Split
Sky Air

air conditioning systems

technical data

Split - Sky Air

ISO14001 assures an effective environmental


management system in order to help protect
human health and the environment from the potential
impact of our activities, products and services and to
assist in maintaining and improving the quality of
the environment

Daikin Europe N.V. is approved by LRQA for its Quality


Management System in accordance with the ISO9001
standard. ISO9001 pertains to quality assurance regarding
design, development, manufacturing as well as to services
related to the product.

Daikin units comply with the European


regulations that guarantee the safety of
the product.

Daikin Europe N.V. is participating


in the EUROVENT Certification Programme.
Products are as listed in the EUROVENT
Directory of Certified Products.

Zandvoordestraat 300
B - 8400 Ostend Belgium
Internet: http://www.daikineurope.com

EEDE02-1/1 05/2002
Prepared in Belgium by Goekint Graphics

Specifications are subject to change without prior notice

Pair Application R-22 RE18-40GA/R25-45DC/R60FA/R71-250F

TABLE OF CONTENTS
R(E)
1

Features

Specifications

.................................................................................

.......................................................................

2
3

Technical specifications
Electrical specifications

Capacity tables

Dimensional drawings

...................................................................

13

.....................................................

28

Operation range

.................................................................

31

Piping diagrams

..................................................................

34

Wiring diagrams

.................................................................

38

Sound level

..........................................................................

45

Sound level data


Sound pressure spectrum

Accessories

..........................................................................

49

Optional accessories

10

Centre of gravity

11

Installation

12

Safety device settings

Split - Sky Air Outdoor Units

................................................................

50

............................................................................

51

......................................................

56

Pair Application R-22 RE18-40GA/R25-45DC/R60FA/R71-250F

16
1

Features

Outdoor units for pair application


Daikin outdoor units are neat and sturdy and can be mounted
easily on a roof or terrace or simply placed against an outside
wall. They are fitted with either rotary or scroll compressor,
renowned for low noise and high energy efficiency.

Split - Sky Air Outdoor Units

A special acryl precoated fin for anti-corrosion treatment on the


heat exchanger ensures greater resistance against severe weather
conditions.

Pair Application R-22 RE18-40GA/R25-45DC/R60FA/R71-250F

Specifications

16
2

TECHNICAL SPECIFICATIONS
OUTDOOR UNITS
DIMENSIONS

Unit

WEIGHT
MATERIAL
COLOUR
SOUND LEVEL

Unit
Unit
Sound pressure (1)

FAN

HEAT EXCHANGER

REFRIGERANT CIRCUIT

COMPRESSOR

PIPING CONNECTIONS

INSULATION MATERIAL

Sound power (2)


Air flow rate
Speed

H
W
D

high
low
high
steps
high
low

Type
Qty x model
Qty x motor output
Type
Rows x stages x fin pitch
Face area
Refrigerant type
Refrigerant charge
Additional refrigerant
Maximum interunit piping length
Maximum interunit level difference
No. of circuits
Type
Qty x model
Number of cylinders
Speed
Oil type
Oil charge volume
Crankcase heater
liquid
gas
drain
Heat insulation tape

mm
mm
mm
kg

dBA
dBA
dBA
m3/min
rpm
rpm

kg
g/m
m
m

RE40GA7V1
540
750
270
43

45
56
24

50
63
30

685
1 x F62P15U22
1 x 15

W
mm
m2

RE18GA7V1
540
750
270
28

1 x 20 x 2.0
0.381
R-22
0.65
20g/m for piping length > 8m
15
15
Max. 1

rpm

1 x RC17V1N-R
2,850

!
W
mm
mm
mm

0.4
6.4
9.5
18 x 4

1 step

Painted metal
Ivory white

R25DC7V11
540
750
270
31

R35DC7V11
540
750
270
39

43
56
25

48
61
27

865
710
325
1 x F62P45J22
1 x F62P15S22
1 x 45
1 x 15
WL fin, Hi-XA U-cooling tube
2 x 20 x 2.0
1 x 20 x 2.0
0.372
0.381
R-22
R-22
1.2
0.85
20g/m for piping length > 8m
15m > 20g/m > 25m
15
25
15
15
Max. 1
Max. 1
Hermetically sealed rotary compressor
1 x RC60V1TNRT
1 x RC30BV1R2T
2,850
2,850
SUNISO 4GSDI
0.85
0.4
6.4
6.4
12.7
9.5
18 x 4
18
Both liquid and gas pipes

2 steps

815
490
1 x UE6S-31SA4P
1 x 30
2 x 20 x 2.0
0.372
R-22
1.4
15m > 20g/m > 25m
25
15
Max. 1
1 x PS40ATRV1
2,850
0.4
6.4
12.7
18 x 3
3TW01011-1B
3TW01101-1C
3TW00021-1F
3TW00031-1G

Split - Sky Air Outdoor Units

Pair Application R-22 RE18-40GA/R25-45DC/R60FA/R71-250F

Specifications

16
2

TECHNICAL SPECIFICATIONS
OUTDOOR UNITS
DIMENSIONS

Unit

WEIGHT
MATERIAL
COLOUR
SOUND LEVEL

Unit
Unit
Sound pressure (1)

FAN

HEAT EXCHANGER

REFRIGERANT CIRCUIT

COMPRESSOR

PIPING CONNECTIONS

INSULATION MATERIAL

Sound power (2)


Air flow rate
Speed

H
W
D

mm
mm
mm
kg

high
low

dBA
dBA
dBA
m3/min

high
steps
high
low

Type
Qty x model
Qty x motor output
Type
Rows x stages x fin pitch
Face area
Refrigerant type
Refrigerant charge
Additional refrigerant
Maximum interunit piping length
Maximum interunit level difference
No. of circuits
Type
Qty x model
Number of cylinders
Speed
Oil type
Oil charge volume
Crankcase heater
liquid
gas
drain
Heat insulation tape

rpm
rpm

W
mm
m2
kg
m
m
m

rpm
!
W
mm
mm
mm

R45DC7V11/W11
R60FA7V1/W1
540
660
750
880
270
350
45
64
Painted metal
50
63
30/29

Ivory white

49
62
51

52
64
94

3 steps
785
455
1 x AF-220-49-6-1
1 x P47L11S
1 x P47L11S
1 x 49
1 x 75
1 x (80+85)
WL fin, Hi-XA U-cooling tube
2 x 20 x 2.0
2 x 24 x 2.0
2 x 38 x 2.0
2 x 54 x 2.0
0.372
0.481
0.719
1,022
R-22
R-22
R-22
R-22
1.57
1.7
2
2.5
15m > 20g/m > 25m
10m > 20g/m > 25m
7.5m > 30g/m > 50m
7.5m > 30g/m > 50m
25
25
50
50
15
15
30
30
Max. 1
Max. 1
Hermetically sealed rotary compressor
Hermetically sealed scroll compressor
1 x (RC70AV1TRT/RC70YEN-R) 1 x (NH41VMDT/NH41YDPT) 1 x (JT90BC-V1/JT90BC-YE) 1 x (JT118BC-V1/JT118BC-YE)
1
1
2,850
2,850/2,900
SUNISO 4GSDI
DIAMOND MS32(N-1)
SUNISO 4GSDID-K
SUNISO 4GSDID-K
0.85
1.2/1.3
1.2
1.5
33
33
6.4
6.4
9.5
9.5
15.9
15.9
15.9
19.1
18
18 x 3
26 x 3
26 x 3
Both liquid and gas pipes
890
470
1 x F62P45J22
1 x 45

2 steps

54
67
43

R71B7V1/W1
R100B7V1/W1
860
1,215
880
880
320
320
85/82
100/95
Painted galvanised steel plate

3TW0041-1F
3TW00051-1F
3TW01121-1C
3TW01131-1C
3TW23181-1
3TW23191-1
3TW23221-1
3TW23231-1

Split - Sky Air Outdoor Units

Pair Application R-22 RE18-40GA/R25-45DC/R60FA/R71-250F

Specifications

16
2

TECHNICAL SPECIFICATIONS
OUTDOOR UNITS
DIMENSIONS

Unit

WEIGHT
MATERIAL
COLOUR
SOUND LEVEL

Unit
Unit
Sound pressure (1)

FAN

HEAT EXCHANGER

REFRIGERANT CIRCUIT

COMPRESSOR

PIPING CONNECTIONS

INSULATION MATERIAL

Sound power (2)


Air flow rate
Speed

Type
Qty x model
Qty x motor output
Type

H
W
D

mm
mm
mm
kg

high
low

dBA
dBA
dBA
m3/min

high
steps
high
low

Rows x stages x fin pitch


Face area
Refrigerant type
Refrigerant charge
Additional refrigerant
Maximum interunit piping length
Maximum interunit level difference
No. of circuits
Type
Qty x model
Number of cylinders
Speed
Oil type
Oil charge volume
Crankcase heater
liquid
gas
drain
Heat insulation tape

rpm
rpm

W
mm
m2
kg
m
m
m

R125B7W1
1,215
880
320
97

52
65
91
3 steps
2 x P47L11S
1 x (80+85)
Non symm. waffle louvre, Hi-XA cooling
tube
2 x 54 x 2.0
1,022
R-22
3
7.5m > 30g/m > 50m
50
30
-

rpm

1 x JT150BC-YE
-

!
W
mm
mm
mm

1.5
33
9.5
19.1
26 x 3

R200F7W1
1,220
1,290
700
169
Painted galvanised steel plate
Ivory white
56
77
150

R250F7W1
1,440
1,290
700
191

2 x 40 x 2
1.57
R-22
5.55
No additional refrigerant charge
70m equivalent
30
Hermetically sealed scroll compressor
1 x JT236D-YE@2
2,900
SUNISO 4GSDID-K
4
50
12.7 x 0.90
28.6 x 1.15
26 x 6
Both liquid and gas pipes

2 x 50 x 2
1.97
R-22
6.025
No additional refrigerant charge
70m equivalent
30
-

56
77
170

1 step
1 x P55J11F
1 x P55J11F
& x (230+140)
230+140
Assymetric louvre, J8 Hi-XA tube

1 x JT300D-YE@2
2,900
4
50
15.9 x 0.95
28.6 x 1.15
26 x 6
3TW23261-1
3TW21481-1C
3TW21491-1C

Split - Sky Air Outdoor Units

Pair Application R-22 RE18-40GA/R25-45DC/R60FA/R71-250F

Specifications

16
2

ELECTRICAL SPECIFICATIONS
OUTDOOR UNITS
CURRENT

OUTDOOR UNITS
POWER SUPPLY
NOMINAL DISTRIBUTION
SYSTEM VOLTAGE

Nominal running current


Max. running current
Starting current

Phase
Frequency
Voltage

A
A
A

RE18GA7V1
2.5
-

RE40GA7V1
7.1
-

R25DC7V11
3.8
18

R35DC7V11
6.1
26

Hz
V

RE18GA7V1
V1
1
50
230

RE40GA7V1
V1
1
50
230

R25DC7V11
V1
1
50
230

R35DC7V11
V1
1
50
230

A
A
A

R45DC7V11/W11
10.8/4.4
44/19

R60FA7V1/W1
10.4/5.2
13.5/6.7
53/27

R71B7V1/W1
-

R100B7V1/W1
-

Hz
V

R45DC7V11/W11
V11/W11
1/3N
50
230/400

R60FA7V1/W1
V1/W1
1/3N
50
230/400

R71B7V1/W1
V1/W1
1/3N
50
230/400

R100B7V1/W1
V1/W1
1/3N
50
230/400

ELECTRICAL SPECIFICATIONS
OUTDOOR UNITS
CURRENT

OUTDOOR UNITS
POWER SUPPLY
NOMINAL DISTRIBUTION
SYSTEM VOLTAGE

Nominal running current


Max. running current
Starting current

Phase
Frequency
Voltage

ELECTRICAL SPECIFICATIONS
OUTDOOR UNITS
CURRENT

OUTDOOR UNITS
POWER SUPPLY
NOMINAL DISTRIBUTION
SYSTEM VOLTAGE

Nominal running current


Max. running current
Starting current

Phase
Frequency
Voltage

A
A
A

R125B7W1
-

R200F7W1
18.9
21.9
-

R250F7W1
19.2
22.8
-

Hz
V

R125B7W1
W1
3N
50
400

R200F7W1
W1
3N
50
400

R250F7W1
W1
3N
50
400

NOTES

The sound pressure level is measured via a microphone at 1m distance from the unit. For measuring conditions: please refer to item 8 of this
chapter.

The sound power level is an absolute value indicating the power which a sound source generates.

Split - Sky Air Outdoor Units

Pair Application R-22 RE18-40GA/R25-45DC/R60FA/R71-250F

Specifications

16
2

ELECTRICAL DATA
RE18GA7V1

Connection ratio (%)

Indoor unit

Hz-Volts
50-220
50-230
50-240

FT18JV1B

Power supply
Voltage range
Max. 264V
Min. 198V

MCA

TOCA

MFA

Compressor
LRA
RLA

3.1

15.0

11

15

2.2

OFM

FLA

0.2

19

IFM

FLA

0.2

EH

FLA

3TW01011-3B

RE40GA7V1

Connection ratio (%)

Indoor unit

FT40GV1B

FL40GAV1NB

Hz-Volts
50-220
50-230
50-240
50-220
50-230
50-240

Power supply
Voltage range

MCA

TOCA

MFA

Compressor
LRA
RLA

Max. 264V
Min. 198V

8.6

20.0

34

6.5

Max. 264V
Min. 198V

8.9

20.0

34

6.6

OFM

FLA

45

0.3

45

0.3

IFM

EH

FLA

FLA

18

0.2

34

0.3

3TW01101-3C

R25DC7V11

Connection ratio (%)

Indoor unit

FT25JV1B

FL25GAV1NB

FHEB25GZ7V1

Hz-Volts
50-220
50-230
50-240
50-220
50-230
50-240
50-220
50-230
50-240

Power supply
Voltage range

MCA

TOCA

MFA

Compressor
LRA
RLA

Max. 264V
Min. 198V

4.9

15.0

19

3.6

Max. 264V
Min. 198V

5.0

15.0

19

Max. 264V
Min. 198V

5.1

15.0

19

OFM

FLA

15

0.2

3.6

15

3.8

15

IFM

EH

FLA

FLA

19

0.2

0.2

34

0.3

0.2

10

0.2

3TW00021-2D

R35DC7V11

Connection ratio (%)

Indoor unit

FT35JV1B

FL35GAV1NB

Hz-Volts
50-220
50-230
50-240
50-220
50-230
50-240

Power supply
Voltage range

MCA

TOCA

MFA

Compressor
LRA
RLA

Max. 264V
Min. 198V

7.2

15.0

26

5.4

Max. 264V
Min. 198V

7.3

15.0

26

5.4

OFM

FLA

30

0.3

30

0.3

IFM

EH

FLA

FLA

19

0.2

34

0.3

3TW00031-2C

SYMBOLS
MCA
TOCA
MFA
LRA
RLA
OFM
IFM
FLA
W
EH

:
:
:
:
:
:
:
:
:
:

NOTES

Min. Circuit Amps


Total Over Current Amps
Max. Fuse Amps
Locked Rotor Amps
Rated Load Amps (A)
Outdoor Fan Motor
Indoor Fan Motor
Full Load Amps
Rated motor output (W)
Electric heater

Split - Sky Air Outdoor Units

1. RLA is based on the following conditions:


Indoor temp.: 27CDB/19.0CWB
2. TOCA means the total value of each OC set.
3. Voltage range
Units are suitable for use on electrical systems where voltage supplied
to unit terminals is not below or above listed operation range limits
4. Maximum allowable voltage unbalance between phases is 2%.
5. MCA/MFA
MCA = 1.25 x RLA + ea. FLA + 1.25 x EH FLA
MFA < 2.25 x RLA + ea. FLA + 2.25 x EH FLA
(next lower standard fuse rating, min.15A)

Pair Application R-22 RE18-40GA/R25-45DC/R60FA/R71-250F

Specifications

16
2

ELECTRICAL DATA
R45DC7V11

Connection ratio (%)

Indoor unit

FT45GAV1B

FL45GAV1NB

Hz-Volts
50-220
50-230
50-240
50-220
50-230
50-240

Power supply
Voltage range

MCA

TOCA

MFA

Compressor
LRA
RLA

Max. 264V
Min. 198V

12.9

25.0

44

9.9

Max. 264V
Min. 198V

12.7

25.0

44

9.7

OFM

FLA

45

0.3

45

0.3

IFM

EH

FLA

FLA

40

0.2

34

0.3

3TW00041-2C

R45DC7W11

Connection ratio (%)

Indoor unit

FT45GAV1B

FL45GAV1NB

Hz-Volts
50-380
50-400
50-415
50-380
50-400
50-415

Power supply
Voltage range

MCA

TOCA

MFA

Compressor
LRA
RLA

Max. 400V
Min. 342V

5.5

15.0

19

3.7

Max. 440V
Min. 342V

5.3

15.0

19

3.7

OFM

FLA

45

0.3

45

0.3

IFM

EH

FLA

FLA

40

0.2

34

0.3

3TW00051-2E

R60FA7V1/W1

Unit combination
Indoor unit
Outdoor unit
FT60GAV1B

R60FA7V1

FT60GAV1B

R60FA7W1

Hz-Volts
50-220
50-230
50-240
50-400

Power supply
Voltage range

MCA

TOCA

MFA

Max. 254V
Min. 198V

13

20

Max. 440V
Min. 360V

6.2

15

Compressor
LRA
RLA
52
9.9
55
9.6
58
9.3
22

4.2

OFM

FLA

55.3

0.3

49

0.5

IFM

EH

FLA

FLA

130

0.6

40

0.2

3TW01121-2B + 3TW01131-2B

SYMBOLS
MCA
TOCA
MFA
LRA
RLA
OFM
IFM
FLA
W
EH

:
:
:
:
:
:
:
:
:
:

NOTES

Min. Circuit Amps


Total Over Current Amps
Max. Fuse Amps
Locked Rotor Amps
Rated Load Amps (A)
Outdoor Fan Motor
Indoor Fan Motor
Full Load Amps
Rated motor output (W)
Electric heater

Split - Sky Air Outdoor Units

1. RLA is based on the following conditions:.


Indoor temp.: 27CDB/19,5CWB
Outdoor temp. : 35CDB
2. TOCA means the total value of each OC set.
3. Maximum allowable voltage variation between phases is 2%.
4. Select wire size based on the larger value of MCA or TOCA
5. Instead of fuse, use circuit breaker
6. Units are suitable for use on electrical systems where voltage supplied
to unit terminals is not below or above listed operation range limits

Pair Application R-22 RE18-40GA/R25-45DC/R60FA/R71-250F

Specifications

16
2

ELECTRICAL DATA
R71B7V1/W1

Unit combination
Indoor unit
Outdoor unit
FHYC71/FUY71
R71B7V1
FH71
R71B7V1
FHY71
R71B7V1
FAY71
R71B7V1
FHYK71
R71B7V1
FHYB71
R71B7V1
FHYC71/FUY71
R71B7W1
FH71
R71B7W1
FHY71
R71B7W1
FAY71
R71B7W1
FHYK71
R71B7W1
FHYB71
R71B7W1

Hz - Volts
50-230
50-230
50-230
50-230
50-230
50-230
50-400/230
50-400/230
50-400/230
50-400/230
50-400/230
50-400/230

Power supply
Voltage range
Max. 50Hz-253V
Min. 50Hz-197V

Max. 50Hz-400/253V
Min. 50Hz-360/197V

MCA
17.9
17.6
17.9
17.6
17.8
18.2
7.1
6.8
7.1
6.8
7.0
7.4

TOCA
23.3
23.0
23.3
23.0
23.2
23.6
8.8
8.5
8.8
8.5
8.7
9.1

MFA
32
32
32
32
32
32
16
16
16
16
16
16

Compressor
LRA
RLA
93
13.3
93
13.3
93
13.3
93
13.3
93
13.3
93
13.3
40
4.6
40
4.6
40
4.6
40
4.6
40
4.6
40
4.6

kW
0.075
0.075
0.075
0.075
0.075
0.075
0.075
0.075
0.075
0.075
0.075
0.075

OFM

FLA
0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.7

kW
0.045
0.057
0.062
0.046
0.045
0.125
0.045
0.057
0.062
0.046
0.045
0.125

IFM

FLA
0.6
0.3
0.6
0.3
0.5
0.9
0.6
0.3
0.6
0.3
0.5
0.9

3TW23189-2A

SYMBOLS
MCA
TOCA
MFA
LRA
RLA
OFM
IFM
FLA
W

:
:
:
:
:
:
:
:
:

NOTES

Min. Circuit Amps


Total Over Current Amps
Max. Fuse Amps (See note 7)
Locked Rotor Amps
Rated Load Amps (A)
Outdoor Fan Motor
Indoor Fan Motor
Full Load Amps
Rated motor output (W)

Split - Sky Air Outdoor Units

1. RLA is based on the following conditions:


Indoor temp.: 27CDB/19,5CWB
Outdoor temp. : 35CDB
2. TOCA means the total value of each OC set
3. Voltage range
Units are suitable for use on electrical systems where voltage supplied
to unit terminals is not below or above listed operation range limits
4. Maximum allowable voltage unbalance between phases is 2%
5. MCA/MFA
MCA = 1.25 x RLA + ea. FLA
MFA 2.25 x RLAA + ea. FLA
(next lower standard fuse rating min 16A)
6. Select wire size based on the larger value of MCA or TOCA
7. Instead of fuse, use circuit breaker

Pair Application R-22 RE18-40GA/R25-45DC/R60FA/R71-250F

Specifications

16
2

ELECTRICAL DATA
R100B7V1/W1

Unit combination
Indoor unit
Outdoor unit

Hz - Volts

Power supply
Voltage range

MCA

TOCA

MFA

Compressor
LRA
RLA

FHYC100
FUY100

R100B7V1

50-230

23.2

28.5

40

114

16.5

FH100

R100B7V1

50-230

23.1

28.4

40

114

16.5

FHY100

R100B7V1

50-230

22.9

28.2

40

114

16.5

FHYB100

R100B7V1

50-230

23.2

28.5

40

114

16.5

FAY100

R100B7V1

50-230

22.6

27.9

40

114

16.5

FHYC100
FUY100

R100B7W1

50-400/230

9.8

12.5

16

53

5.8

FH100

R100B7W1

50-400/230

9.7

12.4

16

53

5.8

FHY100

R100B7W1

50-400/230

9.5

12.2

16

53

5.8

FHYB100

R100B7W1

50-400/230

9.8

12.5

16

53

5.8

FAY100

R100B7W1

50-400/230

9.2

11.9

16

53

5.8

Max. 50Hz-253V
Min. 50Hz-197V

Max. 50Hz-400/253V
Min. 50Hz-360/197V

kW
0.08
+
0.085
0.08
+
0.085
0.08
+
0.085
0.08
+
0.085
0.08
+
0.085
0.08
+
0.085
0.08
+
0.085
0.08
+
0.085
0.08
+
0.085
0.08
+
0.085

OFM

FLA
0.84
+
0.7
0.84
+
0.7
0.84
+
0.7
0.84
+
0.7
0.84
+
0.7
0.84
+
0.7
0.84
+
0.7
0.84
+
0.7
0.84
+
0.7
0.84
+
0.7

kW

IFM

FLA

0.09

1.0

0.13

0.9

0.13

0.7

0.135

1.0

0.049

0.4

0.09

1.0

0.13

0.9

0.13

0.7

0.135

1.0

0.049

0.4

3TW23229-2A

SYMBOLS
MCA
TOCA
MFA
LRA
RLA
OFM
IFM
FLA
W

10

:
:
:
:
:
:
:
:
:

NOTES

Min. Circuit Amps


Total Over Current Amps
Max. Fuse Amps (see note 7)
Locked Rotor Amps
Rated Load Amps (A)
Outdoor Fan Motor
Indoor Fan Motor
Full Load Amps
Rated motor output (W)

Split - Sky Air Outdoor Units

1. RLA is based on the following conditions:


Indoor temp.: 27CDB/19,5CWB
Outdoor temp. : 35CDB
2. TOCA means the total value of each OC set
3. Voltage range
Units are suitable for use on electrical systems where voltage supplied
to unit terminals is not below or above listed operation range limits
4. Maximum allowable voltage unbalance between phases is 2%
5. MCA/MFA
MCA = 1.25 x RLA + ea. FLA
MFA 2.25 x RLAA + ea. FLA
(next lower standard fuse rating min 16A)
6. Select wire size based on the larger value of MCA or TOCA
7. Instead of fuse, use circuit breaker

Pair Application R-22 RE18-40GA/R25-45DC/R60FA/R71-250F

Specifications

16
2

ELECTRICAL DATA
R125B7W1

Unit combination
Indoor unit
Outdoor unit

Hz - Volts

Power supply
Voltage range

MCA

TOCA

MFA

Compressor
LRA
RLA

FHYC125
FUY125

R125B7W1

50-400/230

11.5

15.5

20

67

7.2

FH125

R125B7W1

50-400/230

11.4

15.4

20

67

7.2

FHY125

R125B7W1

50-400/230

11.2

15.2

20

67

7.2

FHYB125

R125B7W1

50-400/230

11.9

15.9

20

67

7.2

FDY125

R125B7W1

50-400/230

14.7

18.7

20

67

7.2

Max. 50Hz-440/253V
Min. 50Hz-360/197V

kW
0.085
+
0.08
0.085
+
0.08
0.085
+
0.08
0.085
+
0.08
0.085
+
0.08

OFM

FLA
0.84
+
0.7
0.84
+
0.7
0.84
+
0.7
0.84
+
0.7
0.84
+
0.7

kW

IFM

FLA

0.09

1.0

0.13

0.9

0.13

0.7

0.225

1.4

0.5

4.2

3TW23269-2

SYMBOLS
MCA
TOCA
MFA
LRA
RLA
OFM
IFM
FLA
W

:
:
:
:
:
:
:
:
:

NOTES

Min. Circuit Amps


Total Over Current Amps
Max. Fuse Amps (See note 7)
Locked Rotor Amps
Rated Load Amps (A)
Outdoor Fan Motor
Indoor Fan Motor
Full Load Amps
Rated motor output (W)

Split - Sky Air Outdoor Units

1. RLA is based on the following conditions:


Indoor temp.: 27CDB/19,5CWB
Outdoor temp. : 35CDB
2. TOCA means the total value of each OC set
3. Voltage range
Units are suitable for use on electrical systems where voltage supplied
to unit terminals is not below or above listed operation range limits
4. Maximum allowable voltage unbalance between phases is 2%
5. MCA/MFA
MCA = 1.25 x RLA + ea. FLA
MFA 2.25 x RLAA + ea. FLA
(next lower standard fuse rating, min.15A)
6. Select wire size based on the larger value of MCA or TOCA
7. Instead of fuse, use circuit breaker

11

Pair Application R-22 RE18-40GA/R25-45DC/R60FA/R71-250F

Specifications

16
2

ELECTRICAL DATA
R200-250F7W1

Unit combination
Indoor unit
Outdoor unit

Hz - Volts

FDY200F7V1

R200F7W1

50-400

FDY250F7V1

R250F7W1

50-400

Power supply
Voltage range
Min. 360V
Max. 440V

MCA
16.5
19.3

MFA
25
+
26
32
+
16

Compressor
LRA
RLA
89

11.2

89

13.4

kW
0.14
+
0.23
0.14
+
0.23

OFM

FLA
1.1
+
1.43
1.1
+
1.43

IFM

kW

FLA

650

6.8

1000

7.6

3TW21481-2A

SYMBOLS
MCA
TOCA
MFA
LRA
RLA
OFM
IFM
FLA
W

12

:
:
:
:
:
:
:
:
:

NOTES

Min. Circuit Amps


Total Over Current Amps
Max. Fuse Amps (See note 7)
Locked Rotor Amps
Rated Load Amps (A)
Outdoor Fan Motor
Indoor Fan Motor
Full Load Amps
Rated motor output (W)

Split - Sky Air Outdoor Units

1. RLA is based on the following conditions:


Indoor temp.: 27CDB/19,5CWB
Outdoor temp. : 35CDB
2. TOCA means the total value of each OC set
3. Voltage range
Units are suitable for use on electrical systems where voltage supplied
to unit terminals is not below or above listed operation range limits
4. Maximum allowable voltage unbalance between phases is 2%
5. MCA/MFA
MCA = 1.25 x RLA + ea. FLA
MFA 2.25 x RLAA + ea. FLA
(next lower standard fuse rating, min.15A)
6. Select wire size based on the larger value of MCA or TOCA
7. Instead of fuse, use circuit breaker

Pair Application R-22 RE18-40GA/R25-45DC/R60FA/R71-250F

Capacity tables

RE18GA7V1 + FT18JV1B
Cooling capacity

EWB
(C)
12.0
14.0
16.0
18.0
19.0
22.0
24.0

Indoor

EDB
(C)
18.0
20.0
22.0
25.0
27.0
30.0
32.0

TC
1.68
1.79
1.91
2.03
2.09
2.27
2.39

Model
AFR
BF

230V [50Hz]

20
SHC
1.61
1.67
1.73
1.79
1.82
1.91
1.97

PI
0.42
0.43
0.43
0.44
0.44
0.45
0.45

TC
1.58
1.70
1.82
1.94
2.00
2.17
2.29

25
SHC
1.54
1.60
1.66
1.72
1.75
1.84
1.90

PI
0.46
0.46
0.47
0.47
0.48
0.48
0.49

TC
1.44
1.56
1.68
1.80
1.86
2.04
2.16

32
SHC
1.44
1.50
1.56
1.63
1.66
1.75
1.81

Outdoor temperature (C)


PI
0.51
0.51
0.52
0.53
0.53
0.54
0.54

TC
1.38
1.50
1.62
1.74
1.80
1.98
2.10

35
SHC
1.40
1.46
1.52
1.58
1.61
1.71
1.77

PI
0.53
0.54
0.54
0.55
0.55
0.56
0.56

TC
1.28
1.40
1.52
1.64
1.70
1.88
2.00

40
SHC
1.33
1.39
1.45
1.52
1.55
1.64
1.70

PI
0.57
0.57
0.58
0.58
0.59
0.59
0.60

16
3

FT
7.3
0.28

TC
1.23
1.34
1.46
1.58
1.64
1.82
1.94

43
SHC
1.29
1.35
1.41
1.47
1.51
1.60
1.66

PI
0.59
0.60
0.60
0.61
0.61
0.62
0.62

3TW01012-1B

Model

RE18GA7V1 + FHEB18BA7V1
Cooling capacity

EWB
(C)
12.0
14.0
16.0
18.0
19.0
22.0
24.0

Indoor

EDB
(C)
18.0
20.0
22.0
25.0
27.0
30.0
32.0

TC
1.61
1.75
1.88
2.01
2.09
2.29
2.43

230V [50Hz]

20
SHC
1.09
1.13
1.18
1.22
1.24
1.30
1.35

PI
0.40
0.41
0.42
0.43
0.43
0.45
0.46

TC
1.48
1.62
1.76
1.89
1.96
2.16
2.30

25
SHC
1.05
1.09
1.13
1.18
1.19
1.26
1.30

PI
0.44
0.45
0.46
0.47
0.47
0.49
0.49

TC
1.30
1.43
1.57
1.71
1.77
1.98
2.12

32
SHC
0.99
1.03
1.08
1.12
1.14
1.20
1.24

Outdoor temperature (C)


PI
0.49
0.49
0.50
0.51
0.52
0.53
0.54

FHEB
6.50
0.43

AFR
BF

TC
1.22
1.36
1.50
1.64
1.70
1.90
2.04

35
SHC
0.96
1.00
1.05
1.09
1.11
1.18
1.22

PI
0.51
0.52
0.53
0.54
0.54
0.56
0.57

TC
1.09
1.23
1.37
1.51
1.57
1.77
1.91

40
SHC
0.92
0.96
1.00
1.05
1.07
1.13
1.18

PI
0.55
0.56
0.57
0.58
0.58
0.59
0.60

TC
0.55
0.62
0.68
0.75
0.79
0.89
0.96

46
SHC
0.46
0.48
0.50
0.52
0.53
0.57
0.59

PI
0.27
0.28
0.28
0.29
0.29
0.30
0.30

3TW01012-2A

Model

RE40GA7V1 + FT40GV1B
+ FL40GAV1NB
Cooling capacity

EWB
(C)
12.0
14.0
16.0
18.0
19.0
22.0
24.0

Indoor

EDB
(C)
18.0
20.0
22.0
25.0
27.0
30.0
32.0

TC
3.67
3.96
4.25
4.54
4.69
5.13
5.44

20
SHC
2.73
2.78
2.84
2.90
2.93
3.01
3.07

230V [50Hz]

PI
1.17
1.19
1.22
1.23
1.24
1.27
1.28

TC
3.55
3.82
4.10
4.39
4.52
4.96
5.25

25
SHC
2.66
2.72
2.77
2.83
2.86
2.95
2.99

PI
1.27
1.29
1.31
1.34
1.35
1.38
1.40

TC
3.34
3.60
3.87
4.13
4.27
4.67
4.94

32
SHC
2.56
2.61
2.67
2.73
2.76
2.84
2.90

AFR
BF

Outdoor temperature (C)


PI
1.41
1.44
1.47
1.50
1.51
1.55
1.57

TC
3.25
3.51
3.76
4.02
4.15
4.54
4.80

35
SHC
2.51
2.57
2.63
2.69
2.72
2.80
2.86

FT
8.3
0.24

FL
6.5
0.20

PI
1.48
1.51
1.54
1.57
1.58
1.62
1.65

TC
3.08
3.33
3.57
3.82
3.94
4.31
4.56

Correction
FL
40
SHC
2.44
2.50
2.56
2.61
2.64
2.73
2.78

PI
1.59
1.62
1.65
1.69
1.71
1.76
1.79

TC
0

TC
2.97
3.21
3.45
3.68
3.80
4.16
4.40

SHC
0

PI
+0.05

43
SHC
2.40
2.46
2.51
2.57
2.60
2.69
2.74

PI
1.66
1.70
1.73
1.77
1.79
1.84
1.87

3TW01102-1C

SYMBOLS
AFR:
BF:
EWB:
EDB:
TC:
SHC:
PI:

NOTES

Air flow rate


Bypass factor
Entering wet bulb temp.
Entering dry bulb temp.
Total cooling/heating capacity
Sensible heating capacity
Power input
(comp.+indoor+outdoor fan motor)

(m3/min)
(CWB)
(CDB)
(kW)
(kW)
(kW)

Caution:
TC and SHC are shown by kW

Split - Sky Air Outdoor Units

1. Ratings shown are net capacities which include a deduction for indoor fan
motor heat
2.
Shows nominal capacities
3. SHC is based on each EWB and EDB
SHC* = SHC correction for other dry bulb
SHC* = 0.34 x 60 x AFR (m3/min) x (DB-EDB)/1000.
Add SHC* to SHC if SHC > TC, then TC equal SHC
4. Add the correction value to power input (W) as shown above
5. Direct interpolation is permissible. Do not extrapolate.
6. Capacities are based on the following conditions:
Corresponding refrigerant piping length:
7.5 m
Level difference:
0m

13

Pair Application R-22 RE18-40GA/R25-45DC/R60FA/R71-250F

16
3

Capacity tables

R25DC7V11 (R25DB7V11) + FT25JV1B


+ FL25GAV1NB

Model

Cooling capacity

EWB
(C)
12.0
14.0
16.0
18.0
19.0
22.0
24.0

Indoor

EDB
(C)
18.0
20.0
22.0
25.0
27.0
30.0
32.0

TC
2.34
2.50
2.65
2.80
2.88
3.11
3.26

AFR
BF

230V [50Hz]

20
SHC
1.95
2.01
2.07
2.13
2.15
2.24
2.30

PI
0.67
0.68
0.69
0.70
0.71
0.72
0.73

TC
2.20
2.35
2.51
2.66
2.74
2.96
3.12

25
SHC
1.87
1.93
1.98
2.04
2.07
2.16
2.21

PI
0.72
0.73
0.74
0.75
0.76
0.77
0.78

TC
2.00
2.15
2.31
2.46
2.54
2.76
2.92

32
SHC
1.75
1.81
1.86
1.92
1.95
2.04
2.09

Outdoor temperature (C)


PI
0.80
0.81
0.81
0.82
0.83
0.84
0.85

FT
6.6
0.24

TC
1.92
2.07
2.22
2.37
2.45
2.68
2.83

35
SHC
1.70
1.75
1.81
1.87
1.90
1.99
2.04

PI
0.83
0.84
0.85
0.86
0.86
0.87
0.88

TC
1.77
1.93
2.08
2.23
2.31
2.54
2.69

40
SHC
1.61
1.67
1.73
1.78
1.81
1.90
1.96

PI
0.88
0.89
0.90
0.91
0.91
0.93
0.94

TC
1.60
1.75
1.91
2.06
2.14
2.37
2.52

FL
7.5
0.21
46
SHC
1.51
1.57
1.62
1.68
1.71
1.80
1.85

PI
0.94
0.95
0.96
0.97
0.97
0.99
1.00

3TW00022-2D

Model

R25DC7V11 + FHEB25GZ7V1
Cooling capacity

EWB
C
12.0
14.0
16.0
18.0
19.0
22.0
24.0

Indoor

EDB
C
18.0
20.0
22.0
25.0
27.0
30.0
32.0

TC
2.30
2.44
2.59
2.74
2.82
3.04
3.19

230V [50Hz]

20
SHC
1.91
1.97
2.03
2.08
2.11
2.20
2.25

PI
0.69
0.70
0.71
0.72
0.72
0.74
0.75

TC
2.16
2.31
2.45
2.60
2.68
2.90
3.05

25
SHC
1.83
1.89
1.94
2.00
2.03
2.11
2.17

PI
0.74
0.75
0.76
0.77
0.77
0.79
0.80

TC
1.96
2.11
2.26
2.41
2.48
2.71
2.86

32
SHC
1.71
1.77
1.83
1.88
1.91
1.99
2.05

Outdoor temperature (C)


PI
0.81
0.82
0.83
0.84
0.85
0.86
0.87

FHEB25
6.5
0.43

AFR
BF

TC
1.88
2.03
2.18
2.33
2.40
2.62
2.77

35
SHC
1.66
1.72
1.78
1.83
1.86
1.94
2.00

PI
0.85
0.86
0.87
0.88
0.88
0.89
0.90

TC
1.74
1.89
2.04
2.19
2.26
2.48
2.63

40
SHC
1.58
1.64
1.69
1.75
1.78
1.86
1.92

PI
0.90
0.91
0.92
0.93
0.93
0.95
0.96

TC
1.57
1.72
1.87
2.02
2.09
2.32
2.47

46
SHC
1.48
1.54
1.59
1.65
1.68
1.76
1.82

PI
0.96
0.97
0.98
0.99
1.00
1.01
1.02

3TW00022-2D

Model

R35DC7V11 + FT35GV1B
+ FL35GV1NB
Cooling capacity

EWB
(C)
12.0
14.0
16.0
18.0
19.0
22.0
24.0

Indoor

EDB
(C)
18.0
20.0
22.0
25.0
27.0
30.0
32.0

TC
3.24
3.42
3.59
3.77
3.86
4.12
4.29

20
SHC
2.54
2.59
2.63
2.67
2.69
2.75
2.79

230V [50Hz]

PI
0.92
0.94
0.97
0.99
1.01
1.04
1.07

TC
3.07
3.25
3.42
3.60
3.69
3.95
4.12

25
SHC
2.46
2.50
2.54
2.58
2.60
2.66
2.70

PI
1.01
1.03
1.06
1.08
1.09
1.13
1.16

TC
2.84
3.01
3.19
3.36
3.45
3.71
3.89

32
SHC
2.33
2.37
2.41
2.45
2.48
2.54
2.58

AFR
BF

Outdoor temperature (C)


PI
1.13
1.15
1.18
1.20
1.22
1.25
1.28

TC
2.74
2.91
3.09
3.26
3.35
3.61
3.79

35
SHC
2.28
2.32
2.36
2.40
2.42
2.48
2.52

FT
7.8
0.26

FL
8
0.31

PI
1.18
1.21
1.23
1.26
1.27
1.31
1.33

TC
2.57
2.74
2.92
3.09
3.18
3.44
3.62

Correction
FL
40
SHC
2.19
2.23
2.27
2.31
2.33
2.40
2.44

PI
1.27
1.30
1.32
1.35
1.36
1.40
1.42

TC
+0.05

TC
2.37
2.54
2.72
2.89
2.98
3.24
3.42

SHC
+0.05

PI
+0.02

46
SHC
2.08
2.12
2.17
2.21
2.23
2.29
2.33

PI
1.38
1.40
1.43
1.45
1.46
1.50
1.53

3TW00032-6C

SYMBOLS
AFR:
BF:
EWB:
EDB:
TC:
SHC:
PI:

NOTES

Air flow rate


Bypass factor
Entering wet bulb temp.
Entering dry bulb temp.
Total cooling/heating capacity
Sensible heating capacity
Power input
(comp.+indoor+outdoor fan motor)

(m3/min)
(CWB)
(CDB)
(kW)
(kW)
(kW)

Caution:
TC and SHC are shown by kW

14

Split - Sky Air Outdoor Units

1. Ratings shown are net capacities which include a deduction for indoor fan
motor heat
2.
Shows nominal capacities
3. SHC is based on each EWB and EDB
SHC* = SHC correction for other dry bulb
SHC* = 0.34 x 60 x AFR (m3/min) x (DB-EDB)/1000.
Add SHC* to SHC if SHC > TC, then TC equal SHC
4. Add the correction value to power input (W) as shown above
5. Direct interpolation is permissible. Do not extrapolate.
6. Capacities are based on the following conditions:
Corresponding refrigerant piping length:
7.5 m
Level difference:
0m

Pair Application R-22 RE18-40GA/R25-45DC/R60FA/R71-250F

Capacity tables

16

R45DC7V11 + FT45GAV1B
+ FL40GAV1NB
Cooling capacity

EWB
C
12.0
14.0
16.0
18.0
19.0
22.0
24.0

Indoor

EDB
C
18.0
20.0
22.0
25.0
27.0
30.0
32.0

TC
4.86
5.18
5.50
5.82
5.98
6.45
6.77

20
SHC
3.43
3.50
3.57
3.64
3.68
3.78
3.85

Model
230V [50Hz]
400V [50Hz]

PI
1.53
1.57
1.61
1.65
1.67
1.73
1.77

TC
4.62
4.94
5.26
5.58
5.73
6.21
6.53

25
SHC
3.34
3.41
3.48
3.55
3.59
3.69
3.76

PI
1.69
1.73
1.77
1.81
1.83
1.89
1.93

TC
4.28
4.60
4.92
5.24
5.40
5.87
6.19

32
SHC
3.22
3.29
3.36
3.43
3.47
3.57
3.64

AFR
BF

Outdoor temperature (C)


PI
1.92
1.96
2.00
2.04
2.06
2.12
2.16

TC
4.14
4.45
4.77
5.09
5.25
5.73
6.05

35
SHC
3.17
3.24
3.31
3.38
3.41
3.52
3.59

FT
11.8
0.18

FL
10.7
0.18

PI
2.02
2.06
2.10
2.14
2.16
2.22
2.26

TC
3.89
4.21
4.53
4.85
5.01
5.49
5.80

Correction
FL
40
SHC
3.08
3.15
3.22
3.29
3.32
3.43
3.50

PI
2.18
2.22
2.26
2.30
2.32
2.38
2.42

TC
-0.1

TC
3.60
3.92
4.24
4.56
4.72
5.19
5.51

SHC
-0.06

PI
-0.03

46
SHC
2.97
3.04
3.11
3.18
3.22
3.32
3.39

PI
2.38
2.42
2.46
2.50
2.52
2.58
2.62

3TW00042-6C

R45DC7W11 + FT45GAV1B
+ FL45GAV1NB
Cooling capacity

EWB
C
12.0
14.0
16.0
18.0
19.0
22.0
24.0

Indoor

EDB
C
18.0
20.0
22.0
25.0
27.0
30.0
32.0

TC
4.86
5.18
5.50
5.82
5.98
6.45
6.77

20
SHC
3.43
3.50
3.57
3.64
3.68
3.78
3.85

Model
230V [50Hz]
400V [50Hz]

PI
1.42
1.46
1.50
1.54
1.56
1.62
1.66

TC
4.62
4.94
5.26
5.58
5.73
6.21
6.53

25
SHC
3.34
3.41
3.48
3.55
3.59
3.69
3.76

PI
1.58
1.62
1.66
1.70
1.72
1.78
1.82

TC
4.28
4.60
4.92
5.24
5.40
5.87
6.19

32
SHC
3.22
3.29
3.36
3.43
3.47
3.57
3.64

AFR
BF

Outdoor temperature (C)


PI
1.81
1.85
1.89
1.93
1.95
2.01
2.05

TC
4.14
4.45
4.77
5.09
5.25
5.73
6.05

35
SHC
3.17
3.24
3.31
3.38
3.41
3.52
3.59

FT
11.8
0.18

FL
10.7
0.18

PI
1.91
1.95
1.99
2.03
2.05
2.11
2.15

TC
3.89
4.21
4.53
4.85
5.01
5.49
5.80

Correction
FL
40
SHC
3.08
3.15
3.22
3.29
3.32
3.43
3.50

PI
2.07
2.11
2.15
2.19
2.21
2.27
2.31

TC
-0.1

TC
3.60
3.92
4.24
4.56
4.72
5.19
5.51

SHC
-0.06

PI
-0.03

46
SHC
2.97
3.04
3.11
3.18
3.22
3.32
3.39

PI
2.27
2.31
2.35
2.39
2.41
2.47
2.51

3TW00052-1C

R60FA7V1,W1 + FT60GAV1B

Model

Cooling capacity

EWB
(C)
12.0
14.0
16.0
18.0
19.0
22.0
24.0

Indoor

EDB
(C)
18.0
20.0
22.0
25.0
27.0
30.0
32.0

TC
5.95
6.29
6.63
6.97
7.14
7.65
7.99

20
SHC
4.46
4.52
4.58
4.64
4.67
4.76
4.82

PI
1.58
1.63
1.68
1.73
1.76
1.83
1.88

TC
5.69
6.03
6.37
6.71
6.88
7.39
7.73

25
SHC
4.39
4.45
4.51
4.57
4.60
4.69
4.75

PI
1.78
1.83
1.88
1.93
1.96
2.03
2.08

TC
5.32
5.66
6.00
6.34
6.51
7.02
7.36

32
SHC
4.28
4.34
4.40
4.46
4.49
4.58
4.64

Outdoor temperature (C)


PI
2.06
2.11
2.16
2.21
2.23
2.31
2.36

FT
13.3
0.15

AFR
BF

230V [50Hz]
400V [50Hz]

TC
5.16
5.50
5.84
6.18
6.35
6.86
7.20

35
SHC
4.24
4.30
4.36
4.42
4.45
4.54
4.60

PI
2.18
2.23
2.28
2.33
2.35
2.43
2.48

TC
4.90
5.24
5.58
5.92
6.09
6.60
6.94

40
SHC
4.16
4.22
4.28
4.34
4.37
4.46
4.52

PI
2.37
2.42
2.47
2.52
2.55
2.62
2.67

TC
4.58
4.92
5.26
5.60
5.77
6.28
6.62

46
SHC
4.07
4.13
4.19
4.25
4.28
4.37
4.43

FV
13.7
0.18

PI
2.61
2.66
2.71
2.76
2.78
2.86
2.91

3TW01122-1B

SYMBOLS
AFR:
BF:
EWB:
EDB:
TC:
SHC:
PI:

NOTES

Air flow rate


Bypass factor
Entering wet bulb temp.
Entering dry bulb temp.
Total cooling/heating capacity
Sensible heating capacity
Power input
(comp.+indoor+outdoor fan motor)

(m3/min)
(CWB)
(CDB)
(kW)
(kW)
(kW)

Caution:
TC and SHC are shown by kW

Split - Sky Air Outdoor Units

1. Ratings shown are net capacities which include a deduction for indoor fan
motor heat
2.
Shows nominal capacities
3. SHC is based on each EWB and EDB
SHC* = SHC correction for other dry bulb
SHC* = 0.34 x 60 x AFR (m3/min) x (DB-EDB)/1000.
Add SHC* to SHC if SHC > TC, then TC equal SHC
4. Add the correction value to power input (W) as shown above
5. Direct interpolation is permissible. Do not extrapolate.
6. Capacities are based on the following conditions:
Corresponding refrigerant piping length:
7.5 m
Level difference:
0m

15

Pair Application R-22 RE18-40GA/R25-45DC/R60FA/R71-250F

16
3

Capacity tables

FH3560 + R35DC7V11
R45DC7V11/W11
R60FA7V1/W1
Cooling capacity

Outdoor

35

45

60

Indoor
EWB
EDB
(C)
(C)
12.0
18.0
14.0
20.0
16.0
22.0
18.0
25.0
19.0
27.0
19.5
27.0
22.0
30.0
24.0
32.0
12.0
18.0
14.0
20.0
16.0
22.0
18.0
25.0
19.0
27.0
19.5
27.0
22.0
30.0
24.0
32.0
12.0
18.0
14.0
20.0
16.0
22.0
18.0
25.0
19.0
27.0
22.0
30.0
24.0
32.0

Model
AFR
BF

V11: 230V [50Hz]


W11: 400V [50Hz]

TC
3.98
4.20
4.40
4.62
4.73
4.79
5.05
5.28
4.73
5.11
5.47
5.85
6.04
6.12
6.62
7.02
5.98
6.32
6.67
7.04
7.23
7.82
8.22

20
SHC
2.84
2.87
2.92
2.97
2.99
3.00
3.05
3.09
3.52
3.59
3.66
3.73
3.78
3.80
3.88
3.95
4.05
4.11
4.18
4.24
4.26
4.35
4.41

PI
1.06
1.09
1.14
1.16
1.18
1.18
1.21
1.25
1.60
1.63
1.66
1.68
1.69
1.70
1.73
1.75
1.72
1.75
1.79
1.82
1.84
1.90
1.95

TC
3.76
3.98
4.21
4.42
4.53
4.57
4.75
5.07
4.58
4.93
5.29
5.66
5.83
5.93
6.39
6.77
5.78
6.12
6.46
6.82
7.01
7.58
7.97

25
SHC
2.73
2.77
2.82
2.87
2.90
2.91
2.95
3.00
3.43
3.51
3.58
3.65
3.68
3.69
3.80
3.86
3.97
4.03
4.09
4.16
4.19
4.27
4.33

PI
1.18
1.21
1.24
1.27
1.28
1.29
1.32
1.36
1.73
1.76
1.79
1.82
1.84
1.84
1.88
1.91
1.88
1.91
1.96
2.00
2.02
2.09
2.14

TC
3.48
3.70
3.90
4.12
4.23
4.29
4.56
4.78
4.31
4.65
4.99
5.33
5.50
5.59
6.02
6.37
5.49
5.81
6.14
6.48
6.66
7.21
7.59

Outdoor temperature (CDB)


32
35
SHC
PI
TC
SHC
2.60
1.32
3.34
2.53
2.65
1.36
3.56
2.59
2.69
1.39
3.79
2.64
2.73
1.42
4.00
2.67
2.75
1.43
4.05
2.69
2.76
1.44
4.22
2.70
2.82
1.48
4.43
2.76
2.86
1.51
4.64
2.81
3.29
1.92
4.19
3.24
3.36
1.96
4.52
3.31
3.44
2.00
4.85
3.38
3.52
2.04
5.19
3.46
3.56
2.05
5.35
3.50
3.58
2.06
5.44
3.52
3.66
2.11
5.85
3.61
3.73
2.14
6.19
3.68
3.87
2.13
5.36
3.82
3.93
2.17
5.67
3.88
3.99
2.22
5.99
3.94
4.05
2.27
6.33
4.00
4.08
2.29
6.50
4.03
4.18
2.37
7.03
4.13
4.24
2.43
7.40
4.19

PI
1.40
1.43
1.46
1.49
1.50
1.51
1.54
1.58
2.01
2.05
2.09
2.13
2.15
2.16
2.21
2.25
2.24
2.29
2.34
2.40
2.42
2.51
2.56

TC
3.15
3.35
3.57
3.79
3.89
3.96
4.23
4.44
3.97
4.29
4.61
4.92
5.07
5.16
5.56
5.87
5.13
5.43
5.74
6.06
6.22
6.73
7.08

35
13
0.2
40
SHC
2.44
2.49
2.53
2.58
2.60
2.61
2.67
2.70
3.15
3.22
3.29
3.36
3.41
3.43
3.52
3.59
3.76
3.81
3.87
3.93
3.96
4.05
4.11

PI
1.50
1.53
1.57
1.59
1.61
1.61
1.65
1.69
2.16
2.21
2.25
2.30
2.32
2.33
2.39
2.43
2.44
2.51
2.56
2.62
2.65
2.74
2.80

FH..B
45
13
0.09

TC
2.90
3.11
3.32
3.54
3.65
3.71
3.98
4.20
3.68
3.98
4.28
4.58
4.72
4.79
5.18
5.46
4.84
5.12
5.41
5.71
5.86
6.34
5.69

60
16
0.10
46
SHC
2.33
2.37
2.42
2.45
2.48
2.48
2.54
2.60
3.05
3.12
3.19
3.26
3.29
3.31
3.41
3.49
3.66
3.73
3.79
3.84
3.87
3.96
4.02

PI
1.64
1.67
1.70
1.73
1.74
1.75
1.79
1.81
2.36
2.41
2.46
2.51
2.54
2.55
2.61
2.66
2.73
2.79
2.85
2.91
2.94
3.03
3.09

3TW01582-4
+3TW01122-2C

SYMBOLS
AFR:
BF:
EWB:
EDB:
ED*:
TC:
SHC:
PI:

NOTES

Air flow rate


Bypass factor
Entering wet bulb temp.
Entering dry bulb temp.
Dry bulb temperature
Total cooling capacity
Sensible heating capacity
Power input
(comp.+indoor+outdoor fan motor)

(m /min)
(CWB)
(CDB)
(CDB)
(kW)
(kW)
(kW)

Caution:
TC and SHC are shown by kW
V1(1): 230V
W1(1): 400V

16

Split - Sky Air Outdoor Units

1. Ratings shown are net capacities which include a deduction for indoor
fan motor heat
2.
Shows nominal capacities
3. SHC is based on each EWB and EDB
SHC* = SHC correction for other dry bulb
SHC* = 0.34 x 60 x AFR (m3/min) x (DB-EDB)/1000.
Add SHC* to SHC if SHC > TC, then TC equal SHC
4. Direct interpolation is permissible.
Do not extrapolate.
5. Capacities are based on the following conditions:
Corresponding refrigerant piping length:
7.5 m
Level difference:
0m

Pair Application R-22 RE18-40GA/R25-45DC/R60FA/R71-250F

Capacity tables

16

FHC3560 + R35DC7V11
R45DC7V11/W11
R60FA7V1/W1

Cooling capacity

Outdoor

35

45

60

Indoor
EWB
EDB
(C)
(C)
12.0
18.0
14.0
20.0
16.0
22.0
18.0
25.0
19.0
27.0
19.5
27.0
22.0
30.0
24.0
32.0
12.0
18.0
14.0
20.0
16.0
22.0
18.0
25.0
19.0
27.0
19.5
27.0
22.0
30.0
24.0
32.0
12.0
18.0
14.0
20.0
16.0
22.0
18.0
25.0
19.0
27.0
22.0
30.0
24.0
32.0

Model
AFR
BF

V11: 230V [50Hz]


W11: 400V [50Hz]

TC
3.83
4.04
4.24
4.45
4.55
4.61
4.86
5.08
4.60
4.97
5.32
5.69
5.87
5.95
6.43
6.82
5.98
6.32
6.67
7.04
7.23
7.82
8.22

20
SHC
2.73
2.76
2.81
2.86
2.88
2.89
2.94
2.98
3.42
3.49
3.56
3.63
3.67
3.69
3.77
3.84
4.05
4.11
4.18
4.24
4.26
4.35
4.41

PI
0.96
0.99
1.03
1.05
1.07
1.07
1.10
1.13
1.60
1.63
1.66
1.68
1.69
1.70
1.73
1.75
1.72
1.75
1.79
1.82
1.84
1.90
1.95

TC
3.62
3.83
4.05
4.26
4.36
4.40
4.57
4.88
4.45
4.79
5.14
5.50
5.67
5.76
6.21
6.58
5.78
6.12
6.46
6.82
7.01
7.58
7.97

25
SHC
2.63
2.67
2.72
2.76
2.79
2.80
2.84
2.89
3.33
3.41
3.48
3.55
3.58
3.59
3.69
3.75
3.97
4.03
4.09
4.16
4.19
4.27
4.33

PI
1.07
1.10
1.12
1.15
1.16
1.17
1.20
1.23
1.73
1.76
1.79
1.82
1.84
1.84
1.88
1.91
1.88
1.91
1.96
2.00
2.02
2.09
2.14

TC
3.35
3.56
3.76
3.97
4.07
4.13
4.39
4.60
4.19
4.52
4.85
5.18
5.35
5.43
5.85
6.19
5.49
5.81
6.14
6.48
6.66
7.21
7.59

Outdoor temperature (CDB)


32
35
SHC
PI
TC
SHC
2.50
1.20
3.22
2.44
2.55
1.23
3.43
2.49
2.59
1.26
3.65
2.54
2.63
1.29
3.85
2.57
2.65
1.30
3.90
2.59
2.66
1.31
4.06
2.60
2.72
1.34
4.27
2.66
2.75
1.37
4.47
2.71
3.20
1.92
4.07
3.15
3.27
1.96
4.39
3.22
3.34
2.00
4.71
3.29
3.42
2.04
5.04
3.36
3.46
2.05
5.20
3.41
3.48
2.06
5.29
3.42
3.56
2.11
5.69
3.51
3.63
2.14
6.02
3.58
3.87
2.13
5.36
3.82
3.93
2.17
5.67
3.88
3.99
2.22
5.99
3.94
4.05
2.27
6.33
4.00
4.08
2.29
6.50
4.03
4.18
2.37
7.03
4.13
4.24
2.43
7.40
4.19

PI
1.27
1.30
1.32
1.35
1.36
1.37
1.40
1.43
2.01
2.05
2.09
2.13
2.15
2.16
2.21
2.25
2.24
2.29
2.34
2.40
2.42
2.51
2.56

TC
3.03
3.23
3.44
3.65
3.75
3.81
4.07
4.28
3.86
4.17
4.48
4.78
4.93
5.02
5.40
5.71
5.13
5.43
5.74
6.06
6.22
6.73
7.08

35
14
0.16
40
SHC
2.35
2.40
2.44
2.48
2.50
2.51
2.57
2.60
3.06
3.13
3.20
3.27
3.31
3.33
3.42
3.49
3.76
3.81
3.87
3.93
3.96
4.05
4.11

PI
1.36
1.39
1.42
1.44
1.46
1.46
1.50
1.53
2.16
2.21
2.25
2.30
2.32
2.33
2.39
2.43
2.44
2.51
2.56
2.62
2.65
2.74
2.80

FHC..B
45
15
0.12

TC
2.79
2.99
3.20
3.41
3.51
3.57
3.83
4.04
3.58
3.87
4.16
4.45
4.59
4.66
5.03
5.31
4.84
5.12
5.41
5.71
5.86
6.34
5.69

60
18.0
0.10
46
SHC
2.24
2.28
2.33
2.36
2.39
2.39
2.45
2.50
2.96
3.03
3.10
3.17
3.20
3.22
3.31
3.39
3.66
3.73
3.79
3.84
3.87
3.96
4.02

PI
1.49
1.51
1.54
1.57
1.58
1.59
1.62
1.64
2.36
2.41
2.46
2.51
2.54
2.55
2.61
2.66
2.73
2.79
2.85
2.91
2.94
3.03
3.09

3TW01582-3
+3TW01122-2C

SYMBOLS
AFR:
BF:
EWB:
EDB:
ED*:
TC:
SHC:
PI:

NOTES

Air flow rate


Bypass factor
Entering wet bulb temp.
Entering dry bulb temp.
Dry bulb temperature
Total cooling capacity
Sensible heating capacity
Power input
(comp.+indoor+outdoor fan motor)

(m /min)
(CWB)
(CDB)
(CDB)
(kW)
(kW)
(kW)

Caution:
TC and SHC are shown by kW
V1(1): 230V
W1(1): 400V

Split - Sky Air Outdoor Units

1. Ratings shown are net capacities which include a deduction for indoor
fan motor heat
2.
Shows nominal capacities
3. SHC is based on each EWB and EDB
SHC* = SHC correction for other dry bulb
SHC* = 0.34 x 60 x AFR (m3/min) x (DB-EDB)/1000.
Add SHC* to SHC if SHC > TC, then TC equal SHC
4. Direct interpolation is permissible.
Do not extrapolate.
5. Capacities are based on the following conditions:
Corresponding refrigerant piping length:
7.5 m
Level difference:
0m

17

Pair Application R-22 RE18-40GA/R25-45DC/R60FA/R71-250F

16
3

Capacity tables

FHB35-60 + R35DC7V11
R45DC7V11/W11
R60FA7V1/W1
Cooling capacity

Outdoor

35

45

60

Indoor
EWB
EDB
(C)
(C)
12.0
18.0
14.0
20.0
16.0
22.0
18.0
25.0
19.0
27.0
19.5
27.0
22.0
30.0
24.0
32.0
12.0
18.0
14.0
20.0
16.0
22.0
18.0
25.0
19.0
27.0
19.5
27.0
22.0
30.0
24.0
32.0
12.0
18.0
14.0
20.0
16.0
22.0
18.0
25.0
19.0
27.0
22.0
30.0
24.0
32.0

230V [50Hz]

TC
3.88
4.09
4.30
4.51
4.61
4.67
4.93
5.15
4.69
5.06
5.42
5.80
5.99
6.07
6.56
6.95
5.98
6.32
6.67
7.04
7.23
7.82
8.22

20
SHC
2.77
2.80
2.85
2.89
2.92
2.93
2.97
3.02
3.48
3.55
3.63
3.70
3.74
3.76
3.85
3.92
4.05
4.11
4.18
4.24
4.26
4.35
4.41

PI
0.96
0.99
1.03
1.05
1.07
1.07
1.10
1.13
1.62
1.64
1.67
1.69
1.70
1.71
1.74
1.76
1.72
1.75
1.79
1.82
1.84
1.90
1.95

TC
3.67
3.88
4.10
4.31
4.41
4.46
4.73
4.94
4.53
4.88
5.24
5.60
5.78
5.87
6.33
6.70
5.78
6.12
6.46
6.82
7.01
7.58
7.97

25
SHC
2.66
2.71
2.75
2.80
2.82
2.83
2.88
2.93
3.40
3.47
3.54
3.62
3.65
3.66
3.76
3.82
3.97
4.03
4.09
4.16
4.19
4.27
4.33

PI
1.07
1.10
1.12
1.15
1.16
1.17
1.20
1.23
1.74
1.77
1.80
1.83
1.85
1.85
1.89
1.93
1.88
1.91
1.96
2.00
2.02
2.09
2.14

TC
3.39
3.60
3.81
4.02
4.12
4.18
4.46
4.66
4.27
4.60
4.95
5.28
5.46
5.54
5.97
6.31
5.49
5.81
6.14
6.48
6.66
7.21
7.59

Outdoor temperature (CDB)


32
35
SHC
PI
TC
SHC
2.53
1.20
3.26
2.47
2.58
1.23
3.47
2.52
2.63
1.26
3.69
2.57
2.66
1.29
3.90
2.60
2.68
1.30
3.95
2.63
2.70
1.31
4.11
2.64
2.75
1.34
4.32
2.70
2.79
1.37
4.53
2.74
3.26
1.94
4.15
3.21
3.34
1.98
4.48
3.28
3.41
2.02
4.80
3.36
3.48
2.06
5.13
3.43
3.52
2.07
5.30
3.47
3.54
2.08
5.39
3.48
3.63
2.13
5.80
3.57
3.70
2.16
6.13
3.65
3.87
2.13
5.36
3.82
3.93
2.17
5.67
3.88
3.99
2.22
5.99
3.94
4.05
2.27
6.33
4.00
4.08
2.29
6.50
4.03
4.18
2.37
7.03
4.13
4.24
2.43
7.40
4.19

PI
1.27
1.30
1.32
1.35
1.36
1.37
1.40
1.43
2.03
2.07
2.11
2.15
2.17
2.18
2.23
2.27
2.24
2.29
2.34
2.40
2.42
2.51
2.56

TC
3.07
3.28
3.49
3.69
3.80
3.86
4.12
4.33
3.94
4.25
4.56
4.87
5.03
5.11
5.51
5.82
5.13
5.43
5.74
6.06
6.22
6.73
7.08

40
SHC
2.38
2.43
2.47
2.51
2.53
2.54
2.60
2.64
3.12
3.19
3.26
3.34
3.38
3.40
3.48
3.55
3.76
3.81
3.87
3.93
3.96
4.05
4.11

PI
1.36
1.39
1.42
1.44
1.46
1.46
1.50
1.53
2.18
2.23
2.27
2.32
2.34
2.35
2.41
2.46
2.44
2.51
2.56
2.62
2.65
2.74
2.80

TC
2.82
3.03
3.24
3.45
3.56
3.61
3.88
4.09
3.65
3.95
4.24
4.53
4.68
4.75
5.12
5.41
4.84
5.12
5.41
5.71
5.86
6.34
5.69

46
SHC
2.27
2.31
2.36
2.39
2.42
2.42
2.49
2.53
3.01
3.09
3.16
3.23
3.26
3.28
3.38
3.45
3.66
3.73
3.79
3.84
3.87
3.96
4.02

PI
1.49
1.51
1.54
1.57
1.58
1.59
1.62
1.64
2.38
2.43
2.49
2.54
2.57
2.58
2.64
2.69
2.73
2.79
2.85
2.91
2.94
3.03
3.09

3TW00032-4
+3TW01122-2C

6. Air flow rate and BF are tabulated below.

SYMBOLS
AFR:
BF:
EWB:
EDB:
TC:
SHC:
PI:

Air flow rate


Bypass factor
Entering wet bulb temp.
Entering dry bulb temp.
Total cooling capacity
Sensible heating capacity
Power input
(comp.+indoor+outdoor fan motor)

(m3/min)
(CWB)
(CDB)
(kW)
(kW)
(kW)

Caution:
TC and SHC are shown by kW
V1(1): 230V
W1(1): 400V

NOTES
1. Ratings shown are net capacities which include a deduction for indoor
fan motor heat
2.
Shows nominal capacities
3. SHC is based on each EWB and EDB
SHC* = SHC correction for other dry bulb
SHC* = 0.34 x 60 x AFR (m3/min) x (DB-EDB)/1000.
Add SHC* to SHC if SHC > TC, then TC equal SHC
4. Direct interpolation is permissible.
Do not extrapolate.
5. Capacities are based on the following conditions:
Corresponding refrigerant piping length:
7.5 m
Level difference:
0m

18

Split - Sky Air Outdoor Units

Model
35
45
60

AFR
BF
AFR
BF
AFR
BF

FHB
11.5
0.15
14
0.16
17
0.10

Pair Application R-22 RE18-40GA/R25-45DC/R60FA/R71-250F

Capacity tables

16

FHK3560FJV1 + R35DC7V11
R45DC7V11/W11
R60FA7V1/W1

Cooling capacity

Outdoor

35

45

60

Indoor
EWB
EDB
(C)
(C)
12.0
18.0
14.0
20.0
16.0
22.0
18.0
25.0
19.0
27.0
19.5
27.0
22.0
30.0
24.0
32.0
12.0
18.0
14.0
20.0
16.0
22.0
18.0
25.0
19.0
27.0
19.5
27.0
22.0
30.0
24.0
32.0
12.0
18.0
14.0
20.0
16.0
22.0
18.0
25.0
19.0
27.0
22.0
30.0
24.0
32.0

230V [50Hz]

TC
3.98
4.19
4.41
4.62
4.73
4.79
5.05
5.28
4.73
5.11
5.48
5.85
6.04
6.13
6.62
7.02
5.98
6.32
6.67
7.04
7.23
7.82
8.22

20
SHC
2.84
2.87
2.92
2.97
2.99
3.00
3.05
3.10
3.51
3.59
3.66
3.73
3.78
3.80
3.88
3.95
4.05
4.11
4.18
4.24
4.26
4.35
4.41

PI
0.91
0.94
0.96
0.98
1.00
1.00
1.03
1.06
1.58
1.59
1.62
1.64
1.65
1.66
1.69
1.71
1.72
1.75
1.79
1.82
1.84
1.90
1.95

TC
3.76
3.98
4.20
4.42
4.53
4.57
4.85
5.06
4.57
4.93
5.29
5.65
5.83
5.93
6.39
6.77
5.78
6.12
6.46
6.82
7.01
7.58
7.97

25
SHC
2.73
2.78
2.82
2.87
2.89
2.91
2.95
3.00
3.43
3.50
3.58
3.65
3.68
3.69
3.80
3.86
3.97
4.03
4.09
4.16
4.19
4.27
4.33

PI
1.00
1.03
1.05
1.08
1.09
1.10
1.13
1.16
1.69
1.72
1.75
1.78
1.80
1.80
1.84
1.87
1.88
1.91
1.96
2.00
2.02
2.09
2.14

TC
3.48
3.69
3.91
4.12
4.23
4.29
4.56
4.78
4.31
4.65
4.99
5.33
5.51
5.59
6.02
6.37
5.49
5.81
6.14
6.48
6.66
7.21
7.59

Outdoor temperature (CDB)


32
35
SHC
PI
TC
SHC
2.60
1.13
3.35
2.54
2.64
1.16
3.56
2.58
2.69
1.18
3.79
2.63
2.73
1.21
4.00
2.67
2.75
1.22
4.05
2.69
2.76
1.23
4.22
2.70
2.82
1.26
4.43
2.76
2.86
1.29
4.65
2.81
3.29
1.88
4.19
3.24
3.27
1.92
4.52
3.31
3.44
1.96
4.85
3.39
3.51
2.00
5.18
3.46
3.56
2.01
5.35
3.50
3.58
2.02
5.44
3.51
3.66
2.07
5.85
3.61
3.73
2.10
6.19
3.68
3.87
2.13
5.36
3.82
3.93
2.17
5.67
3.88
3.99
2.22
5.99
3.94
4.05
2.27
6.33
4.00
4.08
2.29
6.50
4.03
4.18
2.37
7.03
4.13
4.24
2.43
7.40
4.19

PI
1.19
1.22
1.24
1.27
1.28
1.29
1.32
1.35
1.97
2.01
2.05
2.09
2.11
2.12
2.17
2.21
2.24
2.29
2.34
2.40
2.42
2.51
2.56

TC
3.14
3.36
3.57
3.79
3.90
3.95
4.23
4.44
3.98
4.29
4.61
4.92
5.08
5.16
5.56
5.87
5.13
5.43
5.74
6.06
6.22
6.73
7.08

40
SHC
2.44
2.49
2.54
2.57
2.60
2.61
2.67
2.70
3.15
3.22
3.29
3.37
3.41
3.43
3.51
3.59
3.76
3.81
3.87
3.93
3.96
4.05
4.11

PI
1.28
1.31
1.34
1.36
1.38
1.38
1.41
1.44
2.12
2.17
2.21
2.26
2.28
2.29
2.35
2.39
2.44
2.51
2.56
2.62
2.65
2.74
2.80

TC
2.89
3.11
3.32
3.54
3.65
3.70
3.98
4.19
3.68
3.99
4.28
4.57
4.72
4.79
5.17
5.47
4.84
5.12
5.41
5.71
5.86
6.34
5.69

46
SHC
2.32
2.37
2.42
2.45
2.48
2.48
2.55
2.60
3.04
3.12
3.19
3.26
3.29
3.31
3.41
3.48
3.66
3.73
3.79
3.84
3.87
3.96
4.02

PI
1.40
1.42
1.45
1.48
1.49
1.50
1.53
1.55
2.32
2.37
2.42
2.47
2.50
2.51
2.57
2.62
2.73
2.79
2.85
2.91
2.94
3.03
3.09

3TW00032-5
3TW01122-2C

6. Air flow rate and BF are tabulated below.

SYMBOLS
AFR:
BF:
EWB:
EDB:
TC:
SHC:
PI:

Air flow rate


Bypass factor
Entering wet bulb temp.
Entering dry bulb temp.
Total cooling capacity
Sensible heating capacity
Power input
(comp.+indoor+outdoor fan motor)

(m3/min)
(CWB)
(CDB)
(kW)
(kW)
(kW)

Model
35
45
60

AFR
BF
AFR
BF
AFR
BF

FHK
12
0.16
12
0.18
17
0.10

Caution:
TC and SHC are shown by kW
V1(1): 230V
W1(1): 400V

NOTES
1. Ratings shown are net capacities which include a deduction for indoor
fan motor heat
2.
Shows nominal capacities
3. SHC is based on each EWB and EDB
SHC* = SHC correction for other dry bulb
SHC* = 0.34 x 60 x AFR (m3/min) x (DB-EDB)/1000.
Add SHC* to SHC if SHC > TC, then TC equal SHC
4. Direct interpolation is permissible.
Do not extrapolate.
5. Capacities are based on the following conditions:
Corresponding refrigerant piping length:
7.5 m
Level difference:
0m

Split - Sky Air Outdoor Units

19

Pair Application R-22 RE18-40GA/R25-45DC/R60FA/R71-250F

16
3

Capacity tables

FHYK71FJV1 + R71B7V1
R71B7W1
Cooling capacity

Outdoor

71

Indoor
EWB
EDB
(C)
(C)
12.0
18.0
14.0
20.0
16.0
22.0
18.0
25.0
19.0
27.0
19.5
27.0
22.0
30.0
24.0
32.0

230V [50Hz]

TC
6.4
6.8
7.3
7.8
8.1
8.2
8.8
9.5

20
SHC
5.0
5.0
5.1
5.3
5.3
5.3
5.4
5.4

PI
2.0
2.1
2.1
2.1
2.1
2.1
2.1
2.2

TC
6.3
6.7
7.1
7.6
7.8
8.0
8.6
9.1

25
SHC
4.9
4.9
5.0
5.1
5.1
5.1
5.3
5.3

PI
2.1
2.2
2.2
2.3
2.3
2.3
2.4
2.4

TC
6.1
6.4
6.8
7.3
7.5
7.6
8.3
8.8

Outdoor temperature (CDB)


32
35
SHC
PI
TC
SHC
4.8
2.4
6.0
4.7
4.8
2.5
6.3
4.7
4.9
2.5
6.7
4.8
5.0
2.6
7.1
4.9
5.0
2.6
7.4
4.9
5.0
2.6
7.5
4.9
5.1
2.7
8.1
5.0
5.1
2.8
8.4
5.0

PI
2.6
2.6
2.7
2.8
2.8
2.8
2.9
2.9

TC
5.7
6.1
6.5
6.8
7.0
7.1
7.7
8.2

40
SHC
4.7
4.7
4.7
4.7
4.8
4.8
4.9
4.9

PI
2.9
2.9
3.0
3.1
3.1
3.1
3.2
3.3

TC
5.4
5.7
6.1
6.5
6.7
6.8
7.3
7.7

46
SHC
4.4
4.4
4.6
4.7
4.7
4.7
4.7
4.7

PI
3.3
3.3
3.4
3.4
3.5
3.5
3.5
3.5

3TW20332-4B

6. Air flow rate and BF are tabulated below.

SYMBOLS
AFR:
BF:
EWB:
EDB:
TC:
SHC:
PI:

Air flow rate


Bypass factor
Entering wet bulb temp.
Entering dry bulb temp.
Total cooling capacity
Sensible heating capacity
Power input
(comp.+indoor+outdoor fan motor)

(m3/min)
(CWB)
(CDB)
(kW)
(kW)
(kW)

Caution:
TC and SHC are shown by kW
V1: 230V
W1: 400V

71

1. Ratings shown are net capacities which include a deduction for indoor
fan motor heat
2.
Shows nominal capacities
3. SHC is based on each EWB and EDB
SHC* = SHC correction for other dry bulb
SHC* = 0.34 x 60 x AFR (m3/min) x (DB-EDB)/1000.
Add SHC* to SHC if SHC > TC, then TC equal SHC
4. Direct interpolation is permissible.
Do not extrapolate.
5. Capacities are based on the following conditions:
Corresponding refrigerant piping length:
7.5 m
Level difference:
0m

Split - Sky Air Outdoor Units

AFR
BF

FHYK
19
0.07

7. Add the following correction value to power input (kW) of each unit

Model
71

NOTES

20

Model

Supply
V1
W1

FHYK
0.2
0.0

Pair Application R-22 RE18-40GA/R25-45DC/R60FA/R71-250F

Capacity tables

16

FHYC71125 + R71100B7V1
R71125B7W1

Cooling capacity

Outdoor

71

100

125

Indoor
EWB
EDB
(C)
(C)
12.0
18.0
14.0
20.0
16.0
22.0
18.0
25.0
19.0
27.0
19.5
27.0
22.0
30.0
24.0
32.0
12.0
18.0
14.0
20.0
16.0
22.0
18.0
25.0
19.0
27.0
19.5
27.0
22.0
30.0
24.0
32.0
12.0
18.0
14.0
20.0
16.0
22.0
18.0
25.0
19.0
27.0
19.5
27.0
22.0
30.0
24.0
32.0

230V [50Hz]

TC
6.3
6.7
7.2
7.7
8.0
8.1
8.7
9.4
8.9
9.5
10.2
10.9
11.2
11.3
12.2
13.0
11.0
11.7
12.5
13.3
13.6
13.8
15.0
15.9

20
SHC
4.9
4.9
5.0
5.2
5.2
5.2
5.3
5.3
7.2
7.2
7.4
7.5
7.6
7.6
7.7
7.8
9.1
9.1
9.2
9.5
9.6
9.7
9.8
9.9

PI
2.0
2.1
2.1
2.1
2.1
2.1
2.1
2.2
2.5
2.6
2.6
2.6
2.6
2.6
2.7
2.7
3.3
3.4
3.4
3.5
3.5
3.5
3.6
3.7

TC
6.2
6.6
7.0
7.5
7.7
7.9
8.5
9.0
8.7
9.4
9.9
10.6
11.0
11.1
11.9
12.6
10.8
11.4
12.2
13.0
13.3
13.5
14.6
15.4

25
SHC
4.8
4.8
4.9
5.0
5.0
5.0
5.2
5.2
7.1
7.1
7.2
7.4
7.5
7.5
7.6
7.7
8.8
8.8
8.9
9.1
9.2
9.2
9.4
9.5

PI
2.1
2.2
2.2
2.3
2.3
2.3
2.4
2.4
2.7
2.7
2.8
2.8
2.9
2.9
3.0
3.0
3.6
3.6
3.7
3.8
3.8
3.8
3.9
4.0

TC
6.0
6.3
6.7
7.2
7.4
7.5
8.2
8.7
8.3
8.8
9.5
10.0
10.3
10.5
11.3
12.0
10.2
10.9
11.6
12.3
12.8
12.9
13.8
14.6

Outdoor temperature (CDB)


32
35
SHC
PI
TC
SHC
4.7
2.4
5.9
4.6
4.7
2.5
6.2
4.6
4.8
2.5
6.6
4.7
4.9
2.6
7.0
4.8
4.9
2.6
7.3
4.8
4.9
2.6
7.4
4.8
5.0
2.7
8.0
4.9
5.0
2.8
8.3
4.9
6.9
3.1
8.1
6.8
6.9
3.1
8.7
6.8
7.0
3.1
9.2
6.9
7.1
3.1
9.8
7.0
7.2
3.2
10.2
7.1
7.2
3.2
10.3
7.1
7.4
3.3
11.1
7.2
7.5
3.4
11.8
7.4
8.5
4.0
9.8
8.4
8.5
4.1
10.5
8.4
8.6
4.2
11.1
8.5
8.8
4.2
11.9
8.7
8.9
4.3
12.3
8.7
8.9
4.4
12.5
8.8
9.1
4.4
13.5
9.0
9.2
4.5
14.3
9.1

PI
2.6
2.6
2.7
2.8
2.8
2.8
2.9
2.9
3.2
3.2
3.3
3.3
3.4
3.4
3.5
3.6
4.3
4.3
4.4
4.4
4.5
4.5
4.6
4.7

TC
5.6
6.0
6.4
6.7
6.9
7.0
7.6
8.1
7.7
8.3
8.8
9.3
9.7
9.8
10.6
11.2
9.5
10.2
10.8
11.4
11.7
11.9
12.9
13.6

40
SHC
4.6
4.6
4.6
4.6
4.7
4.7
4.8
4.8
6.5
6.5
6.7
6.9
6.9
6.9
7.1
7.1
8.2
8.2
8.3
8.5
8.6
8.6
8.7
8.9

PI
2.9
2.9
3.0
3.1
3.1
3.1
3.2
3.3
3.5
3.6
3.6
3.7
3.7
3.7
3.8
3.8
4.6
4.7
4.7
4.8
4.9
4.9
5.0
5.1

TC
5.3
5.6
6.0
6.4
6.6
6.7
7.2
7.6
7.2
7.8
8.3
8.8
9.1
9.2
9.9
10.4
8.7
9.4
9.9
10.8
11.1
11.1
12.1
12.5

46
SHC
4.3
4.3
4.5
4.6
4.6
4.6
4.6
4.6
6.3
6.3
6.4
6.5
6.7
6.7
6.9
6.9
7.8
7.8
8.0
8.2
8.3
8.3
8.5
8.5

PI
3.3
3.3
3.4
3.4
3.5
3.5
3.5
3.5
3.7
3.7
3.8
3.8
3.9
3.9
4.0
4.1
5.1
5.2
5.2
5.3
5.4
5.4
5.5
5.6

3TW20332-1B

6. Air flow rate and BF are tabulated below.

SYMBOLS
AFR:
BF:
EWB:
EDB:
TC:
SHC:
PI:

Air flow rate


Bypass factor
Entering wet bulb temp.
Entering dry bulb temp.
Total cooling capacity
Sensible heating capacity
Power input
(comp.+indoor+outdoor fan motor)

(m3/min)
(CWB)
(CDB)
(kW)
(kW)
(kW)

Caution:
TC and SHC are shown by kW
V1: 230V
W1: 400V

Model
71
100
125

AFR
BF
AFR
BF
AFR
BF

FHYC
18
0.10
28
0.16
31
0.07

7. Add the following correction value to power input (kW) of each unit

Model

NOTES

71

1. Ratings shown are net capacities which include a deduction for indoor
fan motor heat
2.
Shows nominal capacities
3. SHC is based on each EWB and EDB
SHC* = SHC correction for other dry bulb
SHC* = 0.34 x 60 x AFR (m3/min) x (DB-EDB)/1000.
Add SHC* to SHC if SHC > TC, then TC equal SHC
4. Direct interpolation is permissible.
Do not extrapolate.
5. Capacities are based on the following conditions:
Corresponding refrigerant piping length:
7.5 m
Level difference:
0m

Split - Sky Air Outdoor Units

100
125

Supply
V1
W1
V1
W1
W1

FHYC
0.2
0.0
0.3
0.0
0.0

21

Pair Application R-22 RE18-40GA/R25-45DC/R60FA/R71-250F

16
3

Capacity tables

FHY71125BJV1 + R71100B7V1
R71125B7W1
Cooling capacity

Outdoor

71

100

125

Indoor
EWB
EDB
(C)
(C)
12.0
18.0
14.0
20.0
16.0
22.0
18.0
25.0
19.0
27.0
19.5
27.0
22.0
30.0
24.0
32.0
12.0
18.0
14.0
20.0
16.0
22.0
18.0
25.0
19.0
27.0
19.5
27.0
22.0
30.0
24.0
32.0
12.0
18.0
14.0
20.0
16.0
22.0
18.0
25.0
19.0
27.0
19.5
27.0
22.0
30.0
24.0
32.0

230V [50Hz]

TC
6.3
6.8
7.3
7.8
8.1
8.2
8.8
9.5
9.0
9.6
10.3
11.0
11.3
11.4
12.4
13.1
11.0
11.8
12.6
13.4
13.8
14.0
15.1
16.0

20
SHC
5.0
5.0
5.1
5.3
5.3
5.3
5.4
5.4
7.3
7.3
7.5
7.6
7.7
7.7
7.7
7.8
9.2
9.2
9.3
9.6
9.7
9.8
9.9
10.0

PI
2.0
2.1
2.1
2.1
2.1
2.1
2.1
2.2
2.5
2.6
2.6
2.6
2.6
2.6
2.7
2.7
3.3
3.4
3.4
3.5
3.5
3.5
3.6
3.7

TC
6.2
6.7
7.1
7.6
7.8
8.0
8.6
9.1
8.8
9.5
10.0
10.7
11.1
11.2
12.0
12.8
10.9
11.5
12.3
13.1
13.4
13.7
14.7
15.5

25
SHC
4.9
4.9
5.0
5.1
5.1
5.1
5.3
5.3
7.2
7.2
7.3
7.5
7.6
7.6
7.7
7.7
8.9
8.9
9.0
9.2
9.3
9.3
9.5
9.6

PI
2.1
2.2
2.2
2.3
2.3
2.3
2.4
2.4
2.7
2.7
2.8
2.8
2.9
2.9
3.0
3.0
3.6
3.6
3.7
3.8
3.8
3.8
3.9
4.0

TC
6.1
6.3
6.8
7.3
7.5
7.6
8.3
8.8
8.3
8.9
9.6
10.1
10.4
10.6
11.4
12.2
10.3
10.9
11.7
12.4
12.9
13.0
14.0
14.7

Outdoor temperature (CDB)


32
35
SHC
PI
TC
SHC
4.8
2.4
6.0
4.7
4.8
2.5
6.2
4.7
4.9
2.5
6.7
4.8
5.0
2.6
7.1
4.9
5.0
2.6
7.4
4.9
5.0
2.6
7.5
4.9
5.1
2.7
8.1
5.0
5.1
2.8
8.5
5.0
7.0
3.1
8.1
6.9
7.0
3.1
8.8
6.9
7.1
3.1
9.3
7.0
7.2
3.1
9.9
7.1
7.3
3.2
10.3
7.2
7.3
3.2
10.4
7.2
7.5
3.3
11.2
7.3
7.6
3.4
11.9
7.5
8.5
4.0
9.9
8.4
8.5
4.1
10.6
8.4
8.7
4.2
11.2
8.5
8.9
4.2
12.0
8.8
9.0
4.3
12.4
8.8
9.0
4.4
12.6
8.9
9.2
4.4
13.7
9.1
9.3
4.5
14.4
9.2

PI
2.6
2.6
2.7
2.8
2.8
2.8
2.9
2.9
3.2
3.2
3.3
3.3
3.4
3.4
3.5
3.6
4.3
4.3
4.4
4.4
4.5
4.5
4.6
4.7

TC
5.7
6.1
6.4
6.8
7.0
7.1
7.7
8.2
7.7
8.3
8.9
9.4
9.8
9.9
10.7
11.3
9.6
10.3
10.9
11.5
11.8
12.0
13.0
13.8

40
SHC
4.6
4.6
4.7
4.7
4.8
4.8
4.9
4.9
6.6
6.6
6.8
7.0
7.0
7.0
7.2
7.2
8.2
8.2
8.3
8.5
8.7
8.7
8.8
9.0

PI
2.9
2.9
3.0
3.1
3.1
3.1
3.2
3.3
3.5
3.6
3.6
3.7
3.7
3.7
3.8
3.8
4.6
4.7
4.7
4.8
4.9
4.9
5.0
5.1

TC
5.4
5.7
6.1
6.4
6.7
6.8
7.3
7.7
7.3
7.8
8.3
8.9
9.2
9.3
10.0
10.5
8.8
9.5
10.0
10.9
11.1
11.2
12.2
12.6

46
SHC
4.3
4.3
4.5
4.6
4.6
4.6
4.7
4.7
6.4
6.4
6.5
6.6
6.8
6.8
7.0
7.0
7.8
7.8
8.0
8.2
8.3
8.3
8.5
8.5

PI
3.3
3.3
3.4
3.4
3.5
3.5
3.5
3.5
3.7
3.7
3.8
3.8
3.9
3.9
4.0
4.1
5.1
5.2
5.2
5.3
5.4
5.4
5.5
5.6

3TW20332-2A

6. Air flow rate and BF are tabulated below.

SYMBOLS
AFR:
BF:
EWB:
EDB:
ED*:
TC:
SHC:
PI:

Air flow rate


Bypass factor
Entering wet bulb temp.
Entering dry bulb temp.
Dry bulb temperature
Total cooling capacity
Sensible heating capacity
Power input
(comp.+indoor+outdoor fan motor)

(m3/min)
(CWB)
(CDB)
(CDB)
(kW)
(kW)
(kW)

Caution:
TC and SHC are shown by kW
V1: 230V
W1: 400V

71
100
125

AFR
BF
AFR
BF
AFR
BF

FHY
17
0.1
24
0.14
30
0.13

7. Add the following correction value to power input (kW) of each unit

Model
71

NOTES
1. Ratings shown are net capacities which include a deduction for indoor
fan motor heat
2.
Shows nominal capacities
3. SHC is based on each EWB and EDB
SHC* = SHC correction for other dry bulb
SHC* = 0.34 x 60 x AFR (m3/min) x (DB-EDB)/1000.
Add SHC* to SHC if SHC > TC, then TC equal SHC
4. Direct interpolation is permissible.
Do not extrapolate.
5. Capacities are based on the following conditions:
Corresponding refrigerant piping length:
7.5 m
Level difference:
0m

22

Model

Split - Sky Air Outdoor Units

100
125

Supply
V1
W1
V1
W1
W1

FHY
0.1
0
0.2
0
0

Pair Application R-22 RE18-40GA/R25-45DC/R60FA/R71-250F

Capacity tables

16

FHYB71125FK7V1 + R71100B7V1
R71125B7W1

Cooling capacity

Outdoor

71

100

125

Indoor
EWB
EDB
(C)
(C)
12.0
18.0
14.0
20.0
16.0
22.0
18.0
25.0
19.0
27.0
19.5
27.0
22.0
30.0
24.0
32.0
12.0
18.0
14.0
20.0
16.0
22.0
18.0
25.0
19.0
27.0
19.5
27.0
22.0
30.0
24.0
32.0
12.0
18.0
14.0
20.0
16.0
22.0
18.0
25.0
19.0
27.0
19.5
27.0
22.0
30.0
24.0
32.0

230V [50Hz]

TC
6.2
6.6
7.1
7.6
7.9
7.9
8.6
9.3
9.2
9.8
10.5
11.2
11.5
11.6
12.6
13.4
11.0
11.8
12.6
13.4
13.8
14.0
15.1
16.0

20
SHC
4.9
4.9
5.0
5.1
5.1
5.1
5.2
5.2
7.4
7.4
7.6
7.7
7.8
7.8
7.9
8.0
9.2
9.2
9.3
9.6
9.7
9.8
9.9
10.0

PI
2.0
2.1
2.1
2.1
2.2
2.2
2.2
2.3
2.5
2.6
2.6
2.7
2.7
2.7
2.8
2.8
3.3
3.5
3.5
3.6
3.6
3.6
3.7
3.8

TC
6.1
6.5
6.9
7.4
7.6
7.8
8.4
8.9
9.0
9.7
10.2
10.9
11.3
11.4
12.2
13.0
10.9
11.5
12.3
13.1
13.4
13.7
14.7
15.5

25
SHC
4.8
4.8
4.9
5.0
5.0
5.0
5.1
5.1
7.3
7.3
7.4
7.6
7.7
7.7
7.8
7.9
8.9
8.9
9.0
9.2
9.3
9.3
9.5
9.6

PI
2.2
2.3
2.3
2.4
2.4
2.4
2.5
2.5
2.8
2.8
2.9
2.9
3.0
3.0
3.1
3.1
3.7
3.7
3.8
3.9
3.9
3.9
4.0
4.1

TC
5.9
6.2
6.6
7.1
7.3
7.4
8.0
8.6
8.5
9.1
9.8
10.3
10.6
10.8
11.6
12.4
10.3
10.9
11.7
12.4
12.9
13.0
14.0
14.7

Outdoor temperature (CDB)


32
35
SHC
PI
TC
SHC
4.7
2.5
5.8
4.6
4.7
2.6
6.1
4.6
4.8
2.6
6.5
4.7
4.9
2.7
6.9
4.8
4.9
2.7
7.2
4.8
4.9
2.7
7.3
4.8
5.0
2.8
7.9
4.9
5.0
2.9
8.2
4.9
7.1
3.2
8.3
7.0
7.1
3.2
9.0
7.0
7.2
3.2
9.5
7.1
7.3
3.2
10.1
7.2
7.4
3.3
10.5
7.3
7.4
3.3
10.6
7.3
7.6
3.4
11.4
7.4
7.7
3.5
12.1
7.6
8.5
4.1
9.9
8.4
8.5
4.2
10.6
8.4
8.7
4.3
11.2
8.5
8.9
4.3
12.0
8.8
9.0
4.4
12.4
8.8
9.0
4.5
12.6
8.9
9.2
4.5
13.7
9.1
9.3
4.6
14.4
9.2

PI
2.7
2.7
2.8
2.9
2.9
2.9
3.0
3.0
3.3
3.3
3.4
3.4
3.5
3.5
3.6
3.7
4.4
4.4
4.5
4.5
4.6
4.6
4.7
4.8

TC
5.5
5.9
6.3
6.6
6.8
6.9
7.5
7.9
7.9
8.5
9.1
9.6
10.0
10.1
10.9
11.5
9.6
10.3
10.9
11.5
11.8
12.0
13.0
13.8

40
SHC
4.5
4.5
4.6
4.6
4.7
4.7
4.8
4.8
6.7
6.7
6.9
7.1
7.1
7.1
7.3
7.3
8.2
8.2
8.3
8.5
8.7
8.7
8.8
9.0

PI
3.0
3.0
3.1
3.2
3.2
3.2
3.3
3.4
3.6
3.7
3.7
3.8
3.8
3.9
3.9
3.9
4.7
4.8
4.8
4.9
5.0
5.0
5.1
5.2

TC
5.2
5.5
5.9
6.3
6.5
6.6
7.1
7.5
7.4
8.0
8.5
9.1
9.4
9.5
10.2
10.7
8.8
9.5
10.0
10.9
11.1
11.2
12.2
12.6

46
SHC
4.2
4.2
4.4
4.5
4.5
4.5
4.6
4.6
6.5
6.5
6.6
6.7
6.9
6.9
7.1
7.1
7.8
7.8
8.0
8.2
8.3
8.3
8.5
8.5

PI
3.4
3.4
3.5
3.5
3.6
3.6
3.7
3.7
3.8
3.9
3.9
3.9
4.0
4.0
4.1
4.2
5.2
5.3
5.3
5.4
5.5
5.5
5.6
5.8

3TW20332-3B

6. Air flow rate and BF are tabulated below.

SYMBOLS
AFR:
BF:
EWB:
EDB:
TC:
SHC:
PI:

Air flow rate


Bypass factor
Entering wet bulb temp.
Entering dry bulb temp.
Total cooling capacity
Sensible heating capacity
Power input
(comp.+indoor+outdoor fan motor)

(m3/min)
(CWB)
(CDB)
(kW)
(kW)
(kW)

Caution:
TC and SHC are shown by kW
V1: 230V
W1: 400V

Model
71
100
125

AFR
BF
AFR
BF
AFR
BF

FHYB
19
0.11
27
0.20
35
0.14

7. Add the following correction value to power input (kW) of each unit

Model

NOTES

71

1. Ratings shown are net capacities which include a deduction for indoor
fan motor heat
2.
Shows nominal capacities
3. SHC is based on each EWB and EDB
SHC* = SHC correction for other dry bulb
SHC* = 0.34 x 60 x AFR (m3/min) x (DB-EDB)/1000.
Add SHC* to SHC if SHC > TC, then TC equal SHC
4. Direct interpolation is permissible.
Do not extrapolate.
5. Capacities are based on the following conditions:
Corresponding refrigerant piping length:
7.5 m
Level difference:
0m

Split - Sky Air Outdoor Units

100
125

Supply
V1
W1
V1
W1
W1

FHYB
0.2
0.0
0.3
0.0
0.0

23

Pair Application R-22 RE18-40GA/R25-45DC/R60FA/R71-250F

16
3

Capacity tables

FAY71100FJV1 + R71100B7V1
R71125B7W1
Cooling capacity

Outdoor

71

100

Indoor
EWB
EDB
(C)
(C)
12.0
18.0
14.0
20.0
16.0
22.0
18.0
25.0
19.0
27.0
19.5
27.0
22.0
30.0
24.0
32.0
12.0
18.0
14.0
20.0
16.0
22.0
18.0
25.0
19.0
27.0
19.5
27.0
22.0
30.0
24.0
32.0

230V [50Hz]

TC
6.4
6.8
7.3
7.8
8.1
8.2
8.8
9.5
8.6
9.2
9.9
10.6
10.9
11.0
11.8
12.6

20
SHC
5.0
5.0
5.1
5.3
5.3
5.3
5.4
5.4
7.2
7.2
7.4
7.5
7.6
7.6
7.7
7.8

PI
2.1
2.2
2.2
2.2
2.2
2.2
2.2
2.3
2.5
2.6
2.6
2.6
2.6
2.6
2.7
2.7

TC
6.3
6.7
7.1
7.6
7.8
8.0
8.6
9.1
8.4
9.1
9.6
10.3
10.7
10.8
11.6
12.2

25
SHC
4.9
4.9
5.0
5.1
5.1
5.1
5.3
5.3
7.1
7.1
7.2
7.4
7.5
7.5
7.6
7.7

PI
2.2
2.3
2.3
2.4
2.4
2.4
2.5
2.5
2.7
2.7
2.8
2.8
2.9
2.9
3.0
3.0

TC
6.1
6.4
6.8
7.3
7.5
7.6
8.3
8.8
8.1
8.5
9.2
9.7
10.0
10.2
11.0
11.6

Outdoor temperature (CDB)


32
35
SHC
PI
TC
SHC
4.8
2.5
6.0
4.7
4.8
2.6
6.3
4.7
4.9
2.6
6.7
4.8
5.0
2.7
7.1
4.9
5.0
2.7
7.4
4.9
5.0
2.7
7.5
4.9
5.1
2.8
8.1
5.0
5.1
2.9
8.4
5.0
6.9
3.1
7.9
6.8
6.9
3.1
8.4
6.8
7.0
3.1
8.9
6.9
7.1
3.1
9.5
7.0
7.2
3.2
9.9
7.1
7.2
3.2
10.0
7.1
7.4
3.3
10.8
7.2
7.5
3.4
11.5
7.4

PI
2.7
2.7
2.8
2.9
2.9
2.9
3.0
3.0
3.2
3.2
3.3
3.3
3.4
3.4
3.5
3.6

TC
5.7
6.1
6.5
6.8
7.0
7.1
7.7
8.2
7.5
8.1
8.5
9.0
9.4
9.5
10.3
10.9

40
SHC
4.7
4.7
4.7
4.7
4.8
4.8
4.9
4.9
6.5
6.5
6.7
6.9
6.9
6.9
7.1
7.1

PI
3.0
3.0
3.1
3.2
3.2
3.2
3.3
3.4
3.5
3.6
3.6
3.7
3.7
3.7
3.8
3.8

TC
5.4
5.7
6.1
6.5
6.7
6.8
7.3
7.7
7.0
7.6
8.1
8.5
8.8
8.9
9.6
10.1

46
SHC
4.4
4.4
4.6
4.7
4.7
4.7
4.7
4.7
6.3
6.3
6.4
6.5
6.7
6.7
6.9
6.9

PI
3.4
3.4
3.5
3.5
3.6
3.6
3.6
3.6
3.7
3.7
3.8
3.8
3.9
3.9
4.0
4.1

3TW20332-5B

6. Air flow rate and BF are tabulated below.

SYMBOLS
AFR:
BF:
EWB:
EDB:
TC:
SHC:
PI:

Air flow rate


Bypass factor
Entering wet bulb temp.
Entering dry bulb temp.
Total cooling capacity
Sensible heating capacity
Power input
(comp.+indoor+outdoor fan motor)

(m3/min)
(CWB)
(CDB)
(kW)
(kW)
(kW)

Caution:
TC and SHC are shown by kW
V1: 230V
W1: 400V

71
100

71
100

1. Ratings shown are net capacities which include a deduction for indoor
fan motor heat
2.
Shows nominal capacities
3. SHC is based on each EWB and EDB
SHC* = SHC correction for other dry bulb
SHC* = 0.34 x 60 x AFR (m3/min) x (DB-EDB)/1000.
Add SHC* to SHC if SHC > TC, then TC equal SHC
4. Direct interpolation is permissible.
Do not extrapolate.
5. Capacities are based on the following conditions:
Corresponding refrigerant piping length:
7.5 m
Level difference:
0m

Split - Sky Air Outdoor Units

AFR
BF
AFR
BF

FAY
27
0.1
27
0

7. Add the following correction value to power input (kW) of each unit

Model

NOTES

24

Model

Supply
V1
W1
V1
W1

FAY
0.2
0
0.3
0

Pair Application R-22 RE18-40GA/R25-45DC/R60FA/R71-250F

Capacity tables

16

FUY71125FJV1 + R71100B7V1
R71125B7W1

Cooling capacity

Outdoor

71

100

125

Indoor
EWB
EDB
(C)
(C)
12.0
18.0
14.0
20.0
16.0
22.0
18.0
25.0
19.0
27.0
19.5
27.0
22.0
30.0
24.0
32.0
12.0
18.0
14.0
20.0
16.0
22.0
18.0
25.0
19.0
27.0
19.5
27.0
22.0
30.0
24.0
32.0
12.0
18.0
14.0
20.0
16.0
22.0
18.0
25.0
19.0
27.0
19.5
27.0
22.0
30.0
24.0
32.0

230V [50Hz]

TC
6.3
6.7
7.2
7.7
8.0
8.1
8.7
9.4
8.6
9.2
9.9
10.6
10.9
11.0
11.8
12.6
11.0
11.7
12.5
13.3
13.6
13.8
15.0
15.9

20
SHC
4.9
4.9
5.0
5.2
5.2
5.2
5.3
5.3
7.2
7.2
7.4
7.5
7.6
7.6
7.7
7.8
9.1
9.1
9.2
9.5
9.6
9.7
9.8
9.9

PI
2.1
2.2
2.2
2.2
2.2
2.2
2.2
2.3
2.5
2.6
2.6
2.6
2.6
2.6
2.7
2.7
3.3
3.4
3.4
3.5
3.5
3.5
3.6
3.7

TC
6.2
6.6
7.0
7.5
7.7
7.9
8.5
9.0
8.4
9.1
9.6
10.3
10.7
10.8
11.6
12.2
10.8
11.4
12.2
13.0
13.3
13.5
14.6
15.4

25
SHC
4.8
4.8
4.9
5.0
5.0
5.0
5.2
5.2
7.1
7.1
7.2
7.4
7.5
7.5
7.6
7.7
8.8
8.8
8.9
9.1
9.2
9.2
9.4
9.5

PI
2.2
2.3
2.3
2.4
2.4
2.4
2.5
2.5
2.7
2.7
2.8
2.8
2.9
2.9
3.0
3.0
3.6
3.6
3.7
3.8
3.8
3.8
3.9
4.0

TC
6.0
6.3
6.7
7.2
7.4
7.5
8.2
8.7
8.1
8.5
9.2
9.7
10.0
10.2
11.0
11.6
10.2
10.9
11.6
12.3
12.8
12.9
13.8
14.6

Outdoor temperature (CDB)


32
35
SHC
PI
TC
SHC
4.7
2.5
5.9
4.6
4.7
2.6
6.2
4.6
4.8
2.6
6.6
4.7
4.9
2.7
7.0
4.8
4.9
2.7
7.3
4.8
4.9
2.7
7.4
4.8
5.0
2.8
8.0
4.9
5.0
2.9
8.3
4.9
6.9
3.1
7.9
6.8
6.9
3.1
8.4
6.8
7.0
3.1
8.9
6.9
7.1
3.1
9.5
7.0
7.2
3.2
9.9
7.1
7.2
3.2
10.0
7.1
7.4
3.3
10.8
7.2
7.5
3.4
11.5
7.4
8.5
4.0
9.8
8.4
8.5
4.1
10.5
8.4
8.6
4.2
11.1
8.5
8.8
4.2
11.9
8.7
8.9
4.3
12.3
8.7
8.9
4.4
12.5
8.8
9.1
4.4
13.5
9.0
9.2
4.5
14.3
9.1

PI
2.7
2.7
2.8
2.9
2.9
2.9
3.0
3.0
3.2
3.2
3.3
3.3
3.4
3.4
3.5
3.6
4.3
4.3
4.4
4.4
4.5
4.5
4.6
4.7

TC
5.6
6.0
6.4
6.7
6.9
7.0
7.6
8.1
7.5
8.1
8.5
9.0
9.4
9.5
10.3
10.9
9.5
10.2
10.8
11.4
11.7
11.9
12.9
13.6

40
SHC
4.6
4.6
4.6
4.6
4.7
4.7
4.8
4.8
6.5
6.5
6.7
6.9
6.9
6.9
7.1
7.1
8.2
8.2
8.3
8.5
8.6
8.6
8.7
8.9

PI
3.0
3.0
3.1
3.2
3.2
3.2
3.3
3.4
3.5
3.6
3.6
3.7
3.7
3.7
3.8
3.8
4.6
4.7
4.7
4.8
4.9
4.9
5.0
5.1

TC
5.3
5.6
6.0
6.4
6.6
6.7
7.2
7.6
7.0
7.6
8.1
8.5
8.8
8.9
9.6
10.1
8.7
9.4
9.9
10.8
11.1
11.1
12.1
12.5

46
SHC
4.3
4.3
4.5
4.6
4.6
4.6
4.6
4.6
6.3
6.3
6.4
6.5
6.7
6.7
6.9
6.9
7.8
7.8
8.0
8.2
8.3
8.3
8.5
8.5

PI
3.4
3.4
3.5
3.5
3.6
3.6
3.6
3.6
3.7
3.7
3.8
3.8
3.9
3.9
4.0
4.1
5.1
5.2
5.2
5.3
5.3
5.4
5.5
5.6

3TW20332-7B

6. Air flow rate and BF are tabulated below.

SYMBOLS
AFR:
BF:
EWB:
EDB:
TC:
SHC:
PI:

Air flow rate


Bypass factor
Entering wet bulb temp.
Entering dry bulb temp.
Total cooling capacity
Sensible heating capacity
Power input
(comp.+indoor+outdoor fan motor)

(m3/min)
(CWB)
(CDB)
(kW)
(kW)
(kW)

Caution:
TC and SHC are shown by kW
V1: 230V
W1: 400V

Model
71
100
125

AFR
BF
AFR
BF
AFR
BF

FUY
19
0.07
29
0.07
32
0.07

7. Add the following correction value to power input (kW) of each unit

Model

NOTES

71

1. Ratings shown are net capacities which include a deduction for indoor
fan motor heat
2.
Shows nominal capacities
3. SHC is based on each EWB and EDB
SHC* = SHC correction for other dry bulb
SHC* = 0.34 x 60 x AFR (m3/min) x (DB-EDB)/1000.
Add SHC* to SHC if SHC > TC, then TC equal SHC
4. Direct interpolation is permissible.
Do not extrapolate.
5. Capacities are based on the following conditions:
Corresponding refrigerant piping length:
7.5 m
Level difference:
0m

Split - Sky Air Outdoor Units

100
125

Supply
V1
W1
V1
W1
W1

FUY
0.2
0
0.3
0
0

25

Pair Application R-22 RE18-40GA/R25-45DC/R60FA/R71-250F

16
3

Capacity tables

FDY125B7V1 + R125B7W1
Cooling capacity

Outdoor

125

EWB
(C)
12
14
16
18
19
22
24

Indoor

230V [50Hz]

EDB
(C)
18
20
22
25
27
30
32

TC
11.1
11.9
12.6
13.5
13.9
15.2
16.1

20
SHC
9.6
9.7
9.8
10.4
9.5
9.7
9.8

PI
3.6
3.7
3.8
3.9
3.9
4.1
4.2

TC
10.8
11.5
12.2
13.0
13.4
14.7
15.6

25
SHC
9.4
9.5
9.5
10.1
10.7
10.7
10.6

PI
4.0
4.0
4.1
4.2
4.3
4.4
4.5

TC
10.2
10.9
11.6
12.3
12.7
13.9
14.8

Outdoor temperature (CDB)


32
35
SHC
PI
TC
SHC
9.0
4.5
10.0
8.8
9.1
4.6
10.6
8.9
9.2
4.7
11.3
9.0
9.7
4.8
12.0
9.6
10.3
4.8
12.4
10.1
10.3
5.0
13.6
10.1
10.2
5.1
14.4
10.1

PI
4.8
4.8
4.9
5.0
5.1
5.3
5.4

TC
9.5
10.1
10.8
11.5
11.8
13.0
13.7

40
SHC
8.5
8.6
8.7
9.2
9.8
9.8
9.8

PI
5.2
5.3
5.4
5.5
5.6
5.8
5.9

TC
8.9
9.5
10.1
10.8
11.1
12.2
12.9

46
SHC
8.1
8.2
8.3
8.8
9.4
9.4
9.4

PI
5.8
5.9
6.0
6.1
6.2
6.4
6.5

3TW20372-6A

SYMBOLS
AFR:
BF:
EWB:
EDB:
DB*:
TC:
SHC:
PI:

NOTES

Air flow rate


Bypass factor
Entering wet bulb temp.
Entering dry bulb temp.
Dry bulb temperature
Total cooling capacity
Sensible heating capacity
Power input
(comp.+indoor+outdoor fan motor)

(m3/min)
(CWB)
(CDB)
(CDB)
(kW)
(kW)
(kW)

Caution:
TC and SHC are shown by kW
V1: 230V
W1: 400V

1. Ratings shown are net capacities which include a deduction for indoor
fan motor heat
2.
Shows nominal capacities
3. SHC is based on each EWB and EDB
SHC* = SHC correction for other dry bulb
SHC* = 0.34 x 60 x AFR (m3/min) x (DB-EDB)/1000.
Add SHC* to SHC if SHC > TC, then TC equal SHC
4. Direct interpolation is permissible.
Do not extrapolate.
5. Capacities are based on the following conditions:
Corresponding refrigerant piping length:
7.5 m
Level difference:
0m
6. Air flow rate and BF are tabulated below.

Model
125

26

Split - Sky Air Outdoor Units

AFR
BF

FDY
45
0.25

Pair Application R-22 RE18-40GA/R25-45DC/R60FA/R71-250F

Capacity tables
Model

FDY200250F7V1 + R200250F7V1
Cooling capacity

Outdoor

200

250

EWB
(C)
12
14
16
18
19
22
24
12
14
16
18
19
22
24

Indoor

AFR
BF

230V [50Hz]

EDB
(C)
18
20
22
25
27
30
32
18
20
22
25
27
30
32

TC
17.9
19.2
20.5
21.8
22.5
24.7
26.2
21.7
23.2
24.8
26.4
27.2
29.9
31.7

20
SHC
15.7
15.8
15.9
16.8
17.8
17.8
17.8
18.9
19.0
19.1
20.3
21.5
21.4
21.5

PI
6.1
6.1
6.2
6.3
6.4
6.5
6.7
7.0
7.1
7.2
7.3
7.4
7.6
7.7

TC
17.2
18.4
19.7
21.0
21.6
23.8
25.3
20.8
22.3
23.8
25.4
26.2
28.8
30.6

25
SHC
15.2
15.3
15.4
16.4
17.3
17.3
17.3
18.3
18.4
18.6
19.7
20.9
20.9
20.9

PI
6.5
6.6
6.7
6.8
6.9
7.0
7.2
7.6
7.7
7.8
7.9
8.0
8.2
8.3

TC
16.2
17.4
18.6
19.8
20.5
22.6
24.0
19.6
21.0
22.5
24.0
24.8
27.3
29.0

FDY200
72
0.25

Outdoor temperature (CDB)


32
35
SHC
PI
TC
SHC
14.5
7.3
15.8
14.2
14.6
7.4
16.9
14.4
14.7
7.5
18.1
14.5
15.7
7.6
19.4
15.5
16.7
7.7
20.0
16.4
16.7
7.9
22.0
16.4
16.7
8.0
23.5
16.4
17.5
8.5
19.1
17.2
17.7
8.6
20.5
17.3
17.8
8.7
21.9
17.5
19.0
8.9
23.4
18.7
20.1
8.9
24.2
19.8
20.1
9.2
26.7
19.8
20.2
9.3
28.4
19.8

PI
7.7
7.8
7.9
8.0
8.1
8.3
8.5
8.9
9.0
9.2
9.3
9.4
9.7
9.8

TC
15.1
16.3
17.4
18.6
19.3
21.2
22.7
18.3
19.7
21.1
22.5
23.3
25.7
27.4

40
SHC
13.8
13.9
14.0
15.0
16.0
16.0
16.0
16.6
16.8
17.0
18.1
19.3
19.3
19.3

PI
8.4
8.5
8.7
8.8
8.9
9.1
9.3
9.8
9.9
10.0
10.2
10.3
10.5
10.7

TC
14.4
15.5
16.7
17.8
18.4
20.3
21.7
17.5
18.8
20.2
21.6
22.3
24.6
26.2

FDY250
90
0.25
46
SHC
13.3
13.4
13.5
14.5
15.5
15.5
15.5
16.0
16.2
16.4
17.6
18.7
18.7
18.7

16
3

PI
9.4
9.5
9.7
9.8
9.9
10.1
10.3
10.9
11.1
11.2
11.4
11.5
11.8
12.0

3TW21482-1

SYMBOLS
AFR:
BF:
EWB:
EDB:
TC:
SHC:
PI:

NOTES

Air flow rate


Bypass factor
Entering wet bulb temp.
Entering dry bulb temp.
Total cooling capacity
Sensible heating capacity
Power input
(comp.+indoor+outdoor fan motor)

(m /min)
(CWB)
(CDB)
(kW)
(kW)
(kW)

Caution:
TC and SHC are shown by kW
V1: 230V
W1: 400V

Split - Sky Air Outdoor Units

1. Ratings shown are net capacities which include a deduction for indoor
fan motor heat
2.
Shows nominal capacities
3. SHC is based on each EWB and EDB
SHC* = SHC correction for other dry bulb
SHC* = 0.34 x 60 x AFR (m3/min) x (DB-EDB)/1000.
Add SHC* to SHC if SHC > TC, then TC equal SHC
4. Direct interpolation is permissible.
Do not extrapolate.
5. Capacities are based on the following conditions:
Corresponding refrigerant piping length:
7.5 m
Level difference:
0m

27

Pair Application R-22 RE18-40GA/R25-45DC/R60FA/R71-250F

Dimensional drawings

16
4

R2545DC7
RE1840GA7
1
2
3
4
5
6
7
8

unit (mm)

Drain outlet
4x holes for anchor bolts (M8 or M10)
Service cover + wiring diagram
Power intake
Low pressure gas stop valve
Liquid stop valve (Cu1/4)
Low pressure service port
Name plate

Minimum installation space (mm)

Space for air passage

H
1000
> 1000

j
5 JA
J9.5mm or 3/8CuT
J12.7mm or 1/2CuT
J15.9mm or 5/8CuT
J9.5mm or 3/8CuT
J9.5mm or 3/8CuT
J12.7mm or 1/2CuT
J12.7mm or 1/2CuT

R25DC7
R35DC7
R45DC7
RE18G7V1
RE25G7V1
RE35G7V1
RE40G7V1

j
6 JB
J6.4mm or 1/4CuT
J6.4mm or 1/4CuT
J6.4mm or 1/4CuT
J6.4mm or 1/4CuT
J6.4mm or 1/4CuT
J6.4mm or 1/4CuT
J6.4mm or 1/4CuT

A
> 250
> 500
3TW01574-1B

R60FA7

unit (mm)
R60FA7

j
5 JA
J5.9mm or 5/8CuT

j
6 J
J6.4mm or 1/4CuT

1
2
3
4
5
6
7
8
9

Drain outlet (3x)


4 holes for anchor bolts (M10)
Service cover
Power intake
Low pressure gas stop valve JA
Liquid stop valve JB
Low pressure service port
Name plate Daikin
Outdoor air thermostat

Space for air passage


Minimum installation space (mm)

H 1000
H > 1000

A
300
600

3TW01754-1B

28

Split - Sky Air Outdoor Units

Pair Application R-22 RE18-40GA/R25-45DC/R60FA/R71-250F

Dimensional drawings

16
R71B7

unit (mm)

Hole for anchor bolt


4-M12

Name plate

1
2
3
4
5
6

Gas pipe connection J15.9 flare


Liquid pipe connection - J9.5 flare
Service port (in the unit)
Grounding terminal M5 (in switch box)
Drain outlet
Stop valve cover

3TW23184-1A

R100-125B7

unit (mm)

Hole for anchor bolt


4-M12

Name plate

1
2
3
4
5
6

Gas pipe connection J19.1 flare


Liquid pipe connection - J9.5 flare
Service port (in the unit)
Grounding terminal M5 (in switch box)
Drain outlet
Stop valve cover

3TW23224-1A

Split - Sky Air Outdoor Units

29

Pair Application R-22 RE18-40GA/R25-45DC/R60FA/R71-250F

Dimensional drawings

16
R200F7
1
2
3
4

unit (mm)

Liquid piping connection opening


Gas piping connection opening
Ground terminal
Power supply wiring outlet

(distance between foundation holes)

Foundation hole

(distance between
foundation holes)

Note: The dimensions marked with z refer to distances


after fixing the accessory pipes.
(pipes connected to the side)

Knock hole for lower piping

(pipes connected to
the front)

3TW21484-1C

R250F7
Liquid piping connection opening
Gas piping connection opening
Ground terminal
Power supply wiring outlet

(distance between foundation holes)

Foundation hole
(distance between
foundation holes)

1
2
3
4

unit (mm)

Note: The dimensions marked with z refer to distances


after fixing the accessory pipes.

(pipes connected to the side)

Knock hole for lower piping

(pipes connected to
the front)

3TW21494-1C

30

Split - Sky Air Outdoor Units

Pair Application R-22 RE18-40GA/R25-45DC/R60FA/R71-250F

Operation range

16
5

Pull-down period

Outdoor temp. (CDB)

RE18-40GA7

Notes:
The graph is based on the following conditions:
1. Equivalent piping length
7.5 m
2. Level difference
0m

Indoor temp. (CWB)


4TW01013-1

Pull-down period

Outdoor temp. (CDB)

R25DC7
R35DC7
R45DC7

Notes:
The graph is based on the following conditions:
+ Equivalent piping length
7,5m
+ Level difference
0m
+ Air flow rate
Hi speed

Indoor temp. (CWB)

4TW00573-1

Split - Sky Air Outdoor Units

31

Pair Application R-22 RE18-40GA/R25-45DC/R60FA/R71-250F

Operation range

16
R60FA7

Pull-down period

Outdoor temp. (CDB)

Notes:
The graph is based on the following conditions:
+ Equivalent piping length
7,5m
+ Level difference
0m
Hi speed
+ Air flow rate

Indoor temp. (CWB)

4TW00623-1

Allowable range of operation (pull-down)

Outdoor temp. (CDB)

R71-125B7

Indoor temp. (CWB)

3TW23183-1A

32

Split - Sky Air Outdoor Units

Pair Application R-22 RE18-40GA/R25-45DC/R60FA/R71-250F

Operation range

16
5

Outdoor temp. (CDB)

Pull-down period

R200-250B7

Indoor temp. (CWB)

Split - Sky Air Outdoor Units

Notes:
The graph is based on the following conditions:
+ Equivalent piping length
+ Level difference
+ Air flow rate

70m
30 m
72 m3/min

3TW21483-1

33

Pair Application R-22 RE18-40GA/R25-45DC/R60FA/R71-250F

Piping diagrams

16
6

RE18-25-35GA7
Heat exchanger

Filter
Propeller fan

Liquid line stop


valve

Capillary tube

Compressor

Gas line stop valve with service


port

Field piping
(6.4 CuT)

Field piping
(9.5 CuT for RE18G7V1, RE25G7V1)
(12.7 CuT for RE35G7V1)

Accumulator

M1C : Compressor motor


M2F : Fan motor

: Refrigerant flow

O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe

3TW01015-1

RE40GA7V1
Heat exchanger

Filter
Propeller fan

Capillary tube
Muffler
Compressor

Liquid line stop


valve

Field piping
(6.4 CuT)

Gas line stop valve with service


port
Field piping
(12.7 CuT)

Accumulator

M1C: Compressor motor


M2F: Fan motor

: Refrigerant flow

O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe

34

Split - Sky Air Outdoor Units

3TW01105-1

Pair Application R-22 RE18-40GA/R25-45DC/R60FA/R71-250F

Piping diagrams

16
6

R25-35-45DC7
Heat exchanger

Service port

Filter
Propeller fan

Liquid line stop


valve

Capillary tube

Compressor

Gas line stop valve with service


port

Field piping
(6.4 CuT)

Field piping
(9.5 CuT for R25DB7V1)
(12.7 CuT for R35DB7V1)
(15.9 CuT for R45DB7V1/W1)

Accumulator

M1C : Compressor motor


M2F : Fan motor

: Refrigerant flow

3TW00025-1A

O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe

R60FA7
Heat exchanger
Service port

Filter

Liquid line stop


valve
Propeller fan

Field piping
(6.4 CuT)

Capillary tube

Compressor

(15.9 CuT)

Gas line stop valve with


service port
Accumulator

M1C : Compressor motor


M2F : Fan motor

S2PH

: High pressure switch


: Refrigerant flow

O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe

Split - Sky Air Outdoor Units

3TW00625-1C

35

Pair Application R-22 RE18-40GA/R25-45DC/R60FA/R71-250F

Piping diagrams

16
6

R71B7
Capillary tube

Filter

Electronic expansion
valve

Indoor heat exchanger

Outdoor heat exchanger

Filter
Pressure switch
(high)

Pressure
switch (low)

Service port 1/4

Field piping J9.5 C122OT-O


Filter
Compressor

Field piping J15.9 C122OT-O

Indoor unit

Outdoor unit

Stop valve
(with service port 1/4 flare)

3TW23185-1

R100-125B7
Capillary tube

Electronic expansion
valve

Filter
Outdoor heat exchanger

Indoor heat exchanger

Filter
Pressure
switch (low)

Pressure switch
(high)

Service port 1/4


Field piping J9.5 C122OT-O
Filter
Compressor

Field piping J15.9 C122OT-O

Outdoor unit

Indoor unit
Stop valve
(with service port 1/4 flare)

36

Split - Sky Air Outdoor Units

3TW23225-1

Pair Application R-22 RE18-40GA/R25-45DC/R60FA/R71-250F

Piping diagrams

16
6

R200-250F7
Capillary tube

Outdoor heat exchanger

Indoor heat exchanger

Filter

Fan
Propeller fan

Pressure switch
(high)

Field piping J A

Pressure
switch (low)
Field pipingJ B

Indoor unit

Service port 1/4

Stop valve
(with service port 1/4 flare)

Accumulator

Compressor

Outdoor unit

A
12.7
15.9

B
28.6
28.6

Split - Sky Air Outdoor Units

Model
R200
R250

3TW21485-1A

37

Pair Application R-22 RE18-40GA/R25-45DC/R60FA/R71-250F

Wiring diagrams

16
7

RE18GA7
L
N

Live
Neutral
Protective earth

g Field wiring

Indoor

Outdoor

C1R,C2R
F1U
F2S
K1M
M1C
M2F

: Running capacitor
: Field fuse
: Surge absorber
: Compressor contactor
: Compressor motor
: Fan motor

Q1CL
Q3M
Q5E
X1M

: Overcurrent overload switch (compressor)


: Thermal protector
: Field earth leak protector
: Terminal strip

3TW01016-1A

RE40GA7
L
N

Live
Neutral
Protective earth

g Field wiring

Indoor

Outdoor

C1R,C2R
F1U
F2S
K1M
M1C
M2F

38

: Running capacitor
: Field fuse
: Surge absorber
: Compressor contactor
: Compressor motor
: Fan motor

Q2L
Q3M,Q4M
Q5E
X1M
X2A

Split - Sky Air Outdoor Units

: Overload switch (compressor)


: Thermal protector
: Field earth leak protector
: Terminal strip
: Connector

3TW01036-1B

Pair Application R-22 RE18-40GA/R25-45DC/R60FA/R71-250F

Wiring diagrams

16
7

R25DC7

L
N

Live
Neutral
Protective earth

Outdoor

g Field wiring

Indoor

C1R,C2R
F1U
F2S
K1M
M1C
M2F

: Running capacitor
: Field fuse
: Surge absorber
: Compressor contactor
: Compressor motor
: Fan motor

Q1CL
Q3M
Q5E

: Overcurrent overload switch (compressor)


: Thermal protector
: Field earth leak protector

S1T
X1M
X2A
Z1F

: Thermostat
: Terminal strip
: Connector
: Noise filter

3TW00576-1B

R35DC7

L
N

Live
Neutral
Protective earth

Outdoor

g Field wiring

Indoor

C1R,C2R
F1U
F2S
K1M
M1C
M2F

: Running capacitor
: Field fuse
: Surge absorber
: Compressor contactor
: Compressor motor
: Fan motor

Q2L
Q3M,Q4M
Q5E

: Overload protector (compressor)


: Thermal protector
: Field earth leak protector

S1T
X1M
X2A
Z1F

: Thermostat
: Terminal strip
: Connector
: Noise filter

3TW00596-1D

Split - Sky Air Outdoor Units

39

Pair Application R-22 RE18-40GA/R25-45DC/R60FA/R71-250F

Wiring diagrams

16
7

R45DC7

L
N

Live
Neutral
Protective earth
Outdoor

g Field wiring

Indoor

C1R,C2R
F1U
F2S,F3S
K1M
M1C
M2F

: Running capacitor
: Field fuse
: Surge absorber
: Compressor contactor
: Compressor motor
: Fan motor

Q2L
Q3M,Q4M
Q5E

: Overload protector (compressor)


: Thermal protector
: Field earth leak protector

S1T
X1M
X2A
Z1F

: Thermostat
: Terminal strip
: Connector
: Noise filter

3TW00606-1A

R45DC7
N
L1,L2,L3

Neutral
Live
Protective earth

g Field wiring

Indoor

Outdoor

C2R
F1U
F2S, F35
K1M
M1C
M2F

40

: Running capacitor
: Field fuse
: Surge absorber
: Compressor contactor
: Compressor motor
: Fan motor

Q3M
Q5E
Q2L
F3C
K2R
R1P

: Thermal protector
: Field earth leak protector
: Overload protector (compressor)
: Overcurrent relay
: Magnetic relay
: Reverse phase protector

Split - Sky Air Outdoor Units

S1T
X1M
X2A
Z1F

: Thermostat
: Terminal strip
: Connector
: Noise filter

3TW00616-1C

Pair Application R-22 RE18-40GA/R25-45DC/R60FA/R71-250F

Wiring diagrams

16
7

R60FA7V1

Room A

Indoor

g Field wiring
L
N

Live
Neutral
Protective earth

Outdoor

C1R
FU
F1U
SA
K1M
M1C
M2F

: Running capacitor
: Fuse
: Field fuse
: Surge absorber
: Compressor contactor
: Compressor motor
: Fan motor

Q3M,Q4M
Q5E
SA
MR1,MR2
PCB
Q2L

: Thermal protector
: Field earth leak protector
: Surge absorber
: Magnetic relay
: Printed circuit board
: Overload protector

X1M
R1T
S1S5
X11A,X12A
S2PH
T1R

: Terminal strip
: Thermistor
: Connector
: Connector
: High pressure switch
: Transformer

3TW01126-1B

R60FA7W1

Outdoor
Room A

Indoor

g Field wiring
L1L3
N

Live
Neutral
Protective earth

C2R
CT1,CT2
FU1FU3
F1U
K1M
M1C

: Running current
: Current transformer
: Fuse
: Field fuse
: Compressor contactor
: Compressor motor

M2F
MRoc
PCB
Q2L
Q3M,Q4M
Q5E

: Fan motor
: Magnetic relay
: Printed circuit board
: Overload protector
: Thermal protector
: Field earth leak protector

SA
: Surge absorber
S1T
: Thermostat
S2PH
: High pressure switch
X1M
: Terminal strip
Z1F
: Noise filter
S1,S2,S4,S5,S10,X11A : Connector

3TW01136-1D

Split - Sky Air Outdoor Units

41

Pair Application R-22 RE18-40GA/R25-45DC/R60FA/R71-250F

Wiring diagrams

16
7

R71B7
Indoor
Note:
Do not operate the unit by short-circuiting S1LP

g Field wiring
D
: Terminal
F
: Connector

: Wire clamp
b
: Protective earth (screw)

Switch box

Colours
BLK: Black/ BLU: Blue/ WHT: White/
RED: Red/ ORG: Orange/ YLW:Yellow

Outdoor

L-RED

N-BLU

A1P,A2P
BS1
C1R
C3R,C4R
F1C
F1U

Printed circuit board


Push button (pump down)
Capacitor (M1F)
Capacitor (M1C)
Overcurrent relay (M1C)
Fuse (250V, 5A)

F3U
H1P
H2P,H3P
J1HC
K1M
M1C
M1F

Field fuse
LED (service monitor green)
LED (service monitor red)
Crankcase heater
Magnetic contactor (M1C)
Motor (compressor)
Motor (fan)

Q1L
Q3E
R1T
R2T
R3T
RC
RyC

Thermo switch (M1F)


Earth leak detector
Thermistor (air)
Thermistor (coil)
Thermistor (discharge pipe)
Signal receiver circuit
Magnetic relay (K1M)

RyF1-3
S1LP
S1PH
SD
SS1
T1R
TC
X1M
Y1E

Magnetic relay (M1F)


Pressure switch (low)
Pressure switch (high)
Safety devices input
Selector switch (emergency)
Transformer (220-240V/16V)
Signal transmission circuit
Terminal strip
Expansion valve (electronic type)

2TW23186-1A

R71B7
Indoor

Note:
Do not operate the unit by short-circuiting S1LP

g Field wiring
D
: Terminal
F
: Connector

: Wire clamp
b
: Protective earth (screw)
Colours
BLK: Black/ BLU: Blue/ WHT: White/
RED: Red/ ORG: Orange/ YLW:Yellow

Switch box

Outdoor

42

L-RED

L2-WHT

L3-BLK

N-BLU

A1P,A2P
BS1
C1R
F1C
F1U,F2U
F3U
H1P

Printed circuit board


Push button (pump down)
Capacitor (M1F)
Overcurrent relay (M1C)
Fuse (250V, 5A)
Field fuse
Light emitting diode (service monitor green)

H2P,H3P
J1HC
K1M
M1C
M1F
PRC
Q1L
Q3E

Light emitting diode (service monitor red)


Crankcase heater
Magnetic contactor (M1C)
Motor (compressor)
Motor (fan)
Phase reverse circuit
Thermo switch (M1F)
Earth leak detector

R1T
R2T
R3T
RC
RyC
RyF1-3
S1LP
S1PH

Split - Sky Air Outdoor Units

Thermistor (air)
Thermistor (coil)
Thermistor (discharge pipe)
Signal receiver circuit
Magnetic relay (K1M)
Magnetic relay (M1F)
Pressure switch (low)
Pressure switch (high)

SD
SS1
T1R
TC
X1M
Y1E

Safety devices input


Selector switch (emergency)
Transformer (220-240V/16V)
Signal transmission circuit
Terminal strip
Expansion valve (electronic type)

2TW23196-1

Pair Application R-22 RE18-40GA/R25-45DC/R60FA/R71-250F

Wiring diagrams

16
7

R100B7
Note:
Do not operate the unit by short-circuiting S1LP
Indoor
g Field wiring
D
: Terminal
F
: Connector

: Wire clamp
b
: Protective earth (screw)

Switch box

Colours
BLK: Black/ BLU: Blue/ WHT: White/
RED: Red/ ORG: Orange/ YLW:Yellow

Outdoor
L-RED

N-BLU

A1P,A2P
BS1
C1R,C2R
C3R,C4R
F1C
F1U
F3U

Printed circuit board


Push button (pump down)
Capacitor (M1F-M2F)
Capacitor (M1C)
Overcurrent relay (M1C)
Fuse (250V, 5A)
Field fuse

H1P
H2P,H3P
J1HC
K1M
M1C
M1F,M2F
Q1L,Q2L

Light emitting diode (service monitor red)


Light emitting diode (service monitor green)
Crankcase heater
Magnetic contactor (M1C)
Motor (compressor)
Motor (fan)
Thermo switch (M1F, M2F)

Q3E
R1T
R2T
R3T
RC
RyC
RyF1-4

Earth leak detector


Thermistor (air)
Thermistor (coil)
Thermistor (discharge pipe)
Signal receiver circuit
Magnetic relay (K1M)
Magnetic relay (M1F,M2F)

S1LP
S1PH
SD
SS1
T1R
TC
X1M
Y1E

Pressure switch (low)


Pressure switch (high)
Safety devices input
Selector switch (emergency)
Transformer (220-240V/16V)
Signal transmission circuit
Terminal strip
Expansion valve (electronic type)

2TW23226-1A

R100-125B7
Note:

Indoor

Do not operate the unit by short-circuiting S1LP

g Field wiring
D
: Terminal
F
: Connector

: Wire clamp
b
: Protective earth (screw)

Switch box

Colours
BLK: Black/ BLU: Blue/ WHT: White/
RED: Red/ ORG: Orange/ YLW:Yellow

Outdoor

L-RED

L2-WHT

L3-BLK

N-BLU

A1P,A2P
BS1
C1R,C2R
F1C
F1U,F2U
F3U
H1P

Printed circuit board


Push button (pump down)
Capacitor (M1F-M2F)
Overcurrent relay (M1C)
Fuse (250V, 5A)
Field fuse
Light emitting diode (service monitor
green)

H2P,H3P
J1HC
K1M
M1C
M1F,M2F
PRC
Q1L,Q2L
Q3E

Light emitting diode (service monitor red)


Crankcase heater
Magnetic contactor (M1C)
Motor (compressor)
Motor (fan)
Phase reverse circuit
Thermo switch (M1F, M2F)
Earth leak detector

R1T
R2T
R3T
RC
RyC
RyF1-4
S1LP
S1PH

Thermistor (air)
Thermistor (coil)
Thermistor (discharge pipe)
Signal receiver circuit
Magnetic relay (K1M)
Magnetic relay (M1F,M2F)
Pressure switch (low)
Pressure switch (high)

Split - Sky Air Outdoor Units

SD
SS1
T1R
TC
X1M
Y1E

Safety devices input


Selector switch (emergency)
Transformer (220-240V/16V)
Signal transmission circuit
Terminal strip
Expansion valve (electronic type)

2TW23236-1A

43

Pair Application R-22 RE18-40GA/R25-45DC/R60FA/R71-250F

Wiring diagrams

16
7

R200-250F7
Note:
Do not operate the unit by short-circuiting S1LP

Indoor

g Field wiring
D
: Terminal
F
: Connector

: Wire clamp
b
: Protective earth (screw)
Colours
BLK: Black/ BLU: Blue/ WHT: White/
RED: Red/ ORG: Orange/ YLW:Yellow

Switch box

Outdoor

44

L-RED

L2-WHT

L3-BLK

N-BLU

A1P,A2P
BS1
C1R,C2R
F1C
F1U,F2U
F3U
H1P

Printed circuit board


Push button (pump down)
Capacitor (M1F-M2F)
Overcurrent relay (M1C)
Fuse (250V, 5A)
Field fuse
Light emitting diode (service monitor
green)

H2P,H3P
J1HC
K1M
M1C
M1F,M2F
PRC
Q1L,Q2L,Q3L
Q3E

Light emitting diode (service monitor red)


Crankcase heater
Magnetic contactor (M1C)
Motor (compressor)
Motor (fan)
Phase reverse circuit
Thermo switch (M1F, M2F)
Earth leak detector

R1T
RC
RyC
RyF1
S1LP
S1PH
SD
SS1

Thermistor (air)
Signal receiver circuit
Magnetic relay (K1M)
Magnetic relay (M1F)
Pressure switch (low)
Pressure switch (high)
Safety devices input
Selector switch (emergency)

Split - Sky Air Outdoor Units

T1R
TC
X1M

Transformer (220-240V/16V)
Signal transmission circuit
Terminal strip

2TW21486-1A

Pair Application R-22 RE18-40GA/R25-45DC/R60FA/R71-250F

8
8-1

Sound level
Sound level data

16

Cooling only

Sound pressure level (H)


230V
Model

50Hz

Measuring location

V1
RE18GA7

8-1

Sound power level (H)

V1

45

56
Center

RE40GA7V1

50

63
Sound pressure level (H)

230V
Model

400V

Sound power level (H)

50Hz

Measuring location

V1

W1

V1

W1

R25DC7V11

43

56

R35DC7V11

48

61

R45DC7V11/W11

50

50

63

63

R60FA7V1/W1

54

54

67

67

Center

Sound pressure level (H)


230V
Model

400V
50Hz

Sound power level (H)


Measuring location

V1

W1

V1

W1

R71B7

49

49

62

62

R100B7

52

52

64

64

R125B7

52

65

R200F7

56

77

R250F7

56

77

Center

Note:
Sound pressure level is measured in an anechoic chamber.

Split - Sky Air Outdoor Units

45

Pair Application R-22 RE18-40GA/R25-45DC/R60FA/R71-250F

16

8
8-2

Sound level
Sound pressure spectrum
RE18GA7V1

Sound pressure level [dB(A)]

8-2

RE40GA7V1
Sound pressure level [dB(A)]

3TW01017-1A

3TW01107-1

Octave band center frequency (Hz)

Octave band center frequency (Hz)

Notes

Data is valid at free field condition


Operation sound levels are valid at nominal operation condition 230V
dBA = A-weighted sound pressure level (A-scale according to IEC)
Reference acoustic pressure 0dB = 20Pa

R35DC7V11
Sound pressure level [dB(A)]

Sound pressure level [dB(A)]

R25DC7V11

3TW00017-1

46

Octave band center frequency (Hz)

Split - Sky Air Outdoor Units

3TW00037-1

Octave band center frequency (Hz)

Pair Application R-22 RE18-40GA/R25-45DC/R60FA/R71-250F

8
8-2

Sound level
Sound pressure spectrum

16

R45DC7W11

Sound pressure level [dB(A)]

Sound pressure level [dB(A)]

R45DCV11

3TW00047-1

8-2

3TW00057-1

Octave band center frequency (Hz)

Octave band center frequency (Hz)

Notes

Data is valid at free field condition


Operation sound levels are valid at nominal operation condition 230V
dBA = A-weighted sound pressure level (A-scale according to IEC)
Reference acoustic pressure 0dB = 20Pa

R60FA7W1
Sound pressure level [dB(A)]

Sound pressure level [dB(A)]

R60FA7V1

3TW01127-1

Octave band center frequency (Hz)

Split - Sky Air Outdoor Units

3TW01137-1

Octave band center frequency (Hz)

47

Pair Application R-22 RE18-40GA/R25-45DC/R60FA/R71-250F

16

8
8-2

Sound level
Sound pressure spectrum
R125FJ7W1

R100FJ7V1/W1

R71FJ7V1/W1

Octave band sound pressure level


dB:(0dB = 0.0002 bar)

Octave band sound pressure level


dB:(0dB = 0.0002 bar)

Octave band sound pressure level


dB:(0dB = 0.0002 bar)

8-2

DU427-4261

approximate threshold
hearing for continuous
noise

approximate threshold
hearing for continuous
noise

approximate threshold
hearing for continuous
noise

Octave band center frequency (Hz)

DU428-4211

Octave band center frequency (Hz)

R250F7
Sound pressure level [dB(A)]

Sound pressure level [dB(A)]

R200F7

3TW21487-1

48

DU429-4178

Octave band center frequency (Hz)

Octave band center frequency (Hz)

Split - Sky Air Outdoor Units

3TW21497-1A

Octave band center frequency (Hz)

Pair Application R-22 RE18-40GA/R25-45DC/R60FA/R71-250F

9
9-1

Accessories
Optional accessories

16

Available options for R71-125B7(V1,W1,T1)

Kit name

Name of option

R71B

R100B

Central drain plug

9-1

R125B

KKPJ5F180
Twin

Refrigerant branch piping

KHRP79BA7

Triple

KHRP96H7

3TW23189-1

Available options for R200-250F7W1

Option

Name of option

Fan motor size up

NFM22C5

R200F

R250F

Fan motor size up

NFM22C10

Kit for discharge duct

EKND26A10

Refnet

KHRP79BA7

Refnet

KHRP102BA7

Refnet

KHRP127HA7

Refer to the table with possible indoor combinations*


3TW21489-2

* table with possible indoor combinations = combination matrix 3TW23619-1 (See chapter R-B7 - twin / triple / double twin application).

Suction gas side joint

KHRP79BA7

Liquid side joint


Outlet

Inlet

Sky Air

Outlet
Outlet

Outlet

Inlet
Outlet

Liquid side joint

Others

Suction gas side header

Insulator
Installation manual

Inlet
Inlet
Outlet
Outlet

Sky Air

KHRP96H7

Insulator
Installation manual

Inlet

Outlet

Insulator
Installation manual

Inlet

KHRP127HA7

Insulator
Installation manual

Inlet

Outlet

KHRP102BA7

Others

Outlet

Inlet

Outlet
Outlet

Outlet

Outlet

Outlet

1TW21559-11A

Split - Sky Air Outdoor Units

49

Pair Application R-22 RE18-40GA/R25-45DC/R60FA/R71-250F

10

Centre of gravity

16
10

R200-250F7

4TW23619-1

50

Model

R(Y)200F7W1
R(Y)P200B7W1

380

R(Y)250F7W1
R(Y)P250B7W1

510

Split - Sky Air Outdoor Units

Pair Application R-22 RE18-40GA/R25-45DC/R60FA/R71-250F

11
Installation
11-1 Max. allowable piping length and level difference
R35-45DC7 + R60FA

16
11

R2545DC7-R60FA7

R71B7125B7

Max.allowable piping length

25m

50m

Max. allowable piping length and


level difference

15m

30m

11-1

R200-250F7W1

Allowable pipe length


Allowable pipe length
L
Max.allowable piping length

50m

L1+L2,L1+L3,L1+L4
L1+L2+L4
L1,L2,L3

Max branch pipe length

L2+L4
L2-L3,L2-L4,L3-L4

Max difference between branch length

(L2+L4)-(L3+L7)

Max. difference between

L2-L3

Max. difference between

L4-L5,L6-L7
H1,H2,H3
H1,H2,H3,H4,H5

Max height difference

30m

Pair

11-2 Refrigerant charge


(1) R2545DC7+R60FA7

R2560
Additional charge

20g/m
(Exceeding 15 m (R35-45)
and 10 m (R60))

R200-250F7
The cooling only unit does not require any additional charging of refrigerant.
3TW21489-3A

Split - Sky Air Outdoor Units

51

Pair Application R-22 RE18-40GA/R25-45DC/R60FA/R71-250F

16
11

11-3

11
Installation
11-3 Installation service space
The numerical figures used here represent the dimensions for the models R71.
The figures inside () indicate the dimensions for the models R100 and R125.
(Unit: mm)
The figures inside < > indicate the dimension of discharge grille when it is
installed facing downward
When installing multiple units in lateral connection, discharge grille cannot be set
to discharge air in Left/Right direction

(A) In case obstacles exist in front of the air inlet

(B) In case obstacles exist only in front of outlet side

+ Where there are no


obstacles above the unit.
1

Installation of single unit


+ In case obstacles exist only in
front of outlet side.

Installation of multiple units in


lateral connection (2 units or
more).

150 or more
20 mm or more
20 mm or more

+ Where there are no obstacles above


the unit
1

Installation of single unit


+ In case obstacles exist only in front of the
air inlet.
+ In case obstacles exist in front of the air
inlet and on both sides of the unit.

50 or more (100)

1000 mm or
more

+ Where there are


obstacles above the
unit.

100 or more

2 Installation of multiple units in lateral


connection.

Installation of single unit


+ In case obstacles exist
only in front of outlet
side.

Installation of multiple units


in lateral connection (2
units or more).

100 or more

100 or more

100 or more

500 or less

20 mm or more
20 mm or more

+ In case obstacles exist in front


of the air inlet and on both
sides of the unit.

1000 mm or more

500 mm or more

500 or less
200 or more (300)

20 mm or more

1000 mm or more

20 mm or more

+ Where there are obstacles above the


unit.

+ In case obstacles exist


only in front of outlet
side.

1000 mm or more

500 or less

Installation of single unit


+ In case obstacles exist only in
front of outlet side.

20 mm or more

100 or more
500 or less
1000 mm or more

+ In case obstacles exist in front


of the air inlet and on both
sides of the unit.

1000 mm or more

(C) In case obstacles exist in


front of both the air inlet and
outlet sides.

Pattern 1
150 or more

150 or more

150 or more

+ Where there are no obstacles


above the unit.

500 or less
20 mm or more

1000 mm or more

2 Installation of multiple units in lateral


connection (2 units or more).
+ In case obstacles exist in front of
the air inlet and on both sides of
the unit.

Where obstacle in
front of the air outlet
is higher than the
unit.

1000 mm or more

20 mm or more

Installation of single
unit.
Installation of
multiple units in
lateral connection
(2 units or more).

50 or more (100)
500 or more (1000)

20 mm or more
20 mm or more

200 or more (300)

200 or more (300)


200 mm or more

52

Split - Sky Air Outdoor Units

1000 or more
(1500)

Pair Application R-22 RE18-40GA/R25-45DC/R60FA/R71-250F

11
Installation
11-3 Installation service space
+ Where there are obstacles above the unit.

16
11

Installation of multiple units in


lateral connection (2units or less).
500 or less

Installation of single unit.

Relation of dimensions of H, A, and L are


shown in the table below.
LH
H<L

Relation of dimensions of H, A, and L


are shown in the table below.

1000 mm or more

LH

150 or more (250)

Installation of multiple units in lateral


connection (2 units or more).

20 mm or
more

100 or more

H<L

20 mm or
more

1000 or more (1500)

Get the lower part of the frame sealed so that


air from the outlet does not bypass

(D) In case of stacked installation


1 In case obstacles exist in front of the
outlet side.
Do not stack more than one unit.
About 100mm is required as the
dimension for laying the upper outdoor
units drain pipe.
Get the portion A sealed so that air from
the outlet does not bypass.

500 or less

Relation of dimensions of H, A, and L are


shown in the table below.
LH

11-3

Do not install more than 2 units

Get the lower part of the frame sealed so that


air from the outlet does not bypass
2

L
A
0 < L 1/2 H
150 (250)
1/2 H < L
200 (300)
Set the frame to be L<=H

H<L

L
A
0 < L 1/2 H
750<1250>
1/2 H < L
1000<1500>
Set the frame to be L<=H

1000 mm or more

500 or less

L
A
0 < L 1/2 H
1000<1500>
1/2 H < L
1250<1750>
Set the frame to be L<=H

20 mm or more

1000 mm or more

200 or more (300)

Get the lower part of the frame sealed so that


air from the outlet does not bypass
Do not install more than 2 units

Pattern 2

20 mm or more

Do not stack more than one unit.

Where obstacle in front of the air outlet is


lower than the unit.

About 100mm is required as the


dimension for laying the upper outdoor
units drain pipe.
Get the portion A sealed so that air from
the outlet does not bypass.

+ Where there are no obstacles above


the unit.
1

In case obstacles exist in front of the


air inlet.

200 or more (300)

Installation of single unit.


50 or more (100)

Installation of multiple units in lateral connection


(2 units or more).

(E) In case of multiple-low installation


(for roof top use, etc.).

500 or more (1000)

1
Relation of dimensions of H, A, and L are
shown in the table below.
L
0 < L 1/2 H
1/2 H < L

In case of installing
one unit per row.

20 mm or more

A
150 (250)
200 (300)

50 or more (100)
1000 or more (2000)

100 or more (200)


500 or more (1000)

+ Where there are obstacles above the


unit.
1

20 mm or more

In case of installing
multiple units (2 units
or more) in lateral
connection per row.

20 mm or more
20 mm or more

1000 or more (1500)

Installation of single unit.


500 or less
1000 mm or more

Relation of dimensions of H, A, and L are


shown in the table below.
LH
H<L

L
A
0 < L 1/2 H
50 (100)
1/2 H < L
100 (200)
Set the frame to be L<=H

2000 or more (3000)

400 or more (600)


1000 or more (1500)

Relation of dimensions of H, A, and L are shown in the table below.

Get the lower part of the frame sealed so


that air from the outlet does not bypass

500 or more (1000)

LH
H<L

L
A
0 < L 1/2 H
150 (250)
1/2 H < L
200 (300)
Installation impossible
DU427-826

Split - Sky Air Outdoor Units

53

Pair Application R-22 RE18-40GA/R25-45DC/R60FA/R71-250F

11
Installation
11-3 Installation service space

Case 1

Case 1

Case 2

Case 2

Case 2

Case 3

Case 3

suction side

front side

2
3
4

3TW23619-4

Split - Sky Air Outdoor Units

Case 1and case 2


+ Front wall height is 1500mm
+ Suction wall height is 500mm
+ Side wall height has no limit
+ Case 3 wall height has no limit
If the wall is higher than mentioned in note 1: ADO h2/2 (front side) and ANO h1/2 (suction
side) to the mentioned values for installation. (h1 and h2: see figure to the left)
Before installing, please check the passage of humans and air at the side, and select a place
which is suitable for the case. (If there are a lot of units to be installed, take care that there is
no shortcircuit of air)
Please install considering piping installation at the front side.

Pair Application R-22 RE18-40GA/R25-45DC/R60FA/R71-250F

Case 1

11
Installation
11-3 Installation service space

Conentrated installation

16

Split - Sky Air Outdoor Units

Installation in a row

11

11-3

54
Single installation

Pair Application R-22 RE18-40GA/R25-45DC/R60FA/R71-250F

11

Installation

16

Non stacked installation

11

When installing link of multiple units,


leave a space of 200 mm or more
between the casing of one unit and
the stop valves of the other unit.

11-3

Legend

Suction side obstacle


Discharge side obstacle

Left side obstacle

Right side obstacle

Top side obstacle

Obstacle is present

Stacked installation
Obstacles exist in front of the outlet side

Obstacles exist in front of the air inlet

Do not stack more than one unit


About 100mm is required as the dimension for laying the upper outdoor units drain pipe
Get the portion A sealed so that air from the outlet does not bypass

Multiple-row installation
Installation of one unit per row

Installing multiple units (2 units or more) in


lateral connection per row

Relation of dimensions of H, A, and L are shown in the table below.


LH
H<L

L
A
0 < L 1/2 H
150 (250)
1/2 H < L
200 (300)
Installation impossible
3TW23189-4

Split - Sky Air Outdoor Units

55

Pair Application R-22 RE18-40GA/R25-45DC/R60FA/R71-250F

12

Safety device settings

16
12

Model

RE18GA7V1

RE40GA7V1

Fan motor
Thermal protector

Off 135 5C
On 115 5C

Off 135 5C
On 115 5C

Compressor
Internal protector

Off 175 5C
On 100 10C

Off 150 7C
On 69 10C

Off 130 3C
On 95 10C

*Off 3.6A 12%

Safety device

Overload relay
Overcurrent relay

4TW01011-2B + 4TW01101-2

Model

R25DC7V11

R35DC7V11

R45DC7V11

R45DC7W11

Off 185 5C
On 100 10C

Off 175 5C
On 100 5C

On 86 15C

Thermal protector fan

Off 135 5C
On 115 5C

Off 145 5C
On 75 5C

Off 135 5C
On 115 5C

Off 135 5C
On 115 5C

Overcurrent

Off 6.7A 12C

Off 5A

Overload

Off 150 7C
On 85 10C

Off 130 3C
On 95 10C

Off 130 3C
On 95 10C

Off 130 3C
On 95 10C

Safety device

Internal protector of compressor

Off 14.0 2C
On 16.5 2C

Thermostat

4TW01101-2

Model

R60FA7V1

R60FA7W1

Fan motor thermal protector

Off 135 5C
On 86 15C

Off 135 5C
On 86 15C

Compressor
Internal protector

Off 170 5C
On 110 9C

Off 115 5C
On 85 7C

Off 7A

Safety device

Overload relay
Overcurrent relay

4TW00621-3C

56

Split - Sky Air Outdoor Units