Sunteți pe pagina 1din 7

International Electrical Engineering Journal (IEEJ) Vol. 2 (2011) No. 2, pp.

536-542 ISSN 2078-2365

Voltage Sag mitigation in Electric Arc Furnace with D-STATCOM


Saji Chacko, Naveen Goel
Abstract Arc furnace represents one of the most intensive and disturbing loads in the electric power system. Utilities are concerned about these effects and try to take precautions to minimize them. Therefore, an accurate model of an arc furnace is needed to test and verify proposed solutions to this end. This paper, presents the results of a study, where furnace arc is modeled using both chaotic and deterministic elements. Voltage fluctuations (Sag), is captured using the well-studied circuit whereas a dynamic model in the form of differential equation is used for the electric arc. Simulation of developed model is done in Sim-Power-System environment of the MATLAB 7.1 Version. Index Terms Electric Arc Furnace, Simulink, Voltage Flicker

I. INTRODUCTION Electric Arc Furnace (EAF) is a widely used device in metallurgical and processing industries. It is a nonlinear time varying load, which can cause many problems to the power system quality such as unbalance, harmonic inter harmonic and voltage flicker. Thus study of electric arc furnaces has potential benefits for both customers and utilities. An accurate modeling of an EAF will help in dealing with the problems caused by its operation. Minimization of the undesirable impact of EAFs can improve electric efficiency and reduce power fluctuations in the system. The description of an arc furnace load depends on the following parameters: arc voltage, arc current and arc length (which is determined by the position of the electrodes). Based on the study of above essential parameters, many models are set up for the purpose of harmonic and flicker analysis. In general, they may be classified as follows, a) Time domain analysis method (Characteristic Method, Time Domain Equivalent Nonlinear Circuit Method), and b) Frequency
Saji Chacko, Shri Shankaracharya College of Engineering & Technology, Department of Electrical & Electronics, Junwani, Bhilai (CG) 490020, INDIA. e-mail: chackosaji68@gmail.com, Ph: +919893174845 Naveen Goel, Shri Shankaracharya College of Engineering & Technology, Department of Electrical & Electronics, Junwani, Bhilai (CG) 490020, INDIA. e-mail: ngoel_18@rediffmail.com. Ph: +917828699244

Domain analysis method (Harmonic Voltage Source Model, Harmonic domain Solution of nonlinear differential equation). Each method has its own advantages and disadvantages. Comparison and commendation of different arc furnace models were presented in [1]. Most of the existing models make some kinds of approximation on the characteristic of arc. There have been two general approaches to the problem of arc furnace modeling: stochastic and chaotic. In most of the previous studies, stochastic ideas are used to capture the periodic, nonlinear, and time-varying behavior of arc furnaces [2][4]. In [2], the arc furnace load is modeled as a voltage source. The model is based on representation of the V-I characteristics using sinusoidal variations of arc resistance and band limited white noise. Here empirical formulas related to the arcing process are used. Recent study shows that, the electrical fluctuations in the arc furnace voltage have proven to be chaotic in nature. Some chaos-based models reported in specialized literature [5] [6] have been applied to simulate ac [7]-[8] and dc arc furnaces [9]. In [7] the Lorenz chaotic model has been used to represent the highly varying behavior of currents in an ac arc furnace and a tuning procedure is applied to obtain the model parameters. In this work instead of using single valued piece-wise linear V-I characteristics of the arc furnace load, a dynamic and multi-valued V-I characteristics are obtained by using corresponding differential equations [8]. The output of dynamic model developed is modulated with low frequency chaos signal to produce the arc furnace model. The model developed is connected to sample power system to study the voltage fluctuation.

II. ARC FURNACE OPERATION Electric arc furnaces are available in both alternating current (AC) and Direct current (DC) models. A transformer directly energizes furnace electrodes in a high current circuit in arc furnaces, whereas dc furnaces employ a controlled rectifier to supply dc to the furnace electrodes. Arc furnace operation may be classified into stages, depending on the status of the 536

Saji et al. Voltage Sag mitigation in Electric Arc Furnace with D-STATCOM melt and the time lapse from the initial energization of the unit. Consider the case of the processing of scrap steel in an ac EAF. During the melting period, pieces of steel create momentary short circuits on the secondary side of the furnace transformer. These load changes affect the arc characteristics, causing fluctuations of current. The current fluctuations cause variations in reactive power, which cause a momentary voltage drop or flicker, both at the supply bus and at nearby buses in the interconnected system. The arc currents are more uniform during the refining period and result in less impact on the power quality of the system. Arc furnaces also create harmonic load currents and asynchronous spectral components. Harmonics represent an important power quality issue, because they may cause undesirable operating conditions such as excess losses in transformers maloperation of drive controllers etc.[12]. Figure.1 shows typical installation of EAF. The dynamic V-I characteristics of arc furnace load is obtained by using a general dynamic arc model in the form of a differential equation derived as

k1r n k2 r

dr k 2 m3 i dt r 2

where r stands for the arc radius and is chosen as the state variable. The arc voltage is given by i v g where g is defined as arc conductance and is given by the following equation
g r m2 k3

IV. ARC FURNACE MODEL The development of general dynamic arc model in the form of a differential equation is based on the principle of conservation of energy. The approach is fundamentally different from those methods where some empirical relation is used to represents the electrical arc. In the dynamic model such relations which are implicit for steady state conditions are not pre defined and gives result for different conditions depending on both frequency and current magnitude. Here the arc furnace is modeled in two stages. First dynamic electric arc modeling is done and the obtained arc voltage is then modulated with chaotic signal to produce final arc furnace model. The power balance equation for the arc is (1) Where, p1 represents the power transmitted in the form of heat to the external environment, p2 represents the power, which increases the internal energy in the arc, and which therefore affects its radius, and p3 represents the total power developed in the arc and converted into heat. The above equation can be represented in the form of differential equation [10] of the arc: (2) Here r stands for the arc radius which is chosen as a state variable instead of taking arc resistance or conductance. The arc voltage is then given by i (3) v
g

Transmission system xsc

Substation transformer HV/M V

EAF transformer M V/LV

Xe

Re

Generating source Electric arc furnace

Fig. 1 Typical installation of EAF

III. CHAOTIC DYNAMICS IN ELECTRIC ARC FURNACES Chaos, also known as the strange attractor, does not generally have an accepted precise mathematical definition. Usually from a practical view point, it can be defined as the bounded steady-state behavior that does not fall into the categories of the other three steady-state behaviors i.e. the equilibrium points, periodic solutions, and quasi periodic solutions [6]. The equilibrium points are zero dimensional and periodic solutions are one dimensional ,where as strange attractors are more complex and their dimension is a fraction. A chaotic system is a deterministic system that exhibits random movement and it is a nonlinear system that exhibits extreme sensitivity in the state trajectory with respect to the initial conditions. It has been observed that the electric fluctuations in an arc furnace are chaotic in nature. The chaotic component of the arc furnace voltage is obtained from the chaotic circuit of Chua [8]. To exhibit chaos, the circuit consisting of resistors capacitors and inductors has to contain the following: (i) At least one locally active reactor (ii) At least one nonlinear element. (iii) At least three energy storage elements Chuas circuit satisfies the above requirements. The arc furnace model is composed of two main parts. The first point is about the use of dynamic multi valued voltage current characteristic of the electric arc. The second point makes use of the chaotic current.

p1 p2 p3

k1r n k2 r

dr k 2 m3 i dt r 2

Where g is defined as arc conductance and given by the m2 equation g r (4) k3 It is possible to represent the different stages of the arcing process by simply modifying the parameters of m and n in (2). The complete set of combination of these parameters for different stages of electric arc can be found in [7].

537 | P a g e

International Electrical Engineering Journal (IEEJ) Vol. 2 (2011) No. 2, pp. 536-542 ISSN 2078-2365

Fig. 2 Dynamic characteri

Ia

-CVs Sequence Analyzer 2


abc A Mag Phase

Conn 1 Conn 2 Conn 3 In 1

DSTATCOM 1
A B C N A Vabc Iabc B a b C c

Iarc

A B C RL

A B C

Vabc a a2 b2 c2 a3 b3 c3
Conn 3 Conn 2 Conn 1

B b C c

A B C

a b c

Measurement 2

Breaker

Source

Measurement 1

Transformer 1 Discrete , Ts = 5e-005 s. A B C RLC Load


A B C a b c a b c A B C

Arcfurnace Transformer
a b c A B C

Breaker1

Measurement

Fig. 3 Control Scheme and test system using MATLAB/ Simulink stics of electric Arc Furnace

538

Saji et al. Voltage Sag mitigation in Electric Arc Furnace with D-STATCOM

The dynamic voltage/current characteristic of the electric arc furnace fig. 2 using the above equations is implemented using Simulink blockset as shown in fig. 4. This model is then combined with the band limit white noise to create the chaotic nature of the arc furnace voltage and current parameters as shown in fig. 5.
1/s Integrator Unit Delay 1 z 7 Gain1 Fcn (u^2) In1 1 Gain -Kf(u) Fcn2 1/(u^2) Fcn1 -KGain2 1 Out1

taken from the grid will be nearly sine wave. If D-STATCOM does not contain any active power storage it only injects or draws reactive power. Limited voltage sag mitigation is possible with the injection of reactive power only, but active power is needed if both magnitude and phase angle of the pre-event voltage need to be kept constant. The device rating determines the maximum total current which can be injected. In case an energy storage is connected to the D-STATCOM its capacity also needs to be rated. D-STATCOM equipped with energy storage and additional high-speed switchgear is able to inject also active power and thus support the load even during an interruption on the grid side. The steady state model of analyzing the rms voltages and currents, fundamental frequency power and energy flows, applies to D-STATCOM. Operating modes of D-STATCOM This is shunt connected device operates in two control modes Current Control: In this mode D-STATCOM acts as active filter, power factor controller, load balance etc. These functions are called load compensation. Voltage Control: In this mode a D-STATCOM can regulate voltage against any distortion, Sag/ Swells, unbalance and even short duration interruptions. Voltage Sag Correction by D-STATCOM The schematic diagram of a D-STATCOM is shown in Fig. 3. In this diagram, the shunt injected current corrects the voltage sag by adjusting the voltage drop across the system impedance Z. The value of current can be controlled by adjusting the output voltage of the converter. The shunt injected current can be written as:
Vth Rth Is
volate source converter D-STATCOM Energy storage

Fig. 4.Control Structure of Arc Furnace

1/s Integrator 1 z

1/(u^2) Fcn1

-K-

s -

Unit Delay -K-

f(u) Fcn2 Band-Limited White Noise Fcn (u^2)

Controlled Voltage Source

1 Conn1

In1 1

Fig. 5 Control Structure of Arc Furnace with Chaotic nature

The MATLAB implementation for a 3 phase EAF model that includes dynamic arc model and chaotic circuit is shown in Fig. 2.

V. SHUNT VOLTAGE CONTROLLER:


DISTRIBUTION STATIC COMPENSATOR (DSTATCOM) A D-STATCOM, which is schematically depicted in Fig. 6 consists of a voltage source converter (VSC) shunt connected to the distribution network through a coupling transformer. This configuration allows the device to absorb or generate controllable reactive power. The D-STATCOM has been utilized for voltage regulation, correction of power factor and elimination of current harmonics. In distribution voltage level, the switching element is usually the IGBT (Integrated Gate Bipolar Transistor) due to its lower switching losses and reduced size. Moreover, the power rating of custom power devices is relatively low. Consequently, the output voltage control may be executed through PWM (Pulse Width Modulation) switching method. It is also capable of flicker and harmonics mitigation. A D-STATCOM is connected in parallel with the distribution feeder. It generates a current injection, which is summed to the non-sinusoidal load current. Thus the phase currents

jX th

VL

I sh

PL jQL

Fig. 6 Schematic representation of the D-STATCOM

Ish = (IL IS ) = IL (VTH / ZTH ) .(1) VL = V L Ish = Ish 539 | P a g e

International Electrical Engineering Journal (IEEJ) Vol. 2 (2011) No. 2, pp. 536-542 ISSN 2078-2365

IL = IL - VTH = VTH ZTH = ZTH


Current (pu)

500 400 300 200 100 0 -100 -200 -300

Put this value in equation (1) ISh= IL- (VTH - VL 0) / ZTH ) ISh= IL- (VTH (- ) / ZTH ) + (VL - )/ ZTH ...(2) The complex power injection of the D-STATCOM can be expressed as

SSh = VL ISh * ... (3)


It may be mentioned here that the effectiveness of the D-STATCOM in correcting voltage sag depends on the value of Z or fault level of the load bus. When the shunt injected current I is kept in quadrature with the desired voltage correction can again be achieved without injecting any active power into the system. On the other hand when the value of is minimized, the same voltage correction can be achieved with minimum apparent power injection into the system [18-19].

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

Time (sec)
Fig. 8 Single phase System Current without Statcom
x 10
4

1.5

Arc current (pu)

1.4 1.2 1

0.5

Voltage (pu)

-0.5

0.8 0.6 0.4


-1 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8

Time (sec)
Fig. 9 Arc Furnace Current without Statcom

0.2 0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

Time(sec)

Fig. 7 Single Phase System Voltage (pu) without Statcom

540

Saji et al. Voltage Sag mitigation in Electric Arc Furnace with D-STATCOM VI. CONCLUSION The main aim of this Paper is to try to find out the types of power disturbances that are occurring in power distribution system, mainly due to nonlinear loads with special emphasis on the Arc furnace loads. These loads not only introduce harmonic in the power lines but also cause heavy voltage sag and affect the working of Critical drive equipments connected to the Point of Common Coupling (PCC). The paper presents the modelling of arc furnace loads and its implementing using MATLAB/Simulink, its effect on the Power system and how the use of voltage compensation devices like D-STATCOM improves the voltage stability.
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8

1.4 1.2 1

Voltage (pu)

0.8 0.6 0.4 0.2 0

Time (sec)
Fig.10 System Voltage of single phase with Statcom

500 400 300

APPENDIX Parameters of EAF model and sample power system are as follows, Source: Ideal sinusoidal ac voltage source with amplitude=50.6 kV and zero phase shift. Z Thevenin: Resistance=0.346 and inductance, L=9.8mH. Transformer: Three windings linear single-phase transformer. Nominal power: Pn=60 MVA. Winding 1 parameters: V1 (Vrms)=46 kV, R1 (pu)=0.002, L1 (pu)=0.55, Winding 2 parameters: V2 (Vrms)=770 V, R2 (pu)=0.002, L2 (pu)=0.55, Magnetization resistance and reactance: Rm(pu)=500 Lm(pu)=500 Arc Furnace: (Parameters for corresponding differential equation) k1=3000.0,k2=1.0,k3=12.5 m=0,n=2. (Chuas circuit) C1=200nF,C2=0.2 F,L=3.6m H with a series resistor Ro=12.5,G=5.442E-4 mho.

Current (pu)

200 100 0 -100 -200 -300

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

Time (sec)
Fig. 11 System Current of Single phase with Statcom
1.5 x 10
6

1
Arc Current (pu)

0.5

-0.5

-1

-1.5

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

Time (sec)
Fig. 12 Arc Furnace Current with Statcom

541 | P a g e

International Electrical Engineering Journal (IEEJ) Vol. 2 (2011) No. 2, pp. 536-542 ISSN 2078-2365

REFERENCES
[1] T. Zheng, E. B. Makram, and A. A. Girgis, Effect of different arc furnace models on voltage distortion, in Proceedings of the Eighth International Conference on Harmonics and Quality of Power (ICHPQ), Oct.1998, Pp. 10791085 R. C.Bellido and T. Gomez, Identification and modeling of a three phase arc furnace for voltage disturbance systems, IEEE Trans. PWRD. Vol. 12, Pp. 18121817, Oct. 1997. G. C. Montanari, M. Loggini, A. Cavallini, L. Pitti, and D. Zanielli, Arc furnace model for the study of flicker compensation in electrical networks IEEE Trans. Power Delivery, Vol. 8, Pp. 20262036, Oct. 1994. S. Varadan, E. B. Makram, and A. A. Girgis, A new time domain voltage source model for an arc furnace using EMTP, IEEE Trans. Power Delivery, Vol. 11, Pp. 16851690, July 1996. M. P. Kennedy, Three steps to chaos, Part 1:Evolution, IEEE Trans. Circuit Syst. I, vol. 40, no. 10, Pp. 640656, October 1993. M. P. Kennedy Three steps to chaos, Part 2:A Chuas circuit primer, IEEE Trans. Circuits Syst. I, Vol. 40, pp. 657674, Oct. 1993. E. ONeill-Carrillo, G. Heydt, E. J. Kostelich, S. S. Venkata, and A.Sundaram, Nonlinear deterministic modeling of highly varying loads, IEEE Trans. Power Delivery, Vol. 14, pp. 537542, Apr. 1999. O. Ozgun and A. Abur, Development of an arc furnace model for power quality studies, Proc. IEEE-PES Summer Meeting 1999 , Vol. 1, Pp. 507511, 1999. G. Carpinelli, F. Iacovone, A. Russo, P. Verde, and D. Zaninelli, DC arc furnaces: Comparison of arc models to evaluate waveform distortion and voltage fluctuations, in Proc. IEEE Power Engineering Society 33rd Annual North America Power Symp., Pp. 574580 E. Acha, A. Semlyen, and N. Rajakovic, A harmonic domain computational Package for nonlinear problems and its application to electric arcs, IEEE Trans. Power Delivery, Vol. 5, Pp. 13901397, July 1990. M.M. Morcos, J.C. Gomez Flicker Sources and Mitigation IEEE Power Engineering Review, November 2002 P 5-10 M. H. J. Bollen, Understanding Power Quality ProblemsVoltage Sags and Interruptions Piscataway, New York: IEEE Press 2000. O. Ozgun, A Abur Flicker study using a Novel Arc Furnace Model IEEE Trans. on PWRD, Vol. 17, No. 4, Oct-2002 pp. 1158-1163 Adly A. Girgis, Jhon Stephens and Elam B. Makram Measurement and prediction of voltage flicker magnitude and frequency, IEEE Trans. on Power Delivery, July 1995. Singh G.K., Power System Harmonics Research: A Survey, European Transaction on Electrical Power , 2009, 19:151-172. K. Anuradha, Muni B.P., Rajkumar A.D., Electric Arc Furnace Modeling and Voltage Flicker Mitigation by D Statcom, IEEE Region 10 Collogium and the third ICIIS, Kharagpur, India, December 8-10, 2008 Chiang H., Liu C., Varaiya P.P., wu F., Lauby M.G. Chaos in a Simple Power System, IEEE Transaction on Power System, Vol. 8, No. 4, Pp. 1407-1471,Nov.1993 Sung-Min Woo, Dae-Wook Kang and Woo-Chol Lee, The Distribution STATCOM for reducing the Effect of Voltage Sag and Swell IECON01: The 27th Annual Conference of the IEEE Industrial Electronic Society, Pages 17-22, 2001 Arindam Ghosh, and Gerard Ledwich Compensation of Distribution System Voltage Using DVR, IEEE Transactions on Power Delivery, Vol. 17, No. 4, October 2002.

[2] [3]

[4] [5] [6] [7]

[8] [9]

[10]

[11] [12] [13] [14] [15] [16]

[17]

[18]

[19]

542

S-ar putea să vă placă și