Documente Academic
Documente Profesional
Documente Cultură
Rigid Steel Conduit Electrical Metallic Tubing Intermediate Metal Conduit Aluminium Conduit PVC Conduit PVC Coated Conduit Flexible Steel Conduit KopexMartel PVC Pipes &fFittings
SSP Saudi Steel Pipe Company SAPPCO Saudi Plastic Products Company Wheat Land Tube Company Zindco International Metal Hose Matsushita Decoduct Kopex - Martel Al Flex - Liquidtight Egatube Appleton
Electrolines Est.
P. O. Box. 942 Yanbu Saudi Arabia Tel: +966 4 3225418 Fax: +966 4 3222213 Al-Jubail: Tel: +966 3 3632967 Fax: +966 3 3612967
Conduits
Saudi Steel Pipe
Hot-Dipped Galvanized Rigid Steel Conduit provides GREATER RESISTANCE TO CORROSION than any other conduits. Another important ADVANTAGE of using Rigid Steel Conduit is SAFETY. Its heavy wall maximises the protection against probable FIRE HAZARDS and PHYSICAL ABUSE. Hot-Dipped Galvanized Rigid Steel Conduit is manufactured strictly in conformance to the following standards: American National Standard Institute (ANSI) C 80.11977 Underwriters Laboratories Specification No. 6 (UL-6)
Conduit Tubes
ANSI C80.1 1983, Rigid Steel Conduit, Hot Dip Galvanized Nominal Size A B 15 20 25 32 40 50 65 80 90 100 125 150 1/2 3/4 1 11/4 11/2 2 21/2 3 31/2 4 5 6 Nominal Inside Diameter in. mm. 0.632 0.836 1.063 1.394 1.624 2.083 2.489 3.090 3.570 4.050 5.073 6.093 16.0 21.3 27.0 35.4 41.3 52.9 63.2 78.5 90.7 102.9 128.9 154.8 Outside Diameter in. mm. 0.840 1.050 1.315 1.660 1.900 2.375 2.875 3.500 4.000 4.500 5.563 6.625 21.3 26.7 33.4 42.2 48.3 60.3 73.0 88.9 101.6 114.3 141.3 168.3 Nominal Wall Thickness in. mm. 0.104 0.107 0.126 0.133 0.138 0.146 0.193 0.205 0.215 0.225 0.245 0.266 2.64 2.72 3.20 3.38 3.51 3.71 4.90 5.21 5.46 5.72 6.22 6.76 Length Without Coupling ft & in. m 911-1/4 911-1/4 911 911 911 911 910-1/2 910-1/2 910-1/4 910-1/4 910 910 3.03 3.03 3.02 3.02 3.02 3.02 3.01 3.01 3.00 3.00 3.00 3.00 Minimum Weight of Ten Unit Lengths With Couplings Attached lb kg 79.0 105.0 153.0 201.0 249.0 332.0 527.0 682.6 831.0 972.3 1313.6 1745.3 35.83 47.63 69.40 91.17 112.95 150.60 239.05 309.63 376.94 441.04 595.85 791.67 Pieces Per Bundle 120 84 60 42 36 26 18 14 10 8 7 5
NOTE: Applicable tolerances: Length: 1/4 in ( 6.35 mm) (without coupling) Ouside Diameter: for trade sizes 1/2 through 2 in: 0.015 in ( 0.38 mm); for trade sizes 2-1/2 through 4 in: 0.025 in ( 0.64 mm); for trade sizes 5 and 6 in: 1% Wall thickness: 12.5%
Wheatland
Wheatland, EMT, are manufactured in conformance to standards established by the American National Standard Institute (ANSI), and the Underwriters Laboratories. EMT American National Standard Institute (ANSI) C80.3-1994 Underwriters Laboratories Specification UL 797 National Electric Code Article 348
1 1 2 3
Electrolines Est. P. O. Box. 942 Yanbu Saudi Arabia Tel: +966 4 3225418 Fax: +966 4 3222213 Al-Jubail: Tel: +966 3 3632967 Fax: +966 3 3612967
Conduits
Intermediate Metal Conduit (IMC)
Intermediate Metal Conduit (IMC). IMC is made from high strength steel that is coldformed and electrically welded into a uniform tube. IMC is 25% lighter in weight than rigid conduit but it is still capable of being threaded.The exterior surface is thoroughly coated with zinc.The interior surface is protected by a specially formulated lubricating coating for easier wire pulling. IMC American National Standard Institute (ANSI) C80.6-1994 Underwriters Laboratories Specification UL 1242 National Electric Code Article 345
IMC
Weights and Dimensions
Trade Size Designator NPS 1/2 3/4 1 1/4 1/2 2 1/2 3 1/2 4 Metric 16 21 27 35 41 53 63 78 91 103 Outside Diameter in 0.815 1.029 1.290 1.638 1.883 2.360 2.857 3.476 3.971 4.466 mm 20.7 26.1 32.8 41.6 47.8 59.9 72.6 88.3 100.9 113.4 Wall Thickness in .078 0.83 .093 .095 .100 .105 .150 .150 .150 .150 mm 1.98 2.10 2.36 2.41 2.54 2.67 3.81 3.81 3.81 3.81 Wheatland Nom.Wt. Feet Per 10 Unit Lengths Per with Couplings Bundle lb kg 62 84 119 158 194 256 441 543 629 700 28.1 38.1 64.0 71.7 88.0 116.1 200.0 246.3 285.3 317.6 100 50 50 ... ... ... ... ... ... ... Feet Per Bundle 30.5 15.2 15.2 ... ... ... ... ... ... ... Quantity Per Lift Feet 3,500 2,500 1,700 1,350 1,100 800 370 300 240 240 Meters 1,067.5 762.5 518.5 411.8 335.5 244.0 112.9 91.5 73.2 73.2 Wheatland Crane Lift lb. 2,170 2,100 2,023 2,133 2,134 2,048 1,632 1,629 1,510 1,680 Packaging NEMA Color Code Cubic Ft. Thread Protectors 30.3 33.6 34.2 37.9 41.3 42.2 32.5 40.8 41.3 43.1 Yellow Green Orange Green Yellow Orange Yellow Orange Yellow Orange
1 1 2 3
Length without Coupling and Threads Per inch (mm) are the same as Rigid conduit
Aluminum Conduit
Tolerances and Specifications Trade Size 1/2 3/4 1 1/4 1/2 2 1/2 3 1/2 4 5 6 Nominal Pipe Size O.D. X Wall .840 1.050 1.315 1.660 1.900 2.375 2.875 3.500 4.000 4.500 5.563 6.625 x x x x x x x x x x x x .109 .113 .133 .140 .145 .154 .203 .216 .226 .237 .258 .280 Outside Diameter Min. .809 1.019 1.284 1.629 1.869 2.351 2.846 3.465 3.960 4.455 5.507 6.559 Max. .855 1.065 1.330 1.675 1.916 2.399 2.904 3.535 4.040 4.545 5.619 6.691 Wall Thickness Minimum .095 .099 .116 .122 .127 .135 .178 .189 .198 .207 .226 .245 Length 1/4 Without Coupling 9 - 11 1/4 9 - 11 1/4 9 - 11 9 - 11 9 - 11 9 - 11 9 - 10 1/2 9 - 10 1/2 9 - 10 1/4 9 - 10 1/4 9 - 10 9 - 10 Couplings Packaging Minimum Nominal Wt. No. Pieces Pcs. Per Wt. of Master Bundle Length 10 Pieces Per Bundle Master Bdl. 1.562 1.625 2.00 2.062 2.062 2.125 3.125 3.250 3.375 3.500 3.750 4.000 .61 # .91# 1.25# 1.89# 2.33# 3.46# 6.83# 9.14# 10.8# 14.2# 24.2# 32.1# 10 10 10 5 5 5 250 250 200 100 100 45 30 20 20 20 8 6 703# 935# 1090# 716# 887# 533# 562# 492# 591# 700# 383# 378#
1 1 2 3
Electrolines Est. P. O. Box. 942 Yanbu Saudi Arabia Tel: +966 4 3225418 Fax: +966 4 3222213 Al-Jubail: Tel: +966 3 3632967 Fax: +966 3 3612967
Conduits
Material
PVC Conduit and Duct Pipe made from Rigid PVC Compound fully meet the material requirements of American specifications ASTM D 1784 and ASTM D 4396 as specified in NEMA standards.
Manufacturing standards
NEMA TC 2 Electrical Plastic Tubing (EPT) and Conduit (EPC-40 and EPC-80) NEMA TC 6 Plastic Utilities Duct for underground installation. NEMA TC 8 Extra-Strength Plastic Utilities Duct for underground installation. ASTM F 512 Smooth-wall PVC conduit and fittings for underground installation.
Length of Pipe
Standard 3 meter length for NEMA TC 2 tubing and conduit. Standard 6 meter lengths for NEMA TC 6 and TC 8 ducts. (Other lengths available on request)
Colour
Grey (Other colour by special arrangement)
SAPPCO Rigid PVC Tubing and Conduit for above and below ground use
Dimensions based on NEMA TC 2
Nominal Size Inch 1/2 3/4 1 1 1/4 1 1/2 2 2 1/2 3 4 5 6 Average EPT - A - PVC EPC - 40 - PVC EPC - 80 - PVC outside Nominal Weight Wall Thickness Nominal Weight Wall Thickness Nominal Weight Thickness Wall diameter (Minimum mm) Kg / m (Minimum mm) Kg / m (Minimum mm) Kg / m mm 21.34 1.52 0.155 2.77 0.248 3.73 0.309 26.67 1.52 0.198 2.87 0.329 3.91 0.418 33.40 1.52 0.251 3.38 0.483 4.55 0.614 42.16 1.78 0.365 3.56 0.652 4.85 0.850 48.26 2.03 0.470 3.68 0.779 5.08 1.03 60.32 2.54 0.719 3.91 1.04 5.54 1.43 73.02 2.79 0.952 5.16 1.65 7.01 2.18 88.90 3.18 1.31 5.49 2.16 7.62 2.91 114.30 3.81 2.00 6.02 3.07 8.56 4.26 141.30 6.55 4.17 9.52 5.91 168.28 7.11 5.41 10.97 8.13 Electrical Plastic Tubing Designed to be encased in concrete. Electrical Plastic Conduit Designed for normal duty application. Electrical Plastic Conduit Designed for heavy duty application.
Wall Thickness Nominal Weight Wall Thickness Nominal Weight (Minimum mm) Kg / m (Minimum mm) Kg / m 1.52 0.251 1.52 0.369 1.52 0.465 1.96 0.576 1.93 0.847 3.00 1.25 2.54 1.39 3.91 2.05 3.86 3.02 5.77 4.42
Type EB Type DB
Designed for ENCASED BURIAL in concrete. Designed for normal DIRECT BURIAL without encasement in concrete.
Electrolines Est. P. O. Box. 942 Yanbu Saudi Arabia Tel: +966 4 3225418 Fax: +966 4 3222213 Al-Jubail: Tel: +966 3 3632967 Fax: +966 3 3612967
Conduits
a sacrificial, metallised protection which has the added benefit that it does not interfere with electrical continuity requirements.The complete Electrolines range of coated conduits and fittings conform to current National Electrical Manufacturers Association (NEMA) Standards.
Conduit fittings conform to: UL 886 Outlet Boxes and Fittings for use in hazardous locations. External PVC coating thickness Nominal 40 mils (0.040 inches) (+ 10 mils - 5 mils) Internal Urethane lining thickness Nominal 2 mils (0.002 inches)
Applications
Electrolines Conduits and fittings are
especially recommended for installation in very corrosive environments such as those experienced in coastal or offshore locations. Particular examples include the construction of oil and offshore platforms, refineries, power and desalination plants, chemical and other industrial facilities.
Other Products
The complete range of coated products available from Electrolines includes the DURABOLTTM range of Corrosion Resistant Fasteners and pre packaged Flange Jointing Sets. FIRE-LINETM, WATER-LINETM and CHEMI-LINETM coated and lined Flange Pipe Systems for conveying raw and sweet water supplies, chemicals, hydrocarbons, corrosive or abrasive fluids, and slurries. WELL GUARDTM coated and line Down Well Casings and Pipes. All PVC coated products are designed to offer significant cost savings. Details are available on request.
Technical Specifications
Conduits conform to: ANSI C80.1 Specification for rigid steel conduit, zinc coated. NEMA RN1 Polyvinyl-Chloride externally coated, galvanized rigid steel conduit.
Conduits
General Description
High quality Polyvinyl Chloride resin coating system applied on a wide range of substrates; steel, aluminum and cast iron. Coating offers sterling performance characteristics over a broad spectrum of applications including aesthetic as well as chemical. Applied over suitably prepared substrates, the coating demonstrates a tenacious bond allowing the substrates to be machined and post formed*. Heavy film thickness are possible, up to 10mm for severe duty applications.
Coating Material
PVC
Typical Applications
Electrical conduits, Conduit fittings and raceway Fence posts and fittings Cushion coatings
Colour Range
Dark green and grey in stock. Other colours are available upon request but subject to a minimum quantity.
Technical Specifications
Coating thickness Gloss Impact strength 250 microns - 10 mm 70 deg 1.7 joules 250% 85 50 mg/10 10 ohn/m 30 kv/mm Working temperature Water absorbtion Salt spray ASTM B117 Chemical resistance Chalking resistance 20 Repairability 80 deg C 0.5% 1000 hrs Excellent Good Possible Gardener drop weight 23 deg C At break Shore A Taber H18, 500 grm Resistivity Dielectric Continuous Max Pass Except solvents
350 332
Conduit
(UL listed. Reduced wall steel type RWS.) Features:
Steel Construction Premium hot dip galvanized zinc coating Superior corrosion resistance Smooth interior for easy wire pull-thru Easy installation to follow contours Available cut to custom lengths Extra flexibility for simplified positioning Listed connectors available from leading manufacturers Complies with UL-1, NEC Article 350 and Federal Specification WW-C-566C
Trade Size And Catalog Number HWS5/16 RWS3/8 RWS1/2 RWS3/4 RWS1 RWS1-1/4 RWS1-1/2 RWS2 RWS2-1/2 RWS3 HWS3-1/2 HWS4
Acceptable Internal Diameter Min. Max. 0.312 0.375 0.393 0.625 0.645 0.812 0.835 1.000 1.040 1.250 1.300 1.500 1.575 2.000 2.080 2.500 3.000 3.500 4.000
Acceptable External Diameter Min. Max. 0.470 0.510 0.560 0.610 0.860 0.920 1.045 1.105 1.300 1.380 1.550 1.630 1.850 1.950 2.350 2.450 2.860 3.060 3.360 3.560 3.860 4.060 4.360 4.560
Approx. Weight of 100 Ft. 15 17.5 28 34 52 65 80 100 150 190 322 374
Approx. Feet Per Standard Coil 250 or 500 100 or 250 100 100 50 50 25 25 25 25 25 25
Electrolines Est. P. O. Box. 942 Yanbu Saudi Arabia Tel: +966 4 3225418 Fax: +966 4 3222213 Al-Jubail: Tel: +966 3 3632967 Fax: +966 3 3612967
Conduits
Flexible Steel Conduit
(Non-UL Commercial Grade.Type IC.) Features: Lightweight for easier handling
Steel Construction Hot dip galvanized zinc coating wont flake or peel Corrosion resistant Smooth interior for easy wire pull-thru
Trade Size And Catalog Number IC3/8 IC1/2 IC3/4 IC1 IC1-1/4 IC1-1/2 IC2 IC2-1/2 IC3 IC3-1/2 IC4 Acceptable Internal Diameter 0.375 0.625 0.812 1.000 1.250 1.500 2.000 2.500 3.000 3.500 4.000 Acceptable External Diameter 0.610 0.920 1.105 1.380 1.630 1.950 2.450 3.060 3.560 4.060 4.560
Easy installation to follow contours Built in flexibility for simplified positioning Exceptional crush proof qualities Standard connectors available from leading manufacturers
Bending Radius in Inches 2 3 4 5 61/4 71/2 10 121/2 15 171/2 20 Approx. Weight of 100 Ft. 13 19 25 28 38 48 105 115 140 154 196 Approx. Feet Per Standard Coil 100 or 250 100 100 50 50 25 25 25 25 25 25
Specifications:
Sequentially marketd in feet for easy measurement Packaged in handy payout carton Easily cut to length on the job Accepts standard liquid-tight connectors Delivers long lasting wiring protection where listed products are not required Available in custom lengths, or can be cut by the customer
Bending Radius in Inches 11/2 2 23/4 5 6 7 9 11 151/2 18 22 301/2 Approx. Weight of 100 Ft. 17 20 32 50 68 87 119 140 230 290 350 568 Approx. Feet Per Standard Coil 100-250 100-200 100-175 100 100 50 50 50 25 25 25 25
Specifications:
Specifications:
Trade Size And Catalog Number UALT3/8 UALT1/2 UALT3/4 UALT1 UALT1-1/4 UALT1-1/2 UALT2 UALT2-1/2 UALT3 UALT3-1/2 UALT4 Acceptable Internal Diameter Min. Max. 0.484 0.622 0.820 1.041 1.380 1.575 2.020 2.480 3.070 3.500 4.000 0.504 0.642 0.840 1.066 1.410 1.600 2.045 2.505 3.100 3.540 4.040 Acceptable External Diameter Min. Max. 0.690 0.820 1.030 1.290 1.630 1.865 2.340 2.840 3.460 3.960 4.460 0.710 0.840 1.050 1.315 1.660 1.900 2.375 2.875 3.500 4.000 4.500 Bending Radius in Inches 2 31/4 41/4 61/2 8 9 11 14 17-1/2 20 24 Approx. Weight of 100 Ft. 22 25 34 64 84 102 148 174 290 385 426 Approx. Feet Per Standard Coil 100 or 200 100 or 200 100 or 150 100 50 50 50 50 25 25 25
Electrolines Est. P. O. Box. 942 Yanbu Saudi Arabia Tel: +966 4 3225418 Fax: +966 4 3222213 Al-Jubail: Tel: +966 3 3632967 Fax: +966 3 3612967
Conduits
Kopex - Matrel
Features:
Halogen free Self-extinguishing / light weight Temperature resistant Flexible with tight bend radius Dust / water resistant to IP66 when fitted with liquid tight seal A wide and unique range of connectors Crush resistant, with good recovery properties Ease of assembly Economical in price and installation time
u u u
LIMITED FIRE HAZARD (LFH) LT -S Flexible (Limited Fire Hazard) Construction: Galvanised steel core. Twine packed with black LFH covering. Temp. range: 40C to +110C
LT -PVC Flexible
Construction: Galvanised steel core. Twine packed with black or grey PVC covering. Temp. range: 25C to +105C (For grey PVC order FLG).
CSA Flexible
Construction: Galvanised steel core. Twine packed, black PVC covering. CSA rated +75C
UL Flexible
Construction: Galvanised steel core. Copper packed, grey PVC covering. UL approved. UL rated: 10C to +60C
**10, 20, 30 should be added according to coil length. eg. 20 m of 32mm LT-H is FLH 0620
Normally held in stock with the manufacturer If not stock 6-8 weeks delivery Price and delivery status on application
US Trade Size Ins 3 /8 1 /2 3 /4 1 11/4 11/2 2 3 /8 1 /2 3 /4 1 11/4 11/2 2 3 /8 1 /2 3 /4 1 11/4 11/2 2 3 /8 1 /2 3 /4 1 11/4 11/2 2 3 /8 1 /2 3 /4 1 11/4 11/2 2
Ordering Code FLH03 ** FLH04 FLH05 FLH06 FLH07 FLH08 FLH09 FLS03 ** FLS04 FLS05 FLS06 FLS07 FLS08 FLS09 FLB03 ** FLB04 FLB05 FLB06 FLB07 FLB08 FLB09 FCB03 ** FCB04 FCB05 FCB06 FCB07 FCB08 FCB09 FUG03 ** FUG04 FUG05 FUG06 FUG07 FUG08 FUG09
10m. u u u u u u u u u 5 u u 5
Electrolines Est. P. O. Box. 942 Yanbu Saudi Arabia Tel: +966 4 3225418 Fax: +966 4 3222213 Al-Jubail: Tel: +966 3 3632967 Fax: +966 3 3612967
Conduits
MEDIUM DUTY CONDUIT
Material: nylon Temp. range: -40C to +100C British Coil Length Conduit Code Size mm 10 m. 30m. 50m. 12 16 20 25 32 ERG02 ** ERG03 ERG04 ERG05 ERG06 International Ordering Code PAST-10S PAST-12S PAST-17S
u u u
u u u
Normally held in stock with the manufacturer If not stock 6-8 weeks delivery Price and delivery status on application
** 10, 30, 50 should be added according to coil length. e.g. 30 metres of 20 mm Nylon Conduit is EPG0430.
Kopex
Superscren Type H Construction: Black type H Covering (layers) Leaded Steel Leaded Steel Kraft Paper Temp. range: 50C to +130C Rec. connector: C18
British Coil length Conduit Ordering Size mm Code 10m. 20m. 30m.
16 20 25 32 40 50 63 PHH03 ** PHH04 PHH05 PHH06 PHH07 PHH08 PHH09
u u u
u u u
**10, 20, 30 should be added according to coil length. 30 metres of Superscreen Type H 16mm is PHH0330. Conduit construction can include addtional layers on larger sizes.
u u u 5 5 5
PHS0310 PHS0330 PHS0410 PHS0430 PHS0510 PHS0530 PHS0610 PHS0620 PHS0710 PHS0720 PHS0810 PHS0820 PHS0910 PHS0920
10 30 10 30 10 30 10 20 10 20 10 20 10 20
NLS1-PVC Pliable Construction: Grey PVC Covering (layers) Leaded Steel, Kraft Paper Temp. range: 40C to +150C Rec. connector: C12, C14 LS1 Pliable Construction: Leaded Steel (layers) Kraft Paper Temp. range: 40C to +150C Rec. connector: C10, C16
British Coil length Conduit Ordering Size mm Code 10m. 20m. 30m. 12 PNG02** 5 5 16 PNG03 u u
20 25 12 16 20 25 32 40 50 63 75 12 16 20 25 32 40 50 63 PNG04 PNG05 PSU02 ** PSU03 PSU04 PSU05 PSU06 PSU07 PSU08 PSU09 PSU10 PHU02** PHU03 PHU04 PHU05 PHU06 PHU07 PHU08 PHU09 PLU02 ** PLU03 PLU04 PLU05 PLU06 PLU07
u u u u u 5 5 u u u 5 5 5
u u
LS2-PVC Pliable Construction: Black PVC Covering (layers) Leaded Steel, Leaded Steel Kraft Paper Temp. range: 40C to +105C Rec. connector: C12, C14
5 u u 5 5 5 5
5 u
u 5 5 5 5
LS2 Pliable Construction: Leaded Steel (layers) Leaded Steel Temp. range: 40C to +150C Rec. connector: C10, C16
u u u 5 5
u u
AL2-PVC Pliable Construction: Black PVC Covering (layers) Aluminium, Aluminium Kraft Paper Temp. range: 40C to +105C Rec. connector: C12, C14
12 16 20 25 32 40 50 63 75
5 5 5 5 5 5 5
5 5
5 5 5 5 5
AL1 Pliable Construction: Aluminium 12 (layers) Kraft paper 16 Temp. range: 40C to +150C 20 Rec. connector: C10, C16
25 32 40
u 5 5 5
5 5
u u
5 5 5
** 10, 20, 30 should be added according to coil length. e.g. 30 m of LS1-PVC 16mm is PSB0330
Normally held in stock with the manufacturer If not stock 6-8 weeks delivery Price and delivery status on application
Electrolines Est. Tel: +966 4 3225418 Fax: +966 4 3222213 Al-Jubail: Tel: +966 3 3632967 Fax: +966 3 3612967
Electrolines Est.
Tel: +966 4 3225418 Fax: +966 4 3222213 Al-Jubail: Tel: +966 3 3632967 Fax: +966 3 3612967