5
5.1 menu setting..........................................................................................................................6 5.1.1 Test parameters setting..............................................................................................6 5.1.2 date time setting.........................................................................................................7 5.1.3Option.......................................................................................................................7 5.1.4Delete definitions.....................................................................................................7 5.1.5 State check.................................................................................................................7 5.2Test in main menu........................................................................................................7 5.2.1 Test sequence..............................................................................................................7 5.2.2 Low voltage test.........................................................................................................7 5.3View in main menu......................................................................................................7 5.3.1Curves ......................................................................................................................8 5.3.2Comprehensive data.................................................................................................8 5.3.3 Bounce........................................................................................................................8 5.3.4 Speed analysis............................................................................................................8 5.3.5 Print............................................................................................................................9 5.3.6 Comprehensive print..................................................................................................9 5.3.7 Curves zoom in..........................................................................................................9 5.4File in main menu........................................................................................................9 5.4.1Open file...................................................................................................................9 5.4.2 Save file......................................................................................................................9
6 Test connection.........................................................................9
6.1 Time channels and earth connection...........................................................................10 6.2 Closing and opening control lines connection............................................................10
7 Sensor installation...................................................................10
7.1 Universal sensor (Acceleration sensor)......................................................................10 7.2Angle sensor.................................................................................................................11 7.3 Line sensor .................................................................................................................11
7 Accessories list.......................................................................12
1 Technique index
1) Power supply: AC220V10% 50Hz10% 2) Temperature: 10~40 humidity: <80% 3) Insulation resistance >2Mohm, 1.5kv voltage withstand 1minute no breakdown. 4) Time measurement range: 400ms, resolution 0.1ms Time measurement error <0.2ms 5) Speed measurement: Range 2m/s resolution 0.01m/s max error<0.1m/s Range 20m/s resolution 0.01m/s max error<0.2m/s 6) Travel measurement: Range 50.0mm resolution 0.1mm max error<1%RGD+0.1%FS Range 300.0mm resolution 1mm max error<1%RGD+0.1%FS Range 600.0mm resolution 1mm max error<1%RGD+0.1%FS 7) Coil current measurement range 20.00A, resolution 0.01A, error 2%+0.2%FS 8) Closing resistance value measurement range: 100~10000ohm, error: 5%RGD 9) DC Power out: DC30V~250V/20A (instantaneous) 10) Size: 360mm*280mm*300mm 11) Weight: 10kg
2 Main Functions
1) Test standard: IEC62271 2) Closing and opening time measurement of 12 channels 3) Max difference of closing or opening time measurement of three phases 4) C-O and O-C time measurement 5) Rated operation sequence test 6) Bounce time and frequency measurement of breaker closing 7) Circuit breaker closing and opening speed measurement 8) Travel-time, Coil current-time curve of circuit breaker operation measurement 9) Travel and clearance of circuit breaker measurement 10) Variable DC circuit breaker operation power supply 11) Closing arc resistance value and connected time measurement 12) Closing time and opening time of graphite circuit breaker measurement 13) Print test results by internal micro printers
3 Definitions
1) Closing time and opening time: reference to IEC62271 2) Max difference in three phases: reference to IEC62271 3) Max difference in the same phase: the max closing/Opening difference in the same phases 4) Closing and opening speed: reference to IEC62271 5) Average closing and opening speed: 10%~90% travel range average speed 6) Max speed: The max speed value calculation from per 10ms range. For example 0~10ms speed V1, 10~20ms speed V2, 20~30ms speed V3.Vx. Max speed is the max value in those calculation data. 7)
Item
Functions Earth grounding connection 12 channels time measurement ports is the reference ground of A3 B3 C3/A4 B4 C4 it is not connected to earth
Keys
Micro printer
Close and open control by internal power source. The trip signal output by the tester Connected to close or open coil in parallel. The voltage trip in coil would start the measurement program Connected to travel and speed sample sensors Calibration port or save data to flash disk AC220V10% 50Hz10% 10A power supply All parameters setting and test data are showed in this LCD Contrast adjustment Cursor position setting Cursor position setting [ok] confirm current setting or start test [cancel] back to previous menu [Reset] Reset the software system of the tester Print the test data and curves
5 Software operation
The start-up screen figure 2 would be showed on the LCD when tester is powered on
5.1.3 Option
LCD display items setting. Please hold the factory value.
5.3.1 Curves
The curves in the test results include the channel state-time curve, travel-time curve and coil current-time curve. All those curve are displayed in the same time coordinate system.
5.3.3 Bounce
Display the bounce time and bounce frequency of channels. Press down ok in detail the detail information of the bounce would be showed.
5.3.5 Print
Print the content of current LCD show.
6 Test connection
Warning: For safety reasons please connect the earth to the earth connection( ) on the
panel first when the tester is located in the power station. The earth connection is the last connection uninstall in the power station
7 Sensor installation
The configuration of the tester includes three different sensors. They are line, angle and universal sensor. The connection cable of the three sensor are the same one.
7.2Angle sensor
The universal sensor is applied to replace the line sensor. But some circuit breaker in the market can not find a line movement parts in the breaker body. All the line movement parts have been sealed in the body of the circuit breaker. There is only a rotate part could be found in the circuit breaker. You would have to measure the speed and travel by the rotate part of the circuit breaker. Angle sensor is designed for this application. The installation of angle sensor is as figure 4
7 Accessories list
Main box Universal sensor Accessories box Closing and opening conrol cable Time channel cable4M+6M Grounding cable Power cable Print paper Pass certificate 1 1 1 1 6 1 1 2 1 Unit Unit Unit Set Unit Unit Unit Unit Unit
1 1
unit unit