W.O. No: T10107 Prepared By: Title: JL Calc No: Date: 2011/1/18 Sheet No: Checked By: CJP Cont'd on: Date: 2011/1/20
2 x 685 MW RAIPUR - CHHATTISGARH Coal Fired Power Plant - Primary Air Fan Foundation
NATURAL FREQUENCIES The following natural frequencies were computed by the STAAD analysis:
Modes
1 Sliding in Z-Axis 2 Sliding in X-Axis 3 Torsion about Y-Axis 4 Vertical Vibration 5 Rocking About Z-Axis 6 Rocking About X-Axis 7+ High Frequency Modes
Operating Frequency for PA Fan = 24.8 Hz 0 7fn = 17.4 0.7f Exclusion Zones: 17 4 Hz to 2 x (0.8fn) = 39.7 Hz to
0.124 mm
2 x 685 MW RAIPUR - CHHATTISGARH Coal Fired Power Plant - Primary Air Fan Foundation
x =
y =
z =
All of these responses are less than the allowable velocity = 2.3 mm/sec
OK
0.12 mm
OK