Sunteți pe pagina 1din 15

Automatic Detectors Series IQ8Quad (Intelligent Addressable)

Automatic intelligent fire detectors with high reliability, used for premises and items of
property with medium and high concentration of valuable assets.
Detector series IQ8Quad features, system advantages
designed for optimal operation on System 8000 and IQ8Control fire alarm systems
with multisensor detectors for the detection of all types of fires, even under the most diffi-
cult operating conditions
detector with and without loop isolator
Different options of installation
-wiring in loop and spur combination, e.g.
-maximum number of detectors with cable lengths of up to 3500 m with installation cable
for fire detection, e.g. cables I-Y(St)Yn x 2 x 0.8 mm
-up to 127 detectors and detector zones per loop installation
-up to 32 detectors per zone
Easy commissioning
-automatic detector addressing
-fixed address assignment of detector location, even after detectors have been replaced or
added
-localization of wire breaks and short circuits on loop
-detector-LED used as alarm indicator and as an indicator for detectors in service
-adaptation to changing operating conditions
-dedicated LED for indicating operation (green LED)
-disconnection of individual detectors, detector zones and detection areas
-disconnection of individual sensors or several sensors at once within a multisensor
detector; either manually or depending on programmed time of the day
Automatic adaptation to varying environmental conditions
-compensation of changing levels of air pressure, humidity, smoke concentration
according to the double chamber principle
-electronic compensation of long-term influences like aging or pollution
Reliable detection
-constant alarm sensitivity of multisensor detector for all types of fire
-large signal to noise ratio due to the special design of the sensors and the electronics to
suppress electromagnetic interference
Reliable false alarm suppression
-high immunity against false alarms by means of timed evaluation of different sensor
criteria
-signal patterns not typical for fires are eliminated by using special filter algorithms
-automatic self-monitoring of detector electronics
-continuous loop monitoring even during short-circuits through isolating the relevant
segment
-automatic monitoring of all sensors to guarantee operational capacity and correct condi-
tion.
Increased operating reliability
-short-circuit and wire break tolerant through monitoring from both ends of the loop
-alarm decision inside detector
-fail-safe circuit activated if communication fails
Maintenance
-automatic maintenance request
-heat detector identification through a black circle on the light transmission plate
-multisensor gas detector identification through a golden loop on the circle transmission
plate
-operating time-, alarm- and fault counter in each detector
-automatic, cyclic loop check
-complete status interrogation from the control panel
-interrogation of operating data from all detectors on loop via standard service PC and
detector interface
Comprehensive range of accessories
-standard detector base and relay base
-base adapter for ceiling mounting
-dust cover for fire detector or detector base
-kit for suspended ceiling mounting
-RF base
www.esser-systems.com 90
q6h=
q6h/G&
802171
802171.F
Fixed heat detector IQ8Quad
Fixed heat detector IQ8Quad - France
Automatic heat detector with fast semiconductor sensor to guarantee reliable detection of
fires with strong heat generation. Intelligent fire detector with decentralised intelligence,
automatic function self-test, CPU failure mode, alarm and operating data memory, alarm
indicator, soft-addressing and operating indication.
The detector is provided with an integrated isolator. A parallel detector indicator can be
connected.
As 802171, but with NF-Approval Mark at the backside.
Automatic Detectors Series IQ8Quad (Intelligent Addressable)
Detector without integrated alarm devices
Detector base is not supplied as standard
Accessories
767800 mounting bracket
805590 Standard detector base for IQ8Quad
805591 Detector base with relay contact for IQ8Quad
Technical Data
Operating voltage 8 ... 42 V DC
Alarm current w/o communication curtain approx. 18 mA
Air speed 0 ... 25.4 m/s
Storage temperature -25 C ... 75 C
Air Humidity < 95 % (non-condensing)
Type of protection IP 43 (with base + option)
Material ABS plastic
Color white, similar to RAL 9010
Weight approx. 110 g
Dimensions : 117 mm H: 49 mm (62 mm incl. base)
VdS, CNBOP, BOSEC
CNMIS
Approval:
Approval:
Technical Data
Quiescent current @ 19 V DC approx. 40 A
Area to be monitored max. 30 m
Height to be monitored max. 7.5 m
Application temperature -20 C ... 50 C
Detector specification EN 54 - 5 A1S / -17
Technical Data
Operating voltage 8 ... 42 V DC
Quiescent current @ 19 V DC approx. 40 A
Height to be monitored max. 7.5 m
Application temperature -20 C ... 50 C
Detector specification EN 54 - 5 A1S, EN54-17
Special-colour on demand
The detectors part no. 802271, 803271, 802371, 803371, 802373, 802374 and 803374 are
approved in the scope of the DIBt system authorization for the operation with an Automatic Door
System.
Special marking for heat detector on the light pipe: black ring.
Marquage spcial pour le dtecteur de chaleur sur le diffuseur lumineux: Cercle noir.
Fire detector with base
117
62

1
2
3
4
5
6
7
8
9
10
11
12
17
16
13
14
15
1
91
q6nO
q7h?
q7h/G(
qAhS
802177
802271
802271.F
803271
Fixed heat detector class B IQ8Quad
Rate-of-rise heat detector IQ8Quad
Rate-of-rise heat detector IQ8Quad - France
IQ8Quad Rate-of-rise detector without loop isolator
As 802171, but for increased operating temperature according to EN 54-5 Class B.
Automatic heat detector with fast semiconductor sensor to guarantee reliable detection of
fires with rapidly rising temperatures and integrated fixed temperature function for the
detection of fires with slowly rising temperatures. Intelligent fire detector with decentral-
ised intelligence, automatic function self-test, CPU failure mode, alarm and operating data
memory, alarm indicator, soft-addressing and operating indication.
The detector is provided with an integrated isolator. A parallel detector indicator can be
connected.
As 802271, but with NF-Approval Mark at the backside.
As 802271 but without loop isolator.
The detector can be operated in a standard detector group as well as independently.
Automatic Detectors Series IQ8Quad (Intelligent Addressable)
VdS
VdS, CNBOP, BOSEC
CNMIS
VdS, CNBOP
Approval:
Approval:
Approval:
Approval:
Technical Data
Quiescent current @ 19 V DC approx. 40 A
Area to be monitored max. 30 m
Height to be monitored max. 6 m
Application temperature -20 C ... 65 C
Detector specification EN 54-5 BS / -17
Technical Data
Quiescent current @ 19 V DC approx. 40 A
Area to be monitored max. 30 m
Height to be monitored max. 7.5 m
Application temperature -20 C ... 50 C
Detector specification EN 54-5 A1 / -17
Technical Data
Operating voltage 8 ... 42 V DC
Quiescent current @ 19 V DC approx. 40 A
Height to be monitored max. 7.5 m
Application temperature -20 C ... 50 C
Detector specification EN 54-5 A1R, EN 54-17
Technical Data
Quiescent current @ 19 V DC approx. 40 A
Area to be monitored max. 30 m
Height to be monitored max. 7.5 m
Application temperature -20 C ... 50 C
Detector specification EN 54-5 A1
DIBt approval Z-6.5-1764 license system 8000-FSA Z-6.5-1759
license system IQ8FSA 8619 Z-6.5-1808 license
system 8000-FSA-PLus
Special marking for heat detector on the light pipe: black ring.
Special marking for heat detector on the light pipe: black ring.
Marquage spcial pour le dtecteur de chaleur sur le diffuseur lumineux: Cercle noir.

www.esser-systems.com 92
q8hA
qBhU
q8jG
802371
803371
802373
Optical smoke detector IQ8Quad
IQ8Quad Optical smoke detector without loop isolator
OT multisensor detector IQ8Quad
Optical smoke detector to guarantee safe and early detection of fire. Intelligent fire detector
with decentralised intelligence, automatic function self-test, CPU failure mode, alarm and
operating data memory, alarm indicator, soft-addressing and operating indication. The
detector is provided with an integrated isolator. A parallel detector indicator can be
connected.
As 802371 but without loop isolator.
The detector can be operated in a standard detector group as well as independently.
Multisensor detector with integrated optical detector and heat detector, with time-
controlled signal analysis and weighted data combination of both detector functions for
detecting smouldering fires and fires with extreme heat generation. Intelligent detector with
decentralised intelligence, self function test, CPU redundancy mode, automatic adaptation
to the environments, alarm and operating data storage, alarm indication and soft
addressing.
The loop isolator is integrated in the detector. A parallel detector indicator is additionally
attachable.
Automatic Detectors Series IQ8Quad (Intelligent Addressable)
VdS, CNBOP, BOSEC
VdS, CNBOP
VdS
Approval:
Approval:
Approval:
Technical Data
Quiescent current @ 19 V DC approx. 50 A
Area to be monitored max. 110 m
Height to be monitored max. 12 m
Application temperature -20 C ... 72 C
Detector specification EN 54-7 / -17
Technical Data
Quiescent current @ 19 V DC approx. 50 A
Area to be monitored max. 110 m
Height to be monitored max. 12 m
Application temperature -20 C ... 72 C
Detector specification EN 54-7
DIBt approval Z-6.5-1764 license system 8000-FSA Z-6.5-1759
license system IQ8FSA 8619 Z-6.5-1808 license
system 8000-FSA-PLus
Technical Data
Quiescent current @ 19 V DC approx. 50 A
Area to be monitored max. 110 m
Height to be monitored max. 12 m
Application temperature -20 C ... 50 C
Detector specification EN 54-7/-5 A2 /-17, CEA 4021

1
2
3
4
5
6
7
8
9
10
11
12
17
16
13
14
15
1
93
q8lM
q8l/G6
q8kJ
802375
802375.F
802374
OTblue multisensor detector IQ8Quad
OTblue multisensor IQ8Quad - France
O
2
T multisensor IQ8Quad
Multisensor with integrated optical detector and heat detector. The optical measurement
chamber is provided with a newly developed sensor technology, enabling the detection of
open fires, smouldering fires and fires with high heat generation. Especially for open fires,
the classical ionisation technology implemented in ionisation detectors is replaced by the
new detection technology. The detector is capable of identifying the TF1 and TF6 test fires
described in the EN 54-9:1982 specification.
The OTblue multisensor is an intelligent detector with time-related signal analysis, signal
correlation of the sensor data, decentralised intelligence, automatic function self-test, CPU
failure mode, automatic adaptation to environmental conditions, alarm and operating data
memory, alarm indicator and soft-addressing.
The detector is provided with an integrated isolator and a parallel detector indicator can be
connected.
As 803275, but with NF-Approval Mark at the backside.
Multisensor detector provided with two built-in optical smoke sensors with different
scattered light angles as well as additional heat detector sensor evaluation to guarantee the
detection of different types of fire from smouldering fires to open fires with constant sens-
itivity level. Smoke sensor signal identification to ensure smoke classification and reduc-
tion of deceptive alarms caused, for instance, by water vapour or dust.
Because of its excellent detection characteristics, the detector is also able to identify the
standardized TF1 and TF6 test fires. The OT multisensor detector is also suitable for
applications with higher temperatures of up to +65 C. The detector is provided with an
integrated isolator. A parallel detector indicator can be connected.
Automatic Detectors Series IQ8Quad (Intelligent Addressable)
VdS
NF-SSI
VdS, CNBOP, BOSEC
Approval:
Approval:
Approval:
Technical Data
Quiescent current @ 19 V DC approx. 50 A
Area to be monitored max. 110 m
Height to be monitored max. 12 m
Application temperature -20 C ... 50 C
Detector specification EN 54-7/-5 A2 /-17, CEA 4021
Technical Data
Operating voltage 8 ... 42 V DC
Quiescent current @ 19 V DC approx. 50 A
Height to be monitored max. 12 m
Application temperature -20 C ... 50 C
Detector specification EN 54-7/5 A2, EN54-17
Technical Data
Quiescent current @ 19 V DC approx. 60 A
Area to be monitored max. 110 m
Height to be monitored max. 12 m
Application temperature -20 C ... 65 C
Detector specification EN 54-7/-5 B /-17, CEA 4021

www.esser-systems.com 94
q8k/G3
qBk^
q9jI
802374.F
803374
802473
O
2
T multisensor IQ8Quad - France
IQ8Quad O
2
T Intelligent detector without loop isolator
OTG multisensor (CO) IQ8Quad
As 802374, but with NF-Approval Mark at the backside.
As 802374 but without Loop isolator.
The detector can be operated in a standard detector group as well as independently.
Multisensor detector with integrated smoke detector, heat detector and gas sensor (CO) for
preventive and early detection of fires ranging from smouldering fires to open fires through
combined evaluation of scattered light, temperature and gas. An alarm is actuated at
carbon monoxide (CO) concentration levels that are life-threatening for humans. The
detector is provided with an integrated isolator. A parallel detector indicator can be
connected.
Automatic Detectors Series IQ8Quad (Intelligent Addressable)
NF-SSI
VdS, CNBOP
VdS
Approval:
Approval:
Approval:
Technical Data
Operating voltage 8 ... 42 V DC
Quiescent current @ 19 V DC approx. 60 A
Height to be monitored max. 12 m
Application temperature -20 C ... 65 C
Detector specification EN 54-7/5 B, EN54-17
Technical Data
Quiescent current @ 19 V DC approx. 60 A
Area to be monitored max. 110 m
Height to be monitored max. 12 m
Application temperature -20 C ... 65 C
Detector specification EN 54-7/-5 B, CEA 4021
DIBt approval Z-6.5-1764 license system 8000-FSA Z-6.5-1759
license system IQ8FSA 8619 Z-6.5-1808 license
system 8000-FSA-PLus
Technical Data
Quiescent current @ 19 V DC approx. 65 A
Area to be monitored max. 110 m
Height to be monitored max. 12 m
Application temperature -20 C ... 50 C
Detector specification EN 54-7/-5 A2 /-17, CEA 4021
In the course of installation, we recommend testing the integrated CO sensor with our CO test
gas (part no. 805583) or CO capsule (part no. 805553).
Programmable CO-alarm-thresholds: 10-150 ppm.
Gas sensors (CO) mainly react to the carbon monoxide arising from a fire (CO). They have,
however, also a cross sensitivity to other gases, as for example hydrogen (H2), acetylene (C2H2)
or nitric oxide (NO).
Special marking for gas detector on the light pipe: black ring.

1
2
3
4
5
6
7
8
9
10
11
12
17
16
13
14
15
1
95
O
2
T Detector with integrated alarm devices
The IQ8Quad smoke detectors with built-in alarm device incorporate up to 4 different func-
tionalities (detect, flash, sound, and/or speech) depending on the type (OT/F, OT/So, OT/
Sp, OT/FSp) of detector.
- fire detection as per EN 54-7
- integrated heat sensor as per EN 54-5
- optical alarm via flash lamp
- acoustic alarm via sounder as per as per EN 54-3
- acoustic alarm speech messages
Detection
Multisensor detectors with two built-in optical smoke sensors with different scattered light
angles as well as additional heat detector sensor evaluation for detecting everything from
smouldering fires to open fires with consistent response performance. Smoke sensor
signal identification to ensure smoke classification and reduction of false alarms caused,
for instance, by water vapour or dust. Each detector is provided with an integrated isolator.
Alarm signaling
The alarm signaling device is activated by the control panel. No further short address
needs to be allocated. It is programmed with tools 8000 as of software version 1.05.
Alarm tone / speech message programming
For detectors with speech message and/or alarm tone function with up to five language
options, up to 4 signals can be programmed. Two signals are reserved for alarm signaling
and evacuation in the case of fire. Two further signals can be programmed for other events.
Each signal can consist of up to four signal components, enabling one signal to be
programmed as a DIN tone combined with subsequent speech messages in three different
languages.
Alarm tones can be chosen from a table with various tone types. For application in schools,
a break signal to signify the breaks between class can be activated.
Four different speech messages, each in three languages, are available:
- "An incident has been reported in the building. Please await further instructions.
- "Attention please. This is an emergency. Please leave the building by the nearest avail-
able exit.
- "This is a fire alarm. Please leave the building immediately by the nearest available exit.
- This is a test message. No action is required.
When the basic setting is selected, signals / signal components can be continuously
repeated until the signalling function is interrupted by the control panel. They can also be
programmed with a repetition rate of one to three times. Thus, the break signal in schools
can be deliberately set to only one repetition. In the same way, the total signal can be set to
continuous repetition, with the DIN tone being played only once while subsequent speech
messages are played up to three times.
Sound pressure programming
The sound level [dB (A)] can be set to eight levels, from approximately 64dB (A) to approx-
imately 92dB (A).
All the security you need in one housing with four functions detection, flasher, sounder and
speech alarm.
Automatic Detectors Series IQ8Quad (Intelligent Addressable)
Features
Detection
The reliable OT multisensor principle for
consistent response performance at the highest
level of security against false alarms
Flash lamp
Loop powered - no need for external power
supply
No additional short address
Automatic synchronization of various IQ8Quad
alarm signaling devices
High flash energy
Loop powered - no need for external power
supply
No additional short address
Automatic synchronization of various IQ8Quad
alarm signaling devices
Maximum sound level: 92 dB (A) at 1 m
Maximum sound pressure can be set
Multiple signal patterns can be combined to one
signal
Signal pattern and repetition rates can be set
20 different signal tones, incl. DIN-tone
Speech massage with sounder
Loop powered - no need for external power
supply
No additional short address
Automatic synchronization of various IQ8Quad
alarm signaling devices
Maximum sound level: 92 dB (A) at 1 m
Maximum sound pressure can be set
Multiple signal patterns can be combined to one
signal
Signal pattern and repetition rates can be set
20 different signal tones, incl. DIN-tone
Speech messages can be played in up to 5
languages
5 alarm messages per languages are prepro-
grammed
www.esser-systems.com 96
Automatic Detectors Series IQ8Quad (Intelligent Addressable)
sequence 2

sequence 1

signal 1
(evacuation)
sequence 2
sequence 3

sequence 1

sequence 4

sequence 3

sequence 4

signal 2
(alarm)
sequence 2
sequence 3 sequence 1

sequence 4

signal 3
(event 1)
sequence 2
sequence 3

sequence 1

sequence 4

signal 4
(event 2)

Signals
All IQ8Quad detectors with built-in alarm devices can only be operated on the powered loop. For
physical reasons, an increased sound level leads to a higher current consumption rate of the
alarm device, the respective load factor must be considered when calculating the maximum
number on the loop. Altogether up to 127 bus devices per loop can still be connected.
Please consider that an extra training is required when dealing with IQ8Quad with a built-in
alarm device. The training includes installation planning and commisioning techniques. For
further information take a look at our training brochure. Information concerning the calculation
can be found in the "Project Planning Support chapter.
1
2
3
4
5
6
7
8
9
10
11
12
17
16
13
14
15
1
97
O
2
T/Optical detector with integrated alarm devices
1 School bell complex complex
2
FP 1063.1 Telecoms
BS 5839 Pt1
3 BS 5839 Pt1
4 BS 5839 Pt1
5 BS 5839 Pt1
6 BS 5839 Pt1
7 BS 5839 Pt1
8 BS 5839 Pt1
9 BS 5839 Pt1
10
DIN Tone
DIN 33404 Part 3
11 French fire sound
12 NL - Slow Whoop
13 US - Horn
14
US - Horn with
Temporal Pattern
15
US - March
Time
16
US - Slow
Whoop
17 US - Siren
18 US - Hi/Lo
19
US - NFPA
Whoop

20
IMO
GA-Signal
0,5sec.
0,5sec.
1,5sec.
0,5sec.
0,5sec.
1,5sec.
0,5sec.
0,5sec.
1,5sec.
0,5sec.
0,5sec.
0,25sec.
0,25sec.
1,0sec.
0,25sec.
10 ms
1,0 sec.
0,25sec.
0,25sec.
0,25sec.
0,25sec.
0,85 sec. 1,0 sec.
1,0sec.
1,0sec.
1,0sec.
t
t
t
t
t
t
t
t
t
t
t
t
t
t
t
t
t
t
t
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
f
No. Description Frequency Pulse rate
Alternating 800 / 970 Hz at 2 Hz
Alternating 800 / 970 Hz at 1 Hz
Intermittent 970 Hz at 1 Hz 0.5 sec.
Intermittent 2850 Hz at 1 Hz 0.5 sec.
Intermittent 970 Hz 1/4 sec. ON - 1 sec. OFF
Continious 970 Hz
Sweep tone 800 Hz tp 970 Hz at 7 Hz
Sweep tone 800 Hz to 970 Hz at 1 Hz
1200 - 500 Hz at 1 Hz
554 Hz / 100 ms + 440 Hz / 400 ms + 10 %
500 Hz - 1200 Hz at 3.5 sec. break of 0.5 sec.
Continious 485 Hz
Intermittent 485 Hz
(0,5 sec. ON; 0.5 sec. OFF; 3 times; 1.5 sec. OFF; Repeat)
Alternating 485 Hz
(0,25 sec. ON; 0.25 sec. OFF; Repeat)
Sweep tone 500 Hz to 1200 Hz
(4.0 sec. ON; 0.5 sec. OFF; Repeat)
Sweep tone 600 Hz to 1200 Hz
(1,0 sec. ON, Repeat)
Alternating 100 Hz / 800 Hz
(0.25 sec. ON; Alternate; 0.25 sec. ON; Alternate; Repeat)
Sweep tone 422 Hz to 775 Hz
(upwards sweep 0.85 sec.; 3 times; 1 sec. OFF; Repeat)
Intermittent 800 Hz (1,0 sec. ON; 1,0 sec.
OFF: 7 times; 2.0 sec. ON: 2.0 sec. OFF; Repeat)
1,0 sec.
0,1sec.
0,4sec.
3,5sec.
0,5sec.
4,0sec.
0,5sec.
Germany
(DE)
de
Dies ist ein
Feueralarm. Bitte
verlassen Sie das
Gebude um-
gehend ber die
nchsten Flucht-
wege. Die Feuer-
wehr ist alarmiert.
Achtung, Achtung!
Dies ist eine Gefahr-
enmeldung. Bitte
verlassen Sie das
Gebude ber die
nchsten
Ausgnge.
Achtung, im Ge-
bude ist eine
Gefahrensituation
gemeldet worden.
Bitte bleiben Sie
ruhig, und warten
Sie auf weitere
Anweisungen.
Dies ist eine
Testdurchsage.
France
(FR)
Ceci est une alarme
incendie,veuillez
vacuer
immdiatement les
locaux par la sortie
la plus proche.
fr
Votre attention s'il
vous plat, ceci est
une alarme. Veuillez
vacuer les locaux
par la sortie la plus
proche.
Un incident est
signal dans le
batiment. Merci de
garder votre calme
et attendez les
prochaines
instructions.
Ceci est un test.
L'alarme est
prsent annule.
Veuillez nous excuser
pour le dsagrment.
Die Gefahrensituation
ist jetzt behoben. Wir
entschuldigen uns
fr jegliche
Unannehmlichkeiten.
Great Britain
(GB)
en
This is a fire alarm.
Please leave the
building immedia-
tely by the nearest
available exit.
Attention please.
This is an emergen-
cy. Please leave the
building by the
nearest available exit.
An incident has
been reported in the
building. Please
await further
instructions.
This is a test
message.
No action is
required.
The emergency is
now cancelled. We
apologize for any
inconvenience.
Spain
(ES)
es
Esto es una alarma
de incendio.
Abandonen
por favor el edificio
inmediatamente
por la salida de
evacuacin
ms cercana.
Atencin. Esto es
una emergencia.
Por favor
abandonen el
edificio por la
salida de
evacuacin
ms cercana.
Atencin, se ha
reportado un
incidente
en el edificio.
Aguarden por favor
otras instrucciones.
Esto es un
mensaje
de prueba.
No se requiere
ninguna accin.
La emergencia ha
sido cancelada.
Pedimos disculpas
por las molestias
causadas.
Country code
acc. to ISO
3166 -Alpha-2
Language
code acc.
to ISO 639-1 Evacuation 1 Evacuation 2 Alarm Test-message All-Clear
Standard speech messages of IQ8Quad detectors and IQ8Alarm
IQ8Quad detector and IQ8Alarm tone table
Italy
(IT)
it
Attenzione.
Allarme incendio.
Abbandonare
l'edificio tramite
l'uscita di
emergenza pi
vicina.
Attenzione.
Allarme in corso.
Vi preghiamo di
recarvi presso
l'uscita di
emergenza pi
vicina.
Attenzione.
E' stato rilevato un
allarme.Ulteriori
disposizioni vi
verranno
comunicate
appena possibile.
Attenzione.
E' in corso una
prova di allarme.
Non richiesta
alcuna azione.
Attenzione. Cessato
allarme.La situazione
di normalit stata
ripristinata.
Automatic Detectors Series IQ8Quad (Intelligent Addressable)
www.esser-systems.com 98
Automatic Detectors Series IQ8Quad (Intelligent Addressable)
Detector with integrated alarm devices
Accessories
767800 mounting bracket
805590 Standard detector base for IQ8Quad
esserbus-PLus
Loop length max. 3.5 km
esserbus

transponder
flash speech signal
IQ8Control C
speech sound
speech
flash
Application example
Technical Data
Operating voltage 8 ... 42 V DC
Area to be monitored max. 110 m
Height to be monitored max. 12 m
Air speed 0 ... 25.4 m/s
Application temperature -20 C ... 65 C
Storage temperature -25 C ... 75 C
Air humidity d 95% (ohne Betauung)
Type of protection IP 42
Material ABS plastic
Color white, similar to RAL 9010
Weight approx. 145 g
Detector specification En 54-7/5 B, CEA 4021
Dimensions : 117 mm H: 59 mm
Detector bases are not supplied as standard.
The 769836 demo package is available for presentations. Further data can be viewed in the
accessories section for automatic detectors. For calculating the battery capacity of fire alarm
control panels, the detector data "quiescent current @ FACP battery" can be added.
Special-colours on demand!
It is not possible to use the detector base with relay contact (part no. 805591).
Fire detector with base
117
65
1
2
3
4
5
6
7
8
9
10
11
12
17
16
13
14
15
1
99
q8te
q8sb
802383
802382
O
2
T/F multisensor IQ8Quad
O/So optical smoke detector IQ8Quad
In addition to smoke detection with the conventional OT multisensor technology, the
detector is provided with a built-in flash lamp.
Scatter smoke detector for safe and early detection of smouldering fires with light smoke
generation. Intelligent detector with decentralised intelligence, automatic function self-test,
CPU failure mode, alarm and operating data memory, alarm indicator, soft-addressing and
operating indication. The detector is provided with a loop isolator.
Along with smoke detection components, the detector is provided with a built-in sounder.
Automatic Detectors Series IQ8Quad (Intelligent Addressable)
VdS
VdS
OT/F multisensor IQ8Quad with integrated flasher
O/So optical smoke detector IQ8Quad with integrated sounder
Approval:
Approval:
Technical Data
Quiescent current @ 19 V DC approx. 75 A
Quiescent current @ FACP battery approx. 400 A
Load factor 2
Lighting energy ca. 3 J
Strength of light max. 15,8 cd peak / 2,63 cd effective
Signal flashing lamp red
Technical Data
Quiescent current @ 19 V DC approx. 80 A
Load factor 2
Sound level max. 92 dB (A), +/- 2 db (A) @ 1m for DIN tone
Detector specification EN54-7, EN 54-17
Not suitable for application in relay base 805591!
Not suitable for application in relay base 805591!

www.esser-systems.com 100
q8s/G1T
q8uh
802382.F0
802384
O/So optical smoke detector IQ8Quad - France
O
2
T/So multisensor IQ8Quad
Scatter smoke detector for safe and early detection of smouldering fires with light smoke
generation. Intelligent detector with decentralised intelligence, automatic function self-test,
CPU failure mode, alarm and operating data memory, alarm indicator, soft-addressing and
operating indication. The detector is provided with a loop isolator.
Along with smoke detection components, the detector is provided with a built-in sounder.
In addition to smoke detection with the conventional OT multisensor technology, the
detector is provided with a built-in alarm signalling device. The sound level can be set to
eight different levels.
Automatic Detectors Series IQ8Quad (Intelligent Addressable)
VdS
VdS
O/So optical smoke detector IQ8Quad with integrated sounder
OT/So multisensor IQ8Quad with integrated sounder
Approval:
Approval:
Technical Data
Quiescent current @ 19 V DC approx. 80 A
Load factor 2
Sound level max. 92 dB (A), +/- 2 db (A) @ 1m for DIN tone
Detector specification EN54-7, EN 54-17
Technical Data
Quiescent current @ 19 V DC approx. 80 A
Quiescent current @ FACP battery approx. 450 A
Load factor 2
Sound level max. 92 dB (A), +/- 2 db (A) @ 1m for DIN tone
Specification EN 54-3 acoustic signalling device
Not suitable for application in relay base 805591!
Not suitable for application in relay base 805591!

1
2
3
4
5
6
7
8
9
10
11
12
17
16
13
14
15
1
101
q8wn
q8vk
802386
802385
O
2
T/Sp multisensor IQ8Quad
O
2
T/FSp multisensor IQ8Quad
In addition to smoke detection with conventional OT multisensor technology, the detector
is provided with a built-in voice alarm device. It can be set to eight different levels.
In addition to smoke detection with the conventional OT multisensor technology, the
detector is provided with a built-in voice alarm device. It can be set to eight different levels.
Automatic Detectors Series IQ8Quad (Intelligent Addressable)
VdS
VdS
OT/Sp multisensor IQ8Quad with integrated sounder and speech
OT/FSp multisensor IQ8Quad with integrated flasher, sounder and speech
Approval:
Approval:
Programmed with 5 standard national languages (DE/GB/FR/ES/IT).
Programmed with 5 standard national languages (DE/GB/FR/ES/IT).
Technical Data
Quiescent current @ 19 V DC approx. 90 A
Quiescent current @ FACP battery approx. 500 A
Load factor 3
Sound level max. 92 dB (A), +/- 2 db (A) @ 1m for DIN tone
Specification EN 54-3 acoustic signalling device
EN 54-3 acoustic speech signalling device (Q2/2011)
Technical Data
Quiescent current @ 19 V DC approx. 90 A
Quiescent current @ FACP battery approx. 500 A
Load factor 3
Sound level max. 92 dB (A), +/- 2 db (A) @ 1m for DIN tone
Lighting energy ca. 3 J
Strength of light max. 15,8 cd peak / 2,63 cd effective
Signal flashing lamp red
Specification EN 54-3 acoustic signalling device
EN 54-3 acoustic speech signalling device (Q2/2011)
Not suitable for application in relay base 805591!
Not suitable for application in relay base 805591!

www.esser-systems.com 102
q8v/TW:9
q8v/TW::&
802385.SV98
802385.SV99
802385.N0
O
2
T/FSp multisensor detector IQ8Quad with composition of other
languages
O
2
T/FSp multisensor detector IQ8Quad as customized version
O
2
T/FSp multisensory IQ8Quad Nordic
As with 802385, but with an individual combination of national languages.
As 802385, but with individual text and/or sounds. The max. recording time per device is
169 seconds.
Automatic Detectors Series IQ8Quad (Intelligent Addressable)
VdS
VdS
OT/FSp multisensor IQ8Quad with integrated flasher, sounder and speech
OT/FSp multisensor IQ8Quad with integrated flasher, sounder and speech
Approval:
Approval:
Programmed with an individual combination of up to 5 national languages.
Programmed according to customer specifications.
When ordering, please note the "Ordering information for IQ8Quad and IQ8Alarm" printed in the
appendix.
Cancellations or returns are not possible.
Not suitable for application in relay base 805591!
When ordering, please note the "Ordering information for IQ8Quad and IQ8Alarm" printed in the
appendix.
Costs for the recording of customer-specific texts and/or tones can be obtained by request.
Cancellations or returns are not possible.
Not suitable for application in relay base 805591!

1
2
3
4
5
6
7
8
9
10
11
12
17
16
13
14
15
1
103
q8vk
802385.F0 O
2
T/FSp multisensor IQ8Quad
In addition to smoke detection with the conventional OT multisensor technology, the
detector is provided with a built-in voice alarm device. It can be set to eight different levels.
Automatic Detectors Series IQ8Quad (Intelligent Addressable)
VdS
OT/FSp multisensor IQ8Quad with integrated flasher, sounder and speech
Approval:
Programmed with 5 standard national languages (DE/GB/FR/ES/IT).
Technical Data
Quiescent current @ 19 V DC approx. 90 A
Quiescent current @ FACP battery approx. 500 A
Load factor 3
Sound level max. 92 dB (A), +/- 2 db (A) @ 1m for DIN tone
Lighting energy ca. 3 J
Strength of light max. 15,8 cd peak / 2,63 cd effective
Signal flashing lamp red
Detector specification EN 54-7, EN54-17
Specification acoustic signalling device EN 54-3
acoustic signalling device EN 54-3
Not suitable for application in relay base 805591!

www.esser-systems.com 104

S-ar putea să vă placă și