Sunteți pe pagina 1din 10

Conduits

Rigid Steel Conduit Electrical Metallic Tubing Intermediate Metal Conduit Aluminium Conduit PVC Conduit PVC Coated Conduit Flexible Steel Conduit KopexMartel PVC Pipes &fFittings

SSP Saudi Steel Pipe Company SAPPCO Saudi Plastic Products Company Wheat Land Tube Company Zindco International Metal Hose Matsushita Decoduct Kopex - Martel Al Flex - Liquidtight Egatube Appleton

Electrolines Est.
P. O. Box. 942 Yanbu Saudi Arabia Tel: +966 4 3225418 Fax: +966 4 3222213 Al-Jubail: Tel: +966 3 3632967 Fax: +966 3 3612967

Conduits
Saudi Steel Pipe
Hot-Dipped Galvanized Rigid Steel Conduit provides GREATER RESISTANCE TO CORROSION than any other conduits. Another important ADVANTAGE of using Rigid Steel Conduit is SAFETY. Its heavy wall maximises the protection against probable FIRE HAZARDS and PHYSICAL ABUSE. Hot-Dipped Galvanized Rigid Steel Conduit is manufactured strictly in conformance to the following standards: American National Standard Institute (ANSI) C 80.11977 Underwriters Laboratories Specification No. 6 (UL-6)

Conduit Tubes
ANSI C80.1 1983, Rigid Steel Conduit, Hot Dip Galvanized Nominal Size A B 15 20 25 32 40 50 65 80 90 100 125 150 1/2 3/4 1 11/4 11/2 2 21/2 3 31/2 4 5 6 Nominal Inside Diameter in. mm. 0.632 0.836 1.063 1.394 1.624 2.083 2.489 3.090 3.570 4.050 5.073 6.093 16.0 21.3 27.0 35.4 41.3 52.9 63.2 78.5 90.7 102.9 128.9 154.8 Outside Diameter in. mm. 0.840 1.050 1.315 1.660 1.900 2.375 2.875 3.500 4.000 4.500 5.563 6.625 21.3 26.7 33.4 42.2 48.3 60.3 73.0 88.9 101.6 114.3 141.3 168.3 Nominal Wall Thickness in. mm. 0.104 0.107 0.126 0.133 0.138 0.146 0.193 0.205 0.215 0.225 0.245 0.266 2.64 2.72 3.20 3.38 3.51 3.71 4.90 5.21 5.46 5.72 6.22 6.76 Length Without Coupling ft & in. m 911-1/4 911-1/4 911 911 911 911 910-1/2 910-1/2 910-1/4 910-1/4 910 910 3.03 3.03 3.02 3.02 3.02 3.02 3.01 3.01 3.00 3.00 3.00 3.00 Minimum Weight of Ten Unit Lengths With Couplings Attached lb kg 79.0 105.0 153.0 201.0 249.0 332.0 527.0 682.6 831.0 972.3 1313.6 1745.3 35.83 47.63 69.40 91.17 112.95 150.60 239.05 309.63 376.94 441.04 595.85 791.67 Pieces Per Bundle 120 84 60 42 36 26 18 14 10 8 7 5

NOTE: Applicable tolerances: Length: 1/4 in ( 6.35 mm) (without coupling) Ouside Diameter: for trade sizes 1/2 through 2 in: 0.015 in ( 0.38 mm); for trade sizes 2-1/2 through 4 in: 0.025 in ( 0.64 mm); for trade sizes 5 and 6 in: 1% Wall thickness: 12.5%

Wheatland
Wheatland, EMT, are manufactured in conformance to standards established by the American National Standard Institute (ANSI), and the Underwriters Laboratories. EMT American National Standard Institute (ANSI) C80.3-1994 Underwriters Laboratories Specification UL 797 National Electric Code Article 348

Electrical Metallic Tubing


Weights and Dimensions Trade Size Designator NPS Metric 1/2 3/4 1 1/4 1/2 2 1/2 3 1/2 4 16 21 27 35 41 53 63 78 91 103 Outside Diameter IN MM .706 .922 1.163 1.510 1,740 2.197 2,875 3,500 4,000 4.500 17.9 23.4 29.5 38.4 44.2 55.8 73.0 88.9 101.6 114.3 Wall Thickness IN MM .042 .049 .057 .065 .065 .065 .072 .072 .083 .083 1.07 1.24 1.45 1.65 1.65 1.65 1.83 1.83 2.11 2.11 Wt. Per 10 Units Lengths LB. KG. 30 46 67 101 116 148 216 263 349 393 13.6 20.9 30.4 45.8 52.6 67.1 98.0 119.3 158.3 178.2 Feet Per Bundle 100 100 100 50 50 ... ... ... ... ... Meters Per Bundle 30.5 30.5 30.5 15.2 15.2 ... ... ... ... ... Lift Size Feet 7,000 5,000 3,000 2,000 1,500 1,200 610 510 370 300 Meters 2,135.0 1,525.0 915.0 610.0 457.6 366.0 186.1 155.6 112.9 91.5 Wheatland Crane Lift lb. Cubic Ft. 2,100 2,300 2,010 2,020 1,740 1,776 1,318 1,341 1,291 1,179 27.8 32.5 27.1 30.5 33.6 35.1 41.5 48.9 48.6 41.7

1 1 2 3

Electrolines Est. P. O. Box. 942 Yanbu Saudi Arabia Tel: +966 4 3225418 Fax: +966 4 3222213 Al-Jubail: Tel: +966 3 3632967 Fax: +966 3 3612967

Conduits
Intermediate Metal Conduit (IMC)
Intermediate Metal Conduit (IMC). IMC is made from high strength steel that is coldformed and electrically welded into a uniform tube. IMC is 25% lighter in weight than rigid conduit but it is still capable of being threaded.The exterior surface is thoroughly coated with zinc.The interior surface is protected by a specially formulated lubricating coating for easier wire pulling. IMC American National Standard Institute (ANSI) C80.6-1994 Underwriters Laboratories Specification UL 1242 National Electric Code Article 345

IMC
Weights and Dimensions
Trade Size Designator NPS 1/2 3/4 1 1/4 1/2 2 1/2 3 1/2 4 Metric 16 21 27 35 41 53 63 78 91 103 Outside Diameter in 0.815 1.029 1.290 1.638 1.883 2.360 2.857 3.476 3.971 4.466 mm 20.7 26.1 32.8 41.6 47.8 59.9 72.6 88.3 100.9 113.4 Wall Thickness in .078 0.83 .093 .095 .100 .105 .150 .150 .150 .150 mm 1.98 2.10 2.36 2.41 2.54 2.67 3.81 3.81 3.81 3.81 Wheatland Nom.Wt. Feet Per 10 Unit Lengths Per with Couplings Bundle lb kg 62 84 119 158 194 256 441 543 629 700 28.1 38.1 64.0 71.7 88.0 116.1 200.0 246.3 285.3 317.6 100 50 50 ... ... ... ... ... ... ... Feet Per Bundle 30.5 15.2 15.2 ... ... ... ... ... ... ... Quantity Per Lift Feet 3,500 2,500 1,700 1,350 1,100 800 370 300 240 240 Meters 1,067.5 762.5 518.5 411.8 335.5 244.0 112.9 91.5 73.2 73.2 Wheatland Crane Lift lb. 2,170 2,100 2,023 2,133 2,134 2,048 1,632 1,629 1,510 1,680 Packaging NEMA Color Code Cubic Ft. Thread Protectors 30.3 33.6 34.2 37.9 41.3 42.2 32.5 40.8 41.3 43.1 Yellow Green Orange Green Yellow Orange Yellow Orange Yellow Orange

1 1 2 3

Length without Coupling and Threads Per inch (mm) are the same as Rigid conduit

ALUMINUM RIGID CONDUIT


Aluminum rigid conduit offers the electrical industry all the inherent physical advantages of this light metal at a cost competitive with ordinary conduit. Alloy: 6063 aluminum alloy,T-1 temper. (Former designation T-42) Specification compliance: Federal Specification WW-C-540c. Underwriters Laboratories UL-6, latest revision. American National Standards Institute (ANSI) C80.5. Thread Protectors: Aluminum Rigid Conduit is shipped with thread protectors, which shield threads, and simplify size selection. Recommended Installation procedures The conventional tools and practices used on ordinary conduit can be utilized on Aluminum Rigid Conduit. Cutting: A hacksaw is recommended to cut sizes 11/4 and smaller. Larger sizes can be cut with power cut-off equipment. Bending: Standard EMT benders, one size larger than the size of the conduit, should be used on conuit sizes 1 and smaller. For sizes over 1, conventional equipment is recommended. Threading: Sharp dies and conventional cutting oil should be used for aluminum conduit. Excellent results can be obtained with a general purpose emulsifiable oil. Fittings: Aluminum fittings are recommended; however, cadmium plated or galvanized fittings are satisfactory for most installations. In concrete: Aluminum conduit can safely be embedded in concrete where chlorides are not present, whether the installation is below or above grade.The 1963 revision to Concrete Institute prohibits the addition of additives containing calcium chloride to any concrete that may be in contact with prestressing steel. Aluminum conduit should not be directly imbedded in concrete containing soluble chlorides, such as calcium chloride, unwashed beach sand, sea water, or coral bearing aggregates. Aluminum conduit can be safely installed in concrete containing chlorides if an adequate protective coating of bitumastic or asphalt-base paint is applied, or the conduit wrapped with plastic tape. In Soil or Cinders: Aluminum conduit or steel conduit, when buried in soil or cinders, should be treated with a protective coating of bitumastic or asphalt-base paint, or wrapped with plastic tape.

Aluminum Conduit
Tolerances and Specifications Trade Size 1/2 3/4 1 1/4 1/2 2 1/2 3 1/2 4 5 6 Nominal Pipe Size O.D. X Wall .840 1.050 1.315 1.660 1.900 2.375 2.875 3.500 4.000 4.500 5.563 6.625 x x x x x x x x x x x x .109 .113 .133 .140 .145 .154 .203 .216 .226 .237 .258 .280 Outside Diameter Min. .809 1.019 1.284 1.629 1.869 2.351 2.846 3.465 3.960 4.455 5.507 6.559 Max. .855 1.065 1.330 1.675 1.916 2.399 2.904 3.535 4.040 4.545 5.619 6.691 Wall Thickness Minimum .095 .099 .116 .122 .127 .135 .178 .189 .198 .207 .226 .245 Length 1/4 Without Coupling 9 - 11 1/4 9 - 11 1/4 9 - 11 9 - 11 9 - 11 9 - 11 9 - 10 1/2 9 - 10 1/2 9 - 10 1/4 9 - 10 1/4 9 - 10 9 - 10 Couplings Packaging Minimum Nominal Wt. No. Pieces Pcs. Per Wt. of Master Bundle Length 10 Pieces Per Bundle Master Bdl. 1.562 1.625 2.00 2.062 2.062 2.125 3.125 3.250 3.375 3.500 3.750 4.000 .61 # .91# 1.25# 1.89# 2.33# 3.46# 6.83# 9.14# 10.8# 14.2# 24.2# 32.1# 10 10 10 5 5 5 250 250 200 100 100 45 30 20 20 20 8 6 703# 935# 1090# 716# 887# 533# 562# 492# 591# 700# 383# 378#

1 1 2 3

Electrolines Est. P. O. Box. 942 Yanbu Saudi Arabia Tel: +966 4 3225418 Fax: +966 4 3222213 Al-Jubail: Tel: +966 3 3632967 Fax: +966 3 3612967

Conduits

Super high impact uPVC Conduit


Decoduct
Super high impact uPVC conduit, manufactured from specially formulated PVC, to meet the stringent requirements of BS4607, BS6099, Saudi Arabian Standards SSA254/255, Gulf Standards GS32/33 and relevant I.E.E. regulations Decoduct uPVC conduit is available in five main types i) Rigid PVC conduit - Very Heavy Gauge (BS6099 HEAVY) ii) Rigid PVC conduit - Heavy Gauge - (BS6099 MEDIUM, GS32/33, SSA254/255) iii) Rigid PVC conduit - Light Gauge - (BS6099 LIGHT) iv) Pliable (corrugated) PVC conduit - Heavy Gauge - (BS4607), GS32/33, SSA254/255) v) Pliable (corrugated) PVC conduit - Light Gauge - (BS4607, GS32/33, SSA254/255) The comprehensive range of Decoduct PVC fittings & accessories is fully compatible with all the above listed conduit types

Material
PVC Conduit and Duct Pipe made from Rigid PVC Compound fully meet the material requirements of American specifications ASTM D 1784 and ASTM D 4396 as specified in NEMA standards.

Manufacturing standards
NEMA TC 2 Electrical Plastic Tubing (EPT) and Conduit (EPC-40 and EPC-80) NEMA TC 6 Plastic Utilities Duct for underground installation. NEMA TC 8 Extra-Strength Plastic Utilities Duct for underground installation. ASTM F 512 Smooth-wall PVC conduit and fittings for underground installation.

Length of Pipe
Standard 3 meter length for NEMA TC 2 tubing and conduit. Standard 6 meter lengths for NEMA TC 6 and TC 8 ducts. (Other lengths available on request)

Colour
Grey (Other colour by special arrangement)

SAPPCO Rigid PVC Tubing and Conduit for above and below ground use
Dimensions based on NEMA TC 2
Nominal Size Inch 1/2 3/4 1 1 1/4 1 1/2 2 2 1/2 3 4 5 6 Average EPT - A - PVC EPC - 40 - PVC EPC - 80 - PVC outside Nominal Weight Wall Thickness Nominal Weight Wall Thickness Nominal Weight Thickness Wall diameter (Minimum mm) Kg / m (Minimum mm) Kg / m (Minimum mm) Kg / m mm 21.34 1.52 0.155 2.77 0.248 3.73 0.309 26.67 1.52 0.198 2.87 0.329 3.91 0.418 33.40 1.52 0.251 3.38 0.483 4.55 0.614 42.16 1.78 0.365 3.56 0.652 4.85 0.850 48.26 2.03 0.470 3.68 0.779 5.08 1.03 60.32 2.54 0.719 3.91 1.04 5.54 1.43 73.02 2.79 0.952 5.16 1.65 7.01 2.18 88.90 3.18 1.31 5.49 2.16 7.62 2.91 114.30 3.81 2.00 6.02 3.07 8.56 4.26 141.30 6.55 4.17 9.52 5.91 168.28 7.11 5.41 10.97 8.13 Electrical Plastic Tubing Designed to be encased in concrete. Electrical Plastic Conduit Designed for normal duty application. Electrical Plastic Conduit Designed for heavy duty application.

RIGID PVC CONDUIT Very Heavy Gauge


Item Outside Nominal wall Standard code diameter thickness (mm) Pcs DCV1 16 1.6 50 DCV2 20 1.8 20 DCV3 25 1.9 20 DCV4 32 2.5 10 DCV5 38 2.5 10 DCV6 50 3.2 10 Heavy Gauge DCH1 16 DCH2 20 DCH3 25 DCH4 32 DCH5 38 DCH6 50 Light Gauge DCL1 16 DCL2 20 DCL3 25 DCL4 32 DCL5 38 DCL6 50 1.4 1.55 1.8 2.1 2.2 2.5 1.1 1.2 1.4 1.5 1.5 1.9 50 20 20 10 10 10 50 20 20 10 10 10 Packs Mtrs 145 58 58 29 29 29 145 58 58 29 29 29 145 58 58 29 29 29

EPT-A EPC-40 EPC-80

Rigid PVC Utilities Duct for Underground Installation


Dimensions based on NEMA TC 6 and ASTM F 512
Nominal Size Inch 2 3 4 6 Average outside diameter mm 60.32 88.90 114.30 168.28 PVC - TYPE EB PVC - TYPE DB Wall Thickness Nominal Weight Wall Thickness Nominal Weight (Minimum mm) Kg / m (Minimum mm) Kg / m 1.52 0.465 1.52 0.465 1.55 0.703 2.34 1.00 2.08 1.17 3.07 1.65 3.18 2.53 4.62 3.57

Standard length 2.9 mtrs, available in black or white.

Rigid PVC Extra Strength Utilities Duct For Underground Installation


Dimensions based on NEMA TC 8 and ASTM F 512
Nominal Size Inch 1 1 1/2 2 3 4 6 Average outside diameter mm 33.40 48.26 60.32 88.90 114.30 168.28
PVC - TYPE EB PVC - TYPE DB

PLIABLE PVC CONDUIT CORRUGATED Heavy Gauge (white colour)


Item code DPH2 DPH3 Item code DPL2 DPL3 Outside Standard roll diameter (mm) length (mtrs) 20 50 25 50 Outside Standard roll diameter (mm) length (mtrs) 20 50 25 50

Light Gauge (grey colour)

Wall Thickness Nominal Weight Wall Thickness Nominal Weight (Minimum mm) Kg / m (Minimum mm) Kg / m 1.52 0.251 1.52 0.369 1.52 0.465 1.96 0.576 1.93 0.847 3.00 1.25 2.54 1.39 3.91 2.05 3.86 3.02 5.77 4.42

Type EB Type DB

Designed for ENCASED BURIAL in concrete. Designed for normal DIRECT BURIAL without encasement in concrete.

Electrolines Est. P. O. Box. 942 Yanbu Saudi Arabia Tel: +966 4 3225418 Fax: +966 4 3222213 Al-Jubail: Tel: +966 3 3632967 Fax: +966 3 3612967

Conduits

PVC Coated Conduits

ZAMIL Industrial Coating

Electrical Conduits and Conduit Fittings


Description
Electrolines Conduits and conduit fittings have been specifically designed for installation in severe and corrosive environments.The complete range of Electrolines conduits and conduit fittings are coated externally in grey PVC and lined internally with a Urethane Polymer. In environments where high humidity is present, conventional conduits and fittings have been observed to corrode from the inside. In addition to improving the corrosion resistance, the intrnal Urethane lining also facilitates easier wire pulling. All conduit threads receive

a sacrificial, metallised protection which has the added benefit that it does not interfere with electrical continuity requirements.The complete Electrolines range of coated conduits and fittings conform to current National Electrical Manufacturers Association (NEMA) Standards.

Conduit fittings conform to: UL 886 Outlet Boxes and Fittings for use in hazardous locations. External PVC coating thickness Nominal 40 mils (0.040 inches) (+ 10 mils - 5 mils) Internal Urethane lining thickness Nominal 2 mils (0.002 inches)

Applications
Electrolines Conduits and fittings are
especially recommended for installation in very corrosive environments such as those experienced in coastal or offshore locations. Particular examples include the construction of oil and offshore platforms, refineries, power and desalination plants, chemical and other industrial facilities.

Other Products
The complete range of coated products available from Electrolines includes the DURABOLTTM range of Corrosion Resistant Fasteners and pre packaged Flange Jointing Sets. FIRE-LINETM, WATER-LINETM and CHEMI-LINETM coated and lined Flange Pipe Systems for conveying raw and sweet water supplies, chemicals, hydrocarbons, corrosive or abrasive fluids, and slurries. WELL GUARDTM coated and line Down Well Casings and Pipes. All PVC coated products are designed to offer significant cost savings. Details are available on request.

Technical Specifications
Conduits conform to: ANSI C80.1 Specification for rigid steel conduit, zinc coated. NEMA RN1 Polyvinyl-Chloride externally coated, galvanized rigid steel conduit.

Quality Product Made Even Better


Upon your request , Electrolines can apply Fluoropolymer (PTFE) coating on the internal surface of the conduits or fittings. Fluoropolymer (PTFE) is a coating resin that is being used on multitudes of products to inhibit corrosion as well as friction, i.e. Fluoropolymer coated nuts and bolts. This internal coating provides a co-efficient of friction of .05, serving as dry lubrication that reduces friction between the cable and the internal surface of the conduits or fittings, thus it makes cable pulling easier. PTFE as internal coating provides maximum durability for the product as well as convenience for you a perfect combination of corrosion protection and dry lubrication only from elctrolines.
Electrolines Est. P. O. Box. 942 Yanbu Saudi Arabia Tel: +966 4 3225418 Fax: +966 4 3222213 Al-Jubail: Tel: +966 3 3632967 Fax: +966 3 3612967

Conduits
General Description
High quality Polyvinyl Chloride resin coating system applied on a wide range of substrates; steel, aluminum and cast iron. Coating offers sterling performance characteristics over a broad spectrum of applications including aesthetic as well as chemical. Applied over suitably prepared substrates, the coating demonstrates a tenacious bond allowing the substrates to be machined and post formed*. Heavy film thickness are possible, up to 10mm for severe duty applications.

Coating Material

* Electrical conduits; cutting, threading and bending.

PVC

Typical Applications
Electrical conduits, Conduit fittings and raceway Fence posts and fittings Cushion coatings

Colour Range
Dark green and grey in stock. Other colours are available upon request but subject to a minimum quantity.

Technical Specifications
Coating thickness Gloss Impact strength 250 microns - 10 mm 70 deg 1.7 joules 250% 85 50 mg/10 10 ohn/m 30 kv/mm Working temperature Water absorbtion Salt spray ASTM B117 Chemical resistance Chalking resistance 20 Repairability 80 deg C 0.5% 1000 hrs Excellent Good Possible Gardener drop weight 23 deg C At break Shore A Taber H18, 500 grm Resistivity Dielectric Continuous Max Pass Except solvents

PVC Coated Conduits


Size Quantity Per STD. Pallet

Elongation Hardness Abrasion Electrical 193 145 99 76 45 20

3/4 1 1 - 1/4 1 - 1/2 2 2 - 1/2 3 4 5 6

350 332

International Metal Hose Company Specifications: Flexible Steel

Conduit
(UL listed. Reduced wall steel type RWS.) Features:
Steel Construction Premium hot dip galvanized zinc coating Superior corrosion resistance Smooth interior for easy wire pull-thru Easy installation to follow contours Available cut to custom lengths Extra flexibility for simplified positioning Listed connectors available from leading manufacturers Complies with UL-1, NEC Article 350 and Federal Specification WW-C-566C

Trade Size And Catalog Number HWS5/16 RWS3/8 RWS1/2 RWS3/4 RWS1 RWS1-1/4 RWS1-1/2 RWS2 RWS2-1/2 RWS3 HWS3-1/2 HWS4

Acceptable Internal Diameter Min. Max. 0.312 0.375 0.393 0.625 0.645 0.812 0.835 1.000 1.040 1.250 1.300 1.500 1.575 2.000 2.080 2.500 3.000 3.500 4.000

Acceptable External Diameter Min. Max. 0.470 0.510 0.560 0.610 0.860 0.920 1.045 1.105 1.300 1.380 1.550 1.630 1.850 1.950 2.350 2.450 2.860 3.060 3.360 3.560 3.860 4.060 4.360 4.560

Bending Radius in Inches 1-3/4 2 3 4 5 61/4 71/2 10 12-1/2 15 171/2 20

Approx. Weight of 100 Ft. 15 17.5 28 34 52 65 80 100 150 190 322 374

Approx. Feet Per Standard Coil 250 or 500 100 or 250 100 100 50 50 25 25 25 25 25 25

Electrolines Est. P. O. Box. 942 Yanbu Saudi Arabia Tel: +966 4 3225418 Fax: +966 4 3222213 Al-Jubail: Tel: +966 3 3632967 Fax: +966 3 3612967

Conduits
Flexible Steel Conduit
(Non-UL Commercial Grade.Type IC.) Features: Lightweight for easier handling
Steel Construction Hot dip galvanized zinc coating wont flake or peel Corrosion resistant Smooth interior for easy wire pull-thru
Trade Size And Catalog Number IC3/8 IC1/2 IC3/4 IC1 IC1-1/4 IC1-1/2 IC2 IC2-1/2 IC3 IC3-1/2 IC4 Acceptable Internal Diameter 0.375 0.625 0.812 1.000 1.250 1.500 2.000 2.500 3.000 3.500 4.000 Acceptable External Diameter 0.610 0.920 1.105 1.380 1.630 1.950 2.450 3.060 3.560 4.060 4.560

Easy installation to follow contours Built in flexibility for simplified positioning Exceptional crush proof qualities Standard connectors available from leading manufacturers
Bending Radius in Inches 2 3 4 5 61/4 71/2 10 121/2 15 171/2 20 Approx. Weight of 100 Ft. 13 19 25 28 38 48 105 115 140 154 196 Approx. Feet Per Standard Coil 100 or 250 100 100 50 50 25 25 25 25 25 25

Specifications:

Sealskin Extra Flexible Liquid-Tight Metallic Conduit


(Non-UL Contractor Grade.Type EFLT.) Smooth interior for easy wire pull-thru Features:
Extra flexible for extra easy use Galvanized steel core for lasting mechanical protection Durable, abrasion resistant PVC jacket wont wrinkle or shrink from cut ends Complete protection against liquid and moisture vapor Resists sunlight, heat, oil and chemical degradation
Trade Size And Catalog Number EFLT3/8 EFLT1/2 EFLT3/4 EFLT1 EFLT1-1/4 EFLT1-1/2 EFLT2* EFLT2-1/2 EFLT3 EFLT3-1/2 EFLT4 EFLT5 Acceptable Internal Diameter Min. Max. 0.484 0.504 0.622 0.642 0.820 0.840 1.041 1.066 1.380 1.410 1.575 1.600 2.020 2.045 2.480 2.505 3.070 3.100 3.500 3.540 4.000 4.040 4.975 5.035 Acceptable External Diameter Min. Max. 0.690 0.710 0.820 0.840 1.030 1.050 1.290 1.315 1.630 1.660 1.865 1.900 2.340 2.375 2.840 2.875 3.460 3.500 3.960 4.000 4.460 4.500 5.505 5.565

Sealskin UL Listed Liquid-Tight Flexible Metallic Conduit


(UL Listed.Type UALT.) Features:
Galvanized steel core for lasting mechanical protection Durable, abrasion resistant PVC jacket wont wrinkle or shrink from cut ends Exceptional crush proof qualities Smooth interior for easy wire pull-thru Sequentially marketd in feet for easy measurement Complete protection against liquid and moisture vapor Resists sunlight, heat, oil and chemical degradation The armor is approved as an equipment ground in sizes 3/8 through 1 1/4 Accepts standard UL Listed liquid-tight connectors Superior protection for circuits located in hostile environments Installs quickly and easily from handy payout carton Complies with UL standard 360. File number E34028, NEC article 351

Sequentially marketd in feet for easy measurement Packaged in handy payout carton Easily cut to length on the job Accepts standard liquid-tight connectors Delivers long lasting wiring protection where listed products are not required Available in custom lengths, or can be cut by the customer
Bending Radius in Inches 11/2 2 23/4 5 6 7 9 11 151/2 18 22 301/2 Approx. Weight of 100 Ft. 17 20 32 50 68 87 119 140 230 290 350 568 Approx. Feet Per Standard Coil 100-250 100-200 100-175 100 100 50 50 50 25 25 25 25

Specifications:

Specifications:
Trade Size And Catalog Number UALT3/8 UALT1/2 UALT3/4 UALT1 UALT1-1/4 UALT1-1/2 UALT2 UALT2-1/2 UALT3 UALT3-1/2 UALT4 Acceptable Internal Diameter Min. Max. 0.484 0.622 0.820 1.041 1.380 1.575 2.020 2.480 3.070 3.500 4.000 0.504 0.642 0.840 1.066 1.410 1.600 2.045 2.505 3.100 3.540 4.040 Acceptable External Diameter Min. Max. 0.690 0.820 1.030 1.290 1.630 1.865 2.340 2.840 3.460 3.960 4.460 0.710 0.840 1.050 1.315 1.660 1.900 2.375 2.875 3.500 4.000 4.500 Bending Radius in Inches 2 31/4 41/4 61/2 8 9 11 14 17-1/2 20 24 Approx. Weight of 100 Ft. 22 25 34 64 84 102 148 174 290 385 426 Approx. Feet Per Standard Coil 100 or 200 100 or 200 100 or 150 100 50 50 50 50 25 25 25

Electrolines Est. P. O. Box. 942 Yanbu Saudi Arabia Tel: +966 4 3225418 Fax: +966 4 3222213 Al-Jubail: Tel: +966 3 3632967 Fax: +966 3 3612967

Conduits
Kopex - Matrel

Specialist Conduit Systems


Designed specifically for use in Zone 1 hazardous areas, the Specialist Cable Protection System, which is lighter and more compact than armoured cables, offers a high degree of flexibility. The SCP system is available in robust core types and a choice of different coverings to suit most applications. The system includes: Type H - high/low temperature capability, chemical and oil resistant. Type S - meets NES 518 requirements for Low Fire Hazard (LFH) applications.Type S is also capable of withstanding high levels of radiation. This product has proved durable and dependable in arduous conditions throughout the world, where flexing, vibration, and the attack of chemicals, ozone, oils, acid, petrol and the weather are a constant danger to electrical and electronic installations.

PMA halogen free nylon conduit systems


The Kopex PMA system is one of the most versatile conduit systems available offering an extensive range of conduit, unique connectors and many accessories to meet almost any cable protection requirement. Manufactured from tough, self-extinguishing 100% nylon, the system will withstand wide temperature variations, the stress of continuous movement and most mineral oils, chemicals and solvents.

Features:
Halogen free Self-extinguishing / light weight Temperature resistant Flexible with tight bend radius Dust / water resistant to IP66 when fitted with liquid tight seal A wide and unique range of connectors Crush resistant, with good recovery properties Ease of assembly Economical in price and installation time

PMA CONDUIT RANGE


Material : grey, nylon code C black, nylon Code E Temp. range : -40C to +120C British International Ordering Coil Length Conduit Ordering Code Size mm 10 m. 30m. 50m. Code 10 12 16 20 25 32 40 50 70 95 16 20 25 32 EPG01 ** EPG02 EPG03 EPG04 EPG05 EPG06 EPG07 EPG08 EPG10 EPG12 EPB03 ** EPB04 EPB05 EPB06 available per meter available per meter u u u u u u PAHD-07 PAHD-10 PAHD-12 PAHD-17 PAHD-23 PAHD-29 VOHG-36 VOHG-48 PIHG-70 PIHG-95

u u u

OIL & CHEMICAL RESISTANT LT -H Flexible


Construction: Galvanised steel core. Twine packed with black type H covering. Temp. range: 50C to +130C Oil and chemical resistant.
(Blue type H covering available for intrinsically safe areas, order FLLH). Sizes 16-32mm only)

LIMITED FIRE HAZARD (LFH) LT -S Flexible (Limited Fire Hazard) Construction: Galvanised steel core. Twine packed with black LFH covering. Temp. range: 40C to +110C

LT -PVC Flexible
Construction: Galvanised steel core. Twine packed with black or grey PVC covering. Temp. range: 25C to +105C (For grey PVC order FLG).

CSA Flexible
Construction: Galvanised steel core. Twine packed, black PVC covering. CSA rated +75C

UL Flexible
Construction: Galvanised steel core. Copper packed, grey PVC covering. UL approved. UL rated: 10C to +60C
**10, 20, 30 should be added according to coil length. eg. 20 m of 32mm LT-H is FLH 0620

Normally held in stock with the manufacturer If not stock 6-8 weeks delivery Price and delivery status on application

British Conduit Size mm 16 20 25 32 40 50 63 16 20 25 32 40 50 63 16 20 25 32 40 50 63 16 20 25 32 40 50 63 16 20 25 32 40 50 63

US Trade Size Ins 3 /8 1 /2 3 /4 1 11/4 11/2 2 3 /8 1 /2 3 /4 1 11/4 11/2 2 3 /8 1 /2 3 /4 1 11/4 11/2 2 3 /8 1 /2 3 /4 1 11/4 11/2 2 3 /8 1 /2 3 /4 1 11/4 11/2 2

Ordering Code FLH03 ** FLH04 FLH05 FLH06 FLH07 FLH08 FLH09 FLS03 ** FLS04 FLS05 FLS06 FLS07 FLS08 FLS09 FLB03 ** FLB04 FLB05 FLB06 FLB07 FLB08 FLB09 FCB03 ** FCB04 FCB05 FCB06 FCB07 FCB08 FCB09 FUG03 ** FUG04 FUG05 FUG06 FUG07 FUG08 FUG09

10m. u u u u u u u u u 5 u u 5

Coil length 20m. 30m. u u u u u u u u u 5 u u 5

Electrolines Est. P. O. Box. 942 Yanbu Saudi Arabia Tel: +966 4 3225418 Fax: +966 4 3222213 Al-Jubail: Tel: +966 3 3632967 Fax: +966 3 3612967

Conduits
MEDIUM DUTY CONDUIT
Material: nylon Temp. range: -40C to +100C British Coil Length Conduit Code Size mm 10 m. 30m. 50m. 12 16 20 25 32 ERG02 ** ERG03 ERG04 ERG05 ERG06 International Ordering Code PAST-10S PAST-12S PAST-17S

LIGHT DUTY CONDUIT


Material: Polypropylene Temp. range: 0C to +60C British Ordering Conduit Code Size mm 16 20 25 32 ELG03 ** ELG03 ELG03 ELG03

Coil Length 10 m. 30m.

u u u

u u u
Normally held in stock with the manufacturer If not stock 6-8 weeks delivery Price and delivery status on application

** 10, 30, 50 should be added according to coil length. e.g. 30 metres of 20 mm Nylon Conduit is EPG0430.

Kopex

Superscreen Conduit Range


Superscreen Type H Oil & Chemical Resistant
Superscren Type S (Limited Fire Hazard) Construction: Black LFH Covering (layers) Leaded Steel, Leaded Steel Kraft Paper Temp. range: 40C to +110C Rec. connector: C18 British Conduit Size mm
16 16 20 20 25 25 32 32 40 40 50 50 63 63

Superscreen Type S Limited Fire Hazard (LFH)


Coil Ordering length Nato Stock Code Number m.

Superscren Type H Construction: Black type H Covering (layers) Leaded Steel Leaded Steel Kraft Paper Temp. range: 50C to +130C Rec. connector: C18

British Coil length Conduit Ordering Size mm Code 10m. 20m. 30m.
16 20 25 32 40 50 63 PHH03 ** PHH04 PHH05 PHH06 PHH07 PHH08 PHH09

u u u

u u u

**10, 20, 30 should be added according to coil length. 30 metres of Superscreen Type H 16mm is PHH0330. Conduit construction can include addtional layers on larger sizes.

u u u 5 5 5

PHS0310 PHS0330 PHS0410 PHS0430 PHS0510 PHS0530 PHS0610 PHS0620 PHS0710 PHS0720 PHS0810 PHS0820 PHS0910 PHS0920

10 30 10 30 10 30 10 20 10 20 10 20 10 20

5975-99-650-2580 5975-99-751-7805 5975-99-874-2955 5975-99-106-0422

PLIABLE CONDUIT RANGE


LS1-PVC Pliable Construction: Black PVC Covering (layers) Leaded Steel Kraft Paper Temp. range: 40C to +105C Rec. connector: C12, C14 British Coil length Conduit Ordering Size mm Code 10m. 20m. 30m.
10 12 16 20 25 32 40 50 63 75 12 16 20 25 32 40 50 63 75 PSB01 ** PSB02 PSB03 PSB04 PSB05 PSB06 PSB07 PSB08 PSB09 PSB10 PHB02 ** PHB03 PHB04 PHB05 PHB06 PHB07 PHB08 PHB09 PHB10 u

NLS1-PVC Pliable Construction: Grey PVC Covering (layers) Leaded Steel, Kraft Paper Temp. range: 40C to +150C Rec. connector: C12, C14 LS1 Pliable Construction: Leaded Steel (layers) Kraft Paper Temp. range: 40C to +150C Rec. connector: C10, C16

British Coil length Conduit Ordering Size mm Code 10m. 20m. 30m. 12 PNG02** 5 5 16 PNG03 u u
20 25 12 16 20 25 32 40 50 63 75 12 16 20 25 32 40 50 63 PNG04 PNG05 PSU02 ** PSU03 PSU04 PSU05 PSU06 PSU07 PSU08 PSU09 PSU10 PHU02** PHU03 PHU04 PHU05 PHU06 PHU07 PHU08 PHU09 PLU02 ** PLU03 PLU04 PLU05 PLU06 PLU07


u u u u u 5 5 u u u 5 5 5
u u

LS2-PVC Pliable Construction: Black PVC Covering (layers) Leaded Steel, Leaded Steel Kraft Paper Temp. range: 40C to +105C Rec. connector: C12, C14

5 u u 5 5 5 5

5 u

u 5 5 5 5

LS2 Pliable Construction: Leaded Steel (layers) Leaded Steel Temp. range: 40C to +150C Rec. connector: C10, C16

u u u 5 5

u u

AL2-PVC Pliable Construction: Black PVC Covering (layers) Aluminium, Aluminium Kraft Paper Temp. range: 40C to +105C Rec. connector: C12, C14

12 16 20 25 32 40 50 63 75

PLB02 ** PLB03 PLB04 PLB05 PLB06 PLB07 PLB08 PLB09 PLB10

5 5 5 5 5 5 5

5 5

5 5 5 5 5

AL1 Pliable Construction: Aluminium 12 (layers) Kraft paper 16 Temp. range: 40C to +150C 20 Rec. connector: C10, C16
25 32 40

u 5 5 5
5 5


u u

5 5 5

** 10, 20, 30 should be added according to coil length. e.g. 30 m of LS1-PVC 16mm is PSB0330

P. O. Box. 942 Yanbu Saudi Arabia

Normally held in stock with the manufacturer If not stock 6-8 weeks delivery Price and delivery status on application

Electrolines Est. Tel: +966 4 3225418 Fax: +966 4 3222213 Al-Jubail: Tel: +966 3 3632967 Fax: +966 3 3612967

Electrolines Est.

P. O. Box. 942 Yanbu Saudi Arabia

Tel: +966 4 3225418 Fax: +966 4 3222213 Al-Jubail: Tel: +966 3 3632967 Fax: +966 3 3612967