Procedure
Initialization
This procedure is completed in two steps. The first step is to configure the CX. The second is to configure the AB DeviceNet scanner card along with RSLogix 5000. In this example one DeviceNet cable with an external terminating resistor built into the connector is used.
4 October 2007
www.infoPLC.net
TwinCAT Configuration
4 October 2007
www.infoPLC.net
4 October 2007
www.infoPLC.net
Once "Search Ethernet" is selected, select "Broadcast Search". This sends out a broadcast ADS search. All ADS devices on the network will reply. Select the CX, click "IP Address", then "Add Route". Type your username and password. (By default the WINce username is "Administrator" and the password is left blank. The WINxpe username is "Administrator" and the password is: 1.) Click "Close", select the device, and click "OK".
4 October 2007
www.infoPLC.net
Now scan in the IO. Right click on "I/O Devices" and choose "Scan Devices".
4 October 2007
www.infoPLC.net
You will receive the following message: Hint: Not all devices will be found automatically. Click "OK". Now choose the devices you wish to scan into the System Manager. This exercise will only use the CX1500-B520 and the local CX1100. Click "OK".
Choose "Yes" to scan for boxes, then choose "OK" for the selected Baudrate.
4 October 2007
www.infoPLC.net
After scanning devices the System Manager should look similar to the one below. The CX1500-B520 will have 8 bytes in and 8 bytes out. This is important to know because later it will be scanned with the Rockwell controller.
Activate this configuration and put this system into run mode. TwinCAT setup is now complete.
4 October 2007
www.infoPLC.net
Open a new instance of RSNetworx and scan the network. Be sure the correct EDS file has been downloaded.
4 October 2007
10
www.infoPLC.net
4 October 2007
11
www.infoPLC.net
4 October 2007
12
www.infoPLC.net
Save this file and open a new RSLogix 5000 session. Add a DeviceNet card and point it to the RSNetworx file you just saved. Apply and go online.
4 October 2007
13