FT 35 AUTOMATIC ALARM SYSTEM

AUTOMATIC FIRE DETECTORS


OBJECTIVE 1. To explain the fundamentals of detection, types of detectors, types of detectors their function and operation. REFERENCE 2. a. b. Manual of Fireman ship Book 9. Fire College Notes.

CONTENTS FIRE ALARM SYSTEMS 3. Introduction. What do you understand by fires alarm systems? It is a means of informing people of the situation at or around their area of a fire outbreak, smoke or both and its spreading effect. By informing we can do many things or get many things done viz. a. b. c. d. e. 4. Evacuate people from the danger area. Reduce the spread fire/smoke or both. Reduce damage or further damage. Stop the fire at its initial stage. Call for help i.e. fire brigade, police, ambulance, salvage team and etc.

Means of Activating Alarm: a. b. c. d. By shouting fire, fire, fire. By blowing whistle. Telephone. Ring or sound bells siren, gongs etc.

e. By its automatic function if an automatic fire alarm system is installed using a combination of detectors, call points and also, if a more sophisticated system, suppression. 5. Automatic Fire Alarm System. Most of the modern complexes civilian and military and especially high rise building and high risk areas these automatic systems are employed. Its usually a combination of manual break glass call points, bells, detector heads (smoke, heat and flame etc) and suppression component (if included). 6 Automatic Detection consists of various types of detection components/elements: a. b. c. d. Smoke detectors. Heat detectors. Radiation (Flame) detectors. Laser beam detectors.

7. Prime function of fire detector is to detect one or more changes in the protected environment, indicative of the development of a fire condition. Detectors are normally ceiling mounted or cavity, floor or ducts mounted to monitor: 206

a. After ignition has occurred and the invisible products of combustion are being released. b. When visible smoke is being produced. c. When fire is producing flame and certain degree of a predetermined figure, (RATE OF RISE OR FIXED TEMPERATURE). 8. Automatic Fire Detectors. Automatic fire detection is desirable because fires which occur in premises normally only occupied in daytime have usually reached serious proportions before discovery if they occur at night or weekend. The times included are: a. b. c. Outbreak to discovery. Discovery to call. Call to arrival of Fire Brigade.

9. With today modern appliances and location of fire station the time taken for is at a minimum so ways to reduce the times (a) and (b) have to be found and one of these ways in to install automatic fire detector equipment. The value of this equipment in recognized by insurance companies and they will grant reductions in premiums depending upon the grade of equipment installed. 10. The British Standard Code of Practice No 327/104 lays down specification for design and installation. 11. Automatic fire detectors will be considered under the following heading: a. b. c. 12. Requirements of a good detector and system. The working principles of those detectors. The types of circuits in which they can be installed.

The Detector and System: a. b. c. d. e. f. Must be able to detect fire quickly. Must sound audible alarm. Indicates location of fire. Should not give frequent false alarms. Must not be susceptible to easy damage. Should be reliable throughout its working life.

g. Must not be affected by changes in its surrounding atmosphere and must compensate for ordinary temperature increases. 13. The Working Principles Employed in Detectors. They can break down into three main classes: a. b. c. Those which detect heat. Those which detect smoke or visible vapors. Those which detect flame.

14. All the detected signals by the various forms of detector and sensors will be fed to a central monitor panel called control and indicating panel; or depending on the system design and the vastness of the complexes or the number of building involved, these panels may be known as Master Control Panel, Control Panel, Sub panel or Zone panel. 15. From these panel, alarm will be activated and also if a suppression system is included, the extinguishing agent will be released to put off the fire.

207

16. The input into the alarm and suppression system is if could an electrical voltage which be amplified in most cases and via relays , series of RC and Diode and Transistors, the required voltage, usually 21 volts is fed to either: a. b. c. d. Solenoid coil triggering mechanism. Explosive devices. Hydraulic or pneumatic lever/devices. Other triggering mechanism.

17. All this triggering mechanism will break a disc or open a mechanical valve of some sort to release the suppression extinguishing agent e.g. Foam, Dry Powder, halon Gas, CO2, BCF. 18. These triggering mechanisms are usually situated within the agent cylinders or tanks and normally around the neck area where a small thin but robust metal disc is used to seal off the extinguishing agent under pressure inside the container. 19. Smoke Detectors. As the name implies, it detects smoke long before flame occurs as most fires will start with smoke or smoldering. 20. Type of Smoke Detectors: a. b. Ionization. Optical. (1) (2) (3) Light sea tier type. Obscuration type. Sampling Detectors.

21. Ionization. What is ionization? An atom made up of protons, electrons and neutrons. In its normal condition the protons and electrons are balanced i.e. three of each in ions as shown in diagram. (next page page 5). a. The Theory. If the atom is subjected to radiation from a radioactive source some electrons is knee ked off, resulting in atom becoming positively charge (more protons than electrons). b. The free electrons linkup with another atom and becoming negatively charged (more electrons than protons). These new atom are called ions and the process called ionization.

Fig. 11.1 Diagram of an Atom

208

Fig.11.2 Illustration of ionization

Fig.11.3. Diagram of an ionization detector (Non Fire Condition)

Fig 11.4 Diagram of an Ionization Detector (Fire Condition) 209

c. Thus if the atoms of air in a container is subject to radiation ionization taken place in the same manner but ions moved about haphazardly. By introducing a positively and negatively charged plates a more orderly and predictable movement if ions taken place. Positive ions attached to negative plates and vice versa. The forms the basis of ionization detector movement of ions between plates in the chamber reduces the resistance of the air enabling small electric current flows in the external circuit and amplified for monitoring. d. The Practice. Normally a double chamber ionization detector principle is used. One ionization chamber in a semi scaled environment which does not permit entry of smoke, the other chamber in open to atmosphere allowing smoke to enter. e. In normal condition both the inner and open chambers are free from smoke and formed a balanced electrical circuit. In the cold cathode tube (2) which acts an a switching circuit controlling the operation of the relay. f. When the smoke enters the open chamber, it will slow the movement of ions as explained. As the movement of ions is slowed only in the open chamber this effectively in balances the electrical circuit offering higher resistance to flow of electricity than the inner chamber. Thus voltage or (1) increases causing the cold cathode tube to strike, thus allowing the high current path to operate relay and sound alarm. g. Transistors are actually used as amplifier and switching mechanism in most ionization detectors. Effective sensitivity in early stages of fire where smoke particles are small Thus care to be taken in sitting of these type of detector heads. Kitchen and garages to be avoided, so is ventilation exhaust and fresh air inlet as current of clean air inhibit speed of reaction in fire situation. h. Most types of ionization detector heads are designed to be mounted on ceiling and usually provide coverage for 100 sq meter floor area; with some modification it can be used in air duels and trucking for air celled machinery to give.

Fig 11.5 Illustration of an Ionization Detector

210

22. Optical Detectors. An ionization detector responds to invisible products of combination. Optical detector reacts to visible products of combustion i.e. particles of carbon land other chemical which give smoke its characteristic appearance. Two important components a light source and photoelectric cells. 23. The critical factor in operation of optical detector is the amount of light falling on the photoelectric cells. There are two main types of optical detectors: a. b. Light Scatter Obstruction During fire situation more light is thrown onto the photoelectric cell. Less light thrown onto photoelectric cells.

24. Light Setter Type. The light source and photoelectric cells are mounted in a light proof darken housing allowing smoke to flow uninterrupted. In non fire situation light from the sources does not fall on to the photoelectric cells. 25. During fire condition, some light will be deflected by the smoke upwards to the photoelectric cells. With the falling light, the cell will either create an electrical current in the detector circuit or allowing more current to flow through it (depending on type of cell used). The small increase in current is normally amplified by a transistorized circuit in order to energize relay controlling alarm. Detector is preset so that alarm is given where smoke density reaches a predetermined level. a. Practice. Light scatter are commonly used when smoke scatter the light and on the light and on the photoelectric cell a small electrical charges produced and amplified thus actuating alarm relay which raises the alarm and also switch on indicator lamp on the detector and identify which head is operating. b. Should there be a failure in the power or light supply in the detector, a special relay will signal this at a central point (control panel) and also lithium the indicator lamp on the head; actual fire signal is not produced in this condition. c. The area protected by a detector head will vary depending on risk involved, floor plane and other variables. Nominal area coverage for the detector is 100 square meters per head but for specific risks or areas, this figure can decrease of increase. d. It is possible with modifications, to mount some optical detectors in air ducts for protection of calling, air-cond return and machineries.

An Optical Smoke Detector Light Scatter Non-Fire Condition 26. Obscuration Type: a. Theory. This type works on the reverse of the light scatter principle i.e. the light is obscured (blocked) by smoke thus reducing the intensity of light falling on photoelectric cell causing alarm signal to be raised.

211

b. Practice. Optical detector particularly useful for the protection of large areas, one detector head can throw the light beam from 3 to 45 meters with 6 meter sensitivity on either side. c. Usually the light source and less are housed at the end of the protected area and the photoelectric cell at appetite end (like infra-red beam fire detection system Beam Master). d. L.E.D (Light emitting dudes) are now widely used as light source in optical detector instead of tungsten filament lamp which consume little current and more efficient and long lasting light source.

An Optical Smoke Detector Light Scatter Type (Fire Condition) 27. Sampling Detectors. Consists of a series of small bore sampling tubes located in dire risk zone and are connected to a central monitor unit. The monitor unit continuously samples the atmosphere in protected zone by drawing air through the small holes in the tubes by mean of motor driver fan. The air is then passed through an ionization chamber which is designed to raise the alarm when the level of combustion products reaches a predetermined level a set level. 28. Conclusion. Detection of fire by smoke detectors is dependent on a number of factors e.g. smoke concentration, size and shape of smoke particles i.e. the density of smoke level a resultant of various different materials burnt. In the initial stages of most fires the smoke particles accumulated and combine together forming bigger particles. 27. Ionization detector detects smoke particles and usually more sensitive to smaller invisible smoke particles. Very useful in early stages of relatively clean burning fires e.g. wood and paper. 29. Optical detector is more efficient on dense smoke (if larger particles) in earlier than heat sensitive detector. 30. On the whole, earlier detection can be obtained with a smoke sensitive detector than heat sensitive detector. 31. Radiation Detector: a. b. c. Infra-red radiation. Visible light Ultra-violet radiation.

212

32. Fire, apart from producing hot gases and raising the temperature of its surround, it also releases radiant energy traveling in waves. Thus radiation detectors are produce to detect these sources. 33. Visible light or flame detectors were produced initially to detect light or flame, but these detectors create too many problems as they cannot differentiate between the several of lights and those particularly produced by fire. 34. Therefore, two new types of radiation detectors were made to see and identify actual source from fire. They are: a. b. Infra-red radiation. Ultra-violet radiation.

35. Both these detectors uses photoelectric cell which is sensitive to one of these sources. But these cells and electrical components attached to it must be protected from dust or dirts an moistures but at the same time allowing the infra -red or ultra violet lamp to pass through a certain type of quarts (a crystal stone material). 36. These quartz less is supported by means of special filter/amplifier which allows only one type of source, either an ultraviolet or infra-red radiation. 37. However, flame is not the only producer in infra-red radiation there may be a limited number of other producers e.g. sunlight or heaters. But flame of fire has a distinctive flicker i.e. a frequency or vibration and normally in the range of 4 Hz - 15 Hz. So you can see the function of the filter/amplifier therefore it is range. This signal is then fed to an interrogations/timer which will activate the alarm circuit only if the signal persists for a preset period. (usually 2 15 secs). 38. This small delay may a lightly off set the quick response time of the detector, but necessary to reduce false alarm to a minimum. Once any signal is rejected the detector goes back on standby/monitoring modes. 39. As an infra-red detector must see a flame before it with raise an alarm, the diagram above is useful where the risk is divided into compartments or congested area in which visibility night be impaired. Individual detector head can protect each compartment or be places in strategic position in congested area. 40. For longer areas, free of congestion land with a more open plan, a scanning infra-red detector is available. The deflector continually scan the protected area (approx every 20 secs) in a 360 horizontal cell is stuck by deflected infra -red radiation and the characteristic flicker is identified by the filter/amplifier, the integrator/timers directly and allows the radiation to fall continuously on the photoelectric cell.

Diagram of an Infra Scan Radiation Detector 213

41. The diagram below shows how these components are fitted into an actual detector which also has a neon Flanders to indicate.

Schematic Diagram of an Infra-Red Radiation Detector

Non-Fire Condition

Optical Detector Obscuration Type 42. The timer than check and ensure the flame flicker persists for 2 5 cells. It the flickers do persist beyond this period than the alarm is raised if not than the integrator restarts the deflector motor thus putting the detector on standby/monitor.

214

43. This detector has an amber fault light which light up a few second after a fault is detected, the red alarm light illuminates once the integrator activate the alarm. The lend cover is thermally insulated and the cell and deflector are shielded by quartz globe. 44. Theoretically there is no limit to the range of the infra scan detector but for better efficiency and effect evenness especially in the early stages of the fire, the radius of detection should be limited to about 90 meters. 45. Wider area of coverage can be obtained from the scanning type than from the static type. But any particular types used depend on the area to be protected and the internal plan. 46. Infra-red detectors can provide rapid detection in risk areas where flame is likely to develop at an early stage of combustion because of the almost instantaneous transmission of radiation. And unlike smoke or heat detector infra-red detectors are equally efficient inside or outside of buildings. As it only need to see the flame, where as heat or smoke detectors have to rely on ceilings or walls to direct combustion products to the sensing head. 47. Thus this make the infra-red detector especially scanning type useful for protection of open storage areas e.g. timber yards and fuel depots. 48. The Practice. The principle of operation is very similar to that of the ionization smoke detector. When the ultra violet radiation/rays strikes the gas filled tube it ionizes the gas in the tube, producing a small current between the two elect roles and the tube becomes a conductor of electricity, when the current flow increased beyond the set point of the amplifier the alarm relay closes to sound alarm. The circuit also has a built in delay for 1015 secs to suppress false alarms from lightning, arching sparks etc. 49. The detectors are not sensitive to sun light or artificial light, thus it helps in minimizing false alarm but are sensitive to welding areas, furnaces etc. Usually used for protecting aircraft engine, fuel storage, oil drilling rig, ware house, paint spray booths etc. 50. Ultra Violet Radiation: a. The Theory. Like the infra-red detector, this type also needs to see the flame before it will operate, but since actual sources of ultra violet radiation is very limited, flicker identification is not needed. Basically, the ultra violet detector consists of an amplifier and a photoelectric cell or gas filled tube sensitive to ultra violet radiation.

Diagrammatic Illustration of an Ultra-Violet Detector

215