Documente Academic
Documente Profesional
Documente Cultură
8/28/2011
Protection Coordination AGAIN? Its been already well covered by many studies and books...
Introduction
8/28/2011 Primax Technologies Inc. 2
Very simple: 99% of all available literature and standards are about AC applications. Very few cover DC faults.
Introduction
8/28/2011 Primax Technologies Inc. 3
In this presentation, Well focus on Fault (short circuit) coordination assuming that overload protection is much easier to define and manage. Challenge Better understand the whole DC backup system fault behaviour in order to get to a conclusion for safe and reliable solution.
Introduction
8/28/2011 Primax Technologies Inc. 4
In typical DC backup systems multiple sources of energy are: connected in parallel simultaneously contributing into the fault Each has different time constant and amplitude Fault effect reflected on AC mains must be taken in consideration. Ex. 2 chargers, 1 or more batteries, inductive loads, fully charged capacitors....
Rational
8/28/2011 Primax Technologies Inc. 5
Once breaking current of each source is defined, one has to refer to the country standard to specify the required components IEC std ratings and requirements may vary from CSA, UL, IEEE, NFPA...
Rule
8/28/2011 Primax Technologies Inc. 6
Fuses, circuit breakers, switches, bus bars, cables and other equipment need to operate safely and reliably during fault: Breakers and Fuses Need to open SELECTIVELY Cables, switches, bus bars... Need to WITHSTAND the fault energy
Bottom line
8/28/2011 Primax Technologies Inc. 7
For the purpose of this discussion we define the following: Fault: refers to a very low impedance path created when both polarity conductors are shorted.
Failure: refers to over-current: Ex. Failing load, leakage in battery or DC source has lost regulation
Basics
8/28/2011 Primax Technologies Inc. 8
During fault evolution: System voltage decays gradually. The decay rate is related to impedance rate-of-change of all parallel sources over the period of time before that protection devices open. This calculation is less accurate than the initial fault current.
At the occurrence of a fault, a badly coordinated protection device may lead to: Device failure: Circuit breaker contacts may weld during opening, so the fault is not interrupted
Explosion: the device will explode due to the energy available during the fault arcing. Fire: due to the arc ignition of material during the contact opening Injury or death: Operators will be operating in unsafe environment. Note: Arc flash hazard level is directly proportional to the duration of the arc fault.
Effects
8/28/2011 Primax Technologies Inc. 10
To define minimum protection fault current ratings, we need to evaluate the contribution in the fault of each of the DC components
Energy sources
8/28/2011 Primax Technologies Inc. 11
Typical layouts
8/28/2011 Primax Technologies Inc. 12
Typical layout
8/28/2011 Primax Technologies Inc. 13
Redundant layout
8/28/2011 Primax Technologies Inc. 14
Depending on the battery technology, plate thickness and number, specific gravity (in the case of Lead acid batteries) available fault current may vary. Check with battery manufacturers for the exact fault current. Time constant: consider 10ms
Battery
8/28/2011 Primax Technologies Inc. 20
Typical 350AH battery fault current at its terminals: VLA 0.33 thick Flat calcium plate battery with 1.215 SG: 3200A
Tubular VLA 0.35 thick plate battery with 1.215 SG: 3400A AGM VRLA : 4361A Gel VRLA: 3750A Ni-Cd Medium performance: 3200A
Battery example
8/28/2011 Primax Technologies Inc. 21
Filter Capacitors
8/28/2011 Primax Technologies Inc. 22
0,008 0,016
AC mains impedance Power transformer impedance Inductive filter design Other series components
As a rule of thumb take 15-20 times the full current rating time constant 25ms Ex. 500A battery charger with a 3.5% Z transformer impedance may deliver up to 10 000A during a short circuit until its own protection gets into action to interrupt.
Charger/rectifier
8/28/2011 Primax Technologies Inc. 24
Main concern is DC motors: They operate switchgear, turbine lube pumps During deceleration, motors act as a generators contributing in the short circuit.
-
Consider that all motors are connected and running at the time of the fault Typical motor armature has large L/R time constant 20-60ms lower di/dt longer time to clear protection Rule of thumb: Use 4 times of running FLA
Inductive loads
8/28/2011 Primax Technologies Inc. 25
Its not bad to have high fault availability from the source to efficiently perform selective clearance. So if the protection fuse or breaker has larger I2t than what the source can provide, then this protection cannot clear its load fault. Ex. Switchmode power supplies provide fast current limiting and current foldback feature leading to a challenge in clearing faults.
Note
8/28/2011 Primax Technologies Inc. 26
Fuse or circuit breaker? Both provide over-current, short circuit protection, selective coordination and arc flash protection. Breakers can provide remote monitoring, adjustability, reset and control. Semiconductor fuses for ex. can provide subcycle fault protection and long term overload capacity
Protection
8/28/2011 Primax Technologies Inc. 27
DC Interrupting KA Flexibility (optional features) Adjustable Resettable Reliability (maintenance) Arc flash protection
Fuse data
8/28/2011 Primax Technologies Inc. 29
HKD400 HJD250
At first, one can think that protection is perfect: 250A CB is fed from 400A main CB!!
Case: DC protection coordination
8/28/2011 Primax Technologies Inc. 34
Breakers coordination
8/28/2011 Primax Technologies Inc. 35
3500ASC
7250ASC
7250ASC
22kADC breakers X
To Inverter
Case
8/28/2011 Primax Technologies Inc. 36
Soft start
If fault occurs during the soft start period of the rectifiers, available currents can be limited to lower value and chargers might shut down.
Connection cables
Interconnecting cable impedance reduces the fault current. This depends on their material, cross section and length. In general, battery interconnecting cable voltage drop is accounted in the short circuit capabilities of the batteries. Ex. 4/0-259 strands copper cable has a DC resistance of 0.15 /km.
IEEE 946: Recommended Practice for the Design of DC Auxiliary Power Systems for Generating Stations
IEEE 1375: Guide for the Protection of Stationary Battery Systems IEEE 1584 empirical equations are used to calculate arc-flash levels
ANSI/IEEE C37.40 (1993), "Standard Service Conditions and Definitions for High-Voltage Fuses, Distribution Enclosed Single-Pole Air Switches, Fuse Disconnecting Switches, and Accessories"
IEC 60909: Short-circuit currents in three-phase-a.c. systems IEC 60947: Low-voltage switchgear and control gear IEC 60127 family: requirements applicable to fuses
UL 489 and CSA 22.2-5-09 Harmonized Standards: Molded-Case Circuit Breakers, Molded-Case Switches and Circuit-Breaker Enclosures
During faults, DC system components response will be non linear, resulting into complicated behaviour. Consequently, rule of thumb and past experience might be needed to define breaking currents.
Conclusion
8/28/2011 Primax Technologies Inc. 39
However, in special or large applications, Rules of thumb might lead to overestimated values affecting the size and cost of the installation. So, in this case, more accurate assumptions and calculations must be made.
Conclusion
8/28/2011 Primax Technologies Inc. 40
Take all precautions to properly define your equipment protection and selectivity: ASK FOR
Fault capabilities of all connected energy sources Require professionals with relevant experience and background to help
Conclusion
8/28/2011 Primax Technologies Inc. 41
QUESTIONS?
8/28/2011
42
Thank you !
8/28/2011
43