Instruction Sheet AMPTRAC*, Cat 5e, Modular, Universal Wiring, Patch Panels

NOTE Although a 2226 AWG wire size is recommended, some types of insulation (due to outer diameter measurement or material) may not terminate properly. Outside diameters of 1.27 mm [.050 in.] or larger are not typically recommended. Although, depending on the type of insulation, larger diameters may make acceptable terminations. Some wire types falling below 1.27 mm [.050 in.] diameter may not terminate properly because of a tougher insulation type. Qualification testing was conducted using 2226 AWG wire with an outside diameter of 0.91 mm [.036 in.].

4088682
21 AUG 02 Rev A

Standard 483 mm [19 In.] Panel Rack with 1032 or 1224 Tapped Holes

Identification Label (Customer Supplied)

The 110Connect Blocks may be terminated with Standard Impact Tool 5584181, Pro Impact Tool 13753081, Universal Wire Insertion Tool, or 788J1Type 5Pair Tool. Remove loose wire pieces. If tool does not properly trim wires, replace tool blade. Use of other cutting tools to trim wires may damage patch panel.

Sensor Contact Area (Typ) Cutoff Blade Insertion Blade

1032 or 1224 Steel Screw

Figure 1

1. INTRODUCTION
This instruction sheet covers the installation procedures for AMPTRAC, Cat 5e, Modular, Universal Wiring, Patch Panels 14353611 and 14353621. The panels can be mounted on any standard 483 mm [19 in.] equipment rack or communication cabinet as shown in Figure 1. NOTE All dimensions are in millimeters [with inches in brackets]. Figures are not drawn to scale.

2. DESCRIPTION
Each panel includes the necessary mounting hardware, universal T568A/T568B wiring labels, and cable management cable ties. See Figures 1 and 2.

3. INSTALLATION PROCEDURES (Figure 2) 3.1. General Instructions


Unpack assembly and install universal wiring labels, with the T568A or T568B side facing up, to match the wiring pattern being used at the outlet. Match label port numbers to port numbers on front of panel. Assemble cable ties or cable management bar(s).

Reasons for revision of this instruction sheet are provided in Section 4, REVISION SUMMARY.

E2002 Tyco Electronics Corporation, Harrisburg, PA.

This controlled document is subject to change. For latest revision call the AMP FAX* number. All International Rights Reserved. For more information on NETCONNECT* products, AMP and Tyco are trademarks. visit our website at www.ampnetconnect.com *Trademark Other products, logos, and company names used are the property of their respective owners.

TOOLING ASSISTANCE CENTER 18007221111 AMP FAX/PRODUCT INFO 18005226752 For Regional Customer Service, visit our website at www.tycoelectronics.com

1 of 2
LOC B

AMPTRAC, Cat 5e, Modular, Universal Wiring, Patch Panels

4088682

Rack

T568B Side or Tear Along Perforations Wiring Label Cable Tie Do Not Overtighten Bend Radius Not Less Than Four Times Cable Diameter Color Marks on T568A Side of Wiring Label
[ BLU BLU WHT WHT BLU GRN GRN WHT WHT GRN ORG ORG WHT WHT ORG BRN ] BRN WHT WHT BRN

T568A Side

Sheet of Universal Wiring Labels

Tie Release

Release Feature May be Used to Add Cables or Loosen Cable Tie

Color Marks on T568B Side of Wiring Label


[ BLU BLU WHT WHT BLU ORG ORG WHT WHT ORG GRN GRN WHT WHT GRN BRN ] BRN WHT WHT BRN

Cable Tie Application Cables

Cable Tie Holder

Cable Management Bar 4060421 (63.5 mm [2.50 In.] Deep) or 5575481 (127 mm [5 In.] Deep) Mounts Directly to Rack (Bar Purchased Separately)

Allow No More than 13 mm [0.5 In.] to Untwist

Strip Back Minimum Amount of Cable Jacket

Cable Cable Ties (Customer Supplied)


Figure 2

3.2. Special Instructions for Category 5 Enhanced Applications


At all times, the wiring practices must comply with practices of ANSI/TIA/EIA568A Specification. Guidelines covered in the above specification and shown in Figure 2 must be followed. NOTE

4. REVISION SUMMARY
Per EC 0990123702:
S Added ProImpact Tool reference to Figure 1

2 of 2