Control & Relay Protection Philosophy for 220 KV POPDA Sub Station
A) Bus Bar Configuration 220 KV System: - Two Bus (One Main and One Main cum Transfer bus) 132KV System: - Single Bus 66 KV System: - Two Bus (Two Main bus) Isolator system 220 KV System: - Four isolator configuration (Three Bus isolators and a Line isolator) 132KV System: - Two isolator configuration (One Bus and a Line Isolator) 66 KV System: - Three isolator configuration (Two Bus isolators and a Line isolator) B) Control Voltage 220V DC C) Control & Relay panels Control & protection Panels to be mounted in Yard Kiosk D) PLCC panels PLCC / FOTE Panels to be mounted in Control Room PLCC / FOTE BCU panel to be mounted in Control Room for interface between Control & protection Panels and PLCC Panels, through GOOSE commands E) Nos. of 220 KV Bays Feeder Bay 4 Nos. Transformer Bay 4 Nos. Bus coupler Bay - 1 No Total No. of Bays planned in first phase 9 Nos. Future Bays 02 Nos. Total Bays Planned 11 Nos. Bays to be connected to Bus Bar Protection in first phase - 9 Nos. Bus Bar Protection Control Unit (Central Unit) - 24 Bays Bay Units (Peripheral Unit) - 9 Nos. + 1 No (to be kept as spare) F) Nos. of 132 KV Bays Feeder Bay 2 Nos. 220/132KV Transformer LV Bay 2 No. Total Nos of Bays planned 04 Nos. G) Nos. of 66 KV Bays Feeder Bay 6 Nos. 220/66KV Transformer LV Bay 2 No Station Transformer Bay 1 No. Bus Coupler Bay 1 No. Total Nos of Bays planned 10 Nos.

Page 1 of 5

GETCO / E / 2S-113 / PP - 015 1A / R0 Dt.19.11.2011

Control Philosophy POPDA Sub Station


System 220 KV Bay 132 KV Bay 66 KV Bay Controlling Device to be Adopted Bay Control Unit Bay Control Unit Bay Control & Protection Unit Type of Controlling Device BCU with IEC 61850 Protocol BCU with IEC 61850 Protocol BCPU with IEC 61850 Protocol

Protection Philosophy POPDA Sub Station


A) Feeder Protection Feeder 220 KV Feeders Protection to be Adopted 1 Two Distance Protection [shall be of two different make (i.e. from different manufacturers) or of same make with two different platforms with same specifications] -Main-I Protection & -Main II Protection 2 Two Stage Over Voltage Protection - Stage I - Stage II 3 Local Breaker Backup (LBB) Protection. 1 2 3 Type of Relay Numerical Relay with IEC 61850 Protocol

Integrated in Main I & Main II Protection

132 KV Feeders

132 KV Feeders (Short Lines)

Integrated in Main I Protection and Bus Bar protection Distance Protection Numerical Relay with IEC 61850 Protocol Directional O/C & E/F Numerical Relay with IEC protection (Backup protection) 61850 Protocol Local Breaker Backup (LBB) Integrated in Distance Protection. protection and Backup protection Line Differential Protection* Numerical Relay with IEC with inbuilt fault locator 61850 Protocol. *Note:End to end communication for Differential relays will be through Fiber Optic. Directional O/C & E/F Numerical Relay with IEC protection (Backup protection) 61850 Protocol Local Breaker Backup (LBB) Integrated in Line Differential Protection. protection and Backup protection Directional O/C & E/F Integrated in Bay Control & Protection Protection Unit (BCPU) with IEC 61850 Protocol Local Breaker Backup (LBB) Integrated in BCPU Protection.

2 3

66 KV Feeders

Page 2 of 5

GETCO / E / 2S-113 / PP - 015 1A / R0 Dt.19.11.2011

B) Power Transformer Protection Equipment 220/66 KV Transformer Protection to be Adopted 1 Differential Protection 2 Restricted Earth Fault Protection (on HV & LV side) 3 Directional O/C & E/F Protection (HV side) 4 Directional O/C & E/F Protection (LV side) 5 Over Fluxing Protection 6 Local Breaker Backup (LBB) Protn. - 220 KV side Type of Relay Numerical Relay with IEC 61850 Protocol Numerical Relays with IEC 61850 Protocol Numerical Relays with IEC 61850 Protocol Integrated in Bay Control & Protection Unit (BCPU) with IEC 61850 Protocol Integrated in Differential Protection

-Integrated in Differential Protection and Bus Bar protection

- 66 KV side 7 Buchholz Relay

10

11

12

220/132 KV Transformer

1 2

- Integrated in BCPU Integrated in Transformer. Auxiliary relay in protection panel. Pressure Relief Device Integrated in Transformer. Auxiliary relay in protection panel. Oil & Wdg. Temp. Alarm & Integrated in Transformer. Auxiliary relay in protection Tripping panel. OLTC Oil Surge Relay Integrated in Transformer. Auxiliary relay in protection panel. Oil Level Low Alarm Integrated in Transformer. Auxiliary relay in protection panel. Transformer Cooling Troubles Integrated in Transformer. Auxiliary relay in protection panel. Differential Protection Numerical Relay with IEC 61850 Protocol Restricted Earth Fault Numerical Relays with IEC Protection 61850 Protocol (on HV & LV side) Directional O/C & E/F Numerical Relays with IEC Protection 61850 Protocol (HV & LV side) Integrated in Differential Over Fluxing Protection Protection

Page 3 of 5

GETCO / E / 2S-113 / PP - 015 1A / R0 Dt.19.11.2011

5 Local Breaker Backup (LBB) Protn. - 220 KV side

-Integrated in Differential Protection and Bus Bar protection - Integrated in Dir. O/C & E/F protection Integrated in Transformer. Auxiliary relay in protection panel. Integrated in Transformer. Auxiliary relay in protection panel. Integrated in Transformer. Auxiliary relay in protection panel. Integrated in Transformer. Auxiliary relay in protection panel. Integrated in Transformer. Auxiliary relay in protection panel. Integrated in Transformer. Auxiliary relay in protection panel. Numerical Relay with IEC 61850 Protocol Integrated in Bay Control & Protection Unit (BCPU) with IEC 61850 Protocol Integrated in BCPU Transformer. in protection Transformer. in protection Transformer. in protection Transformer. in protection Transformer. in protection

- 132 KV side 6 Buchholz Relay

7 Pressure Relief Device

8 Oil & Wdg. Temp. Alarm & Tripping 9 OLTC Oil Surge Relay

10 Oil Level Low Alarm

11 Transformer Cooling Trouble

66/11 KV Transformer

1 Differential Protection 2 Non Directional O/C & E/F Protection - 66 KV side 3 Local Breaker Backup (LBB) Protection. 4 Buchholz Relay

Integrated in Auxiliary relay panel. Pressure Relief Device Integrated in Auxiliary relay panel. Oil & Wdg Temp. Alarm & Integrated in Tripping Auxiliary relay panel. OLTC Oil Surge Relay Integrated in Auxiliary relay panel. Integrated in Oil Level Low Alarm Auxiliary relay panel.

C) Bus Coupler Protection 220 KV Bus coupler

1 Non Directional O/C & E/F Protection 2 Local Breaker Backup (LBB) Protection.

Numerical Relay with IEC 61850 Protocol Integrated in Non Dir. O/C & E/F Protection and Bus Bar protection.

Page 4 of 5

GETCO / E / 2S-113 / PP - 015 1A / R0 Dt.19.11.2011

66 KV Bus coupler

1 Non Directional O/C & E/F Protection 2 Local Breaker Backup (LBB) Protection.

Integrated in Bay Control & Protection Unit (BCPU) with IEC 61850 Protocol Integrated in BCPU

E) Bus Bar Protection 220 KV Bus bar

1 Bus Differential Protection Numerical Relay with IEC (Single scheme) 61850 Protocol 9 Bays, Extendable up to 24 Bays (i. e. Control Unit - 24 Bays) F) Disturbance Recorder & Event Loggers Integrated feature of protective relays is used to provide the information about the Disturbance and to log the events. G) GPS based Time Synchronizing Equipment 220 KV Sub station is to be provided with IEC 61850 compatible Global Positioning System based Time Synchronizing Equipment to synchronize all the protections.

Page 5 of 5