Microprocessor 3-phase measurement and monitoring unit with optional connection to the FRAKO Starkstrombus to detect, analyse and monitor electrical measurement variables in 400 V and 525 V low voltage mains or medium voltage mains (100 V, secondary). Measurement via three external current converters Automatic range switch-over Determination of current in PEN (neutral + PE) Measurement of active demand for incoming and recovery power Menu-driven in plain text and 6 parameters displayed for direct comparison Alarm on exceeding set limits with potential-free NO contact as well as plain text shown on a flashing backlit display Menu-driven programming in plain text with operator prompts Storage of all meter readings and limit values on mains failure Illuminated LC display of measured values Optional connection to the FRAKO Starkstrombus for remote indication of measured values, limit values and current and voltage curves, remote operation and data management of historical data (daily graphs, monthly and yearly evaluations) via PC Can be connected directly to a PC using an additional RS232 adapter
Simple configuration
The EMA 1101 mains monitoring unit can easily be programmed using the EMA-SW software and an RS 232 interface adapter. The unit is immediately ready to use once the transformer ratios for voltage and current have been entered. Individual alarm values can be set in the EMA 1101 mains monitoring unit to evaluate and monitor the quality of the mains system. These values can be simply and easily entered using the menu item EMA Configuration. The alarm relay of the EMA 1101 is activated when the range is exceeded. Faults can thus be identified and the appropriate procedures carried out.
Detailed evaluation
The EMA 1101 mains monitoring unit stores all key minimum and maximum values. These can easily be read using the EMA-SW software to provide a detailed evaluation of the system.
3x X/ 5 A (conv. current >6 mA) max. 1.8 VA per converter conn. 250 VAC / max. 3 A (potential-free NO contact) To select from 2 profiles (e.g. HT/LT) For connecting to the FRAKO Energy Management-System, acc. to EN 50170 (P-Net), standard RS 485 Fieldbus 76.8 kbit/s Via RS232 adapter (optional) for directly connecting to PC 19200 baud Sealed keypad with 5 keys Illuminated LC display (4 lines each of 20 characters) Plug-in connecting strips (supplied)
Outputs
1 Alarm contact
Inputs
Tariff input
Technical data
Power supply
Voltage Frequency Power consumption Fusing 230 VAC +/- 10 % 48 to 62 Hz max. 7 VA 2 A external protection required
Measuring input
Voltage circuit
Type Range Meas. voltage phase/ phase conductors EMA 1101 EMA 1101 105V 400V mains 525V mains 100V mains 3x 250 to 550 VAC 3x 50 to 105 VAC
144 x 144 mm (DIN 43700) 138 x 138 mm (DIN 43700) 105 mm Enclosure IP54, terminals IP20 Contamination level 3, to VDE 0470 / EN60529 To VDE 0411 / EN61010 After mounting: Prot. class 1 EN 50081-1, EN 50082-2 Flame-resistant to UL94-V0 From front panel with screwdriver As required Approx. 1.3 kg -10 C to +50 C
Operating conditions
Ambient temperature
Dimensions
Connection Diagramm
Dimensions in mm