7SR224 Relay
L1 L2 L3 L4 L5 L6 L7 L8 A PH Fault B PH Fault C PH Fault Gnd Fault SEF L11 Lockout Aux Power OK Recloser OK L12 Hot Line Tag ON L18 Reclose ON L17 L10 Close L16 Inst Protn OFF L9 Open L15 All Protn OFF

L13 C

Gnd Fault L19 Protn OFF

L14

SEF L20 Protn OFF

Trip & Reclose

Item A B C LED L1 L2 L3 L4 L5 L6 L7 L8

Description MLFB model number Ratings label Programming port Description Phase A target Phase B target Phase C target

LED L9 L10 L11 L12 L13 L14 L15

Button F1 F2 F3 F4 F5 F6 F7 F8 F9 F10 F11 F12

Description Push-to-open recloser Push-to-close recloser Push-to-toggle reclose functionality ON/OFF Push-to-toggle hot line tag ON/OFF Push-to-toggle ground fault protection ON/OFF Push-to-toggle SEF protection ON/OFF Push-to-toggle all protection ON/OFF Push-to-toggle instantaneous protection ON/OFF User defined User defined User defined Push-to-trip and reclose recloser Description CT secondary current (1 A for recloser) 50 Hz/60 Hz (user defined)

If associated LED is lit, status: Recloser is OPEN Recloser is CLOSED Reclose functionality is ON Hot line tag is ON Ground fault protection is OFF SEF protection is OFF All protection is OFF Instantaneous protection is OFF User defined User defined User defined ----

Ground fault target Sensitive earth fault (SEF) target Recloser is locked out AC input power to control cubicle ok Capacitors charged and system ready to reclose L16 L17 L18 L19 L20 Item In Fn Vn Vx BI Config Serial No.

Voltage supplied to relay from voltage sensors Power supply voltage range (dc volts) Voltage to activate a binary input Firmware revision number Serial number

01: 1/4/2012 TGH 02/12 DR: _______ TGH 02/12 CH: _______ ---AP: _______ Similar To: Scale: NONE Sheet: 1 of 4

Type 7SR224 Relay Name: Quick Reference Guide For Three-Phase SDR Recloser Bulletin: 01-12 Part No: Issue/Rev: 01

18-671-296-402

Quick reference navigation tree guide for type 7SR relay


Press enter. If LCD screen does not say ENTER to CONTROL, press the Cancel button until it does. This will not cause the recloser to operate.

Control Mode

Settings Mode

Instrument Mode

Fault Data

CB: Open/Closed/Travel

System Config

Favorite Meters

Fault 1

AR: Out of Service IN/OUT

CT/VT Config

Current Meters

Fault 2

AR: Trip & Close

Function Config

Voltage

Fault 3

AR: Trip & Lockout

Current Protn

Frequency Meters

Fault 4

Hotline Working IN/OUT

Voltage Protn

Power Meters

Fault 5

G/F Protn IN/OUT

Supervision

Energy Meters

Fault 6

SGF Protn IN/OUT

Control & Logic

Directional Meters

Fault 7

Inst Protn IN/OUT

Input Config

Thermal Meters

Fault 8

Loss of Voltage IN/OUT

Output Config

Autoreclose Meters

Fault 9

Battery Test Initiate

Maintenance

Loss of Voltage Meters

Fault 10

Set Local

Data Storage

Maintenance Meters

Notes: For all arrows pointing push the ,

Set L or R

Communications

General Alarm Meters

Set Remote

Battery Condition

button. ,

Set Service

Capacitor Condition

For all arrows pointing


Power Quality Meters

push the
Demand Meters

button. ,

Refer to page three for detailed Settings Mode tree.

For all arrows pointing


Binary Input Meters

push the
Virtual Meters

button.

To go back one level,


Comm Meters

push the
Misc Meters

button.

To select,
Quick Logic Meters

push the

button.

01: 1/4/2012 TGH 02/12 DR: _______ TGH 02/12 CH: _______ ---AP: _______ Similar To: Scale: NONE Sheet: 2 of 4

Type 7SR224 Relay Name: Quick Reference Guide For Three-Phase SDR Recloser Bulletin: 01-12 Part No: Issue/Rev: 01

18-671-296-402

Settings mode detailed tree


Settings Mode
System Config Establish system parameters, recloser name, active settings group, viewing/editing settings group and other parameters.

CT/VT Config

Establish current transformer (CT) and voltage transformer.(VT) parameters.

Function Config

Enable functions..

Current Protn

Phase Overcurrent

67-N

51-N thru 51-4

50-1 thru 50-4

Voltage Cont O/C

Cold Load

Measured E/F

51-G thru 51G-4

50G1- thru 50G-4

Sensitive E/F

67-N

50SEF-1 thru 50SEF-4

Restricted E/F

NPS Overcurrent

46IT

46DT Undercurrent

Thermal

Voltage Protn

Phase U/O Voltage

27/59-1 thru 27/59-4

Vx U/O Voltage

NPS Overvoltage

47-1 & 47-2

Neutral Overvoltage

59NIT

59NDT

U/O Frequency

01: 1/4/2012 TGH 02/12 DR: _______ TGH 02/12 CH: _______ ---AP: _______ Similar To: Scale: NONE Sheet: 3 of 4

Type 7SR224 Relay Name: Quick Reference Guide For Three-Phase SDR Recloser Bulletin: 01-12 Part No: Issue/Rev: 01

18-671-296-402

Supervision

CB Fail

VT Supervision

CT Supervision

Settings mode detailed tree

Broken Conductor

Trip CCT Supervision

Inrush Detector

Battery Test

Capacitor Test

Power Quality

27SAG

59SWELL

Control & Logic

Autorecloser Protn

Autorecloser Config

Manual Close

Circuit Breaker

Quicklogic

Input Config

Input Matrix

Function Key Matrix

Binary Input Config

General Alarms

Output Config

Output Matrix

Binary Output Config

LED Config

Pickup Config

Maintenance

CB Counters

12T CB Wear

Output Matrix Test

Data Storage

Communications

01: 1/4/2012 TGH 02/12 DR: _______ TGH 02/12 CH: _______ ---AP: _______ Similar To: Scale: NONE Sheet: 4 of 4