Type ST-C Cables

Extra Hard Service Thermoplastic Insulated, C: Common Use

Description
Multi-conductor Cable, two, three or four flexible soft copper conductors polyolefin insulated, twisted and external PVC Rubber jacket

Construction
Conductor Flexible soft copper conductor, Class K stranded Insulation Polyolefin (75 C) Jacket Flame retardant Polyvinyl Chloride with content of rubber

Characteristics
Operating Temperature 75 C. Operating Voltage 600 V.

Applications
Hard Service Cord for equipment and portable tools, special for factories, scenes and display cabinets. Open wiring installation, in portable extensions with terminals. By being of common use, it can be used like portable cord, control and power cable. Easy handling and flexibility in reduced spaces.

Specifications
CENTELSA ST-C Cables are manufactured under the following standards:
UL 1581, NTC-3203 Reference Standard for Electrical Wires, Cables and Flexible Cords UL 62, NTC-2356 Flexible Cord and Fixture Wire.

CENTELSA Specifications for ST-C Cables


7

Certifications
CENTELSA ST-C Flexible cords are certified by: CIDET (Colombia). Cert. No. 02005, according to RETIE (Colombian Technical Code of Electrical Installations) requirements

Colors
Conductors identification: 2, black-white; 3, black-white-green; 4, blackwhite-red-green. Black colored Jacket.

Packaging
Wood Reels. Reel lengths between 500 m and 2500 m.

Note: Other configurations, sizes, colors and length not specified herein
are available upon request.

Flexible Cord Type ST-C 600V, 60oC (International System Unit)


Extra Hard Service Thermoplastic Insulated, C: Common Use Standards: UL 62, NTC 2356 and CENTELSA specifications for ST-C cables

SIZE AWG

COPPER CONDUCTOR CONDUCTORS STRANDS STRAND SECTION No. DIAMETER (mm2) (mm)

DIAMETER (mm)

INSULATION JACKET OVERALL THICKNESS THICKNESS DIAMETER (mm) (mm) (mm)

APPROX. TOTAL WEIGHT (kg/km)

DC RESISTANCE AT 20C 1 (ohm/km)

AMPACITY 2 (A) 3

AMPACITY 2 (A) 4

20

18

16

14

12

10

2 3 4 2 3 4 2 3 4 2 3 4 2 3 4 2 3 4 2 3 4 2 3 4 2 3 4 2 3 4

10

0.254

0.51

0.97

0.64

16

0.254

0.81

1.23

0.76

26

0.254

1.32

1.51

0.76

41

0.254

2.08

1.98

0.76

65

0.254

3.29

2.52

0.76

104

0.254

5.27

3.21

0.76

168

0.254

8.51

3.66

1.14

266

0.254

13.48

4.77

1.52

420

0.254

21.28

6.00

1.52

665

0.254

33.70

7.56

1.52

0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 1.14 1.14 1.14 1.52 1.52 1.52 2.03 2.03 2.03 2.03 2.41 2.41 2.41 2.41 2.41 2.41

6.26 6.62 7.23 7.26 7.70 8.43 7.82 8.30 9.11 8.76 9.32 10.24 9.84 10.48 12.32 12.00 12.74 14.78 15.25 16.19 18.77 20.05 21.28 23.33 23.29 24.71 27.08 26.41 28.07 30.85

50 59 70 69 82 99 86 104 127 113 139 171 152 190 255 231 288 382 380 476 630 635 790 976 902 1133 1407 1254 1600 2003

35.4 35.4 35.4 22.1 22.1 22.1 13.6 13.6 13.6 8.63 8.63 8.63 5.45 5.45 5.45 3.40 3.40 3.40 2.11 2.11 2.11 1.33 1.33 1.33 0.843 0.843 0.843 0.532 0.532 0.532

10

13

10

18

15

25

20

30

25

40

35

55

45

70

60

95

80

Notes: 1. DC Resistance calculated based on a 17.241 ohm-mm2/km copper resistivity. 2. Ampacities based on 75C conductor temperature, and Section 400 of NEC (NTC 2050) and 30C ambient temperature. 3. Two current carrying conductors. 4. Three current carrying conductors. 5. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

Flexible Cord Type ST-C 600V, 60oC


Extra Hard Service Thermoplastic Insulated, C: Common Use Standards: UL 62, NTC 2356 and CENTELSA specifications for ST-C cables

SIZE AWG

COPPER CONDUCTOR CONDUCTORS STRANDS STRAND SECTION No. DIAMETER (kcmil) (mils)

DIAMETER (mils)

INSULATION JACKET OVERALL THICKNESS THICKNESS DIAMETER (mils) (mils) (mils)

APPROX. TOTAL WEIGHT (lb/kft)

DC RESISTANCE AT 20C 1 (ohm/kft)

AMPACITY 2 (A) 3

AMPACITY 2 (A) 4

20

18

16

14

12

10

2 3 4 2 3 4 2 3 4 2 3 4 2 3 4 2 3 4 2 3 4 2 3 4 2 3 4 2 3 4

10

10.0

1.00

38

25

16

10.0

1.60

48

30

26

10.0

2.60

59

30

41

10.0

4.10

78

30

65

10.0

6.50

99

30

104

10.0

10.40

126

30

168

10.0

16.80

144

45

266

10.0

26.60

188

60

420

10.0

42.00

236

60

665

10.0

66.50

298

60

30 30 30 30 30 30 30 30 30 30 30 30 30 30 45 45 45 60 60 60 80 80 80 80 95 95 95 95 95 95

246 261 284 286 303 332 308 327 359 345 367 403 387 413 485 472 502 582 600 637 739 789 838 919 917 973 1066 1040 1105 1215

33 39 47 46 55 67 58 70 85 76 93 115 102 128 172 155 194 256 256 320 423 427 531 656 606 761 945 843 1075 1346

10.8 10.8 10.8 6.74 6.74 6.74 4.15 4.15 4.15 2.63 2.63 2.63 1.66 1.66 1.66 1.04 1.04 1.04 0.642 0.642 0.642 0.406 0.406 0.406 0.257 0.257 0.257 0.162 0.162 0.162

10

13

10

18

15

25

20

30

25

40

35

55

45

70

60

95

80

Notas: 1. DC Resistance calculated based on a 10.371 ohm-cmil/ft copper resistivity. 2. Ampacities based on 75C conductor temperature, and Section 400 of NEC (NTC 2050) and 30C ambient temperature. 3. Two current carrying conductors. 4. Three current carrying conductors. 5. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

10

Flexible Cords Type ST


Extra Hard Service Thermoplastic Insulated

Description
Multi-conductor Cable, two, three or four flexible soft copper conductors polyvinyl chloride (PVC) insulated, twisted and external PVC jacket

Construction
Conductor Flexible soft copper conductor, Class K stranded Insulation Flame Retardant Polyvinyl chloride (PVC 60 C) Jacket Flame Retardant Polyvinyl chloride (PVC 60 C)

Characteristics
Operating Temperature 60 C. Operating Voltage 600 V.

Applications
Hard Service Cord for equipment and portable tools, special for factories, scenes and display cabinets. Open wiring installation, in portable extensions with terminals.

Specifications
CENTELSA ST Cables are manufactured under the following standards:
UL 1581, NTC-3203 Reference Standard for Electrical Wires, Cables and Flexible Cords UL 62, NTC-2356 Flexible Cord and Fixture Wire.

Certifications
CENTELSA ST Flexible cords are certified by UL, File E203934
11

Colors
Conductors identification: 2, black-white; 3, black-white-green; 4, blackwhite-red-green. Black colored Jacket.

Note: Other configurations, sizes, colors and length not specified herein
are available upon request.

12

Flexible Cords Type ST 600V, 60oC (International System Unit)


Extra Hard Service Thermoplastic Insulated Standard: UL 62, NTC-2356 Flexible Cord and Fixture Wire.

SIZE AWG

COPPER CONDUCTOR CONDUCTORS STRANDS STRAND SECTION No. DIAMETER (mm2) (mm)

DIAMETER (mm)

INSULATION JACKET OVERALL THICKNESS THICKNESS DIAMETER (mm) (mm) (mm)

APPROX. TOTAL WEIGHT (kg/km)

DC RESISTANCE AT 20C 1 (ohm/km)

AMPACITY 2 (A) 3

AMPACITY 2 (A) 4

14

12

10

2 3 4 2 3 4 2 3 4 2 3 4 2 3 4 2 3 4 2 3 4

41

0.254

2.08

1.98

1.14

65

0.254

3.29

2.52

1.14

104

0.254

5.27

3.21

1.14

168

0.254

8.51

3.66

1.52

266

0.254

13.48

4.12

1.52

420

0.254

21.28

6.72

1.52

665

0.254

33.70

8.58

1.52

2.03 2.03 2.03 2.41 2.41 2.41 2.41 2.41 2.41 2.79 2.79 3.18 3.18 3.18 3.56 3.56 3.56 3.94 3.94 3.94 4.32

12.91 13.58 14.71 14.77 15.53 16.80 16.15 17.02 18.47 19.40 20.45 23.01 21.10 22.23 24.90 27.09 28.62 31.96 31.59 33.41 37.15

210 244 290 283 331 394 357 425 512 535 644 818 692 851 1082 1088 1327 1674 1541 1899 2388

8.63 8.63 8.63 5.45 5.45 5.45 3.40 3.40 3.40 2.11 2.11 2.11 1.33 1.33 1.33 0.843 0.843 0.843 0.532 0.532 0.532

18

15

25

20

30

25

40

35

55

45

70

60

95

80

Notes: 1. DC Resistance calculated based on a 17.241 ohm-mm2/km copper resistivity. 2. Ampacities based on 60C conductor temperature, and Section 400 of NEC (NTC 2050) and 30C ambient temperature. 3. Two current carrying conductors. 4. Three current carrying conductors. 5. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

13

Flexible Cords Type ST 600V, 60oC


Extra Hard Service Thermoplastic Insulated Standard: UL 62, NTC-2356 Flexible Cord and Fixture Wire.

SIZE AWG

COPPER CONDUCTOR CONDUCTORS STRANDS STRAND SECTION No. DIAMETER (kcmil) (mils)

DIAMETER (mils)

INSULATION JACKET OVERALL THICKNESS THICKNESS DIAMETER (mils) (mils) (mils)

APPROX. TOTAL WEIGHT (lb/kft)

DC RESISTANCE AT 20C 1 (ohm/kft)

AMPACITY 2 (A) 3

AMPACITY 2 (A) 4

14

12

10

2 3 4 2 3 4 2 3 4 2 3 4 2 3 4 2 3 4 2 3 4

41

10.0

4.10

78

45

65

10.0

6.50

99

45

104

10.0

10.40

126

45

168

10.0

16.80

144

60

266

10.0

26.60

162

60

420

10.0

42.00

265

60

665

10.0

66.50

338

60

80 80 80 95 95 95 95 95 95 110 110 125 125 125 140 140 140 155 155 155 170

508 535 579 582 611 661 636 670 727 764 805 906 831 875 980 1066 1127 1258 1244 1315 1463

141 164 195 190 222 265 240 286 344 359 433 550 465 572 727 731 892 1125 1036 1277 1605

2.63 2.63 2.63 1.66 1.66 1.66 1.04 1.04 1.04 0.642 0.642 0.642 0.406 0.406 0.406 0.257 0.257 0.257 0.162 0.162 0.162

18

15

25

20

30

25

40

35

55

45

70

60

95

80

Notes: 1. DC Resistance calculated based on a 10.371 ohm-cmil/ft copper resistivity. 2. Ampacities based on 60C conductor temperature, and Section 400 of NEC (NTC 2050) and 30C ambient temperature. 3. Two current carrying conductors. 4.Three current carrying conductors. 5. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

14

Flexible Cords Type SJT


Junior Hard Service Thermoplastic Insulated

Description
Multi-conductor Cable, two, three or four flexible soft copper conductors polyvinyl chloride (PVC) insulated, twisted and external PVC jacket

Construction
Conductor Flexible soft copper conductor, Class K stranded Insulation Flame Retardant Polyvinyl chloride (PVC 60 C) Jacket Flame Retardant Polyvinyl chloride (PVC 60 C)

Characteristics
Operating Temperature 60 C. Operating Voltage 300 V.

Applications
Junior Hard Service Cord for industrial, commercial and residential equipment. Open wiring installation, in portable extensions with terminals.

Specifications
CENTELSA SJT Cables are manufactured under the following standards:
UL 1581, NTC-3203 Reference Standard for Electrical Wires, Cables and Flexible Cords UL 62, NTC-2356 Flexible Cord and Fixture Wire.

15

Certifications
CENTELSA SJT Flexible cords are certified by UL, File E203934

Colors
Conductors identification: 2, black-white; 3, black-white-green; 4, blackwhite-red-green. Black colored Jacket.

Note: Other configurations, sizes, colors and length not specified herein
are available upon request.

16

Flexible Cords Type SJT 600V, 60oC (International System Unit)


Junior Hard Service Thermoplastic Insulated Standard: UL 62, NTC-2356 Flexible Cord and Fixture Wire.

SIZE AWG

COPPER CONDUCTOR CONDUCTORS STRANDS STRAND SECTION No. DIAMETER (mm2) (mm)

DIAMETER (mm)

INSULATION JACKET OVERALL THICKNESS THICKNESS DIAMETER (mm) (mm) (mm)

APPROX. TOTAL WEIGHT (kg/km)

DC RESISTANCE AT 20C 1 (ohm/km)

AMPACITY 2 (A) 3

AMPACITY 2 (A) 4

18

16

14

12

10

2 3 4 2 3 4 2 3 4 2 3 4 2 3 4

16

0.254

0.81

1.23

0.76

26

0.254

1.32

1.51

0.76

41

0.254

2.08

1.98

0.76

65

0.254

3.29

2.52

0.76

104

0.254

5.27

3.21

1.14

0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 1.14 1.14 1.14 1.52 1.52 1.52

7.26 7.70 8.43 7.82 8.30 9.11 8.76 9.32 10.24 10.62 11.26 12.32 14.35 15.22 16.67

69 82 99 86 104 127 113 139 171 169 208 255 298 363 445

22.1 22.1 22.1 13.6 13.6 13.6 8.63 8.63 8.63 5.45 5.45 5.45 3.40 3.40 3.40

10

13

10

18

15

25

20

30

25

Notes: 1. DC Resistance calculated based on a 17.241 ohm-mm2/km copper resistivity. 2. Ampacities based on 60C conductor temperature, and Section 400 of NEC (NTC 2050) and 30C ambient temperature. 3. Two current carrying conductors. 4. Three current carrying conductors. 5. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

Flexible Cords Type SJT 600V, 60oC


Junior Hard Service Thermoplastic Insulated Standard: UL 62, NTC-2356 Flexible Cord and Fixture Wire.
COPPER CONDUCTOR CONDUCTORS STRANDS STRAND SECTION No. DIAMETER (kcmil) (mils) INSULATION JACKET OVERALL THICKNESS THICKNESS DIAMETER (mils) (mils) (mils) APPROX. TOTAL WEIGHT (lb/kft) DC RESISTANCE AT 20C 1 (ohm/kft) AMPACITY 2 (A) 3 AMPACITY 2 (A) 4

SIZE AWG

DIAMETER (mils)

18

16

14

12

10

2 3 4 2 3 4 2 3 4 2 3 4 2 3 4

16

10.0

1.60

48

30

26

10.0

2.60

59

30

41

10.0

4.10

78

30

65

10.0

6.50

99

30

104

10.0

10.40

126

45

30 30 30 30 30 30 30 30 30 45 45 45 60 60 60

286 303 332 308 327 359 345 367 403 418 443 485 565 599 656

46 55 67 58 70 85 76 93 115 114 140 172 200 244 299

6.74 6.74 6.74 4.15 4.15 4.15 2.63 2.63 2.63 1.66 1.66 1.66 1.04 1.04 1.04

10

13

10

18

15

25

20

30

25

Notes:

1. DC Resistance calculated based on a 10.371 ohm-cmil/ft copper resistivity. 2. Ampacities based on 60C conductor temperature, and Section 400 of NEC (NTC 2050) and 30C ambient temperature. 3. Two current carrying conductors. 4. Three current carrying conductors. 5. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

17

Flexible Cords Type SVT


Service Vacuum-cleaner cord, Thermoplastic Insulated

Description
Multi-conductor Cable, two, three or four flexible soft copper conductors polyvinyl chloride (PVC) insulated, twisted and external PVC jacket

Construction
Conductor Flexible soft copper conductor, Class M stranded Insulation Flame Retardant Polyvinyl chloride (PVC 60 C) Jacket Flame Retardant Polyvinyl chloride (PVC 60 C)

Characteristics
Operating Temperature 60 C. Operating Voltage 300 V.

Applications
Service Cord, vacuum cleaner cord computers and similar equipments. Open wiring installation, in portable extensions with terminals.

Specifications
CENTELSA SVT Cables are manufactured under the following standards:
UL 1581, NTC-3203 Reference Standard for Electrical Wires, Cables and Flexible Cords UL 62, NTC-2356 Flexible Cord and Fixture Wire.

18

Certifications
CENTELSA SVT Flexible cords are certified by UL, File E203934

Colors
Conductors identification: 2, black-white; 3, black-white-green; 4, black-whitered-green. Black colored Jacket.

Note: Other configurations, sizes, colors and length not specified herein are available
upon request.

19

Flexible Cord Type SVT 300V 60C (International System Unit)


Service Vacuum-cleaner cord, Thermoplastic Insulated Standard: UL 62, NTC-ICONTEC 2356. Flexible and Fixture Wire

SIZE AWG

COPPER CONDUCTOR CONDUCTORS STRANDS STRAND SECTION No. DIAMETER (mm2) (mm)

DIAMETER (mm)

INSULATION JACKET OVERALL THICKNESS THICKNESS DIAMETER (mm) (mm) (mm)

APPROX. TOTAL WEIGHT (kg/km)

DC RESISTANCE AT 20C 1 (ohm/km)

AMPACITY 2 (A) 3

AMPACITY 2 (A) 4

18

16

2 3 4 2 3 4

41

0.160

0.82

65

0.160

1.31

1.16 6.76 6.00 1.48 6.76 6.00

0.38

0.38

0.76 0.76 0.76 0.76 0.76 0.76

5.60 5.91 6.43 6.24 6.60 7.20

46 56 68 62 76 94

22.1 22.1 22.1 13.6 13.6 13.6

10

13

10

Notes: 1. Fourth conductor is used as grounding conductor. 2. DC Resistance calculated based on a 17.241 ohm-mm2/km copper resistivity. 3. Ampacities based on 60C conductor temperature, and Section 400 of NEC (NTC 2050) and 30C ambient temperature. 4. Two current carrying conductors. 5. Three current carrying conductors. 6. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

Flexible Cord Type SVT 300V 60C


Service Vacuum-cleaner cord, Thermoplastic Insulated Standard: UL 62, NTC-ICONTEC 2356. Flexible and Fixture Wire
COPPER CONDUCTOR CONDUCTORS STRANDS STRAND SECTION No. DIAMETER (kcmil) (mils) INSULATION JACKET OVERALL THICKNESS THICKNESS DIAMETER (mils) (mils) (mils) APPROX. TOTAL WEIGHT (lb/kft) DC RESISTANCE AT 20C 1 (ohm/kft) AMPACITY 2 (A) 3 AMPACITY 2 (A) 4

SIZE AWG

DIAMETER (mils)

18

16

2 3 4 2 3 4

41

6.3

1.63

46

15

65

6.3

2.58

58

15

30 30 30 30 30 30

220 233 253 246 260 284

31 38 46 41 51 63

6.74 6.74 6.74 4.15 4.15 4.15

10

13

10

Notes: 1. Fourth conductor is used as grounding conductor. 2. DC Resistance calculated based on a 10.371 ohm-cmil/ft copper resistivity. 3. Ampacities based on 60C conductor temperature, and Section 400 of NEC (NTC 2050) and 30C ambient temperature. 4. Two current carrying conductors. 5. Three current carrying conductors. 6. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

20

Parallel Cord Type SPT-C


Parallel Cord, Thermoplastic Insulated

Description
Two copper flexible copper conductor, paralleled and PVC insulated.

Construction
Flexible soft copper conductor, Class K stranded Insulation Flame Retardant Polyvinyl chloride (PVC 60 C) Integral insulation with separation membrane, and polarization ridges in one conductor.

Characteristics
Operating Temperature 60 C. Operating Voltage 300 V. (600V optional)

Applications
Service Cord, for portable electrical devices. Open wiring installation, in portable extensions with terminals.

Specifications
CENTELSA SPT Cables are manufactured under the following standards:
UL 1581, NTC-3203 Reference Standard for Electrical Wires, Cables and Flexible Cords UL 62, NTC-2356 Flexible Cord and Fixture Wire.

CENTELSA Specifications for SPT-C Cables

Certifications
CENTELSA SPT-C Paralleled cords are certified by: CIDET (Colombia). Cert. No. 02004, according to RETIE (Colombian Technical Code of Electrical Installations) requirements
21

Colors
White, grey brown and black. Optional with red strip at one conductor for polarization indication.

Packaging
100 m spools covered with plastic thermo pack, in corrugated carton boxes.

Note: Other configurations, sizes, colors and length not specified herein
are available upon request.

22

Paralleled Cord Type SPT-C 300V, 60C (International System Unit)


Parallel Cord, Thermoplastic Insulated Standards: UL 62, NTC 2356 and CENTELSA specifications for SPT-C cables

COPPER CONDUCTOR SIZE AWG STRANDS STRAND SECTION DIAMETER (mm2) (mm) DIAMETER (mm)

INSULATION THICKNESS (mm)

EXTERNAL DIMENSIONS (mm)

APPROX. TOTAL WEIGHT (kg/km)

DC RESISTANCE AT 20C 1 (ohm/km)

AMPACITY 2 (A)

2 2 2 2 2 2

X X X X X X

22 20 18 16 14 12

7 10 16 26 41 65

0.254 0.254 0.254 0.254 0.254 0.254

0.35 0.51 0.81 1.32 2.08 3.29

0.76 0.97 1.23 1.51 1.98 2.52

0.51 0.51 0.64 0.64 0.64 0.64

1.86 2.07 2.59 2.87 3.34 3.88

X X X X X X

3.72 4.14 5.17 5.73 6.67 7.75

14 17 28 39 57 84

49.6 34.7 21.7 13.3 8.46 5.34

2 10 13 18 25

Notes: 1. DC Resistance calculated based on a 17.241 ohm-mm2/km copper resistivity. 2. Ampacities based on 60C conductor temperature, and Section 400 of NEC (NTC 2050) and 30C ambient temperature. 3. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

Paralleled Cord Type SPT-C 300V, 60C)


Parallel Cord, Thermoplastic Insulated Standards: UL 62, NTC 2356 and CENTELSA specifications for SPT-C cables
COPPER CONDUCTOR SIZE AWG STRANDS STRAND SECTION DIAMETER (kcmil) (mils) DIAMETER (mils) INSULATION THICKNESS (mils) EXTERNAL DIMENSIONS (mils) APPROX. TOTAL WEIGHT (lb/kft) DC RESISTANCE AT 20C 1 (ohm/kft) AMPACITY 2 (A)

2 2 2 2 2 2

X X X X X X

22 20 18 16 14 12

7 10 16 26 41 65

10.0 10.0 10.0 10.0 10.0 10.0

0.70 1.00 1.60 2.60 4.10 6.50

30 38 48 59 78 99

20 20 25 25 25 25

73 82 102 113 131 153

X X X X X X

147 163 204 226 263 305

9 12 19 26 38 56

15.1 10.6 6.61 4.07 2.58 1.63

2 10 13 18 25

Notes: 1. DC Resistance calculated based on a 10.371 ohm-cmil/ft copper resistivity. 2. Ampacities based on 60C conductor temperature, and Section 400 of NEC (NTC 2050) and 30C ambient temperature. 3. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

23

Paralleled Cord Type SPT-1 SPT-2 SPT-3


Parallel Cord, Thermoplastic Insulated

Description
Two copper flexible copper conductor, paralleled and PVC insulated. Conductor Flexible soft copper conductor, Class M stranded for SPT-1 and SPT2 Flexible soft copper conductor, Class K stranded for SPT-3 Insulation Flame Retardant Polyvinyl chloride (PVC 60 C) Integral insulation with separation membrane, and polarization ridges in one conductor.

Characteristics
Operating Temperature 60 C. Operating Voltage 300 V.

Applications
SPT-1: Portable lamps feeders, fans, radios, clocks, household appliances and office equipment. SPT-2: Same as above, stereo and video devices SPT-3: Freezers, coolers, air conditioning equipment, dish washing machines, waste disposers and office equipment.

Specifications
CENTELSA SPT-1, SPT-2 and SPT-3 Paralleled Cords are manufactured under the following standards:
UL 1581, NTC-3203 Reference Standard for Electrical Wires, Cables and Flexible Cords
24

UL 62, NTC-2356 Flexible Cord and Fixture Wire.

Colors
White, grey, brown and black.

Packaging
100 m spools covered with plastic thermo pack, in corrugated carton boxes.

Note: Other configurations, sizes, colors and length not specified herein are available
upon request.

25

Paralleled Cords Type SPT-1 SPT-2 SPT-3 300V, 60C (International System Unit)
Parallel Cord, Thermoplastic Insulated Standard: UL 62, NTC 2356. Flexible and Fixture Wire

COPPER CONDUCTOR TYPE SIZE AWG STRANDS STRAND SECTION DIAMETER (mm2) (mm) DIAMETER (mm)

INSULATION THICKNESS (mm)

EXTERNAL DIMENSIONS (mm)

APPROX. TOTAL WEIGHT (kg/km)

DC RESISTANCE AT 20C 1 (ohm/km)

AMPACITY 2 (A)

SPT-1 SPT-2

SPT-3

2 2 2 2 2 2 2 2 2

X X X X X X X X X

20 18 18 16 18 16 14 12 10

26 41 41 65 16 26 41 65 104

0.160 0.160 0.160 0.160 0.254 0.254 0.254 0.254 0.254

0.52 0.82 0.82 1.31 0.81 1.32 2.08 3.29 5.27

0.92 1.16 1.16 1.48 1.23 1.51 1.98 2.52 3.21

0.76 0.76 1.14 1.14 1.52 1.52 2.03 2.41 2.79

2.52 2.76 3.53 3.85 4.39 4.67 6.16 7.48 8.96

X 4.63 X 5.11 X 6.78 X 7.42 X 8.49 X 9.05 X 11.01 X 12.87 X 15.04

17 24 36 50 51 68 115 177 268

33.6 21.3 21.3 13.5 21.7 13.3 8.46 5.34 3.34

2 10 10 13 10 13 18 25 30

Notes: 1. DC Resistance calculated based on a 17.241 ohm-mm2/km copper resistivity. 2. Ampacities based on 60C conductor temperature, and Section 400 of NEC (NTC 2050) and 30C ambient temperature. 3. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

Paralleled Cords Type SPT-1 SPT-2 SPT-3 300V, 60C


Parallel Cord, Thermoplastic Insulated Standard: UL 62, NTC 2356. Flexible and Fixture Wire
COPPER CONDUCTOR TYPE SIZE AWG STRANDS STRAND SECTION DIAMETER (kcmil) (mils) DIAMETER (mils) INSULATION THICKNESS (mils) EXTERNAL DIMENSIONS (mils) APPROX. TOTAL WEIGHT (lb/kft) DC RESISTANCE AT 20C 1 (ohm/kft) AMPACITY 2 (A)

SPT-1 SPT-2

SPT-3

2 2 2 2 2 2 2 2 2

X X X X X X X X X

20 18 18 16 18 16 14 12 10

26 41 41 65 16 26 41 65 104

6.3 6.3 6.3 6.3 10.0 10.0 10.0 10.0 10.0

1.03 1.63 1.63 2.58 1.60 2.60 4.10 6.50 10.40

36 46 46 58 48 59 78 99 126

30 30 45 45 60 60 80 95 110

99 109 139 152 173 184 243 295 353

X X X X X X X X X

182 201 267 292 334 356 434 507 592

12 16 24 33 35 46 77 119 180

10.3 6.50 6.50 4.10 6.61 4.07 2.58 1.63 1.02

2 10 10 13 10 13 18 25 30

Notes: 1. DC Resistance calculated based on a 10.371 ohm-cmil/ft copper resistivity. 2. Ampacities based on 60C conductor temperature, and Section 400 of NEC (NTC 2050) and 30C ambient temperature. 3. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

26

Cables Type TFF and TWK


Thermoplastic Insulation, Flexible Fixture Wire Thermoplastic Insulation, Suitable for Wet Locations, Class K Stranding

Description
Soft copper flexible conductor PVC insulated.

Construction
Conductor Flexible soft copper conductor, Class K stranded Insulation Flame Retardant Polyvinyl chloride (PVC 60 C)

Characteristics
Operation Temperature 60 C. Operating Voltage 600 V.

Applications
Internal equipment wiring, boards, in ducts or raceways. Also used in low voltage automotive wiring.

Specifications
CENTELSA TFF and TWK Cables are manufactured under the following standards:
UL 1581, NTC-3203 Reference Standard for Electrical Wires, Cables and Flexible Cords UL 62, NTC-2356 Flexible Cord and Fixture Wire, for TFF UL 83, NTC-1332 Thermoplastic insulated Wires and Cables, for TWK

Colors
Black, white, red, green, yellow, blue.

27

Packaging
100 m spools covered with plastic thermo pack, in corrugated carton boxes.

Note: Other configurations, sizes, colors and length not specified herein
are available upon request.

28

Cables Type TFF and TWK 600V, 60C (International System Units)
Thermoplastic Insulation, Flexible Fixture Wire Thermoplastic Insulation, Suitable for Wet Locations, Class K Stranding Standard: UL 62, NTC 2356. Flexible and Fixture Wire, for TFF UL 83, NTC-1332 Thermoplastic insulated Wires and Cables, for TWK

TYPE

SIZE AWG

STRANDS

STRAND SECTION CONDUCTOR DIAMETER (mm2) DIAMETER (mm) (mm)

INSULATION THICKNESS (mm)

DIAMETER OVER INSULATION (mm)

APPROX. TOTAL WEIGHT (kg/km)

DC RESISTANCE AT 20C 1 (ohm/km)

AMPACITY 2 (A)

TFF

TWK

18 16 14 12 10 8 6

16 26 41 65 104 168 266

0.254 0.254 0.254 0.254 0.254 0.254 0.254

0.81 1.32 2.08 3.29 5.27 8.51 13.48

1.23 1.51 1.98 2.52 3.21 3.66 4.12

0.76 0.76 0.76 0.76 0.76 1.14 1.52

2.83 3.11 3.58 4.12 4.81 6.04 7.28

15 20 29 42 63 104 164

21.7 13.3 8.46 5.34 3.34 2.07 1.30

10 13 18 25 30 40 55

Notes: 1. DC Resistance calculated based on a 17.241 ohm-mm2/km copper resistivity. 2. Ampacities based on 60C conductor temperature, and Section 400 of NEC (NTC 2050) and 30C ambient temperature. 3. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

Cables Type TFF and TWK 600V, 60C


Thermoplastic Insulation, Flexible Fixture Wire Thermoplastic Insulation, Suitable for Wet Locations, Class K Stranding Standard: UL 62, NTC 2356. Flexible and Fixture Wire, for TFF UL 83, NTC-1332 Thermoplastic insulated Wires and Cables, for TWK
AMPACITY 2 (A)

TYPE

SIZE AWG

STRANDS

STRAND SECTION CONDUCTOR DIAMETER (kcmil) DIAMETER (mils) (mils)

INSULATION THICKNESS (mils)

DIAMETER OVER INSULATION (mils)

APPROX. TOTAL WEIGHT (lb/kft)

DC RESISTANCE AT 20C 1 (ohm/kft)

TFF

TWK

18 16 14 12 10 8 6

16 26 41 65 104 168 266

10.0 10.0 10.0 10.0 10.0 10.0 10.0

1.60 2.60 4.10 6.50 10.40 16.80 26.60

48 59 78 99 126 144 162

30 30 30 30 30 45 60

111 122 141 162 189 238 287

10 14 20 28 42 70 110

6.61 4.07 2.58 1.63 1.02 0.630 0.398

10 13 18 25 30 40 55

Notes: 1. Resistance calculated based on a 10.371 ohm-cmil/ft copper resistivity. 2. Ampacities based on 60C conductor temperature, and Section 400 of NEC (NTC 2050) and 30C ambient temperature. 3. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

29

Cables Type TFFN


Thermoplastic Insulation, Flexible Fixture Wire, Nylon Jacket

Description Soft copper conductor, PVC insulated and with a Nylon covering Construction Conductor

Flexible soft copper conductor, Class K stranded


Insulation Polyvinyl Chloride (PVC 90 C), flame retardant Jacket Abrasion resistant Nylon Characteristics Operating Temperature 90C. Operating Voltage 600 V. Applications TFFN cables and wires are used generally in internal equipment and board wiring. Installation: in ducts tubing and boards. Special for locations with abrasive environment, oil, grease, gasoline and other chemical agents contaminated ambient. Its reduced diameter permits an optimum utilization of ducts or sites where is installed. Standards CENTELSA TFFN wires and cables are manufactured under the following standards: UL 1581, NTC-3203 Reference Standard for Electrical Wires, Cables and Flexible Cords UL 62, NTC-2356 Flexible Cord and Fixture Wire

30

Colors Black, white, red, yellow, blue. Packaging 100 m spools covered with plastic thermo pack, in corrugated carton boxes. Note: Other configurations, sizes, colors and length not specified herein are available upon request.

31

Cable Type TFFN 600V (International System Units) Thermoplastic Insulation, Fixture Wire, Nylon Jacket (90 C) Standard: UL 62, NTC-2356. Flexible Cord and Fixture Wire.
SIZE AWG STRANDS STRAND SECTION CONDUCTOR DIAMETER (mm2) DIAMETER (mm) (mm) INSULATION THICKNESS (mm) DIAMETER JACKET OVER THICKNESS INSULATION (mm) (mm) DIAMETER OVER JACKET (mm) APPROX. TOTAL WEIGHT (kg/km) DC RESISTANCE AT 20C 1 (ohm/km) AMPACITY 2 (A)

18 16

16 26

0.254 0.254

0.81 1.32

1.23 1.51

0.38 0.38

2.06 2.36

0.10 0.10

2.29 2.59

11 17

21.4 13.4

6 8

Notes: 1. DC Resistance calculated based on a 17.241 ohm-mm2/km copper resistivity. 2. Ampacities based on 60C conductor temperature, and Section 400 of NEC (NTC 2050) and 30C ambient temperature. 3. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

Cable Type TFFN 600V, 90C Thermoplastic Insulation, Fixture Wire, Nylon Jacket Standard: UL 62, NTC-2356. Flexible Cord and Fixture Wire.
SIZE AWG STRANDS STRAND SECTION CONDUCTOR INSULATION DIAMETER (kcmil) DIAMETER THICKNESS (mils) (mils) (mils) DIAMETER JACKET DIAMETER OVER THICKNESS OVER INSULATION (mils) JACKET (mils) (mm) APPROX. TOTAL WEIGHT (lb/kft) DC RESISTANCE AT 20C 1 (ohm/kft) AMPACITY 2 (A)

18 16

16 26

10.0 10.0

1.60 2.60

48 59

15 15

81 93

4 4

90 102

8 11

6.51 4.10

6 8

Notes: 1. DC Resistance calculated based on a 10.371 ohm-cmil/ft copper resistivity. 2. Ampacities based on 60C conductor temperature, and Section 400 of NEC (NTC 2050) and 30C ambient temperature. 3. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

32

Lighting Cables

Description
Soft copper flexible conductor PVC insulated.

Construction
Conductor Flexible soft copper conductor, Class K stranded Insulation Flame Retardant Polyvinyl chloride (PVC 105 C)

Characteristics
Operating Temperature 105 C. Operating Voltage 600 V.

Applications
Lighting connections and high temperature applications.

Specifications
CENTELSA LIGHTING Cables are manufactured under the following standards:
UL 1581, NTC-3203 Reference Standard for Electrical Wires, Cables and Flexible Cords UL 83, NTC-1332 Thermoplastic insulated Wires and Cables UL 62, NTC-2356 Flexible Cord and Fixture Wire (Sizes 20 to 16 AWG)

CENTELSA Specifications for LIGHTING Cables


Colors Black, white, red, yellow, blue.

33

Packaging 100 m spools covered with plastic thermo pack, in corrugated carton boxes. Note: Other configurations, sizes, colors and length not specified herein are available upon request.

34

Lighting Cables 105C (International System Units)


Standard: UL 62, NTC 2356. Flexible and Fixture Wire UL 83, NTC-1332 Thermoplastic insulated Wires and Cables CENTELSA Specifications for LIGHTING Cables
STRAND SECTION CONDUCTOR DIAMETER DIAMETER (mm2) (mm) (mm) INSULATION THICKNESS (mm) DIAMETER OVER INSULATION (mm) APPROX. TOTAL WEIGHT (kg/km) DC RESISTANCE AT 20C 1 (ohm/km)

SIZE AWG

STRANDS

20 18 16 14 12 10 8 6

10 16 26 41 65 104 168 266

0.254 0.254 0.254 0.254 0.254 0.254 0.254 0.254

0.51 0.81 1.32 2.08 3.29 5.27 8.51 13.48

0.97 1.23 1.51 1.98 2.52 3.21 3.66 4.12

0.76 0.76 0.76 0.76 0.76 0.76 1.14 1.52

2.23 2.49 2.77 3.24 3.78 4.47 5.52 6.58

9 13 18 26 39 59 96 152

34.7 21.7 13.3 8.46 5.34 3.34 2.07 1.30

Notes: 1. DC Resistance calculated based on a 17.241 ohm-mm2/km copper resistivity. 2. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

Lighting Cables 105C


Standard: UL 62, NTC 2356. Flexible and Fixture Wire UL 83, NTC-1332 Thermoplastic insulated Wires and Cables CENTELSA Specifications for LIGHTING Cables
STRAND SECTION CONDUCTOR DIAMETER DIAMETER (kcmil) (mils) (mils) INSULATION THICKNESS (mils) DIAMETER OVER INSULATION (mils) APPROX. TOTAL WEIGHT (lb/kft) DC RESISTANCE AT 20C 1 (ohm/kft)

SIZE AWG

STRANDS

20 18 16 14 12 10 8 6

10 16 26 41 65 104 168 266

10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0

1.00 1.60 2.60 4.10 6.50 10.40 16.80 26.60

38 48 59 78 99 126 144 162

30 30 30 30 30 30 45 60

88 98 109 128 149 176 217 259

6 8 12 18 26 40 65 102

10.6 6.6 4.1 2.58 1.63 1.02 0.63 0.40

Notes: 1. DC Resistance calculated based on a 10.371 ohm-cmil/ft copper resistivity. 2. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

35

Cables Type XGW


Cross (X) Linked Polyethylene Insulated 125C, General Purpose Wire

Description
Soft copper flexible conductor XLPE insulated.

Construction
Conductor Flexible soft copper conductor, Class K stranded Insulation Flame retardant Black Cross Linked Polyethylene (XLPE 125C)

Characteristics
Operating Temperature 125 C.

Applications
Used generally in internal equipment and board wiring. Installation in ducts or raceways. High temperature applications. Also used in automotive low voltage wiring. Insulation resistant to abrasion, gasoline, oil, solvents and chemical agents.

Specifications
CENTELSA XGW Cables are manufactured under the following standards:
UL 1581, NTC-3203 Reference Standard for Electrical Wires, Cables and Flexible Cords

CENTELSA Specifications for XGW Cables

36

Packaging 100 m spools covered with plastic thermo pack, in corrugated carton boxes. Note: Other configurations, sizes, colors and length not specified herein are available upon request.

37

Cables Type XGW 600V, 125C (International System Units)


Cross (X) Linked Polyethylene Insulated 125C, General Purpose Wire Standard: CENTELSA Specifications for XGW Cables

SIZE AWG

STRANDS

STRAND SECTION CONDUCTOR DIAMETER DIAMETER (mm2) (mm) (mm)

INSULATION THICKNESS (mm)

DIAMETER OVER INSULATION (mm)

APPROX. TOTAL WEIGHT (kg/km)

DC RESISTANCE AT 20C 1 (ohm/km)

20 18 16 14 12 10 8

10 16 26 41 65 104 168

0.254 0.254 0.254 0.254 0.254 0.254 0.254

0.51 0.81 1.32 2.08 3.29 5.27 8.51

0.97 1.23 1.51 1.98 2.52 3.21 3.66

0.74 0.76 0.81 0.89 0.94 1.04 1.09

2.19 2.49 2.85 3.44 4.06 4.91 5.42

9 13 18 28 41 64 95

34.7 21.7 13.3 8.46 5.34 3.34 2.07

Notes: 1. DC Resistance calculated based on a 17.241 ohm-mm2/km copper resistivity. 2. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

Cables Type XGW 600V, 125C

Cross (X) Linked Polyethylene Insulated 125C, General Purpose Wire Standard: CENTELSA Specifications for XGW Cables
SIZE AWG STRANDS STRAND SECTION CONDUCTOR DIAMETER DIAMETER (kcmil) (mils) (mils) INSULATION THICKNESS (mils) DIAMETER OVER INSULATION (mils) APPROX. TOTAL WEIGHT (lb/kft) DC RESISTANCE AT 20C 1 (ohm/kft)

20 18 16 14 12 10 8

10 16 26 41 65 104 168

10.0 10.0 10.0 10.0 10.0 10.0 10.0

1.00 1.60 2.60 4.10 6.50 10.40 16.80

38 48 59 78 99 126 144

29 30 32 35 37 41 43

84 95 110 133 157 191 211

6 8 12 19 28 43 64

10.6 6.61 4.07 2.58 1.63 1.02 0.630

Notes: 1. DC Resistance calculated based on a 10.371 ohm-cmil/ft copper resistivity. 2. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

38

Cables Type HTS-C

Heavy Duty Thermoset Elastomer (Synthetic Rubber) Insulated 150C, C: Common use

Description
Soft tinned copper flexible conductor Thermoset Elastomer insulated.

Construction
Conductor Flexible tinned soft copper conductor, Class K stranded Insulation Black Thermoset Elastomer Flame retardant (XLPE 150C)

Characteristics
Operating Temperature 150 C.

Applications
Used generally in internal equipment and board wiring. Installation in ducts or raceways, transit zones, high temperature applications. Also used in automotive low voltage wiring. Flexible insulation, low smoke emissions, non halogenated, lead free and excellent thermal stability.

Specifications
CENTELSA HTS-C Cables are manufactured under the following standards:
UL 1581, NTC-3203 Reference Standard for Electrical Wires, Cables and Flexible Cords

CENTELSA Specifications for HTS-C Cables

39

Packaging 100 m spools covered with plastic thermo pack, in corrugated carton boxes. Note: Other configurations, sizes, colors and length not specified herein are available upon request.

40

Heavy Duty Thermoset Elastomer (Synthetic Rubber) Insulated 150C, C: Common use
Standard: CENTELSA Specifications for HTS-C Cables

Cables Type HTS-C 600V, 150C (International System Unit)

SIZE AWG

STRANDS

STRAND SECTION CONDUCTOR DIAMETER DIAMETER (mm2) (mm) (mm)

INSULATION THICKNESS (mm)

DIAMETER OVER INSULATION (mm)

APPROX. TOTAL WEIGHT (kg/km)

DC RESISTANCE AT 20C 1 (ohm/km)

18 16 14 12 10 8 6 4 2 1 1/0 2/0 3/0 4/0

16 26 41 65 104 168 266 420 665 836 1064 1323 1666 2107

0.254 0.254 0.254 0.254 0.254 0.254 0.254 0.254 0.254 0.254 0.254 0.254 0.254 0.254

0.81 1.32 2.08 3.29 5.27 8.51 13.48 21.28 33.70 42.36 53.91 67.04 84.42 106.76

1.23 1.51 1.98 2.52 3.21 3.66 4.12 6.72 8.58 9.77 11.10 12.47 14.10 15.97

0.73 0.79 0.82 0.90 0.90 1.10 1.19 1.27 1.29 1.29 1.29 1.29 1.54 1.54

2.77 3.17 3.70 4.42 5.11 5.94 6.60 9.36 11.26 12.45 13.78 15.15 17.30 19.17

14 20 29 44 65 101 151 239 365 451 564 691 878 1094

22.6 13.9 8.8 5.6 3.5 2.1 1.4 0.9 0.5 0.4 0.3 0.3 0.2 0.2

Notes: 1. DC Resistance calculated based on a 17.241 ohm-mm2/km copper resistivity. 2. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

Cables Type HTS-C 600V, 150C

Heavy Duty Thermoset Elastomer (Synthetic Rubber) Insulated 150C, C: Common use
Standard: CENTELSA Specifications for HTS-C Cables

SIZE AWG

STRANDS

STRAND SECTION CONDUCTOR DIAMETER DIAMETER (kcmil) (mils) (mils)

INSULATION THICKNESS (mils)

DIAMETER OVER INSULATION (mils)

APPROX. TOTAL WEIGHT (lb/kft)

DC RESISTANCE AT 20C 1 (ohm/kft)

18 16 14 12 10 8 6 4 2 1 1/0 2/0 3/0 4/0

16 26 41 65 104 168 266 420 665 836 1064 1323 1666 2107

10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0

1.60 2.60 4.10 6.50 10.40 16.80 26.60 42.00 66.50 83.60 106.40 132.30 166.60 210.70

48 59 78 99 126 144 162 265 338 385 437 491 555 629

29 31 32 36 36 43 47 50 51 51 51 51 61 61

109 125 146 174 201 234 260 369 443 490 543 596 681 755

9 14 20 30 44 68 102 161 245 303 379 464 590 735

6.9 4.23 2.68 1.69 1.06 0.65 0.41 0.26 0.16 0.13 0.10 0.08 0.06 0.05

Notes: 1. DC Resistance calculated based on a 10.371 ohm-cmil/ft copper resistivity. 2. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

41

Automotive Cables Type GPT


General Purpose Thermoplastic Insulated

Description
Soft copper flexible conductor PVC insulated.

Construction
Conductor Flexible soft copper conductor, Class K stranded Insulation Flame Retardant Polyvinyl chloride (PVC 75 C)

Characteristics
Operating Temperature 75 C. Operating Voltage 50 V.

Applications
Low voltage automotive wiring. Insulation resistant to abrasion gasoline and oil.

Specifications
CENTELSA GPT Cables are manufactured under the following standards:
UL 1581, NTC-3203 Reference Standard for Electrical Wires, Cables and Flexible Cords SAE J1128 NTC-1116 Primary Low Voltage Cables Colors Black, white, red, yellow, blue, brown, orange grey and violet.

42

Packaging 100 m spools covered with plastic thermo pack, in corrugated carton boxes. Note: Other configurations, sizes, colors and length not specified herein are available upon request.

43

Automotive Cables Type GPT 50V, 75C (International System Units)


General Purpose Thermoplastic Insulated Standard: SAE J1128 NTC-1116, Primary Low Voltage Cables

SIZE AWG

STRANDS

STRAND SECTION CONDUCTOR DIAMETER DIAMETER (mm2) (mm) (mm)

INSULATION THICKNESS (mm)

DIAMETER OVER INSULATION (mm)

APPROX. TOTAL WEIGHT (kg/km)

DC RESISTANCE AT 20C 1 (ohm/km)

22 20 18 16 14 12 10 8

7 10 16 26 41 65 104 168

0.254 0.254 0.254 0.254 0.254 0.254 0.254 0.254

0.35 0.51 0.81 1.32 2.08 3.29 5.27 8.51

0.76 0.97 1.23 1.51 1.98 2.52 3.21 3.66

0.58 0.58 0.58 0.58 0.58 0.66 0.79 0.94

1.76 1.97 2.23 2.51 2.98 3.62 4.51 5.20

6 8 11 16 24 38 59 93

49.6 34.7 21.7 13.3 8.46 5.34 3.34 2.07

Notes: 1. DC Resistance calculated based on a 17.241 ohm-mm2/km copper resistivity. 2. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

Automotive Cables Type GPT 50V, 75C


General Purpose Thermoplastic Insulated Standard: SAE J1128 NTC-1116, Primary Low Voltage Cables
SIZE AWG STRANDS STRAND SECTION CONDUCTOR DIAMETER DIAMETER (kcmil) (mils) (mils) INSULATION THICKNESS (mils) DIAMETER OVER INSULATION (mils) APPROX. TOTAL WEIGHT (lb/kft) DC RESISTANCE AT 20C 1 (ohm/kft)

22 20 18 16 14 12 10 8

7 10 16 26 41 65 104 168

10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0

0.70 1.00 1.60 2.60 4.10 6.50 10.40 16.80

30 38 48 59 78 99 126 144

23 23 23 23 23 26 31 37

69 78 88 99 117 143 178 205

4 5 8 11 16 25 40 62

15.1 10.6 6.61 4.07 2.58 1.63 1.02 0.630

Notes: 1. DC Resistance calculated based on a 10.371 ohm-cmil/ft copper resistivity. 2. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

44

Automotive Cables Type TWP


Thin Wall, Thermo Plastic Insulated

Description
Soft copper flexible conductor PVC insulated.

Construction
Conductor Flexible soft copper conductor, Class K stranded Insulation Flame Retardant Polyvinyl chloride (PVC 75 C)

Characteristics
Operating Temperature 75 C. Operating Voltage 50 V.

Applications
Low voltage automotive wiring where the reduced diameter offers an optimum utilization of site in which is installed. Insulation resistant to abrasion gasoline and oil.

Specifications
CENTELSA TWP Cables are manufactured under the following standards:
UL 1581, NTC-3203 Reference Standard for Electrical Wires, Cables and Flexible Cords SAE J1128 NTC-1116 Primary Low Voltage Cables Colors Black, white, red, yellow, blue, brown, orange grey and violet.

45

Packaging 100 m spools covered with plastic thermo pack, in corrugated carton boxes. Note: Other configurations, sizes, colors and length not specified herein are available upon request.

46

Automotive Cable Type TWP 50V, 75C (Internacional System Units)


Thin Wall, ThermoPlastic Insulated Standard: SAE J1128 NTC-1116, Primary Low Voltage Cables

SIZE AWG

STRANDS

STRAND SECTION CONDUCTOR DIAMETER DIAMETER (mm2) (mm) (mm)

INSULATION THICKNESS (mm)

DIAMETER OVER INSULATION (mm)

APPROX. TOTAL WEIGHT (kg/km)

DC RESISTANCE AT 20C 1 (ohm/km)

22 20 18 16 14 12 10 8

7 10 16 26 41 65 104 168

0.254 0.254 0.254 0.254 0.254 0.254 0.254 0.254

0.35 0.51 0.81 1.32 2.08 3.29 5.27 8.51

0.76 0.97 1.23 1.51 1.98 2.52 3.21 3.66

0.40 0.40 0.40 0.40 0.40 0.45 0.50 0.55

1.44 1.65 1.91 2.19 2.66 3.32 4.07 4.58

5 7 10 15 22 35 55 86

49.6 34.7 21.7 13.3 8.46 5.34 3.34 2.07

Notes: 1. DC Resistance calculated based on a 17.241 ohm-mm2/km copper resistivity. 2. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

Automotive Cable Type TWP 50V, 75C


Thin Wall, ThermoPlastic Insulated Standard: SAE J1128 NTC-1116, Primary Low Voltage Cables
SIZE AWG STRANDS STRAND SECTION CONDUCTOR DIAMETER DIAMETER (kcmil) (mils) (mils) INSULATION THICKNESS (mils) DIAMETER OVER INSULATION (mils) APPROX. TOTAL WEIGHT (lb/kft) DC RESISTANCE AT 20C 1 (ohm/kft)

22 20 18 16 14 12 10 8

7 10 16 26 41 65 104 168

10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0

0.70 1.00 1.60 2.60 4.10 6.50 10.40 16.80

30 38 48 59 78 99 126 144

16 16 16 16 16 18 20 22

55 63 73 84 103 127 157 178

3 4 7 10 15 24 37 58

15.1 10.6 6.61 4.07 2.58 1.63 1.02 0.630

Notes: 1. DC Resistance calculated based on a 10.371 ohm-cmil/ft copper resistivity. 2. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

47

Automotive Cables Type SGT. Battery Cable


Starter or Ground, General Purpose Thermoplastic Insulated

Description
Soft copper flexible conductor PVC insulated.

Construction
Conductor Flexible soft copper conductor, Class K stranded Insulation Flame Retardant Polyvinyl chloride (PVC 75 C)

Characteristics
Operating Temperature 75 C. Operating Voltage 50 V.

Applications
SGT cables are used to connect the system of engine Start-up. Insulation is resistant to abrasion, gasoline, oil, solvents and chemical agents.

Specifications
CENTELSA SGT Cables are manufactured under the following standards:
UL 1581, NTC-3203 Reference Standard for Electrical Wires, Cables and Flexible Cords

SAE J1127 NTC-1955 Battery Cables

48

Packaging Wood reels or spools upon request. Note: Other configurations, sizes, colors and length not specified herein are available upon request.

Automotive Cables Type SGT 50V, 75C (International System Unit)


Starter or Ground, General Purpose Thermoplastic Insulated
Standard: SAE J1127 NTC-1955. Battery Cables

SIZE AWG

STRANDS

STRAND SECTION CONDUCTOR DIAMETER DIAMETER (mm2) (mm) (mm)

INSULATION THICKNESS (mm)

DIAMETER OVER INSULATION (mm)

APPROX. TOTAL WEIGHT (kg/km)

DC RESISTANCE AT 20C 1 (ohm/km)

6 4 2 1 1/0 2/0 3/0 4/0

266 420 665 836 1064 1323 1666 2107

0.254 0.254 0.254 0.254 0.254 0.254 0.254 0.254

13.48 21.28 33.70 42.36 53.91 67.04 84.42 106.76

4.12 6.72 8.58 9.77 11.10 12.47 14.10 15.97

1.52 1.65 1.65 1.65 1.65 1.65 1.98 1.98

6.58 9.40 11.26 12.45 13.78 15.15 17.30 19.17

152 243 368 454 568 697 886 1105

1.30 0.826 0.522 0.415 0.326 0.262 0.208 0.165

Notes: 1. DC Resistance calculated based on a 17.241 ohm-mm2/km copper resistivity. 2. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

Automotive Cables Type SGT 50V, 75C


Starter or Ground, General Purpose Thermoplastic Insulated
Standard: SAE J1127 NTC-1955. Battery Cables
SIZE AWG STRANDS STRAND SECTION CONDUCTOR DIAMETER DIAMETER (kcmil) (mils) (mils) INSULATION THICKNESS (mils) DIAMETER OVER INSULATION (mils) APPROX. TOTAL WEIGHT (lb/kft) DC RESISTANCE AT 20C 1 (ohm/kft)

6 4 2 1 1/0 2/0 3/0 4/0

266 420 665 836 1064 1323 1666 2107

10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0

26.60 42.00 66.50 83.60 106.40 132.30 166.60 210.70

162 265 338 385 437 491 555 629

60 65 65 65 65 65 78 78

259 370 443 490 543 596 681 755

102 163 247 305 382 469 595 742

0.398 0.252 0.159 0.127 0.0994 0.0800 0.0635 0.0502

Notes: 1. DC Resistance calculated based on a 10.371 ohm-cmil/ft copper resistivity. 2. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

49

Automotive Cables Type SXL


Special Purpose, Cross (X) Linked Polyethylene Insulated

Description
Soft copper flexible conductor XLPE insulated.

Construction
Conductor Flexible soft copper conductor, Class K stranded Insulation Flame retardant Cross Linked Polyethylene (XLPE 125C)

Characteristics
Operating Temperature 125 C. Operating Voltage 50 V.

Applications
Low voltage automotive, special for vane motor. Applications where heavy duty requires more than GPT cables. Insulation resistant to abrasion gasoline and oil.

Specifications
CENTELSA SXL Cables are manufactured under the following standards:
UL 1581, NTC-3203 Reference Standard for Electrical Wires, Cables and Flexible Cords SAE J1128 NTC-1116 Primary Low Voltage Cables Colors Black, red, orange
50

Packaging 100 m spools covered with plastic thermo pack, in corrugated carton boxes. Note: Other configurations, sizes, colors and length not specified herein are available upon request.

51

Automotive Cables Type SXL 50V, 75C (International System Unit)


Special Purpose, Cross (X) Linked Polyethylene Insulated Standard: SAE J1128 NTC-1116, Primary Low Voltage Cables

SIZE AWG

STRANDS

STRAND SECTION CONDUCTOR DIAMETER DIAMETER (mm2) (mm) (mm)

INSULATION THICKNESS (mm)

DIAMETER OVER INSULATION (mm)

APPROX. TOTAL WEIGHT (kg/km)

DC RESISTANCE AT 20C 1 (ohm/km)

20 18 16 14 12 10 8

10 16 26 41 65 104 168

0.254 0.254 0.254 0.254 0.254 0.254 0.254

0.51 0.81 1.32 2.08 3.29 5.27 8.51

0.97 1.23 1.51 1.98 2.52 3.21 3.66

0.74 0.76 0.81 0.89 0.94 1.04 1.09

2.19 2.49 2.85 3.44 4.06 4.91 5.42

9 13 18 28 41 64 95

34.7 21.7 13.3 8.46 5.34 3.34 2.07

Notes: 1. DC Resistance calculated based on a 17.241 ohm-mm2/km copper resistivity. 2. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

Automotive Cables Type SXL 50V, 75C


Special Purpose, Cross (X) Linked Polyethylene Insulated Standard: SAE J1128 NTC-1116, Primary Low Voltage Cables
SIZE AWG STRANDS STRAND SECTION CONDUCTOR DIAMETER DIAMETER (kcmil) (mils) (mils) INSULATION THICKNESS (mils) DIAMETER OVER INSULATION (mils) APPROX. TOTAL WEIGHT (lb/kft) DC RESISTANCE AT 20C 1 (ohm/kft)

20 18 16 14 12 10 8

10 16 26 41 65 104 168

10.0 10.0 10.0 10.0 10.0 10.0 10.0

1.00 1.60 2.60 4.10 6.50 10.40 16.80

38 48 59 78 99 126 144

29 30 32 35 37 41 43

84 95 110 133 157 191 211

6 8 12 19 28 43 64

10.6 6.61 4.07 2.58 1.63 1.02 0.630

Notes: 1. DC Resistance calculated based on a 10.371 ohm-cmil/ft copper resistivity. 2. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

52

Silicon Cables Type SF


Silicon Insulated Flexible

Description
Soft copper flexible conductor Silicon Rubber insulated.

Construction
Conductor Flexible soft copper conductor, Class K stranded Insulation Silicon Rubber natural color (Beige)

Characteristics
Operation Temperature 200 C. Operating Voltage 600 V.

Applications
High temperature applications like motors wiring, internal wiring of luminaries, ballast, dryers, ovens, freezers, coolers Excellent insulation performance at high temperatures

Specifications
CENTELSA SF Cables are manufactured under the following standards:
UL 1581, NTC-3203 Reference Standard for Electrical Wires, Cables and Flexible Cords UL 62, NTC-2356 Flexible Cord and Fixture Wire

53

Packaging
100 m spools covered with plastic thermo pack, in corrugated carton boxes.

Note: Other configurations, sizes, colors and length not specified herein
are available upon request.

Silicon Cable Type SF 600V, 200C (International System Unit)


Silicon Insulated Flexible
Standard: UL 62, NTC-2356. Flexible and Fixture Wire

SIZE AWG

STRANDS

STRAND SECTION CONDUCTOR DIAMETER DIAMETER (mm2) (mm) (mm)

INSULATION THICKNESS (mm)

DIAMETER OVER INSULATION (mm)

APPROX. TOTAL WEIGHT (kg/km)

DC RESISTANCE AT 20C 1 (ohm/km)

18 16 14 12 10

16 26 41 65 104

0.254 0.254 0.254 0.254 0.254

0.81 1.32 2.08 3.29 5.27

1.23 1.51 1.98 2.52 3.21

0.76 0.76 0.76 0.76 0.76

2.83 3.11 3.58 4.12 4.81

13 19 27 40 60

21.7 13.3 8.46 5.34 3.34

Notes: 1. DC Resistance calculated based on a 17.241 ohm-mm2/km copper resistivity. 2. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

Silicon Cable Type SF 600V, 200C


Silicon Insulated Flexible
Standard: UL 62, NTC-2356. Flexible and Fixture Wire

SIZE AWG

STRANDS

STRAND SECTION CONDUCTOR DIAMETER DIAMETER (kcmil) (mils) (mils)

INSULATION THICKNESS (mils)

DIAMETER OVER INSULATION (mils)

APPROX. TOTAL WEIGHT (lb/kft)

DC RESISTANCE AT 20C 1 (ohm/kft)

18 16 14 12 10

16 26 41 65 104

10.0 10.0 10.0 10.0 10.0

1.60 2.60 4.10 6.50 10.40

48 59 78 99 126

30 30 30 30 30

111 122 141 162 189

9 13 18 27 40

6.61 4.07 2.58 1.63 1.02

Notes: 1. DC Resistance calculated based on a 10.371 ohm-cmil/ft copper resistivity. 2. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

54

Welding Cable

Description
Soft copper flexible conductor with Elastomer Thermoplastic insulation

Construction
Conductor Flexible soft copper conductor, Class K stranded Insulation Flame Retardant Black Elastomer Thermoplastic i(TPR 105C)

Characteristics
Operation Temperature 105 C. Operating Voltage 600 V.

Applications
Extra hard service Cable, flexible and resistant to heavy-duty, for electric welding equipments. Insulation: Rough handling, abrasion and spark welding resistant.

Specifications
CENTELSA SF Cables are manufactured under the following standards:
UL 1581, NTC-3203 Reference Standard for Electrical Wires, Cables and Flexible Cords UL 62, NTC-2356 Flexible Cord and Fixture Wire

55

Packaging
100 m spools covered with plastic thermo pack, in corrugated carton boxes.

Note: Other configurations, sizes, colors and length not specified herein
are available upon request.

56

Welding Cable 600V, 105oC (International System Units)


Standard:

BS 638. Arc welding power coerces equipment and accessories. CENTELSA Specifications for HTS-C Cables
STRANDS STRAND SECTION CONDUCTOR DIAMETER DIAMETER (mm2) (mm) (mm) INSULATION THICKNESS (mm) DIAMETER OVER INSULATION (mm) APPROX. TOTAL WEIGHT (kg/km) DC RESISTANCE AT 20C 1 (ohm/km) AMPACITY 2 (A)

SIZE AWG

6 4 2 1 1/0 2/0 3/0 4/0 250 300 350

266 420 665 836 1064 1323 1666 2107 2499 2989 3458

0.254 0.254 0.254 0.254 0.254 0.254 0.254 0.254 0.254 0.254 0.254

13.48 21.28 33.70 42.36 53.91 67.04 84.42 106.76 126.63 151.45 175.22

4.12 6.72 8.58 9.77 11.10 12.47 14.10 15.97 17.40 19.02 20.61

2.00 2.00 2.00 2.20 2.40 2.40 2.60 2.80 2.80 3.00 3.20

8.28 10.88 12.74 14.31 16.04 17.41 19.46 21.73 23.16 25.20 27.21

168 258 389 487 616 756 947 1189 1390 1658 1933

1.30 0.826 0.522 0.415 0.326 0.262 0.208 0.165 0.139 0.116 0.100

125 170 232 270 318 369 431 505 566 639 705

Notes: 1. DC Resistance calculated based on a 17.241 ohm-mm2/km copper resistivity. 2. Ampacity based on 5 minutes working cycles and 80% Load Factor. 3. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

WELDING Cable 600V, 105oC


Standard:

BS 638. Arc welding power coerces equipment and accessories. CENTELSA Specifications for HTS-C Cables
STRANDS STRAND SECTION CONDUCTOR DIAMETER DIAMETER (kcmil) (mils) (mils) INSULATION THICKNESS (mils) DIAMETER OVER INSULATION (mils) APPROX. TOTAL WEIGHT (lb/kft) DC RESISTANCE AT 20C 1 (ohm/kft) AMPACITY 2 (A)

SIZE AWG

6 4 2 1 1/0 2/0 3/0 4/0 250 300 350

266 420 665 836 1064 1323 1666 2107 2499 2989 3458

10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0

26.60 42.00 66.50 83.60 106.40 132.30 166.60 210.70 249.90 298.90 345.81

162 265 338 385 437 491 555 629 685 749 811

79 79 79 87 94 94 102 110 110 118 126

326 428 502 563 631 685 766 856 912 992 1071

113 174 261 327 414 508 636 799 934 1114 1299

0.398 0.252 0.159 0.127 0.0994 0.0800 0.0635 0.0502 0.0423 0.0354 0.0306

125 170 232 270 318 369 431 505 566 639 705

Notes: 1. DC Resistance calculated based on a 10.371 ohm-cmil/ft copper resistivity. 2. Ampacity based on 5 minutes working cycles and 80% Load Factor. 3. Values herein indicated are approximated and are subject to normal manufacturing tolerances.