Dear Sathiah, Attached Micom P633 configuartion. Download this new configuration into the relay.

Connection for Micom P633 relay mentioned below : 1) Take out the down green colour connector from the rear side of relay 2) Connect Red wire on Point 1. 3) Short Point 1 to 4. 4) Connect Black colour wire on point 2. 5) Short point 2 with point 5 6) Terminate this two Red and Black colour wire on a TB located on top of the panel. Connection for Micom P442 relay : sk4 1) Take a Nine pin Male port. Nine numbers will be mentioned on both side of the pin. 2) Connect a red wire on no.4 pin 3) Connect a black colour wire on no.7 pin. 4) Terminate these two wire on a TB on the rear side of the panel. Bus wiring in between panels : 1) Now loop all red colur wire by a bus wire in these three panel 2) Loop all black colour wire by a bus wire in these three panel. Connection Between one end of panel and RS485/RS232 Converter. 1) Measure the Cable lenght required between PC and one end of the panel. 2) Take a two core cable of Red and Black colour wire. 3) Take a 9 Pin RS 232 Point 4) Connect Red colour wire on No.2 Point. 5) Short No.2 point with No.4 point on this 9 pin female point. 6) Connect Black colour wire on No.6 Point. 7) Short No.6 point with No.8 point on this 9 pin female point. 8) Connect this female point on the RS485/RS232 conver where it is mentioned PS485 on the converter. 9) Other side of the wire is open. Connect Red colour wire to the TB where Red colour

wire from the relay is terminated. 10) Connect Black colour wire to the TB where Black colour wire from the relay is terminated. Connection between RS485/RS232 converter and PC. 1) Take RS232 straight cable and connect PC with converter. The cable which you are using to download setting of relay from from front port of relay to your laptop is a RS 232 straight cable. 2) Load Micom S1 on the PC and now you can ectract settings and DR from the rear port of the relay. Address of the relay mentioned below: Micom P633 is address 1 P442 power grid is address 2 P442 power grid 4 is address 3

We checked up with project management and they informed me that RS485/RS232 converter has been supplied. Check up with the customer. If you have any doubt plase contact me.

Regards Sisir Nayak Automation Support-DCS AREVA T&D INDIA LIMITED Ph: +91 44 22648404

All relay communication with RS 485/RS232 converter


1) Take a 9 Pin female port 2) Connect Red colour wire on No.2 Point. 3) Short No.2 point with No.4 point on this 9 pin female point. 4) Connect Black colour wire on No.6 Point. 5) Short No.6 point with No.8 point on this 9 pin female point. 6) Connect this female point on the RS485/RS232 conver where it is mentioned PS485 on the converter. KITZ 101 INTERFACE

1)From relay to KITZ 101 two wire (red & block) connected with 1&2 terminal in KITZ 101 side 2)from KITZ 101 to PC KITZ 101 side 25 pin female port PC side 9 pin female port 2----------------------------------------------2 3----------------------------------------------3 7----------------------------------------------5