INDUSTRIAL ELECTRONICS

INDUSTRIAL INTERFACE CARD mod. MFI-U/EV

THEORY AND EXERCISES

TEACHER/STUDENT handbook

31045 MOTTA DI LIVENZA (Treviso) - ITALIA Via Postumia, 16

COPYRIGHT BY ELETTRONICA VENETA & INEL SPA

MFU$01E0.DOC

CONTENTS

SAFETY RULES 1 INTRODUCTION 2. Industrial Interface Card MOD. MFI-U/EV 3. Software Installation 4. Development Software 1 3 4 8

APPENDIX A: Examples of application APPENDIX B: Use of the MPTEXT APPENDIX C: Connection of the modules MPT

13 25 27

SAFETY RULES

SAFETY RULES

Keep this handbook at hand for any further help. After the packaging has been removed, set all accessories in order so that they can be easily found. Check that the card or the unit is integral and shows no visible damage. Before connecting the equipment to the power supply, be sure that the power supply wires are properly connected to the power supply. This equipment must be employed only for the use it has been conceived, i.e. as educational equipment, and must be used under the direct supervision of expert personnel. Any other use is not proper and therefore dangerous. The manufacturer cannot be held responsible for eventual damages due to inappropriate, wrong or unreasonable uses.

PRECAUTIONS MFI-U/EV When the version MFI-U/EV (USB port connection) is used, before carrying out the connection between the unit and the USB port, be sure that the software Visual Designer is in execution; before disconnecting the unit from the USB port, be sure to exit the software Visual Designer.

1. INTRODUCTION

1. INTRODUCTION

INDUSTRIAL INTERFACE UNIT The industrial interface unit enables to transform any Personal Computer into an equipment of industrial kind for applications of data acquisition, analysis, monitoring and control. The obtained industrial system becomes an ideal unit for data acquisition of general use, tests, measurements and for the transmission of commands to external systems (control and supervision applications). The interfacing to the Personal Computer enables the development of exercises for data acquisition, supervision and process control. Depending on the characteristics of the control software of the industrial interface, you can make the supervision of the inputs and outputs of the modules MPT/EV and, in case of process control, only the inputs coming from transducers and the outputs toward the actuators can be employed to carry out a PID process control with algorithm provided directly by the software. The closed loop control chain present in the modules MPT/EV with speed and position, flow and level, luminosity, temperature and pressure process control enables the study of the typical problems of automatic controls, such as the stability, the response speed, the search for the best setting of the PID controller in line with the modern industrial applications. The control software of the industrial interface make it possible to facilitate the analysis made directly on the modules with the use of virtual instruments.

-1-

1. INTRODUCTION

Hardware The acquisition system is configured with the industrial interface: 1. portable unit communicating via USB line mod. MFI-U

Application Software The system is provided with a series of software programs for the applications with the modules of the Student Trainer MPT/EV. Such programs enable the acquisition of the input variables and the processing of the control commands, the control and supervision of industrial processes reproduced by the modules. Development Software The development software (optional) is a powerful and simple instrument to create applications of data acquisition, tests, instruments, measurements and control on Personal Computer. It enables to change the provided applications programs and to develop personalized applications.

-2-

2. Plug-in card MFI-I/EV

2. INDUSTRIAL INTERFACE UNIT MOD. MFI-U/EV

The Industrial interface unit is connected to the Personal Computer via a standard USB port. Technical characteristics Analog inputs Number of channels: 16 12-bit single-ended Voltage range: 10Vdc Maximum voltage: 15Vdc Analog outputs Number of channels: 2 8-bit single-ended Voltage range: 10Vdc Error: 1.5% Digital I/O Number of IN channels Number of OUT channels Counters: Number of channels: Accessories: USB connection cable Drivers and test program 8 TTL 8 TTL 1 TTL

-3-

2. Unit MFI-U

3. SOFTWARE INSTALLATION

3.1 Introduction The development software enables to use the application programs through RUN.EXE, to change the provided application programs and to create new personalized applications through DIAGRAM.EXE. DIAGRAM.EXE is a powerful and simple instrument to create applications for data acquisition, tests, instruments, measurements and control on Personal Computer. It is sufficient to plot a block diagram of the application, specifying the parameters for the functions and to enter the application. A large number of function blocks is available that can be combined to create a large number of even very complex applications. 3.2 Installation of the Main software First, the software Visual Designer MFIDEV must be installed, if separately provided, otherwise you must follow the described procedure from the single CD-ROM of the application MPTEXT: insert the CD-ROM software MPTEXT into the PC double click on the folder\ Vd-prg \ Install enter the program Setup.exe Follow the guided installation procedure Note: During this phase the following error message could be shown: String variable is not large enough for string Check the string declarations Error 401 In case this message should be shown, it must be ignored ( press OK ) The program is installed into the folder: Programs\Program Files\Visual Designer\Visual Designer 4.0

3.3 Drivers installation for Unit MFI-U Before proceeding with the data acquisition via the Unit MFI-U, the Drivers must be installed, following the described mode: Insert the CD-ROM software MPTEXT into the PC double click on the folder \ Drivers enter the program SetDrv2k.exe or SetDrv98.exe depending on whether the operative system is Win2000/XP or Win98/Me. -4-

3. SOFTWARE INSTALLATION

Follow the guided installation procedure.

3.4 Installazione Nuovo Hardware Dopo aver installato i Drivers occorre eseguire il riconoscimento del nuovo Hardware: Collegare lUnit MFI-U al computer con il cavo USB Sul monitor comparir la finistra: Trovato Nuovo Hardware. Sul monitor comparir la finestra: Installazione guidata Nuovo Hardware. Selezionare: si, solo in questa occasione. Andare avanti fino alla fine. 3.5 Installation of the Blocks GpADP for Visual Designer Before using the modules MPT via the unit MFI-U, the I/O blocks must be installed, following the described mode: insert the CD-ROM software MPTEXT into PC double click on the folder \ MPTEXT enter the program MFUsetup.exe Follow the guided installation procedure. If at the end this message is shown: Setup Generated by Setup Factory 4.0 Click on Do not send. If at the end this message is shown: Error creating MsgWndClass Click on OK. Block GpADP per Visual Designer

I/O \ GpADP

The block GpADP controls the interface with the card GpADP used with the software Visual Designer. It is present with the abbreviation GpADP Device in the unit called IO. Once selected it appears on the screen with the following icon:

The block does not require parameters and is characterized by the following Inputs and Outputs:

-5-

2. Unit MFI-U

Block INPUTS Code GpADP Digital Outputs Kind of data Description unsigned int The datum provided to this input is sent to the Digital outputs of the card GpADP. It is of the 16-bit 'unsigned int' kind. Each bit represents the state of one of the 16 outputs. Use a block of the Bit Pack kind in case the Digital outputs of the card should be provided by more blocks. int The datum supplied to this input is sent to the Analog Output No. 1 of the card GpADP. It is of the 'int' kind with range between -128 and +127, corresponding to output voltage values between -10V and +10V. The datum provided to this input is sent to the Analog Output N.1 of the card GpADP. It is of the 'int' kind and it ranges between -128 and +127, corresponding to output voltage values between -10V and +10V.

GpADP Analog Output 1

GpADP Analog Output 2

int

Block OUTPUTS Code GpADP Digital Inputs Kind of data Description unsigned int The datum provided by the this output comes from the Digital inputs of the card GpADP. It is of the 16-bit 'unsigned int' kind. Each bit represents the state of the one of the 16 inputs. Use a block of the Bit Unpack kind in case the Digital Inputs of the card should be sent to more separate blocks. GpADP Analog Input 1 int The datum provided by this output comes from the Analog input No. 1 of the card GpADP. It is of the 'int' kind with range between -2048 and +2047, corresponding to input voltage values between -10V and +10V. GpADP Analog Input 16 int The datum provided by the this output comes from the Analog input No. 1 of the card GpADP. It is of the 'int' kind with range between -2048 and +2047, corresponding to input voltage values between -10V and +10V.

-6-

3. SOFTWARE INSTALLATION

3.6 Installation in the Start Menu of the executable Exemples MPTEXT Before proceeding with the use of the modules MPT via the Unit MFIU, the application Programs concerning the modules to be controlled must be installed, following the described mode: insert the CD-ROM software MPTEXT into the PC double click on the folder \ MPTEXT enter the program e.g. APLsetup.exe Follow the guided installation procedure.

3.7 Installation of the executable Applications MPTEXT Before proceeding with the use of the modules MPT via the Unit MFIU, the application Programs concerning the modules to be controlled must be installed, following the described mode: insert the CD-ROM software MPTEXT into the PC double click on the folder \ MPTEXT enter the program e.g. G34setup.exe Follow the guided installation procedure. Repeat the last two commands for all modules MPT of the laboratory.

Attention: when the Unit MFI-U is not connected to the computer it shown the message: Node: GpADP Devices 1 returned code: 40001 from LOAD_MSG.

-7-

4. Development Software

4. DEVELOPMENT SOFTWARE

The development software allows modification of the provided application programs and the development of personalized applications. It consists of a simple but powerful data acquisition, tests, instruments, measurements and control generator on Personal Computer. It is sufficient to plot a block diagram of the application, specifying the parameters for the functions and to enter the application. A large number of function blocks is available that can be combined to create a large number of even very complex applications. 4.1 General function blocks The following function-blocks are available:

Communication IEE488 Inputs Outputs RS-232 Inputs Outputs Comparison Comparison Alarm Trigger Alarm window Data Conversion Accumulator Whole-digital conversion Concatenation Extraction Decimal Delay Unit modification Multiplexer Compression Selection Type conversion Database Data export from a generated database to Microsoft Access DDE Data reception from other Windows applications Commands transmission to other Windows applications -8-

4. Software di Sviluppo

Display Analog instruments Message displays Bars displays Recorders Digital instruments Lists display Multi-channel recorders Video clip displays XY displays XY recorders DSP Correlation FFT Filters Power spectrum I/o Files Reading files ASCII Writing files ASCII Files generation for other applications Generation of a file name Reading file Writing file Generators Constant generator Pulse generator Random generator Sine generator I/O HARDWARE Counter 8254 Card selection Analog inputs DMA analog inputs Analog outputs DMA analog outputs Burst generator Counter Digital inputs 8-bit digital inputs DMA digital inputs Digital outputs 8-bit digital outputs DMA digital outputs Period measurement TTL pulse generator Thermocouple -9-

4. Development Software

Logic AND Counter increment NAND NOR NOT Single pulse OR Set Reset Flip Flop XOR Mathematics Absolute value Sum Values selection Derivatives Division Equation Integrals Inverse Ln Log Mean Multiplication LINEAR RELATION Mx+B Power Square root Subtraction Table X^Y Measurement Histogram Maximum Average/addition Minimum Peak Sort RMS Memory functions 16 bit I/O from hardware sites 16 bit I/O from hardware sites 16 bit in from memory address sites 16 bit out from memory address sites 32 bit in from memory address sites 32 bit out from memory address sites 8 bit I/O from hardware sites 8 bit I/O from hardware sites - 10 -

4. Software di Sviluppo

8 bit from memory address sites 8 bit from memory address location

Different functions Function call Buffer export Buffer extraction Buffer import Block memorization Block charging PID RETURN of a function RUN TIME TIMER Wait BMP background Display Special programming blocks Continue? Do...while Select ... Case Subprogram String conversion Capital/lower case conversion Character search String search String comparison String chain String conversion String redimensioning String format String interpretation String length String compacting String compacting

User interface Input from keyboard Audio messages Beep messages Number editing Interval selection with Cursor Selection with Pushbutton User Prompt DASport p8254Counter pAnalogInput - 11 -

4. Development Software

pAnalogInputHS pAnalogOutput pAnalogOutputHS pBatteryStatus pDigitalInput pdigitalInputBit pDigitalOutput pDigitalOutputBit pThermocouple

Once the function blocks with their parameters are selected, they must be functionally connected to establish the data flow from block to block. For applications requiring the execution of blocks in a specific order, it is possible to establish a flow of preferential program connecting the blocks with flow execution lines. Systems REQUISITES PC compatible Pentium VGA graphic card (suggested graphic accelerator card) 16MB of minimum RAM (suggested 32MB) Microsoft Windows 95/98

The ambient is Windows 95/98

- 12 -

APPENDIX A: Example of application #2

APPENDIX A. EXAMPLES OF APLLICATIONS

A1. EXAMPLE OF APPLICATION #1 Acquisition and display of the input signal ANALOG IN0. Connect the unit MFI-U to the computer via the USB cable. Purpose of the exercise is to display the value, expressed in C, of the input voltage on the ANALOG IN0. The phases to be carried out to proceed are the following: - signal acquisition from the MFI-U (the input analog signal to the MFIU is transmitted to the software as whole number); - conversion of the value from whole number to 0-10V; - conversion of the value from 0-10V to C; - display of the obtained value. The development of an application requires the use of the VISUAL DESIGNER - Diagram packet for the generation of application programs. Once the Diagram development ambient is entered, carry out the following phases: 1) Select Blocks, IO, GpADP Device 2) Select Blocks, Convert, Type conversion 3) Specify that the concerned parameter must be float kind:

Fig. A 1.1 4) Link the Block GpADP Device to the block Type conversion - 13 -

APPENDIX A. Example of application #2

5) Specify the card/channel parameters (E.g. Input 0):

Fig. A 1.2 6) Select Blocks, Math, mx+b, 7) Specify the parameters of the block mx+b:

Fig. A 1.3 Note: m is fixed equal to 0.004885 while b equal to 0 (the zeroes correspond while 10V correspond to 2047). 8) Link the Block Type conversion to the block mx+b; - 14 -

APPENDIX A: Example of application #2

Fig. A 1.4 9) Select Blocks, Math, mx+b 10) Specify the parameters of the block mx+b:

Fig. A 1.5 Note: m is fixed equal to 17 while b equal to -50 (we supposed that 0V corresponds to 50C and 10V corresponds to 120 C).

- 15 -

APPENDIX A. Example of application #2

11) Link the Block mx+b inserted before with the just inserted block mx+b:

Fig. A 1.6 12) Select Blocks, Display, Digital meter 13) Set the parameters label, format, decimals, etc.:

Fig. A 1.7

- 16 -

APPENDIX A: Example of application #2

14) Connect the output of the block mx+b to the display instrument.

Fig. A 1.8 The general diagram takes the following structure:

Fig. A 1.9

- 17 -

APPENDIX A. Example of application #2

15) Compile selecting the icon:

to generate the executable application 16) Save the application specifying the name The following is shown:

Fig. A 1.10 In order to complete the exercise, the temperature values can be displayed, too, respectively, in whole number and in volt. On this purpose, repeat the procedure related to the command Display Digital Meter linking, each time, the icon related to the parameter to be displayed on the icon Digital Meter.

- 18 -

APPENDIX A: Example of application #2

EXAMPLE OF APPLICATION #2 Setting the fan speed and transmission to an analog output channel. Connect the unit MFI-U to the computer through the USB cable. The purpose of the exercise is to set the value, expressed in volt, of a fan speed and to transmit it to the ANALOG OUT0. The phases to be carried out to proceed are the following: - setting the fan speed value from the keyboard - displaying the set value on a proper graph - transmitting the set value to the MFI-U. The development of an application requires the use of the VISUAL DESIGNER - Diagram packet for the generation of application programs. Once the Diagram development ambient is entered, carry out the following phases: 1) Select Blocks, Userlntf, Slider

Fig. A 2.1 2) Select Blocks, Display, Analog Meter 3) Set the parameters of the display instrument

- 19 -

APPENDIX A. Example of application #2

4) Connect the output of the block Slider to the block Analog Meter

Fig. A 2.2 5) Select Blocks, Math, mx+b 6) Specify the parameters of the block mx+b:

Fig. A 2.3 Note: m is fixed equal to 6.35 while b equal to 0

- 20 -

APPENDIX A: Example of application #2

7) Link the block Slider to the block mx+b:

Fig. A 2.4 8) Select Blocks, Convert, Type conversion 9) Specify that the concerned parameter must be integral type:

Fig. A 2.5

- 21 -

APPENDIX A. Example of application #2

10) Link the block mx+b to the block Type conversion:

Fig. A 2.6 11) Select Blocks, IO, GpADP Device 12) Link the block Type conversion to the block GpADP Device 13) Specify the card/channels parameters (Es. AnalogOutput1):

Fig. A 2.7

- 22 -

APPENDIX A: Example of application #2

The general diagram takes this structure:

Fig. A 2.8 14) Compile selecting the icon: to generate the executable application 15) Save the application specifying the name This is shown:

Fig. A 2.9

- 23 -

APPENDIX A. Example of application #2

In order to complete the exercise you can display the fan speed in rpm. On this purpose, transform the data from volt into rpm linking the icon related to the Slider to a proper function mx+b and then linking this to the icon Digital Meter. N.B.: Obviously in order to make the program transmit the speed values to the fan, the Trainer FCBA/EV must be switched on and connected via USB cable to the remote computer; besides the manual switch related to the speed control of the fan must be set to PC.

- 24 -

APPENDIX B. Use of the applications for the MPT modules

APPENDIX B. USE OF THE APPLICATIONS MPTEXT

B.1 Use of the applications MPTEXT 1) Select from Start, Programs, MPTEXT ( interf. MFI-U ), enter MFIUtest or another application e.g. G34RTSPVUSB.fco. 2) Or Select to carry out the application, select from Start, Programs, VISUAL DESIGNER enter VISUAL DESIGNER - RUN

Fig. B 1.1

Select File and then the application MFIUtest1.fco

- 25 -

APPENDIX B. Use of the applications for the MPT modules

Fig. B 1.2 The main screen for the testing unit MFI-U is shown

- 26 -

APPENDIX C. Connection of the MPT modules

APPENDIX C. Connection of the MPT modules

The unit MFI-U/EV TERMINAL BOARD TB1/EV is provided with: 16 ANALOG INPUTS, 2 ANALOG OUTPUTS. 8 DIGITAL INPUTS and 8 DIGITAL OUTPUTS. 1 COUNTER CK IN. This unit must be connected to the PC through an USB cable.

Fig. C 1.1

- 27 -

APPENDIX C: Connections of the MPT modules: G36A/EV

G36A/EV DOUBLE SPEED RING POSITION CONTROL

Step response: Process Supervision Process Supervision file: G36pospvusb.fco Connections on module: 4-21, 6-8, 7-23, 9-10, 26-27, 29-30, 11-12, 13-14, 15-16, 17-18. Connections between module and MFI-U: 23-Analog IN0, 5-Analog OUT0, GND-GND

Process Control

file: G36popidusb.fco Connections on module: 26-27, 29-30. Connections between module and MFI-U: 21-Analog IN0, 23-Analog IN1, 18-Analog OUT0, GND-GND PID PARAMETERS: P=10, I=1, D=10 ___________________________________________________

Step response: Process Supervision file: G36vespvusb.fco Connections on module: 6-10, 11-12, 13-14, 15-6, 4-23, 27-18, 29-30, 26-27. Connections between module and MFI-U: 23-Analog IN0, 5-Analog OUT0, GND-GND

Process Control

file: G36vepidusb.fco Connections on module: 26-27, 29-30. Connections between module and MFI-U: 23-Analog IN0, 18-Analog OUT0, GND-GND - 28 -

APPENDIX C: Connections of the MPT modules: G36A/EV

PID PARAMETERS: P=1, I=1, D=10

- 29 -

APPENDICE C: Collegamenti dei moduli MPT: G35/EV

G35/EV PRESSURE CONTROL TRANSDUCER

Step response

Process Supervision

file: G35spvusb.fco Connections on module: 9-10, 13-14, 5-8, 4-21. Connections between module and MFI-U: 21-Analog IN0, 3-Analog OUT0, GND-GND

Process Control

file: G35pidusb.fco Connections between module and MFI-U: 21-Analog IN0, 14-Analog OUT0, GND-GND PID PARAMETERS: P=10, I=1, D=10

Sensor Characteristic Connections on module: 2-3, 5-8, 9-10, 13-14, 5-8, 4-21. Connections between module and MFI-U: 21-Analog IN0, GND-GND

- 30 -

APPENDIX C: Connections of the MPT modules: G36A/EV

G29/EV PROXIMITY SENSORS

Sensors characterisctcs

Capacitive Sensor

file: G29catusb.fco Connections between module and MFI-U: 12-Analog IN0, GND-GND

Linear Inductive Sensor file: G29iltsusb.fco Connections between module and MFI-U: 3-Analog IN0, GND-GND

ON-OFF Inductive Sensor file: G29iotsusb.fco Connections between module and MFI-U: 9-Analog IN0, GND-GND

- 31 -

APPENDIX C: Connections of the MPT modules: G29/EV

G25/EV G16/EV WEIGHT TRANSDUCER STEPPING MOTOR

Stepping Motor ( Unipolar Full-step 1 phase control ) file: G16ctr01usb.fco Connections on module: A1-A1, B1-B1, A2-A2, B2-B2. Set I1 to unipolar, set I2 to Full-step, set I3 to CW (COMP) Insert the TB1 adapter on the C/D connector. Connections between TB1 adapter and MFI-U: 9-Digital OUT0, 8-Digital OUT1, GND-GND.

Sensor characteristic

Sensor Characteristic

file: G25tsdusb.fco Connections between module and MFI-U: 7-Analog IN0, GND-GND

- 32 -

APPENDICE C: Collegamenti dei moduli MPT: G26/EV

G26/EV PROCESS SIMULATION

Step response

Process Supervision

file: G26spvusb.fco Connections on module: 36-2, 7-8, 9-10, 14-18, 20-21, 22-29, 34-35. Set switch RESET OFF, switch TRANSPORT LAG to SLOW, switch STAGE to SLOW, switch CONTROL OUT to ODD STAGE, set the potentiometers KP to 1.6, KI to 400, KD to O Connections between module and MFI-U: 34-Analog IN0, 2-Analog OUT0, GND-GND

Process Control

file: G26pidusb.fco Connections on module: 20-21, 22-29. Set switch RESET OFF, switch TRANSPORT LAG to SLOW, switch STAGE to SLOW, switch CONTROL OUT to ODD STAGE, set the potentiometers KP to 1.6, KI to 400, KD to O Connections between module and MFI-U: 34-Analog IN0, 18-Analog OUT0, GND-GND PID PARAMETERS: P=2.8, I=0.01, D=10

- 33 -

APPENDICE C: Collegamenti dei moduli MPT: G34/EV

G34/EV TEMPERATURE CONTROL & TRANSDUCERS

Step response

Process Supervision

file: G34rtspvusb.fco RTD transducer Power the 24-Vac section of the module with the power supply PS2A/EV Connections on module: 9-11, 28-4-10. Set switch METER to RTD-TH, switch RTD to ON, switch I cooler to AUT Connections between module and MFI-U: 28-Analog IN0, 17-Analog IN1, 11-Analog IN2, 3-Analog OUT0, GND-GND

Process Control

file: G34rtpidusb.fco RTD transducer Power the 24-Vac section of the module with the power supply PS2A/EV Connections on module: 10-28. Set switch METER to RTD-TH, switch RTD ON, switch I cooler to AUT Connections between module and MFI-U: 28-Analog IN0, 11-Analog OUT0, GND-GND PID PARAMETERS: P=10, I=1, D=1

- 34 -

APPENDICE C: Collegamenti dei moduli MPT: G30A/EV G30B/EV

G30A/EV G30B/EV LEVEL & FLOWRATE CONTROL Level control Step response Process Supervision file: G30lispvusb.fco Connections on module G30B: 4-5, 6-7, 8-9, 10-11, 12-13. Remove the jumper near P1 Set switch I1 to LEVEL, set the potentiometers KP to 5th notch, KI to 1st notch, KD to 3rd notch Connections on module G30A: 6-7, 8-14. Set switch I1 to LEVEL, I3 to FREQ. I4 ON. Connections between G30B and G30A: 3-6, 15-12V/1.5A, GND-GND. Connections between module G30B and MFI-U: 2-Analog OUT0, GND-GND Connections between module G30A and MFI-U: 6-Analog IN0, GND-GND

Process Control

file: G30lipidusb.fco Connections on module G30A: 6-7, 8-14. Turn switch I1 to LEVEL, I3 to FREQ. I4 ON. Connections between G30B and G30A: 15-12V/1.5A, GND-GND. Connections between module G30B and MFI-U: 13-Analog OUT0, GND-GND Connections between module G30A and MFI-U: 6-Analog IN0, GND-GND - 35 -

APPENDIX C: Connections of the MPT modules: G30A/EV G30B/EV

PID PARAMETERS: P=10, I=0.01, D=10

- 36 -

APPENDICE C: Collegamenti dei moduli MPT: G30A/EV G30B/EV

G30A/EV G30B/EV LEVEL & FLOWRATE CONTROL Flowrate control Step response Process Supervision file: G30pospvusb.fco Connections on module G30B: 4-5, 6-7, 8-9, 10-11, 12-13. Remove the jumper near P1 Set switch I1 to FLOWRATE, set the potentiometers KP to 5th notch, KI to 1st notch, KD to 3rd notch Connections on module G30A: 19-20, 19-14. Set switch I1 to LEVEL, I3 to FREQ. I4 ON. Connections between G30B and G30A: 3-22, 15-12V/1.5A, GND-GND. Connections between module G30B and MFI-U: 2-Analog OUT0, GND-GND Connections between module G30A and MFI-U: 22-Analog IN0, GND-GND

Process Control

file: G30popidusb.fco Connections on module G30A: 19-20, 19-14. Turn switch I1 to LEVEL, I3 to FREQ. I4 ON. Connections between G30B and G30A: 15-12V/1.5A, GND-GND. Connections between module G30B and MFI-U: 13-Analog OUT0, GND-GND Connections between module G30A and MFI-U: 22-Analog IN0, GND-GND - 37 -

APPENDIX C: Connections of the MPT modules: G30A/EV G30B/EV

PID PARAMETERS: P=2, I=0.10, D=2

- 38 -

APPENDICE C: Collegamenti dei moduli MPT: G13/EV

G13/EV LIGHT CONTROL

Step response Process Supervision file: G13luspvusb.fco Connections on module: 4-5, 6-7, 10-11, 3-15, 13-18. Set switch I1 in the B position. Set the potentiometers KP to 5 notch, KI to 1 notch, KD to 3 notch Connections between module and MFI-U: 14-Analog OUT0, 18-Analog IN0, GND-GND

Process Control

file: G13lupidusb.fco Connections on module: Set switch I1 in the B position. Connections between module and MFI-U: 11-Analog OUT0, 18-Analog IN0, GND-GND PARAMETRI PID: P=10, I=0.01, D=10

- 39 -