Sunteți pe pagina 1din 2

Rated primary voltage : 100V - 600V

TOTAL
IMPEDANCE
LOSSES
AT 75 C
AT 75 C

VOLTAGE
REGULATION
AT FULL LOAD
(P.F.=1)

CAPACITY

NO-LOAD
LOSSES

LOAD
LOSSES
AT 75 C

(kVA)

(Watt)

(Watt)

(Watt)

(%)

Load
(%)

Full Load
(%)

(%)

16

36

52

2.0

99.69

99.68

3.56

45

110

155

2.0

99.68

99.66

EFFICIENCY
(P.F.=1)

NOISE
LEVEL dB
(A) : 0.3 m

OUTLINE DIMENSION
(APPROX. in mm.)

TOTAL WEIGHT

(kg)

20

300

300

300

105

3.62

20

300

340

400

155

75

180

255

2.0

99.68

99.66

3.56

25

350

400

450

185

10

150

365

515

2.0

99.68

99.66

3.60

25

350

460

500

250

15

230

520

750

3.0

99.69

99.67

3.45

30

350

520

570

295

20

350

690

1040

3.0

99.70

99.70

3.44

30

380

580

620

335

30

450

1060

1510

3.0

99.68

99.67

3.52

30

400

640

700

390

40

580

1480

2060

3.0

99.67

99.65

3.68

30

400

700

750

450

50

790

1800

2590

3.0

99.69

99.67

3.58

30

400

760

800

545

60

900

2100

3000

3.0

99.68

99.67

3.48

40

450

820

900

600

80

1240

2610

3850

3.0

99.70

99.69

3.25

40

500

900

950

705

100

1500

3500

5000

3.0

99.68

99.67

3.48

40

550

1000

1050

830

120

1950

4100

6050

3.0

99.70

99.69

3.40

40

550

1000

1100

950

150

2050

5200

7250

3.0

99.67

99.65

3.45

40

600

1100

1150

935

200

2950

6300

9250

3.0

99.69

99.69

3.15

40

650

1150

1200

1235

250

3350

6850

10200

3.0

99.70

99.70

2.75

45

700

1200

1300

1250

300

3850

7850

11700

3.0

99.70

99.70

2.63

45

800

1300

1400

1440

Note :

TME-TDCDT-1909

1. The transformer is designed to operated under the following conditions


Altitude
:
Up to 1000 m above sea level
Ambient air temperature
:
40 C maximum
2. Limits of temperature rise (winding)
:
not exceeding 100 C
3. Insulation class
:
F
4. Connection symbol
:
Dyn 11
5. Reference standard
:
IEC 76 and ANSI C57.12
6. Type of cooling
:
AN (air natural self cooled)
7. Special vector group and other voltage available upon request

The contents and specifications of this datasheet are subject to change without prior notice. No part of this data may be reproduced without the prior approval of Thai Maxwell Electric.

TECHNICAL DATA OF CONVENTIONAL DRY TYPE THREE PHASE TRANSFORMER

Rated primary voltage : 100V - 600V


TOTAL
IMPEDANCE
LOSSES
AT 75 C
AT 75 C

VOLTAGE
REGULATION
AT FULL LOAD
(P.F.=1)

CAPACITY

NO-LOAD
LOSSES

LOAD
LOSSES
AT 75 C

(kVA)

(Watt)

(Watt)

(Watt)

(%)

Load
(%)

Full Load
(%)

(%)

0.1

2.0

99.70

99.70

3.94

0.5

18

25

2.0

99.67

99.64

16

35

51

2.0

99.69

31

72

103

2.0

99.68

45

100

145

2.5

60

130

190

73

170

85

210

100

EFFICIENCY
(P.F.=1)

NOISE
LEVEL dB
(A) : 0.3 m

OUTLINE DIMENSION
(APPROX. in mm.)

TOTAL WEIGHT

(kg)

20

200

280

170

105

3.56

20

200

280

170

155

99.68

3.46

25

200

280

170

185

99.67

3.56

25

300

300

300

250

99.69

99.68

3.31

30

300

300

300

295

2.5

99.69

99.68

3.23

30

300

300

300

335

243

2.5

99.68

99.67

3.37

30

300

340

400

390

295

3.0

99.68

99.65

3.48

30

300

340

400

450

230

330

3.0

99.69

99.67

3.28

30

350

400

500

545

130

280

410

3.0

99.69

99.69

3.48

40

350

400

500

600

150

310

460

3.0

99.70

99.69

3.43

40

350

450

550

705

10

165

350

515

3.0

99.69

99.69

3.48

40

350

450

550

830

15

240

510

750

3.0

99.69

99.69

3.39

40

400

450

650

950

20

330

670

1000

3.0

99.70

99.70

3.34

40

400

500

750

935

25

410

850

1260

3.0

99.70

99.69

3.39

40

400

500

750

1235

30

490

990

1480

3.0

99.70

99.70

3.29

45

450

550

800

1250

35

580

1170

1750

3.0

99.70

99.70

3.33

45

450

550

800

1440

Note :

TME-TDCDT-2009

1. The transformer is designed to operated under the following conditions


Altitude
:
Up to 1000 m above sea level
Ambient air temperature
:
40 C maximum
2. Limits of temperature rise (winding)
:
not exceeding 100 C
3. Insulation class
:
F
4. Connection symbol
:
Dyn 11
5. Reference standard
:
IEC 76 and ANSI C57.12
6. Type of cooling
:
AN (air natural self cooled)
7. Special vector group and other voltage available upon request

The contents and specifications of this datasheet are subject to change without prior notice. No part of this data may be reproduced without the prior approval of Thai Maxwell Electric.