Instrument Transformer Dimensioning, Page 1
Measuring CTs should work properly within the rated current range (< 2 x In)
measurement range
additional ordering information none ext. 120 % ext. 150 % ext. 200 %
standard
Power Technogies
Instrument Transformer Dimensioning, Page 2
Seite 1
accuracy class
centiradians
20 0.24 0.45 1.35 2.7 100 0.15 0.3 0.9 1.8 120 0.15 0.3 0.9 1.8
Power Technogies
Instrument Transformer Dimensioning, Page 3
accuracy class
%
1 5 0.35 0.75 20 0.2 0.5 100 0.2 0.5 120 0.2 0.5 1 30 90 5 15 45
minutes
20 10 30 100 10 30 120 10 30 0.9 2.7 5 0.45 1.35
centiradians
20 0.3 0.9 100 0.3 0.9 120 0.3 0.9
0.2S 0.5S
0.75 1.5
Note: This table is applicable only to transformers having a rated secondary current of 5A.
Power Technogies
Instrument Transformer Dimensioning, Page 4
Seite 2
Measurement ranges: 1 - 1.33 - 1.5 - 2 - 3 - 4 x In 1.0 x In 1.5 x In ... - without special indication - factor 1.5 at indication of rated current
the specification of an accuracy limiting factor is unusual Indication of power ratings: B 0.1 - B 0.2 - B 0.5 - B 0.9 - B 1.8 The rated power is not indicated directly. Instead of that the impedance of the rated burden is mentioned on the name plate. The rated burden is always related to a secondary current of 5 Amps. B 0.5 rated burden = 0.5 Ohm rated power = 25 x 0.5 = 12.5 VA
Power Technogies
Instrument Transformer Dimensioning, Page 5
range of overcurrent
Under overcurrent conditions the downstream measurement devices should be protected against impermissible thermal overloadings With rated burden (cos = 0.8) and rated factor of security (FS) the composite error has to result to 10% at least to the CT is under saturated condition
Power Technogies
Instrument Transformer Dimensioning, Page 6
Seite 3
Protection CT
range of rated current
range of overcurrent
range of overcurrent
Power Technogies
Instrument Transformer Dimensioning, Page 7
Power Technogies
Instrument Transformer Dimensioning, Page 8
Seite 4
Measuring CTs should be dimensioned that the connected burden including the
connecting cables is not exceeding the rated CT-burden.
Power Technogies
Instrument Transformer Dimensioning, Page 9
There is also the classes S FS. The accuracy is also specified at 0.001 In (only for 5 Amps secondary current) e.g.
100/ 5 20 VA -cl.
0.5S
FS 5
Power Technogies
Instrument Transformer Dimensioning, Page 10