Documente Academic
Documente Profesional
Documente Cultură
Page 1
My Ecodial L V3.4
6/19/2012
Page 2
Project
Network
Earthing arrangement: Voltage: Max. permissible CSA: CSA N / CSA Ph: CSA tolerance: Target power factor: System frequency: TN-S 380 V 630.0 mm 1 0.0 % 0.85 60 Hz
Circuit :
Upstream : Downstream : Voltage :
Source :
Upstream Upstream short-circuit power max: Upstream short-circuit power min: Upstream impedances:
T1
500 MVA 500 MVA Resistance Rt: Inductance Xt: dry-type 1 1600 kVA Delta-Star Resistance Rt: Inductance Xt: 2430.95 A -
0.0317 mOhm 0.3168 mOhm Earthing arrangement: Unit power: Short-circuit voltage: 1.6787 mOhm 5.7292 mOhm TN-S 1600.0 kVA 6.00 %
Transformer :
Type: Number of transformers: Total power: Connection: Source impedances: Ib: Insulation Monitoring Device:
Type: KTC3200 Length: 18.0 m Calculation mode : End Installation method: Standard Sizing constraint: overloads The electrodynamic withstand was checked Correction : Voltage drop U (%) upstream 0.00 user Protection circuit 0.34 downst. 0.34
C1
: 1.00 : 1.00
Calculation results:
Isc upstr. (kA) R (m) X (m) Z (m) Ik3max 37.1511 1.9277 6.2188 6.5107 Ik2max 32.3157 3.8714 12.3728 12.9643 Ik1max 28.9876 2.5908 7.9319 8.3443 Ik2min 29.1582 3.9886 12.3728 12.9998 Ik1min 26.1081 2.7106 7.9319 8.3823 I fault 18.0759 5.9856 10.5239 12.1070
Calculation results in accordance with guide UTE C15-500 (CENELEC report R064-003). UTE approval 15L-602. All assumptions and device choices are the user's responsibility. Circuit breaker: Q1
Frame rating (In): Trip unit: 2500 A Micrologic 5.0 A Name: NW25H1-65.0 kA Trip unit rating: 2500.00 A Number of poles: 3P3d Discrimination limit: BC reinforced by cascading: Earth leakage protection: No Earth leakage protection device : Sensitivity : Delay : Earth leakage discrimination : Settings:
Overload: Magnetic:
6/19/2012
Page 3
tm = 50 ms
My Ecodial L V3.4
6/19/2012
Page 4
Circuit :
Upstream : Downstream : Voltage :
Busbars:
Designation: Type : Ambient temperature: Short-circuit temperature: Ks : Voltage drop:
B2
STANDARD Standard on edge 40 C 85 C 0.88 0.0000 % Dimensions: Metal: I available: Isc max: Peak Isc (k) : 0.0 m-4// 5.0 mmx63 mm Copper 2180 A 37.31 kA 78.35 kA
My Ecodial L V3.4
6/19/2012
Page 5
Circuit :
Upstream : Downstream : Voltage :
Circuit breaker:
Q7
Frame rating (In): Trip unit: 100 A TM-D
Name: NSX100N-50.0 kA Trip unit rating: 100.00 A Number of poles: 3P3d Discrimination limit: T BC reinforced by cascading: No Earth leakage protection: No Earth leakage protection device : Sensitivity : Delay : Earth leakage discrimination : Settings:
Overload: Magnetic:
Cable :
Length: Installation method: Cable type: Insulation: Arrangement of conductors: Ambient temperature:
C7
52.0 m E-circuits spaced out Multi-core cables on perforated horizontal tray Multi-core Number of layers: XLPE Nb additional touching circuits: Trefoil 40 C THDI level: 157.9 A 131.1 A : 0.91 : 1.00 : 1.00 : 0.91 : 1.00 : 1.00 ______ 0.83 metal Copper Copper Copper (52-D1) (A.52-16) (D.52-1) (52-E4) (433.1)
1 5 15 %
Permitted current by the cable (Iz): Iz under normal conditions of use (A): Iz x correction factors (real conditions of use): Sizing constraint: user-defined Correction : Temperature x Soil thermal resistivity x Neutral loaded x touching conductors x User / Protection )
reference
downstream 1.44
Thermal stress check: Energy received by the phase conductor : 19200000 As Permitted thermal stress : 25050025 As
Calculation results:
(kA) R (m) X (m) Z (m) Isc upstr. 37.3088 1.9277 6.1900 6.4832 Ik3max 7.6834 29.4283 11.1820 31.4811 Ik2max 6.6527 58.8725 22.3568 62.9746 Ik1max 4.0103 57.5919 17.9159 60.3142 Ik2min 4.8798 74.3900 22.3568 77.6769 Ik1min 2.9073 73.1121 17.9159 75.2752 I fault 1.8244 118.1879 20.5079 119.9540
Calculation results in accordance with guide UTE C15-500 (CENELEC report R064-003). UTE approval 15L-602. All assumptions and device choices are the user's responsibility. Load
I: P: 74.00 A 41.40 kW Polarity of circuit: Earthing arrangement: 3P+N TN-S
My Ecodial L V3.4
6/19/2012
Page 6
Power factor
0.85
1.0
My Ecodial L V3.4
6/19/2012
Page 7
Circuit :
Upstream : Downstream : Voltage :
Circuit breaker:
Q3
Frame rating (In): Trip unit: 100 A TM-D
Name: NSX100N-50.0 kA Trip unit rating: 40.00 A Number of poles: 3P3d Discrimination limit: T BC reinforced by cascading: No Earth leakage protection: No Earth leakage protection device : Sensitivity : Delay : Earth leakage discrimination : Settings:
Overload: Magnetic:
Cable :
Length: Installation method: Cable type: Insulation: Arrangement of conductors: Ambient temperature:
C3
50.5 m E-circuits spaced out Multi-core cables on perforated horizontal tray Multi-core Number of layers: XLPE Nb additional touching circuits: Trefoil 40 C THDI level: 74.7 A 62.0 A : 0.91 : 1.00 : 1.00 : 0.91 : 1.00 : 1.00 ______ 0.83 metal Copper Copper Copper (52-D1) (A.52-16) (D.52-1) (52-E4) (433.1)
1 5 15 %
Permitted current by the cable (Iz): Iz under normal conditions of use (A): Iz x correction factors (real conditions of use): Sizing constraint: user-defined Correction : Temperature x Soil thermal resistivity x Neutral loaded x touching conductors x User / Protection )
reference
downstream 2.00
Thermal stress check: Energy received by the phase conductor : 950000 As Permitted thermal stress : 2044900 As
Calculation results:
(kA) R (m) X (m) Z (m) Isc upstr. 37.3088 1.9277 6.1900 6.4832 Ik3max 2.5186 95.4032 11.0380 96.0396 Ik2max 2.1810 190.8224 22.0688 192.0943 Ik1max 1.2707 189.5418 17.6279 190.3598 Ik2min 1.5517 243.2858 22.0688 244.2847 Ik1min 0.9019 242.0079 17.6279 242.6491 I fault 0.8892 245.2829 20.2199 246.1149
Calculation results in accordance with guide UTE C15-500 (CENELEC report R064-003). UTE approval 15L-602. All assumptions and device choices are the user's responsibility. Load
I: P: 35.00 A 19.58 kW Polarity of circuit: Earthing arrangement: 3P+N TN-S
My Ecodial L V3.4
6/19/2012
Page 8
Power factor
0.85
1.0
My Ecodial L V3.4
6/19/2012
Page 9
Circuit :
Upstream : Downstream : Voltage :
Circuit breaker:
Q4
Frame rating (In): Trip unit: 100 A TM-D
Name: NSX100N-50.0 kA Trip unit rating: 32.00 A Number of poles: 3P3d Discrimination limit: T BC reinforced by cascading: No Earth leakage protection: No Earth leakage protection device : Sensitivity : Delay : Earth leakage discrimination : Settings:
Overload: Magnetic:
Cable :
Length: Installation method: Cable type: Insulation: Arrangement of conductors: Ambient temperature:
C4
58.5 m E-circuits spaced out Multi-core cables on perforated horizontal tray Multi-core Number of layers: XLPE Nb additional touching circuits: Trefoil 40 C THDI level: 74.7 A 62.0 A : 0.91 : 1.00 : 1.00 : 0.91 : 1.00 : 1.00 ______ 0.83 metal Copper Copper Copper (52-D1) (A.52-16) (D.52-1) (52-E4) (433.1)
1 5 15 %
Permitted current by the cable (Iz): Iz under normal conditions of use (A): Iz x correction factors (real conditions of use): Sizing constraint: user-defined Correction : Temperature x Soil thermal resistivity x Neutral loaded x touching conductors x User / Protection )
reference
downstream 1.55
Thermal stress check: Energy received by the phase conductor : 608000 As Permitted thermal stress : 2044900 As
Calculation results:
(kA) R (m) X (m) Z (m) Isc upstr. 37.3088 1.9277 6.1900 6.4832 Ik3max 2.1822 110.2112 11.8060 110.8417 Ik2max 1.8897 220.4384 23.6048 221.6986 Ik1max 1.0995 219.1578 19.1639 219.9941 Ik2min 1.3433 281.1943 23.6048 282.1833 Ik1min 0.7800 279.9164 19.1639 280.5717 I fault 0.7705 283.1914 21.7559 284.0258
Calculation results in accordance with guide UTE C15-500 (CENELEC report R064-003). UTE approval 15L-602. All assumptions and device choices are the user's responsibility. Load
I: P: 22.00 A 12.31 kW Polarity of circuit: Earthing arrangement: 3P+N TN-S
My Ecodial L V3.4
6/19/2012
Page 10
Power factor
0.85
1.0
My Ecodial L V3.4
6/19/2012
Page 11
Circuit :
Upstream : Downstream : Voltage :
Circuit breaker:
Q5
Frame rating (In): Trip unit: 100 A TM-D
Name: NSX100N-50.0 kA Trip unit rating: 32.00 A Number of poles: 3P3d Discrimination limit: T BC reinforced by cascading: No Earth leakage protection: No Earth leakage protection device : Sensitivity : Delay : Earth leakage discrimination : Settings:
Overload: Magnetic:
Cable :
Length: Installation method: Cable type: Insulation: Arrangement of conductors: Ambient temperature:
C5
62.5 m E-circuits spaced out Multi-core cables on perforated horizontal tray Multi-core Number of layers: XLPE Nb additional touching circuits: Trefoil 40 C THDI level: 74.7 A 62.0 A : 0.91 : 1.00 : 1.00 : 0.91 : 1.00 : 1.00 ______ 0.83 metal Copper Copper Copper (52-D1) (A.52-16) (D.52-1) (52-E4) (433.1)
1 5 15 %
Permitted current by the cable (Iz): Iz under normal conditions of use (A): Iz x correction factors (real conditions of use): Sizing constraint: user-defined Correction : Temperature x Soil thermal resistivity x Neutral loaded x touching conductors x User / Protection )
reference
downstream 1.58
Thermal stress check: Energy received by the phase conductor : 608000 As Permitted thermal stress : 2044900 As
Calculation results:
(kA) R (m) X (m) Z (m) Isc upstr. 37.3088 1.9277 6.1900 6.4832 Ik3max 2.0456 117.6152 12.1900 118.2452 Ik2max 1.7714 235.2464 24.3728 236.5056 Ik1max 1.0301 233.9658 19.9319 234.8133 Ik2min 1.2587 300.1486 24.3728 301.1365 Ik1min 0.7306 298.8706 19.9319 299.5345 I fault 0.7223 302.1456 22.5239 302.9840
Calculation results in accordance with guide UTE C15-500 (CENELEC report R064-003). UTE approval 15L-602. All assumptions and device choices are the user's responsibility. Load
I: P: 21.00 A 11.75 kW Polarity of circuit: Earthing arrangement: 3P+N TN-S
My Ecodial L V3.4
6/19/2012
Page 12
Power factor
0.85
1.0
My Ecodial L V3.4
6/19/2012
Page 13
Circuit :
Upstream : Downstream : Voltage :
Circuit breaker:
Q6
Frame rating (In): Trip unit: 100 A TM-D
Name: NSX100N-50.0 kA Trip unit rating: 32.00 A Number of poles: 3P3d Discrimination limit: T BC reinforced by cascading: No Earth leakage protection: No Earth leakage protection device : Sensitivity : Delay : Earth leakage discrimination : Settings:
Overload: Magnetic:
Cable :
Length: Installation method: Cable type: Insulation: Arrangement of conductors: Ambient temperature:
C6
66.5 m E-circuits spaced out Multi-core cables on perforated horizontal tray Multi-core Number of layers: XLPE Nb additional touching circuits: Trefoil 40 C THDI level: 74.7 A 62.0 A : 0.91 : 1.00 : 1.00 : 0.91 : 1.00 : 1.00 ______ 0.83 metal Copper Copper Copper (52-D1) (A.52-16) (D.52-1) (52-E4) (433.1)
1 5 15 %
Permitted current by the cable (Iz): Iz under normal conditions of use (A): Iz x correction factors (real conditions of use): Sizing constraint: user-defined Correction : Temperature x Soil thermal resistivity x Neutral loaded x touching conductors x User / Protection )
reference
downstream 1.84
Thermal stress check: Energy received by the phase conductor : 608000 As Permitted thermal stress : 2044900 As
Calculation results:
(kA) R (m) X (m) Z (m) Isc upstr. 37.3088 1.9277 6.1900 6.4832 Ik3max 1.9250 125.0192 12.5740 125.6499 Ik2max 1.6670 250.0544 25.1408 251.3151 Ik1max 0.9689 248.7738 20.6999 249.6335 Ik2min 1.1842 319.1028 25.1408 320.0916 Ik1min 0.6871 317.8248 20.6999 318.4982 I fault 0.6798 321.0998 23.2919 321.9435
Calculation results in accordance with guide UTE C15-500 (CENELEC report R064-003). UTE approval 15L-602. All assumptions and device choices are the user's responsibility. Load
I: P: 24.00 A 13.43 kW Polarity of circuit: Earthing arrangement: 3P+N TN-S
My Ecodial L V3.4
6/19/2012
Page 14
Power factor
0.85
1.0
My Ecodial L V3.4
6/19/2012
Page 15
Circuit :
Upstream : Downstream : Voltage :
Circuit breaker:
Q8
Frame rating (In): Trip unit: 630 A Micrologic 2.3
Name: NSX630N-50.0 kA Trip unit rating: 630.00 A Number of poles: 3P3d Discrimination limit: T BC reinforced by cascading: No Earth leakage protection: No Earth leakage protection device : Sensitivity : Delay : Earth leakage discrimination : Settings:
Overload: Magnetic:
Cable :
Length: Installation method: Cable type: Insulation: Arrangement of conductors: Ambient temperature:
C8
25.0 m E-circuits spaced out Multi-core cables on perforated horizontal tray Multi-core Number of layers: XLPE Nb additional touching circuits: Trefoil 40 C THDI level: 912.1 A 757.0 A : 0.91 : 1.00 : 1.00 : 0.91 : 1.00 : 1.00 ______ 0.83 metal Copper Copper Copper (52-D1) (A.52-16) (D.52-1) (52-E4) (433.1)
1 5 15 %
Permitted current by the cable (Iz): Iz under normal conditions of use (A): Iz x correction factors (real conditions of use): Sizing constraint: user-defined Correction : Temperature x Soil thermal resistivity x Neutral loaded x touching conductors x User / Protection )
reference
downstream 0.73
Thermal stress check: Energy received by the phase conductor : 297675000 As Permitted thermal stress : 699867025 As
Calculation results:
(kA) R (m) X (m) Z (m) Isc upstr. 37.3088 1.9277 6.1900 6.4832 Ik3max 30.0678 3.1784 7.3900 8.0445 Ik2max 26.0400 6.3727 14.7728 16.0887 Ik1max 20.9992 5.0921 10.3319 11.5186 Ik2min 23.0710 7.1903 14.7728 16.4297 Ik1min 18.3842 5.9123 10.3319 11.9039 I fault 13.0412 10.7039 12.9239 16.7810
Calculation results in accordance with guide UTE C15-500 (CENELEC report R064-003). UTE approval 15L-602. All assumptions and device choices are the user's responsibility. Load
I: P: 433.21 A 242.36 kW Polarity of circuit: Earthing arrangement: 3P+N TN-S
My Ecodial L V3.4
6/19/2012
Page 16
Power factor
0.85
1.0
My Ecodial L V3.4
6/19/2012
Page 17
Circuit :
Upstream : Downstream : Voltage :
Circuit breaker:
Q9
Frame rating (In): Trip unit: 630 A Micrologic 2.3
Name: NSX630F-36.0 kA Trip unit rating: 630.00 A Number of poles: 4P4d Discrimination limit: BC reinforced by cascading: No Earth leakage protection: No Earth leakage protection device : Sensitivity : Delay : Earth leakage discrimination : Settings:
Overload: Magnetic:
Load
I: P: Power factor
My Ecodial L V3.4
6/19/2012
Page 18
Circuit :
Upstream : Downstream : Voltage :
Generator:
Number of generators: Total power: Transient reactance: Earthing arrangement:
G112
1 400 kVA 30.000 % TN-S Unit power: 400 kVA Zero phase-sequence reactance: 6.000 % Subtransient reactance: 30.000 %
Cable :
Length: Installation method: Cable type: Insulation: Arrangement of conductors: Ambient temperature:
C112
10.0 m E-circuits spaced out Multi-core cables on perforated horizontal tray Multi-core Number of layers: XLPE Nb additional touching circuits: Trefoil 40 C THDI level: 912.1 A 784.4 A : 0.91 : 1.00 : 1.00 : 0.95 : 1.00 : 1.00 ______ 0.86 metal Copper Copper Copper (52-D1) (A.52-16) (D.52-1) (52-E4) (433.1)
1 2 15 %
Permitted current by the cable (Iz): Iz under normal conditions of use (A): Iz x correction factors (real conditions of use): Sizing constraint: user-defined Correction : Temperature x Soil thermal resistivity x Neutral loaded x touching conductors x User / Protection )
reference
downstream 0.18
Calculation results:
Isc upstr. (kA) R (m) X (m) Z (m) Ik3max 2.2236 0.5003 108.7800 108.7812 Ik2max 1.9257 1.0005 217.5600 217.5623 Ik1max 3.0090 1.0005 80.3800 80.3862 Ik2min 1.7422 1.2807 217.5600 217.5638 Ik1min 2.7223 1.2807 80.3800 80.3902 I fault 2.7389 0.6403 79.9000 79.9026
Calculation results in accordance with guide UTE C15-500 (CENELEC report R064-003). UTE approval 15L-602. All assumptions and device choices are the user's responsibility. Circuit breaker:
Name: NSX630F-36.0 kA Trip unit rating: 630.00 A Number of poles: 4P4d Discrimination limit: BC reinforced by cascading: Earth leakage protection: No Earth leakage protection device : Sensitivity : Delay : Earth leakage discrimination : Settings:
Q112
Overload: Magnetic:
6/19/2012
Page 19
My Ecodial L V3.4
6/19/2012
Page 20
Circuit :
Upstream : Downstream : Voltage :
Busbars:
Designation: Type : Ambient temperature: Short-circuit temperature: Ks : Voltage drop:
B10
Linergy 800 Prisma-Linergy 40 C 85 C 0.88 0.0000 % Dimensions: Metal: I available: Isc max: Peak Isc (k) : 0.0 m-1// 0.0 mmx0 mm Copper 750 A 30.07 kA 63.14 kA
My Ecodial L V3.4
6/19/2012
Page 21
Circuit :
Upstream : Downstream : Voltage :
Circuit breaker:
Q11
Frame rating (In): Trip unit: 100 A TM-D
Name: NSX100N-50.0 kA Trip unit rating: 32.00 A Number of poles: 3P3d Discrimination limit: T BC reinforced by cascading: No Earth leakage protection: No Earth leakage protection device : Sensitivity : Delay : Earth leakage discrimination : Settings:
Overload: Magnetic:
Cable :
Length: Installation method: Cable type: Insulation: Arrangement of conductors: Ambient temperature:
C11
60.0 m E-circuits spaced out Multi-core cables on perforated horizontal tray Multi-core Number of layers: XLPE Nb additional touching circuits: Trefoil 40 C THDI level: 74.7 A 62.0 A : 0.91 : 1.00 : 1.00 : 0.91 : 1.00 : 1.00 ______ 0.83 metal Copper Copper Copper (52-D1) (A.52-16) (D.52-1) (52-E4) (433.1)
1 13 15 %
Permitted current by the cable (Iz): Iz under normal conditions of use (A): Iz x correction factors (real conditions of use): Sizing constraint: user-defined Correction : Temperature x Soil thermal resistivity x Neutral loaded x touching conductors x User / Protection )
reference
downstream 1.76
Thermal stress check: Energy received by the phase conductor : 608000 As Permitted thermal stress : 2044900 As
Calculation results:
(kA) R (m) X (m) Z (m) Isc upstr. 58.8078 1.4681 1.3440 1.9904 Ik3max 2.1452 112.5281 7.1040 112.7521 Ik2max 1.8577 225.0721 14.2008 225.5197 Ik1max 1.0724 225.0822 14.3736 225.5407 Ik2min 1.2951 291.5039 26.2928 292.6873 Ik1min 0.7519 290.2259 21.8519 291.0474 I fault 0.7393 295.0175 24.4439 296.0284
Calculation results in accordance with guide UTE C15-500 (CENELEC report R064-003). UTE approval 15L-602. All assumptions and device choices are the user's responsibility. Load
I: P: 18.00 A 10.07 kW Polarity of circuit: Earthing arrangement: 3P+N TN-S
My Ecodial L V3.4
6/19/2012
Page 22
Power factor
0.85
1.0
My Ecodial L V3.4
6/19/2012
Page 23
Circuit :
Upstream : Downstream : Voltage :
Circuit breaker:
Q12
Frame rating (In): Trip unit: 100 A TM-D
Name: NSX100N-50.0 kA Trip unit rating: 32.00 A Number of poles: 3P3d Discrimination limit: T BC reinforced by cascading: No Earth leakage protection: No Earth leakage protection device : Sensitivity : Delay : Earth leakage discrimination : Settings:
Overload: Magnetic:
Cable :
Length: Installation method: Cable type: Insulation: Arrangement of conductors: Ambient temperature:
C12
72.0 m E-circuits spaced out Multi-core cables on perforated horizontal tray Multi-core Number of layers: XLPE Nb additional touching circuits: Trefoil 40 C THDI level: 100.1 A 83.1 A : 0.91 : 1.00 : 1.00 : 0.91 : 1.00 : 1.00 ______ 0.83 metal Copper Copper Copper (52-D1) (A.52-16) (D.52-1) (52-E4) (433.1)
1 13 15 %
Permitted current by the cable (Iz): Iz under normal conditions of use (A): Iz x correction factors (real conditions of use): Sizing constraint: user-defined Correction : Temperature x Soil thermal resistivity x Neutral loaded x touching conductors x User / Protection )
reference
downstream 1.64
Thermal stress check: Energy received by the phase conductor : 608000 As Permitted thermal stress : 5234944 As
Calculation results:
(kA) R (m) X (m) Z (m) Isc upstr. 58.8078 1.4681 1.3440 1.9904 Ik3max 2.8402 84.7631 8.2560 85.1642 Ik2max 2.4594 169.5421 16.5048 170.3436 Ik1max 1.4197 169.5522 16.6776 170.3705 Ik2min 1.7053 220.4255 28.5968 222.2728 Ik1min 0.9926 219.1475 24.1559 220.4748 I fault 0.9704 223.9391 26.7479 225.5309
Calculation results in accordance with guide UTE C15-500 (CENELEC report R064-003). UTE approval 15L-602. All assumptions and device choices are the user's responsibility. Load
I: P: 21.00 A 11.75 kW Polarity of circuit: Earthing arrangement: 3P+N TN-S
My Ecodial L V3.4
6/19/2012
Page 24
Power factor
0.85
1.0
My Ecodial L V3.4
6/19/2012
Page 25
Circuit :
Upstream : Downstream : Voltage :
Circuit breaker:
Q13
Frame rating (In): Trip unit: 80 A C
Name: NG125H-36.0 kA Trip unit rating: 25.00 A Number of poles: 3P3d Discrimination limit: T BC reinforced by cascading: No Earth leakage protection: No Earth leakage protection device : Sensitivity : Delay : Earth leakage discrimination : Settings:
Overload: Magnetic:
Ir = 25.0 A Im(Isd) = -
Cable :
Length: Installation method: Cable type: Insulation: Arrangement of conductors: Ambient temperature:
C13
93.0 m E-circuits spaced out Multi-core cables on perforated horizontal tray Multi-core Number of layers: XLPE Nb additional touching circuits: Trefoil 40 C THDI level: 100.1 A 83.1 A : 0.91 : 1.00 : 1.00 : 0.91 : 1.00 : 1.00 ______ 0.83 metal Copper Copper Copper (52-D1) (A.52-16) (D.52-1) (52-E4) (433.1)
1 13 15 %
Permitted current by the cable (Iz): Iz under normal conditions of use (A): Iz x correction factors (real conditions of use): Sizing constraint: user-defined Correction : Temperature x Soil thermal resistivity x Neutral loaded x touching conductors x User / Protection )
reference
downstream 1.90
Thermal stress check: Energy received by the phase conductor : 250000 As Permitted thermal stress : 5234944 As
Calculation results:
(kA) R (m) X (m) Z (m) Isc upstr. 58.8078 1.4681 1.3440 1.9904 Ik3max 2.2081 109.0575 10.2720 109.5402 Ik2max 1.9122 218.1308 20.5368 219.0954 Ik1max 1.1039 218.1409 20.7096 219.1217 Ik2min 1.3324 282.6191 32.6288 284.4964 Ik1min 0.7740 281.3411 28.1879 282.7497 I fault 0.7604 286.1327 30.7799 287.7835
Calculation results in accordance with guide UTE C15-500 (CENELEC report R064-003). UTE approval 15L-602. All assumptions and device choices are the user's responsibility. Load
I: P: 20.90 A 11.69 kW Polarity of circuit: Earthing arrangement: 3P+N TN-S
My Ecodial L V3.4
6/19/2012
Page 26
Power factor
0.85
1.0
My Ecodial L V3.4
6/19/2012
Page 27
Circuit :
Upstream : Downstream : Voltage :
Circuit breaker:
Q14
Frame rating (In): Trip unit: 100 A TM-D
Name: NSX100N-50.0 kA Trip unit rating: 32.00 A Number of poles: 3P3d Discrimination limit: T BC reinforced by cascading: No Earth leakage protection: No Earth leakage protection device : Sensitivity : Delay : Earth leakage discrimination : Settings:
Overload: Magnetic:
Cable :
Length: Installation method: Cable type: Insulation: Arrangement of conductors: Ambient temperature:
C14
102.0 m E-circuits spaced out Multi-core cables on perforated horizontal tray Multi-core Number of layers: XLPE Nb additional touching circuits: Trefoil 40 C THDI level: 100.1 A 83.1 A : 0.91 : 1.00 : 1.00 : 0.91 : 1.00 : 1.00 ______ 0.83 metal Copper Copper Copper (52-D1) (A.52-16) (D.52-1) (52-E4) (433.1)
1 13 15 %
Permitted current by the cable (Iz): Iz under normal conditions of use (A): Iz x correction factors (real conditions of use): Sizing constraint: Fault I (Ph-Ph min Isc) Correction : Temperature x Soil thermal resistivity x Neutral loaded x touching conductors x User / Protection )
reference
downstream 1.37
Thermal stress check: Energy received by the phase conductor : 608000 As Permitted thermal stress : 5234944 As
Calculation results:
(kA) R (m) X (m) Z (m) Isc upstr. 58.8078 1.4681 1.3440 1.9904 Ik3max 2.0159 119.4693 11.1360 119.9872 Ik2max 1.7457 238.9546 22.2648 239.9896 Ik1max 1.0078 238.9647 22.4376 240.0158 Ik2min 1.2181 309.2735 34.3568 311.1760 Ik1min 0.7072 307.9955 29.9159 309.4450 I fault 0.6959 312.7871 32.5079 314.4718
Calculation results in accordance with guide UTE C15-500 (CENELEC report R064-003). UTE approval 15L-602. All assumptions and device choices are the user's responsibility. Load
I: P: 10.30 A 5.76 kW Polarity of circuit: Earthing arrangement: My Ecodial L V3.4 3P+N TN-S
6/19/2012
Page 28
Power factor
0.85
1.0
My Ecodial L V3.4
6/19/2012
Page 29
Circuit :
Upstream : Downstream : Voltage :
Circuit breaker:
Q15
Frame rating (In): Trip unit: 100 A TM-D
Name: NSX100N-50.0 kA Trip unit rating: 32.00 A Number of poles: 3P3d Discrimination limit: T BC reinforced by cascading: No Earth leakage protection: No Earth leakage protection device : Sensitivity : Delay : Earth leakage discrimination : Settings:
Overload: Magnetic:
Cable :
Length: Installation method: Cable type: Insulation: Arrangement of conductors: Ambient temperature:
C15
94.0 m E-circuits spaced out Multi-core cables on perforated horizontal tray Multi-core Number of layers: XLPE Nb additional touching circuits: Trefoil 40 C THDI level: 100.1 A 83.1 A : 0.91 : 1.00 : 1.00 : 0.91 : 1.00 : 1.00 ______ 0.83 metal Copper Copper Copper (52-D1) (A.52-16) (D.52-1) (52-E4) (433.1)
1 13 15 %
Permitted current by the cable (Iz): Iz under normal conditions of use (A): Iz x correction factors (real conditions of use): Sizing constraint: Fault I (Ph-Ph min Isc) Correction : Temperature x Soil thermal resistivity x Neutral loaded x touching conductors x User / Protection )
reference
downstream 1.32
Thermal stress check: Energy received by the phase conductor : 608000 As Permitted thermal stress : 5234944 As
Calculation results:
(kA) R (m) X (m) Z (m) Isc upstr. 58.8078 1.4681 1.3440 1.9904 Ik3max 2.1850 110.2143 10.3680 110.7009 Ik2max 1.8921 220.4446 20.7288 221.4170 Ik1max 1.0923 220.4547 20.9016 221.4433 Ik2min 1.3186 285.5807 32.8208 287.4605 Ik1min 0.7660 284.3027 28.3799 285.7157 I fault 0.7527 289.0943 30.9719 290.7487
Calculation results in accordance with guide UTE C15-500 (CENELEC report R064-003). UTE approval 15L-602. All assumptions and device choices are the user's responsibility. Load
I: P: 10.30 A 5.76 kW Polarity of circuit: Earthing arrangement: My Ecodial L V3.4 3P+N TN-S
6/19/2012
Page 30
Power factor
0.85
1.0
My Ecodial L V3.4
6/19/2012
Page 31
Circuit :
Upstream : Downstream : Voltage :
Circuit breaker:
Q16
Frame rating (In): Trip unit: 100 A TM-D
Name: NSX100N-50.0 kA Trip unit rating: 32.00 A Number of poles: 3P3d Discrimination limit: T BC reinforced by cascading: No Earth leakage protection: No Earth leakage protection device : Sensitivity : Delay : Earth leakage discrimination : Settings:
Overload: Magnetic:
Cable :
Length: Installation method: Cable type: Insulation: Arrangement of conductors: Ambient temperature:
C16
82.0 m E-circuits spaced out Multi-core cables on perforated horizontal tray Multi-core Number of layers: XLPE Nb additional touching circuits: Trefoil 40 C THDI level: 74.7 A 62.0 A : 0.91 : 1.00 : 1.00 : 0.91 : 1.00 : 1.00 ______ 0.83 metal Copper Copper Copper (52-D1) (A.52-16) (D.52-1) (52-E4) (433.1)
1 13 15 %
Permitted current by the cable (Iz): Iz under normal conditions of use (A): Iz x correction factors (real conditions of use): Sizing constraint: user-defined Correction : Temperature x Soil thermal resistivity x Neutral loaded x touching conductors x User / Protection )
reference
downstream 0.97
Thermal stress check: Energy received by the phase conductor : 608000 As Permitted thermal stress : 2044900 As
Calculation results:
(kA) R (m) X (m) Z (m) Isc upstr. 58.8078 1.4681 1.3440 1.9904 Ik3max 1.5755 153.2501 9.2160 153.5270 Ik2max 1.3643 306.5161 18.4248 307.0694 Ik1max 0.7877 306.5262 18.5976 307.0899 Ik2min 0.9550 395.7522 30.5168 396.9270 Ik1min 0.5536 394.4743 26.0759 395.3352 I fault 0.5467 399.2659 28.6679 400.2938
Calculation results in accordance with guide UTE C15-500 (CENELEC report R064-003). UTE approval 15L-602. All assumptions and device choices are the user's responsibility. Load
I: P: 3.00 A 1.68 kW Polarity of circuit: Earthing arrangement: My Ecodial L V3.4 3P+N TN-S
6/19/2012
Page 32
Power factor
0.85
1.0
My Ecodial L V3.4
6/19/2012
Page 33
Circuit :
Upstream : Downstream : Voltage :
Circuit breaker:
Q17
Frame rating (In): Trip unit: 100 A TM-D
Name: NSX100N-50.0 kA Trip unit rating: 32.00 A Number of poles: 3P3d Discrimination limit: T BC reinforced by cascading: No Earth leakage protection: No Earth leakage protection device : Sensitivity : Delay : Earth leakage discrimination : Settings:
Overload: Magnetic:
Cable :
Length: Installation method: Cable type: Insulation: Arrangement of conductors: Ambient temperature:
C17
78.0 m E-circuits spaced out Multi-core cables on perforated horizontal tray Multi-core Number of layers: XLPE Nb additional touching circuits: Trefoil 40 C THDI level: 74.7 A 62.0 A : 0.91 : 1.00 : 1.00 : 0.91 : 1.00 : 1.00 ______ 0.83 metal Copper Copper Copper (52-D1) (A.52-16) (D.52-1) (52-E4) (433.1)
1 13 15 %
Permitted current by the cable (Iz): Iz under normal conditions of use (A): Iz x correction factors (real conditions of use): Sizing constraint: user-defined Correction : Temperature x Soil thermal resistivity x Neutral loaded x touching conductors x User / Protection )
reference
downstream 0.96
Thermal stress check: Energy received by the phase conductor : 608000 As Permitted thermal stress : 2044900 As
Calculation results:
(kA) R (m) X (m) Z (m) Isc upstr. 58.8078 1.4681 1.3440 1.9904 Ik3max 1.6554 145.8461 8.8320 146.1133 Ik2max 1.4336 291.7081 17.6568 292.2420 Ik1max 0.8276 291.7182 17.8296 292.2626 Ik2min 1.0029 376.7980 29.7488 377.9705 Ik1min 0.5815 375.5200 25.3079 376.3718 I fault 0.5739 380.3116 27.8999 381.3336
Calculation results in accordance with guide UTE C15-500 (CENELEC report R064-003). UTE approval 15L-602. All assumptions and device choices are the user's responsibility. Load
I: P: 3.00 A 1.68 kW Polarity of circuit: Earthing arrangement: My Ecodial L V3.4 3P+N TN-S
6/19/2012
Page 34
Power factor
0.85
1.0
My Ecodial L V3.4
6/19/2012
Page 35
Circuit :
Upstream : Downstream : Voltage :
Circuit breaker:
Q18
Frame rating (In): Trip unit: 100 A TM-D
Name: NSX100N-50.0 kA Trip unit rating: 32.00 A Number of poles: 3P3d Discrimination limit: T BC reinforced by cascading: No Earth leakage protection: No Earth leakage protection device : Sensitivity : Delay : Earth leakage discrimination : Settings:
Overload: Magnetic:
Cable :
Length: Installation method: Cable type: Insulation: Arrangement of conductors: Ambient temperature:
C18
74.0 m E-circuits spaced out Multi-core cables on perforated horizontal tray Multi-core Number of layers: XLPE Nb additional touching circuits: Trefoil 40 C THDI level: 74.7 A 62.0 A : 0.91 : 1.00 : 1.00 : 0.91 : 1.00 : 1.00 ______ 0.83 metal Copper Copper Copper (52-D1) (A.52-16) (D.52-1) (52-E4) (433.1)
1 13 15 %
Permitted current by the cable (Iz): Iz under normal conditions of use (A): Iz x correction factors (real conditions of use): Sizing constraint: user-defined Correction : Temperature x Soil thermal resistivity x Neutral loaded x touching conductors x User / Protection )
reference
downstream 0.95
Thermal stress check: Energy received by the phase conductor : 608000 As Permitted thermal stress : 2044900 As
Calculation results:
(kA) R (m) X (m) Z (m) Isc upstr. 58.8078 1.4681 1.3440 1.9904 Ik3max 1.7439 138.4421 8.4480 138.6996 Ik2max 1.5102 276.9001 16.8888 277.4147 Ik1max 0.8718 276.9102 17.0616 277.4353 Ik2min 1.0558 357.8437 28.9808 359.0153 Ik1min 0.6123 356.5658 24.5399 357.4093 I fault 0.6039 361.3574 27.1319 362.3745
Calculation results in accordance with guide UTE C15-500 (CENELEC report R064-003). UTE approval 15L-602. All assumptions and device choices are the user's responsibility. Load
I: P: 3.00 A 1.68 kW Polarity of circuit: Earthing arrangement: My Ecodial L V3.4 3P+N TN-S
6/19/2012
Page 36
Power factor
0.85
1.0
My Ecodial L V3.4
6/19/2012
Page 37
Circuit :
Upstream : Downstream : Voltage :
Circuit breaker:
Q19
Frame rating (In): Trip unit: 100 A TM-D
Name: NSX100N-50.0 kA Trip unit rating: 32.00 A Number of poles: 3P3d Discrimination limit: T BC reinforced by cascading: No Earth leakage protection: No Earth leakage protection device : Sensitivity : Delay : Earth leakage discrimination : Settings:
Overload: Magnetic:
Cable :
Length: Installation method: Cable type: Insulation: Arrangement of conductors: Ambient temperature:
C19
70.0 m E-circuits spaced out Multi-core cables on perforated horizontal tray Multi-core Number of layers: XLPE Nb additional touching circuits: Trefoil 40 C THDI level: 74.7 A 62.0 A : 0.91 : 1.00 : 1.00 : 0.91 : 1.00 : 1.00 ______ 0.83 metal Copper Copper Copper (52-D1) (A.52-16) (D.52-1) (52-E4) (433.1)
1 13 15 %
Permitted current by the cable (Iz): Iz under normal conditions of use (A): Iz x correction factors (real conditions of use): Sizing constraint: user-defined Correction : Temperature x Soil thermal resistivity x Neutral loaded x touching conductors x User / Protection )
reference
downstream 0.94
Thermal stress check: Energy received by the phase conductor : 608000 As Permitted thermal stress : 2044900 As
Calculation results:
(kA) R (m) X (m) Z (m) Isc upstr. 58.8078 1.4681 1.3440 1.9904 Ik3max 1.8424 131.0381 8.0640 131.2860 Ik2max 1.5955 262.0921 16.1208 262.5874 Ik1max 0.9211 262.1022 16.2936 262.6082 Ik2min 1.1147 338.8895 28.2128 340.0618 Ik1min 0.6466 337.6115 23.7719 338.4474 I fault 0.6373 342.4031 26.3639 343.4166
Calculation results in accordance with guide UTE C15-500 (CENELEC report R064-003). UTE approval 15L-602. All assumptions and device choices are the user's responsibility. Load
I: P: 3.00 A 1.68 kW Polarity of circuit: Earthing arrangement: My Ecodial L V3.4 3P+N TN-S
6/19/2012
Page 38
Power factor
0.85
1.0
My Ecodial L V3.4
6/19/2012
Page 39
Circuit :
Upstream : Downstream : Voltage :
Circuit breaker:
Q20
Frame rating (In): Trip unit: 100 A TM-D
Name: NSX100N-50.0 kA Trip unit rating: 32.00 A Number of poles: 3P3d Discrimination limit: T BC reinforced by cascading: No Earth leakage protection: No Earth leakage protection device : Sensitivity : Delay : Earth leakage discrimination : Settings:
Overload: Magnetic:
Cable :
Length: Installation method: Cable type: Insulation: Arrangement of conductors: Ambient temperature:
C20
66.0 m E-circuits spaced out Multi-core cables on perforated horizontal tray Multi-core Number of layers: XLPE Nb additional touching circuits: Trefoil 40 C THDI level: 74.7 A 62.0 A : 0.91 : 1.00 : 1.00 : 0.91 : 1.00 : 1.00 ______ 0.83 metal Copper Copper Copper (52-D1) (A.52-16) (D.52-1) (52-E4) (433.1)
1 13 15 %
Permitted current by the cable (Iz): Iz under normal conditions of use (A): Iz x correction factors (real conditions of use): Sizing constraint: user-defined Correction : Temperature x Soil thermal resistivity x Neutral loaded x touching conductors x User / Protection )
reference
downstream 1.67
Thermal stress check: Energy received by the phase conductor : 608000 As Permitted thermal stress : 2044900 As
Calculation results:
(kA) R (m) X (m) Z (m) Isc upstr. 58.8078 1.4681 1.3440 1.9904 Ik3max 1.9527 123.6341 7.6800 123.8724 Ik2max 1.6909 247.2841 15.3528 247.7602 Ik1max 0.9762 247.2942 15.5256 247.7811 Ik2min 1.1804 319.9353 27.4448 321.1103 Ik1min 0.6850 318.6573 23.0039 319.4865 I fault 0.6745 323.4489 25.5959 324.4601
Calculation results in accordance with guide UTE C15-500 (CENELEC report R064-003). UTE approval 15L-602. All assumptions and device choices are the user's responsibility. Load
I: P: 15.00 A 8.39 kW Polarity of circuit: Earthing arrangement: My Ecodial L V3.4 3P+N TN-S
6/19/2012
Page 40
Power factor
0.85
1.0
My Ecodial L V3.4
6/19/2012
Page 41
Circuit :
Upstream : Downstream : Voltage :
Circuit breaker:
Q21
Frame rating (In): Trip unit: 100 A TM-D
Name: NSX100N-50.0 kA Trip unit rating: 80.00 A Number of poles: 3P3d Discrimination limit: T BC reinforced by cascading: No Earth leakage protection: No Earth leakage protection device : Sensitivity : Delay : Earth leakage discrimination : Settings:
Overload: Magnetic:
Cable :
Length: Installation method: Cable type: Insulation: Arrangement of conductors: Ambient temperature:
C21
58.5 m E-circuits spaced out Multi-core cables on perforated horizontal tray Multi-core Number of layers: XLPE Nb additional touching circuits: Trefoil 40 C THDI level: 157.9 A 131.1 A : 0.91 : 1.00 : 1.00 : 0.91 : 1.00 : 1.00 ______ 0.83 metal Copper Copper Copper (52-D1) (A.52-16) (D.52-1) (52-E4) (433.1)
1 13 15 %
Permitted current by the cable (Iz): Iz under normal conditions of use (A): Iz x correction factors (real conditions of use): Sizing constraint: user-defined Correction : Temperature x Soil thermal resistivity x Neutral loaded x touching conductors x User / Protection )
reference
downstream 1.79
Thermal stress check: Energy received by the phase conductor : 12288000 As Permitted thermal stress : 25050025 As
Calculation results:
(kA) R (m) X (m) Z (m) Isc upstr. 58.8078 1.4681 1.3440 1.9904 Ik3max 7.2976 32.4062 6.9600 33.1452 Ik2max 6.3186 64.8284 13.9128 66.3045 Ik1max 3.6455 64.8384 14.0856 66.3508 Ik2min 4.2014 86.3919 26.0048 90.2209 Ik1min 2.4924 85.1140 21.5639 87.8032 I fault 1.5739 136.9316 24.1559 139.0459
Calculation results in accordance with guide UTE C15-500 (CENELEC report R064-003). UTE approval 15L-602. All assumptions and device choices are the user's responsibility. Load
I: P: 62.70 A 35.07 kW Polarity of circuit: Earthing arrangement: 3P+N TN-S
My Ecodial L V3.4
6/19/2012
Page 42
Power factor
0.85
1.0
My Ecodial L V3.4
6/19/2012
Page 43
Circuit :
Upstream : Downstream : Voltage :
Circuit breaker:
Q22
Frame rating (In): Trip unit: 100 A TM-D
Name: NSX100N-50.0 kA Trip unit rating: 80.00 A Number of poles: 3P3d Discrimination limit: BC reinforced by cascading: No Earth leakage protection: No Earth leakage protection device : Sensitivity : Delay : Earth leakage discrimination : Settings:
Overload: Magnetic:
Load
I: P: Power factor
My Ecodial L V3.4
6/19/2012
Page 44
Circuit :
Upstream : Downstream : Voltage :
Busbars:
Designation: Type : Ambient temperature: Short-circuit temperature: Ks : Voltage drop:
B23
Linergy 800 Prisma-Linergy 40 C 85 C 0.95 0.0000 % Dimensions: Metal: I available: Isc max: Peak Isc (k) : 0.0 m-1// 0.0 mmx0 mm 750 A 7.30 kA 12.41 kA
My Ecodial L V3.4
6/19/2012
Page 45
Circuit :
Upstream : Downstream : Voltage :
Circuit breaker:
Q24
Frame rating (In): Trip unit: 100 A TM-D
Name: NSX100N-50.0 kA Trip unit rating: 32.00 A Number of poles: 3P3d Discrimination limit: 0.63 kA BC reinforced by cascading: No Earth leakage protection: No Earth leakage protection device : Sensitivity : Delay : Earth leakage discrimination : Settings:
Overload: Magnetic:
Cable :
Length: Installation method: Cable type: Insulation: Arrangement of conductors: Ambient temperature:
C24
13.0 m E-circuits spaced out Multi-core cables on perforated horizontal tray Multi-core Number of layers: XLPE Nb additional touching circuits: Trefoil 40 C THDI level: 74.7 A 68.0 A : 0.91 : 1.00 : 1.00 : 1.00 : 1.00 : 1.00 ______ 0.91 metal Copper Copper Copper (52-D1) (A.52-16) (D.52-1) (52-E4) (433.1)
1 0 15 %
Permitted current by the cable (Iz): Iz under normal conditions of use (A): Iz x correction factors (real conditions of use): Sizing constraint: user-defined Correction : Temperature x Soil thermal resistivity x Neutral loaded x touching conductors x User / Protection )
reference
downstream 1.94
Thermal stress check: Energy received by the phase conductor : 608000 As Permitted thermal stress : 2044900 As
Calculation results:
(kA) R (m) X (m) Z (m) Isc upstr. 7.2976 32.4062 6.9600 33.1452 Ik3max 4.2389 56.4692 8.2080 57.0626 Ik2max 3.6705 112.9544 16.4088 114.1400 Ik1max 2.1185 112.9644 16.5816 114.1749 Ik2min 2.5151 147.9932 28.5008 150.7126 Ik1min 1.4720 146.7153 24.0599 148.6750 I fault 1.0925 198.5328 26.6519 200.3138
Calculation results in accordance with guide UTE C15-500 (CENELEC report R064-003). UTE approval 15L-602. All assumptions and device choices are the user's responsibility. Load
I: P: 13.00 A 7.27 kW Polarity of circuit: Earthing arrangement: My Ecodial L V3.4 3P+N TN-S
6/19/2012
Page 46
Power factor
0.85
1.0
My Ecodial L V3.4
6/19/2012
Page 47
Circuit :
Upstream : Downstream : Voltage :
Load
My Ecodial L V3.4
6/19/2012
Page 48
Circuit :
Upstream : Downstream : Voltage :
Circuit breaker:
Q26
Frame rating (In): Trip unit: 100 A TM-D
Name: NSX100N-50.0 kA Trip unit rating: 80.00 A Number of poles: 3P3d Discrimination limit: T BC reinforced by cascading: No Earth leakage protection: No Earth leakage protection device : Sensitivity : Delay : Earth leakage discrimination : Settings:
Overload: Magnetic:
Cable :
Length: Installation method: Cable type: Insulation: Arrangement of conductors: Ambient temperature:
C26
60.0 m E-circuits spaced out Multi-core cables on perforated horizontal tray Multi-core Number of layers: XLPE Nb additional touching circuits: Trefoil 40 C THDI level: 157.9 A 131.1 A : 0.91 : 1.00 : 1.00 : 0.91 : 1.00 : 1.00 ______ 0.83 metal Copper Copper Copper (52-D1) (A.52-16) (D.52-1) (52-E4) (433.1)
1 13 15 %
Permitted current by the cable (Iz): Iz under normal conditions of use (A): Iz x correction factors (real conditions of use): Sizing constraint: user-defined Correction : Temperature x Soil thermal resistivity x Neutral loaded x touching conductors x User / Protection )
reference
downstream 1.78
Thermal stress check: Energy received by the phase conductor : 12288000 As Permitted thermal stress : 25050025 As
Calculation results:
(kA) R (m) X (m) Z (m) Isc upstr. 58.8078 1.4681 1.3440 1.9904 Ik3max 7.1244 33.1995 7.1040 33.9510 Ik2max 6.1686 66.4149 14.2008 67.9161 Ik1max 3.5590 66.4250 14.3736 67.9623 Ik2min 4.1090 88.4228 26.2928 92.2491 Ik1min 2.4359 87.1448 21.8519 89.8428 I fault 1.5381 140.1682 24.4439 142.2836
Calculation results in accordance with guide UTE C15-500 (CENELEC report R064-003). UTE approval 15L-602. All assumptions and device choices are the user's responsibility. Load
I: P: 60.64 A 33.92 kW Polarity of circuit: Earthing arrangement: 3P+N TN-S
My Ecodial L V3.4
6/19/2012
Page 49
Power factor
0.85
1.0
My Ecodial L V3.4
6/19/2012
Page 50
Circuit :
Upstream : Downstream : Voltage :
Circuit breaker:
Q27
Frame rating (In): Trip unit: 100 A TM-D
Name: NSX100N-50.0 kA Trip unit rating: 80.00 A Number of poles: 3P3d Discrimination limit: BC reinforced by cascading: No Earth leakage protection: No Earth leakage protection device : Sensitivity : Delay : Earth leakage discrimination : Settings:
Overload: Magnetic:
Load
I: P: Power factor
My Ecodial L V3.4
6/19/2012
Page 51
Circuit :
Upstream : Downstream : Voltage :
Busbars:
Designation: Type : Ambient temperature: Short-circuit temperature: Ks : Voltage drop:
B34
Linergy 800 Prisma-Linergy 40 C 85 C 0.95 0.0000 % Dimensions: Metal: I available: Isc max: Peak Isc (k) : 0.0 m-1// 0.0 mmx0 mm 750 A 7.12 kA 12.11 kA
My Ecodial L V3.4
6/19/2012
Page 52
Circuit :
Upstream : Downstream : Voltage :
Circuit breaker:
Q32
Frame rating (In): Trip unit: 100 A TM-D
Name: NSX100N-50.0 kA Trip unit rating: 32.00 A Number of poles: 3P3d Discrimination limit: 0.63 kA BC reinforced by cascading: No Earth leakage protection: No Earth leakage protection device : Sensitivity : Delay : Earth leakage discrimination : Settings:
Overload: Magnetic:
Cable :
Length: Installation method: Cable type: Insulation: Arrangement of conductors: Ambient temperature:
C32
10.0 m E-circuits spaced out Multi-core cables on perforated horizontal tray Multi-core Number of layers: XLPE Nb additional touching circuits: Trefoil 40 C THDI level: 74.7 A 68.0 A : 0.91 : 1.00 : 1.00 : 1.00 : 1.00 : 1.00 ______ 0.91 metal Copper Copper Copper (52-D1) (A.52-16) (D.52-1) (52-E4) (433.1)
1 0 15 %
Permitted current by the cable (Iz): Iz under normal conditions of use (A): Iz x correction factors (real conditions of use): Sizing constraint: user-defined Correction : Temperature x Soil thermal resistivity x Neutral loaded x touching conductors x User / Protection )
reference
downstream 1.85
Thermal stress check: Energy received by the phase conductor : 608000 As Permitted thermal stress : 2044900 As
Calculation results:
(kA) R (m) X (m) Z (m) Isc upstr. 7.1244 33.1995 7.1040 33.9510 Ik3max 4.6218 51.7095 8.0640 52.3345 Ik2max 4.0021 103.4349 16.1208 104.6836 Ik1max 2.3098 103.4450 16.2936 104.7203 Ik2min 2.7327 135.8084 28.2128 138.7079 Ik1min 1.6019 134.5304 23.7719 136.6145 I fault 1.1555 187.5538 26.3639 189.3977
Calculation results in accordance with guide UTE C15-500 (CENELEC report R064-003). UTE approval 15L-602. All assumptions and device choices are the user's responsibility. Load
I: P: 8.00 A 4.48 kW Polarity of circuit: Earthing arrangement: My Ecodial L V3.4 3P+N TN-S
6/19/2012
Page 53
Power factor
0.85
1.0
My Ecodial L V3.4
6/19/2012
Page 54
Circuit :
Upstream : Downstream : Voltage :
Load
My Ecodial L V3.4
6/19/2012
Page 55
Circuit :
Upstream : Downstream : Voltage :
Circuit breaker:
Q28
Frame rating (In): Trip unit: 80 A C
Name: NG125H-36.0 kA Trip unit rating: 80.00 A Number of poles: 3P3d Discrimination limit: T BC reinforced by cascading: No Earth leakage protection: No Earth leakage protection device : Sensitivity : Delay : Earth leakage discrimination : Settings:
Overload: Magnetic:
Ir = 80.0 A Im(Isd) = -
Cable :
Length: Installation method: Cable type: Insulation: Arrangement of conductors: Ambient temperature:
C28
70.0 m E-circuits spaced out Multi-core cables on perforated horizontal tray Multi-core Number of layers: XLPE Nb additional touching circuits: Trefoil 40 C THDI level: 157.9 A 131.1 A : 0.91 : 1.00 : 1.00 : 0.91 : 1.00 : 1.00 ______ 0.83 metal Copper Copper Copper (52-D1) (A.52-16) (D.52-1) (52-E4) (433.1)
1 13 15 %
Permitted current by the cable (Iz): Iz under normal conditions of use (A): Iz x correction factors (real conditions of use): Sizing constraint: user-defined Correction : Temperature x Soil thermal resistivity x Neutral loaded x touching conductors x User / Protection )
reference
downstream 1.94
Thermal stress check: Energy received by the phase conductor : 2560000 As Permitted thermal stress : 25050025 As
Calculation results:
(kA) R (m) X (m) Z (m) Isc upstr. 58.8078 1.4681 1.3440 1.9904 Ik3max 6.1510 38.4881 8.0640 39.3238 Ik2max 5.3260 76.9921 16.1208 78.6617 Ik1max 3.0732 77.0022 16.2936 78.7072 Ik2min 3.5829 101.9615 28.2128 105.7928 Ik1min 2.1154 100.6835 23.7719 103.4518 I fault 1.3354 161.7455 26.3639 163.8800
Calculation results in accordance with guide UTE C15-500 (CENELEC report R064-003). UTE approval 15L-602. All assumptions and device choices are the user's responsibility. Load
I: P: 59.96 A 33.55 kW Polarity of circuit: Earthing arrangement: 3P+N TN-S
My Ecodial L V3.4
6/19/2012
Page 56
Power factor
0.85
1.0
My Ecodial L V3.4
6/19/2012
Page 57
Circuit :
Upstream : Downstream : Voltage :
Circuit breaker:
Q29
Frame rating (In): Trip unit: 63 A C
Name: C60N-10.0 kA Trip unit rating: 63.00 A Number of poles: 3P3d Discrimination limit: BC reinforced by cascading: No Earth leakage protection: No Earth leakage protection device : Sensitivity : Delay : Earth leakage discrimination : Settings:
Overload: Magnetic:
Ir = 63.0 A Im(Isd) = -
Load
I: P: Power factor
My Ecodial L V3.4
6/19/2012
Page 58
Circuit :
Upstream : Downstream : Voltage :
Busbars:
Designation: Type : Ambient temperature: Short-circuit temperature: Ks : Voltage drop:
B37
Linergy 800 Prisma-Linergy 40 C 85 C 0.95 0.0000 % Dimensions: Metal: I available: Isc max: Peak Isc (k) : 0.0 m-1// 0.0 mmx0 mm 750 A 6.15 kA 10.46 kA
My Ecodial L V3.4
6/19/2012
Page 59
Circuit :
Upstream : Downstream : Voltage :
Circuit breaker:
Q35
Frame rating (In): Trip unit: 100 A TM-D
Name: NSX100N-50.0 kA Trip unit rating: 32.00 A Number of poles: 3P3d Discrimination limit: BC reinforced by cascading: No Earth leakage protection: No Earth leakage protection device : Sensitivity : Delay : Earth leakage discrimination : Settings:
Overload: Magnetic:
Cable :
Length: Installation method: Cable type: Insulation: Arrangement of conductors: Ambient temperature:
C35
10.0 m E-circuits spaced out Multi-core cables on perforated horizontal tray Multi-core Number of layers: XLPE Nb additional touching circuits: Trefoil 40 C THDI level: 74.7 A 68.0 A : 0.91 : 1.00 : 1.00 : 1.00 : 1.00 : 1.00 ______ 0.91 metal Copper Copper Copper (52-D1) (A.52-16) (D.52-1) (52-E4) (433.1)
1 0 15 %
Permitted current by the cable (Iz): Iz under normal conditions of use (A): Iz x correction factors (real conditions of use): Sizing constraint: user-defined Correction : Temperature x Soil thermal resistivity x Neutral loaded x touching conductors x User / Protection )
reference
downstream 2.00
Thermal stress check: Energy received by the phase conductor : 608000 As Permitted thermal stress : 2044900 As
Calculation results:
(kA) R (m) X (m) Z (m) Isc upstr. 6.1510 38.4881 8.0640 39.3238 Ik3max 4.1915 56.9981 9.0240 57.7080 Ik2max 3.6295 114.0121 18.0408 115.4306 Ik1max 2.0948 114.0222 18.2136 115.4677 Ik2min 2.4879 149.3471 30.1328 152.3566 Ik1min 1.4562 148.0691 25.6919 150.2815 I fault 1.0370 209.1311 28.2839 211.0351
Calculation results in accordance with guide UTE C15-500 (CENELEC report R064-003). UTE approval 15L-602. All assumptions and device choices are the user's responsibility. Load
I: P: 7.00 A 3.92 kW Polarity of circuit: Earthing arrangement: My Ecodial L V3.4 3P+N TN-S
6/19/2012
Page 60
Power factor
0.85
1.0
My Ecodial L V3.4
6/19/2012
Page 61
Circuit :
Upstream : Downstream : Voltage :
Load
My Ecodial L V3.4
6/19/2012
Page 62
Circuit :
Upstream : Downstream : Voltage :
Circuit breaker:
Q30
Frame rating (In): Trip unit: 160 A TM-D
Name: NG160N-25.0 kA Trip unit rating: 160.00 A Number of poles: 3P3d Discrimination limit: T BC reinforced by cascading: 36.0 kA Earth leakage protection: No Earth leakage protection device : Sensitivity : Delay : Earth leakage discrimination : Settings:
Overload: Magnetic:
Ir = Im(Isd) = 1250 A
Cable :
Length: Installation method: Cable type: Insulation: Arrangement of conductors: Ambient temperature:
C30
73.5 m E-circuits spaced out Multi-core cables on perforated horizontal tray Multi-core Number of layers: XLPE Nb additional touching circuits: Trefoil 40 C THDI level: 245.6 A 203.8 A : 0.91 : 1.00 : 1.00 : 0.91 : 1.00 : 1.00 ______ 0.83 metal Copper Copper Copper (52-D1) (A.52-16) (D.52-1) (52-E4) (433.1)
1 13 15 %
Permitted current by the cable (Iz): Iz under normal conditions of use (A): Iz x correction factors (real conditions of use): Sizing constraint: user-defined Correction : Temperature x Soil thermal resistivity x Neutral loaded x touching conductors x User / Protection )
reference
downstream 1.82
Thermal stress check: Energy received by the phase conductor : 39482726 As Permitted thermal stress : 100200100 As
Calculation results:
(kA) R (m) X (m) Z (m) Isc upstr. 58.8078 1.4681 1.3440 1.9904 Ik3max 10.7368 20.9036 8.4000 22.5282 Ik2max 9.2959 41.8231 16.7928 45.0685 Ik1max 5.3582 41.8332 16.9656 45.1425 Ik2min 5.9364 56.9452 28.8848 63.8521 Ik1min 3.5996 55.6672 24.4439 60.7975 I fault 2.4447 85.3363 27.0359 89.5166
Calculation results in accordance with guide UTE C15-500 (CENELEC report R064-003). UTE approval 15L-602. All assumptions and device choices are the user's responsibility. Load
I: P: 95.13 A 53.22 kW Polarity of circuit: Earthing arrangement: 3P+N TN-S
My Ecodial L V3.4
6/19/2012
Page 63
Power factor
0.85
1.0
My Ecodial L V3.4
6/19/2012
Page 64
Circuit :
Upstream : Downstream : Voltage :
Circuit breaker:
Q31
Frame rating (In): Trip unit: 160 A TM-D
Name: NG160E-16.0 kA Trip unit rating: 100.00 A Number of poles: 3P3d Discrimination limit: BC reinforced by cascading: No Earth leakage protection: No Earth leakage protection device : Sensitivity : Delay : Earth leakage discrimination : Settings:
Overload: Magnetic:
Ir = Im(Isd) = 1000 A
Load
I: P: Power factor
My Ecodial L V3.4
6/19/2012
Page 65
Circuit :
Upstream : Downstream : Voltage :
Busbars:
Designation: Type : Ambient temperature: Short-circuit temperature: Ks : Voltage drop:
B40
Linergy 800 Prisma-Linergy 40 C 85 C 0.95 0.0000 % Dimensions: Metal: I available: Isc max: Peak Isc (k) : 0.0 m-1// 0.0 mmx0 mm 750 A 10.74 kA 21.47 kA
My Ecodial L V3.4
6/19/2012
Page 66
Circuit :
Upstream : Downstream : Voltage :
Circuit breaker:
Q38
Frame rating (In): Trip unit: 100 A TM-D
Name: NSX100N-50.0 kA Trip unit rating: 32.00 A Number of poles: 3P3d Discrimination limit: BC reinforced by cascading: No Earth leakage protection: No Earth leakage protection device : Sensitivity : Delay : Earth leakage discrimination : Settings:
Overload: Magnetic:
Cable :
Length: Installation method: Cable type: Insulation: Arrangement of conductors: Ambient temperature:
C38
10.0 m E-circuits spaced out Multi-core cables on perforated horizontal tray Multi-core Number of layers: XLPE Nb additional touching circuits: Trefoil 40 C THDI level: 74.7 A 68.0 A : 0.91 : 1.00 : 1.00 : 1.00 : 1.00 : 1.00 ______ 0.91 metal Copper Copper Copper (52-D1) (A.52-16) (D.52-1) (52-E4) (433.1)
1 0 15 %
Permitted current by the cable (Iz): Iz under normal conditions of use (A): Iz x correction factors (real conditions of use): Sizing constraint: user-defined Correction : Temperature x Soil thermal resistivity x Neutral loaded x touching conductors x User / Protection )
reference
downstream 1.91
Thermal stress check: Energy received by the phase conductor : 608000 As Permitted thermal stress : 2044900 As
Calculation results:
(kA) R (m) X (m) Z (m) Isc upstr. 10.7368 20.9036 8.4000 22.5282 Ik3max 5.9709 39.4136 9.3600 40.5098 Ik2max 5.1701 78.8431 18.7128 81.0333 Ik1max 2.9831 78.8532 18.8856 81.0832 Ik2min 3.4844 104.3308 30.8048 108.7835 Ik1min 2.0574 103.0528 26.3639 106.3717 I fault 1.6110 132.7219 28.9559 135.8438
Calculation results in accordance with guide UTE C15-500 (CENELEC report R064-003). UTE approval 15L-602. All assumptions and device choices are the user's responsibility. Load
I: P: 11.00 A 6.15 kW Polarity of circuit: Earthing arrangement: My Ecodial L V3.4 3P+N TN-S
6/19/2012
Page 67
Power factor
0.85
1.0
My Ecodial L V3.4
6/19/2012
Page 68
Circuit :
Upstream : Downstream : Voltage :
Load
My Ecodial L V3.4
6/19/2012
Page 69
Circuit :
Upstream : Downstream : Voltage :
Circuit breaker:
Q110
Frame rating (In): Trip unit: 160 A TM-D
Name: NG160N-25.0 kA Trip unit rating: 125.00 A Number of poles: 3P3d Discrimination limit: T BC reinforced by cascading: 36.0 kA Earth leakage protection: No Earth leakage protection device : Sensitivity : Delay : Earth leakage discrimination : Settings:
Overload: Magnetic:
Ir = Im(Isd) = 1250 A
Cable :
Length: Installation method: Cable type: Insulation: Arrangement of conductors: Ambient temperature:
C110
110.0 m E-circuits spaced out Multi-core cables on perforated horizontal tray Multi-core Number of layers: XLPE Nb additional touching circuits: Trefoil 40 C THDI level: 198.2 A 180.4 A : 0.91 : 1.00 : 1.00 : 1.00 : 1.00 : 1.00 ______ 0.91 metal Copper Copper Copper (52-D1) (A.52-16) (D.52-1) (52-E4) (433.1)
1 0 15 %
Permitted current by the cable (Iz): Iz under normal conditions of use (A): Iz x correction factors (real conditions of use): Sizing constraint: voltage drop Correction : Temperature x Soil thermal resistivity x Neutral loaded x touching conductors x User / Protection )
reference
downstream 3.16
Thermal stress check: Energy received by the phase conductor : 15343750 As Permitted thermal stress : 51122500 As
Calculation results:
(kA) R (m) X (m) Z (m) Isc upstr. 58.8078 1.4681 1.3440 1.9904 Ik3max 5.5177 42.1901 11.9040 43.8373 Ik2max 4.7777 84.3961 23.8008 87.6880 Ik1max 2.7566 84.4062 23.9736 87.7447 Ik2min 3.2376 111.4386 35.8928 117.0763 Ik1min 1.9103 110.1607 31.4519 114.5627 I fault 1.5472 137.2912 34.0439 141.4491
Calculation results in accordance with guide UTE C15-500 (CENELEC report R064-003). UTE approval 15L-602. All assumptions and device choices are the user's responsibility. Load
I: P: 106.35 A 59.50 kW Polarity of circuit: Earthing arrangement: 3P+N TN-S
My Ecodial L V3.4
6/19/2012
Page 70
Power factor
0.85
1.0
My Ecodial L V3.4
6/19/2012
Page 71
Circuit :
Upstream : Downstream : Voltage :
Circuit breaker:
Q41
Frame rating (In): Trip unit: 2000 A Micrologic 2.0 A
Name: NW20N1-42.0 kA Trip unit rating: 2000.00 A Number of poles: 3P3d Discrimination limit: BC reinforced by cascading: No Earth leakage protection: No Earth leakage protection device : Sensitivity : Delay : Earth leakage discrimination : Settings:
Overload: Magnetic:
Load
I: P: Power factor
My Ecodial L V3.4
6/19/2012
Page 72
Circuit :
Upstream : Downstream : Voltage :
D42
1900.0 A 1.58 % Floor rising
Type: KTC2000 In permissible: Length: 101.0 m U (%): Calculation mode : Non-uniform distribution Installation method: Standard Application: distribution Sizing constraint: overloads The electrodynamic withstand was checked Correction : Voltage drop U (%) Circuit PPR TAP OFF TO BUS-41 TO BUS-42 LP41 TO BUS-T1 TO BUS-T2 LPT1 TO BUS-S1 TO BUS-S2 LPS1 TO BUS-F1 TO BUS-F2 LPF1 LPTG TAP OFF upstream 0.34 No. of circuits 1 1 1 1 1 1 1 1 1 1 1 1 1 1 user Protection circuit 1.58 d(m) 101 94 93 92 84 83 82 74 73 72 64 63 62 53 54.00 544.85 54.00 119.87 101.98 54.00 119.87 101.98 57.00 119.87 101.98 downst. 1.92 Ib(A) 114.84 119.87 147.16 : 1.00 : 1.00
Calculation results:
(kA) R (m) X (m) Z (m) Isc upstr. 37.3088 1.9277 6.1900 6.4832 Ik3max 28.0451 3.7525 7.7656 8.6247 Ik2max 25.4989 7.4831 14.6271 16.4301 Ik1max 18.3633 6.2773 11.5800 13.1720 Ik2min 25.0014 3.9886 14.6271 15.1612 Ik1min 18.4011 2.7106 11.5800 11.8930 I fault 5.9615 5.9856 36.2183 36.7096
Calculation results in accordance with guide UTE C15-500 (CENELEC report R064-003). UTE approval 15L-602. All assumptions and device choices are the user's responsibility.
My Ecodial L V3.4
6/19/2012
Page 73
Circuit :
Upstream : Downstream : Voltage :
Circuit breaker:
Q99
Frame rating (In): Trip unit: 160 A TM-D
Name: NSX160N-50.0 kA Trip unit rating: 160.00 A Number of poles: 3P3d Discrimination limit: T BC reinforced by cascading: No Earth leakage protection: No Earth leakage protection device : Sensitivity : Delay : Earth leakage discrimination : Settings:
Overload: Magnetic:
Cable :
Length: Installation method: Cable type: Insulation: Arrangement of conductors: Ambient temperature:
C99
10.0 m E-circuits spaced out Multi-core cables on perforated horizontal tray Multi-core Number of layers: XLPE Nb additional touching circuits: Trefoil 40 C THDI level: 346.2 A 315.0 A : 0.91 : 1.00 : 1.00 : 1.00 : 1.00 : 1.00 ______ 0.91 metal Copper Copper Copper (52-D1) (A.52-16) (D.52-1) (52-E4) (433.1)
1 0 15 %
Permitted current by the cable (Iz): Iz under normal conditions of use (A): Iz x correction factors (real conditions of use): Sizing constraint: user-defined Correction : Temperature x Soil thermal resistivity x Neutral loaded x touching conductors x User / Protection )
reference
downstream 2.03
Thermal stress check: Energy received by the phase conductor : 49152000 As Permitted thermal stress : 294465600 As
Calculation results:
(kA) R (m) X (m) Z (m) Isc upstr. 28.0451 3.7525 7.7656 8.6247 Ik3max 23.6986 5.2950 8.7256 10.2065 Ik2max 21.6866 10.5681 16.1714 19.3184 Ik1max 14.7231 9.3623 13.5000 16.4287 Ik2min 18.6320 12.3437 16.1714 20.3441 Ik1min 12.4957 11.1569 13.5000 17.5136 I fault 3.9188 40.7943 38.1383 55.8454
Calculation results in accordance with guide UTE C15-500 (CENELEC report R064-003). UTE approval 15L-602. All assumptions and device choices are the user's responsibility. Load
I: P: 114.84 A 64.26 kW Polarity of circuit: Earthing arrangement: 3P+N TN-S
My Ecodial L V3.4
6/19/2012
Page 74
Power factor
0.85
1.0
My Ecodial L V3.4
6/19/2012
Page 75
Circuit :
Upstream : Downstream : Voltage :
TO PPR ( ) - Calculated
PPR TAP OFF PPR 380 V Frame rating (In): Trip unit: 160 A TM-D
Circuit breaker:
Name: NG160E-16.0 kA Trip unit rating: 160.00 A Number of poles: 4P4d Discrimination limit: BC reinforced by cascading: 30.0 kA Earth leakage protection: No Earth leakage protection device : Sensitivity : Delay : Earth leakage discrimination : Settings:
Overload: Magnetic:
Ir = Im(Isd) = 1250 A
Load
I: P: Power factor
My Ecodial L V3.4
6/19/2012
Page 76
Circuit :
Upstream : Downstream : Voltage :
Busbars:
Designation: Type : Ambient temperature: Short-circuit temperature: Ks : Voltage drop:
B106
Linergy 800 Prisma-Linergy 40 C 85 C 0.95 0.0121 % Dimensions: Metal: I available: Isc max: Peak Isc (k) : 10.0 m-1// 0.0 mmx0 mm Copper 750 A 23.70 kA 49.77 kA
My Ecodial L V3.4
6/19/2012
Page 77
Circuit :
Upstream : Downstream : Voltage :
Circuit breaker:
Q100
Frame rating (In): Trip unit: 100 A TM-D
Name: NSX100N-50.0 kA Trip unit rating: 40.00 A Number of poles: 3P3d Discrimination limit: BC reinforced by cascading: No Earth leakage protection: No Earth leakage protection device : Sensitivity : Delay : Earth leakage discrimination : Settings:
Overload: Magnetic:
Cable :
Length: Installation method: Cable type: Insulation: Arrangement of conductors: Ambient temperature:
C100
17.5 m E-circuits spaced out Multi-core cables on perforated horizontal tray Multi-core Number of layers: XLPE Nb additional touching circuits: Trefoil 40 C THDI level: 100.1 A 83.1 A : 0.91 : 1.00 : 1.00 : 0.91 : 1.00 : 1.00 ______ 0.83 metal Copper Copper Copper (52-D1) (A.52-16) (D.52-1) (52-E4) (433.1)
1 9 15 %
Permitted current by the cable (Iz): Iz under normal conditions of use (A): Iz x correction factors (real conditions of use): Sizing constraint: user-defined Correction : Temperature x Soil thermal resistivity x Neutral loaded x touching conductors x User / Protection )
reference
downstream 2.25
Thermal stress check: Energy received by the phase conductor : 950000 As Permitted thermal stress : 5234944 As
Calculation results:
(kA) R (m) X (m) Z (m) Isc upstr. 23.6986 5.2950 8.7256 10.2065 Ik3max 8.7706 25.5403 10.4056 27.5787 Ik2max 7.6637 51.0588 19.5314 54.6670 Ik1max 4.5962 49.8529 16.8600 52.6267 Ik2min 5.6509 64.1717 19.5314 67.0782 Ik1min 3.3564 62.9849 16.8600 65.2024 I fault 2.1562 92.6223 41.4983 101.4938
Calculation results in accordance with guide UTE C15-500 (CENELEC report R064-003). UTE approval 15L-602. All assumptions and device choices are the user's responsibility. Load
I: P: 19.75 A 11.05 kW Polarity of circuit: Earthing arrangement: 3P+N TN-S
My Ecodial L V3.4
6/19/2012
Page 78
Power factor
0.85
1.0
My Ecodial L V3.4
6/19/2012
Page 79
Circuit :
Upstream : Downstream : Voltage :
Circuit breaker:
Q101
Frame rating (In): Trip unit: 100 A TM-D
Name: NSX100N-50.0 kA Trip unit rating: 40.00 A Number of poles: 3P3d Discrimination limit: BC reinforced by cascading: No Earth leakage protection: No Earth leakage protection device : Sensitivity : Delay : Earth leakage discrimination : Settings:
Overload: Magnetic:
Cable :
Length: Installation method: Cable type: Insulation: Arrangement of conductors: Ambient temperature:
C101
22.5 m E-circuits spaced out Multi-core cables on perforated horizontal tray Multi-core Number of layers: XLPE Nb additional touching circuits: Trefoil 40 C THDI level: 100.1 A 83.1 A : 0.91 : 1.00 : 1.00 : 0.91 : 1.00 : 1.00 ______ 0.83 metal Copper Copper Copper (52-D1) (A.52-16) (D.52-1) (52-E4) (433.1)
1 9 15 %
Permitted current by the cable (Iz): Iz under normal conditions of use (A): Iz x correction factors (real conditions of use): Sizing constraint: user-defined Correction : Temperature x Soil thermal resistivity x Neutral loaded x touching conductors x User / Protection )
reference
downstream 2.31
Thermal stress check: Energy received by the phase conductor : 950000 As Permitted thermal stress : 5234944 As
Calculation results:
(kA) R (m) X (m) Z (m) Isc upstr. 23.6986 5.2950 8.7256 10.2065 Ik3max 7.2939 31.3247 10.8856 33.1622 Ik2max 6.3579 62.6275 20.4914 65.8946 Ik1max 3.7821 61.4217 17.8200 63.9545 Ik2min 4.6455 78.9797 20.4914 81.5947 Ik1min 2.7421 77.7929 17.8200 79.8078 I fault 1.8945 107.4303 42.4583 115.5161
Calculation results in accordance with guide UTE C15-500 (CENELEC report R064-003). UTE approval 15L-602. All assumptions and device choices are the user's responsibility. Load
I: P: 19.75 A 11.05 kW Polarity of circuit: Earthing arrangement: 3P+N TN-S
My Ecodial L V3.4
6/19/2012
Page 80
Power factor
0.85
1.0
My Ecodial L V3.4
6/19/2012
Page 81
Circuit :
Upstream : Downstream : Voltage :
Circuit breaker:
Q102
Frame rating (In): Trip unit: 100 A TM-D
Name: NSX100N-50.0 kA Trip unit rating: 40.00 A Number of poles: 3P3d Discrimination limit: BC reinforced by cascading: No Earth leakage protection: No Earth leakage protection device : Sensitivity : Delay : Earth leakage discrimination : Settings:
Overload: Magnetic:
Cable :
Length: Installation method: Cable type: Insulation: Arrangement of conductors: Ambient temperature:
C102
11.0 m E-circuits spaced out Multi-core cables on perforated horizontal tray Multi-core Number of layers: XLPE Nb additional touching circuits: Trefoil 40 C THDI level: 100.1 A 83.1 A : 0.91 : 1.00 : 1.00 : 0.91 : 1.00 : 1.00 ______ 0.83 metal Copper Copper Copper (52-D1) (A.52-16) (D.52-1) (52-E4) (433.1)
1 9 15 %
Permitted current by the cable (Iz): Iz under normal conditions of use (A): Iz x correction factors (real conditions of use): Sizing constraint: user-defined Correction : Temperature x Soil thermal resistivity x Neutral loaded x touching conductors x User / Protection )
reference
downstream 2.13
Thermal stress check: Energy received by the phase conductor : 950000 As Permitted thermal stress : 5234944 As
Calculation results:
(kA) R (m) X (m) Z (m) Isc upstr. 23.6986 5.2950 8.7256 10.2065 Ik3max 11.7966 18.0207 9.7816 20.5043 Ik2max 10.3716 36.0194 18.2834 40.3941 Ik1max 6.3396 34.8135 15.6120 38.1538 Ik2min 7.8155 44.9213 18.2834 48.4995 Ik1min 4.7127 43.7345 15.6120 46.4375 I fault 2.6150 73.3719 40.2503 83.6870
Calculation results in accordance with guide UTE C15-500 (CENELEC report R064-003). UTE approval 15L-602. All assumptions and device choices are the user's responsibility. Load
I: P: 14.24 A 7.97 kW Polarity of circuit: Earthing arrangement: My Ecodial L V3.4 3P+N TN-S
6/19/2012
Page 82
Power factor
0.85
1.0
My Ecodial L V3.4
6/19/2012
Page 83
Circuit :
Upstream : Downstream : Voltage :
Circuit breaker:
Q103
Frame rating (In): Trip unit: 100 A TM-D
Name: NSX100N-50.0 kA Trip unit rating: 50.00 A Number of poles: 3P3d Discrimination limit: BC reinforced by cascading: No Earth leakage protection: No Earth leakage protection device : Sensitivity : Delay : Earth leakage discrimination : Settings:
Overload: Magnetic:
Cable :
Length: Installation method: Cable type: Insulation: Arrangement of conductors: Ambient temperature:
C103
20.0 m E-circuits spaced out Multi-core cables on perforated horizontal tray Multi-core Number of layers: XLPE Nb additional touching circuits: Trefoil 40 C THDI level: 100.1 A 83.1 A : 0.91 : 1.00 : 1.00 : 0.91 : 1.00 : 1.00 ______ 0.83 metal Copper Copper Copper (52-D1) (A.52-16) (D.52-1) (52-E4) (433.1)
1 9 15 %
Permitted current by the cable (Iz): Iz under normal conditions of use (A): Iz x correction factors (real conditions of use): Sizing constraint: user-defined Correction : Temperature x Soil thermal resistivity x Neutral loaded x touching conductors x User / Protection )
reference
downstream 2.29
Thermal stress check: Energy received by the phase conductor : 1000000 As Permitted thermal stress : 5234944 As
Calculation results:
(kA) R (m) X (m) Z (m) Isc upstr. 23.6986 5.2950 8.7256 10.2065 Ik3max 7.9671 28.4325 10.6456 30.3601 Ik2max 6.9521 56.8431 20.0114 60.2627 Ik1max 4.1506 55.6373 17.3400 58.2768 Ik2min 5.1002 71.5757 20.0114 74.3205 Ik1min 3.0188 70.3889 17.3400 72.4933 I fault 2.0174 100.0263 41.9783 108.4778
Calculation results in accordance with guide UTE C15-500 (CENELEC report R064-003). UTE approval 15L-602. All assumptions and device choices are the user's responsibility. Load
I: P: 20.90 A 11.69 kW Polarity of circuit: Earthing arrangement: 3P+N TN-S
My Ecodial L V3.4
6/19/2012
Page 84
Power factor
0.85
1.0
My Ecodial L V3.4
6/19/2012
Page 85
Circuit :
Upstream : Downstream : Voltage :
Circuit breaker:
Q104
Frame rating (In): Trip unit: 100 A TM-D
Name: NSX100N-50.0 kA Trip unit rating: 25.00 A Number of poles: 3P3d Discrimination limit: BC reinforced by cascading: No Earth leakage protection: No Earth leakage protection device : Sensitivity : Delay : Earth leakage discrimination : Settings:
Overload: Magnetic:
Cable :
Length: Installation method: Cable type: Insulation: Arrangement of conductors: Ambient temperature:
C104
11.0 m E-circuits spaced out Multi-core cables on perforated horizontal tray Multi-core Number of layers: XLPE Nb additional touching circuits: Trefoil 40 C THDI level: 100.1 A 83.1 A : 0.91 : 1.00 : 1.00 : 0.91 : 1.00 : 1.00 ______ 0.83 metal Copper Copper Copper (52-D1) (A.52-16) (D.52-1) (52-E4) (433.1)
1 9 15 %
Permitted current by the cable (Iz): Iz under normal conditions of use (A): Iz x correction factors (real conditions of use): Sizing constraint: user-defined Correction : Temperature x Soil thermal resistivity x Neutral loaded x touching conductors x User / Protection )
reference
downstream 2.11
Thermal stress check: Energy received by the phase conductor : 405000 As Permitted thermal stress : 5234944 As
Calculation results:
(kA) R (m) X (m) Z (m) Isc upstr. 23.6986 5.2950 8.7256 10.2065 Ik3max 11.7966 18.0207 9.7816 20.5043 Ik2max 10.3716 36.0194 18.2834 40.3941 Ik1max 6.3396 34.8135 15.6120 38.1538 Ik2min 7.8155 44.9213 18.2834 48.4995 Ik1min 4.7127 43.7345 15.6120 46.4375 I fault 2.6150 73.3719 40.2503 83.6870
Calculation results in accordance with guide UTE C15-500 (CENELEC report R064-003). UTE approval 15L-602. All assumptions and device choices are the user's responsibility. Load
I: P: 10.45 A 5.85 kW Polarity of circuit: Earthing arrangement: My Ecodial L V3.4 3P+N TN-S
6/19/2012
Page 86
Power factor
0.85
1.0
My Ecodial L V3.4
6/19/2012
Page 87
Circuit :
Upstream : Downstream : Voltage :
Circuit breaker:
Q105
Frame rating (In): Trip unit: 100 A TM-D
Name: NS100N-36.0 kA Trip unit rating: 32.00 A Number of poles: 3P3d Discrimination limit: 1.25 kA BC reinforced by cascading: 50.0 kA Earth leakage protection: No Earth leakage protection device : Sensitivity : Delay : Earth leakage discrimination : Settings:
Overload: Magnetic:
Cable :
Length: Installation method: Cable type: Insulation: Arrangement of conductors: Ambient temperature:
C105
26.0 m E-circuits spaced out Multi-core cables on perforated horizontal tray Multi-core Number of layers: XLPE Nb additional touching circuits: Trefoil 40 C THDI level: 100.1 A 83.1 A : 0.91 : 1.00 : 1.00 : 0.91 : 1.00 : 1.00 ______ 0.83 metal Copper Copper Copper (52-D1) (A.52-16) (D.52-1) (52-E4) (433.1)
1 9 15 %
Permitted current by the cable (Iz): Iz under normal conditions of use (A): Iz x correction factors (real conditions of use): Sizing constraint: user-defined Correction : Temperature x Soil thermal resistivity x Neutral loaded x touching conductors x User / Protection )
reference
downstream 2.26
Thermal stress check: Energy received by the phase conductor : 608000 As Permitted thermal stress : 5234944 As
Calculation results:
(kA) R (m) X (m) Z (m) Isc upstr. 23.6986 5.2950 8.7256 10.2065 Ik3max 6.5178 35.3738 11.2216 37.1110 Ik2max 5.6750 70.7256 21.1634 73.8241 Ik1max 3.3624 69.5198 18.4920 71.9372 Ik2min 4.1283 89.3453 21.1634 91.8176 Ik1min 2.4295 88.1585 18.4920 90.0770 I fault 1.7446 117.7959 43.1303 125.4436
Calculation results in accordance with guide UTE C15-500 (CENELEC report R064-003). UTE approval 15L-602. All assumptions and device choices are the user's responsibility. Load
I: P: 14.05 A 7.86 kW Polarity of circuit: Earthing arrangement: My Ecodial L V3.4 3P+N TN-S
6/19/2012
Page 88
Power factor
0.85
1.0
My Ecodial L V3.4
6/19/2012
Page 89
Circuit :
Upstream : Downstream : Voltage :
Circuit breaker:
Q107
Frame rating (In): Trip unit: 100 A TM-D
Name: NS100N-36.0 kA Trip unit rating: 32.00 A Number of poles: 3P3d Discrimination limit: 1.25 kA BC reinforced by cascading: 50.0 kA Earth leakage protection: No Earth leakage protection device : Sensitivity : Delay : Earth leakage discrimination : Settings:
Overload: Magnetic:
Cable :
Length: Installation method: Cable type: Insulation: Arrangement of conductors: Ambient temperature:
C107
23.0 m E-circuits spaced out Multi-core cables on perforated horizontal tray Multi-core Number of layers: XLPE Nb additional touching circuits: Trefoil 40 C THDI level: 100.1 A 83.1 A : 0.91 : 1.00 : 1.00 : 0.91 : 1.00 : 1.00 ______ 0.83 metal Copper Copper Copper (52-D1) (A.52-16) (D.52-1) (52-E4) (433.1)
1 9 15 %
Permitted current by the cable (Iz): Iz under normal conditions of use (A): Iz x correction factors (real conditions of use): Sizing constraint: user-defined Correction : Temperature x Soil thermal resistivity x Neutral loaded x touching conductors x User / Protection )
reference
downstream 2.24
Thermal stress check: Energy received by the phase conductor : 608000 As Permitted thermal stress : 5234944 As
Calculation results:
(kA) R (m) X (m) Z (m) Isc upstr. 23.6986 5.2950 8.7256 10.2065 Ik3max 7.1722 31.9032 10.9336 33.7247 Ik2max 6.2507 63.7844 20.5874 67.0246 Ik1max 3.7159 62.5785 17.9160 65.0926 Ik2min 4.5640 80.4605 20.5874 83.0526 Ik1min 2.6927 79.2737 17.9160 81.2730 I fault 1.8716 108.9111 42.5543 116.9295
Calculation results in accordance with guide UTE C15-500 (CENELEC report R064-003). UTE approval 15L-602. All assumptions and device choices are the user's responsibility. Load
I: P: 14.24 A 7.97 kW Polarity of circuit: Earthing arrangement: My Ecodial L V3.4 3P+N TN-S
6/19/2012
Page 90
Power factor
0.85
1.0
My Ecodial L V3.4
6/19/2012
Page 91
Circuit :
Upstream : Downstream : Voltage :
Load
My Ecodial L V3.4
6/19/2012
Page 92
Circuit :
Upstream : Downstream : Voltage :
Circuit breaker:
AUTO248
Frame rating (In): Trip unit: 160 A TM-D
Name: NSX160N-50.0 kA Trip unit rating: 125.00 A Number of poles: 3P3d Discrimination limit: T BC reinforced by cascading: No Earth leakage protection: No Earth leakage protection device : Sensitivity : Delay : Earth leakage discrimination : Settings:
Overload: Magnetic:
Ir = Im(Isd) = 1049 A
Load
I: P: Power factor
My Ecodial L V3.4
6/19/2012
Page 93
Circuit :
Upstream : Downstream : Voltage :
D98
155.2 A 1.80 % Plug-in tap-off units
Type: KNA160 In permissible: Length: 128.0 m U (%): Calculation mode : Non-uniform distribution Installation method: Standard Application: Sizing constraint: overloads The electrodynamic withstand was checked Correction : Voltage drop U (%) Circuit CB4-4 CB4-5 CB4-6 CB4-7 upstream 1.90 No. of circuits 1 1 1 1 user Protection circuit 1.80 d(m) 13 26 39 50 downst. 3.70 Ib(A) 18.85 21.60 28.44 64.30 : 1.00 : 1.00
Calculation results:
(kA) R (m) X (m) Z (m) Isc upstr. 37.3088 3.6261 7.6564 8.4717 Ik3max 2.5995 81.7061 44.5204 93.0481 Ik2max 1.9831 162.1128 135.4652 211.2614 Ik1max 1.1644 164.7418 126.5272 207.7234 Ik2min 2.7932 8.0895 135.4652 135.7065 Ik1min 1.7271 6.8964 126.5272 126.7150 I fault 1.3117 33.3941 163.4615 166.8377
Calculation results in accordance with guide UTE C15-500 (CENELEC report R064-003). UTE approval 15L-602. All assumptions and device choices are the user's responsibility.
My Ecodial L V3.4
6/19/2012
Page 94
Circuit :
Upstream : Downstream : Voltage :
Circuit breaker:
Q94
Frame rating (In): Trip unit: 100 A TM-D
Name: NSX100N-50.0 kA Trip unit rating: 40.00 A Number of poles: 3P3d Discrimination limit: T BC reinforced by cascading: No Earth leakage protection: No Earth leakage protection device : Sensitivity : Delay : Earth leakage discrimination : Settings:
Overload: Magnetic:
Cable :
Length: Installation method: Cable type: Insulation: Arrangement of conductors: Ambient temperature:
C94
10.0 m E-circuits spaced out Multi-core cables on perforated horizontal tray Multi-core Number of layers: XLPE Nb additional touching circuits: Trefoil 40 C THDI level: 74.7 A 68.0 A : 0.91 : 1.00 : 1.00 : 1.00 : 1.00 : 1.00 ______ 0.91 metal Copper Copper Copper (52-D1) (A.52-16) (D.52-1) (52-E4) (433.1)
1 0 15 %
Permitted current by the cable (Iz): Iz under normal conditions of use (A): Iz x correction factors (real conditions of use): Sizing constraint: user-defined Correction : Temperature x Soil thermal resistivity x Neutral loaded x touching conductors x User / Protection )
reference
downstream 2.67
Thermal stress check: Energy received by the phase conductor : 950000 As Permitted thermal stress : 2044900 As
Calculation results:
(kA) R (m) X (m) Z (m) Isc upstr. 14.9005 11.5561 11.4004 16.2331 Ik3max 7.4407 30.0661 12.3604 32.5077 Ik2max 6.3962 59.9828 26.3112 65.4997 Ik1max 3.7672 59.1618 24.9472 64.2066 Ik2min 4.7122 76.0151 26.3112 80.4399 Ik1min 2.7617 75.2120 24.9472 79.2415 I fault 1.8195 109.6397 49.4615 120.2801
Calculation results in accordance with guide UTE C15-500 (CENELEC report R064-003). UTE approval 15L-602. All assumptions and device choices are the user's responsibility. Load
I: P: 18.85 A 10.55 kW Polarity of circuit: Earthing arrangement: 3P+N TN-S
My Ecodial L V3.4
6/19/2012
Page 95
Power factor
0.85
1.0
My Ecodial L V3.4
6/19/2012
Page 96
Circuit :
Upstream : Downstream : Voltage :
Circuit breaker:
Q95
Frame rating (In): Trip unit: 100 A TM-D
Name: NSX100N-50.0 kA Trip unit rating: 40.00 A Number of poles: 3P3d Discrimination limit: T BC reinforced by cascading: No Earth leakage protection: No Earth leakage protection device : Sensitivity : Delay : Earth leakage discrimination : Settings:
Overload: Magnetic:
Cable :
Length: Installation method: Cable type: Insulation: Arrangement of conductors: Ambient temperature:
C95
10.0 m E-circuits spaced out Multi-core cables on perforated horizontal tray Multi-core Number of layers: XLPE Nb additional touching circuits: Trefoil 40 C THDI level: 74.7 A 68.0 A : 0.91 : 1.00 : 1.00 : 1.00 : 1.00 : 1.00 ______ 0.91 metal Copper Copper Copper (52-D1) (A.52-16) (D.52-1) (52-E4) (433.1)
1 0 15 %
Permitted current by the cable (Iz): Iz under normal conditions of use (A): Iz x correction factors (real conditions of use): Sizing constraint: user-defined Correction : Temperature x Soil thermal resistivity x Neutral loaded x touching conductors x User / Protection )
reference
downstream 3.21
Thermal stress check: Energy received by the phase conductor : 950000 As Permitted thermal stress : 2044900 As
Calculation results:
(kA) R (m) X (m) Z (m) Isc upstr. 9.8010 19.4861 15.1444 24.6792 Ik3max 5.8612 37.9961 16.1044 41.2681 Ik2max 4.9823 75.7128 36.5812 84.0869 Ik1max 2.8889 75.2818 36.6472 83.7279 Ik2min 3.6711 96.5551 36.5812 103.2525 Ik1min 2.1270 96.1420 36.6472 102.8898 I fault 1.4400 138.4997 62.5655 151.9757
Calculation results in accordance with guide UTE C15-500 (CENELEC report R064-003). UTE approval 15L-602. All assumptions and device choices are the user's responsibility. Load
I: P: 21.60 A 12.08 kW Polarity of circuit: Earthing arrangement: 3P+N TN-S
My Ecodial L V3.4
6/19/2012
Page 97
Power factor
0.85
1.0
My Ecodial L V3.4
6/19/2012
Page 98
Circuit :
Upstream : Downstream : Voltage :
Circuit breaker:
Q96
Frame rating (In): Trip unit: 100 A TM-D
Name: NSX100N-50.0 kA Trip unit rating: 40.00 A Number of poles: 3P3d Discrimination limit: T BC reinforced by cascading: No Earth leakage protection: No Earth leakage protection device : Sensitivity : Delay : Earth leakage discrimination : Settings:
Overload: Magnetic:
Cable :
Length: Installation method: Cable type: Insulation: Arrangement of conductors: Ambient temperature:
C96
10.0 m E-circuits spaced out Multi-core cables on perforated horizontal tray Multi-core Number of layers: XLPE Nb additional touching circuits: Trefoil 40 C THDI level: 74.7 A 68.0 A : 0.91 : 1.00 : 1.00 : 1.00 : 1.00 : 1.00 ______ 0.91 metal Copper Copper Copper (52-D1) (A.52-16) (D.52-1) (52-E4) (433.1)
1 0 15 %
Permitted current by the cable (Iz): Iz under normal conditions of use (A): Iz x correction factors (real conditions of use): Sizing constraint: user-defined Correction : Temperature x Soil thermal resistivity x Neutral loaded x touching conductors x User / Protection )
reference
downstream 3.71
Thermal stress check: Energy received by the phase conductor : 950000 As Permitted thermal stress : 2044900 As
Calculation results:
(kA) R (m) X (m) Z (m) Isc upstr. 7.2653 27.4161 18.8884 33.2929 Ik3max 4.8346 45.9261 19.8484 50.0316 Ik2max 4.0775 91.4428 46.8512 102.7464 Ik1max 2.3393 91.4018 48.3472 103.4009 Ik2min 3.0055 117.0951 46.8512 126.1202 Ik1min 1.7278 117.0720 48.3472 126.6622 I fault 1.1915 167.3597 75.6695 183.6713
Calculation results in accordance with guide UTE C15-500 (CENELEC report R064-003). UTE approval 15L-602. All assumptions and device choices are the user's responsibility. Load
I: P: 28.44 A 15.91 kW Polarity of circuit: Earthing arrangement: 3P+N TN-S
My Ecodial L V3.4
6/19/2012
Page 99
Power factor
0.85
1.0
My Ecodial L V3.4
6/19/2012
Page 100
Circuit :
Upstream : Downstream : Voltage :
Circuit breaker:
Q97
Frame rating (In): Trip unit: 100 A TM-D
Name: NSX100N-50.0 kA Trip unit rating: 80.00 A Number of poles: 3P3d Discrimination limit: T BC reinforced by cascading: No Earth leakage protection: No Earth leakage protection device : Sensitivity : Delay : Earth leakage discrimination : Settings:
Overload: Magnetic:
Cable :
Length: Installation method: Cable type: Insulation: Arrangement of conductors: Ambient temperature:
C97
10.0 m E-circuits spaced out Multi-core cables on perforated horizontal tray Multi-core Number of layers: XLPE Nb additional touching circuits: Trefoil 40 C THDI level: 157.9 A 143.7 A : 0.91 : 1.00 : 1.00 : 1.00 : 1.00 : 1.00 ______ 0.91 metal Copper Copper Copper (52-D1) (A.52-16) (D.52-1) (52-E4) (433.1)
1 0 15 %
Permitted current by the cable (Iz): Iz under normal conditions of use (A): Iz x correction factors (real conditions of use): Sizing constraint: user-defined Correction : Temperature x Soil thermal resistivity x Neutral loaded x touching conductors x User / Protection )
reference
downstream 3.88
Thermal stress check: Energy received by the phase conductor : 12288000 As Permitted thermal stress : 25050025 As
Calculation results:
(kA) R (m) X (m) Z (m) Isc upstr. 5.9528 34.1261 22.0564 40.6334 Ik3max 5.2994 39.4146 23.0164 45.6428 Ik2max 4.3638 78.3100 55.5412 96.0067 Ik1max 2.4725 78.5989 58.2472 97.8290 Ik2min 3.2978 100.6283 55.5412 114.9386 Ik1min 1.8779 100.9352 58.2472 116.5360 I fault 1.1685 165.9715 86.7575 187.2789
Calculation results in accordance with guide UTE C15-500 (CENELEC report R064-003). UTE approval 15L-602. All assumptions and device choices are the user's responsibility. Load
I: P: 64.30 A 35.97 kW Polarity of circuit: Earthing arrangement: 3P+N TN-S
My Ecodial L V3.4
6/19/2012
Page 101
Power factor
0.85
1.0
My Ecodial L V3.4
6/19/2012
Page 102
Circuit :
Upstream : Downstream : Voltage :
Circuit breaker:
AUTO235
Frame rating (In): Trip unit: 160 A TM-D
Name: NSX160N-50.0 kA Trip unit rating: 160.00 A Number of poles: 3P3d Discrimination limit: T BC reinforced by cascading: No Earth leakage protection: No Earth leakage protection device : Sensitivity : Delay : Earth leakage discrimination : Settings:
Overload: Magnetic:
Load
I: P: Power factor
My Ecodial L V3.4
6/19/2012
Page 103
Circuit :
Upstream : Downstream : Voltage :
D92
242.5 A 1.03 % Plug-in tap-off units
Type: KSA250 In permissible: Length: 77.0 m U (%): Calculation mode : Non-uniform distribution Installation method: Standard Application: Sizing constraint: overloads The electrodynamic withstand was checked Correction : Voltage drop U (%) Circuit CB4-3 CB4-2 CB4-1 upstream 1.90 No. of circuits 1 1 1 user Protection circuit 1.03 d(m) 13 22 42 downst. 2.93 Ib(A) 20.10 43.11 100.30 : 1.00 : 1.00
Calculation results:
(kA) R (m) X (m) Z (m) Isc upstr. 37.3088 3.6080 7.6408 8.4498 Ik3max 7.1756 25.1680 22.4248 33.7090 Ik2max 5.8186 57.2471 43.6706 72.0024 Ik1max 2.9419 62.9653 52.8710 82.2190 Ik2min 4.6852 68.1059 43.6706 80.9045 Ik1min 2.4949 69.9919 52.8710 87.7166 I fault 1.7316 103.1725 72.9911 126.3814
Calculation results in accordance with guide UTE C15-500 (CENELEC report R064-003). UTE approval 15L-602. All assumptions and device choices are the user's responsibility.
My Ecodial L V3.4
6/19/2012
Page 104
Circuit :
Upstream : Downstream : Voltage :
Circuit breaker:
Q89
Frame rating (In): Trip unit: 100 A TM-D
Name: NS100N-36.0 kA Trip unit rating: 40.00 A Number of poles: 3P3d Discrimination limit: 2 kA BC reinforced by cascading: 50.0 kA Earth leakage protection: No Earth leakage protection device : Sensitivity : Delay : Earth leakage discrimination : Settings:
Overload: Magnetic:
Cable :
Length: Installation method: Cable type: Insulation: Arrangement of conductors: Ambient temperature:
C89
10.0 m E-circuits spaced out Multi-core cables on perforated horizontal tray Multi-core Number of layers: XLPE Nb additional touching circuits: Trefoil 40 C THDI level: 74.7 A 68.0 A : 0.91 : 1.00 : 1.00 : 1.00 : 1.00 : 1.00 ______ 0.91 metal Copper Copper Copper (52-D1) (A.52-16) (D.52-1) (52-E4) (433.1)
1 0 15 %
Permitted current by the cable (Iz): Iz under normal conditions of use (A): Iz x correction factors (real conditions of use): Sizing constraint: user-defined Correction : Temperature x Soil thermal resistivity x Neutral loaded x touching conductors x User / Protection )
reference
downstream 2.48
Thermal stress check: Energy received by the phase conductor : 950000 As Permitted thermal stress : 2044900 As
Calculation results:
(kA) R (m) X (m) Z (m) Isc upstr. 19.4103 7.2480 10.1368 12.4615 Ik3max 8.6242 25.7580 11.0968 28.0466 Ik2max 7.4280 52.6671 20.1826 56.4018 Ik1max 4.2902 52.6253 20.2310 56.3801 Ik2min 5.5249 65.5715 20.1826 68.6073 Ik1min 3.2194 64.8975 20.2310 67.9778 I fault 2.1519 92.3181 42.6551 101.6961
Calculation results in accordance with guide UTE C15-500 (CENELEC report R064-003). UTE approval 15L-602. All assumptions and device choices are the user's responsibility. Load
I: P: 20.10 A 11.24 kW Polarity of circuit: Earthing arrangement: 3P+N TN-S
My Ecodial L V3.4
6/19/2012
Page 105
Power factor
0.85
1.0
My Ecodial L V3.4
6/19/2012
Page 106
Circuit :
Upstream : Downstream : Voltage :
Circuit breaker:
Q90
Frame rating (In): Trip unit: 100 A TM-D
Name: NSX100N-50.0 kA Trip unit rating: 63.00 A Number of poles: 3P3d Discrimination limit: 2 kA BC reinforced by cascading: No Earth leakage protection: No Earth leakage protection device : Sensitivity : Delay : Earth leakage discrimination : Settings:
Overload: Magnetic:
Cable :
Length: Installation method: Cable type: Insulation: Arrangement of conductors: Ambient temperature:
C90
10.0 m E-circuits spaced out Multi-core cables on perforated horizontal tray Multi-core Number of layers: XLPE Nb additional touching circuits: Trefoil 40 C THDI level: 127.4 A 115.9 A : 0.91 : 1.00 : 1.00 : 1.00 : 1.00 : 1.00 ______ 0.91 metal Copper Copper Copper (52-D1) (A.52-16) (D.52-1) (52-E4) (433.1)
1 0 15 %
Permitted current by the cable (Iz): Iz under normal conditions of use (A): Iz x correction factors (real conditions of use): Sizing constraint: user-defined Correction : Temperature x Soil thermal resistivity x Neutral loaded x touching conductors x User / Protection )
reference
downstream 2.70
Thermal stress check: Energy received by the phase conductor : 1587600 As Permitted thermal stress : 12780625 As
Calculation results:
(kA) R (m) X (m) Z (m) Isc upstr. 15.7389 9.7680 11.8648 15.3684 Ik3max 11.2857 17.1720 12.8248 21.4325 Ik2max 9.7405 36.3051 23.0626 43.0110 Ik1max 5.4032 37.0733 25.0910 44.7659 Ik2min 7.6084 44.1601 23.0626 49.8197 Ik1min 4.3320 43.8461 25.0910 50.5177 I fault 2.4139 77.4077 47.1911 90.6584
Calculation results in accordance with guide UTE C15-500 (CENELEC report R064-003). UTE approval 15L-602. All assumptions and device choices are the user's responsibility. Load
I: P: 43.11 A 24.12 kW Polarity of circuit: Earthing arrangement: 3P+N TN-S
My Ecodial L V3.4
6/19/2012
Page 107
Power factor
0.85
1.0
My Ecodial L V3.4
6/19/2012
Page 108
Circuit :
Upstream : Downstream : Voltage :
Circuit breaker:
Q91
Frame rating (In): Trip unit: 160 A TM-D
Name: NG160H-36.0 kA Trip unit rating: 125.00 A Number of poles: 3P3d Discrimination limit: BC reinforced by cascading: 50.0 kA Earth leakage protection: No Earth leakage protection device : Sensitivity : Delay : Earth leakage discrimination : Settings:
Overload: Magnetic:
Ir = Im(Isd) = 1250 A
Cable :
Length: Installation method: Cable type: Insulation: Arrangement of conductors: Ambient temperature:
C91
10.0 m E-circuits spaced out Multi-core cables on perforated horizontal tray Multi-core Number of layers: XLPE Nb additional touching circuits: Trefoil 40 C THDI level: 157.9 A 143.7 A : 0.91 : 1.00 : 1.00 : 1.00 : 1.00 : 1.00 ______ 0.91 metal Copper Copper Copper (52-D1) (A.52-16) (D.52-1) (52-E4) (433.1)
1 0 15 %
Permitted current by the cable (Iz): Iz under normal conditions of use (A): Iz x correction factors (real conditions of use): Sizing constraint: overloads Correction : Temperature x Soil thermal resistivity x Neutral loaded x touching conductors x User / Protection )
reference
downstream 3.22
Thermal stress check: Energy received by the phase conductor : 15343750 As Permitted thermal stress : 25050025 As
Calculation results:
(kA) R (m) X (m) Z (m) Isc upstr. 11.0081 15.3680 15.7048 21.9731 Ik3max 9.1136 20.6566 16.6648 26.5407 Ik2max 7.7801 45.0742 29.4626 53.8491 Ik1max 4.0551 47.6424 35.8910 59.6487 Ik2min 6.1318 54.3446 29.4626 61.8173 Ik1min 3.3395 54.8306 35.8910 65.5329 I fault 2.0053 92.8999 57.2711 109.1346
Calculation results in accordance with guide UTE C15-500 (CENELEC report R064-003). UTE approval 15L-602. All assumptions and device choices are the user's responsibility. Load
I: P: 100.30 A 56.11 kW Polarity of circuit: Earthing arrangement: 3P+N TN-S
My Ecodial L V3.4
6/19/2012
Page 109
Power factor
0.85
1.0
My Ecodial L V3.4
6/19/2012
Page 110
Circuit :
Upstream : Downstream : Voltage :
Circuit breaker:
Q87
Frame rating (In): Trip unit: 100 A TM-D
Name: NSX100N-50.0 kA Trip unit rating: 63.00 A Number of poles: 3P3d Discrimination limit: T BC reinforced by cascading: No Earth leakage protection: No Earth leakage protection device : Sensitivity : Delay : Earth leakage discrimination : Settings:
Overload: Magnetic:
Cable :
Length: Installation method: Cable type: Insulation: Arrangement of conductors: Ambient temperature:
C87
11.0 m E-circuits spaced out Multi-core cables on perforated horizontal tray Multi-core Number of layers: XLPE Nb additional touching circuits: Trefoil 40 C THDI level: 100.1 A 91.1 A : 0.91 : 1.00 : 1.00 : 1.00 : 1.00 : 1.00 ______ 0.91 metal Copper Copper Copper (52-D1) (A.52-16) (D.52-1) (52-E4) (433.1)
1 0 15 %
Permitted current by the cable (Iz): Iz under normal conditions of use (A): Iz x correction factors (real conditions of use): Sizing constraint: user-defined Correction : Temperature x Soil thermal resistivity x Neutral loaded x touching conductors x User / Protection )
reference
downstream 2.26
Thermal stress check: Energy received by the phase conductor : 1587600 As Permitted thermal stress : 5234944 As
Calculation results:
(kA) R (m) X (m) Z (m) Isc upstr. 28.6997 3.5899 7.6252 8.4280 Ik3max 13.0878 16.3156 8.6812 18.4814 Ik2max 11.5056 32.6126 16.1960 36.4128 Ik1max 7.0877 31.4000 13.3669 34.1267 Ik2min 8.6754 40.5799 16.1960 43.6925 Ik1min 5.2618 39.3850 13.3669 41.5915 I fault 2.9311 65.3886 36.0407 74.6633
Calculation results in accordance with guide UTE C15-500 (CENELEC report R064-003). UTE approval 15L-602. All assumptions and device choices are the user's responsibility. Load
I: P: 57.00 A 31.89 kW Polarity of circuit: Earthing arrangement: 3P+N TN-S
My Ecodial L V3.4
6/19/2012
Page 111
Power factor
0.85
1.0
My Ecodial L V3.4
6/19/2012
Page 112
Circuit :
Upstream : Downstream : Voltage :
Circuit breaker:
AUTO216
Frame rating (In): Trip unit: 160 A Micrologic 2.2
Name: NSX160N-50.0 kA Trip unit rating: 125.00 A Number of poles: 3P3d Discrimination limit: T BC reinforced by cascading: No Earth leakage protection: No Earth leakage protection device : Sensitivity : Delay : Earth leakage discrimination : Settings:
Overload: Magnetic:
Load
I: P: Power factor
My Ecodial L V3.4
6/19/2012
Page 113
Circuit :
Upstream : Downstream : Voltage :
D86
155.2 A 1.80 % Plug-in tap-off units
Type: KNA160 In permissible: Length: 128.0 m U (%): Calculation mode : Non-uniform distribution Installation method: Standard Application: Sizing constraint: overloads The electrodynamic withstand was checked Correction : Voltage drop U (%) Circuit CBT-4 CBT-5 CBT-6 CBT-7 upstream 1.84 No. of circuits 1 1 1 1 user Protection circuit 1.80 d(m) 13 26 39 50 downst. 3.64 Ib(A) 18.85 21.60 28.44 64.30 : 1.00 : 1.00
Calculation results:
(kA) R (m) X (m) Z (m) Isc upstr. 37.3088 3.4454 7.5004 8.2539 Ik3max 2.6061 81.5254 44.3644 92.8148 Ik2max 1.9868 161.7552 135.2792 210.8678 Ik1max 1.1673 164.3768 126.1660 207.2139 Ik2min 1.5180 209.8933 135.2792 249.7112 Ik1min 0.8854 212.5311 126.1660 247.1585 I fault 0.6193 314.6383 160.9175 353.4002
Calculation results in accordance with guide UTE C15-500 (CENELEC report R064-003). UTE approval 15L-602. All assumptions and device choices are the user's responsibility.
My Ecodial L V3.4
6/19/2012
Page 114
Circuit :
Upstream : Downstream : Voltage :
Circuit breaker:
Q82
Frame rating (In): Trip unit: 100 A TM-D
Name: NSX100N-50.0 kA Trip unit rating: 40.00 A Number of poles: 3P3d Discrimination limit: T BC reinforced by cascading: No Earth leakage protection: No Earth leakage protection device : Sensitivity : Delay : Earth leakage discrimination : Settings:
Overload: Magnetic:
Cable :
Length: Installation method: Cable type: Insulation: Arrangement of conductors: Ambient temperature:
C82
10.0 m E-circuits spaced out Multi-core cables on perforated horizontal tray Multi-core Number of layers: XLPE Nb additional touching circuits: Trefoil 40 C THDI level: 74.7 A 68.0 A : 0.91 : 1.00 : 1.00 : 1.00 : 1.00 : 1.00 ______ 0.91 metal Copper Copper Copper (52-D1) (A.52-16) (D.52-1) (52-E4) (433.1)
1 0 15 %
Permitted current by the cable (Iz): Iz under normal conditions of use (A): Iz x correction factors (real conditions of use): Sizing constraint: user-defined Correction : Temperature x Soil thermal resistivity x Neutral loaded x touching conductors x User / Protection )
reference
downstream 2.61
Thermal stress check: Energy received by the phase conductor : 950000 As Permitted thermal stress : 2044900 As
Calculation results:
(kA) R (m) X (m) Z (m) Isc upstr. 15.1224 11.3754 11.2444 15.9949 Ik3max 7.4929 29.8854 12.2044 32.2813 Ik2max 6.4357 59.6252 26.1252 65.0975 Ik1max 3.7954 58.7968 24.5860 63.7302 Ik2min 4.7401 75.5789 26.1252 79.9668 Ik1min 2.7806 74.7667 24.5860 78.7053 I fault 1.8772 106.7239 46.9175 116.5815
Calculation results in accordance with guide UTE C15-500 (CENELEC report R064-003). UTE approval 15L-602. All assumptions and device choices are the user's responsibility. Load
I: P: 18.85 A 10.55 kW Polarity of circuit: Earthing arrangement: 3P+N TN-S
My Ecodial L V3.4
6/19/2012
Page 115
Power factor
0.85
1.0
My Ecodial L V3.4
6/19/2012
Page 116
Circuit :
Upstream : Downstream : Voltage :
Circuit breaker:
Q83
Frame rating (In): Trip unit: 100 A TM-D
Name: NSX100N-50.0 kA Trip unit rating: 40.00 A Number of poles: 3P3d Discrimination limit: T BC reinforced by cascading: No Earth leakage protection: No Earth leakage protection device : Sensitivity : Delay : Earth leakage discrimination : Settings:
Overload: Magnetic:
Cable :
Length: Installation method: Cable type: Insulation: Arrangement of conductors: Ambient temperature:
C83
10.0 m E-circuits spaced out Multi-core cables on perforated horizontal tray Multi-core Number of layers: XLPE Nb additional touching circuits: Trefoil 40 C THDI level: 74.7 A 68.0 A : 0.91 : 1.00 : 1.00 : 1.00 : 1.00 : 1.00 ______ 0.91 metal Copper Copper Copper (52-D1) (A.52-16) (D.52-1) (52-E4) (433.1)
1 0 15 %
Permitted current by the cable (Iz): Iz under normal conditions of use (A): Iz x correction factors (real conditions of use): Sizing constraint: user-defined Correction : Temperature x Soil thermal resistivity x Neutral loaded x touching conductors x User / Protection )
reference
downstream 3.14
Thermal stress check: Energy received by the phase conductor : 950000 As Permitted thermal stress : 2044900 As
Calculation results:
(kA) R (m) X (m) Z (m) Isc upstr. 9.8966 19.3054 14.9884 24.4408 Ik3max 5.8937 37.8154 15.9484 41.0409 Ik2max 5.0063 75.3552 36.3952 83.6840 Ik1max 2.9058 74.9168 36.2860 83.2418 Ik2min 3.6880 96.1189 36.3952 102.7787 Ik1min 2.1383 95.6967 36.2860 102.3452 I fault 1.4759 135.5839 60.0215 148.2753
Calculation results in accordance with guide UTE C15-500 (CENELEC report R064-003). UTE approval 15L-602. All assumptions and device choices are the user's responsibility. Load
I: P: 21.60 A 12.08 kW Polarity of circuit: Earthing arrangement: 3P+N TN-S
My Ecodial L V3.4
6/19/2012
Page 117
Power factor
0.85
1.0
My Ecodial L V3.4
6/19/2012
Page 118
Circuit :
Upstream : Downstream : Voltage :
Circuit breaker:
Q84
Frame rating (In): Trip unit: 100 A TM-D
Name: NSX100N-50.0 kA Trip unit rating: 40.00 A Number of poles: 3P3d Discrimination limit: T BC reinforced by cascading: No Earth leakage protection: No Earth leakage protection device : Sensitivity : Delay : Earth leakage discrimination : Settings:
Overload: Magnetic:
Cable :
Length: Installation method: Cable type: Insulation: Arrangement of conductors: Ambient temperature:
C84
10.0 m E-circuits spaced out Multi-core cables on perforated horizontal tray Multi-core Number of layers: XLPE Nb additional touching circuits: Trefoil 40 C THDI level: 74.7 A 68.0 A : 0.91 : 1.00 : 1.00 : 1.00 : 1.00 : 1.00 ______ 0.91 metal Copper Copper Copper (52-D1) (A.52-16) (D.52-1) (52-E4) (433.1)
1 0 15 %
Permitted current by the cable (Iz): Iz under normal conditions of use (A): Iz x correction factors (real conditions of use): Sizing constraint: user-defined Correction : Temperature x Soil thermal resistivity x Neutral loaded x touching conductors x User / Protection )
reference
downstream 3.64
Thermal stress check: Energy received by the phase conductor : 950000 As Permitted thermal stress : 2044900 As
Calculation results:
(kA) R (m) X (m) Z (m) Isc upstr. 7.3174 27.2354 18.7324 33.0556 Ik3max 4.8567 45.7454 19.6924 49.8039 Ik2max 4.0936 91.0852 46.6652 102.3433 Ik1max 2.3504 91.0368 47.9860 102.9095 Ik2min 3.0168 116.6589 46.6652 125.6461 Ik1min 1.7353 116.6267 47.9860 126.1128 I fault 1.2160 164.4439 73.1255 179.9698
Calculation results in accordance with guide UTE C15-500 (CENELEC report R064-003). UTE approval 15L-602. All assumptions and device choices are the user's responsibility. Load
I: P: 28.44 A 15.91 kW Polarity of circuit: Earthing arrangement: 3P+N TN-S
My Ecodial L V3.4
6/19/2012
Page 119
Power factor
0.85
1.0
My Ecodial L V3.4
6/19/2012
Page 120
Circuit :
Upstream : Downstream : Voltage :
Circuit breaker:
Q85
Frame rating (In): Trip unit: 100 A TM-D
Name: NSX100N-50.0 kA Trip unit rating: 80.00 A Number of poles: 3P3d Discrimination limit: T BC reinforced by cascading: No Earth leakage protection: No Earth leakage protection device : Sensitivity : Delay : Earth leakage discrimination : Settings:
Overload: Magnetic:
Cable :
Length: Installation method: Cable type: Insulation: Arrangement of conductors: Ambient temperature:
C85
10.0 m E-circuits spaced out Multi-core cables on perforated horizontal tray Multi-core Number of layers: XLPE Nb additional touching circuits: Trefoil 40 C THDI level: 157.9 A 143.7 A : 0.91 : 1.00 : 1.00 : 1.00 : 1.00 : 1.00 ______ 0.91 metal Copper Copper Copper (52-D1) (A.52-16) (D.52-1) (52-E4) (433.1)
1 0 15 %
Permitted current by the cable (Iz): Iz under normal conditions of use (A): Iz x correction factors (real conditions of use): Sizing constraint: user-defined Correction : Temperature x Soil thermal resistivity x Neutral loaded x touching conductors x User / Protection )
reference
downstream 3.82
Thermal stress check: Energy received by the phase conductor : 12288000 As Permitted thermal stress : 25050025 As
Calculation results:
(kA) R (m) X (m) Z (m) Isc upstr. 5.9876 33.9454 21.9004 40.3970 Ik3max 5.3268 39.2340 22.8604 45.4082 Ik2max 4.3820 77.9524 55.3552 95.6074 Ik1max 2.4854 78.2339 57.8860 97.3208 Ik2min 3.3114 100.1920 55.3552 114.4667 Ik1min 1.8871 100.4899 57.8860 115.9699 I fault 1.1925 163.0557 84.2135 183.5186
Calculation results in accordance with guide UTE C15-500 (CENELEC report R064-003). UTE approval 15L-602. All assumptions and device choices are the user's responsibility. Load
I: P: 64.30 A 35.97 kW Polarity of circuit: Earthing arrangement: 3P+N TN-S
My Ecodial L V3.4
6/19/2012
Page 121
Power factor
0.85
1.0
My Ecodial L V3.4
6/19/2012
Page 122
Circuit :
Upstream : Downstream : Voltage :
Circuit breaker:
AUTO203
Frame rating (In): Trip unit: 160 A Micrologic 2.2
Name: NSX160N-50.0 kA Trip unit rating: 125.00 A Number of poles: 3P3d Discrimination limit: T BC reinforced by cascading: No Earth leakage protection: No Earth leakage protection device : Sensitivity : Delay : Earth leakage discrimination : Settings:
Overload: Magnetic:
Load
I: P: Power factor
My Ecodial L V3.4
6/19/2012
Page 123
Circuit :
Upstream : Downstream : Voltage :
D80
155.2 A 1.25 % Plug-in tap-off units
Type: KNA160 In permissible: Length: 77.0 m U (%): Calculation mode : Non-uniform distribution Installation method: Standard Application: Sizing constraint: overloads The electrodynamic withstand was checked Correction : Voltage drop U (%) Circuit CBT-3 CBT-2 CBT-1 upstream 1.83 No. of circuits 1 1 1 user Protection circuit 1.25 d(m) 13 22 42 downst. 3.08 Ib(A) 20.10 43.11 50.10 : 1.00 : 1.00
Calculation results:
(kA) R (m) X (m) Z (m) Isc upstr. 37.3088 3.4273 7.4848 8.2322 Ik3max 4.1363 50.3973 29.6608 58.4778 Ik2max 3.1619 100.0095 86.9126 132.4979 Ik1max 1.8741 101.1003 80.2298 129.0662 Ik2min 2.4334 129.2696 86.9126 155.7704 Ik1min 1.4296 130.3766 80.2298 153.0845 I fault 0.9561 201.1267 109.2551 228.8856
Calculation results in accordance with guide UTE C15-500 (CENELEC report R064-003). UTE approval 15L-602. All assumptions and device choices are the user's responsibility.
My Ecodial L V3.4
6/19/2012
Page 124
Circuit :
Upstream : Downstream : Voltage :
Circuit breaker:
Q77
Frame rating (In): Trip unit: 100 A TM-D
Name: NSX100N-50.0 kA Trip unit rating: 40.00 A Number of poles: 3P3d Discrimination limit: T BC reinforced by cascading: No Earth leakage protection: No Earth leakage protection device : Sensitivity : Delay : Earth leakage discrimination : Settings:
Overload: Magnetic:
Cable :
Length: Installation method: Cable type: Insulation: Arrangement of conductors: Ambient temperature:
C77
10.0 m E-circuits spaced out Multi-core cables on perforated horizontal tray Multi-core Number of layers: XLPE Nb additional touching circuits: Trefoil 40 C THDI level: 74.7 A 68.0 A : 0.91 : 1.00 : 1.00 : 1.00 : 1.00 : 1.00 ______ 0.91 metal Copper Copper Copper (52-D1) (A.52-16) (D.52-1) (52-E4) (433.1)
1 0 15 %
Permitted current by the cable (Iz): Iz under normal conditions of use (A): Iz x correction factors (real conditions of use): Sizing constraint: user-defined Correction : Temperature x Soil thermal resistivity x Neutral loaded x touching conductors x User / Protection )
reference
downstream 2.55
Thermal stress check: Energy received by the phase conductor : 950000 As Permitted thermal stress : 2044900 As
Calculation results:
(kA) R (m) X (m) Z (m) Isc upstr. 15.1450 11.3573 11.2288 15.9710 Ik3max 7.4982 29.8673 12.1888 32.2587 Ik2max 6.4397 59.5895 26.1066 65.0574 Ik1max 3.7982 58.7603 24.5498 63.6825 Ik2min 4.7429 75.5352 26.1066 79.9195 Ik1min 2.7825 74.7222 24.5498 78.6518 I fault 1.8831 106.4323 46.6631 116.2122
Calculation results in accordance with guide UTE C15-500 (CENELEC report R064-003). UTE approval 15L-602. All assumptions and device choices are the user's responsibility. Load
I: P: 20.10 A 11.24 kW Polarity of circuit: Earthing arrangement: 3P+N TN-S
My Ecodial L V3.4
6/19/2012
Page 125
Power factor
0.85
1.0
My Ecodial L V3.4
6/19/2012
Page 126
Circuit :
Upstream : Downstream : Voltage :
Circuit breaker:
Q78
Frame rating (In): Trip unit: 100 A TM-D
Name: NSX100N-50.0 kA Trip unit rating: 63.00 A Number of poles: 3P3d Discrimination limit: T BC reinforced by cascading: No Earth leakage protection: No Earth leakage protection device : Sensitivity : Delay : Earth leakage discrimination : Settings:
Overload: Magnetic:
Cable :
Length: Installation method: Cable type: Insulation: Arrangement of conductors: Ambient temperature:
C78
10.0 m E-circuits spaced out Multi-core cables on perforated horizontal tray Multi-core Number of layers: XLPE Nb additional touching circuits: Trefoil 40 C THDI level: 127.4 A 115.9 A : 0.91 : 1.00 : 1.00 : 1.00 : 1.00 : 1.00 ______ 0.91 metal Copper Copper Copper (52-D1) (A.52-16) (D.52-1) (52-E4) (433.1)
1 0 15 %
Permitted current by the cable (Iz): Iz under normal conditions of use (A): Iz x correction factors (real conditions of use): Sizing constraint: user-defined Correction : Temperature x Soil thermal resistivity x Neutral loaded x touching conductors x User / Protection )
reference
downstream 2.84
Thermal stress check: Energy received by the phase conductor : 1587600 As Permitted thermal stress : 12780625 As
Calculation results:
(kA) R (m) X (m) Z (m) Isc upstr. 11.1000 16.8473 13.8208 21.7910 Ik3max 8.5167 24.2513 14.7808 28.4007 Ik2max 7.1502 48.2675 33.2166 58.5926 Ik1max 4.1840 47.7083 32.6498 57.8108 Ik2min 5.4350 61.3239 33.2166 69.7421 Ik1min 3.1719 60.7808 32.6498 68.9950 I fault 1.8643 103.3119 55.7351 117.3872
Calculation results in accordance with guide UTE C15-500 (CENELEC report R064-003). UTE approval 15L-602. All assumptions and device choices are the user's responsibility. Load
I: P: 43.11 A 24.12 kW Polarity of circuit: Earthing arrangement: 3P+N TN-S
My Ecodial L V3.4
6/19/2012
Page 127
Power factor
0.85
1.0
My Ecodial L V3.4
6/19/2012
Page 128
Circuit :
Upstream : Downstream : Voltage :
Circuit breaker:
Q79
Frame rating (In): Trip unit: 80 A C
Name: NG125L-50.0 kA Trip unit rating: 63.00 A Number of poles: 3P3d Discrimination limit: T BC reinforced by cascading: No Earth leakage protection: No Earth leakage protection device : Sensitivity : Delay : Earth leakage discrimination : Settings:
Overload: Magnetic:
Ir = 63.0 A Im(Isd) = -
Cable :
Length: Installation method: Cable type: Insulation: Arrangement of conductors: Ambient temperature:
C79
10.0 m E-circuits spaced out Multi-core cables on perforated horizontal tray Multi-core Number of layers: XLPE Nb additional touching circuits: Trefoil 40 C THDI level: 157.9 A 143.7 A : 0.91 : 1.00 : 1.00 : 1.00 : 1.00 : 1.00 ______ 0.91 metal Copper Copper Copper (52-D1) (A.52-16) (D.52-1) (52-E4) (433.1)
1 0 15 %
Permitted current by the cable (Iz): Iz under normal conditions of use (A): Iz x correction factors (real conditions of use): Sizing constraint: user-defined Correction : Temperature x Soil thermal resistivity x Neutral loaded x touching conductors x User / Protection )
reference
downstream 3.22
Thermal stress check: Energy received by the phase conductor : 1587600 As Permitted thermal stress : 25050025 As
Calculation results:
(kA) R (m) X (m) Z (m) Isc upstr. 6.9048 29.0473 19.5808 35.0308 Ik3max 6.0454 34.3359 20.5408 40.0110 Ik2max 4.9865 68.2366 49.0166 84.0170 Ik1max 2.8452 68.2774 50.6498 85.0130 Ik2min 3.7791 87.5084 49.0166 100.3013 Ik1min 2.1634 87.5653 50.6498 101.1587 I fault 1.3371 145.0041 75.8951 163.6651
Calculation results in accordance with guide UTE C15-500 (CENELEC report R064-003). UTE approval 15L-602. All assumptions and device choices are the user's responsibility. Load
I: P: 50.10 A 28.03 kW Polarity of circuit: Earthing arrangement: 3P+N TN-S
My Ecodial L V3.4
6/19/2012
Page 129
Power factor
0.85
1.0
My Ecodial L V3.4
6/19/2012
Page 130
Circuit :
Upstream : Downstream : Voltage :
Circuit breaker:
Q75
Frame rating (In): Trip unit: 100 A TM-D
Name: NSX100N-50.0 kA Trip unit rating: 63.00 A Number of poles: 3P3d Discrimination limit: T BC reinforced by cascading: No Earth leakage protection: No Earth leakage protection device : Sensitivity : Delay : Earth leakage discrimination : Settings:
Overload: Magnetic:
Cable :
Length: Installation method: Cable type: Insulation: Arrangement of conductors: Ambient temperature:
C75
11.0 m E-circuits spaced out Multi-core cables on perforated horizontal tray Multi-core Number of layers: XLPE Nb additional touching circuits: Trefoil 40 C THDI level: 100.1 A 91.1 A : 0.91 : 1.00 : 1.00 : 1.00 : 1.00 : 1.00 ______ 0.91 metal Copper Copper Copper (52-D1) (A.52-16) (D.52-1) (52-E4) (433.1)
1 0 15 %
Permitted current by the cable (Iz): Iz under normal conditions of use (A): Iz x correction factors (real conditions of use): Sizing constraint: user-defined Correction : Temperature x Soil thermal resistivity x Neutral loaded x touching conductors x User / Protection )
reference
downstream 2.17
Thermal stress check: Energy received by the phase conductor : 1587600 As Permitted thermal stress : 5234944 As
Calculation results:
(kA) R (m) X (m) Z (m) Isc upstr. 29.4601 3.4093 7.4692 8.2105 Ik3max 13.2547 16.1349 8.5252 18.2487 Ik2max 11.6344 32.2550 16.0100 36.0098 Ik1max 7.1881 31.0350 13.0057 33.6500 Ik2min 8.7706 40.1436 16.0100 43.2184 Ik1min 5.3306 38.9397 13.0057 41.0542 I fault 3.0873 62.4728 33.4967 70.8864
Calculation results in accordance with guide UTE C15-500 (CENELEC report R064-003). UTE approval 15L-602. All assumptions and device choices are the user's responsibility. Load
I: P: 54.00 A 30.21 kW Polarity of circuit: Earthing arrangement: 3P+N TN-S
My Ecodial L V3.4
6/19/2012
Page 131
Power factor
0.85
1.0
My Ecodial L V3.4
6/19/2012
Page 132
Circuit :
Upstream : Downstream : Voltage :
Circuit breaker:
AUTO184
Frame rating (In): Trip unit: 160 A Micrologic 2.2
Name: NSX160N-50.0 kA Trip unit rating: 125.00 A Number of poles: 3P3d Discrimination limit: T BC reinforced by cascading: No Earth leakage protection: No Earth leakage protection device : Sensitivity : Delay : Earth leakage discrimination : Settings:
Overload: Magnetic:
Load
I: P: Power factor
My Ecodial L V3.4
6/19/2012
Page 133
Circuit :
Upstream : Downstream : Voltage :
D74
155.2 A 1.80 % Plug-in tap-off units
Type: KNA160 In permissible: Length: 128.0 m U (%): Calculation mode : Non-uniform distribution Installation method: Standard Application: Sizing constraint: overloads The electrodynamic withstand was checked Correction : Voltage drop U (%) Circuit CBS-4 CBS-5 CBS-6 CBS-7 upstream 1.74 No. of circuits 1 1 1 1 user Protection circuit 1.80 d(m) 13 26 39 50 downst. 3.54 Ib(A) 18.85 21.60 28.44 64.30 : 1.00 : 1.00
Calculation results:
(kA) R (m) X (m) Z (m) Isc upstr. 37.3088 3.2647 7.3444 8.0373 Ik3max 2.6126 81.3447 44.2084 92.5816 Ik2max 1.9905 161.3976 135.0932 210.4741 Ik1max 1.1702 164.0118 125.8048 206.7044 Ik2min 1.5208 209.4570 135.0932 249.2437 Ik1min 0.8875 212.0858 125.8048 246.5912 I fault 0.6259 311.7225 158.3735 349.6471
Calculation results in accordance with guide UTE C15-500 (CENELEC report R064-003). UTE approval 15L-602. All assumptions and device choices are the user's responsibility.
My Ecodial L V3.4
6/19/2012
Page 134
Circuit :
Upstream : Downstream : Voltage :
Circuit breaker:
Q70
Frame rating (In): Trip unit: 100 A TM-D
Name: NSX100N-50.0 kA Trip unit rating: 40.00 A Number of poles: 3P3d Discrimination limit: T BC reinforced by cascading: No Earth leakage protection: No Earth leakage protection device : Sensitivity : Delay : Earth leakage discrimination : Settings:
Overload: Magnetic:
Cable :
Length: Installation method: Cable type: Insulation: Arrangement of conductors: Ambient temperature:
C70
10.0 m E-circuits spaced out Multi-core cables on perforated horizontal tray Multi-core Number of layers: XLPE Nb additional touching circuits: Trefoil 40 C THDI level: 74.7 A 68.0 A : 0.91 : 1.00 : 1.00 : 1.00 : 1.00 : 1.00 ______ 0.91 metal Copper Copper Copper (52-D1) (A.52-16) (D.52-1) (52-E4) (433.1)
1 0 15 %
Permitted current by the cable (Iz): Iz under normal conditions of use (A): Iz x correction factors (real conditions of use): Sizing constraint: user-defined Correction : Temperature x Soil thermal resistivity x Neutral loaded x touching conductors x User / Protection )
reference
downstream 2.51
Thermal stress check: Energy received by the phase conductor : 950000 As Permitted thermal stress : 2044900 As
Calculation results:
(kA) R (m) X (m) Z (m) Isc upstr. 15.3510 11.1947 11.0884 15.7567 Ik3max 7.5458 29.7047 12.0484 32.0552 Ik2max 6.4757 59.2676 25.9392 64.6954 Ik1max 3.8239 58.4318 24.2248 63.2544 Ik2min 4.7683 75.1426 25.9392 79.4937 Ik1min 2.7996 74.3214 24.2248 78.1698 I fault 1.9385 103.8081 44.3735 112.8943
Calculation results in accordance with guide UTE C15-500 (CENELEC report R064-003). UTE approval 15L-602. All assumptions and device choices are the user's responsibility. Load
I: P: 18.85 A 10.55 kW Polarity of circuit: Earthing arrangement: 3P+N TN-S
My Ecodial L V3.4
6/19/2012
Page 135
Power factor
0.85
1.0
My Ecodial L V3.4
6/19/2012
Page 136
Circuit :
Upstream : Downstream : Voltage :
Circuit breaker:
Q71
Frame rating (In): Trip unit: 100 A TM-D
Name: NSX100N-50.0 kA Trip unit rating: 40.00 A Number of poles: 3P3d Discrimination limit: T BC reinforced by cascading: No Earth leakage protection: No Earth leakage protection device : Sensitivity : Delay : Earth leakage discrimination : Settings:
Overload: Magnetic:
Cable :
Length: Installation method: Cable type: Insulation: Arrangement of conductors: Ambient temperature:
C71
10.0 m E-circuits spaced out Multi-core cables on perforated horizontal tray Multi-core Number of layers: XLPE Nb additional touching circuits: Trefoil 40 C THDI level: 74.7 A 68.0 A : 0.91 : 1.00 : 1.00 : 1.00 : 1.00 : 1.00 ______ 0.91 metal Copper Copper Copper (52-D1) (A.52-16) (D.52-1) (52-E4) (433.1)
1 0 15 %
Permitted current by the cable (Iz): Iz under normal conditions of use (A): Iz x correction factors (real conditions of use): Sizing constraint: user-defined Correction : Temperature x Soil thermal resistivity x Neutral loaded x touching conductors x User / Protection )
reference
downstream 3.05
Thermal stress check: Energy received by the phase conductor : 950000 As Permitted thermal stress : 2044900 As
Calculation results:
(kA) R (m) X (m) Z (m) Isc upstr. 9.9941 19.1247 14.8324 24.2024 Ik3max 5.9264 37.6347 15.7924 40.8139 Ik2max 5.0306 74.9976 36.2092 83.2811 Ik1max 2.9228 74.5518 35.9248 82.7560 Ik2min 3.7051 95.6826 36.2092 102.3048 Ik1min 2.1497 95.2514 35.9248 101.8009 I fault 1.5136 132.6681 57.4775 144.5838
Calculation results in accordance with guide UTE C15-500 (CENELEC report R064-003). UTE approval 15L-602. All assumptions and device choices are the user's responsibility. Load
I: P: 21.60 A 12.08 kW Polarity of circuit: Earthing arrangement: 3P+N TN-S
My Ecodial L V3.4
6/19/2012
Page 137
Power factor
0.85
1.0
My Ecodial L V3.4
6/19/2012
Page 138
Circuit :
Upstream : Downstream : Voltage :
Circuit breaker:
Q72
Frame rating (In): Trip unit: 100 A TM-D
Name: NSX100N-50.0 kA Trip unit rating: 40.00 A Number of poles: 3P3d Discrimination limit: T BC reinforced by cascading: No Earth leakage protection: No Earth leakage protection device : Sensitivity : Delay : Earth leakage discrimination : Settings:
Overload: Magnetic:
Cable :
Length: Installation method: Cable type: Insulation: Arrangement of conductors: Ambient temperature:
C72
10.0 m E-circuits spaced out Multi-core cables on perforated horizontal tray Multi-core Number of layers: XLPE Nb additional touching circuits: Trefoil 40 C THDI level: 74.7 A 68.0 A : 0.91 : 1.00 : 1.00 : 1.00 : 1.00 : 1.00 ______ 0.91 metal Copper Copper Copper (52-D1) (A.52-16) (D.52-1) (52-E4) (433.1)
1 0 15 %
Permitted current by the cable (Iz): Iz under normal conditions of use (A): Iz x correction factors (real conditions of use): Sizing constraint: user-defined Correction : Temperature x Soil thermal resistivity x Neutral loaded x touching conductors x User / Protection )
reference
downstream 3.55
Thermal stress check: Energy received by the phase conductor : 950000 As Permitted thermal stress : 2044900 As
Calculation results:
(kA) R (m) X (m) Z (m) Isc upstr. 7.3703 27.0547 18.5764 32.8183 Ik3max 4.8790 45.5647 19.5364 49.5763 Ik2max 4.1098 90.7276 46.4792 101.9402 Ik1max 2.3617 90.6718 47.6248 102.4182 Ik2min 3.0282 116.2226 46.4792 125.1719 Ik1min 1.7429 116.1814 47.6248 125.5637 I fault 1.2415 161.5281 70.5815 176.2756
Calculation results in accordance with guide UTE C15-500 (CENELEC report R064-003). UTE approval 15L-602. All assumptions and device choices are the user's responsibility. Load
I: P: 28.44 A 15.91 kW Polarity of circuit: Earthing arrangement: 3P+N TN-S
My Ecodial L V3.4
6/19/2012
Page 139
Power factor
0.85
1.0
My Ecodial L V3.4
6/19/2012
Page 140
Circuit :
Upstream : Downstream : Voltage :
Circuit breaker:
Q73
Frame rating (In): Trip unit: 100 A TM-D
Name: NSX100N-50.0 kA Trip unit rating: 80.00 A Number of poles: 3P3d Discrimination limit: T BC reinforced by cascading: No Earth leakage protection: No Earth leakage protection device : Sensitivity : Delay : Earth leakage discrimination : Settings:
Overload: Magnetic:
Cable :
Length: Installation method: Cable type: Insulation: Arrangement of conductors: Ambient temperature:
C73
10.0 m E-circuits spaced out Multi-core cables on perforated horizontal tray Multi-core Number of layers: XLPE Nb additional touching circuits: Trefoil 40 C THDI level: 157.9 A 143.7 A : 0.91 : 1.00 : 1.00 : 1.00 : 1.00 : 1.00 ______ 0.91 metal Copper Copper Copper (52-D1) (A.52-16) (D.52-1) (52-E4) (433.1)
1 0 15 %
Permitted current by the cable (Iz): Iz under normal conditions of use (A): Iz x correction factors (real conditions of use): Sizing constraint: user-defined Correction : Temperature x Soil thermal resistivity x Neutral loaded x touching conductors x User / Protection )
reference
downstream 3.73
Thermal stress check: Energy received by the phase conductor : 12288000 As Permitted thermal stress : 25050025 As
Calculation results:
(kA) R (m) X (m) Z (m) Isc upstr. 6.0228 33.7647 21.7444 40.1606 Ik3max 5.3545 39.0533 22.7044 45.1736 Ik2max 4.4004 77.5948 55.1692 95.2082 Ik1max 2.4984 77.8689 57.5248 96.8125 Ik2min 3.3251 99.7557 55.1692 113.9949 Ik1min 1.8963 100.0446 57.5248 115.4037 I fault 1.2174 160.1399 81.6695 179.7629
Calculation results in accordance with guide UTE C15-500 (CENELEC report R064-003). UTE approval 15L-602. All assumptions and device choices are the user's responsibility. Load
I: P: 64.30 A 35.97 kW Polarity of circuit: Earthing arrangement: 3P+N TN-S
My Ecodial L V3.4
6/19/2012
Page 141
Power factor
0.85
1.0
My Ecodial L V3.4
6/19/2012
Page 142
Circuit :
Upstream : Downstream : Voltage :
Circuit breaker:
AUTO171
Frame rating (In): Trip unit: 160 A Micrologic 2.2
Name: NSX160N-50.0 kA Trip unit rating: 125.00 A Number of poles: 3P3d Discrimination limit: T BC reinforced by cascading: No Earth leakage protection: No Earth leakage protection device : Sensitivity : Delay : Earth leakage discrimination : Settings:
Overload: Magnetic:
Load
I: P: Power factor
My Ecodial L V3.4
6/19/2012
Page 143
Circuit :
Upstream : Downstream : Voltage :
D68
155.2 A 1.25 % Plug-in tap-off units
Type: KNA160 In permissible: Length: 77.0 m U (%): Calculation mode : Non-uniform distribution Installation method: Standard Application: Sizing constraint: overloads The electrodynamic withstand was checked Correction : Voltage drop U (%) Circuit CBS-3 CBS-2 CBS-1 upstream 1.73 No. of circuits 1 1 1 user Protection circuit 1.25 d(m) 13 22 42 downst. 2.98 Ib(A) 20.10 43.11 50.10 : 1.00 : 1.00
Calculation results:
(kA) R (m) X (m) Z (m) Isc upstr. 37.3088 3.2467 7.3288 8.0158 Ik3max 4.1530 50.2167 29.5048 58.2430 Ik2max 3.1713 99.6519 86.7266 132.1060 Ik1max 1.8815 100.7353 79.8686 128.5558 Ik2min 2.4407 128.8334 86.7266 155.3047 Ik1min 1.4349 129.9313 79.8686 152.5160 I fault 0.9722 198.2109 106.7111 225.1107
Calculation results in accordance with guide UTE C15-500 (CENELEC report R064-003). UTE approval 15L-602. All assumptions and device choices are the user's responsibility.
My Ecodial L V3.4
6/19/2012
Page 144
Circuit :
Upstream : Downstream : Voltage :
Circuit breaker:
Q65
Frame rating (In): Trip unit: 100 A TM-D
Name: NSX100N-50.0 kA Trip unit rating: 40.00 A Number of poles: 3P3d Discrimination limit: T BC reinforced by cascading: No Earth leakage protection: No Earth leakage protection device : Sensitivity : Delay : Earth leakage discrimination : Settings:
Overload: Magnetic:
Cable :
Length: Installation method: Cable type: Insulation: Arrangement of conductors: Ambient temperature:
C65
10.0 m E-circuits spaced out Multi-core cables on perforated horizontal tray Multi-core Number of layers: XLPE Nb additional touching circuits: Trefoil 40 C THDI level: 74.7 A 66.5 A : 0.91 : 1.00 : 1.00 : 0.98 : 1.00 : 1.00 ______ 0.89 metal Copper Copper Copper (52-D1) (A.52-16) (D.52-1) (52-E4) (433.1)
1 2 15 %
Permitted current by the cable (Iz): Iz under normal conditions of use (A): Iz x correction factors (real conditions of use): Sizing constraint: user-defined Correction : Temperature x Soil thermal resistivity x Neutral loaded x touching conductors x User / Protection )
reference
downstream 2.45
Thermal stress check: Energy received by the phase conductor : 950000 As Permitted thermal stress : 2044900 As
Calculation results:
(kA) R (m) X (m) Z (m) Isc upstr. 15.3742 11.1767 11.0728 15.7329 Ik3max 7.5511 29.6867 12.0328 32.0326 Ik2max 6.4798 59.2319 25.9206 64.6552 Ik1max 3.8268 58.3953 24.1886 63.2068 Ik2min 4.7711 75.0990 25.9206 79.4464 Ik1min 2.8015 74.2769 24.1886 78.1162 I fault 1.9448 103.5165 44.1191 112.5263
Calculation results in accordance with guide UTE C15-500 (CENELEC report R064-003). UTE approval 15L-602. All assumptions and device choices are the user's responsibility. Load
I: P: 20.10 A 11.24 kW Polarity of circuit: Earthing arrangement: 3P+N TN-S
My Ecodial L V3.4
6/19/2012
Page 145
Power factor
0.85
1.0
My Ecodial L V3.4
6/19/2012
Page 146
Circuit :
Upstream : Downstream : Voltage :
Circuit breaker:
Q66
Frame rating (In): Trip unit: 100 A TM-D
Name: NSX100N-50.0 kA Trip unit rating: 63.00 A Number of poles: 3P3d Discrimination limit: T BC reinforced by cascading: No Earth leakage protection: No Earth leakage protection device : Sensitivity : Delay : Earth leakage discrimination : Settings:
Overload: Magnetic:
Cable :
Length: Installation method: Cable type: Insulation: Arrangement of conductors: Ambient temperature:
C66
10.0 m E-circuits spaced out Multi-core cables on perforated horizontal tray Multi-core Number of layers: XLPE Nb additional touching circuits: Trefoil 40 C THDI level: 127.4 A 115.9 A : 0.91 : 1.00 : 1.00 : 1.00 : 1.00 : 1.00 ______ 0.91 metal Copper Copper Copper (52-D1) (A.52-16) (D.52-1) (52-E4) (433.1)
1 0 15 %
Permitted current by the cable (Iz): Iz under normal conditions of use (A): Iz x correction factors (real conditions of use): Sizing constraint: user-defined Correction : Temperature x Soil thermal resistivity x Neutral loaded x touching conductors x User / Protection )
reference
downstream 2.74
Thermal stress check: Energy received by the phase conductor : 1587600 As Permitted thermal stress : 12780625 As
Calculation results:
(kA) R (m) X (m) Z (m) Isc upstr. 11.2229 16.6667 13.6648 21.5524 Ik3max 8.5879 24.0707 14.6248 28.1653 Ik2max 7.1994 47.9099 33.0306 58.1926 Ik1max 4.2209 47.3433 32.2886 57.3057 Ik2min 5.4721 60.8876 33.0306 69.2699 Ik1min 3.1980 60.3355 32.2886 68.4319 I fault 1.9262 100.3961 53.1911 113.6163
Calculation results in accordance with guide UTE C15-500 (CENELEC report R064-003). UTE approval 15L-602. All assumptions and device choices are the user's responsibility. Load
I: P: 43.11 A 24.12 kW Polarity of circuit: Earthing arrangement: 3P+N TN-S
My Ecodial L V3.4
6/19/2012
Page 147
Power factor
0.85
1.0
My Ecodial L V3.4
6/19/2012
Page 148
Circuit :
Upstream : Downstream : Voltage :
Circuit breaker:
Q67
Frame rating (In): Trip unit: 80 A C
Name: NG125L-50.0 kA Trip unit rating: 63.00 A Number of poles: 3P3d Discrimination limit: T BC reinforced by cascading: No Earth leakage protection: No Earth leakage protection device : Sensitivity : Delay : Earth leakage discrimination : Settings:
Overload: Magnetic:
Ir = 63.0 A Im(Isd) = -
Cable :
Length: Installation method: Cable type: Insulation: Arrangement of conductors: Ambient temperature:
C67
10.0 m E-circuits spaced out Multi-core cables on perforated horizontal tray Multi-core Number of layers: XLPE Nb additional touching circuits: Trefoil 40 C THDI level: 157.9 A 143.7 A : 0.91 : 1.00 : 1.00 : 1.00 : 1.00 : 1.00 ______ 0.91 metal Copper Copper Copper (52-D1) (A.52-16) (D.52-1) (52-E4) (433.1)
1 0 15 %
Permitted current by the cable (Iz): Iz under normal conditions of use (A): Iz x correction factors (real conditions of use): Sizing constraint: user-defined Correction : Temperature x Soil thermal resistivity x Neutral loaded x touching conductors x User / Protection )
reference
downstream 3.12
Thermal stress check: Energy received by the phase conductor : 1587600 As Permitted thermal stress : 25050025 As
Calculation results:
(kA) R (m) X (m) Z (m) Isc upstr. 6.9518 28.8667 19.4248 34.7938 Ik3max 6.0811 34.1552 20.3848 39.7758 Ik2max 5.0103 67.8790 48.8306 83.6181 Ik1max 2.8623 67.9124 50.2886 84.5047 Ik2min 3.7970 87.0721 48.8306 99.8297 Ik1min 2.1756 87.1200 50.2886 100.5924 I fault 1.3686 142.0883 73.3511 159.9046
Calculation results in accordance with guide UTE C15-500 (CENELEC report R064-003). UTE approval 15L-602. All assumptions and device choices are the user's responsibility. Load
I: P: 50.10 A 28.03 kW Polarity of circuit: Earthing arrangement: 3P+N TN-S
My Ecodial L V3.4
6/19/2012
Page 149
Power factor
0.85
1.0
My Ecodial L V3.4
6/19/2012
Page 150
Circuit :
Upstream : Downstream : Voltage :
Circuit breaker:
Q63
Frame rating (In): Trip unit: 100 A TM-D
Name: NSX100N-50.0 kA Trip unit rating: 63.00 A Number of poles: 3P3d Discrimination limit: T BC reinforced by cascading: No Earth leakage protection: No Earth leakage protection device : Sensitivity : Delay : Earth leakage discrimination : Settings:
Overload: Magnetic:
Cable :
Length: Installation method: Cable type: Insulation: Arrangement of conductors: Ambient temperature:
C63
11.0 m E-circuits spaced out Multi-core cables on perforated horizontal tray Multi-core Number of layers: XLPE Nb additional touching circuits: Trefoil 40 C THDI level: 100.1 A 91.1 A : 0.91 : 1.00 : 1.00 : 1.00 : 1.00 : 1.00 ______ 0.91 metal Copper Copper Copper (52-D1) (A.52-16) (D.52-1) (52-E4) (433.1)
1 0 15 %
Permitted current by the cable (Iz): Iz under normal conditions of use (A): Iz x correction factors (real conditions of use): Sizing constraint: user-defined Correction : Temperature x Soil thermal resistivity x Neutral loaded x touching conductors x User / Protection )
reference
downstream 2.07
Thermal stress check: Energy received by the phase conductor : 1587600 As Permitted thermal stress : 5234944 As
Calculation results:
(kA) R (m) X (m) Z (m) Isc upstr. 30.2572 3.2286 7.3132 7.9942 Ik3max 13.4258 15.9542 8.3692 18.0161 Ik2max 11.7660 31.8974 15.8240 35.6068 Ik1max 7.2912 30.6700 12.6445 33.1743 Ik2min 8.8679 39.7073 15.8240 42.7442 Ik1min 5.4012 38.4944 12.6445 40.5179 I fault 3.2605 59.5570 30.9527 67.1201
Calculation results in accordance with guide UTE C15-500 (CENELEC report R064-003). UTE approval 15L-602. All assumptions and device choices are the user's responsibility. Load
I: P: 54.00 A 30.21 kW Polarity of circuit: Earthing arrangement: 3P+N TN-S
My Ecodial L V3.4
6/19/2012
Page 151
Power factor
0.85
1.0
My Ecodial L V3.4
6/19/2012
Page 152
Circuit :
Upstream : Downstream : Voltage :
Circuit breaker:
AUTO152
Frame rating (In): Trip unit: 160 A Micrologic 2.2
Name: NSX160N-50.0 kA Trip unit rating: 160.00 A Number of poles: 3P3d Discrimination limit: T BC reinforced by cascading: No Earth leakage protection: No Earth leakage protection device : Sensitivity : Delay : Earth leakage discrimination : Settings:
Overload: Magnetic:
Load
I: P: Power factor
My Ecodial L V3.4
6/19/2012
Page 153
Circuit :
Upstream : Downstream : Voltage :
D61
155.2 A 1.85 % Plug-in tap-off units
Type: KNA160 In permissible: Length: 128.0 m U (%): Calculation mode : Non-uniform distribution Installation method: Standard Application: Sizing constraint: overloads The electrodynamic withstand was checked Correction : Voltage drop U (%) Circuit CBF-4 CBF-5 CBF-6 CBF-7 upstream 1.62 No. of circuits 1 1 1 1 user Protection circuit 1.85 d(m) 13 26 39 50 downst. 3.47 Ib(A) 18.85 21.60 28.44 64.30 : 1.00 : 1.00
Calculation results:
(kA) R (m) X (m) Z (m) Isc upstr. 37.3088 3.0840 7.1884 7.8220 Ik3max 2.6192 81.1640 44.0524 92.3483 Ik2max 1.9942 161.0400 134.9072 210.0805 Ik1max 1.1731 163.6468 125.4436 206.1950 Ik2min 1.5237 209.0207 134.9072 248.7762 Ik1min 0.8895 211.6405 125.4436 246.0240 I fault 0.6327 308.8067 155.8295 345.8965
Calculation results in accordance with guide UTE C15-500 (CENELEC report R064-003). UTE approval 15L-602. All assumptions and device choices are the user's responsibility.
My Ecodial L V3.4
6/19/2012
Page 154
Circuit :
Upstream : Downstream : Voltage :
Circuit breaker:
Q58
Frame rating (In): Trip unit: 100 A TM-D
Name: NSX100N-50.0 kA Trip unit rating: 40.00 A Number of poles: 3P3d Discrimination limit: T BC reinforced by cascading: No Earth leakage protection: No Earth leakage protection device : Sensitivity : Delay : Earth leakage discrimination : Settings:
Overload: Magnetic:
Cable :
Length: Installation method: Cable type: Insulation: Arrangement of conductors: Ambient temperature:
C58
10.0 m E-circuits spaced out Multi-core cables on perforated horizontal tray Multi-core Number of layers: XLPE Nb additional touching circuits: Trefoil 40 C THDI level: 74.7 A 68.0 A : 0.91 : 1.00 : 1.00 : 1.00 : 1.00 : 1.00 ______ 0.91 metal Copper Copper Copper (52-D1) (A.52-16) (D.52-1) (52-E4) (433.1)
1 0 15 %
Permitted current by the cable (Iz): Iz under normal conditions of use (A): Iz x correction factors (real conditions of use): Sizing constraint: user-defined Correction : Temperature x Soil thermal resistivity x Neutral loaded x touching conductors x User / Protection )
reference
downstream 2.41
Thermal stress check: Energy received by the phase conductor : 950000 As Permitted thermal stress : 2044900 As
Calculation results:
(kA) R (m) X (m) Z (m) Isc upstr. 15.5865 11.0140 10.9324 15.5186 Ik3max 7.5993 29.5240 11.8924 31.8292 Ik2max 6.5162 58.9100 25.7532 64.2932 Ik1max 3.8529 58.0668 23.8636 62.7792 Ik2min 4.7968 74.7063 25.7532 79.0206 Ik1min 2.8189 73.8761 23.8636 77.6347 I fault 2.0037 100.8923 41.8295 109.2198
Calculation results in accordance with guide UTE C15-500 (CENELEC report R064-003). UTE approval 15L-602. All assumptions and device choices are the user's responsibility. Load
I: P: 18.85 A 10.55 kW Polarity of circuit: Earthing arrangement: 3P+N TN-S
My Ecodial L V3.4
6/19/2012
Page 155
Power factor
0.85
1.0
My Ecodial L V3.4
6/19/2012
Page 156
Circuit :
Upstream : Downstream : Voltage :
Circuit breaker:
Q59
Frame rating (In): Trip unit: 100 A TM-D
Name: NSX100N-50.0 kA Trip unit rating: 40.00 A Number of poles: 3P3d Discrimination limit: T BC reinforced by cascading: No Earth leakage protection: No Earth leakage protection device : Sensitivity : Delay : Earth leakage discrimination : Settings:
Overload: Magnetic:
Cable :
Length: Installation method: Cable type: Insulation: Arrangement of conductors: Ambient temperature:
C59
10.0 m E-circuits spaced out Multi-core cables on perforated horizontal tray Multi-core Number of layers: XLPE Nb additional touching circuits: Trefoil 40 C THDI level: 74.7 A 68.0 A : 0.91 : 1.00 : 1.00 : 1.00 : 1.00 : 1.00 ______ 0.91 metal Copper Copper Copper (52-D1) (A.52-16) (D.52-1) (52-E4) (433.1)
1 0 15 %
Permitted current by the cable (Iz): Iz under normal conditions of use (A): Iz x correction factors (real conditions of use): Sizing constraint: user-defined Correction : Temperature x Soil thermal resistivity x Neutral loaded x touching conductors x User / Protection )
reference
downstream 2.95
Thermal stress check: Energy received by the phase conductor : 950000 As Permitted thermal stress : 2044900 As
Calculation results:
(kA) R (m) X (m) Z (m) Isc upstr. 10.0935 18.9440 14.6764 23.9640 Ik3max 5.9596 37.4540 15.6364 40.5869 Ik2max 5.0550 74.6400 36.0232 82.8782 Ik1max 2.9401 74.1868 35.5636 82.2706 Ik2min 3.7223 95.2463 36.0232 101.8309 Ik1min 2.1613 94.8061 35.5636 101.2569 I fault 1.5532 129.7523 54.9335 140.9019
Calculation results in accordance with guide UTE C15-500 (CENELEC report R064-003). UTE approval 15L-602. All assumptions and device choices are the user's responsibility. Load
I: P: 21.60 A 12.08 kW Polarity of circuit: Earthing arrangement: 3P+N TN-S
My Ecodial L V3.4
6/19/2012
Page 157
Power factor
0.85
1.0
My Ecodial L V3.4
6/19/2012
Page 158
Circuit :
Upstream : Downstream : Voltage :
Circuit breaker:
Q60
Frame rating (In): Trip unit: 100 A TM-D
Name: NSX100N-50.0 kA Trip unit rating: 40.00 A Number of poles: 3P3d Discrimination limit: T BC reinforced by cascading: No Earth leakage protection: No Earth leakage protection device : Sensitivity : Delay : Earth leakage discrimination : Settings:
Overload: Magnetic:
Cable :
Length: Installation method: Cable type: Insulation: Arrangement of conductors: Ambient temperature:
C60
10.0 m E-circuits spaced out Multi-core cables on perforated horizontal tray Multi-core Number of layers: XLPE Nb additional touching circuits: Trefoil 40 C THDI level: 74.7 A 68.0 A : 0.91 : 1.00 : 1.00 : 1.00 : 1.00 : 1.00 ______ 0.91 metal Copper Copper Copper (52-D1) (A.52-16) (D.52-1) (52-E4) (433.1)
1 0 15 %
Permitted current by the cable (Iz): Iz under normal conditions of use (A): Iz x correction factors (real conditions of use): Sizing constraint: user-defined Correction : Temperature x Soil thermal resistivity x Neutral loaded x touching conductors x User / Protection )
reference
downstream 3.46
Thermal stress check: Energy received by the phase conductor : 950000 As Permitted thermal stress : 2044900 As
Calculation results:
(kA) R (m) X (m) Z (m) Isc upstr. 7.4240 26.8740 18.4204 32.5810 Ik3max 4.9014 45.3840 19.3804 49.3488 Ik2max 4.1261 90.3700 46.2932 101.5372 Ik1max 2.3731 90.3068 47.2636 101.9273 Ik2min 3.0398 115.7863 46.2932 124.6977 Ik1min 1.7506 115.7361 47.2636 125.0148 I fault 1.2680 158.6123 68.0375 172.5890
Calculation results in accordance with guide UTE C15-500 (CENELEC report R064-003). UTE approval 15L-602. All assumptions and device choices are the user's responsibility. Load
I: P: 28.44 A 15.91 kW Polarity of circuit: Earthing arrangement: 3P+N TN-S
My Ecodial L V3.4
6/19/2012
Page 159
Power factor
0.85
1.0
My Ecodial L V3.4
6/19/2012
Page 160
Circuit :
Upstream : Downstream : Voltage :
Circuit breaker:
Q62
Frame rating (In): Trip unit: 100 A TM-D
Name: NSX100N-50.0 kA Trip unit rating: 80.00 A Number of poles: 3P3d Discrimination limit: T BC reinforced by cascading: No Earth leakage protection: No Earth leakage protection device : Sensitivity : Delay : Earth leakage discrimination : Settings:
Overload: Magnetic:
Cable :
Length: Installation method: Cable type: Insulation: Arrangement of conductors: Ambient temperature:
C62
10.0 m E-circuits spaced out Multi-core cables on perforated horizontal tray Multi-core Number of layers: XLPE Nb additional touching circuits: Trefoil 40 C THDI level: 157.9 A 143.7 A : 0.91 : 1.00 : 1.00 : 1.00 : 1.00 : 1.00 ______ 0.91 metal Copper Copper Copper (52-D1) (A.52-16) (D.52-1) (52-E4) (433.1)
1 0 15 %
Permitted current by the cable (Iz): Iz under normal conditions of use (A): Iz x correction factors (real conditions of use): Sizing constraint: user-defined Correction : Temperature x Soil thermal resistivity x Neutral loaded x touching conductors x User / Protection )
reference
downstream 3.65
Thermal stress check: Energy received by the phase conductor : 12288000 As Permitted thermal stress : 25050025 As
Calculation results:
(kA) R (m) X (m) Z (m) Isc upstr. 6.0585 33.5840 21.5884 39.9242 Ik3max 5.3824 38.8726 22.5484 44.9390 Ik2max 4.4189 77.2372 54.9832 94.8090 Ik1max 2.5116 77.5039 57.1636 96.3044 Ik2min 3.3390 99.3195 54.9832 113.5232 Ik1min 1.9057 99.5993 57.1636 114.8377 I fault 1.2433 157.2241 79.1255 176.0121
Calculation results in accordance with guide UTE C15-500 (CENELEC report R064-003). UTE approval 15L-602. All assumptions and device choices are the user's responsibility. Load
I: P: 64.30 A 35.97 kW Polarity of circuit: Earthing arrangement: 3P+N TN-S
My Ecodial L V3.4
6/19/2012
Page 161
Power factor
0.85
1.0
My Ecodial L V3.4
6/19/2012
Page 162
Circuit :
Upstream : Downstream : Voltage :
Circuit breaker:
Q52
Frame rating (In): Trip unit: 160 A Micrologic 2.2
Name: NSX160N-50.0 kA Trip unit rating: 125.00 A Number of poles: 3P3d Discrimination limit: T BC reinforced by cascading: No Earth leakage protection: No Earth leakage protection device : Sensitivity : Delay : Earth leakage discrimination : Settings:
Overload: Magnetic:
Load
I: P: Power factor
My Ecodial L V3.4
6/19/2012
Page 163
Circuit :
Upstream : Downstream : Voltage :
D53
155.2 A 1.25 % Plug-in tap-off units
Type: KNA160 In permissible: Length: 77.0 m U (%): Calculation mode : Non-uniform distribution Installation method: Standard Application: Sizing constraint: overloads The electrodynamic withstand was checked Correction : Voltage drop U (%) Circuit CBF-3 CBF-2 CBF-1 upstream 1.61 No. of circuits 1 1 1 user Protection circuit 1.25 d(m) 13 22 42 downst. 2.86 Ib(A) 20.10 43.11 50.10 : 1.00 : 1.00
Calculation results:
(kA) R (m) X (m) Z (m) Isc upstr. 37.3088 3.0660 7.1728 7.8006 Ik3max 4.1698 50.0360 29.3488 58.0082 Ik2max 3.1808 99.2943 86.5406 131.7142 Ik1max 1.8890 100.3703 79.5074 128.0454 Ik2min 2.4480 128.3971 86.5406 154.8389 Ik1min 1.4403 129.4860 79.5074 151.9475 I fault 0.9887 195.2951 104.1671 221.3390
Calculation results in accordance with guide UTE C15-500 (CENELEC report R064-003). UTE approval 15L-602. All assumptions and device choices are the user's responsibility.
My Ecodial L V3.4
6/19/2012
Page 164
Circuit :
Upstream : Downstream : Voltage :
Circuit breaker:
Q54
Frame rating (In): Trip unit: 80 A C
Name: NG125L-50.0 kA Trip unit rating: 40.00 A Number of poles: 3P3d Discrimination limit: T BC reinforced by cascading: No Earth leakage protection: No Earth leakage protection device : Sensitivity : Delay : Earth leakage discrimination : Settings:
Overload: Magnetic:
Ir = 40.0 A Im(Isd) = -
Cable :
Length: Installation method: Cable type: Insulation: Arrangement of conductors: Ambient temperature:
C54
10.0 m E-circuits spaced out Multi-core cables on perforated horizontal tray Multi-core Number of layers: XLPE Nb additional touching circuits: Trefoil 40 C THDI level: 74.7 A 68.0 A : 0.91 : 1.00 : 1.00 : 1.00 : 1.00 : 1.00 ______ 0.91 metal Copper Copper Copper (52-D1) (A.52-16) (D.52-1) (52-E4) (433.1)
1 0 15 %
Permitted current by the cable (Iz): Iz under normal conditions of use (A): Iz x correction factors (real conditions of use): Sizing constraint: user-defined Correction : Temperature x Soil thermal resistivity x Neutral loaded x touching conductors x User / Protection )
reference
downstream 2.33
Thermal stress check: Energy received by the phase conductor : 640000 As Permitted thermal stress : 2044900 As
Calculation results:
(kA) R (m) X (m) Z (m) Isc upstr. 15.6105 10.9960 10.9168 15.4948 Ik3max 7.6047 29.5060 11.8768 31.8066 Ik2max 6.5203 58.8743 25.7346 64.2530 Ik1max 3.8558 58.0303 23.8274 62.7317 Ik2min 4.7997 74.6627 25.7346 78.9733 Ik1min 2.8208 73.8316 23.8274 77.5812 I fault 2.0105 100.6007 41.5751 108.8531
Calculation results in accordance with guide UTE C15-500 (CENELEC report R064-003). UTE approval 15L-602. All assumptions and device choices are the user's responsibility. Load
I: P: 20.10 A 11.24 kW Polarity of circuit: Earthing arrangement: 3P+N TN-S
My Ecodial L V3.4
6/19/2012
Page 165
Power factor
0.85
1.0
My Ecodial L V3.4
6/19/2012
Page 166
Circuit :
Upstream : Downstream : Voltage :
Circuit breaker:
Q55
Frame rating (In): Trip unit: 80 A C
Name: NG125L-50.0 kA Trip unit rating: 63.00 A Number of poles: 3P3d Discrimination limit: T BC reinforced by cascading: No Earth leakage protection: No Earth leakage protection device : Sensitivity : Delay : Earth leakage discrimination : Settings:
Overload: Magnetic:
Ir = 63.0 A Im(Isd) = -
Cable :
Length: Installation method: Cable type: Insulation: Arrangement of conductors: Ambient temperature:
C55
10.0 m E-circuits spaced out Multi-core cables on perforated horizontal tray Multi-core Number of layers: XLPE Nb additional touching circuits: Trefoil 40 C THDI level: 127.4 A 115.9 A : 0.91 : 1.00 : 1.00 : 1.00 : 1.00 : 1.00 ______ 0.91 metal Copper Copper Copper (52-D1) (A.52-16) (D.52-1) (52-E4) (433.1)
1 0 15 %
Permitted current by the cable (Iz): Iz under normal conditions of use (A): Iz x correction factors (real conditions of use): Sizing constraint: user-defined Correction : Temperature x Soil thermal resistivity x Neutral loaded x touching conductors x User / Protection )
reference
downstream 2.62
Thermal stress check: Energy received by the phase conductor : 1587600 As Permitted thermal stress : 12780625 As
Calculation results:
(kA) R (m) X (m) Z (m) Isc upstr. 11.3486 16.4860 13.5088 21.3137 Ik3max 8.6603 23.8900 14.4688 27.9299 Ik2max 7.2492 47.5523 32.8446 57.7926 Ik1max 4.2584 46.9783 31.9274 56.8007 Ik2min 5.5096 60.4513 32.8446 68.7977 Ik1min 3.2245 59.8902 31.9274 67.8690 I fault 1.9922 97.4803 50.6471 109.8523
Calculation results in accordance with guide UTE C15-500 (CENELEC report R064-003). UTE approval 15L-602. All assumptions and device choices are the user's responsibility. Load
I: P: 43.11 A 24.12 kW Polarity of circuit: Earthing arrangement: 3P+N TN-S
My Ecodial L V3.4
6/19/2012
Page 167
Power factor
0.85
1.0
My Ecodial L V3.4
6/19/2012
Page 168
Circuit :
Upstream : Downstream : Voltage :
Circuit breaker:
Q56
Frame rating (In): Trip unit: 80 A C
Name: NG125L-50.0 kA Trip unit rating: 63.00 A Number of poles: 3P3d Discrimination limit: T BC reinforced by cascading: No Earth leakage protection: No Earth leakage protection device : Sensitivity : Delay : Earth leakage discrimination : Settings:
Overload: Magnetic:
Ir = 63.0 A Im(Isd) = -
Cable :
Length: Installation method: Cable type: Insulation: Arrangement of conductors: Ambient temperature:
C56
10.0 m E-circuits spaced out Multi-core cables on perforated horizontal tray Multi-core Number of layers: XLPE Nb additional touching circuits: Trefoil 40 C THDI level: 157.9 A 143.7 A : 0.91 : 1.00 : 1.00 : 1.00 : 1.00 : 1.00 ______ 0.91 metal Copper Copper Copper (52-D1) (A.52-16) (D.52-1) (52-E4) (433.1)
1 0 15 %
Permitted current by the cable (Iz): Iz under normal conditions of use (A): Iz x correction factors (real conditions of use): Sizing constraint: user-defined Correction : Temperature x Soil thermal resistivity x Neutral loaded x touching conductors x User / Protection )
reference
downstream 3.00
Thermal stress check: Energy received by the phase conductor : 1587600 As Permitted thermal stress : 25050025 As
Calculation results:
(kA) R (m) X (m) Z (m) Isc upstr. 6.9995 28.6860 19.2688 34.5568 Ik3max 6.1172 33.9746 20.2288 39.5408 Ik2max 5.0343 67.5214 48.6446 83.2192 Ik1max 2.8797 67.5474 49.9274 83.9964 Ik2min 3.8150 86.6358 48.6446 99.3582 Ik1min 2.1879 86.6747 49.9274 100.0262 I fault 1.4015 139.1725 70.8071 156.1494
Calculation results in accordance with guide UTE C15-500 (CENELEC report R064-003). UTE approval 15L-602. All assumptions and device choices are the user's responsibility. Load
I: P: 50.10 A 28.03 kW Polarity of circuit: Earthing arrangement: 3P+N TN-S
My Ecodial L V3.4
6/19/2012
Page 169
Power factor
0.85
1.0
My Ecodial L V3.4
6/19/2012
Page 170
Circuit :
Upstream : Downstream : Voltage :
Circuit breaker:
Q51
Frame rating (In): Trip unit: 100 A TM-D
Name: NSX100N-50.0 kA Trip unit rating: 63.00 A Number of poles: 3P3d Discrimination limit: T BC reinforced by cascading: No Earth leakage protection: No Earth leakage protection device : Sensitivity : Delay : Earth leakage discrimination : Settings:
Overload: Magnetic:
Cable :
Length: Installation method: Cable type: Insulation: Arrangement of conductors: Ambient temperature:
C51
11.0 m E-circuits spaced out Multi-core cables on perforated horizontal tray Multi-core Number of layers: XLPE Nb additional touching circuits: Trefoil 40 C THDI level: 74.7 A 68.0 A : 0.91 : 1.00 : 1.00 : 1.00 : 1.00 : 1.00 ______ 0.91 metal Copper Copper Copper (52-D1) (A.52-16) (D.52-1) (52-E4) (433.1)
1 0 15 %
Permitted current by the cable (Iz): Iz under normal conditions of use (A): Iz x correction factors (real conditions of use): Sizing constraint: overloads Correction : Temperature x Soil thermal resistivity x Neutral loaded x touching conductors x User / Protection )
reference
downstream 2.15
Thermal stress check: Energy received by the phase conductor : 1587600 As Permitted thermal stress : 2044900 As
Calculation results:
(kA) R (m) X (m) Z (m) Isc upstr. 31.0935 3.0479 7.1572 7.7792 Ik3max 9.7501 23.4089 8.2132 24.8079 Ik2max 8.4888 46.8105 15.6380 49.3535 Ik1max 5.1244 45.5758 12.2833 47.2020 Ik2min 6.2281 58.8176 15.6380 60.8610 Ik1min 3.7161 57.5956 12.2833 58.8909 I fault 2.6914 76.1877 28.4087 81.3119
Calculation results in accordance with guide UTE C15-500 (CENELEC report R064-003). UTE approval 15L-602. All assumptions and device choices are the user's responsibility. Load
I: P: 54.00 A 30.21 kW Polarity of circuit: Earthing arrangement: 3P+N TN-S
My Ecodial L V3.4
6/19/2012
Page 171
Power factor
0.85
1.0
My Ecodial L V3.4
6/19/2012
Page 172
Circuit :
Upstream : Downstream : Voltage :
Circuit breaker:
Q43
Frame rating (In): Trip unit: 630 A Micrologic 2.3
Name: NSX630N-50.0 kA Trip unit rating: 630.00 A Number of poles: 3P3d Discrimination limit: T BC reinforced by cascading: No Earth leakage protection: No Earth leakage protection device : Sensitivity : Delay : Earth leakage discrimination : Settings:
Overload: Magnetic:
Cable :
Length: Installation method: Cable type: Insulation: Arrangement of conductors: Ambient temperature:
C43
11.0 m E-circuits spaced out Multi-core cables on perforated horizontal tray Multi-core Number of layers: XLPE Nb additional touching circuits: Trefoil 40 C THDI level: 912.1 A 830.0 A : 0.91 : 1.00 : 1.00 : 1.00 : 1.00 : 1.00 ______ 0.91 metal Copper Copper Copper (52-D1) (A.52-16) (D.52-1) (52-E4) (433.1)
1 0 15 %
Permitted current by the cable (Iz): Iz under normal conditions of use (A): Iz x correction factors (real conditions of use): Sizing constraint: user-defined Correction : Temperature x Soil thermal resistivity x Neutral loaded x touching conductors x User / Protection )
reference
downstream 1.67
Thermal stress check: Energy received by the phase conductor : 297675000 As Permitted thermal stress : 699867025 As
Calculation results:
(kA) R (m) X (m) Z (m) Isc upstr. 31.8816 2.8853 7.0168 7.5869 Ik3max 29.1768 3.4356 7.5448 8.2902 Ik2max 26.2388 6.8673 14.4146 15.9669 Ik1max 19.7160 5.6259 10.9022 12.2682 Ik2min 23.1880 7.7096 14.4146 16.3468 Ik1min 17.2558 6.4795 10.9022 12.6823 I fault 6.2923 23.5525 25.5911 34.7797
Calculation results in accordance with guide UTE C15-500 (CENELEC report R064-003). UTE approval 15L-602. All assumptions and device choices are the user's responsibility. Load
I: P: 544.85 A 304.80 kW Polarity of circuit: Earthing arrangement: 3P+N TN-S
My Ecodial L V3.4
6/19/2012
Page 173
Power factor
0.85
1.0
My Ecodial L V3.4
6/19/2012
Page 174
Circuit :
Upstream : Downstream : Voltage :
TO LPTG ( ) - Calculated
LPTG TAP OFF LPTG 380 V Frame rating (In): Trip unit: 630 A Micrologic 2.3
Circuit breaker:
Name: NSX630F-36.0 kA Trip unit rating: 630.00 A Number of poles: 3P3d Discrimination limit: BC reinforced by cascading: 50.0 kA Earth leakage protection: No Earth leakage protection device : Sensitivity : Delay : Earth leakage discrimination : Settings:
Overload: Magnetic:
Load
I: P: Power factor
My Ecodial L V3.4
6/19/2012
Page 175
Circuit :
Upstream : Downstream : Voltage :
Busbars:
Designation: Type : Ambient temperature: Short-circuit temperature: Ks : Voltage drop:
B44
STANDARD Standard on edge 40 C 85 C 0.95 0.0000 % Dimensions: Metal: I available: Isc max: Peak Isc (k) : 0.0 m-1// 5.0 mmx40 mm Copper 500 A 29.18 kA 61.27 kA
My Ecodial L V3.4
6/19/2012
Page 176
Circuit :
Upstream : Downstream : Voltage :
Circuit breaker:
Q45
Frame rating (In): Trip unit: 100 A TM-D
Name: NSX100N-50.0 kA Trip unit rating: 80.00 A Number of poles: 3P3d Discrimination limit: T BC reinforced by cascading: No Earth leakage protection: No Earth leakage protection device : Sensitivity : Delay : Earth leakage discrimination : Settings:
Overload: Magnetic:
Cable :
Length: Installation method: Cable type: Insulation: Arrangement of conductors: Ambient temperature:
C45
12.0 m E-circuits spaced out Multi-core cables on perforated horizontal tray Multi-core Number of layers: XLPE Nb additional touching circuits: Trefoil 40 C THDI level: 100.1 A 83.1 A : 0.91 : 1.00 : 1.00 : 0.91 : 1.00 : 1.00 ______ 0.83 metal Copper Copper Copper (52-D1) (A.52-16) (D.52-1) (52-E4) (433.1)
1 19 15 %
Permitted current by the cable (Iz): Iz under normal conditions of use (A): Iz x correction factors (real conditions of use): Sizing constraint: overloads Correction : Temperature x Soil thermal resistivity x Neutral loaded x touching conductors x User / Protection )
reference
downstream 2.13
Thermal stress check: Energy received by the phase conductor : 544471 As Permitted thermal stress : 5234944 As
Calculation results:
(kA) R (m) X (m) Z (m) Isc upstr. 29.1768 3.4356 7.5448 8.2902 Ik3max 12.4815 17.3181 8.6968 19.3791 Ik2max 10.8941 34.6323 16.7186 38.4566 Ik1max 6.7362 33.3909 13.2062 35.9076 Ik2min 8.1749 43.2488 16.7186 46.3678 Ik1min 4.9686 42.0187 13.2062 44.0451 I fault 3.3491 59.0917 27.8951 65.3450
Calculation results in accordance with guide UTE C15-500 (CENELEC report R064-003). UTE approval 15L-602. All assumptions and device choices are the user's responsibility. Load
I: P: 64.00 A 35.80 kW Polarity of circuit: Earthing arrangement: 3P+N TN-S
My Ecodial L V3.4
6/19/2012
Page 177
Power factor
0.85
1.0
My Ecodial L V3.4
6/19/2012
Page 178
Circuit :
Upstream : Downstream : Voltage :
Circuit breaker:
Q46
Frame rating (In): Trip unit: 160 A TM-D
Name: NG160N-25.0 kA Trip unit rating: 125.00 A Number of poles: 3P3d Discrimination limit: T BC reinforced by cascading: 36.0 kA Earth leakage protection: No Earth leakage protection device : Sensitivity : Delay : Earth leakage discrimination : Settings:
Overload: Magnetic:
Ir = Im(Isd) = 1250 A
Cable :
Length: Installation method: Cable type: Insulation: Arrangement of conductors: Ambient temperature:
C46
45.0 m E-circuits spaced out Multi-core cables on perforated horizontal tray Multi-core Number of layers: XLPE Nb additional touching circuits: Trefoil 40 C THDI level: 198.2 A 164.5 A : 0.91 : 1.00 : 1.00 : 0.91 : 1.00 : 1.00 ______ 0.83 metal Copper Copper Copper (52-D1) (A.52-16) (D.52-1) (52-E4) (433.1)
1 19 15 %
Permitted current by the cable (Iz): Iz under normal conditions of use (A): Iz x correction factors (real conditions of use): Sizing constraint: user-defined Correction : Temperature x Soil thermal resistivity x Neutral loaded x touching conductors x User / Protection )
reference
downstream 2.76
Thermal stress check: Energy received by the phase conductor : 15343750 As Permitted thermal stress : 51122500 As
Calculation results:
(kA) R (m) X (m) Z (m) Isc upstr. 29.1768 3.4356 7.5448 8.2902 Ik3max 10.3652 20.0946 11.8648 23.3359 Ik2max 9.0429 40.1853 23.0546 46.3290 Ik1max 5.5513 38.9439 19.5422 43.5721 Ik2min 6.8441 50.3566 23.0546 55.3832 Ik1min 4.1392 49.1265 19.5422 52.8707 I fault 2.3287 87.5230 34.2311 93.9790
Calculation results in accordance with guide UTE C15-500 (CENELEC report R064-003). UTE approval 15L-602. All assumptions and device choices are the user's responsibility. Load
I: P: 116.70 A 65.29 kW Polarity of circuit: Earthing arrangement: 3P+N TN-S
My Ecodial L V3.4
6/19/2012
Page 179
Power factor
0.85
1.0
My Ecodial L V3.4
6/19/2012
Page 180
Circuit :
Upstream : Downstream : Voltage :
Circuit breaker:
Q47
Frame rating (In): Trip unit: 160 A TM-D
Name: NG160N-25.0 kA Trip unit rating: 100.00 A Number of poles: 3P3d Discrimination limit: T BC reinforced by cascading: 36.0 kA Earth leakage protection: No Earth leakage protection device : Sensitivity : Delay : Earth leakage discrimination : Settings:
Overload: Magnetic:
Ir = Im(Isd) = 1000 A
Cable :
Length: Installation method: Cable type: Insulation: Arrangement of conductors: Ambient temperature:
C47
32.0 m E-circuits spaced out Multi-core cables on perforated horizontal tray Multi-core Number of layers: XLPE Nb additional touching circuits: Trefoil 40 C THDI level: 127.4 A 105.7 A : 0.91 : 1.00 : 1.00 : 0.91 : 1.00 : 1.00 ______ 0.83 metal Copper Copper Copper (52-D1) (A.52-16) (D.52-1) (52-E4) (433.1)
1 19 15 %
Permitted current by the cable (Iz): Iz under normal conditions of use (A): Iz x correction factors (real conditions of use): Sizing constraint: overloads Correction : Temperature x Soil thermal resistivity x Neutral loaded x touching conductors x User / Protection )
reference
downstream 2.87
Thermal stress check: Energy received by the phase conductor : 4370000 As Permitted thermal stress : 12780625 As
Calculation results:
(kA) R (m) X (m) Z (m) Isc upstr. 29.1768 3.4356 7.5448 8.2902 Ik3max 8.3030 27.1284 10.6168 29.1319 Ik2max 7.2211 54.2529 20.5586 58.0175 Ik1max 4.3438 53.0115 17.0462 55.6848 Ik2min 5.3098 68.3631 20.5586 71.3875 Ik1min 3.1596 67.1330 17.0462 69.2634 I fault 2.0622 101.2649 31.7351 106.1211
Calculation results in accordance with guide UTE C15-500 (CENELEC report R064-003). UTE approval 15L-602. All assumptions and device choices are the user's responsibility. Load
I: P: 95.72 A 53.55 kW Polarity of circuit: Earthing arrangement: 3P+N TN-S
My Ecodial L V3.4
6/19/2012
Page 181
Power factor
0.85
1.0
My Ecodial L V3.4
6/19/2012
Page 182
Circuit :
Upstream : Downstream : Voltage :
Circuit breaker:
Q48
Frame rating (In): Trip unit: 160 A TM-D
Name: NG160N-25.0 kA Trip unit rating: 80.00 A Number of poles: 3P3d Discrimination limit: T BC reinforced by cascading: 36.0 kA Earth leakage protection: No Earth leakage protection device : Sensitivity : Delay : Earth leakage discrimination : Settings:
Overload: Magnetic:
Ir = Im(Isd) = 800 A
Cable :
Length: Installation method: Cable type: Insulation: Arrangement of conductors: Ambient temperature:
C48
17.0 m E-circuits spaced out Multi-core cables on perforated horizontal tray Multi-core Number of layers: XLPE Nb additional touching circuits: Trefoil 40 C THDI level: 100.1 A 83.1 A : 0.91 : 1.00 : 1.00 : 0.91 : 1.00 : 1.00 ______ 0.83 metal Copper Copper Copper (52-D1) (A.52-16) (D.52-1) (52-E4) (433.1)
1 19 15 %
Permitted current by the cable (Iz): Iz under normal conditions of use (A): Iz x correction factors (real conditions of use): Sizing constraint: overloads Correction : Temperature x Soil thermal resistivity x Neutral loaded x touching conductors x User / Protection )
reference
downstream 2.34
Thermal stress check: Energy received by the phase conductor : 239000 As Permitted thermal stress : 5234944 As
Calculation results:
(kA) R (m) X (m) Z (m) Isc upstr. 29.1768 3.4356 7.5448 8.2902 Ik3max 9.7304 23.1025 9.1768 24.8584 Ik2max 8.4691 46.2010 17.6786 49.4678 Ik1max 5.1313 44.9596 14.1662 47.1386 Ik2min 6.2458 58.0568 17.6786 60.6888 Ik1min 3.7367 56.8267 14.1662 58.5658 I fault 2.7585 73.8997 28.8551 79.3334
Calculation results in accordance with guide UTE C15-500 (CENELEC report R064-003). UTE approval 15L-602. All assumptions and device choices are the user's responsibility. Load
I: P: 66.00 A 36.92 kW Polarity of circuit: Earthing arrangement: 3P+N TN-S
My Ecodial L V3.4
6/19/2012
Page 183
Power factor
0.85
1.0
My Ecodial L V3.4
6/19/2012
Page 184
Circuit :
Upstream : Downstream : Voltage :
Circuit breaker:
Q49
Frame rating (In): Trip unit: 160 A TM-D
Name: NG160N-25.0 kA Trip unit rating: 160.00 A Number of poles: 3P3d Discrimination limit: T BC reinforced by cascading: 36.0 kA Earth leakage protection: No Earth leakage protection device : Sensitivity : Delay : Earth leakage discrimination : Settings:
Overload: Magnetic:
Ir = Im(Isd) = 1250 A
Cable :
Length: Installation method: Cable type: Insulation: Arrangement of conductors: Ambient temperature:
C49
15.9 m E-circuits spaced out Multi-core cables on perforated horizontal tray Multi-core Number of layers: XLPE Nb additional touching circuits: Trefoil 40 C THDI level: 245.6 A 203.8 A : 0.91 : 1.00 : 1.00 : 0.91 : 1.00 : 1.00 ______ 0.83 metal Copper Copper Copper (52-D1) (A.52-16) (D.52-1) (52-E4) (433.1)
1 19 15 %
Permitted current by the cable (Iz): Iz under normal conditions of use (A): Iz x correction factors (real conditions of use): Sizing constraint: user-defined Correction : Temperature x Soil thermal resistivity x Neutral loaded x touching conductors x User / Protection )
reference
downstream 2.03
Thermal stress check: Energy received by the phase conductor : 39482726 As Permitted thermal stress : 100200100 As
Calculation results:
(kA) R (m) X (m) Z (m) Isc upstr. 29.1768 3.4356 7.5448 8.2902 Ik3max 20.3949 7.6400 9.0712 11.8599 Ik2max 18.0544 15.2761 17.4674 23.2049 Ik1max 12.2213 14.0347 13.9550 19.7918 Ik2min 14.9094 18.4729 17.4674 25.4236 Ik1min 9.8657 17.2428 13.9550 22.1823 I fault 4.4705 39.6974 28.6439 48.9526
Calculation results in accordance with guide UTE C15-500 (CENELEC report R064-003). UTE approval 15L-602. All assumptions and device choices are the user's responsibility. Load
I: P: 146.11 A 81.74 kW Polarity of circuit: Earthing arrangement: 3P+N TN-S
My Ecodial L V3.4
6/19/2012
Page 185
Power factor
0.85
1.0
My Ecodial L V3.4
6/19/2012
Page 186
Circuit :
Upstream : Downstream : Voltage :
Load
My Ecodial L V3.4
6/19/2012
Page 187
My Ecodial L V3.4