Datasheet

Compact size and well known for its proven reliability, the AR-Series utilizes the hydraulic magnetic principle which provides precise operation and performance even when exposed to extremely hot and/or cold application environments. Features: Blue housing 1-6 poles, 0.1 - 50 amps, up to 277 VAC or 80 VDC, Precise, temperature independant, operation Choice of time delays, terminals and actuator colors.

Our Circuit Breakers are designed according to railway regulations: - IEC 60077 - 1/2/3 - NF F62-001 - 1/2/3 - EN 45545-2 & NF F16-101/102 (fire and toxic regulations)

Proven Reliability

Genaral tecnical dats

General technical specifications - AR-Series

Electrical Maximum Voltage Current Ratings

Standard Voltage Coils Auxiliary Switch Rating

Insulation Resistance Dielectric Strength

277VAC 50/60 Hz, 80VDC Standard current coils: 0.100, 0.250, 0.500, 0.750, 1.00, 2.50, 5.00, 7.50, 10.0, 15.0, 20.0, 25.0, 30.0, 35.0, 40.0, 50.0. Other ratings available - consult ordering scheme. DC-6V, 12V; AC-120V, Other ratings available, consult ordering scheme. SPDT; 10.1 A - 250VAC, 1.0 A-65VDC/0.5 A - 80 VDC, 0.1A - 125VAC (with gold contacts). Minimum: 100 Megohms at 500 VDC 1500V 60 Hz for one minute between all electrically isolated terminals. AR-Series rocker circuit breakers comply with the 8mm spacing & 3750V dielectric requirements from hazardous voltage to operator accessible surfaces. Pulse Tolerance Curves

Resistance, Impedance
RESISTANCE, IMPEDANCE VALUES from Line to Load Terminals (Values Based on Series Trip Circuit Breaker)
1000

CURRENT (AMPS)
100

TOLERANCE (%) 15%


Multiple of Rated Current

Ir

60 Hz 1/2 Cycle Inrush Pulse Tolerance


Time Delay Curves 42, 44 & 46 (50 Amps Max.)
Ir

0.10 - 5.0 5.1 - 20.0 20.1 - 50.0

50 Hz 1/2 Cycle Inrush Pulse Tolerance


Time Delay Curves 42, 44 & 46 (50 Amps Max.) Time Delay Curves 22, 24 & 26 (50 Amps Max.) t 5.0 10.0 20.0

25% 35%

Multiple of Rated Current


t

25x

10

22x

O H M S

12x

Time Delay Curves 22, 24 & 26 (50 Amps Max.)

10x

0.1

4.165

8.33

16.67

Time in Milliseconds
0.01

Time in Milliseconds

0.001 0.01

0.1

10

100

AMPERE RATING

Mechanical Endurance Trip Free Trip Indication

10,000 ON-OFF operations @ 6 per minute; with rated Current & Voltage. All AR-Series Circuit Breakers will trip on overload, even when the actuator is forcibly held in the ON position. The operating actuator moves positively to the OFF position when an overload causes the circuit breaker to trip. When mid-trip handle is specified, the handle moves to the mid position on electrical trip of the circuit breaker. When mid-trip handle with alarm switch is specified, the handle moves to the mid position & the alarm switch actuates when the circuit breaker is electrically tripped. 1 - 6 Poles at 30 Amps or less. 1 and 2 poles at 31 Amps thru 50 Amps. Series, (with or without auxiliary switch), Shunt with current or voltage trip coils, Dual Coil, Switch Only with or without auxiliary switch. Approximately 65 grams/pole. (Approximately 2.32 ounces/pole) Housing - Blue; Actuator - White with dual legends. Withstands 100 Gs, 6ms, sawtooth while carrying rated current. Instantaneous and ultra-short curves tested @ 90% of rated current. Withstands 0.060" excursion from 10-55 Hz, and 10 Gs 55-500 Hz, at rated current. Instantaneous and ultrashort curves tested at 90% of rated current. Ten 24-hour cycles @ + 25C to +65C, 80-98% RH.56 days @ +85C, 85% RH. 90-95% RH @ 5% NaCl Solution, 96 hrs. Five cycles @ -55C to +25C to +85C to +25C. -40 C to +85 C

Physical Number of Poles Internal Circuit Configurations Weight Standard Colors Environmental Shock Vibration Moisture Resistance Salt Spray Thermal Shock Operating Temperature

http://www.morssmittrelais.com

Ordering Scheme - AR-Series

AR
1 Series

1
2 Poles

610
3 Current Rating

24
4 Frequency & Delay

B A
5 Circuit 6 Actuator

1
7 Actuator Color

3
8 Aux/Alarm Switch

3
9 Terminal

1
10 Mounting/ Barriers

1
11 Agency approval

1 SERIES AR

8 AUXILIARY/ALARM SWITCH 5 0 2 3 One Two 3 4 Three Four 5 6 Five Six w/o Aux Switch S.P.D.T., 0.110 Q.C. Term. S.P.D.T., 0.139 Solder Lug 4 S.P.D.T., 0.110 Q.C. Term. (Gold Contacts)

2 POLES 1 2 9 TERMINAL9 110 2 311 4 511 6 7 8 9 B Push-On 0.250 Tab (Q.C.) Screw 8-32 w/upturned lugs Screw 8-32 (Bus Type) Screw 10-32 w/upturned lugs Screw 10-32 (Bus Type) Screw 8-32 w/upturned lugs and 30 bend Screw 8-32 (Bus Type) and 30 bend Screw 10-32 w/upturned lugs and 30 bend Screw 10-32 (Bus Type) and 30 bend Screw M5 w/upturned lugs C E11 F G H M11 Q R T11 Screw M4 w/upturned lugs Screw M4 (Bus Type) Screw M5 w/upturned lugs and 30 bend Screw M5 (Bus Type) and 30 bend Screw M5 (Bus Type) M6 Threaded Stud Push-In Stud Screw M4 w/upturned lugs and 30 bend Screw M4 (Bus Type) and 30 bend

3 CURRENT RATING (AMPERES) 210 215 220 225 230 235 240 245 250 255 260 265 270 275 280 0.100 0.150 0.200 0.250 0.300 0.350 0.400 0.450 0.500 0.550 0.600 0.650 0.700 0.750 0.800 285 290 295 410 512 415 517 420 522 527 430 435 440 445 450 0.850 0.900 0.950 1.000 1.250 1.500 1.750 2.000 2.250 2.750 3.000 3.500 4.000 4.500 5.000 455 460 465 470 475 480 485 490 495 610 710 611 711 612 712 5.500 6.000 6.500 7.000 7.500 8.000 8.500 9.000 9.500 10.000 10.500 11.000 11.500 12.000 12.500 613 614 615 616 617 618 620 622 624 625 630 6358 6408 6458 6508 J65 K20 L40 13.000 14.000 15.000 16.000 17.000 18.000 20.000 22.000 24.000 25.000 30.000 35.000 40.000 45.000 50.000 65 AC 120 AC 240 AC

10 MOUNTING/BARRIERS MOUNTING STYLE Threaded Inserts, 2 per pole 6-32 x 0.195 inches 6-32 X 0.195 inches ISO M3 x 5mm ISO M3 x 5mm BARRIERS no yes no yes

OR VOLTAGE COIL (NOMINAL RATED VOLTAGE)6 A06 6 DC A32 32 DC J12 12 AC A12 12 DC A48 48 DC J18 18 AC A18 18 DC A65 65 DC J24 24 AC A24 24 DC J06 6 AC J48 48 AC * Other values on request 4 FREQUENCY & DELAY 03 106 11 12 14 16 206 21 22 24 26 DC 50/60Hz, Switch Only DC Instantaneous DC Ultra Short DC Short DC Medium DC Long 50/60Hz Instantaneous 50/60Hz Ultra Short 50/60Hz Short0 50/60Hz Medium 50/60Hz Long 30 31 32 34 36 427 447 467 527 547 567

1 A 2 B

11 AGENCY APPROVAL 112 DC, 50/60Hz Instantaneous DC, 50/60Hz Ultra Short DC, 50/60Hz Short DC, 50/60Hz Medium DC, 50/60Hz Long 50/60Hz Short, Hi-Inrush 50/60Hz Medium, Hi-Inrush 50/60Hz Long, Hi-Inrush DC, Short,Hi-Inrush DC,Medium, Hi-Inrush DC, Long, Hi-Inrush UL-Recognized, CSA, TUV to EN60077 and NF F62-001

5 CIRCUIT A2 B C D3 Switch Only (No Coil) Series Trip (Current) Series Trip (Voltage) Shunt Trip (Current) E3 H3,4 Shunt Trip (Voltage) Dual Coil with Shunt Trip Voltage Coil
Notes: 1 Actuator Code: A: Handle tie pin spacer(s) and retainers provided unassembled with multi-pole units. S: Handle moves to mid-position only upon electrical trip of the breaker. Available with circuit codes B, C, D, E, and H. T: Handle moves to mid-position and alarm switch activates only upon electrical trip of the breaker. Available with circuit codes B & C. 2 Switch Only circuits, rated up to 50 amps and 6 poles, and only available when tied to a protected pole (Circuit Code B, C, D or H.), For .01 to 30 amps, select Current Code 630. For 35 - 50 amps, select Current Code 650. 3 Available with terminal Codes 1, 2 and 3. Current Rating limited to 30 amps maximum. 4 Consult factory for available Dual Coil options, as special catalog number is required. With Shunt construction, Dual Coils will trip instantaneously on line voltage. Dual coils require 30VA minimum power to trip and are rated for intermittent duty only. 5 On multi-pole breakers, one auxilary switch is supplied, mounted in the extreme right pole. 6 Separate pole type voltage coils not rated for continuous duty. Available only with delay codes 10, 20 & 30. 7 Available with Circuit Codes B & D only and up to 30 amps. 8 Available up to two poles with AC or DC delays. 9 Screw Terminals are recommended on ratings greater than 20 amps. Ratings over 30 amps are only available with Terminal Codes 5, 9, G and H. 10 Terminal Code 1: up to 30 amps, but not recommended over 20 amps. 11 Terminal Codes 3, 5 , 7, 9, E, G and H (Bus Type) are supplied with Lock Washers. Terminal Code M (M6 Threaded Stud) is supplied with lock and flat washers. Preliminary test results showed that the breakers comply to the EN60077 and NF F62-001. 12 Certificates for UL-Recognized and CSA are available on request. For the EN60077 and NF F62-001 the certificates will be available in short notice.

6 ACTUATOR 1 A S T Handle, one per pole Mid-Trip Handle, one per pole Mid-Trip Handle, one per pole & Alarm Switch

7 ACTUATOR COLOR & LEGEND Actuator Color White Black Red Green Blue Yellow Gray Orange I-O A C F H K M P R Dual 1 2 3 4 5 6 7 8 Legend Color Black White White White White Black Black Black

http://www.morssmittrelais.com

Time Delay Values - AR-Series


PERCENT OF RATED CURRENT DELAY 100% 125% 135% 150% 200% 400% 600% 800% 1000% 1200%

10 11 12 14 16 20 21
TRIP TIME (SECONDS)

No Trip No Trip No Trip No Trip No Trip No Trip No Trip No Trip No Trip No Trip No Trip No Trip No Trip No Trip No Trip No Trip No Trip No Trip No Trip

May Trip .013 - .125 .500 - 6.50 2.00 - 60.0 45.0 - 345 May Trip .014 - .150 .700 - 12.0 10.0 - 160 50.0 - 700 May Trip May Trip May Trip .700 - 12.0 7.00 - 100 50.0 - 700 .500 - 6.50 1.50 - 50.0 45.0 - 345

--------------------.400 - 8.00 1.80 - 100 35.0 - 520 -------------

.032 MAX .010 - .070 .300 - 3.00 1.20 - 40.0 20.0 - 150 .040 MAX .011 - .095 .350 - 4.00 6.00 - 60.0 32.0 - 350 .300 - 4.00 1.20 - 60.0 20.0 - 350 .400 - 6.00 3.00 - 50.0 31.0 - 350 .340 - 4.50 .750 - 35.0 19.0 - 170

.024 MAX .008 - .032 .130 - 1.20 .600 - 20.0 9.00 - 60.0 .035 MAX .008 - .055 .130 - 1.30 2.20 - 20.0 10.0 - 90.0 .130 - 1.30 .600 - 20.0 9.00 - 90.0 .180 - 2.30 1.10 - 18.0 12.0 - 150 .180 - 2.30 .350 - 18.0 8.50 - 100

.020 MAX .006 - .020 .031 - .220 .150 - 3.00 1.40 - 11.4 .030 MAX .006 - .035 .027 - .220 .300 - 3.00 1.50 - 15.0 .027 - .220 .150 - 3.00 1.40 - 15.0 .050 - .600 .220 - 3.00 1.50 - 20.0 .051 - .600 .110 - 3.00 1.24 - 15.0

.018 MAX .005 - .020 .011 - .120 .030 - 1.30 .150 - 5.80 .025 MAX .005 - .027 .008 - .130 .050 - 1.30 .500 - 7.00 .008 - .130 .030 - 1.30 .150 - 7.00 .026 - .300 .120 - 1.70 .700 - 10.0 .030 - .320 .070 - 1.70 .410 - 9.00

.016 MAX .004 - .020 .004 - .090 .004 - .600 .009 - 3.70 .020 MAX .005 - .021 .004 - .090 .007 - .500 .020 - 3.00 .004 - .090 .004 - .600 .009 - 3.70 .018 - .200 .075 - 1.20 .404 - 7.90 .018 - .220 .045 - 1.40 .256 - 8.00

.015 MAX .004 - .020 .004 - .060 .004 - .100 .005 - 1.70 .017 MAX .004 - .018 .004 - .045 .005 - .060 .006 - 2.00 .004 - .060 .004 - .110 .005 - 2.00 .014 - .150 .050 - .850 .260 - 6.50 .014 - .200 .039 - 1.30 .210 - 5.50

.013 MAX .004 - .020 .004 - .040 .004 - .100 .005 - .500 .015 MAX .004 - .017 .004 - .040 .005 - .040 .005 - 1.00 .004 - .040 .004 - .100 .004 - 1.00 .012 - .130 .042 - .720 .198 - 5.80 .012 - .130 .035 - 1.30 .198 - 2.90

22 24 26 32 34 36 42 44 46 52 54 56

NOTES: Delay Curves 11,12,14,16,21,22,24,26,42,44,46,52,54,56: Breakers to hold 100% and must trip at 125% of rated current and greater within the time limit shown in this curve. Delay Curves 32,34,36: Breakers to hold 100% and must trip at 135% of rated current and greater within the time limit shown in this curve. Delay Curves 10,20: Breakers to hold 100% and must trip at 150% of rated current and greater within the time limit shown in this curve. All Curves: Curve data shown represents breaker response at ambient temperature of 25C (77F) with no preloading. Breakers are mounted in standard wall-mount position. On 50 amp and less current ratings, the minimum inrush pulse tolerance handling capability is 12 times the rated current on standard delays and 25 times the rated current on high inrush delays. These values are based on a 60 Hz 1/2 cycle, 8.33 ms pulse. High inrush delays should be specified for applications with high initial surge currents of short duration such as switching power supplies, highly capacitive loads and transformer loads.

AC Instantaneous
10000

Ultrashort
10000

Short
10000

50/60 Hz INSTANTANEOUS CURVE NO. 20


1000

50/60 Hz ULTRASHORT DELAY CURVE NO. 21


1000
1000

50/60 Hz SHORT DELAY CURVE NO. 22

TRIP TIME IN SECONDS

TRIP TIME IN SECONDS

10

TRIP TIME IN SECONDS


100 125 200 300 400 500 600 700 800 900 1000 1100 1200

100

100

100

10

10

.1

.1

.1

.01

.01

.01

.001 100 125 150 200 300 400 500 600 700 800 900 1000 1100 1200

.001

.001 100 125 150 200 300 400 500 600 700 800 900 1000 1100 1200

PERCENT OF RATED CURRENT

150

PERCENT OF RATED CURRENT

PERCENT OF RATED CURRENT

Medium
10000

Long
10000

50/60 Hz MEDIUM DELAY CURVE NO. 24


1000

50/60 Hz LONG DELAY CURVE NO. 26


1000

TRIP TIME IN SECONDS

TRIP TIME IN SECONDS

100

100

10

10

.1

.1

.01

.01

.001 100 125 150 200 300 400 500 600 700 800 900 1000 1100 1200

.001

100 125 150

200

300

400

500

600

700

800

900

1000

1100

1200

PERCENT OF RATED CURRENT

PERCENT OF RATED CURRENT

High Inrush AC Short


10000

Medium
10000

Long
10000

50/60 Hz - HI-INRUSH SHORT DELAY CURVE NO. 42


1000
1000

50/60 Hz - HI-INRUSH MEDIUM DELAY CURVE NO. 44


1000

50/60 Hz - HI-INRUSH LONG DELAY CURVE NO. 46

TRIP TIME IN SECONDS

10

TRIP TIME IN SECONDS

10

TRIP TIME IN SECONDS


100 125 150 200 300 400 500 600 700 800 900 1000 1100 1200

100

100

100

10

.1

.1

.1

.01

.01

.01

.001

100 125 150

200

300

400

500

600

700

800

900

1000

1100

1200

.001

.001 100 125 150 200 300 400 500 600 700 800 900 1000 1100 1200

PERCENT OF RATED CURRENT

PERCENT OF RATED CURRENT

PERCENT OF RATED CURRENT

http://www.morssmittrelais.com

Time Delay Values - AR-Series


DC Instantaneous
10000

Ultrashort
10000

Short
D.C. ULTRASHORT DELAY CURVE NO. 11
10000

D.C. INSTANTANEOUS CURVE NO. 10


1000

D.C. SHORT DELAY CURVE NO. 12

1000

1000

TRIP TIME IN SECONDS

100

100

100

TRIP TIME IN SECONDS

10

10

TRIP TIME IN SECONDS


100 125 150 200 300 400 500 600 700 800 900 1000 1100 1200

10

.1

.1

.1

.01

.01

.01

.001 100 125 150 200 300 400 500 600 700 800 900 1000 1100 1200

.001

.001 100 125 150 200 300 400 500 600 700 800 900 1000 1100 1200

PERCENT OF RATED CURRENT

PERCENT OF RATED CURRENT

PERCENT OF RATED CURRENT

Medium
10000 1000

Long
10000

D.C. MEDIUM DELAY CURVE NO. 14

D.C. LONG DELAY CURVE NO. 16

1000

TRIP TIME IN SECONDS

TRIP TIME IN SECONDS

100

100

10

10

.1

.1

.01

.01

.001 100 125 150 200 300 400 500 600 700 800 900 1000 1100 1200

.001 100 125 150 200 300 400 500 600 700 800 900 1000 1100 1200

PERCENT OF RATED CURRENT

PERCENT OF RATED CURRENT

High Inrush DC Short


10000

Medium
10000

Long
10000

D.C. - HI - INRUSH SHORT DELAY CURVE NO. 52


1000

1000

D.C. - HI - INRUSH MEDIUM DELAY CURVE NO. 54


1000

D.C. - HI - INRUSH LONG DELAY CURVE NO. 56

TRIP TIME IN SECONDS

TRIP TIME IN SECONDS

100

100

TRIP TIME IN SECONDS

100

10

10

10

.1

.1

.1

.01

.01

.01

.001 100 125 200 300 400 500 600 700 800 900 1000 1100 1200

.001 100 125 150 200 300 400 500 600 700 800 900 1000 1100 1200

.001 100 125 150 200 300 400 500 600 700 800 900 1000 1100 1200

150

PERCENT OF RATED CURRENT

PERCENT OF RATED CURRENT

PERCENT OF RATED CURRENT

AC/DC Instantaneous
10000 1000

Ultrashort
10000

Short
D.C., 50/60 Hz ULTRASHORT DELAY CURVE NO. 31
10000

D.C., 50/60 Hz INSTANTANEOUS CURVE NO. 30

D.C., 50/60 Hz SHORT DELAY CURVE NO. 32


1000

1000

TRIP TIME IN SECONDS

100

100

TRIP TIME IN SECONDS


100 135 150 200 300 400 500 600 700 800 900 1000 1100 1200

100

TRIP TIME IN SECONDS

10

10

10

.1

.1

.1

.01

.01

.01

.001 100 150 200 300 400 500 600 700 800 900 1000 1100 1200

.001

.001

100 135 150

200

300

400

500

600

700

800

900

1000

1100

1200

PERCENT OF RATED CURRENT

PERCENT OF RATED CURRENT

PERCENT OF RATED CURRENT

Medium
10000

Long
10000

D.C., 50/60 Hz MEDIUM DELAY CURVE NO. 34


1000

D.C., 50/60 Hz LONG DELAY CURVE NO. 36


1000

TRIP TIME IN SECONDS

100

100

10

TRIP TIME IN SECONDS


100 135 150 200 300 400 500 600 700 800 900 1000 1100 1200

10

.1

.1

.01

.01

.001

.001

100 135 150

200

300

400

500

600

700

800

900

1000

1100

1200

PERCENT OF RATED CURRENT

PERCENT OF RATED CURRENT

http://www.morssmittrelais.com

Circuit & Terminal Diagrams - AR-Series


CIRCUIT CODE AUX SWITCH CODE

CIRCUIT BREAKER PROFILE 2 TERMINALS LINE

CIRCUIT SCHEMATIC ANSI SERIES TRIP LINE

ANSI SWITCH ONLY (NO COIL)

MAIN TERMINALS (SEE TABLE A)

LINE A 0 BC 0

LOAD LOAD 1.640 [41.66] 5 TERMINALS .520[13.21] SWITCH ONLY (NO COIL) WITH AUXILIARY SWITCH LINE NC A NO 1 2 3 4 LINE LOAD SERIES TRIP WITH (3) AUXILIARY/ALARM SWITCH NC N0 LINE C N0 BC 1 2 3 4

NC NO C
STANDARD AUX. SWITCH TERMINALS

C NO NC

ALARM SWITCH TERMINALS & STD. AUX. SW. WITH VDE OR >30 AMPS OR AGENCY CODE "P"

LOAD

C LOAD
STANDARD AUX. SWITCH

NC LOAD
ALARM SWITCH

.205[5.21] 3 TERMINALS SHUNT TRIP LINE

DUAL COIL; SERIES TRIP CURRENT COIL, SHUNT TRIP VOLTAGE COIL LINE

DE SHUNT .390[9.91] LOAD

0 VOLTAGE COIL

LOAD

All dimensions in inches and [mm]

Form & Fit Drawings - AR-Series

All dimensions in inches and [mm] 6 http://www.morssmittrelais.com

CIRCUIT CODE AUX SWITCH CODE

CIRCUIT SCHEMATIC

Form & Fit Drawings - AR-Series

AUXILIARY/ALARM SWITCH TERMINAL DETAIL


+.002 -.000 [+.05] [-.00]

.344[8.74]

.250[6.35]

.125[3.18]

.161 DIA [ 4.10]

TABLE A TIGHTENING TORQUE SPECIFICATIONS


.139[3.53]
THREAD SIZE #6-32 & M3 MOUNTING HARDWARE #8-32 & M4 THREAD TERMINAL SCREW #10-32 & M5 THREAD TERMINAL SCREW TORQUE 7-9 IN-LBS [0.8- 1.0 NM] 12-15 IN-LBS [1.4-1.7 NM] 15-20 IN-LB [1.7-2.3 NM]

.050 DIA [1.27]


PUSH-IN STUD MATING HOLE

.110[2.79]

.093[2.36] .058 DIA[1.47] TAB (Q.C.)

TAB (Q.C.)

SOLDER TYPE

SEE TABLE B DEPTH BEHIND PANEL


ON I

TABLE B
.032 [.81] TYP LINE (NETZ) 30 1.350 [34.29]

TERMINAL DESCRIPTION MAIN SHUNT & DUAL COIL AUX. SWITCH *


M6 STUD

MID TRIP OFF O

1.560 [39.62]

1.936[49.17]

LOAD (LAST) 1.640 [41.66] REF .220 [5.59] TYP

SCREW TERM. WITH 30 BEND

PUSH-IN STUD

TAB (Q.C.) SCREW TYPE TAB (Q.C.) SCREW #8-32 W/UPTURNED LUGS .093 TAB (Q.C.) .110 TAB (Q.C.) SOLDER TYPE

DEPTH BEHIND PANEL 2.000 [50.80] 2.032 [51.60] 2.207 [56.10] 2.364 [60.05] 2.095 [53.20] 2.189 [55.60] 1.970 [50.00]

* AVAILABLE ON SERIES TRIP AND SWITCH ONLY CIRCUITS.


WHEN CALLED FOR ON MULTI-POLE UNITS, ONLY ONE AUX. SWITCH IS NORMALLY SUPPLIED.

#6-32 [M3] THREAD X .195 [4.95] DEEP 2 PLCS PER POLE .610 [15.49]

.130 [3.30]
SEE NOTE 3

1.640 [41.66] TYP

LINE
ON

1-POLE

60 1.660 [42.16] TYP 2.000 [50.80] TYP


OFF 1.560 [39.62] TYP

.590 DIA [14.99]

LOAD .170 [4.32] .755 [19.18] MAX


TYPICAL - OPTIONAL "ON-OFF" LEGEND

.690 [17.50] .250[6.35]


SHORT HANDLE

2.000 [50.80] 2.032 [51.61]

TAB (Q.C.) TYPE SCREW TYPE

TAB (Q.C.) TYPE TERMINALS IN SERIES TRIP CIRCUIT CONFIGURATION SHOWN. FOR OTHER CONFIGURATIONS, SEE CIRCUIT AND TERMINAL DIAGRAMS.

2-POLE
.156 DIA [3.96]
.750 [19.05] 1.515 [38.48] MAX 2 PLCS TYP PER POLE
+.010 -.000 [+.25] [-.00]

.630 DIA [16.00] ONE PER POLE

1.660 [42.16]

3-POLE

1.050 [26.67]

.750 [19.05] TYP


PER POLE

AA1, AB2, AB3


.750 [19.05] TYP 2.265 [57.53] MAX

AA2, AB4 AA3 MULTI-POLE HANDLE TIE KIT SHIPPED BULK AA4

PANEL CUTOUT DETAIL 4-POLE


TOLERANCES .005 [.12] UNLESS OTHERWISE SPECIFIED

.750 [19.05] TYP 3.015 [76.58] MAX

All dimensions in inches and [mm] 7

http://www.morssmittrelais.com

Your local distributor:

For further information please contact:


France
MS RELAIS SAS
Tour Rosny 2 Avenue du Gnral de Gaulle F - 93118 Rosny-sous-Bois Cedex France Tel. +33 (0)1 48 12 14 40 Fax +33 (0)1 48 55 90 01 sales@morssmittrelais.com http://www.morssmittrelais.com

USA
MORS SMITT TECHNOLOGIES INC.
50 North New York Avenue Huntington, NY, 11743 USA Tel. +1 (631) 271-8858 Fax +1 (631) 271-8898 mstechnologies@morssmittrelais.com http://www.morssmittrelais.com

The Netherlands
NIEAF-SMITT BV
Vrieslantlaan 6 NL - 3526 AA, Utrecht The Netherlands Tel. +31 (0)30 288 13 11 Fax +31 (0)30 289 88 16 sales@nieaf-smitt.nl http://www.nieaf-smitt.nl/railway

8 Proven Reliability
DS/GB AR-Series 1.50 / 04-04