Surge Protection

Surge Protection

SG13309

SG11309

Surge Protection
SPD Class B
SG13005

Impulse Current Iimp (10/350)s

Type Designation

Article No.

Units per package

Lightning current arresters SPI


No decoupling necessary, if arrester class C with Uc = 460 V are used for combination 35kA 50kA 100kA L - (PE)N N - PE N - PE SPI-35/440 SPI-50/NPE SPI-100/NPE 263137 263138 263139 6 / 120 2 / 120 1 / 60

SPI-35/440

Lightning current arrester Sets, Lightning protection classes I, II, III, IV


Description
SG14605

Type Designation

Article No.

Units per package

SPD Class B, SPI


TN-C-Set TN-S/TT-Set 3-pole 3+1-pole SPI-35/440/3 SPI-3+1 267487 267488 1 / 40 1 / 20

SPI-3+1

Lead-through terminal for SPI


SPB-D-125 248145 2 / 120

SPD Class B+C


SG27112

Impulse Current Iimp (10/350)s PHASE OUT TYPE

Type Designation

Article No.

Units per package

Lightning current arrester - surge arrester SPBT12


12.5kA 100 kA L - (PE) N N-PE SPBT12-280/1 SPBT12-NPE100 158306 158307 12 / 120 1 / 60

SPBT12-280/1

Lightning current arrester - surge arrester Sets, Lightning protection classes III, IV
Description Type Designation Article No. Units per package

SG29612

SPD Class B+C, SPBT12


Without remote indication TN-S/TT-Set TN-S-Set TN-C-Set TN-S-Set TN-S/TT-Set TN-S/TT-Set 1+1-pole 2-pole 3-pole 4-pole 3+1-pole 3+1-pole SPBT12-280-1+NPE SPBT12-280/2 SPBT12-280/3 SPBT12-280/4 SPBT12-280-3+NPE SPBT12-280-3+NPE/BB 158308 158309 158330 158331 158332 158333 1 / 40 1 / 60 1 / 40 1 / 30 1 / 20 1

SPBT12-280/3

PHASE OUT TYPE With remote indication


SG10407

TN-S/TT-Set TN-S/TT-Set

1+1-pole 3+1-pole

SPBT12-280-1+NPE-AX SPBT12-280-3+NPE-AX

158334 158335

1 / 30 1

Accessories Auxiliary switch for SPBT12-280 Busbar


SPBT12-280-3+NPE-AX

ASAUXSC-SPM ZV-KSBI...

131785

4 / 120

Surge Protection
Lightning current arrester - surge arrester Sets, Lightning protection classes I, II, III, IV
Description Type Designation Article No. Units per package

SG14905

SPD Class B+C, SP-B+C/


TN-C-Set TN-S/TT-Set 3-pole 3+1-pole SP-B+C/3 SP-B+C/3+1 267489 267510 1 1

Accessories Auxiliary switch for SP-B+C


SP-B+C/3

ASAUXSC-SPM

131785

8 / 80

Surge Protection
SPD Class C
Max. Cont. Op. Volt. UC In (8/20)s
U1302

Type Designation

Article No.

Units per package

PHASE OUT TYPE

Surge arrester SPC-E


75VAC 130VAC 175VAC 280VAC 335VAC 385VAC 460VAC 580VAC N-PE 260VAC 15kA 20kA 20kA 20kA 20kA 20kA 20kA 20kA 30kA SPC-E-75 SPC-E-130 SPC-E-175 SPC-E-280 SPC-E-335 SPC-E-385 SPC-E-460 SPC-E-580 SPC-E-N/PE 248148 248149 118920 248150 248151 248152 248153 248154 248157 12 / 120 12 / 120 12 / 120 12 / 120 12 / 120 12 / 120 12 / 120 12 / 120 12 / 120

SPC-E-280 PHASE OUT TYPE


SG13109

Plug-in surge arrester SPC-S


Insert 1-pole
Insert 75VAC Insert 130VAC Insert 175VAC Insert 280VAC Insert 335VAC Insert 385VAC Insert 460VAC Insert 580VAC Insert N-PE 260VAC 15kA 20kA 20kA 20kA 20kA 20kA 20kA 20kA 30kA SPC-S-15/75 SPC-S-20/130 SPC-S-20/175 SPC-S-20/280 SPC-S-20/335 SPC-S-20/385 SPC-S-20/460 SPC-S-20/580 SPC-S-N/PE 248158 248159 248160 248161 248162 248163 248164 248165 248166 4 / 120 4 / 120 4 / 120 4 / 120 4 / 120 4 / 120 4 / 120 4 / 120 4 / 120

SPC-S-20/280

Base 1- to 4-pole
SG14802

Base 1-pole Base 1+1 2-pole Base 2-pole Base 3-pole Base 4-pole Base 3+1 4-pole

SPC-S-S1 SPC-S-S2-1+1 SPC-S-S2 SPC-S-S3 SPC-S-S4 SPC-S-S4-3+1

248167 248201 248168 248169 248170 248171

12 / 120 6 / 60 6 / 60 4 / 40 3 / 30 3 / 30

SPC-S-S4-3+1 PHASE OUT TYPE


U1202

Plug-in surge arrester SPC-S, 1- to 4-pole


Complete (2- and multi-pole surge arresters are supplied with busbar)
1-pole 1-pole 2-pole 1-pole 2-pole 3-pole 4-pole 1-pole 2-pole 3-pole 4-pole 1-pole 2-pole 3-pole 4-pole 1-pole 2-pole 3-pole 4-pole 1-pole 1+1p 3+1p 3+1p 130VAC 175VAC 175VAC 280VAC 280VAC 280VAC 280VAC 335VAC 335VAC 335VAC 335VAC 385VAC 385VAC 385VAC 385VAC 460VAC 460VAC 460VAC 460VAC 580VAC 1x20kA 1x20kA 2x20kA 1x20kA 2x20kA 3x20kA 4x20kA 1x20kA 2x20kA 3x20kA 4x20kA 1x20kA 2x20kA 3x20kA 4x20kA 1x20kA 2x20kA 3x20kA 4x20kA 1x20kA SPC-S-20/130/1 SPC-S-20/175/1 SPC-S-20/175/2 SPC-S-20/280/1 SPC-S-20/280/2 SPC-S-20/280/3 SPC-S-20/280/4 SPC-S-20/335/1 SPC-S-20/335/2 SPC-S-20/335/3 SPC-S-20/335/4 SPC-S-20/385/1 SPC-S-20/385/2 SPC-S-20/385/3 SPC-S-20/385/4 SPC-S-20/460/1 SPC-S-20/460/2 SPC-S-20/460/3 SPC-S-20/460/4 SPC-S-20/580/1 SPC-S-1+1 SPC-S-3+1 SPC-S-3+N/PE 248188 248189 248190 248172 248173 248174 248175 248176 248177 248178 248179 248180 248181 248182 248183 248184 248185 248186 248187 248191 248192 248193 115795 12 / 120 12 / 120 1 / 60 12 / 120 1 / 60 1 / 40 1 / 30 12 / 120 1 / 60 1 / 40 1 / 30 12 / 120 1 / 60 1 / 40 1 / 30 12 / 120 1 / 60 1 / 40 1 / 30 12 / 120 1 / 60 1 / 30 1 / 30

SPC-S-20/280/3

Surge Protection
NEW
SG14902

Plug-in surge arrester SPCT2


Insert 1-pole
Insert 75VAC Insert 130VAC Insert 175VAC Insert 280VAC Insert 335VAC Insert 385VAC Insert 460VAC Insert 580VAC Insert 260VAC 20kA 20kA 20kA 20kA 20kA 20kA 20kA 20kA 30kA SPCT2-075 SPCT2-130 SPCT2-175 SPCT2-280 SPCT2-335 SPCT2-385 SPCT2-460 SPCT2-580 SPCT2-NPE60 167577 167582 167587 167592 167597 167602 167607 167612 167617 4/120 4/120 4/120 4/120 4/120 4/120 4/120 4/120 4/120

SPCT2-280

NEW
U1202

Plug-in surge arrester SPCT2, 1- to 4-pole


Complete (2- and multi-pole surge arresters are supplied with busbar)
1-pole 1-pole 1-pole 1-pole 1-pole 1-pole 1-pole 1-pole 1+N 2-pole 2-pole 2-pole 2-pole 2-pole 2-pole 2-pole 2-pole 3-pole 3-pole 3-pole 3-pole 3-pole 3-pole 3-pole 3-pole 4-pole 4-pole 4-pole 4-pole 4-pole 4-pole 4-pole 4-pole 1+N 1+N 1+N 1+N 1+N 3+N 3+N 3+N 3+N 3+N 3+N/BB 3+N/BB 3+N/BB 3+N/BB 75VAC 130VAC 175VAC 280VAC 335VAC 385VAC 460VAC 580VAC 260VAC 75VAC 130VAC 175VAC 280VAC 335VAC 385VAC 460VAC 580VAC 75VAC 130VAC 175VAC 280VAC 335VAC 385VAC 460VAC 580VAC 75VAC 130VAC 175VAC 280VAC 335VAC 385VAC 460VAC 580VAC 280VAC 335VAC 385VAC 460VAC 580VAC 280VAC 335VAC 385VAC 460VAC 580VAC 280VAC 335VAC 385VAC 460VAC 20kA 20kA 20kA 20kA 20kA 20kA 20kA 20kA 30kA 2x20kA 2x20kA 2x20kA 2x20kA 2x20kA 2x20kA 2x20kA 2x20kA 3x20kA 3x20kA 3x20kA 3x20kA 3x20kA 3x20kA 3x20kA 3x20kA 4x20kA 4x20kA 4x20kA 4x20kA 4x20kA 4x20kA 4x20kA 4x20kA 20kA 20kA 20kA 20kA 20kA 20kA 20kA 20kA 20kA 20kA 3x20kA 3x20kA 3x20kA 3x20kA SPCT2-075/1 SPCT2-130/1 SPCT2-175/1 SPCT2-280/1 SPCT2-335/1 SPCT2-385/1 SPCT2-460/1 SPCT2-580/1 SPCT2-NPE60/1 SPCT2-075/2 SPCT2-130/2 SPCT2-175/2 SPCT2-280/2 SPCT2-335/2 SPCT2-385/2 SPCT2-460/2 SPCT2-580/2 SPCT2-075/3 SPCT2-130/3 SPCT2-175/3 SPCT2-280/3 SPCT2-335/3 SPCT2-385/3 SPCT2-460/3 SPCT2-580/3 SPCT2-075/4 SPCT2-130/4 SPCT2-175/4 SPCT2-280/4 SPCT2-335/4 SPCT2-385/4 SPCT2-460/4 SPCT2-580/4 SPCT2-280-1+NPE SPCT2-335-1+NPE SPCT2-385-1+NPE SPCT2-460-1+NPE SPCT2-580-1+NPE SPCT2-280-3+NPE SPCT2-335-3+NPE SPCT2-385-3+NPE SPCT2-460-3+NPE SPCT2-580-3+NPE SPCT2-280-3+NPE/BB SPCT2-335-3+NPE/BB SPCT2-385-3+NPE/BB SPCT2-460-3+NPE/BB 167578 167583 167588 167593 167598 167603 167608 167613 167618 167579 167584 167589 167594 167599 167604 167609 167614 167580 167585 167590 167595 167600 167605 167610 167615 167581 167586 167591 167596 167601 167606 167611 167616 167619 167621 167623 167625 167627 167620 167622 167624 167626 167628 167629 167630 167631 167632 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 12/120 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/40 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/30 1/60 1/60 1/60 1/60 1/60 1/30 1/30 1/30 1/30 1/30 1 1 1 1

SPCT2-280/3

Surge Protection
Surge arrester Set
Description PHASE OUT TYPE
SG14805

Type Designation

Article No.

Units per package

SPD Class C, SPC


Surge arrester set SPC-S-3+1-SET 248194 1

SPC-S-3+1-SET
SG60611

NEW

Auxiliary Switch for SPCT2

ASAUXSC-SPM

131785

8 / 80

Description
SG59511

Type Designation

Article No.

Units per package

Lead-through terminal for SPB, ASLTT-63


ASLTT-63 131784 12 / 120

Photovoltaic - Surge Protection


SPD-type T2 (Class C)
Max. Cont. Op. Volt. UC In ( Type Designation

DC

Article No.

Units per package

Plug-in Surge Arrester SPPT2PA for Photovoltaic application


SG11009

For earthed systems


600 V DC 1000 V DC with auxiliary switch 1000 V DC SPPT2PA-600-2PE SPPT2PA-1000-2PE 132663 132664 1 / 60 1 / 60

SPPT2PA-1000-2PE-AX

132666

1 / 60

For unearthed systems


SG11309

600 V DC 1000 V DC with auxiliary switch 1000 V DC

SPPT2PA-600-2+1PE SPPT2PA-1000-2+1PE

132661 132662

1 / 40 1 / 40

SPPT2PA-1000-2+1PE-AX 132665

1 / 40

Inserts for replacement


600 V DC 1000 V DC 1100 V DC SPPT2PA-600 SPPT2PA-1000 SPPT2PA-1100 132667 132668 132669 1 1 1

VOC Uc:

Open circuit voltage of PV-Generator shall be equal or less than maximum continuous operating voltage of Surge Protective Device (SPD) to prevent its damage.

VOC . . . . . .Open circuit voltage of PV-Generator. UC . . . . . . .Maximum continuous operating voltage of SPD. Attention: Even at switched off DC-Disconnector system stays under high voltage! Before mounting ensure de-energizing and check zero-potential.

Earthed system
SPPT2PA-600-2PE SPPT2PA-1000-2PE(-AX)

Unearthed system
SPPT2PA-600-2+1PE SPPT2PA-1000-2+1PE(-AX)

L-

L-

L+

10

Surge Protection
Poles Type Designation Article No. Units per package

Busbars Z-GV-U/ for SPI, SP-B+C


Z-GV-U/9

2 3 4 5 6 8 9

Z-GV-U/2 Z-GV-U/3 Z-GV-U/4 Z-GV-U/5 Z-GV-U/6 Z-GV-U/8 Z-GV-U/9

272588 272589 274080 274081 274082 274083 274084

20 / 1200 20 / 1200 20 / 1200 20 / 1200 20 / 400 20 / 200 20 / 200

WA_SG11202

Busbar Z-GV-16/3P-3TE/6
for SPI and SPC Z-GV-16/3P-3TE/6 267511 12 / 240

Busbars ZV-KSBI for SPC


2MU 3MU 3MU 2MU+1.5MU 4MU 5MU 5MU 2MU+3x1.5MU 6MU 7MU 7MU 7MU 9MU 11MU ZV-KSBI-2TE ZV-KSBI-3TE ZV-KSBI-3TE/S ZV-KSBI-3TE+HI ZV-KSBI-4TE ZV-KSBI-5TE ZV-KSBI-5TE/N ZV-KSBI-5TE+HI ZV-KSBI-6TE ZV-KSBI-7TE ZV-KSBI-7TE/S ZV-KSBI-7TE/N ZV-KSBI-9TE/N ZV-KSBI-11TE 263961 263962 263963 112370 263964 263965 263966 112371 113118 263967 263968 263969 266874 263970 10 / 600 10 / 600 10 / 600 50 / 150 10 / 600 10 / 200 10 / 200 50 / 150 50 / 500 50 / 500 10 / 100 10 / 100 50 / 500 50 / 500

11

Surge Protection
SPD Class D

Description PHASE OUT TYPE

Type Designation

Article No.

Units per package

Surge protective device SPD-S-1+1 for TN-, TT-systems (3-phase 4-wire)


Complete device Insert N-PE Insert L-N Base 1+1 2-pole Auxiliary switch SPD-S-1+1 SPD-S-N/PE SPD-S-L/N SPC-S-S2-1+1 SPC-S-HK 248202 248199 248200 248201 248203 1 / 60 4 / 120 4 / 120 6 / 60 8 / 80

U1602

SPD-S-1+1 PHASE OUT TYPE

Surge protective device SPD-S-280/2 for IT-, TT-systems (3-phase 3-wire)


Complete device Insert Base Auxiliary switch SPD-S-280/2 SPD-S-280 SPC-S-S2 SPC-S-HK 269088 269087 248168 248203 1 / 60 4 / 120 6 / 60 8 / 80

19 Multiple Outlet Strips NWS-STL/19/7F


N00411

7 outlets, DIN 7 outlets, plus switch, DIN 7 outlets, UTE

NWS-STL/19/7F NWS-STL/19/7F/S/BL NWS-STL/19/7F/UTE

255398 255399 290031

1 1 1

N00511

19 Surge Protection - Multiple Outlet Strips with Switch SPD-STL/19/7F-S/BL


7 outlets, plus switch, DIN 7 outlets, UTE SPD-STL/19/7F-S/BL SPD-STL/19/7F-S/BL/UTE 283449 290032 1 1

Surge Protection Multiple Outlet Strips with High-Range Filter and Energy Absorption for full Equipment Protection SPD-STL/6F-S
N04011

SPD-STL/6F-S (68583) 130000 6 outlets, plus switch, DIN 6 outlets, plus switch, DIN+ISDN SPD-STL/6F-S/ISDN (68585) 147795 NWS-HW/19/SPD-STL/6F-S 166364 19" fixing bracket for SPD-STL/6F-S (1U)

1 1 1

12

Surge Protection
Earthing/Equipotential Bonding
Description Type Designation Article No. Units per package

Equipotential Bonding Bar PAS-7x16


For main equipotential bonding Earthing strip up to 30 x 3.5 / Round conductor 7 - 10 mm

SG07306

7 x 2.5 - 16 mm2

PAS-7x16

107945

10 / 50

Earthing Bar for Antenna Lines PAS-HF-6


Earthing conductor 6 - 25 mm2

SG07206

PAS-HF-6 107946 10 / 100

6 x HF-Cable shields

Earth Clips EBS


For copper and galvanized steel/stainless steel tubes Cross-section for connection 1 x 2.5 mm2 to 2 x 16 mm2

SG07406

Tube 1/8 - 1 Tube 1/8 - 4

EBS-210mm EBS-430mm

107947 107948

20 / 80 20 / 80

13

Surge Protection
SPD Class B, Lightning Current Arrester SPI
Field of application: For the protection of low voltage distribution systems against direct lightning stroke into the overhead power supply line or external lightning protection system (IEC 62305). Application according to IEC 60364-5-53 Clause 534 Test class I in accordance with IEC 61643-1 SPD-type T1 in accordance with EN 61643-1 Capsuled version: during the discharge process, the device does not issue any hot ionised gases. Therefore, there is no need for keeping a safety distance to flammable materials.

Practical Hint
Installation of lightning current arresters upstream of the meter is subject to co-ordination with the relevant power supply company. Installation of an r.m.s.ective protection cascade (SPD classes B, C, D) requires co-ordinated application of the respective protective devices. This is ensured by a defined line length between protective devices. When using lightning current arresters of type SPI in connection with surge arresters SPC with a maximum continuous operating voltage Uc of 460 V AC, no specific line length or decoupling coils are required.

Technical Data
SPI-35/440 Electrical Design Responding time tr Voltage protection level Up Maximum continuous operating voltage UC Temporary overvoltage test value UT (200 ms) (5 s) Rated frequency Discharge current (8/20) s Imax/In Impulse current Iimp (10/350) s Peak current Charge Q Specific energy Insulation resistance RISO Follow current interrupt rating Ifi Short-circuit current strength at max. back-up fuse Maximum back-up fuse Connection diagram capsuled < 100 ns 1.5 kV 440 VAC UT = UC 50/60 Hz 35 kA 35 kA 17.5 As 305 kJ/ >10 M 3kAr.m.s/260V 1.5kAr.m.s/440V 25kAr.m.s 125 AgL SPI-50/NPE capsuled < 100 ns 1.5 kV 260 VAC 1200 VAC 50/60 Hz 50 kA 50 kA 25 As 625 kJ/ >10 M 500Ar.m.s/260V SPI-100/NPE capsuled < 100 ns 1.5 kV 260 VA 1200 VAC 50/60 Hz 100 kA 100 kA 50 As 2500 kJ/ >10 M 100Ar.m.s/260V

Mechanical Frame size Device height Device width Weight Upper and lower lift terminal capacity rigid flexible Tightening torque of terminal screws Mounting Degree of protection acc. to IEC 60529 (installed) Accessories: busbars Permitted relative air humidity Permitted ambient temperature

45 mm 90 mm 17.5 mm 174 g

45 mm 90 mm 17.5 mm 178 g

45 mm 90 mm 35 mm 320 g

0.5 - 35 mm2 0.5 - 35 mm2 10 - 50 mm2 0.5 - 25 mm2 0.5 - 25 mm2 16 - 35 mm2 4 - 4.5 Nm 4 - 4.5 Nm 6 - 8 Nm quick fastening on DIN rail IEC/EN 60715 IP20 (IP40) Z-GV-U/ < 95% -40C to +85C Application Example
Attention! SPI-.../NPE should be used only as a N-PE spark gap in a e.g. TT-system (connection type 2 according to IEC 60364-5534 Clause 534) SPI-35/440

Dimensions (mm)
SPI-35/440, SPI-50/NPE SPI-100/NPE

Spark gap SPI-50/NPE SPI-100/NPE

Lightning current arrester Sets, Lightning protection classes I, II, III, IV


SPI-35/440/3 SPI-3+1
. . .SPI-35/440 . . .SPI-100/NPE . . .SPB-D-125 . . . .Z-GV-U/3 . . .Z-GV-U/6

SPI-50/NPE: for protection class III, IV according to IEC 62305 SPI-100/NPE: for protection class I, II, III, IV according to IEC 62305

10

Surge Protection
SPD Class B+C, Lightning Current Arrester - Surge Arresters SPBT12
Field of application For the protection of low voltage distribution systems against transient overvoltage caused by direct and indirect lightning stroke and switching operations. Application according to IEC 60364-5-53 Clause 534 Test class I , II in accordance with IEC 61643-1 SPD-type T1 , T2 in accordance with EN 61643-11 Lightning protection classes III and IV in accordance with IEC 62305 Busbars ZV-KSBI are available for all customary applications

Block Diagram

Technical Data
SPBT12-280... Electrical Responding time (rate of voltage rise 5 kV/s) Voltage protection level Up Voltage protection level at 5 kA (8/20) s Maximum continuous operating voltage UC Temporary overvoltage test value UT Rated frequency Open circuit voltage Uoc Nominal discharge current (8/20) s In Maximum discharge current Imax Imulse current Iimp (10/350) s Peak current Charge Q Specific energy Follow current interrupt rating Ifi Maximum back-up fuse Maximum short-circuit current Connection diagram per pole < 25 ns < 1.5kV 950 V 280 VAC 370 VAC (5 s) 50/60 Hz 10 kV 25 kA 50 kA 12.5 kA 6.25 As 39.1 kJ/ 160 AgL/gG 50 kAr.m.s < 100 ns < 1.5kV 255 VAC 1200 VAC (200 ms) 50/60 Hz 20 kV 100 kA 100 kA 100 kA 50 As 2500 kJ/ 100 Ar.m.s SPBT12-NPE100

Mechanical Frame size Device height Device width Weight Permitted ambient temperature Degree of protection (built-in) Upper and lower lift terminal capacity Upper and lower open mouthed terminals for busbar thickness up to Tightening torque of terminal screws Quick fastening on DIN rail according to Accessories: busbars 16 mm2

45 mm 80 mm 17.5 mm 121 g -40C to +70C IP40 4 - 25 mm2 1.5 mm 2.4 - 3 Nm IEC/EN 60715 Type ZV-KSBI ...

45 mm 80 mm 35 mm 250 g -40C to +70C IP40 4 - 35 mm2 1.5 mm 2.4 - 3 Nm IEC/EN 60715 Type ZV-KSBI ...

Dimensions (mm)
SPBT12-280 SPBT12-NPE100

Lightning current arrester - surge arrester Sets, Lightning protection classes III, IV

SPBT12280/2

SPBT12-280/3

SPBT12-280/4

. . .SPBT12-280

11

Surge Protection
SPD Class B+C, Lightning Current Arrester - Surge Arresters SPBT12-280
Field of application For the protection of low voltage distribution systems against transient overvoltage caused by direct and indirect lightning stroke and switching operations. Application according to IEC 60364-5-53 Clause 534 Test class I , II in accordance with IEC 61643-1 SPD-type T1 , T2 in accordance with EN 61643-11 Lightning protection classes III and IV in accordance with IEC 62305 Busbars ZV-KSBI are available for all customary applications

Block Diagram

Technical Data
SPBT12-280-1+NPE Electrical Responding time (rate of voltage rise 5 kV/s) Voltage protection level Up Maximum continuous operating voltage UC Temporary overvoltage test value UT (5 s) (200 ms) Rated frequency Open circuit voltage Uoc Nominal discharge current (8/20) s In Maximum discharge current Imax Imulse current Iimp (10/350) s Peak current Charge Q Specific energy Follow current interrupt rating Ifi Maximum back-up fuse Maximum short-circuit current Connection diagram L-N / N-PE L-N / L-PE / N-PE L-N / N-PE L-N / L-PE N-PE per pole < 25 ns / < 100 ns < 1.5kV 280 VAC / 255 VAC 348 VAC / 370 VAC 1200 VAC 50/60 Hz 10 kV 25 kA / 100 kA 50 kA / 100 kA 12.5 kA / 100 kA 50 As 2500 kJ/ 100 Ar.m.s 160 AgL/gG 50 kAr.m.s
PE L

SPBT12-280-3+NPE < 25 ns / < 100 ns < 1.5kV 280 VAC / 255 VAC 348 VAC / 370 VAC 1200 VAC 50/60 Hz 20 kV 3x25 kA / 100 kA 3x50 kA / 100 kA 3x12.5 kA / 100 kA 50 As 2500 kJ/ 100 Ar.m.s 160 AgL/gG 50 kAr.m.s
PE L1 L2 L3

L-N / N-PE L-N / N-PE L-N / N-PE

N-PE

Mechanical Frame size Device height Device width Weight Permitted ambient temperature Degree of protection (built-in) Upper and lower lift terminal capacity Upper and lower open mouthed terminals for busbar thickness up to Tightening torque of terminal screws Quick fastening on DIN rail according to Accessories: busbars 16 mm2

L, N N, PE

45 mm 80 mm 52.5 mm 375 g -40C to +70C IP40 4 - 25 mm2 4 - 35 mm2 1.5 mm 2.4 - 3 Nm IEC/EN 60715 Type ZV-KSBI ...

45 mm 80 mm 87.5 mm 626 g -40C to +70C IP40 4 - 25 mm2 4 - 35 mm2 1.5 mm 2.4 - 3 Nm IEC/EN 60715 Type ZV-KSBI ...

Lightning current arrester - surge arrester Sets, Lightning protection classes III, IV

. . .SPBT12-280 . . .ASAUXSC-SPM . . .SPI-100/NPE


SPBT12-280-1+NPE SPBT12-280-3+NPE SPBT12-280-3+NPE/BB SPBT12-280-1+NPE-AX SPBT12-280-3+NPE-AX

. . .ASLTT-63

12

Surge Protection
Lightning current arrester - surge arrester Sets, Lightning protection classes I, II, III, IV SPD Class B+C, SP-B+C/
Field of application: For the protection of low voltage distribution systems against direct lightning stroke into the overhead power supply line or external lightning protection system (IEC 62305) and against indirect lightning stroke and switching operations. Application according to IEC 60364-5-53 Clause 534 Test class I and II in accordance with IEC 61643-1 SPD-type T1 and T2 in accordance with EN 61643-11 Capsuled version: during the discharge process, the device does not issue any hot ionised gases. Therefore, there is no need for keeping a safety distance to flammable materials.

Practical Hint
Installation of lightning current arresters upstream of the meter is subject to co-ordination with the relevant power supply company. Installation of an r.m.s.ective protection cascade (SPD classes B, C, D) requires co-ordinated application of the respective protective devices. This is ensured by a defined line length between protective devices. When using lightning current arresters of type SPI in connection with surge arresters SPC with a maximum continuous operating voltage Uc of 460 V AC, no specific line length or decoupling coils are required.

Technical Data
SP-B+C/3 Electrical Design Responding time tr Voltage protection level Up Maximum continuous operating voltage UC Temporary overvoltage test value UT capsuled < 25 ns 1.5 kV 440 VAC / UT = Uc 50/60 Hz 3x35 kA 100 kA 50 As 2500 kJ/ 3kArms / 1,5kArms / 25kArms 125 AgL SP-B+C/3+1 capsuled < 25 ns 1.5 kV 440 VAC / 260 VAC UT = Uc 1200 VAC (200 ms) 50/60 Hz 100 kA 100 kA 50 As 2500 kJ/ 3kArms / 100Arms 1,5kArms / 25kArms 125 AgL

L-(PE)N / N-PE L-(PE)N N-PE

Rated frequency Discharge current (8/20) s Imax/In Impulse current Iimp (10/350) s Peak current Charge Q Specific energy Follow current interrupt rating Ifi L-(PE)N / N-PE at 260 V at 440 V Short-circuit current strength at max. back-up fuse Maximum back-up fuse Connection diagram

Mechanical Frame size Device height Device width Weight Upper and lower lift terminal capacity rigid L, N, PEN / PE flexible L, N, PEN / PE Tightening torque of terminal screws Mounting Degree of protection acc. to IEC 60529 (installed) Accessories: busbars Permitted relative air humidity Permitted ambient temperature

45 mm 90 mm 110 mm 1100 g

45 mm 90 mm 164 mm 1420 g

0.5 - 35 mm2 0.5 - 35 mm2 / 10 - 50 mm2 2 0.5 - 25 mm 0.5 - 25 mm2 / 16 - 35 mm2 4 - 4.5 Nm 4 - 4.5 Nm / 6 - 8 Nm quick fastening on DIN rail IEC/EN 60715 IP20 (IP40) Z-GV-U/ < 95% -40C to +70C

Dimensions (mm)
Lightning current arrester - surge arrester . . .SPI-35/440 . . .SPI-100/NPE for protection class I, II, III, IV . . .SPC-S-20/460/3 Lead-through terminal . . .SPB-D-125 Busbar . . .Z-GV-U/6 . . .Z-GV-U/9 . . .Z-GV-16/3P-3TE/6

13

Surge Protection
Busbar Connection Examples according to IEC 60364-5-53 Clause 534
SPD Class B SPI B TN-C-System 3 x 240/415 V AC 3 x 230/400 V AC 3 x 220/380 V AC TT-System 3 x 230 VAC IT-System 3 x 230 VAC

SPI-35/440/3

SPI-35/440/3

4 wires

2 wires TN-S-System

4 wires TT-System

3 wires IT-System 3 x 230/400 VAC

3 x 240/415 V AC 3 x 230/400 V AC 3 x 220/380 V AC

SPI-3+1

CT2 5 wires TN-S-System


Lightning current arrester . . .SPI-35/440

CT2 3 wires

. . .SPI-100/NPE for protection class I, II, III, IV SPI-50/NPE for protection class III, IV Lead-through terminal . . .SPB-D-125 Busbar . . .Z-GV-U/2 . . .Z-GV-U/3 . . .Z-GV-U/4 . . .Z-GV-U/4 at SPI-100/NPE Z-GV-U/3 at SPI-50/NPE . . .Z-GV-U/6 (Z-GV-U/5 at SPI-50/NPE)

CT1 5 wires

CT1 3 wires

CT1 . .Connection type 1 CT2 . .Connection type 2

14

Surge Protection
Busbar Connection Examples according to IEC 60364-5-53 Clause 534
SPD Class B+C SPI B SPC C TN-C-System 3 x 240/415 V AC 3 x 230/400 V AC 3 x 220/380 V AC TT-System 3 x 230 VAC IT-System 3 x 230 VAC

SP-B+C/3

SP-B+C/3

4 wires TN-S-System 3 x 240/415 V AC 3 x 230/400 V AC 3 x 220/380 V AC

4 wires TT-System IT-System 3 x 230/400 VAC

SP-B+C/3+1

CT2 5 wires
Lightning current arrester . . .SPI-35/440 . . .SPI-100/NPE for protection class I, II, III, IV SPI-50/NPE for protection class III, IV . . .SPCT2-460/3 Lead-through terminal . . .SPB-D-125 Busbar . . .Z-GV-U/6 . . .Z-GV-U/9 . . .Z-GV-16/3P-3TE/6 CT2 . .Connection type 2

15

Surge Protection
Application Examples according to IEC 60364-5-53 Clause 534
Lightning current arrester . . .SPI-35/440 . . .SPI-100/NPE . . .SPI-50/NPE Surge arrester . . .SPCT2-460/3 Lead-through terminal . . .SPB-D-125 . . .ASLTT-63 Busbar . . .ZV-KSBI-4TE
Main distribution board Sub-distribution board

Lightning current arrester

Protection Class I, II, III, IV


Main distribution board Sub-distribution board

Lightning current arrester

Protection Class III, IV


Main distribution board Sub-distribution board

Lightning current arrester

16

Surge Protection
SPD Class C, Surge Arresters SPC-E
Field of application For the protection of low voltage distribution systems against transient overvoltage caused by indirect lightning stroke and switching operations. Test class II according to IEC 61643-1+A1 SPD-type T2 according to EN 61643-11 Busbars ZV-KSBI are available for all customary applications Suitable for busbar connection to all Xtra Combinations switchgear

Block Diagram

Technical Data
SPC-E-75 -130 Electrical Responding time (rate of voltage rise 5 kV/s) Voltage protection level at nominal discharge current Voltage protection level at 5 kA (8/20) s Maximum continuous operating voltage UC Temporary overvoltage test value UT (5 s) Rated frequency Nominal discharge current (8/20) s In Charge Q at In Specific energy at In Maximum discharge current Imax Permissible back-up fuse Maximum short-circuit current Connection diagram < 25 ns < 550 V 400 V 75 VAC = Uc 50/60 Hz 15 kA 0.43 As 3.2 kJ/ 30 kA < 25 ns < 800 V 550 V 130 VAC = Uc 50/60 Hz 20 kA 0.57 As 5.7 kJ/ 40 kA < 25 ns < 1kV 700 V 175 VAC = Uc 50/60 Hz 20 kA 0.57 As 5.7 kJ/ 40 kA < 25 ns < 1.4kV 1000 V 280 VAC 350 VAC 50/60 Hz 20 kA 0.57 As 5.7 kJ/ 40 kA < 25 ns < 1.6kV 1200 V 335 VAC 415 VAC 50/60 Hz 20 kA 0.57 As 5.7 kJ/ 40 kA < 25 ns < 1.8kV 1350 V 385 VAC 415 VAC 50/60 Hz 20 kA 0.57 As 5.7 kJ/ 40 kA < 25 ns < 2.2kV 1700 V 460 VAC 580 VAC 50/60 Hz 20 kA 0.57 As 5.7 kJ/ 40 kA < 25 ns < 2.6kV 2000 V 580 VAC = Uc 50/60 Hz 20 kA 0.57 As 5.7 kJ/ 40 kA -175 -280 -335 -385 -460 -580

125 AgL 50 kAr.m.s.

PLHT-C100 20 kAr.m.s.

Mechanical Frame size Device height Device width Weight Permitted ambient temperature Degree of protection (built-in) Upper and lower lift terminal capacity Upper and lower open mouthed terminals for busbar thickness up to Tightening torque of terminal screws Quick fastening on DIN rail according to Accessories: busbars 16 mm2

45 mm 80 mm 17.5 mm 97 g -40C to +70C IP40 4 - 25 mm2 1.5 mm 2.4 - 3 Nm IEC/EN 60715 Type ZV-KSBI ...

17

Surge Protection
Technical Data
SPC-E-N/PE Electrical Responding time (rate of voltage rise 5 kV/s) Voltage protection level at nominal discharge current Maximum continuous operating voltage UC Temporary overvoltage test value UT (200 ms) Rated frequency Nominal discharge current (8/20) s In Charge Q at In Specific energy at In Maximum discharge current Imax Follow current interrupt rating Ifi Maximum back-up fuse Maximum short-circuit current Connection diagram < 100 ns < 1.0 kV 260 VAC 1200 VAC 50/60 Hz 20 kA 0.57 As 5.7 kJ/ 40 kA 100 Ar.m.s

Mechanical Frame size Device height Device width Weight Permitted ambient temperature Degree of protection (built-in) Upper and lower lift terminal capacity Upper and lower open mouthed terminals for busbar thickness up to Tightening torque of terminal screws Quick fastening on DIN rail according to Accessories: busbars 16 mm2

45 mm 80 mm 17.5 mm 97 g -40C to +70C IP40 4 - 25 mm2 1.5 mm 2.4 - 3 Nm IEC/EN 60715 Type ZV-KSBI ...

Dimensions (mm)

Application Examples SPC-E according to IEC 60364-5-53 Clause 534

SPC-E-280

SPC-E-280

SPC-E-460

SPC- SPCEEN/PE 280

ZD63

SPC-E-280

SPCEN/PE

SPC-E-280

ZD63

SPC-E-460

18

Surge Protection
SPD Class C, Plug-in Surge Arresters SPCT2
Field of application: For the protection of low voltage distribution systems against transient overvoltage caused by indirect lightning stroke and switching operations. Test class II according to IEC 61643-1+A1 SPD-type T2 according to EN 61643-11 Auxiliary switch SPC-S-HK for remote message transmission can be mounted onto the device Suitable for busbar connection to all Xtra Combinations switchgear Busbars ZV-KSBI are available for all customary applications

Symbol

Technical Data
Inserts Electrical Mechanical coding x x Responding time (rate of voltage rise 5 kV/s) < 25 ns < 25 ns Voltage protection level at nominal discharge current / Uoc < 550 V < 800 V Voltage protection level at 5 kA (8/20) s 400 V 550 V Maximum continuous operating voltage Uc 75 VAC 130 VAC Temporary overvoltage test value UT (5 s) = UC = UC Rated frequency 50/60 Hz 50/60 Hz Open circuit voltage Uoc Nominal discharge current (8/20) s In 15 kA 20 kA Charge Q at In 0.43 As 0.57 As Specific energy at In 3.2 kJ/ 5.7 kJ/ Maximum discharge current Imax 30 kA 40 kA Follow current interrupt rating Ifi Permissible back-up fuse 125 AgL Maximum short-circuit current 50 kA
r.m.s.

SPCT2-075 SPCT2-130 SPCT2-175 SPCT2-280 SPCT2-335 SPCT2-385 SPCT2-460 x < 25 ns < 1.0 kV 700 V 175 VAC = UC 50/60 Hz 15 kA 0.57 As 5.7 kJ/ 40 kA x < 25 ns < 1.4 kV 1000 V 280 VAC 350 VAC 50/60 Hz 10 kV 20 kA 0.57 As 5.7 kJ/ 40 kA x < 25 ns < 1.6 kV 1200 V 335 VAC 415 VAC 50/60 Hz 5 kV 20 kA 0.57 As 5.7 kJ/ 40 kA x < 25 ns < 1.8 kV 1350 V 385 VAC 415 VAC 50/60 Hz 20 kA 0.57 As 5.7 kJ/ 40 kA x < 25 ns < 2.2 kV 1700 V 460 VAC 580 VAC 50/60 Hz 20 kA 0.57 As 5.7 kJ/ 40 kA

PLHT-C100 20 kAr.m.s.

Connection diagram

Mechanical Frame size Device height Device width 1-pole 1+1-pole 2-pole 3-pole 3+1-pole 4-pole Mechanical coding 1-pole 1+1-pole 2-pole 3-pole 3+1-pole 4-pole Weight Base 1P, 1+1P, 2P, 3P, 3+1P, 4P Weight Complete Devices 1P, 1+1P, 2P, 3P, 3+1P, 4P Permitted ambient temperature Degree of protection (built-in) Upper and lower lift terminal capacity Upper and lower open mouthed terminals for busbar thickness up to Tightening torque of terminal screws Quick fastening on DIN rail according to Accessories: busbars 16 mm2

45 mm 80 mm 17.5 mm (1MU) 35 mm (2MU) 35 mm (2MU) 52.5 mm (3MU) 70 mm (4MU) 70 mm (4MU) x yx xx xxx yxxx xxxx 53/120/120/180/240/240 g 110/201/220/330/412/440 g -40C to +70C IP40 4 - 25 mm2 1.5 mm 2.4 - 3 Nm IEC/EN 60715 Type ZV-KSBI ...

19

Surge Protection
Technical Data
Inserts Electrical Mechanical coding Responding time (rate of voltage rise 5 kV/s) Voltage protection level at nominal discharge current / Uoc Voltage protection level at 5 kA (8/20) s Maximum continuous operating voltage Uc Temporary overvoltage test value UT Rated frequency Nominal discharge current (8/20) s In Charge Q at In Specific energy at In Maximum discharge current Imax Follow current interrupt rating Ifi Permissible back-up fuse Maximum short-circuit current Connection diagram x < 25 ns < 2.6 kV 2000 V 580 VAC = UC (5 s) 50/60 Hz 20 kA 0.57 As 5.7 kJ/ 40 kA 125 AgL 50 kAr.m.s. PLHT-C100 20 kAr.m.s. y < 100 ns < 1.0 kV 260 VAC 1200 VAC (200 ms) 50/60 Hz 20 kA 0.57 As 5.7 kJ/ 40 kA 100 Ar.m.s SPCT2-580 SPCT2-NPE

Mechanical Frame size Device height Device width 1-pole 1+1-pole 2-pole 3-pole 3+1-pole 4-pole Mechanical coding 1-pole 1+1-pole 2-pole 3-pole 3+1-pole 4-pole Weight Base 1P, 1+1P, 2P, 3P, 3+1P, 4P Weight Complete Devices 1P, 1+1P, 2P, 3P, 3+1P, 4P Permitted ambient temperature Degree of protection (built-in) Upper and lower lift terminal capacity Upper and lower open mouthed terminals for busbar thickness up to Tightening torque of terminal screws Quick fastening on DIN rail according to Accessories: busbars 16 mm2

45 mm 80 mm 17.5 mm (1MU) 35 mm (2MU) 35 mm (2MU) 52.5 mm (3MU) 70 mm (4MU) 70 mm (4MU) x yx xx xxx yxxx xxxx 53/120/120/180/240/240 g 110/201/220/330/412/440 g -40C to +70C IP40 4 - 25 mm2 1.5 mm 2.4 - 3 Nm IEC/EN 60715 Type ZV-KSBI ...

Dimensions (mm)

20

Surge Protection
SPD Class C, Plug-in Surge Arresters SPC-S
Field of application: For the protection of low voltage distribution systems against transient overvoltage caused by indirect lightning stroke and switching operations. Test class II according to IEC 61643-1+A1 SPD-type T2 according to EN 61643-11 Auxiliary switch SPC-S-HK for remote message transmission can be mounted onto the device Suitable for busbar connection to all Xtra Combinations switchgear Busbars ZV-KSBI are available for all customary applications

Symbol

Technical Data
Inserts Electrical Mechanical coding x x Responding time (rate of voltage rise 5 kV/s) < 25 ns < 25 ns Voltage protection level at nominal discharge current / Uoc < 550 V < 800 V Voltage protection level at 5 kA (8/20) s 400 V 550 V Maximum continuous operating voltage Uc 75 VAC 130 VAC Temporary overvoltage test value UT (5 s) = UC = UC Rated frequency 50/60 Hz 50/60 Hz Open circuit voltage Uoc Nominal discharge current (8/20) s In 15 kA 20 kA Charge Q at In 0.43 As 0.57 As Specific energy at In 3.2 kJ/ 5.7 kJ/ Maximum discharge current Imax 30 kA 40 kA Follow current interrupt rating Ifi Permissible back-up fuse 160 AgL Maximum short-circuit current 50 kA
r.m.s.

SPC-S-15/75 -20/130

-20/175 x < 25 ns < 1.0 kV 700 V 175 VAC = UC 50/60 Hz 15 kA 0.57 As 5.7 kJ/ 40 kA

-20/280 x < 25 ns < 1.4 kV 1000 V 280 VAC 350 VAC 50/60 Hz 10 kV 20 kA 0.57 As 5.7 kJ/ 40 kA

-20/335 x < 25 ns < 1.6 kV 1200 V 335 VAC 415 VAC 50/60 Hz 5 kV 20 kA 0.57 As 5.7 kJ/ 40 kA

-20/385 x < 25 ns < 1.8 kV 1350 V 385 VAC 415 VAC 50/60 Hz 20 kA 0.57 As 5.7 kJ/ 40 kA

-20/460 x < 25 ns < 2.2 kV 1700 V 460 VAC 580 VAC 50/60 Hz 20 kA 0.57 As 5.7 kJ/ 40 kA

PLHT-C100 20 kAr.m.s.

Connection diagram

Mechanical Frame size Device height Device width 1-pole 1+1-pole 2-pole 3-pole 3+1-pole 4-pole Mechanical coding 1-pole 1+1-pole 2-pole 3-pole 3+1-pole 4-pole Weight Base 1P, 1+1P, 2P, 3P, 3+1P, 4P Weight Complete Devices 1P, 1+1P, 2P, 3P, 3+1P, 4P Permitted ambient temperature Degree of protection (built-in) Upper and lower lift terminal capacity Upper and lower open mouthed terminals for busbar thickness up to Tightening torque of terminal screws Quick fastening on DIN rail according to Accessories: busbars 16 mm2

45 mm 80 mm 17.5 mm (1MU) 35 mm (2MU) 35 mm (2MU) 52.5 mm (3MU) 70 mm (4MU) 70 mm (4MU) x yx xx xxx yxxx xxxx 53/120/120/180/240/240 g 110/201/220/330/412/440 g -40C to +70C IP40 4 - 25 mm2 1.5 mm 2.4 - 3 Nm IEC/EN 60715 Type ZV-KSBI ...

21

Surge Protection
Technical Data
Inserts Electrical Mechanical coding Responding time (rate of voltage rise 5 kV/s) Voltage protection level at nominal discharge current / Uoc Voltage protection level at 5 kA (8/20) s Maximum continuous operating voltage Uc Temporary overvoltage test value UT Rated frequency Nominal discharge current (8/20) s In Charge Q at In Specific energy at In Maximum discharge current Imax Follow current interrupt rating Ifi Permissible back-up fuse Maximum short-circuit current Connection diagram x < 25 ns < 2.6 kV 2000 V 580 VAC = UC (5 s) 50/60 Hz 20 kA 0.57 As 5.7 kJ/ 40 kA 160 AgL 50 kAr.m.s. PLHT-C100 20 kAr.m.s. y < 100 ns < 1.0 kV 260 VAC 1200 VAC (200 ms) 50/60 Hz 20 kA 0.57 As 5.7 kJ/ 40 kA 100 Ar.m.s SPC-S-20/580 -N/PE

Mechanical Frame size Device height Device width 1-pole 1+1-pole 2-pole 3-pole 3+1-pole 4-pole Mechanical coding 1-pole 1+1-pole 2-pole 3-pole 3+1-pole 4-pole Weight Base 1P, 1+1P, 2P, 3P, 3+1P, 4P Weight Complete Devices 1P, 1+1P, 2P, 3P, 3+1P, 4P Permitted ambient temperature Degree of protection (built-in) Upper and lower lift terminal capacity Upper and lower open mouthed terminals for busbar thickness up to Tightening torque of terminal screws Quick fastening on DIN rail according to Accessories: busbars 16 mm2

45 mm 80 mm 17.5 mm (1MU) 35 mm (2MU) 35 mm (2MU) 52.5 mm (3MU) 70 mm (4MU) 70 mm (4MU) x yx xx xxx yxxx xxxx 53/120/120/180/240/240 g 110/201/220/330/412/440 g -40C to +70C IP40 4 - 25 mm2 1.5 mm 2.4 - 3 Nm IEC/EN 60715 Type ZV-KSBI ...

Dimensions (mm)

22

Surge Protection
SPD Class C, Surge Arresters SPCT2-1+NPE, SPCT2-3+NPE
Field of application: For the protection of low voltage distribution systems against transient overvoltage caused by indirect lightning stroke and switching operations. Test class II according to IEC 61643-1+A1 SPD-type T2 according to EN 61643-11 Auxiliary switch SPC-S-HK for remote message transmission can be mounted onto the device Suitable for busbar connection to all Xtra Combinations switchgear Type SPC-S-3+1: consists of 1 base SPC-S-S4-3+1, 1 insert SPC-S-N/PE and 3 inserts SPC-S-20/335 Type SPC-S-1+1: consists of 1 base SPC-S-S2-1+1, 1 insert SPC-S-N/PE and 1 insert SPC-S-20/335

Technical Data
SPCT2-1+NPE Electrical Mechanical coding Responding time (rate of voltage rise 5 kV/s) Maximum continuous operating voltage UC Temporary overvoltage test value UT (5 s) (200 ms) Rated frequency Nominal discharge current In Voltage protection level Up at In Maximum discharge current Imax Follow current interrupt rating Ifi Permissible back-up fuse Maximum short-circuit current Connection diagram x x
N

SPCT2-3+NPE

L-N/N-PE/L-PE L-N/N-PE L-N N-PE L-N/N-PE/L-PE L-N/N-PE/L-PE L-N/N-PE/L-PE N-PE

yx < 25ns/< 100ns/< 100ns 335VAC/260VAC 415 VAC 1200 VAC 50/60 Hz 20 kA (8/20)s 1600V/1000V/1650V 40 kA (8/20)s 100 Ar.m.s. PLHT-C100 20 kAr.m.s.

yxxx < 25ns/< 100ns/< 100ns 280VAC/260VAC 350 VAC 1200 VAC 50/60 Hz 20 kA (8/20)s 1000V/1000V/1300V 40 kA (8/20)s 100 Ar.m.s.

125 AgL 50 kAr.m.s.

L1

L2

L3

x
N

Mechanical Mechanical coding of base Frame size Device height Device width Weight Upper and lower lift terminal capacity Open-mouthed terminals at both sides for busbar thickness up to Tightening torque of terminal screws Permitted ambient temperature Mounting Degree of protection (built-in)

yx yxxx 45 mm 45 mm 80 mm 80 mm 35 mm 70 mm 201 g 412 g 1 - 25 mm2 1 - 25 mm2 1.5 mm 1.5 mm 2.4 - 3 Nm 2.4 - 3 Nm -40C to +70C -40C to +70C quick fastening on DIN rail IEC/EN 60715 IP40 IP40

Dimensions (mm)
SPCT2-1+NPE SPCT2-3+NPE

Application Examples

23

Surge Protection
Application Examples SPCT2 according to IEC 60364-5-53 Clause 534

SPCT2-280/3

SPCT2-280/4

SPCT2-460/4

SPCT21+NPE

ZD63

SPCT2-280/3

SPCT2-460/4

24

Surge Protection
Surge arrester Sets SPD Class C, SPCT2
Surge Arrester Set SPCT2-335-3+NPE/BB
The 3+1 circuit offers a universal solution for surge protection in low voltage distribution systems Suitable for TT- and TN-S systems according to IEC 60364-5-53 Clause 534 Remote message transmission is possibly by mounting auxiliary switch ASAUXSC-SPM Busbar connected, minimum installation work required

Content SPCT2-335-3+NPE/BB - 1 unit SPC-S-3+1 surge arrester - 1 unit ASLTT-63 lead-through terminal - busbar included

25

Surge Protection
Auxiliary Switch for (Lightning Current Arrester-)Surge Arrester ASAUXSC-SPM
Field of application: For mounting onto surge protective devices for external defect message transmission Design basically in accordance with IEC 60947-5-1 Can be mounted subsequently Suitable for SPBT12-280/1, SPCT2

Connection diagram
ASAUXSC-SPM
13 21

22 14

Technical Data
Electrical Rated insulation voltage Rated frequency Switching contact Minimum voltage per contact Rated operational current AC12 Maximum back-up fuse Overvoltage category Pollution degree 250 V 50/60 Hz 1 NC + 1 NO 24 VAC 2A/250VAC 2 A gL IV 2 Mechanical Frame size Device height Device width Weight Mounting Degree of protection, built-in Finger and hand touch safe acc. to Upper and lower terminals Terminal capacity Tightening torque of terminal screws 45 mm 80 mm 8.8 mm 41 g screw-mounting IP40 BGV A3, VE-EN 6 lift terminals 2 x 2.5 mm2 0.8 - 1 Nm

Dimensions (mm)

Application Examples

SPCT2

SPCT2

SPCT2

26

Surge Protection
Lead-Through Terminal for Surge Protective Devices, Class B, SPB-D-125
The lead-through terminal permits orderly wiring of SPDs of class B. It serves as lead-through terminal in circuits requiring vertical connections from the upper to the lower SPD connection level.

Connection diagram

Technical Data
Electrical Design basically in accordance with IEC 61643-1: 1998-02, DIN VDE 0675 Part 6: 1989-11, IEC 61024-1: 1990-03, IEC 60947-7-1: 1989-10, DIN VDE 0110-1: 1997-04 500 V AC/DC 125 A / 30C 100 kA 50 As 2,5 MJ/ III Mechanical Frame size Device height Device width Mounting Degree of protection, built-in Upper and lower terminals 45 mm 90 mm 17.5 mm quick fastening on DIN rail IEC/EN 60715 IP40 lift and open-mouthed terminals

Rated voltage UC Rated current IN Impulse current (10/350) s Peak current Charge Q Specific energy Overvoltage category

Terminal capacity rigid 0.5 - 35 mm2 flexible 0.5 - 25 mm2 Tightening torque of terminal screws 4-4.5 Nm Permitted relative air humidity < 95% Pollution degree 2 Resistance to climatic conditions F / DIN 40040 Creepage a. clearance distances acc. to IEC 60664-1, DIN VDE 0110-1:1997-04 Temperature range -40 to +85C Connection type 2 according to IEC 60364-5-53 Clause 534

Dimensions (mm)

TT-System, TN-S-System , IT- System with Neutral


Lightning current arrester . . . SPI-35/440 . . . SPI-100/NPE . . . SPI-50/NPE Lead-through terminal . . . SPB-D-125 Busbar . . . Z-GV-U/5 . . . Z-GV-U/6

27

Surge Protection
Lead-Through Terminal for Surge Protective Devices, ASLTT-63
The lead-through terminal permits orderly wiring of SPDs. It serves as lead-through terminal in circuits requiring vertical connections from the upper to the lower SPD connection level. 1-pole Suitable for standard busbar connection to all Xtra Combination switchgear

Connection diagram

Technical Data
Electrical Rated voltage Rated current Rated frequency 500V AC/DC 63 A 50/60 Hz Mechanical Frame size Device height Device width Mounting Degree of protection, built-in Finger and hand touch safe acc. to Upper and lower terminals Terminal capacity Busbar thickness Tightening torque of terminal screws 45 mm 80 mm 17.5 mm quick fastening on DIN rail IEC/EN 60715 IP40 BGV A3, VE-EN 6 lift and open-mouthed terminals 1 - 25 mm2 0.8 - 2 mm 2.4 - 3 Nm

Dimensions (mm)

Application Example / Connection type 2 acc. to IEC 603645-53 Clause 534

SPCT2-3353+NPE/BB

ASLT T-63

28

Photovoltaic - Surge Protection


SPD-type T2 (Class C), Plug-in Surge Arresters SPPT2PA-...-2PE
Field of application: Connection For the protection of photovoltaic systems against transient overvoltage SPPT2PA-...-2PE caused by indirect lightning stroke and switching operations. Test class II according to IEC 61643-1 SPD-type T2 according to EN 61643-11 Types SPPT2PA-...-AX for remote message transmission of defective inserts

DC

diagrams

Technical Data
SPPT2PA-600-2PE Electrical Responding time Maximum continuous operating voltage UC Rated frequency Nominal discharge current In Voltage protection level Up Residual voltage at 5 kA (8/20) s Maximum discharge current Imax Permissible back-up fuse Maximum short-circuit current Isc Residual current IPE Mechanical Frame size Device height Device width Weight Upper and lower lift terminal capacity fine- / solid strand Tightening torque of terminal screws Permitted ambient temperature Mounting Degree of protection Polution degree Auxiliary switch Electrical Rated insulation voltage Rated frequency Switching contact Minimum voltage per contact Rated operational current Min. admissible power Mechanical Terminal capacity fine- / solid strand Tightening torque of terminal screws 25 ns 600 V DC DC 15 kA (8/20) s 3 kV 2.5 kV 30 kA (8/20) s 80 A 20 A 45 mm 90 mm 35.6 mm 247 g SPPT2PA-1000-2PE(-AX) 25 ns 1000 V DC DC 15 kA (8/20) s 5 kV 4 kV 30 kA (8/20) s 80 A 20 A 45 mm 90 mm (99 mm) 35.6 mm 247 g (249 g)

4-25/4-35 mm2/AWG11-2 4-25/4-35 mm2/AWG11-2 4.5 Nm 4.5 Nm -40C up to +80C -40C up to +80C quick fastening on DIN rail IEC/EN 60715 IP20 IP20 2 2

250 V 50/60 Hz 1 CO 5 V AC/DC 1.5 A / 250 V AC 1.5 A / 30 V DC 5 mA / 5 V

1.5/1.5 mm2/AWG28-16 0.25 Nm

Dimensions (mm)

Application hints according to EN 50539-12

29

Photovoltaic - Surge Protection


SPD-type T2 (Class C), Plug-in Surge Arresters SPPT2PA-...-2+1PE
Field of application: Connection For the protection of photovoltaic systems against transient overvoltage SPPT2PA-...-2+1PE caused by indirect lightning stroke and switching operations. Test class II according to IEC 61643-1 SPD-type T2 according to EN 61643-11 Galvanic seperation in unearthed systems by means of a spark gap Types SPPT2PA-...-AX for remote message transmission of defective inserts

DC

diagrams

Technical Data
SPPT2PA-600-2+1PE Electrical Responding time Maximum continuous operating voltage UC Rated frequency Nominal discharge current In Voltage protection level Up Residual voltage at 5 kA (8/20) s Maximum discharge current Imax Permissible back-up fuse Maximum short-circuit current Isc Residual current IPE Mechanical Frame size Device height Device width Weight Upper and lower lift terminal capacity fine- / solid strand Tightening torque of terminal screws Permitted ambient temperature Mounting Degree of protection Polution degree Auxiliary switch Electrical Rated insulation voltage Rated frequency Switching contact Minimum voltage per contact Rated operational current Min. admissible power Mechanical Terminal capacity fine- / solid strand Tightening torque of terminal screws L+ -> L- / L -> PE 25 ns / 100 ns 600 V DC DC 15 kA (8/20) s 3 kV / 3 kV 2.5 kV / 2 kV 30 kA (8/20) s 80 A 20 A 45 mm 90 mm 53.4 mm 318 g SPPT2PA-1000-2+1PE(-AX) 25 ns / 100 ns 1000 V DC DC 15 kA (8/20) s 5 kV / 3 kV 4 kV / 2 kV 30 kA (8/20) s 80 A 20 A 45 mm 90 mm (99 mm) 53.4 mm 318 g (323 g)

L+ -> L- / L -> PE L+ -> L- / L -> PE

4-25/4-35 mm2/AWG11-2 4-25/4-35 mm2/AWG11-2 4.5 Nm 4.5 Nm -40C up to +80C -40C up to +80C quick fastening on DIN rail IEC/EN 60715 IP20 IP20 2 2

250 V 50/60 Hz 1 CO 5 V AC/DC 1.5 A / 250 V AC 1.5 A / 30 V DC 5 mA / 5 V

1.5/1.5 mm2/AWG28-16 0.25 Nm

Dimensions (mm)

Application hints according to EN 50539-12

30

Photovoltaic - Surge Protection


Auxiliary Switch for Surge Arresters ASAUXSC-SPM
Field of application: For mounting onto surge protective devices for external defect message transmission Design basically in accordance with IEC 60947-5-1 Can be mounted subsequently Suitable for SPMT2PA

AC

Connection diagram

Technical Data
Electrical Rated insulation voltage Rated frequency Switching contact Minimum voltage per contact Rated operational current AC12 Maximum back-up fuse Overvoltage category Pollution degree 250 V 50/60 Hz 1 CO 24 VAC 2A/250VAC 2 A gL IV 2 Mechanical Frame size Device height Device width Weight Mounting Degree of protection, built-in Finger and hand touch safe acc. to Upper and lower terminals Terminal capacity Tightening torque of terminal screws 45 mm 80 mm 8.8 mm 41 g screw-mounting IP40 BGV A3, VE-EN 6 lift terminals 2 x 2.5 mm2 0.8 - 1 Nm

Dimensions (mm)

Application Examples

SPCT2-280/2

SPBT12-280/3

SPCT2-460/4

Lead-Through Terminal for Surge Protective Devices, SPD-type 2 (Class C), ASLTT-63
The lead-through terminal permits orderly wiring of SPDs types 2 (class C). It serves as lead-through terminal in circuits requiring vertical connections from the upper to the lower SPD connection level. 1-pole Suitable for standard busbar connection to EATON switchgear

Connection diagram

Technical Data
Electrical Rated voltage Rated current Rated frequency 690V AC/DC 63 A 50/60 Hz Mechanical Frame size Device height Device width Mounting Degree of protection, built-in Finger and hand touch safe acc. to Upper and lower terminals Terminal capacity Busbar thickness Tightening torque of terminal screws 45 mm 80 mm 17.5 mm quick fastening on DIN rail IEC/EN 60715 IP40 BGV A3, VE-EN 6 lift and open-mouthed terminals 1 - 25 mm2 0.8 - 2 mm 2.4 - 3 Nm

Dimensions (mm)

Application Example / Connection type 2 acc. to IEC 60364-5-53 Clause 534

SPCT2-3353+NPE

ASLT T-63

31

Surge Protection
Busbars Z-GV-U/
Busbars Z-GV-U/ permit to implement customary SPD combinations Suitable for SPI-..., SPB-D-125 The rated cross-section of Z-GV-U/ is 16 mm2 The busbars must be cut to length in some cases

Technical Data
Electrical Rated voltage Rated current Models 230/400 V, 50/60 Hz 63 A Mechanical Busbar cross section 16 mm2 Cu

Busbars ZV-KSBI
Busbars ZV-KSBI permit to implement customary SPD combinations Suitable for SPB-..., SPC-..., Z-D63 The rated cross-section of ZV-KSBI is 16 mm2 The busbars must be cut to length in some cases

Technical Data
Electrical Rated voltage Rated current Models 230/400 V, 50/60 Hz 63 A Mechanical Busbar cross section 16 mm2 Cu

Marking Label SPI-BZS-L/N/PE


Can be affixed to SPI-..., SPB-D-125 Size 7 x 17mm Colour: white

32

Surge Protection
SPD Class D, Surge Protective Device SPD-S-1+1, SPD-S-280/2
Field of application: For fine protection of user equipment against transient overvoltage For mounting on DIN rails in distribution boxes for electrical installation No decoupling from upstream surge protection in the low voltage distribution system required Test class III according to IEC 61643-1+A1 SPD-type T3 according to EN 61643-11 Suitable for high back-up fuse 63 A gL / C 63 Auxiliary switch SPC-S-HK for remote message transmission can be mounted onto the device

Technical Data
SPD-S-1+1 Electrical Mechanical coding Responding time (rate of voltage rise 5 kV/s) Maximum continuous operating voltage UC Temporary overvoltage test value UT (5 s) (200 ms) Rated frequency Open circuit voltage UOC Voltage protection level Up at UOC Nominal discharge current In Voltage protection level Up at In Maximum discharge current Imax Follow current interrupt rating Ifi Permissible back-up fuse Maximum short-circuit current Connection diagram x x L-N/N-PE/L-PE L-N/N-PE L-N/L-PE N-PE L-N/N-PE/L-PE L-N/N-PE/L-PE L-N/N-PE/L-PE L-N/N-PE/L-PE L-N/N-PE/L-PE N-PE yx < 25ns/< 100ns/< 100ns 335VAC/260VAC 350VAC/416VAC 1200VAC 50/60 Hz 5kV 1000V/ 900V/ 1000V 2,5kA (8/20)s 1000V/ 700V/ 1000V 10kA (8/20)s 100 Ar.m.s. C63 10 kAr.m.s. xx < 25ns 280VAC 350VAC/416VAC 1200VAC 50/60 Hz L1-L2(N)/L2(N)-PE/L1-PE 10kV L1-L2(N)/L2(N)-PE 950V L1-L2(N)/L2(N)-PE 5kA (8/20)s L1-L2(N)/L2(N)-PE 950V L1-L2(N)/L2(N)-PE/L1-PE 10kA (8/20)s L1-L2(N)/L2(N)-PE/L1-PE L1-L2(N)/L2(N)-PE L-N/L-PE N-PE SPD-S-280/2

63 AgL 50 kAr.m.s.

Mechanical Mechanical coding of base Frame size Device height Device width Weight Upper and lower lift terminal capacity Open-mouthed terminals at both sides for busbar thickness up to Tightening torque of terminal screws Permitted ambient temperature Mounting Degree of protection (built-in)

yx 45 mm 80 mm 35 mm 220 g 1 - 25 mm2 1.5 mm 2.4 - 3 Nm -40C to +70C quick fastening on DIN rail IEC/EN 60715 IP40

xx 45 mm 80 mm 35 mm 220 g 1 - 25 mm2 1.5 mm 2.4 - 3 Nm -40C to +70C IP40

Dimensions (mm)

Application Examples

33

Surge Protection
19 Outlet Strips NWS-STL/19/7F
Installation onto 19 rails Installation height: 1U Diagonally arranged socket outlets with earthing contact according to DIN 49440 or NF-C61314 (UTE), 16A / 250VAC Connection cable of 2.5 m H05VV-F 3G1,5 mm2 with an angled connector Max. power consumption: 3680 W Degree of protection: IP20 Temperature range: -5C to +40C Dimensions: 482,6x44x44,45mm (WxDxH) Material: Enclosure made of aluminium, front cover made of plastic similar to RAL 7035 Weight: approx. 0.9 kg Scope of delivery: 1 Outlet strip incl. 19 fixing bracket, different fixing material

19" Outlet Strips with Surge Protection SPD-STL/19/7F-S/BL


Can be mounted on 19 rails Installation height: 1U Diagonally arranged socket outlets with earthing contact according to DIN 49440 or NF-C61314 (UTE), 16A / 250VAC Connection cable of 2.5 m H05VV-F 3G1,5 mm2 with an angled connector On/Off switch, 2-pole, lit Max. power consumption: 3680 W Degree of protection: IP20 Temperature range: -5C up to +40C Surge protection tested according to IEC 61643-1 (Class: SPD Type 3) Response time: < 25 ns Dimensions: 482,6x44x44,45mm (WxDxH) Material: Enclosure made of aluminium, front cover made of plastic similar to RAL 7035 Weight: approx. 0.9 kg Scope of delivery: 1 Outlet strip incl. 19 fixing bracket, different fixing material

Surge Protection Outlet Strips with High-Grade Filter and Energy Absorption for full Equipment Protection SPD-STL/6F-S
Suitable for wall-mounting in indoor areas A 19 fixing bracket is available as an option for mounting the strip in a cabinet Diagonally arranged socket outlets with earthing contact according to DIN 49440, 10A / 250VAC Connection cable of 1.0 m H05VV-F 3G1,0 mm2 with an angled connector On/Off switch with MCB that can be reset Max. power consumption: 2500 W Degree of protection: IP20 Temperature range: -15C to +70C Surge protection tested according to IEC 61643-1 (Class: SPD Type 3) Response time: < 1 ns Dimensions: 390x42x52mm (WxDxH) Material: Enclosure made of plastic similar to RAL 7021 Weight: approx. 0.4 kg Scope of delivery: 1 Multiple outlet strip

19" Fixing Bracket for SPD-STL/6F-S


Fixing bracket for mounting surge protection outlet strips SPD-STL/6F-S on a 19 frame Mounting on 19 rails Installation height: 1U Material: Steel sheet, powder-coated RAL 7035 Weight: approx. 0.4 kg Scope of delivery: 1 Fixing bracket, different fixing material

34

Surge Protection
Earthing/Equipotential Bonding Equipotential Bonding Bar PAS-7x16
Dimensions (mm)

Earthing Bar for Antenna Lines PAS-HF-6


Dimensions (mm)

Earth Clip EBS


Dimensions (mm)