Sunteți pe pagina 1din 12

Power Transmission and Distribution

123 / 145 kV Air Insulated Substation

Simover C

Siemens movable circuit breaker - Compact solution

PTD H 2 E1/0605_E50105_W0048_U090_Description_SimoverC.doc

Page 1/12

Power Transmission and Distribution

HERAUSGEGEBEN VON: PUBLISHED BY: SIEMENS AG POWER TRANSMISSION AND DISTRIBUTION GROUP HIGH VOLTAGE SUBSTATIONS DIVISION PTD H 2 D-91050 ERLANGEN

Bei Rckfragen:

TEL.: FAX:

+49 9131 7 33642 +49 9131 7 31858

nderungen vorbehalten. Alle Rechte vorbehalten, insbesondere (auch auszugsweise) die des Nachdrucks, der Wiedergabe durch Kopieren oder hnliche Verfahren. Zuwiderhandlungen verpflichten zum Schadensersatz. Alle Rechte vorbehalten, insbesondere fr den Fall der Patenterteilung oder GM-Eintrag. Subject to change. All rights, including rights of translation, reproduction by printing, copying or similar methods, even of parts are reserved. Offenders are liable to the payment of damages. All rights are reserved in the event of the grant of patent or registration of a utility model or design.

Stand: 06.2006 Erstellt: PTD H 2 E1 Freigabe: PTD H 2 E

Lingner Nhrig

PTD H 2 E1/0605_E50105_W0048_U090_Description_SimoverC.doc

Page 2/12

Power Transmission and Distribution

1 Table of contents

1 2 3 4 5 6
6.1 6.2 6.3 6.4 6.5 6.6 6.7

TABLE OF CONTENTS DESCRIPTION FUNCTION THE ADVANTAGES IN ONE VIEW TECHNICAL DATA SIMOVER C MODULE DESCRIPTION
Circuit breaker Current transformer Ruhrtal Contact system Built-on Earthing switch mounted at instrument transformer (principle arrangement) Steel structure with driving unit Local control cubicle Transportation vehicle

3 4 4 5 6 7
8 8 9 9 10 11 11

MAINTENANCE

12

PTD H 2 E1/0605_E50105_W0048_U090_Description_SimoverC.doc

Page 3/12

Power Transmission and Distribution

2 Description
For 123 and 145 kV substations with single busbar system a suitable compact alternative is the SimoverC arrangement (Siemens movable circuit breaker). In this kind of switchgear busbar- and outgoing disconnector become inapplicable (switchgear without disconnectors). A common steel frame is the bases for all components necessary for a reliable operation. The movable circuit breaker contains the following mainly type tested standard components:

Circuit breaker type 3AP1 Disconnector contact system DBF Instrument transformer for protection- and measuring purposes Local control system Earthing switch (OHL-connection bays)

Within the client receives all components which are needed for the full function of the Simover C from one source, thus extra orders have become inapplicable. As a result the coordination also takes considerably less time. All systems are pre-assembled as much as possible. So the movable circuit breaker can be mounted efficient and faultless with the help of the installation instructions at the construction site.

3 Function
The isolating distance is reached with the moving of the circuit-breaker on the swingstructure, similar to the well-known withdrawable-unit design technique of medium voltage switchgears. In disconnected position, busbar, circuit-breaker and outgoing circuit are separated from each other by a good visible isolating distance. A drive unit ensures the uninterrupted constant moving motion to the both end positions. The circuit-breaker can only be operated in the ON-position. Mobility with switched-on circuit breaker is impossible. A faulty moving motion, which would be equal to operating a disconnector under load, is interlocked. Also with a possible malfunction of the position switch, respectively travel interruptions between disconnected position and operating position, the operation of the circuit-breaker is stopped.

PTD H 2 E1/0605_E50105_W0048_U090_Description_SimoverC.doc

Page 4/12

Power Transmission and Distribution

4 The advantages in one view


Reduction of total costs compared with the conventional switchbay design. Due to the fact that the control cubicle is directly mounted onto the supporting frame with local operation, interlocking and protection devices, the movable circuit breaker is on principle with a auxiliary supply ready for operation. Because the control cubicle is located at operation operation/control of the movable circuit breaker is possible. height, a trouble-free

An eventually necessary modernisation of the control room is not really necessary because of the integrated control cubicle and can occur at a later point of time. The assembling can be done by the user himself at site. No special erector is needed only the final commissioning and adjustment of the contact system has to be done according to installation instructions. A reduction of required space up to approximately 50% compared with conventional switchbays is achieved because of the compact construction of the movable circuit breaker. The application as an indoor switchbay is possible. Short installation time needed at the construction site because of the pre-assembling at factory. Short terms of delivery because of standardised design as well as using standard type tested components. Because of standard components like circuit breaker 3 AP1 FG / FI no special education for the local staff is necessary

PTD H 2 E1/0605_E50105_W0048_U090_Description_SimoverC.doc

Page 5/12

Power Transmission and Distribution

5 Technical data
Rated Voltage: Rated lightning impulse withstand voltage: Rated current: Short circuit current Rated peak withstand current: Auxiliary voltage (Heater): Control voltage: Drive unit: Creepage distance: Max. Altitude Ambient temperature range: 145 kV 650 kV 1600 A 40 kA, 3 s 108 kA 230 V AC, single phase 110 V DC (others on request) 400/230 V AC 25 mm / kV < 1000 m -25 C / + 40 C

PTD H 2 E1/0605_E50105_W0048_U090_Description_SimoverC.doc

Page 6/12

Power Transmission and Distribution

6 Simover C module description

Each module of the movable Circuit breaker SimoverC consists of: Section 6.1 6.2 6.3 6.4 6.5 6.6 Quantity 1 pc. 3 pcs 1 set 1 set 1 set 1 pc 1 set 3 pcs 1 set 1 set Description 145 kV Circuit Breaker 3AP1FI-145 kV with 1 spring operating mechanism and suitable for single and three phase autoreclosing Current transformer e.g Trench, IOSK 145 or similar Ruhrtal Contactsystem Built-on earthing switch, motor or manual operated, manufacturer Ruhrtal Motive unit Local control cubicle with all necessary equipment for the electrical controlling and electrical interlocking. Position switches (magnetic) Post insulators C6-650 Tubular Busbar conductors and connectors Steel structures and fixing material

PTD H 2 E1/0605_E50105_W0048_U090_Description_SimoverC.doc

Page 7/12

Power Transmission and Distribution

6.1

Circuit breaker

6.2

Current transformer

PTD H 2 E1/0605_E50105_W0048_U090_Description_SimoverC.doc

Page 8/12

Power Transmission and Distribution

6.3

Ruhrtal Contact system

6.4

Built-on Earthing switch mounted at instrument transformer (principle arrangement)

PTD H 2 E1/0605_E50105_W0048_U090_Description_SimoverC.doc

Page 9/12

Power Transmission and Distribution

6.5

Steel structure with motive unit and high voltage equipment

PTD H 2 E1/0605_E50105_W0048_U090_Description_SimoverC.doc

Page 10/12

Power Transmission and Distribution

6.6

Local control cubicle

6.7

Transportation vehicle

If required a transportation vehicle can be provided. The Circuit Breaker can be moved from the closed position towards the open position and further to spot the CB on the support of the vehicle. After moving the motive unit back to closed position the CB can be lowered and move away on the vehicle. The shut-down of the busbar is not required. For moving a plain surfaced access way is desirable. If there is gravel or another surface a temporary road way system (e.g. perforated steel panels) can be used.

PTD H 2 E1/0605_E50105_W0048_U090_Description_SimoverC.doc

Page 11/12

Power Transmission and Distribution

7 Maintenance
All equipment is designed and manufactured for highest reliability with low-maintenance and a use under severe operating conditions. The effort on maintenance depends on the locations of installation. In a clean environment allows a perfect operation above several years. A high polluted location requires more frequent maintenance work. The maintenance schedule for normal environment conditions: A X X X X X X X X
A Checks
1)

B Functional test Tightening of bolts

Maintenance service General visual inspection of all components

Interval 2 years 2 years 2 years 2 years1) 2 years 2 years1) 2 year1) 5 years1)

Greasing of all link joints of the motive unit Cleaning and degreasing of all insulators Cleaning and degreasing of main contacts system and new greasing Cleaning and new greasing of spindles Draining of gear oil, cleaning acc. to manufacturer description and refilling
B Maintenance

Maintenance intervals 2 years or 2000 operating cycles

For the Circuit breaker please consider the maintenance schedule of the manufacturer.

PTD H 2 E1/0605_E50105_W0048_U090_Description_SimoverC.doc

Page 12/12

S-ar putea să vă placă și