AIR CONDITIONING LOAD CALCULATION FOR SCIENCE LAB

Daily range = 300C to 450C = 150C


Occupancy = 50
Lights = 1000 W fluorescent
Fans = 500W
Outdoor design condition = 450C DBT 290C WBT
Inside condition = 25 0C DBT 50%RH
Lab Area = (8) (23.04)

= 184m2

Height = 13 feet (3.96m)


Area of West Windows = (10.97) (0.9144) = 10.03m2
Film co-efficient fo =23 w/m2.k
fi =7 w/m2.k
K for glass

= 0.78 w/m.k

K for concrete = 1.73 w/m.k


K for brick

= 1.32 w/m.k

K for plaster

= 8.64w/m.k

OVERALL HEAT TRANSFER COEFFICIENT (U)


U for Outside wall (West)

9in + 1in plasters

1 1 xb x p 1
= +
+
+
U f o kb
kp
fi
1
1 0.2286 0.0127 1
=
+
+
+
U 23 1.32
8.65
7
1
= 0.00146 + 0.043 + 0.173 + 0.142
U
1
= 0.36
U
W
U = 2.775 2
m .K
U for East wall

9in + 1in plasters


1 1 xb x p 1
= +
+
+
U f o kb
kp
fi
1
1 0.2286 0.0127 1
=
+
+
+
U 23 1.32
8.65
7
1
= 0.00146 + 0.043 + 0.173 + 0.142
U
1
= 0.36
U
W
U = 2.775 2
m .K
U for North wall

9in + 1in plasters


1 1 xb x p 1
= +
+
+
U f o kb
kp
fi

1
1 0.2286 0.0127 1
=
+
+
+
U 23 1.32
8.65
7
1
= 0.00146 + 0.043 + 0.173 + 0.142
U
1
= 0.36
U
W
U = 2.775 2
m .K
U for South wall

9in + 1in plasters


1 1 xb x p 1
= +
+
+
U f o kb
kp
fi
1
1 0.2286 0.0127 1
=
+
+
+
U 23 1.32
8.65
7
1
= 0.00146 + 0.043 + 0.173 + 0.142
U
1
= 0.36
U
W
U = 2.775 2
m .K
U for Floor

1 1 0.2 0.0127 1
= +
+
+
U 7 1.73 8.65
7
1
= 0.142 + 0.1156 + 0.00146 + 0.142
U
1
= 0.40
U
W
U = 2.5 2
m .K

Mass of wall and per unit area


Outside Wall (East)
= (0.0127) (1885) +0.2286(2000) = 481.13 kg/m2
Roof
(0.2)(1900)+ (0.0127) (1885) + (0.0508) (2000) = 505.53 kg/m2
VENTILATION
Q vo /Person = 0.3 cmm
No. of occupants = 50
Q vo = 0.3x50 = 15cmm
CORRECTION FOR EQUIVALENT TEMPERATURE DIFFERENTIALS
For outdoor daily range = (45 -30) 0C
150C > 11.10C
For Medium construction

(15 11.1) 0.5

1.950C

Outside Design Temperature t0 = 450C


Inside Design Temperature ti = 250C
Difference

20 > 8.3

For (t0 - ti) of 200C = 20 8.3 = 11.70C


Total Correction = 11.7 1.95 = 9.750C
Equivalent temperature differential in 0C from Tables and incorporating correction

1 p.m

2 p.m

3 p.m

4 p.m

5 p.m

West Wall

13.65

14.35

16.45

18.25

21.35

North Wall

10.55

11.35

12.05

12.75

13.35

Estimated time for maximum cooling load:


The wall load has maximum at 1 pm. Thus the time of maximum load is most likely to be at
5 p.m.
INFILTRATION
Assume a wind velocity of 12 kmp
We have p = 0.00 47x (12)2 = 0.0678 cmm H20
No of doors = 1
Area of single door = (2.13) (0.76) = 1.6188m2
1door * 1.9813Cmm/door

= 1.9813*1.6188 = 3.20cmm

Infiltration for window = 2(1.67+0.9144)


= 5.168m
Infiltration rate for window = 2.5m3/h/m crack
Infiltration for window =5.168 * 2.5/60cmm/m
= 0.21cmm
Total Infiltration = 3.41cmm
Wall area (exposed wall)
Area of West wall

= (0.45) (3.35)

= 1.50 m 2

DETAIL LOAD CALCULATION


Sensible Heat Gain
Solar And Transmission Heat Gain Though Wall
Q

Item

UAT

Area m2

Sun gain or temp

Factor

Q (watts)

difference or
humidity
difference

West Wall

47.80

21.35

2.775

2832

North Wall

24.47

13.35

2.775

906

Transmission Gains through Other

Doors

1.61

10

0.63

10

West Glass

9.98

20

5.9

1178

North Glass

1.83

20

5.9

216

South wall

31.68

10

2.16

685

East Wall

91.24

10

2.16

1970

Floor

184

2.5

2.5

1150

Infiltration

3.41

10

20.4

695

factor

Watt

Heat gain through Glasses

Item

Area

Sun gain

West Glass

9.98

489

4880

North Glass

1.83

63

115

Internal heat gain

People

50

75

3750

Lights

1000

1.25

1250

Fan

500

500
SUBTOTAL = 20137W

Safety factor = 5%

1006

Room Sensible heat (RSH)

21143

Out door air by passed = 50x20x20.4x0.15 = 3060


Effective room sensible heat (ERSH) = 24203W
Latent Heat Gain

People

50

55

2750

Infiltration

3.41

0.006

50000

1023

SUBTOTAL = 3833
Safety factor = 5% = 191
Room Latent heat (RLH) = 4024
Outdoor air bypassed = 50*0.006x50000x0.15= 2250
Effective Room latent heat (ERLH)) = 6274
Effective Room total Heat (ERTH) = ERSH + ERLH
ERTH = 24203+6274 = 30477
=

10 TR