Industry and Infrastructure Jetfoil - Tunnel Fans

Flkt Woods Jetfoil Fans


Flkt Woods is the industry leader in air movement technology, providing innovative solutions worldwide. Our extensive knowledge of design and applications is based on over 100 years of experience in tunnels, buildings, industry and original equipment manufacturers. Flkt Woods global coverage reaches over 100 countries and is supported by an extensive distribution network. Our expertise in tunnel ventilation applications covers road & rail tunnels, metros, tunnel construction and wind tunnels. Flkt Woods products have been successfully used in underground projects throughout the world and our Jet Fan product range is unrivalled in its technology, innovation and efficiency

The Jetfoil Fan Range


General Information
560 - 1600 mm Thrust up to 3500N 800 mm up to 3000 rpm, 1250 mm up to 1800 rpm and 1600 mm up to 1200 rpm Fully adjustable die cast aluminium impellers in uni-directional and truly reversible configurations; and 100% X-ray of all cast impeller component Mild steel casing - hot dipped galvanised after manufacture, painted or all stainless steel construction Silencers fitted where required Motor protection IP55 minimum High thrust performance Emergency ventilation options up to 400C/2 hours Truly reversible fans provide approximatey equal thrust and airflow in forward and reverse directions

Noise Levels
Flakt Woods offer acoustic analysis and attenuators to ensure the fans are In accordance with environmental requirements and local regulations.

Applications
Longitudinal ventilation of road tunnels Emergency ventilation - smoke control Mine ventilation Hangar/large area ventilation

Ventilation
Ventilation is required for safety and to maintain acceptable temperatures and comfort. Pollution emitted by road vehicles must be removed to provide an acceptable and safe environment. In the case of a fire, smoke must be removed in order to enable safe escape and to assist access to fight the fire. The normal ventilation principles are to dilute pollution and to increase visibility by removal of particles. In an emergency the smoke is controlled by creating sufficient air velocity to drive it away from the fire. Depending on the control strategy, the smoke can then be extracted.

Unrivalled R&D Facilities


Our dedicated laboratory in Colchester, unique in the UK, is equipped to demonstrate and prove product performance and control strategies. We have further R&D facilities in Sweden, Finland, France and the USA. The fan performance,is maintained and improved in line with a planned Research and Development programme to ensure optimised aerodynamic and acoustic performance. Jet Fans Thrust ISO13350; Acoustic Performance BS 848 in a semi reverberant area ISO5136; Over speed 125% for 15 minutes;X-Ray examination ASTME 15; Balance ISO 1940; Vibration BS848 pt7 ISO 14694.

Fan Selector
Fan Selector is the selection software for all the Flkt Woods Fan Group products: Axial Flow Fans (among which Jet Fans for Tunnels), Centrifugal fans, Boxed Fans, Roof Extract units, Plate mounted fans. The Fan Selector allows you to choose fans which fit your required application.

How to Register, easy as 1, 2, 3!


All you need to do to register your details on-line is to follow the simple instructions shown below. 1. Click on the site link to start the process: http://fanselector.flaktwoods.com/signup/ 2. All you need to do is to fill in the fields that have red text labels, but if you wish to complete more of the form, this would be helpful.

Fan Codes

3. Once you have entered your details, just click the Register button at the bottom of the registration page to submit your request.

User Account Set-up


Once a user account has been created, our automatic registration system will send you an e-mail confirming your user name and password. Note: your username will be your e-mail address, so if you have a personal address this would be better than a general one (as this will allow you to personalise our software). The account set-up process normally completed between 24-48 hours after your initial password confirmation.

Desktop CD
Should you prefer to use the Desktop version of the software (which is locally installed onto your computers hard drive), then this is available on request. All you need to do is to advise your full postal address and we would be happy to mail a CD to you.

Link to the On-Line Fan Selector: http://fanselector.flaktwoods. com 1. After logging in, the first screen displayed allows the selection of axial fans, identify and click select to continue. 2. The next screen displays the various types of axial fans, therefore it is necessary to filter the selection by clicking product filter and edit. 3. The desired thrust can be input to identify suitable fans. Other filters can be adjusted so the desired fan is identified. 4. Each fan can be highlighted and technical information made available

400/2 Unidirectional 60Hz


3000 2500 2500

400/2 Reversible 60Hz

2000

Thrust (N)

2000 1500 1000

Thrust (N)
71 4 80 4 90 4 100 6 112 6 125 6 140 6 160 8 160 6

1500

1000

Jetfoil Standard Range


Range includes:
10 diameters - 560 mm to 1600 mm Swept back arm design for improved performance and noise reduction Zinc galvanised or stainless steel casing IP55 motor protection minimum Low installed noise levels High energy efficiency ISO standard 13350

Performance Range with 1D Silencers


500 500

Options:
Option of a silencer with or without acoustic pod Mounting frame to ensure secure installation Epoxy paint

300/2 - Range

0
71 4 80 4 100 6 112 6 125 6 140 8 160 8

300/2 Unidirectional 50Hz


4000 3000 2500 3000

300/2 Reversible 50Hz

Thrust (N)

Thrust (N)

2000 1500 1000

2000

1000 500 0
63 2 71 4 71 2 80 4 90 4 100 6 100 4 112 6 112 4 125 6 125 4 140 6 140 4 160 8 160 6

0
56 2 63 2 71 4 71 2 80 4 80 2 90 4 100 6 100 4 112 6 112 4 125 6 125 4 140 8 140 6 160 8 160 6

300/2 Unidirectional 60Hz


4000 3500 3000 4000 3500 3000

300/2 Reversible 60Hz

Thrust (N)

2500 2000 1500 1000 500 0


71 4 80 4 90 4 100 6 100 4 112 6 112 4 125 6 140 6 160 8 160 6

Thrust (N)

2500 2000 1500 1000 500 0


71 4 80 4 90 4 100 6 112 6 125 6 140 8 140 6 160 8 160 6

High Temperature Range


Range includes:
10 diameters - 560 to 1600 mm 200/2, 300/2 or 400/2 operation 50 Hz or 60 Hz supply HT Approved and certified fans motors Additional impeller locking feature

Options:
Epoxy paint on top of galvanised finish Bolt-on Silencers Accessories

400/2 - Range
400/2 Unidirectional 50Hz
3000 3000

400/2 Reversible 50Hz

2500

2500

Thrust (N)

Thrust (N)

2000

2000

1500

1500

1000

1000

500

500

0 0
71 4 80 4 90 4 100 6 100 4 112 6 112 4 125 6 125 4 140 6 160 8 160 6 56 2 63 2 71 4 71 2 80 4 90 4 100 6 100 4 112 6 112 4 125 6 125 4 140 8 140 6 160 8 160 6

400/2 Unidirectional 60Hz


3000 2500

400/2 Reversible 60Hz

Fan label in accordance with CE marking directive EN12101-3


Thrust (N)

2500 2000 1500 1000 500

2000

Thrust (N)
71 4 80 4 90 4 100 6 112 6 125 6 140 6 160 8 160 6

1500

1000

500

0
71 4 80 4 100 6 112 6 125 6 140 8 160 8

Higher thrust levels available, please enquire for further information


300/2 Unidirectional 50Hz 300/2 Reversible 50Hz
3000 2500 3000

200 for 200C for 2 hours 300 for 300C for 1 hour 400 for 400C for 2 hours
rust (N)

4000

rust (N)

2000 1500

2000

50Hz Unidirectional Range 300/2H


Sound Pressure Weight in free field, (Kg) 45, 10m dB(A) 73 75 66 67 68 69 70 70 72 56 58 60 62 66 68 70 71 61 64 65 67 68 69 68 69 70 72 64 67 69 70 67 68 70 194 194 310 310 310 326 326 326 379 216 282 282 282 282 493 493 540 581 581 727 727 727 845 827 827 968 1074 976 1107 1224 1224 1202 1345 1453

50Hz Truly Reversible Range 300/2H


Sound Pressure in forward Weight direction (Kg) in free field, 45, 10m dB(A) 63 64 66 70 62 64 65 67 68 69 69 69 70 72 73 59 61 63 64 59 61 62 69 70 73 75 66 67 69 71 72 70 71 73 73 74 76 68 69 71 72 69 70 70 74 150 180 180 180 168 197 197 197 314 314 183 244 331 331 385 220 286 286 286 441 441 441 500 500 546 546 589 648 856 856 856 685 841 982 982 1095 1095 991 112 1245 1245 1217 1360 1474 1600

Fan type

Motor Pole Speed

Blade angle

Thrust N

Outlet Absorbed Motor Velocity Power Power m/s kW kW

Nominal Current A

Sound power LwA

Fan type

Motor Pole Speed

Blade angle

Thrust N

Outlet Absorbed Motor Velocity Power Power m/s kW kW

Nominal Current A

Sound power LwA

2 2 63JMG 2 2 2 2 71JMG 2 2 2 4 80JMG 4 4 4 4 100JMG 4 4 4 4 4 112JMG 4 4 4 4 4 125JMG 4 4 4 6 140JMG 6 6 6 6 160JMG 6 6

20 24 29 32 36 22 25 28 34 27 32 36 40 26 31 38 40 21 27 31 34 37 40 20 24 28 33 26 33 37 40 20 25 31

324 419 529 592 672 575 672 772 943 289 355 408 457 661 819 1038 1088 878 1176 1378 1532 1687 1826 1289 1665 2021 2438 1141 1500 1710 1868 1253 1606 2087

29.4 33.5 37.6 39.8 42.4 34.8 37.6 40.3 44.6 21.9 24.3 26 27.5 26.5 29.5 33.2 34 27.2 31.5 34.1 36 37.8 39.3 29.6 33.6 37 40.7 24.9 28.5 30.4 31.8 22.8 25.8 29.4

9.2 12.6 17.6 21.1 26.1 17.8 21.6 26.5 38.9 4.62 6.4 8.2 9.8 12.7 17.7 26.4 28.7 16.7 26.8 34.8 41.6 49 56.9 33.9 46.7 61.2 82.4 21.8 34.5 42.8 49.8 24.7 34.6 51.6

11.04 12.65 18 22.2 27 18 22.2 27 40 4.8 6.6 8.63 11.04 13.2 18 27 33 17.3 27 36 42.55 49.5 63.3 34.5 49.5 63.3 86.3 22.2 36 44.4 51.8 26.4 36 51.8

20.2 23.3 32.6 40.4 49.8 32.6 40.4 49.8 74.6 9.2 12.6 16.3 21 25.4 35 49.8 65 33.1 49.8 67 77.7 94.8 110 63.8 94.8 110 154 42.7 66.2 79.9 92.3 49.7 66.2 92.3

104 106 97 98 99 100 101 101 103 87 89 91 93 97 99 101 102 92 95 96 98 99 100 99 100 101 103 95 98 100 101 98 99 101

2 56JMTS 2 2 2 2 2 63JMTS 2 2 2 2 2 2 71JMTS 2 2 2 4 80JMTS 4 4 4 4 90JMTS 4 4 4 100JMTS 4 4 4 4 4 112JMTS 4 4 4 4 4 125JMTS 4 4 4 4 6 140JMTS 6 6 6 6 160JMTS 6 6 6

22 30 35 40 20 24 28 32 37 40 20 24 28 33 35 30 35 40 44 35 40 43 29 34 39 44 30 33 37 41 44 25 28 31 33 36 40 32 36 40 43 23 27 30 40

133 211 260 304 177 229 290 354 425 466 320 415 516 660 698 259 324 374 395 534 617 648 566 704 896 1011 1023 1180 1356 1495 1551 1074 1300 1546 1715 1960 2251 1186 1393 1555 1631 1234 1571 1856 2555

21.2 26.7 29.7 32.1 21.8 24.8 27.8 30.8 33.7 35.3 25.9 29.5 32.9 37.3 38.3 20.7 23.2 24.9 25.6 26.4 28.4 29.1 24.5 27.3 30.8 32.8 29.4 31.6 33.9 35.6 36.2 27 29.7 32.4 34.1 36.5 39.1 25.3 27.5 29 29.7 22.6 25.5 27.7 32.5

3.3 6.4 8.8 12.2 4.4 6.5 8.8 11.9 17.2 20.7 8.1 12.1 17.4 26.3 30.9 4.6 6.6 8.9 10.8 12.4 17 19.6 12.1 17.1 26.1 31.1 25.4 32 42.6 53.7 61.2 26.4 33.9 43.9 52.1 65.7 83.6 25.7 34.4 44.1 50.9 25.3 34.7 43.3 84.5

3.6 6.6 9 12.65 4.6 6.6 9 12.65 18 22.2 8.25 12.65 18 27 33 4.8 6.6 9 11.04 13.2 17.3 20.35 13.2 17.3 27 33 27 33 44.4 54 63.3 27 34.5 44.4 54 66 86.3 26.4 36 44.4 51.8 26.4 36 44.4 86.3

6.93 12.3 16.4 23.3 9.3 12.3 16.4 23.3 32.6 40.4 15.5 23.3 32.6 49.8 58.8 9.2 12.6 17 21 25.4 33.1 39.5 25.4 33.1 49.8 65 49.8 65 79.3 95.1 110 49.8 63.8 79.3 95.1 115 154 49.7 66.2 79.9 92.3 49.7 66.2 79.9 155

94 95 97 101 93 95 96 98 99 100 100 100 101 103 104 90 92 94 95 90 92 93 100 101 104 106 97 98 100 102 103 101 102 104 104 105 107 99 100 102 103 100 101 101 105

60Hz Unidirectional Range 250/2H


Sound Pressure Weight in free field, (Kg) 45 , 10m dB(A) 67 68 70 74 60 62 64 66 58 60 62 70 71 73 75 65 67 70 71 73 64 67 69 66 69 70 71 72 73 171 180 241 241 216 282 282 370 330 436 525 493 540 540 614 639 727 845 1070 1070 737 827 968 976 1107 1224 1224 1453 1453

60Hz Truly Reversible Range 250/2H


Sound Pressure in forward Weight direction (Kg) in free field, 45, 10m dB(A) 59 174 60 183 62 244 62 220 63 286 66 286 68 380 60 337 61 441 63 441 65 530 67 530 76 739 77 856 78 856 79 856 81 1080 66 748 67 841 69 841 71 982 72 1095 70 991 71 1122 73 1245 73 1360 74 1474 74 1474

Fan type

Motor Pole Speed

Blade angle

Thrust N

Outlet Absorbed Motor Velocity Power Power m/s kW kW

Nominal Current A

Sound power LwA

Fan type

Motor Pole Speed

Blade angle

Thrust N

Outlet Absorbed Motor Velocity Power Power m/s kW kW

Nominal Current A

Sound power LwA

4 71JMG 4 4 4 4 80JMG 4 4 4 4 90JMG 4 4 4 100JMG 4 4 4 4 4 112JMG 4 4 4 6 125JMG 6 6 6 140JMG 6 6 6 160JMG 6 6

23 30 35 40 25 30 35 40 25 29 34 20 25 31 37 20 25 31 34 39 26 32 39 20 27 29 32 21 24

222 307 368 427 378 472 568 640 526 644 806 744 1012 1312 1586 1237 1606 2039 2207 2580 974 1256 1565 1266 1796 1950 2184 1967 2284

21.6 25.4 27.8 30 25 28 30.7 32.6 26.3 29 32.5 28.1 32.8 37.3 41 32.3 36.9 41.5 43.2 46.7 25.7 29.2 32.6 26.2 31.2 32.5 34.4 28.6 30.8

4.1 6.6 9 11.5 6.8 9.6 13.1 16.7 13.3 18.1 25.9 18 26.7 39.1 53.9 27.4 41.7 62.6 74.8 97.5 19.4 28.9 42.2 24.3 42.7 48.8 58.9 47.5 58

4.32 6.93 9.78 12.1 6.93 9.78 13.8 19.6 13.8 19.6 28.8 19.6 28.8 39.6 58.3 28.8 43.2 63.6 75.6 97.8 20.4 30 43.2 25.2 43.2 50.4 61 50.4 61

7.61 12.9 16.3 20.2 12.9 16.3 22.3 32.8 22.3 32.8 46.9 32.8 46.9 66.3 96.7 46.9 68.8 97 115 150 32 50 68.1 41.6 68.1 79.3 94.9 79.3 94.9

98 99 101 105 91 93 95 97 89 91 93 101 102 104 106 96 98 101 102 104 95 98 100 97 100 101 102 103 104

71JMTS

80JMTS

90JMTS

112 JMTS

125JMTS

140JMTS

160JMTS

4 4 4 4 4 4 4 4 4 4 4 4 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6

30 33 36 25 32 37 44 27 30 33 39 44 28 31 35 37 40 28 31 34 40 44 26 30 35 22 24 26

207 239 271 285 419 508 564 489 578 667 818 885 1241 1438 1693 1813 1980 936 1083 1227 1466 1544 1293 1627 2034 1736 1957 2209

20.9 22.4 23.9 21.7 26.4 29 30.6 25.3 27.5 29.6 32.7 34.1 32.4 34.9 37.8 39.2 40.9 25.2 27.1 28.9 31.6 32.4 26.5 29.7 33.2 26.8 28.5 30.3

4.3 5.5 6.9 5.6 9.4 13.1 19 11.8 14.9 18.9 28.4 36 40.2 49.4 63.2 71.7 87.8 19.4 24.2 29.6 41.8 50 29.2 40.2 58.8 41.5 49.4 57.8

4.32 5.76 7.56 5.76 9.78 13.8 19.6 12.1 15 19.6 28.8 39.6 41.4 50.4 63.6 72.5 97.8 20.4 25.2 30 43.2 50.4 30 43.2 61 43.2 50.4 61

7.61 9.75 12.7 9.75 16.3 22.3 32.8 20.2 25.6 32.8 46.9 66.3 65.6 77.9 97 110 150 32 41.6 50 68.1 79.3 50 68.1 94.9 68.1 79.3 94.9

90 91 93 93 94 97 99 91 92 94 96 98 107 108 109 110 112 97 98 100 102 103 101 102 104 104 105 105

10

HT Certification
Emergency, High Temperature, Smoke Extract Fans fall within the scope of the EU Construction Products Directive. The implementation of the Construction Products Directive and the publication of the product specific standard, EN 12101-3 have made it a mandatory requirement for smoke control fans sold into the European Union to carry a CE Mark from April 1st, 2005. The CE mark may only be affixed after successful completion of testing, auditing of factory production control and the issue of a certificate by accredited independent authorities. This procedure is intended to prevent fan failures during an emergency smoke situation, where a fan failure can ultimately lead to the loss of life. Flkt Woods fully endorse the concept that, in such a safety critical application, only fully verified and certified products should be specified. This made the decision to test and certify this core product range all the more easier. The decision was made to embark on a major testing programme in conjunction with BSRIA, a leading authority in building research. Using the expertise of Flkt Woods and BSRIAs new state of the art High Temperature test rig, the Jet Fan range was successfully tested in compliance with this demanding new legislation with minimum complications. This investment resulted in Flkt Woods being able to offer a British Standards Institution Certified, CE marked Jet Fan product for use at 400C/2 hours from 560mm to 1600mm, together with a comprehensive range of approved accessories. Flkt Woods have enhanced their position as the foremost provider of specialist products for emergency high temperature smoke control by becoming the first fan manufacturer in the world to be able to apply CE marking to these safety critical products. CE marking was then obtained from BSI for the JM HT fan range for additional 200C and 300C temperature categories, ensuring that Flkt Woods has one of the most comprehensive range of products available in the Single European Market.

Other Accessories

Jet Fan Silencer

Acoustic pod

Mounting feet

Guards

Bellmouth Inlet

Spring Vibration Isolators

Outline Drawings
It is recommended that a Flkt Woods frame accompany the jet fan to ensure a secure installation. Anti-vibration mounts are available for soft mounting installations.

Base Fan No Silencers

200 for 200C for 2 hours 300 for 300C for 1 hour
11

400 for 400C for 2 hours

12

Outline Drawings

Flkt Woods Extensive Project Tunnel & Metro Reference List


Road Road Rail/Metro Flkt Woods Extensive Project Tunnel & Metro Reference List Country Project Country Project Country Project Algeria Australia Australia Australia Australia Austria Belgium Belgium Brazil Canada China China China China China Croatia Croatia Croatia Croatia Croatia Croatia Croatia Croatia Croatia Croatia Croatia Croatia Croatia Dubai Finland Finland Finland Finland Finland France France France France Greece Greece Hong Kong Hong Kong Hong Kong Hong kong India India Italy Italy Italy Italy Italy Italy Italy Italy Italy Italy Italy Italy Italy Italy Luxembourg Malaysia Monaco Monaco New Zealand Norway Norway Norway Norway Norway Norway Poland Portugal Portugal Algerian Road Tunnel Mitcham Frankston Freeway M5 East Tunnel Lane Cove Brisbane eastern busway Wske Tunnel Gare De Namur Leopold II Lamsa tunnel Toronto Airport Hu Rong Su Tunnel Chong Qin Fang Dou Shan Sky Pier (Tunnel 1) Hu Nan Jia Hou Yan Hu Nan Xue Feng Shan Tunnel Tunnel Trsat Tunnel Skurinje Sveti Rok 2 Mala Kapela Veliki Glozac Tunnel Bisko Tunnel Mravince Tunnel Strazina Cardak Brezovica Sveta Tri Krajla Mala Kapela Tunnel pecine Dubai International Airport Kehu Project Hakamaentie/Kivihaka Tunnel Vuoli Tunnel Keha 1 Kehu 2 Tunnel du Vieux Port A14 A86 A51 Egnatia Odos-Panagia-Grevena Eftaxias Route 8 Sky Plaza Lantau Airport & Railway Contract 708 DAMEL C Doctor Seiano Tunnel Montenegrone Project Martignano Gran Sasso Mongrando Tunnel Gra Salva Candida Cesena Tunnel Valsassina Tunnel Spezia Lonato Tunnel Ronco Tunnel Val Badia Tunnel Marinasco Tunnel Autostrada del Fiori Tunnel Howald SMART T33 Tunnel TFT Tunnel JHT New Zealand E18 - Bjorvika Tunneln Norway Road Tunnel Mesta As Krakeroytunnelen Sporsmal om mal Tussentunneln Rondo Tunnel Tunnel Do Rossio Moscavide aeroporto Puerto Rico Qatar Qatar Saudi Arabia Saudi Arabia Saudi Arabia Saudi Arabia Serbia Singapore Sweden Switzerland Syria Taiwan UK UK UK UK UK UK UK UK USA USA USA USA USA Yemen Tven Urbana New Doha International Airport NDIA Free Trade Zone Jamarat Bridge Phase II Jamarat Bridge Basement King Khalid Road Tunnel King Abdullah Tunnel Vrmac Tunnel Singapore Metro Link Arlandabanan, Stockholm Biasca Tunnel Kafar Sousah Road Tunnel Pinglin A3 Hindhead Tunnel Bell Common Tunnel Holmesdale Tunnel Limehouse Link Terminal 5 - Coach Station T5 - Taxi Bridge Blackwall Tunnel New Tyne Crossing Bunyard Tunnel Detroit Airport Minneapolis Airport Tulip City Airport Whittier Tunnel Sayhut-Nishtun Road Project Italy Italy Italy Italy Italy Italy New Zealand New Zealand Portugal Portugal Puerto Rico Romania Singapore Singapore Singapore Singapore Singapore Singapore Taiwan Taiwan Turkey Turkey UK UK UK UK UK UK UK UK USA USA USA USA USA USA USA USA USA USA USA USA USA USA USA USA USA USA USA USA USA USA USA USA USA USA USA USA USA USA USA USA USA USA USA USA USA USA USA USA USA USA USA Venezuela Milan Metro Metro Station Napoli Milan Metro Line 3 extension Monterrobbio Milan metro 2 Nci Roma Turin Metro Britomart Project Otira Rail Tunnel Lisbon Metro Porto Metro Tren Urbano Bucharest Metro CCL2 CCL3 CCL4 CCL5 KPE Expressway North East Line Nankang Extension Project KMRT Adana Light Rail Antalya Light Rail Bank Station DLR Channel Tunnel Rail Link Cooling the Tube Docklands Light Railway Jubilee Line Extension Liverpool Street Station Heathrow T5 Track Transit Woolwich Arsenal Extension Las Vegas Airport MBTA Greenline (Boston) NYCTA E-31261 NYCTA E-31080 NYCTA E-31255 NYCTA E_31269 NYCTA E-31264 Amtrak Penn Station NYCTA C-20201 NYCTA C-20203 NYCTA E-31265 NYCTA E-31243 Trimet (Portland, OR) MARTA (Atlanta) NJNY PATH BART (San Francisco) MBTA R-10 (Boston) MSP Light Rail NYCTA C-52003 NYCTA E-31271 SDSU LRT Amtrak Weehauken NYCTA E-31277 SEA-TAC NYCTA 03A8607 Cincinnati Airport Denver Airport NYCTA E-31287 NJT NERL Amtrak 1st Ave Beacon Hill (Seattle) NYCTA E-31274 NYCTA E-31278 Maverick (Boston) NYCTA A-36006 NYCTA E-31290R Pittsburgh North Connector Transportation Hub NJT Bergen SDSU LRT Beacon Hill (Seattle) Pittsburgh North Connector LA Mid-Connector Valencia Metro

Jet Fan with 1D Silencers

Jet Fan with 2D Silencers

OPTIONAL ANCI LLARY

Max 3.3 D

D 1.2 D

D 1.2 D

Rail/Metro Country Australia Austria Austria Austria Austria Austria Austria Austria Austria Austria Austria Brazil Canada Canada Canada Canada China Denmark Dubai Greece Greece Greece Hong Kong Hong Kong Hong Kong Hong Kong Hong kong Hungary Hungary India India India India India Iran Italy Italy Italy Italy Italy Italy Italy Italy Italy

Max 5.2D

Project Parramatta Rail Link U3 Station Erdberg U2/1 Schottenring River City U1 Unterwerk U2 Messe U4 Schottenring Vienna Metro - Gross Vienna Metro - Leoup Obb wien mitte U4 schotatenring Sao Paulo Metro Line 4 TTC Shepherd TTC Petrofit TTC York Mills Montreal STCUM Guangzhou Metro Copenhagen Metro Dubai Light Railway Attiko Metro - Elliniko Ext. Egnatio Odos Driscos Tunnel Attiko Metro, Athens TKO South Hong Kong Beacon Hill Tunnel Lok Ma Chau Pennys Bay Line Mtr/tsy station Budapest Metro Line 2 Budapest Metro Line 4 Delhi Metro Phase II Delhi Metro DMRC Phase 1 (Mc1b) Damel Dwarka Sector 21 East Mashhad Metro Passante Ferroviario Di Torino Torino Di Bologna Nodo Di Bologna Passante Ferroviario Turin Metro Turin Metro Lot 6c Project Rome Rail Station Avigliana Alifana Metro

13

OPTIO NAL ANCI LLARY

14

Flkt Woods is a global leader in air management. We specialise in the design and manufacture of a wide range of air climate and air movement solutions. And our collective experience is unrivalled. Our constant aim is to provide systems that precisely deliver required function and performance, as well as maximise energy efficiency.

Solutions for all your air climate and air movement needs
Flkt Woods is providing solutions for ventilation and air climate for buildings as well as fan solutions for Industry and Infrastructure. Air Handling Units (AHUs) Modular, compact and small AHU units. Designed to ensure optimisation of indoor air quality, operational performance and service life. Air Terminal Devices and Ducts Supply and exhaust diffusers and valves for installation on walls, ceiling or floor are all included in our large range and fit all types of applications. Chilled Beams Active induction beams for ventilation, cooling and heating, and passive convection beams for cooling. For suspended or flush-mounted ceiling installation and multi-service configuration. With unique Comfort Control and Flow Pattern Control features. Residential ventilation A complete range of products for residential ventilation. Consists of ventilation units, exhaust air fans and cooker hoods designed to optimise indoor comfort and save energy. Energy recovery Dessicant-based product and systems that recover energy, increase ventilation and control humidity. Fans Advanced axial, centrifugal and boxed fans for general and specialist applications. Comprehensive range including high temperature and ATEX compliant options. Engineered for energy efficiency and minimised life cycle cost. Chillers Air-cooled and water-cooled chillers with cooling capacity up to 1800kW. Designed to minimise annual energy consumption in all types of buildings. Controls and drives Variable speed drives and control systems, all tested to ensure total compatibility with our products. Specialist team can advise on energy saving and overall system integration. Acoustical Products A complete line of sound attenuating products, including rectangular and round silencers, Media Free silencers, custom silencers and acoustic enclosure panels.

Flkt Woods operates a policy of continuous development and improvement. Accordingly, the Company reserves the right to supply products that may differ from those illustrated and described in this publication. Certified dimensions will be supplied on request on receipt of order.

Flkt Woods Limited


Axial Way, Colchester, Essex, C04 5ZD Tel 01206 222 555 Fax 01206 222 777 email info.tunnels@flaktwoods.com www.flaktwoods.co.uk See global website for international sales offices www.flaktwoods.com

FWGJRG/JFB-06/0912