Sunteți pe pagina 1din 25

Insulator Catalogue

Contestability Approved Insulators

Edition 2009 Insulator Catalogue

For Sales and Technical Support Contact our office Phone: (02) 9726 7702 - Fax: (02) 9726 7703

Email: info@mvtechnology.com.au www.mvtech.com.au

About us
MV Technology Solutions is supplier of a diverse range of high quality products throughout the Asia Pacific region to Power, Railway, Heavy Industry & Mining Customers. Our exceptional service along with high quality brands name products from world leading companies around the globe. These world leading brands and our high level of customer service and technical expertise ensure our customer requirements are seen to on every occasion. Our Product Portfolio includes: POWER AND TRANSMISSION PRODUCTS Cable Accessories & Terminations Fault Circuit Indicators H.V. Fuses & Fuse Assembly Tester Integrated Voltage Indication Systems Insulators & Line Hardware Accessories LV Accessories MV Switching & Components Motor Operating Devices Remote and Area Lighting Safety Products Solvents & Lubricants Surge Protection Testers and Testing Sticks OEM SWITCHGEAR COMPONENTS 11 to 33kV Cable Access. & Terminations DIN H.V. Fuses & Fuse Assembly Tester Indoor Air Insulated Disconnectors Indoor Air Insulated Switches Indoor Air Insulated Earth Switches Indoor Vacuum Circuit Breakers Indoor Vacuum Contactors Integrated Voltage Indication Systems Motor Operating Devices RAIL ROLLING STOCK PRODUCTS Speed Measuring & Data Acquisition Surge Protection for Rolling Stock Specialised Railway Testers

Contents
Voltage
11 kV

Product Group
Longrod Insulator

Approved for use


Energex Approved

Page
3

22 kV

Longrod Insulator

Energy Australia / Integral Energy / Country Energy Approved. SP-AusNet Approved.

22 kV

Longrod Insulator

33 kV

Longrod Insulator

SP-AusNet Approved.

6-7

33kV

Longrod Insulator

Energy Australia

33 kV

Longrod Insulator

Energex Approved

33 kV

Longrod Insulator

Energy Australia Approved

10-11

66 kV

Longrod Insulator

SP-AusNet Approved

12-14

66kV

Longrod Insulator

Commonly used throughout private networks

15

66 kV

Longrod Insulator

Integral Energy Approved

16

132 kV

Longrod Insulator

Energex Approved

17-18

66 kV

Horz Post Insulator

Energy Australia Approved

19-20 1 | Page 21-24

132 kV

Horz Post Insulator

Energy Australia Approved

Insulators Long Rod


11 kV Long Rod Insulator EHSIN001/A
(ENERGEX APPROVED)

Drawing number One minute power frequency withstand voltage, 50Hz, wet Lightning impulse withstand voltage, 1,2/50, pos. Arcing distance Minimum creepage distance Specified mechanical load (SML) Routine test load (RTL) Number of sheds Weight (approx.) Clevis in acc. to IEC 60471 (16L) Tongue in acc. to IEC 60471 (16L) SML and RTL are in acc. to IEC 61109 Material Data: Insulator End Fitting Cotter Pin

144 015-044 45 kV 127 kV 160 mm 385 mm 70 kN 55 kN 4 1.1 kg

E-CR Glassfibre rod with HTV Silicone Rubber Housing Steel Cast or Machined - Hot Dip Galv. acc. to EN ISO 1461 Stainless Steel

3 | Page

Insulators Long Rod


22 kV Longrod Insulator EHSIN09/A (ENERGY AUSTRALIA /INTEGRAL ENERGY/COUNTRY ENERGY
. APPROVED)

Drawing number One minute power frequency withstand voltage, 50Hz, wet Lightning impulse withstand voltage, (1,2/50, pos.) Arcing distance Minimum creepage distance Specified mechanical load (SML) Routine test load (RTL) Number of sheds Weight (approx.) Tongue in acc. to IEC 60471 Clevis in acc. to IEC 60471 SML to RTL are in acc. to IEC 61109 Galvanizing (h.d.g.) acc. to EN ISO 1461 Material Data: Insulator End Fittings

144 060-001 110 kV 240 kV 310 mm 765 mm 70 kN 55 kN 8 1.3

E-CR Glassfibre rod with HTV Silicone Rubber Housing Steel Machined Hot Dip Galv. acc. to EN ISO 1461 Stainless Steel

Cotter Pin

4| Page

Insulators Long Rod


22 kV Longrod Insulator - EHSIN19/B (SP-AUSNET APPROVED)

Drawing number One minute power frequency withstand voltage, 50Hz, wet Lightning impulse withstand voltage, 1,2/50, pos. Minimum Arcing distance Minimum creepage distance Specified mechanical load (SML) Routine test load (RTL) Number of sheds Mass(approx.) Ball in acc. to IEC 60120(16) Socket in acc. to IEC 60120(16A) SML and RTL are in acc. to IEC 61109 Material Data: Insulator End Fitting Cotter Pin

144 030-005 60 kV 165 kV 225 mm 560 mm 70 kN 55kN 6 1.27 kg

E-CR Glassfibre rod with HTV Silicone Rubber Housing Steel (Cast or Machined) - Hot Dip Galv. acc. to EN ISO 1461 Stainless Steel

5 | Page

Insulators Long Rod


33 kV Longrod Insulator EHSIN11/A (SP-AUSNET APPROVED)

Drawing number One minute power frequency withstand voltage, 50Hz, wet Lightning impulse withstand voltage, (1,2/50, pos.) Minimum Arcing distance Minimum creepage distance Specified mechanical load (SML) Routine test load (RTL) Number of sheds Mass (approx.) Clevis in acc. to IEC 60471 (16L) Tongue in acc. to IEC 60471 (16 L) SML to RTL are in acc. to IEC 61109 Material Data: Insulator End Fittings Humpback Split Pin

144 065-001 135 kV 280 kV 440 mm 970 mm 70 kV 55 kV 8 1.7 kg

E-CR Glassfibre rod with HTV Silicone Rubber Housing Steel Machined Hot Dip Galv. acc. to EN ISO 1461 Stainless Steel

6 | Page

Insulators Long Rod


33 kV Longrod Insulator EHSIN11/B (SP-AUSNET APPROVED)

Drawing number One minute power frequency withstand voltage, 50Hz, wet Lightning impulse withstand voltage, (1,2/50, pos.) Minimum Arcing distance Minimum creepage distance Specified mechanical load (SML) Routine test load (RTL) Number of sheds Mass (approx.) Ball in acc. to IEC 60120 (16) Socket in acc. to IEC 60120 (16A) SML to RTL are in acc. to IEC 61109 SML and RTL are in acc. to IEC61109 Material Data: Insulator End Fittings Cotter Pin

144 065-005 135 kV 280 kV 440 mm 970 mm 70 kV 55 kV 8 1.7 kg

E-CR Glassfibre rod with HTV Silicone Rubber Housing Steel Hot Dip Galv. Acc. to EN ISO 1461 Stainless steel

7 | Page

Insulators Long Rod


33 Kv Longrod Insulator - EHSIN14/B (Energy Australia Approved)

Drawing number One minute power frequency withstand voltage, 50Hz, wet Lightning impulse withstand voltage, (1,2/50, pos.) Arcing distance Minimum creepage distance Specified mechanical load (SML) Routine test load (RTL) Number of sheds (small/large) Material of fittings Weight (approx.) Ball in acc. to IEC 60120(16) Socket in acc. to IEC 60120 (16A) SML and RTL are in acc. to IEC 61109 Galvanizing (h.d.g.) acc. to EN ISO 1461

145-231-013 105 kV 220 kV 380 mm 1000 mm 70 kN 55 kN 8 Steel, h.d.g. 1.2 kg

8 | Page

Insulators Long Rod


33 kV Longrod Insulator EHSIN13/A (ENERGEX APPROVED)

Drawing number One minute power frequency withstand voltage, 50Hz, wet Lightning impulse withstand voltage, (1,2/50, pos.) Minimum Arcing distance Minimum creepage distance Specified mechanical load (SML) Routine test load (RTL) Number of sheds (small/large) Mass (approx.) Clevis in acc. to IEC 60471 (16L) Tongue in acc. to IEC 60471 (16L) SML and RTL are in acc. to IEC 61109 Material Data: Insulator End Fittings Humpback Split Pin

144 070-044 93 kV 211 kV 290 mm 1000 mm 70 kV 55 kV 5/6 1.5 kg

E-CR Glassfibre rod with HTV Silicone Rubber Housing Steel Hot Dip Galv. Acc. to EN ISO 1461 Stainless steel

9 | Page

Insulators Long Rod


33 kV Longrod Insulator EHSIN14/A (ENERGY AUSTRALIA APPROVED)

Drawing number One minute power frequency withstand voltage, 50Hz, wet Lightning impulse withstand voltage, (1,2/50, pos.) Minimum Arcing distance Minimum creepage distance Specified mechanical load (SML) Routine test load (RTL) Number of sheds Mass (approx.) Tongue in acc. to IEC 60471 (16L) Clevis in acc. to IEC 60471 (16L) SML and RTL are in acc. to IEC 61109 Material Data: Insulator End Fitting Humpback Split Pin

144-075-001 105 kV 255 kV 380 mm 1000 mm 70 kN 55 kN 8 1.2 kg

E-CR Glassfibre rod with HTV Silicone Rubber Housing Steel (cast) Hot Dip Galv. Acc. to EN ISO 1461 Stainless steel

10 | Page

Insulators Long Rod


33 kV Longrod Insulator EHSIN16/A (ENERGY AUSTRALIA APPROVED)

Drawing number One minute power frequency withstand voltage, 50Hz, wet Lightning impulse withstand voltage, (1.2/50, pos.) Arcing distance Minimum creepage distance Specified mechanical load (SML) Routine test load (RTL) Number of sheds (small/large) Material fittings Mass (approx.) SML and RTL are in acc. to IEC 61109 Galvanizing (h.d.g.) acc. to EN ISO 1461

144 090-001 146 kV 285 kV 430 mm 1200 mm 70 kN 55 kN 12 Steel, h.d.g. 1.7 kg

11 | Page

Insulators Long Rod


66 kV Longrod Insulator EHSIN51/A (SP-AUSNET APPROVED)

Drawing number One minute power frequency withstand voltage, 50Hz, wet Lightning impulse withstand voltage, 1,2/50, pos. Minimum Arcing distance Minimum creepage distance Specified mechanical load (SML) Routine test load (RTL) Number of sheds (small/large) Mass(approx.) Tongue / Clevis coupling size acc. to IEC 60471 (19L) SML and RTL are in acc. to IEC 61109 Material Data: Insulator End Fitting Clevis Pin Split Pin

144 021-007 230 kV 400 kV 720 mm 2250 mm 120 kN 60 kN 12/13 5kg

E-CR Glassfibre rod with HTV Silicone Rubber Housing Drop forged steel - Hot Dip Galv. acc. to EN ISO 1461

Steel - Hot Dip Galv. acc to EN ISO 1461 Stainless Steel

12 | Page

Insulators Long Rod


66 kV Longrod Insulator EHSIN51/D

(SP-AUSNET APPROVED)

Drawing number One minute power frequency withstand voltage, 50Hz, wet Dry power frequency withstand voltage (50Hz) Lightning impulse withstand voltage, (1.2/50, pos.) Minimum Arcing distance Minimum creepage distance Specified mechanical load (SML) Routine test load (RTL) Number of sheds (small/large) Mass (approx.) Ball in acc. to IEC 60120 (16) Y-Clevis in acc. to IEC 61466-1 (19) SML and RTL are in acc. to IEC 61109 Material Data: Insulator: End Fittings: Y-Clevis Pin: Humpback Split Pin:

144 021-019 230 kV 250 kV 400 kV 720 mm 2250 mm 120 kN 60 kN 15/16 3.5

E-CR Glassfibre rod with HTV Silicone Rubber Housing Drop forged steel - Hot Dip Galv. acc. to EN ISO 1461 H.T. Steel (Grade 8.8) - Hot Dip Galv. acc. to EN ISO 1461 Stainless Steel

13 | Page

Insulators Long Rod


66 kV Longrod Insulator EHSIN51/A (SP- AUSNET APPROVED)

Drawing number System Voltage, Um One minute power frequency withstand voltage, 50Hz, wet Lightning impulse withstand voltage, (1.2/50, pos.) Minimum Arcing distance Minimum creepage distance Specified mechanical load (SML) Routine test load (RTL) Number of sheds (small/large) Mass (approx.) Ball in acc. to IEC 60120 Socket in acc. to IEC 60120 (A) SML and RTL are in acc. to IEC 61109 Material Data: Insulator End Fittings

460/2250BZ 72.5 230 kV 400 kV 720 mm 2250 mm 120 kN 60 kN 12/13 3kg

E-CR Glassfibre rod with HTV Silicone Rubber Housing Drop forged steel - Hot Dip Galv. acc. to EN ISO 1461 Stainless Steel

Cotter Pin

14 | Page

Insulators Long Rod


66 kV Longrod Insulator EHSIN51/B (Commonly used throughout private networks)

Drawing number One minute power frequency withstand voltage, 50Hz, wet Lightning impulse withstand voltage, (1,2/50, pos.) Minimum Arcing distance Minimum creepage distance Specified mechanical load (SML) Routine test load (RTL) Number of sheds (small/large) Mass (approx.) Ball in acc. to IEC 60120 (16) Socket in acc. to IEC 60120 (16A) SML and RTL are in acc. To IEC 61109 Material Data: Insulator End Fittings Cotter Pin

144 021-006 230 kV 400 kV 720 mm 2250 mm 120 kV 60 kV 12/13 3 kg

E-CR Glassfibre rod with HTV Silicone Rubber Housing Drop forged steel - Hot Dip Galv. acc. to EN ISO 1461 Stainless Steel

15 | Page

Insulators Long Rod


66 kV Longrod Insulator EHSIN51/C (INTEGRAL ENERGY APPROVED)

Drawing number One minute power frequency withstand voltage, 50Hz, wet Lightning impulse withstand voltage, 1,2/50, pos. Minimum Arcing distance Minimum creepage distance Specified mechanical load (SML) Routine test load (RTL) Number of sheds Mass (approx.) Eye in acc. to IEC 61466 (24) SML and RTL are in acc. to IEC 61109 Material Data: Insulator End Fittings

144-021-011 230 kV 400 kV 720 mm 2250 mm 120 kN 60 kN 12/13 3.3 kg

E-CR Glassfibre rod with HTV Silicone Rubber Housing Drop forged steel - Hot Dip Galv. acc. to EN ISO 1461

16 | Page

Insulators Long Rod


132 kV Longrod Insulator EHSINT70/D (ENERGEX APPROVED)

Drawing number One minute power frequency withstand voltage, 50Hz, wet Lightning impulse withstand voltage, 1,2/50, pos. Minimum Arcing distance Minimum creepage distance Specified mechanical load (SML) Routine test load (RTL) Number of sheds (small/large) Mass (approx.) Ball in acc. to IEC 60120 (16) Eye in acc. to IEC 61466 (24) SML and RTL are in acc. to IEC 61109 Material Data: Insulator End Fittings

144 032-005 355 kV 750 kV 1321 mm 4500 mm 120 kN 60 kN 23/24 5.4 kG

E-CR Glassfibre rod with HTV Silicone Rubber Housing Drop forged steel - Hot Dip Galv. acc. to EN ISO 1461

17 | Page

Insulators Long Rod


132 kV Longrod Insulator EHSIN70/D (ENERGEX APPROVED)

Drawing number One minute power frequency withstand voltage, 50Hz, wet Lightning impulse withstand voltage, 1,2/50, pos. Minimum Arcing distance Minimum creepage distance Specified mechanical load (SML) Routine test load (RTL) Number of sheds (small/large) Mass (approx.) Eye in acc. to IEC 61466-1 (24) SML and RTL are in acc. to IEC 61109 Material Data: Insulator End Fitting

144 032-010 355 kV 750 kV 1321 mm 4500 mm 230 kN 60 kN 23/24 5.4 kg

E-CR Glassfibre rod with HTV Silicone Rubber Housing Drop forged steel - Hot Dip Galv. acc. to EN ISO 1461

18 | Page

Insulators Horz Post Insulator


66 kV Horz Post Insulator EHSIP51/C (ENERGY AUSTRALIA APPROVED)

Drawing number One minute power frequency withstand voltage, 50Hz, wet Lightning impulse withstand voltage, (1.2/50, pos.) Arcing distance Minimum creepage distance Specified cantilever load (SCL) Maximum design cantilever load (MDCL) Number of small/large sheds Weight SCL and MDCL are in acc. to IEC 61952 Galvanizing (h.d.g.) acc. to EN ISO 1461

145 241-010H 140 kV 350 kV 580 mm 2250 mm 12.5 kN 6 kN 9/10 12.8 kg

19| Page

Insulators Horz Post Insulator


66 kV Horz Post Insulator EHSIP51/B (ENERGY AUSTRALIA APPROVED)

Drawing number One minute power frequency withstand voltage, 50Hz, wet Lightning impulse withstand voltage, (1.2/50, pos.) Arcing distance Minimum creepage distance Specified cantilever load (SCL) Maximum design cantilever load (MDCL) Number of small/large sheds Weight SCL and MDCL are in acc. to IEC 61952 Galvanizing (h.d.g.) acc. to EN ISO 1461

145 241-015 140 kV 350 kV 580 mm 2250 mm 12.5 kN 5.5 kN 9/10 12.5 kg

20| Page

Insulators Horz Post Insulator


132 kV Horz Post Insulator EHSIP74/C (ENERGY AUSTRALIA APPROVED)

Drawing number One minute power frequency withstand voltage, 50Hz, wet Lightning impulse withstand voltage, (1.2/50, pos.) Minimum Arcing distance Minimum creepage distance Specified cantilever load (SCL) Maximum design cantilever load (MDCL) Specified mechanical tensile load (SML) Number of small/large sheds Mass (Approx.) SCL and MDCL are in acc. to IEC 61952 Material Data: Insulator End Fittings Bendable Base

145 231-013-H 375 kV 720 kV 1218 mm 4500 mm 13.3 kN 6 kN 50 kN 19/20 30 kg

E-cr Glassfibre rod with HTV Silicone Rubber Housing Steel - Hot Dip Galvanized, Pressed Base Plate Steel - Press Formed & Hot Dip Galvanized, acc. to EN ISO 1461

21 | Page

Insulators Horz Post Insulator


132 kV Horz Post Insulator EHSIP76/B (ENERGY AUSTRALIA APPROVED)

Drawing number One minute power frequency withstand voltage, 50Hz, wet Lightning impulse withstand voltage, (1.2/50, pos.) Minimum Arcing distance Minimum creepage distance Specified cantilever load (SCL) Maximum design cantilever load (MDCL) Number of small/large sheds Mass (Approx.) SCL and MDCL are in acc. to IEC 61952 Material Data: Insulator End Fittings Bendable Base

145 231-014 375 kV 720 kV 1218 mm 4500 mm 13.3 kN 5.3 kN 19/20 31 kg

E-CR Glassfibre rod with HTV Silicone Rubber Housing Steel - Hot Dip Galvanized, acc. to EN ISO 1461 Plate Steel - Press Formed & Hot Dip Galvanized, acc. to EN ISO 1461

22| Page

Insulators Horz Post Insulator


132 kV Longrod Horz Post Insulator EHSIP74/C (ENERGY AUSTRALIA APPROVED)

Drawing number One minute power frequency withstand voltage, 50Hz, wet Lightning impulse withstand voltage, 1,2/50, pos.) Arcing distance Minimum creepage distance Specified cantilever load (SCL) Maximum design cantilever load (MDCL) Number of sheds (small/large) SCL and MDCL are in acc. to IEC 61952

145 231-013 350 kV 720 kV 1218 mm 4500 mm 13.3 kN 5.3 kN 19/20

Galvanizing (h.d.g.) acc. to EN ISO 1461 Insulator: E-cr Glassfibre rod with HTV Silicone Rubber Housing End Fitting: Steel, Hot Dip Galvanized, Pressed Base.

23 | Page

Insulators Horz Post Insulator


132 kV Horz Post Insulator EHSIP72/C (ENERGY AUSTRALIA APPROVED)

Drawing number One minute power frequency withstand voltage, 50Hz, wet Lightning impulse withstand voltage, (1.2/50, pos.) Minimum Arcing distance Minimum creepage distance Specified cantilever load (SCL) Maximum design cantilever load (MDCL) Specified mechanical tensile load (SML) Number of small/large sheds Mass (Approx.) Material Data: Insulator End Fittings

145 231-015H 375 kV 720 kV 1218 mm 4500 mm 13.3 kN 6 kN 50 kN 19/20 27 kg

E-cr Glassfibre rod with HTV Silicone Rubber Housing Steel - Hot Dip Galvanized, acc. to EN ISO 1461

24 | Page

MV Technology Solutions
MV Technology Solutions is an Australian company that supplies a diverse range of high quality products for Power and Rail sector throughout Australia and New Zealand

OUR OFFERINGS
MV Technology Solutions only partner with leading brands to ensure your products are of high quality and meet both our local electrical requirements and withstand our vast variety of climates within Australia and New Zealand

TECHNICAL SUPPORT
MV Technology Solutions have the capabilities to assist you in correct selection of your product requirements ensuring your equipment will meet the desired application for every project on every occasion.

CUSTOMER SERVICE
Please contact our customer service office for any further information Ph: +61 (0) 2 9726 7702 Flowline Industries Pty Ltd Fax: +61 (0)2 9726 7703 Email: info@mvtechnology.com.au

Phone: (02) 9726 7702 - Fax: (02) 9726 7703 www.mvtech.com.au


Subject to change without prior notice. The information in this document contains general descriptions of the technical options available, which may not apply in all cases. The required technical options should therefore be specified in the contract.