

70

High & Low Voltage Switch

71

Product Category
Overall & mounting dimensions for BYEM1-225L, M, H connections before the barrier (3-pole, 4-pole) Overall & mounting dimensions for BYEM1-800L, M connections before the panel (3-pole, 4-pole)
Insulation barrier Connection terminal blocks before the barrier (options) Connection terminal blocks before the panel (options) 86 for L type 103 for M, H type 110 for L type 127 for M, H type

Product Category

The dimensions of 3-ple M type or 4-pole type are in bracket

Hole sizes for mounting plate

Hole sizes for mounting plate 4-pole dimensions are in bracket

Overall & mounting dimensions for BYEM1-400L, M, H connections before the panel (3-pole, 4-pole)
Connection terminal blocks before the panel (options)

Model description
4-pole circuit breaker N pole type code* (A, B, C or D) Usage code: No code for distribution protection; 2 for motor protection Tripping method and accessory code (See Table 1) Pole (3, 4) Code for operation methods: No code for handle operation; P for motor-driven operation Z for rotary handle operation Feature code for breaking capacity: L for standard type; M for comparatively high breaking; H for high breaking capacity Frame rated current (63, 100, 225, 400, 630 or 800) Frame rated Molded case circuit breaker code Enterprise code *4-pole circuit breaker N pole type code:

Hole sizes for mounting plate

A indicates the current tripping unit is not installed at N pole, and N pole is normally closed, which is not opened or closed with the other three poles; B indicates the current tripping unit is not installed at N pole, and N pole is opened and closed with the other three poles; C indicates the current tripping unit is installed at N pole, and N pole is opened and closed with the other three poles; D indicates the current tripping unit is installed at N pole, and N pole is normally closed, which is not opened or closed with the three poles

Overall & mounting dimensions for BYEM1-630L, M, H connections before the panel (3-pole, 4-pole)
Insulation barrier Connection terminal blocks before the panel (options)

Hole sizes for mounting plate

72

High & Low Voltage Switch

73

Product Category
Circuit breaker model BYEM1BYEM1-63M 63L BYEM1100L BYEM1100M BYEM1100H BYEM1225L BYEM1225M BYEM1225H

Product Category

BYEM1LE Series MCCB with Residual Current Protection


Overview
current operation is connected with line voltage. The products comply with latest standards of GB14048.2 and

Appearance

Appendix B. They have high breaking capacity, short flashover, adjustable

Rated current (A) 40C Number of poles Rated insulation voltage Ui (V) Rated working voltage Ue (V) Energized Life cycles De-energized AC660V Rated limit breaking capacity Icu (kA) AC380V AC660V Rated operating breaking capacity Ics AC380V (kA) Flashover distance (mm) W Overall dimensions L H

10,16,20,25,32,40,50,63 3 3, 4 500 380 8000 20000 --25 50 ------18 20 78 135 73.5 78(103) 135(135) 81.5(81.5) 35

16,20,25,32,40,50,63,80,100 3 3, 4 2, 3 690 380, 660 8000 20000 8 10 20 35 50 85 4 5 10 20 0 or 20 92 150 68 35 0 or 50 92(122) 150(150) 86(86) 92 150 86 50

100,125,140,160,180,200,225 3 3, 4 2, 3 690 380, 660 8000 20000 8 10 20 35 50 85 4 5 10 25 0or 50 107 165 86 35 0 or 50 107(142) 165(165) 103(103) 107 165 103 50

rated residual operating current and adjustable delayed operation time. They have the indicating device for the residual breaking, and the device can only be reset when it operates again. The products are equipped with overload, short-circuit and under voltage protection features. They can protect personnel from indirect contact and equipment leakage as well as prevent fire disaster caused by earth-fault current due to equipment insulation damages. When the protective device fails, the leakage circuit breaker with rated residual operating current less than 30mA can also be used as auxiliary protection from direct contact. The leakage circuit breakers are working at the rated working voltage AC400V, 50Hz, and the current range 16~800A. The leakage circuit breakers are monobloc type, and their residual
BYEM1LE-100 overall & installation dimensions

It is simple and safe to install accessories: They adopt the design structure of case-type accessory; During the installation, you only need opening the cover at the sites for accessory installation without opening the main part of the leakage circuit breaker. They are applicable in the following working conditions: Temperature is between -5C~+40C, and the altitude of the installation site does not exceed 2000m. They are installed in the sites where there are no explosive hazards, conductive dust, metal corrosion and insulation damage possibilities.

Circuit breaker model

BYEM1BYEM1BYEM1-400M 400H 400L

BYEM1630L

BYEM1BYEM1- BYEM1BYEM1-800L 800M 630M 630H

Appearance
Insulating barrier Mtg hold (removable) Rated current sensitivity Operating time Earth-leakage indication Test button Trip

Connection before barrier


M5x0.8 screw Breaker

Rated current (A) 40C Number of poles Rated insulation voltage Ui (V) Rated working voltage Ue (V) Energized Life cycles De-energized Rated limit AC660V breaking capacity AC380V Icu (kA) Rated operating AC660V breaking capacity AC380V Ics (kA) Flashover distance (mm) W Overall dimensions L H

3, 4

10 50 5 35

225, 250, 315, 350, 400 3 690 38, 660 7500 10000 10 65 5 42 0 or 100 150 257 107

3, 4

-100 -65 150 257 107

10 50 5 35 182(240) 270(270) 110(110)

400, 500, 630 3 690 380, 660 7500 10000 20 65 10 42 0 or 100 182 270 110

-100 -65 182 270 110

630, 70, 800 3, 4 690 380, 660 7500 10000 10 20 50 5 35 0 or 100 210(280) 280 111.5(114.5) 210 280 111.5 65 10 42

Connection

Trip

Neutral pole

(Bust.Max.=5) Bus drilling for direct connection

(3 pole)

M4 x 0.7 screw or 5 (4 pole)

3 pole

4 pole

Connection after barrier


Mounting panel T.Max=3.2 4 pole 3pole

150(198) 257(257) 107(107)

Insulating tube

M4 x 0.7 screw Insulating tube

The dimensions of 4-pole circuit breakers are in bracket.

M8 Screw

(3 pole)

M4 x 0.7 screw or 5

(4 pole)

74

High & Low Voltage Switch

75

Product Category
BYEM1LE-225 overall & installation dimensions Connection before barrier
Mtg hold Insulating barrier (removable) Rated current sensitivity Operating time Earth-leakage indication Test button Neutral pole (Bust.Max.=7) (3 pole) (4 pole) Bus drilling for direct connection M4 x 0.7 screw or 5 (3 pole) (4 pole) Dilling pian 3 pole Trip Trip Neutral pole 4 pole In<630A Max.=t8 In<630A Max.=t10 Bus drilling for direct connection Trip Connection M8 hexagon socket head cap screw Breaker 100~175A 14~95mm2 200~250A 70~125mm2 Mtg hold Insulating barrier (removable) Rated current sensitivity Operating time Earth-leakage indication Test button

Product Category

BYEM1LE-630, 800 overall & installation dimensions Connection before barrier


Bust In<630A Max.=t8 In<630A Max.=t12
8 at rated current 630A 10 ate rated current 800A

Breaker Bus drilling for direct connection

Trip

(3 pole) M4 x 0.7 screw or 7 Dilling pian (4 pole)

Connection after barrier


Mounting panel T.Max=3.2 4 pole 3pole Connection margin M4 x 0.7 screw Insulating tube M8 Screw (3 pole) Dilling pian M4 x 0.7 screw or 5

Connection after barrier


Connection margin Breaker Mounting panel Insulating tube (4 pole) M6 screw or

BYEM1LE-400 overall & installation dimensions Connection before barrier


Insulating barrier (removable) Rated current sensitivity Operating time Earth-leakage indication Trip Test button Neutral pole (Bust.Max.=8) Bus drilling for direct connection (4 pole) M4 x 0.7 screw or 5 (3 pole) (4 pole) Dilling pian M8 hexagon socket head cap screw Breaker

M6 Mounting Screw (3 pole) (4 pole) Dilling pian

Technical parameters
Quick selection table (Model description)
BYE-Enterprise codes M-Molded case circuit breaker 1-Design code LE-Electronic type leakage circuit breaker Selectable codes for number of poles 3: 3-pole 4: 4-pole Selectable codes for tripping methods 2: Electromagnetic only (instantaneous ) tripping unit 3: Thermomagnetic (duplex) tripping unit Selectable codes for different usages No code for power distribution 2: Motor protection

Mtg hold

Residual current operating features Y: Delay type Rated current F: Non-delay type

M12 Screw (3 pole)

Connection after barrier


4 pole Mounting panel T.Max=3.2 3pole M6 screw or Insulating tube Selectable codes for frame rated current 100, 225, 400, 630, 800 Selectable codes for operation methods P: Motor driven operation Z: Rotary handle operation M6 screw Insulating tube M8 Screw (3 pole) (4 pole) Dilling pian Selectable codes for internal accessories 00: No accessory For other codes, see the internal accessory table for the circuit breaker Breaker Optional type codes for 4-pole circuit breaker (No code for 3-pole): A: the current tripping unit is not installed at N pole, and N pole is normally closed, which is not opened or closed with the other three poles; B: the current tripping unit is not installed at N pole, and N pole is opened and closed with the other three poles; C: the current tripping unit is installed at N pole, and N pole is opened and closed with the other three poles; D: the current tripping unit is installed at N pole, and N pole is normally closed, which is not opened or closed with the three poles Note: Type B is a common type, and other types need special order. Codes for the module with leakage alarming unit: I: When leakage occurs, the leakage alarming module sends the signal. Meanwhile, the circuit breaker releases. II: When leakage occurs, the leakage alarming module sends the signal. But the circuit breaker does not release. (Method II meets specific needs in the market. Users need to take careful consideration before using the function)

Note: If a user does not specify delay type or non-delay type when ordering, we supply delay type products.

76

High & Low Voltage Switch

77

Product Category
Model
Frame current Inm (A) Rated current In (A) Rated insulation voltage Ui (V) Rated working voltage Un (V) Rated frequency (Hz) Number of poles Rated impulse withstand voltage Uimp (V) Flashover distance (mm) Rated limit short-circuit breaking capacity Icu (kA) Rated operation short-circuit breaking capacity Ics(kA) Rated residual operating current In (mA) 0 or 45 0 or 60 50 AC400V 25 Delay Non-delay 100, 300, 500 30,100, 500 100, 300, 500 30, 100, 500 1/2 In 12.5 3000 7000 3000 7000 2000 4000 1500 4000 100, 300, 500 30, 100, 500 100, 300, 500 30, 100, 500

Product Category

BYEM1LE-100
100 10, 16, 20, 25, 32 40, 50, 63, 80, 100

BYEM1LE-225
225 100, 125, 140 160, 180, ,200, 225 690 400 50 3, 4

BYEM1LE-400
400 225, 250, 315 350, 400

BYEM1LE-630, 800
630, 800 400, 500, 630 700, 800

BYEM2Z Molded Case Circuit Breaker


Overview

8000 0 or 100 0 or 100

Rated residual non-operating current Ino (mA) Rated residual short-circuit making (breaking) capacity Im (kA) Operating performance Energized De-energized

The product has long time delay of overload, short time delay of short circuit, instantaneous protection of short circuit and lowvoltage protection functions. Rated working voltage of this product is AC400V, 50Hz and rated current is 16~800A. This product meets the latest standard of GB14048.2 and Appendix F. Controller of the product adopts SCM micro programming technology and can realize three-step protection. Users can set and adjust the three-step protection working current and actuation time according to the load current. The breaker can realize prewarning and overload indication through LED.

Model

Size

A
30 35 44 70

B
129 126 194 243

D
4.5 4.5 7 7

E
22 22 65 66

F
50 62 88.6 81

G
17.6 22 30 44

H
92 90 106.5 115.5

H1
110 110 146.5 155

H2
28.5 24 38 45.3

L
150 165 257 280

L1
132 144 224 243

W
92 107 150 210

W1
60 70 96 140

W2
122 142 198 280

W3
90 105 144 210

J
7 10 12 18

K
100 132.5 228.5 240

BYEM27-100 BYEM27-225 BYEM27-400 BYEM27-800

78

High & Low Voltage Switch

79

Product Category

Product Category

Model description
Rated current Application code: no code for power distribution protection; current motor protection code is 2 Release mode and accessory code (see table 1) Number of poles (3, 4) Code of operation mode: handle operation, no code; Electrical operation P; Rotational controller operation, Z

BYEM6, BYEM6LE Series Miniature Circuit Breaker


Overview Model description
Rated current Usage code C (Power distribution protection) D (Motor protection) Number of poles (1, 2, 3, 4) Frame rated current Design code Molded case circuit breaker Enterprise code

Enclosure bracket class (100, 225, 400, 800) Intelligent type Design serial number Code of plastic casing breaker Corporate code

BYEM6 Series Compact Circuit Breakers are applicable in


BYEM2Z-225 BYEM2Z-400 BYEM2Z-800 630 400, 420, 440, 460, 480, 500, 530, 560, 600, 630 3,4 800 400 6000 7500 10000 20000 65 42 9.6 B 198 257 106.5
o o o o o o o o o o

Type of breaker Rated current(A) Overload long time delay setting current Irl (A) 3,4Number of poles Rated insulation voltage Ui (V) Rated operational voltage Ue (V) Rated impulse withstand voltage Uimp (V) Operating characteristics (times) Electrical endurance Mechanical endurance Free of maintemance Needing maintenance 32

BYEM2Z-100 63 100

working sites at AC 50Hz or 60 Hz, rated working voltage up to 400V, and rated current up to 63A. They are mainly used to protect overload, short-circuit and isolation of lighting, power distribution line and equipment of offices, residence and similar buildings. They can also be used for infrequent switching of lines. The products comply with requirement under IEC60898 and GB10963. BYEM6LE-32 Series Leakage Circuit Breakers are assembled with BYEM6 High Breaking Capacity Compact Circuit Breakers and leakage tripping units. Leakage circuit breakers are used for leakage protection. When someone gets an electric shock or the circuit leakage current exceeds the specified value, the leakage circuit breaker can automatically cut off the power in a very short time to ensure personnel safety and prevent accidents caused by electric leakage. The leakage circuit breaker can also be used for short-circuit and overload protection, and infrequent switching of lines at normal conditions. The products comply with requirements under GB16917.1. Frame rated current
63 63 63 63 63 63

225

400

800 360, 640, 660, 680, 700, 720, 740, 760, 780, 800

32, 36, 63, 65, 75, 100, 125, 140, 200, 225, 16, 20, 40, 45, 70,, 85, 160, 180, 200, 250, 280, 25, 32 50, 55, 80, 95, 225 315, 350, 400 60, 63 90, 100 3, 4 800 400 6000 8000 20000 40000 50 35 5 B 92 150 92
o o o o o o o o o o

3,4 800 400 6000 8000 20000 40000 50 35 5 B 122 107 142 165 90
o o o o o o o o o o

3,4 800 400 6000 7500 10000 20000 65 42 5 B 150 210

Icu (kA) Rated limit breaking capacity Icu (kA) Rated operation breaking capacity Ics (kA) Rated short time withstand current Icw (kA/Is) Use classification Overall dimension W L H Wiring in the front of panel Wiring at the back of panel Push-in type wiring Breaker accessories (optional) Alarm contactor Shunt trip Auxiliary contact Undertension trip Rotational handle operating device Electrical operating device BYEM2Z portable programmer
Note: o indicates that this accessory can be configurated by the breaker

280 280 115.5


o o o o o o o o o o

Rated working voltage(V)


230/400 400 230/400 230/400 400 230/400

Rated short-circuit breaking capacity Number of poles


1, 2 3 4 1, 2 3 4 50, 63

Rated current (A)

Prospective current of test lines (A)


6000 6000 6000 4000 4000 4000

Power factor
0. 65~0. 70 0. 65~0. 70 0. 65~0. 70 0. 75~0. 80 0. 75~0. 80 0. 75~0. 80

1, 3, 6,10,16 20, 25, 32, 40

80

High & Low Voltage Switch

81

Product Category
Rated leakage operating current (omissible for 30mA) Rated current Usage code C (Power distribution protection) D (Motor protection) Number of poles (1N, 2, 3, 3N, 4) Frame rated current (32 or 50) Electronic residual leakage current operation type Design code Molded case circuit breaker Enterprise code

Product Category

BYQ2 Series Dual Power Supply Automatic Transfer Switch


Overview

BYQ2 Series Dual Power Supply Automatic Transfer Switches are applicable for emergency power supply system at AC 50Hz or 60 Hz, rated working voltage up to 400V and rated current up to 630A. When one power supply malfunctions, the products can automatically switch between standard power and standby power without manual operation. The products comply with requirements under GB14048.11. Reliable mechanical interlocking devices and electrical devices are installed between two circuit breakers, which completely avoid the possibility of simultaneous closing of both circuit breakers. They have short-circuit and overload function, as well as automatic switching and smart alarming function for over

voltage, under voltage and phase loss. The smart controller uses SCM as the controlling core. The hardware is simple and powerful, convenient to expand and highly reliable. BYQ2 Series Smart Dual Power Automatic Transfer Switch consists of two sets of 3-pole or 4-pole circuit breakers and their accessories (auxiliary and alarming contacts), mechanical interlocking transmission mechanism, and smart controller. They are divided into integral type and split type. The integral type means that the controller and the actuator are installed on the same base; the split type means that the controller is installed on the cubicle panel and the actuator is installed on the base within the cubicle by the user. The controller and the actuator are connected with a cable about 2m long.

Standard power supply

Standard power supply busbar Standby

Standby power supply busbar

power supply

Electrical operating mechanism

Integral controller Actuating circuit breaker

Load

Load busbar

Signal output terminal

Mounting plate

82

High & Low Voltage Switch

83

Product Category
Standard power supply busbar
Standard power supply Standby power supply

Product Category

Standby power supply busbar

Electrical operating mechanism

Model description
Rated current for the circuit breaker Y: Integral type

Connection socket for split type control

F: Split type 3: 3-pole 4: 4-pole Short circuit breaking capacity level of the circuit breaker (L, M or H) Frame rated current R: Automatic change, automatic recovery S: Automatic change, non-automatic recovery F: Power grid - generators Design code CB Dual Power Automatic Transfer Switch Enterprise code

Actuating circuit breaker

Load

Load busbar

Signal output terminal

Mounting plate

Model
Mechanical life
Standard fuse Standby power supply

BYQ-100/225
5000 1000 6000

BYQ2-400
3000 1000 4000 Non-stop working 120%Ue

BYQ2-630/800
2500 500 3000

Electrical life Total service life Rated working days Over voltage switchover setting value Adjustable range for under voltage switchover setting value

Standard fuse

Standard power supply


Product model Compliant standards Rated working voltage Manufacturing Number

(60%~85%) Ue Continuously adjustable < 4s 0.5~30s Continuously adjustable 0.5~30s Continuously adjustable

Contact switchover time Opening delay t 1 Closing delay t 2

Automatic Transfer Switch Device

RClosing

N Closing

Rated current (6, 10, 16, 20, 25, 32, 40, 50 or 63) Transient features of compact circuit breaker (B, C or D) Number of poles (3 or 4) Compact circuit breaker Design code Dual Power Automatic Transfer Switch Enterprise Code

Number of poles
3P 4P

Rated voltage Ue(V)AC


380V

Rated current In(A)AC


6, 10, 16, 20 25, 32, 40, 50, 63

Rated frequency (Hz)


50/60

Control voltage (V)


220V

Switchover time
1.5~3S

Limit short-circuit breaking capacity (A) /cos ()


6000(6~40A) 4000(50~63A)

Mechanical life (cycles)


10000

84

High & Low Voltage Switch

85

Product Category

Product Category

BYES9 Series Dual Power Supply Automatic Transfer Switch


Overview

Model
Rated current (A) Operating current(A) Rated short-time withstand current(kA) Service life Mechanical Electrical 2P

BYES9-32NA
32

BYES9-40NA
40 3.5 5 8000 3000

BYES9-63NA
63

BYES9-125NA
125

Number of poles Weight(Kg) Operating cycles (cycle/second)

3P 4.7

4P 5.2

2P 5

3P 5.5

4P 6.5 15

2P 5

3P 5.5

4P 6.5

2P 5

3P 5.5

4P 6.5

4.2

Model BYQ2 Series Dual Power Supply Automatic Transfer Switches are applicable for emergency power supply system at AC 50Hz or 60 Hz, rated working voltage up to 400V and rated current up to 630A. When one power supply malfunctions, the products can automatically switch between standard power and standby power without manual operation. The products comply with requirements under GB14048.11. BYES9 Series Smart Dual Power Automatic Transfer Switches consist of the switch and switchover controller. The products are driven by electromagnet, and the switchover controller is powered by AC 220V main power supply and standby power supply. There is no need for additional power. The switch has electrical and mechanical closing indicator to indicate insulation function.
Rated current (A) Operating current (A) Rated short-time withstand current(kA) Service life Mechanical Electrical 3P 16

BYES9-160T
160

BYES9-200T
200 7 35 6000 2000

BYES9-250T
250

BYES9-400T
400

Number of poles Weight(Kg) Operating cycles (cycle/second)

4P 18

3P 18

4P 19

3P 18

4P 20

3P 18.5 10

4P 20.5

3P 19

4P 21

Type specification

Controller model DCU-B 2: 2-pole (Limited to products up to 125A) 3: 3-pole 4: 4-pole type ATS up to 125A, the controller and the switch are connected with aviation socket. NA: Integral type ATS up to 125A (No power generation-start function). Companys internal modelC: Split N: Split type ATS up to 125A, the controller and the switch are connected with cable supplied by the user. T: Two-stage ATS at rated current range from 160A to 400A. Current rating M: Two-stage ATS split type ATS at rated current range from 630A to 800A.

Dual Power Automatic Transfer Switch (PC ATS) Enterprise code

86

High & Low Voltage Switch

87

Product Category

Product Category

Vacuum interrupter (Toshiba brand vacuum interrupter have designaged sales regions.)
Overview

Toshiba vacuum interrupter


Toshiba vacuum interrupter is famous for its advanced technology and high quality in the world and is considered as one of the best kinds of vacuum interrupter in this industry. Since its distribution in 1965, its output has exceeded 300 million, ranking the 1st in the world. Toshiba used to take the vacuum interrupter technology as its core technology, so before the joint venture corporation was established, Toshiba only set up manufacture base of vacuum interrupter in Japan. Toshiba used to take the vacuum interrupter technology as its core technology, so before the joint venture corporation was established, Toshiba only set up manufacture base of vacuum interrupter in Japan. Product guarantee: the product degree of vacuum can be guaranteed for at least 20 years. Reject ratio of degree of vacuum is zero: from 1975 till now, the reject ratio of degree of vacuum complained by customers is zero. The joint venture company will adhere to the busineses concept of Toshiba Group, introduces the advanced manufacturing equipment and production technology of Toshiba Group, and provide high quality TOSHIBA vacuum interrupter for China in strict accordance with the management model of Toshiba Group. In order to ensure the high quality of TOSHIBA vacuum interrupter, main materials including contactor, metal porcelain enclosure, corrugated tube, shield cover, sealing ring and welding mateiral are all imported.

Liaoju brand vacuum interrupter


In 1968, national key defense engineering 6895 project was implemented in Jinzhou, and China's first vacuum interrupter Liaoju vacuum interrupter was produced. In 1986, it introduced the primary sealing-exhaust ceramic vacuum interrupter production line and production technology of Westinghouse, making the manufacturing technlolgy of Liaoju vacuum interrupter reach the world level. In 2002, it presented the new generation U series mini vacuum interrupter; it adopts the new style longitudinal magnetic field rectangular distribution contactor, and optimizes the internal structure of the interrupter through computer aided design; in doing so, the breaking ability and internal insulation of the interrupter all reach a higher level. In 2003, the generator protective circuit breaker with the largest breaking ability in our country passed the full set type tests in Xi'an with 80kA ceramic vacuum interrupter and began commercial mass production. In 2005, 40.5kV built-in shield cover excellent ceramic vacuum interrupter developed into a full series and replaced the exposed shield cover type, becoming the new product of the vacuum interrupter of this grade. It won several prizes including the State Torch Project, State New Product, the Prize for National Key Technology Breakthrough Program, State Excellent Project of Technology Innovation, Liaoning Prize for Scientific Research Achievements, Liaoning Golden Cup Prize for Excellent New Products etc. In 2007, it comprehensively carried out the advanced management model and manufacturing technlolgy of Toshiba Group, and from then on, Liaoju vacuum interrupter entered into a totally new development period again.

88

High & Low Voltage Switch

89

Product Category

Product Category

Product specification reference Interrupter specification


Rated voltage (kV)
12 12 12 12 12 12 36 40.5 40.5 7.2/12 36 0.38 1.14 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12

No.
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44

Interrupter
SVB-10M25E1 SVB-10M32E1 SVB-10M40E1 SVB-10P40E1 SVB-10Q40E1 SVB-10Q50A1 SVB-30P25H SVB-40P32E1 SVB-40P32H SVD-6J SVT-30M TD-0.38/2000-65 TD-1.14/400-8 TD-12/630-16 TD-12/630-16(W) TD-12/630-16A TD-12/630-16C TD-12/630-16C(W) TD-12/630-20F(W) TD-12/630-20G TD-12/630-20J(W) TD-12/630-20L(W) TD-12/630-20T TD-12/630-20U TD-12/630-20UC TD-12/1250-20F(W) TD-12/1250-20J(W) TD-12/1250-20K(W) TD-12/1250-20U TD-12/1250-25C(W) TD-12/1250-25D(W) TD-12/1250-25F(W) TD-12/1250-25G(W) TD-12/1250-25S(W) TD-12/1250-31.5A(W) TD-12/1250-31.5B TD-12/1250-31.5E(W) TD-12/1250-31.5F(W) TD-12/1250-31.5D(W) TD-12/1250-31.5G(W) TD-12/1250-31.5UL(W) TD-12/1250-31.5US TD-12/1600-31.5A(W) TD-12/1600-31.5D(W)

Rated current (A)


1250 1250 1250 2000 3150(4000 requires forced air cooling) 3150(4000 requires forced air cooling) 2000 2000 2000(2500 requires forced air cooling) 630 1250 2000 400 630 630 630 630 630 630 630 630 630 630 630 630 1250 1250 1250 1250 1250 1250 1250 1250 1250 1250 1250 1250 1250 1250 1250 1250 1250 1600 1600

Rated short-circuit breaking current (kA)


25 31.5 40 40 40 50 25 31.5 31.5

Usage
circuit breaker circuit breaker circuit breaker circuit breaker circuit breaker circuit breaker circuit breaker circuit breaker circuit breaker load switch load switch circuit breaker circuit breaker circuit breaker circuit breaker circuit breaker circuit breaker circuit breaker circuit breaker circuit breaker circuit breaker circuit breaker circuit breaker circuit breaker circuit breaker circuit breaker circuit breaker circuit breaker circuit breaker circuit breaker circuit breaker circuit breaker circuit breaker circuit breaker circuit breaker circuit breaker circuit breaker circuit breaker circuit breaker circuit breaker circuit breaker circuit breaker circuit breaker circuit breaker

Supporting switch models

Overview
The product is used in vacuum circuit breakers, vacuum load switches, vacuum contactors, which are widely used in electricity, metallurgy, petrochemical, coal mine, electrified railway, high-rise buildings, urban and rural power grid control center. Executive standard JB/T8738 The product mainly consists of insulation housing, contacts, main shield, sylphon, static conductive rod, electrode, sylphon shield. It mainly includes indoor and outdoor types.

Structural Diagram of a Typical Product

65 8 16 16 16 16 16 20 20 20 20 20 20 20 20 20 20 20 25 25 25 25 25 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5

ZW10 ZW6

ZN28 ZW6 ZN18(VK) ZW8 ZW32 ZN100 ZW32 ZN28 ZN18(VK) ZW12 ZN28 ZN21 ZN18(VK) ZN65(3AH) ZN63(VS1) ZN21 ZN21 ZN28 ZN18(VK) ZN28/ZN63(VS1) ZN65(3AH) ZN63(VS1) ZN21 ZN28/ZN63(VS1)

90

High & Low Voltage Switch

91

Product Category
No.
45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89

Interrupter
TD-12/1600-31.5G(W) TD-12/2000-31.5A(W) TD-12/2000-31.5B(W) TD-12/2000-31.5D(W) TD-12/2000-31.5G(W) TD-12/2500-31.5A(W) TD-12/1600-40S(W) TD-12/2000-40(W) TD-12/2000-40UA(W) TD-12/2500-40S(W) TD-12/3150-40(W) TD-12/3150-40B(W) TD-12/3150-40C(W) TD-12/3150-40F(W) TD-12/3150-40G(W) TD-12/3150-40S(W) TD-12/4000-40(W) TD-12/4000-50(W) TD-12/4000-63A TD-12/6300-80 TD-24/1600-31.5(W) TD-40.5/1600-25(W) TD-40.5/1600-25A(W) TD-40.5/1600-25B TD-40.5/1600-25D TD-40.5/1600-31.5B(W) TD-40.5/2000-31.5(W) TD-40.5/2000-31.5A(W) TD-40.5/2000-31.5C(W) TD-40.5/2000-31.5D TD-40.5/2000-31.5E TD-12/1250-31.5UH TF-12/630-16(W) TF-12/630-20B TF-12/630-20C(W) TF-12/630-20UC TF-27.5/2000-25 TF-40.5/1250-12.5A(W) TF-40.5/1250-12.5B(W) TF-40.5/1250-12.5C(W) TF-40.5/1250-12.5D(W) TJ-7.2/250GB TJ-7.2/400G TJ-12/250 TJ-12/400B

Rated voltage (kV)


12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 24 40.5 40.5 40.5 40.5 40.5 40.5 40.5 40.5 40.5 40.5 12 12 12 12 12 27.5 40.5 40.5 40.5 40.5 7.2 7.2 12 12

Rated current (A)


1600 2000 2000 2000 2000 2500 1600 2000 2000 2000 3150 3150 3150 3150 3150 3150 4000 4000 4000 6300 1600 1600 1600 1600 1600 1600 2000 2000 2000 2000 2000 1250 630 630 630 630 2000 1250 1250 1250 1250 250 400 250 400

Rated short-circuit breaking current (kA)


31.5 31.5 31.5 31.5 31.5 31.5 40 40 40 40 40 40 40 40 40 40 40 50 63 80 31.5 25 25 25 25 31.5 31.5 31.5 31.5 31.5 31.5 31.5 16 20 20 20 25 12.5 12.5 12.5 12.5

Usage
circuit breaker circuit breaker circuit breaker circuit breaker circuit breaker circuit breaker circuit breaker circuit breaker circuit breaker circuit breaker circuit breaker circuit breaker circuit breaker circuit breaker circuit breaker circuit breaker circuit breaker circuit breaker circuit breaker circuit breaker circuit breaker circuit breaker circuit breaker circuit breaker circuit breaker circuit breaker circuit breaker circuit breaker circuit breaker circuit breaker circuit breaker circuit breaker load switch load switch load switch load switch load switch load switch load switch load switch load switch contactor contactor contactor contactor

Supporting switch models


ZN65(3AH) ZN12(3AF) ZN28 ZN21 ZN65(3AH) ZN63(VS1) ZN18(VK) ZN63(VS1) ZN21 ZN28 ZN12(3AF) ZN18(VK) ZN65(3AH) ZN63(VS1) ZN21 ZN28/ZN63(VS1) ZN65(3AH) ZN105 ZN91 ZN12(3AF)/ZN23 ZW37 ZW7 ZN91 ZN91 ZN12(3AF)/ZN23 ZN85(3AV3) ZW7

FZN30 VSP5 FZN16

FZW32

92

High & Low Voltage Switch