Split System Air Conditioners SkyAir NU-V1/Y1 Series Cooling Only [50Hz]
ED24-631A
3. Functions.................................................................................................5
3.1 NU Series .................................................................................................5
8. Electric Characteristics..........................................................................45
8.1 R18~26NUV1 / Y1..................................................................................45 8.2 R36~56NUV1 / Y1..................................................................................46
13.Installation .............................................................................................61
13.1 Indoor Unit..............................................................................................61 13.2 Outdoor Unit .........................................................................................103
14.Accessories.........................................................................................116
14.1 Indoor Unit............................................................................................116 14.2 Outdoor Unit .........................................................................................118
Table of Contents
ED24-631A
ii
Table of Contents
ED24-631A
18 18NU
36 36NU 36NU
42 42NU 42NU
48 48NU 48NU
51
56
36NU 36NU
42NU 42NU
48NU 48NU
51NU 51NU
56NU 56NU
18NU
21NU
External Appearance
ED24-631A
1. External Appearance
Indoor Unit
FHC-NU
FH-NU
FDBG-NU
FDMG-NU
Outdoor Unit
R18NU
R21NU
R26NU
R36NU
R42NU
R48 51NU
R56NU
ED24-631A
Note:
ED24-631A
2.2
Nomenclature
Indoor Unit
FDM
18
NU
V1
Power Supply Symbol V1 : 1 phase 220~240V 50Hz Indicates Major Design Category Capacity Indication DIT Products FHC : Ceiling Mounted Cassette Type -Multi FlowFH : Ceiling Suspended Type FDB : Duct Connection Low Static Pressure Type (Cooling Only) FDM : Duct Connection Middle Static Pressure Type (Cooling Only)
Outdoor Unit
18
NU
V1
Power Supply Symbol V1 : 1 phase 220~240V 50Hz Y1 : 3 phase 380~415V 50Hz Indicates Major Design Category Capacity Indication Outdoor Unit R : Cooling Only
ED24-631A
Functions
3. Functions
3.1
FHC-NU
Item Feature Auto swing Swing pattern selection Switchable fan speed Program "Dry" High ceiling application Wired type Two selectable thermo-sensors Wireless type Timer selector Mold resistant treatment for filter Drain water lift-up mechanism Pre-charged for up to 10 m Pre-charged for up to 15 m Long-life filter Filter sign Ceiling soiling prevention Auto-restart Ultra long-life filter High-efficiency filter Fresh air intake kit PE fin for outdoor unit Ceiling Mounted Casssete Type (FHC) { { { { { { { { { { (18~26) { (36~48) { { { { { { { {
NU Series
Comfort
Mildew prevention
FH-NU
Item Comfort Feature Auto swing Switchable fan speed Program "Dry" Timer selector Mold resistant treatment for filter Mildew-proofing drain pan Pre-charged for up to 10 m Pre-charged for up to 15 m Long-life filter Auto-restart PE fin for outdoor unit Ceiling Suspended Type (FH) { { { { { { { (21 26) { (36~48) { { {
FDBG-NU
Item Comfort Work & servicing Control features Others Feature Switchable fan speed Pre-charged for up to 10 m Auto-restart PE fin for outdoor unit Adjustable external static pressure Duct Connection Low Static Pressure Type (FDBG) { { (18~26) { { {
FDMG-NU
Item Comfort Work & servicing Control features Others Feature Switchable fan speed Pre-charged for up to 10 m Pre-charged for up to 15 m Auto-restart PE fin for outdoor unit Adjustable external static pressure Duct Connection Middle Static Pressure Type (FDMG) { { (26) { (36~51) { { {
Specifications
ED24-631A
4. Specifications
FHC (Ceiling Mounted Cassette Type)
Indoor Unit Model Outdoor Unit V1 Y1 Btu/h kW kcal/h mm FHC21NUV1 FHC26NUV1 R21NUV1 R26NUV1 R26NUY1 21,200/21,000 26,300/26,000 6.2/6.2 7.7/7.6 5,340/5,290 6,630/6,550 FHC21NUV1 FHC26NUV1 230840840 230840840 Cross Fin Coil 281.5 281.5 281.5 0.331 0.331 0.331 QTS45B14M QTS45B14M QTS45B14M Turbo Fan 45 45 45 (H) 15 (L) 11 (H) 19 (L) 14 (H) 19 (L) 14 24 24 24 6.4 (Flare) 6.4 (Flare) 9.5 (Flare) 15.9 (Flare) 15.9 (Flare) 15.9 (Flare) I.D.25 O.D.32 I.D.25 O.D.32 I.D.25 O.D.32 BRC1C61 3 BRC7C613W BYC125KW1 BYC125KW1 BYC125KW1 White 40950950 40950950 40950950 Resin Net (with Mold Resistant) 5 5 5 R18NUV1 R21NUV1 R26NUV1 R26NUY1 Ivory White Ivory 540750270 685800300 770900320 Cross Fin Coil 2222.0 2282.0 2342.0 0.372 0.465 0.634 RC70AV1TRT NH41VMDT NH52VNHT NH52YDTT Hermetically Sealed Rotary Type 1.7 2.2 2.5 PZ380 PZ430 P47L11S Propeller 45 53 90 27 40 59 42 61 70 69 6.4 (Flare) 6.4 (Flare) 9.5 (Flare) 15.9 (Flare) 15.9 (Flare) 15.9 (Flare) 18.0 (Hole) 18.0 (Hole) 26.0 (Hole) Thermal Protector for Compressor, Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor. Outdoor Fan Motor and Indoor Fan Internal Protector of Compressor. Reverse Phase Protector (Y1). Fuse. Motor. Fuse. 1000 1000 1000 Capillary Tube 30 (Equivalent Length 50m) 30 (Equivalent Length 50m) 30 (Equivalent Length 50m) 15 15 20 R-22 R-22 R-22 1.20 (Charged for 10m) 1.50 (Charged for 10m) 2.3 (Charged for 10m) Refer to the name plate of compressor. 0.85 1.20 1.3 C : 4D054418A C : 4D054286A FHC18NUV1 R18NUV1 18,100/18,000 5.3/5.3 4,580/4,560 FHC18NUV1 230840840
Fan
HWD Type RowStagesFin Pitch Face Area Model Type Motor Output Air Flow Rate Liquid Gas Drain Wired Wireless
W m/min kg mm mm mm
mm kg V1 Y1 mm
Comp.
m V1 Y1 kW
Fan
Type Motor Output Model Type Motor Output Air Flow Rate kg Liquid Gas Drain
W m/min V1 Y1 mm mm mm
Capacity Step Refrigerant Control Max. Length Ref. Piping Max. Height Difference Model Refrigerant Charge (Factory Charge) Model Ref. Oil Charge Drawing No.
% m m kg L
Note:
1. The above data are based on the following conditions. Cooling (1) (2) Indoor: 27CDB, 19.5CWB Outdoor: 35CDB, 24CWB Indoor: 27CDB, 19.0CWB Outdoor: 35CDB, 24CWB Equivalent Piping Length 7.5m (Horizontal) 7.5m (Horizontal) Hz, Volts 50Hz, 220V (380V) 50Hz, 220V (380V)
2. Capacities are net, including a deduction for cooling for indoor fan motor heat. 3. Wire for remote controller : Field supplied.
ED24-631A
Specifications
Fan
HWD Type RowStagesFin Pitch Face Area Model Type Motor Output Air Flow Rate Liquid Gas Drain Wired Wireless
W m/min kg mm mm mm
mm kg V1 Y1 mm
Comp.
m V1 Y1 kW
Fan
Type Motor Output Model Type Motor Output Air Flow Rate kg Liquid Gas Drain
W m/min V1 Y1 mm mm mm
Capacity Step Refrigerant Control Max. Length Ref. Piping Max. Height Difference Model Refrigerant Charge (Factory Charge) Model Ref. Oil Charge Drawing No.
% m m kg L
Note:
1. The above data are based on the following conditions. Cooling (1) (2) Indoor: 27CDB, 19.5CWB Outdoor: 35CDB, 24CWB Indoor: 27CDB, 19.0CWB Outdoor: 35CDB, 24CWB Equivalent Piping Length 7.5m (Horizontal) 7.5m (Horizontal) Hz, Volts 50Hz, 220V (380V) 50Hz, 220V (380V)
2. Capacities are net, including a deduction for cooling for indoor fan motor heat. 3. Wire for remote controller : Field supplied.
Specifications
ED24-631A
Fan
HWD Type RowStagesFin Pitch Face Area Model Type Motor Output Air Flow Rate 3
mm
W m/min kg mm mm mm
Air Filter Mass (Weight) Piping Connections Liquid Gas Drain Wired Wireless
Comp.
m V1 Y1 kW
Fan
Type Motor Output Model Type Motor Output Air Flow Rate kg Liquid Gas Drain
W m/min V1 Y1 mm mm mm
Safety Devices Capacity Step Refrigerant Control Ref. Piping Refrigerant Ref. Oil Drawing No. Max. Length Max. Height Difference Model Charge (Factory Charge) Model Charge % m m kg L
Note:
1. The above data are based on the following conditions. Cooling (1) (2) Indoor: 27CDB, 19.5CWB Outdoor: 35CDB, 24CWB Indoor: 27CDB, 19.0CWB Outdoor: 35CDB, 24CWB Equivalent Piping Length 7.5m (Horizontal) 7.5m (Horizontal) Hz, Volts 50Hz, 220V (380V) 50Hz, 220V (380V)
2. Capacities are net, including a deduction for cooling for indoor fan motor heat. 3. AFR (Air flow rate) is shown at 220~240V (380~415V). 4. Wire for remote controller : Field supplied.
ED24-631A
Specifications
HWD Type RowStagesFin Pitch Face Area Type Motor Output Air Flow Rate 3 Liquid Gas Drain Wired Wireless
m W m/min kg mm mm mm
Comp.
m V1 Y1 kW
Fan
Type Motor Output Model Type Motor Output Air Flow Rate kg Liquid Gas Drain
W m/min V1 Y1 mm mm mm
Capacity Step Refrigerant Control Max. Length Ref. Piping Max. Height Difference Model Refrigerant Charge (Factory Charge) Model Ref. Oil Charge Drawing No.
% m m kg L
Note:
1. The above data are based on the following conditions. Cooling (1) (2) Indoor: 27C(81F)DB, 19.5C(67F)WB Outdoor: 35C(95F)DB, 24C(75F)WB Indoor: 27C(81F)DB, 19.0C(66F)WB Outdoor: 35C(95F)DB, 24C(75F)WB Equivalent Piping Length 7.5m (Horizontal) 7.5m (Horizontal) Hz, Volts 50Hz, 220V (380V) 50Hz, 220V (380V)
2. Capacities are net, including a deduction for cooling for indoor fan motor heat. 3. Refer to "11. Fan Performance" in detail.
Specifications
ED24-631A
Fan
HWD Type RowStagesFin Pitch Face Area Type Motor Output Air Flow Rate 3 Rated Ext. Static Pressure 3 Liquid Gas Drain Wired Wireless
m W m/min mmH2O kg mm mm mm
Comp.
m V1 Y1 kW
Fan
Type Motor Output Model Type Motor Output Air Flow Rate kg Liquid Gas Drain
W m/min V1 Y1 mm mm mm
Safety Devices Capacity Step Refrigerant Control Max. Length Ref. Piping Max. Height Difference Model Refrigerant Charge (Factory Charge) Model Ref. Oil Charge Drawing No. % m m kg L
Note:
1. The above data are based on the following conditions. Cooling (1) (2) Indoor: 27C(81F)DB, 19.5C(67F)WB Outdoor: 35C(95F)DB, 24C(75F)WB Indoor: 27C(81F)DB, 19.0C(66F)WB Outdoor: 35C(95F)DB, 24C(75F)WB Equivalent Piping Length 7.5m (Horizontal) 7.5m (Horizontal) Hz, Volts 50Hz, 220V (380V) 50Hz, 220V (380V)
2. Capacities are net, including a deduction for cooling for indoor fan motor heat. 3. Refer to "11. Fan Performance" in detail.
10
ED24-631A
Specifications
Fan
HWD Type RowStagesFin Pitch Face Area Type Motor Output Air Flow Rate 3 Rated Ext. Static Pressure 3 Liquid Gas Drain Wired Wireless
m W m/min mmH2O kg mm mm mm
Outdoor Unit Color Dimensions HWD Type Coil RowStagesFin Pitch Face Area Model Comp. Type Motor Output Model Type Fan Motor Output Air Flow Rate Mass (Weight) Liquid Piping Gas Connections Drain Safety Devices Capacity Step Refrigerant Control Max. Length Ref. Piping Max. Height Difference Model Refrigerant Charge (Factory Charge) Model Ref. Oil Charge Drawing No.
mm
kW
W m/min kg mm mm mm
% m m kg L
Note:
1. The above data are based on the following conditions. Cooling (1) (2) Indoor: 27C(81F)DB, 19.5C(67F)WB Outdoor: 35C(95F)DB, 24C(75F)WB Indoor: 27C(81F)DB, 19.0C(66F)WB Outdoor: 35C(95F)DB, 24C(75F)WB Equivalent Piping Length 7.5m (Horizontal) 7.5m (Horizontal) Hz, Volts 50Hz, 220V (380V) 50Hz, 220V (380V)
2. Capacities are net, including a deduction for cooling for indoor fan motor heat. 3. Refer to "11. Fan Performance" in detail.
11
ED24-631A
Indoor Unit
FHC (Ceiling Mounted Cassette Type)
Unit (mm)
4. When the temperature and humidity in the ceiling exceed 30C and RH 80% or the fresh air is inducted into the ceiling or the unit continues 24 hour operation, an additional insulation (thickness 10mm or more of glasswool or polyethylene form) is required.
C : 3D054367
FHC26NU + BYC125K-W1
Unit (mm)
4. When the temperature and humidity in the ceiling exceed 30C and RH 80% or the fresh air is inducted into the ceiling or the unit continues 24 hour operation, an additional insulation (thickness 10mm or more of glasswool or polyethylene form) is required.
C : 3D054368
12
ED24-631A
Unit (mm)
4. When the temperature and humidity in the ceiling exceed 30C and RH 80% or the fresh air is inducted into the ceiling or the unit continues 24 hour operation, an additional insulation (thickness 10mm or more of glasswool or polyethylene form) is required.
C : 3D052528
5.1.2
Unit (mm)
290
6 5 4 3 2 1 Number
Drain pipe connection Gas pipe connection Liquid pipe connection High efficiency filter Decoration panel Indoor unit Description Name JC : 3D032975C
13
ED24-631A
Unit (mm)
6 5 4 3 2 1 Number
Drain pipe connection Gas pipe connection Liquid pipe connection High efficiency filter Decoration panel Indoor unit Description Name J : 3D032976C
5.1.3
FHC with Fresh Air Intake Kit (Without T Joint, Duct Fan)
Unit (mm)
View
Service Access Panel : 450450mm or more Refer to Note 2
Note 4
Connection Chamber (Right) Note:1.When installing this kit, Service Access Panel is necessary. (It is necessary when servicing.) 2.Either one of Service Access Panel must be installed. 3.Field construction. 4.In case of using wireless remote controller kit, this part will be the infrared receiver. 5.When both side intakes can not be ensured due to the obstacles, one side intake is acceptable. 6.When installing the wireless infrared reciever to the unit, air inlet must be on the right side as shown. How to connect Chamber 4 Independently(Refer to Note 5,6)
5 4 3 2 1 Number
Connection chamber(Left) Connection chamber(Right) Suction chamber Decoration panel Indoor unit Description Name JC : 3D032981D
14
ED24-631A
Unit (mm)
Refrigerant Piping
View
Note 4
Connection Chamber (Right) How to connect Chamber 4 Independently(Refer to Note 5,6) Note:1.When installing this kit, Service Access Panel is necessary. (It is necessary when servicing.) 2.Either one of Service Access Panel must be installed. 3.Field construction. 4.In case of using wireless remote controller kit, this part will be the infrared receiver. 5.When both side intakes can not be ensured due to the obstacles, one side intake is acceptable. 6.When installing the wireless infrared reciever to the unit, air inlet must be on the right side as shown.
5 4 3 2 1 Number
Connecting chamber(Left) Connecting chamber(Right) Suction chamber Decoration panel Indoor unit Description Name JC : 3D032984D
5.1.4
FHC with Fresh Air Intake Kit (With T Joint, Without Duct Fan)
Unit (mm)
Flexible Duct (Accessory)
Suction Duct (K-KFD9A) Optional (Accessory) T Joint Plate Band (Accessory) (Accessory)
JC : 3D032987D
15
ED24-631A
Unit (mm)
Flexible Duct (Accessory)
Connecting Chamber (Right) How to connect Chamber 4 Independently(Refer to Note 5) Note:1.When installing this kit, inspection hatch is necessary. (It is necessary when servicing.) 2.Either one of inspection hatch must be installed. 3.Field construction. 4.This kit does not take together with Wireless Remoto Controller kit. 5.When both side intakes can not be ensured due to the obstacles, one side intake is acceptable. 5 4 3 2 1 Number Connecting chamber(Left) Connecting chamber(Right) Suction chamber Decoration panel Indoor unit Description Name
J : 3D032990D
5.1.5
View
Note:When other optional kit is installed, refer to the installation drawing of its optional kit
Dimension between the bottom surface of box and the surface of ceiling
Description JC : 3D005390E
16
ED24-631A
Unit (mm)
View
Note:When other optional kit is installed, refer to the installation drawing of its optional kit
Dimension between the bottom surface of box and the surface of ceiling
Description JC : 3D005391D
5.1.6
FH21NU
Unit (mm)
3D054277
17
ED24-631A
FH26NU
Unit (mm)
3D027538F
Unit (mm)
3D052469
18
ED24-631A
5.1.7
FDBG18NU
Unit (mm)
3D048541A
FDBG21NU
Unit (mm)
3D048542A
19
ED24-631A
FDBG26NU
Unit (mm)
3D048543A
5.1.8
FDMG26NU
Unit (mm)
3D048933B
20
ED24-631A
Unit (mm)
3D048934B
FDMG51NU FDMG56NU
Unit (mm)
3D048935B
21
ED24-631A
5.2
Unit (mm)
3D028952
Unit (mm)
3D052351
22
ED24-631A
2. Holder
23
ED24-631A
4. Wire Cable Cable length : 4m Connecting cable between 1. Digital Remote Controller and 3. Control Board (Box).
KRC47-4 (Digital Remote Controller for Duct Heater Use) (for FDBG-NU and FDMG-NU)
1. Digital Remote Controller
HEAT
COOL
POWER TEMP +
FAN TEMP -
For other parts 2. Holder, 3. Control Board (Box), 4. Wire Cable will be the same as KRC 47-2.
(P0007)
24
ED24-631A
5.3
Unit (mm)
3D005912D
Unit (mm)
3D052347
25
ED24-631A
5.4
R18NU
Outdoor Unit
Unit (mm)
3D053564
R21NU
Unit (mm)
3D053561
26
ED24-631A
R26NU
Unit (mm)
3D054206
R36NU
Unit (mm)
3D052425
27
ED24-631A
R42NU
Unit (mm)
3D052426
R48NU R51NU
Unit (mm)
3D052427
28
ED24-631A
R56NU
Unit (mm)
C : 3D052527
29
ED24-631A
5.5
3D052620A
30
ED24-631A
3D052620A
31
Piping Diagrams
ED24-631A
6. Piping Diagrams
R18 21NU
4D050891B
R26NU
3D053984
32
ED24-631A
Piping Diagrams
R36~56NU
3D052278
33
Wiring Diagrams
ED24-631A
7. Wiring Diagrams
7.1 Indoor Unit
FHC18NUV1 FHC21NUV1 FHC26NUV1 FHC36NUV1 FHC42NUV1 FHC48NUV1
3D052066A
34
ED24-631A
Wiring Diagrams
3D052046A
35
Wiring Diagrams
ED24-631A
3D046565A
36
ED24-631A
Wiring Diagrams
3D052109A
37
Wiring Diagrams
ED24-631A
7.2
Remote Controller
KRC47-1
TEMPERATURE CONTROL
OFF
ON
P2
P3
P4
P1
P2
P3
P4
P5
P6
FDBG FDMG
D Comp. (THERMOSTAT)
A H
B M FAN
C L
E (ON/OFF) L
F N
(P0008-631A)
KRC47-2
REMOTE CONTROLLER
THERMISTOR
CONTROL BOARD P8 P9
P3
P2
P1
P4
P3
P2
P1
P7
FDBG FDMG
F N
E L (ON/OFF)
A H
B M FAN
C L
D Comp. (THERMOSTAT)
(P0009-631A)
38
ED24-631A
Wiring Diagrams
KRC47-4
REMOTE CONTROLLER
THERMISTOR
CONTROL BOARD P8 P9
P3
P2
P1
P4
P3
P2
P1
P7
P6
FDBG FDMG
F N
E L (ON/OFF)
A H
B M
C L
FAN
(P0010-631A)
39
Wiring Diagrams
ED24-631A
7.3
Outdoor Unit
R18NUV1
3D032199B
R21NUV1
3D032200A
40
ED24-631A
Wiring Diagrams
R26NUV1
3D053671A
R26NUY1
3D053670A
41
Wiring Diagrams
ED24-631A
R36NUV1
3D051564A
R36NUY1
3D051536A
42
ED24-631A
Wiring Diagrams
3D051535A
R56NUY1
3D052107
43
Wiring Diagrams
ED24-631A
7.4
Field Wiring
C : 4D054220 C : 4D052570
44
ED24-631A
Electric Characteristics
8. Electric Characteristics
8.1 R18~26NUV1 / Y1
3D054360A 3D054365A
45
Electric Characteristics
ED24-631A
8.2
R36~56NUV1 / Y1
46
ED24-631A
Capacity Tables
9. Capacity Tables
9.1 Capacity Tables
FHC18NUV1 / FDBG18NUV1 + R18NUV1
3D054363A
3D054364A
47
Capacity Tables
ED24-631A
FHC26NUV1 / FH26NUV1 / FDBG26NUV1 / FDMG26NUV1 + R26NUV1 FHC26NUV1 / FH26NUV1 / FDBG26NUV1 / FDMG26NUV1 + R26NUY1
3D054484A
3D052745A
48
ED24-631A
Capacity Tables
3D052746A
3D052747A
49
Capacity Tables
ED24-631A
FDMG51NUV1 + R51NUY1
3D052751A
FDMG56NUV1 + R56NUY1
3D052754A
50
ED24-631A
Capacity Tables
9.2
3D052761A
51
Operation Limit
ED24-631A
3D049550B
52
ED24-631A
Fan Performance
3D048561A
FDBG21NU FDBG26NU
3D048562A
53
Fan Performance
ED24-631A
11.2
FDMG-NU
FDMG26NU
4D049493A
FDMG36NU
4D049488A
54
ED24-631A
Fan Performance
FDMG42NU FDMG48NU
4D049489A
FDMG51NU FDMG56NU
4D049490A
55
Sound Level
ED24-631A
FHC-NU
45 40 42 42 39 40 40 40 39 39
4D049441A
FDBG-NU
4D054358
FDMG-NU
Note:
Operation sound is measured in an anechoic chamber. Sound level will vary depending on a range of factors such as the construction (acoustic absorption coefficient) of the particular room in which the equipment installed.
56
ED24-631A
Sound Level
R21NUV1
54
55
R26NUV1
57
57
4D054355
55 380 V 57
56 415 V 57
R26~51NU
R36NUY1
55
56
4D054333
R42NUY1
57
58
R56NU
R48NUY1
59
60
R51NUY1
59
60
4D049423B
R56NUY1
56
58
Note:
Operation sound is measured in an anechoic chamber. Sound level will vary depending on a range of factors such as the construction (acoustic absorption coefficient) of the particular room in which the equipment installed.
57
Sound Level
ED24-631A
12.2
FHC18NUV1
4D054296
4D054293
4D052541A
FH21NUV1 FH26NUV1
FH36NUV1
FH42NUV1
4D054245
4D052455
4D052456
FH48NUV1
4D052458
58
ED24-631A
Sound Level
FDBG18NUV1
FDBG21NUV1 FDBG26NUV1
FDMG26NUV1
4D054358
4D054357A
4D049441A
FDMG36NUV1
FDMG42NUV1 FDMG48NUV1
FDMG51NUV1 FDMG56NUV1
4D049427B
4D049431B
4D049433B
59
Sound Level
ED24-631A
4D054355
4D054356
4D054333
R36NUV1 R36NUY1
R42NUY1
R48NUY1 R51NUY1
4D052428
4D052429
4D052430
R56NUY1
4D049423B
60
ED24-631A
Installation
13. Installation
13.1 Indoor Unit
13.1.1 FHC-NUV1
k a
j i h f g d e b d c e f R18 21 26 36
R42 48
a Indoor unit b c d e Outdoor unit Remote controller Inlet air Discharged air
i j
Drain pipe Air inlet The built-in air filter removes dust and dirt.
f Air outlet g Air flow flap (at air outlet) h Refrigerant piping, connection electric wire
Drain pumping out device(built-in) k Drains water removed from the room during cooling. l Ground wire Wire to ground from the outdoor unit to prevent electrical shocks.
3PN07217-2A
61
Installation
ED24-631A
3PN07218-2B-5
62
ED24-631A
Installation
3PN07218-2B-6
63
Installation
ED24-631A
3PN07218-2B-7
64
ED24-631A
Installation
3PN07218-2B-8
65
Installation
ED24-631A
3PN07218-2B-9
66
ED24-631A
Installation
3PN07218-2B-10
67
Installation
ED24-631A
3PN07218-2B-11
68
ED24-631A
Installation
3PN07218-2B-12
69
Installation
ED24-631A
3PN07218-2B-13
70
ED24-631A
Installation
C : 3PN07218-2B-14
71
Installation
ED24-631A
3PN07218-2B-15
72
ED24-631A
Installation
3PN07218-2B-16
73
Installation
ED24-631A
3PN07218-2B-17
74
ED24-631A
Installation
3PN07218-2B-18
75
Installation
ED24-631A
3PN07218-2B-19
76
ED24-631A
Installation
3PN07218-2B-20
77
Installation
ED24-631A
3PN07218-2B-21
78
ED24-631A
Installation
3PN07218-2B-22
79
Installation
ED24-631A
3PN07218-2B-23
80
ED24-631A
Installation
13.1.2 FH-NUV1
f e e
g d j b d c e f d h
a b c d e f g h i j k
Indoor unit Outdoor unit Remote controller Inlet air Discharged air Air outlet Air flow flap (at air outlet) Refrigerant piping, connection electric wire Drain pipe Air inlet The built-in air filter removes dust and dirt. Ground wire Wire to ground from the outdoor unit to prevent electrical shocks.
3PN07087-1A
81
Installation
ED24-631A
1PN07240B
82
ED24-631A
Installation
1PN07240B
83
Installation
ED24-631A
1PN07240B
84
ED24-631A
Installation
1PN07240B
85
Installation
ED24-631A
1PN07240B
86
ED24-631A
Installation
1PN07240B
87
Installation
ED24-631A
1PN07241A
88
ED24-631A
Installation
1PN07241A
89
Installation
ED24-631A
1PN07241A
90
ED24-631A
Installation
1PN07241A
91
Installation
ED24-631A
1PN07241A
92
ED24-631A
Installation
13.1.3 FDBG-NUV1
1PN07524
93
Installation
ED24-631A
1PN07524
94
ED24-631A
Installation
1PN07524
95
Installation
ED24-631A
1PN07524
96
ED24-631A
Installation
1PN07524
97
Installation
ED24-631A
13.1.4 FDMG-NUV1
1PN06319D
98
ED24-631A
Installation
1PN06319D
99
Installation
ED24-631A
1PN06319D
100
ED24-631A
Installation
1PN06319D
101
Installation
ED24-631A
1PN06319D
102
ED24-631A
Installation
13.2
Outdoor Unit
1PN07605
103
Installation
ED24-631A
1PN07605
104
ED24-631A
Installation
1PN07605
105
Installation
ED24-631A
1PN07605
106
ED24-631A
Installation
1PN07605
107
Installation
ED24-631A
13.2.2 R26~56NUV1/Y1
1PN07127A
1PN07128B
108
ED24-631A
Installation
1PN07128B
109
Installation
ED24-631A
1PN07128B
110
ED24-631A
Installation
1PN07128B
111
Installation
ED24-631A
1PN07128B
112
ED24-631A
Installation
1PN07128B
113
Installation
ED24-631A
1PN07128B
114
ED24-631A
Installation
1PN07128B
115
Accessories
ED24-631A
14. Accessories
14.1 Indoor Unit
14.1.1 FHC-NU
Standard Accessories
3PN07218-2B-3
Optional Accessories
Name of Option Decoration Panel Sealing Member of Air Discharge Outlet Panel Spacer Fresh Air Intake Kit 3
Remark
Kit Name FHC18~26NU FHC36~48NU BYC125KW1 KDBHJ55K160 KDBP55H160WA KDDP55D160 KDDP55D160K KDDJ55X160 KKSJ55K160 KAFP556D80 KAFP557D80 KAFP552H80 KAFP553H80 KAFP556D160 KAFP557D160 KAFP552H160 KAFP553H160
Chamber Connection Kit 4 HighEfficiency Filter (Colorimetric Method 65%) (Colorimetric Method 90%) Replacement HighEfficiency (Colorimetric Method 65%) Filter (Colorimetric Method 90%) HighEfficiency Filter Chamber Replacement LongLife Filter Resin Net (Gravimetric Method 50%) Ultra LongLife Filter Replacement Ultra LongLife Filter Branch Duct Chamber Remote Controller Wired Type 2 Wireless Type Wired LCD Remote Controller with Weekly Schedule Timer Central Remote Controller Unified ON/OFF Controller Schedule Timer intelligent Touch Controller Adaptor for Wiring (Interlock for Fresh Air Intake Fan) 1 Wiring Adaptor for Electrical Appendices 1 Interface Adaptor for SkyAir Series Installation Box for Adaptor PCB
KDDFP55D160 KAFJ551K160 KAFP55D160 KAFJ55K160H KDJ55K80 KDJ55K160 BRC1C61 BRC7C613W BRC1D61 DCS302CA61 DCS301BA61 DST301BA61 DCS601C51 KRP1B57 KRP4A53 DTA102A52 KRP1B98
C : 3D054362 C : 3D052565
Note:
1. Installation box for adaptor PCB (KRP1B98) is necessary. 2. Wire for remote controller : Field supplied. 3. Refer to the Option Handbook for the detail. 4. When using the filter (HighEfficiency Filter or Ultra LongLife Filter) and the Fresh Air Intake Kit together, this kit is necessary.
116
ED24-631A
Accessories
14.1.2 FH-NU
Standard Accessories
1PN07240B
Optional Accessories
Name of Option Replacement LongLife Filter LType Piping Kit Remote Controller For Upward Direction Wired Type 1 Wireless Type Remark Kit Name FH21 26NU KAFJ501D80 KHFJ5F80 BRC1NU61 BRC7NU66
3D054225 3D052467
Note:
14.1.3 FDBG-NU
Standard Accessories
1PN07524
Optional Accessories
Name of Option Remark Kit Name FDBG18NU KRC47-1 KRC47-2 KRC47-4 KDGF19A45 KKD19A1
4D048550A
FDBG21 26NU
Remote Controller with 3 Minutes Timer Digital Remote Controller with 3 Minutes Timer Digital Remote Controller With Switch for Duct Heater with 3 Minutes Timer Suction Grille Drain Pan Cover
KDGF19A71
Note:
1. If you use local remote controller, 3 minutes timer is necessary for the recycling guard of compressor. 2. Central controls using with VRV controller are available on request. Please consult DAIKIN.
117
Accessories
ED24-631A
14.1.4 FDMG-NU
Standard Accessories
1PN06319D
Optional Accessories
Name of Option Remark Kit Name FDMG26~56NU KRC47-1 KRC47-2 KRC47-4
4D054400 4D052569
Remote Controller with 3 Minutes Timer Digital Remote Controller with 3 Minutes Timer Digital Remote Controller With Switch for Duct Heater with 3 Minutes Timer
Note:
1. If you use local remote controller, 3 minutes timer is necessary for the recycling guard of compressor. 2. Central controls using with VRV controller are available on request. Please consult DAIKIN.
14.2
Outdoor Unit
14.2.1 R-NU
Optional Accessories
Drain Piping Kit Central Drain Plug
Name of Option
118
ED24-631A
Remote Controller
3 7 6 8 13 9 11 10 12 20 19 18
15
14
16
17
21
3PN07217-2A
119
Remote Controller
ED24-631A
3PN07204-2
120
ED24-631A
Remote Controller
Fig.1
Fig.2
C : 3PA63363-4P
121
Remote Controller
ED24-631A
3PN07204-1-4
122
ED24-631A
Remote Controller
3PN07204-1-5
123
ED24-631A
BEFORE INSTALLATION
PRECAUTIONS Refer also to the installation manual attached to the indoor unit. ACCESSORIES Installation manual. NOTE TO INSTALLER Be sure to instruct the customer how to properly operate the system showing him/her the attached operation manual.
45 Lever
Fig. 1 (2) Remove the service cover on the corner. Slide the service cover outward to remove. (Refer to Fig. 3.) Fig. 2
Fig. 3
124
ED24-631A
Air outlet
Decoration panel
Hook
Latch
1)
2) Piping position
2)
4)
Fig. 4 PRECAUTIONS Improper screwing of the screws may cause the troubles shown in Fig. 5. Screw properly. Air leak
Contamination
125
ED24-631A
If gap is still left between the ceiling and the decoration panel after screwing the screws, readjust the indoor unit body height. (Refer to Fig. 6.)
Adjustment of the indoor unit body height from the holes in the corner of the decoration panel is possible if the indoor unit is kept leveled and the drain piping, etc. is unaffected.
No gaps is allowed. Fig. 6 (3) Wiring of the decoration panel (Refer to Fig. 7.) 6) Connect the connectors for swing flap motor lead wire installed on the decoration panel. If connectors are not connected, the malfunction display (A7) appears on the remote controller. Connect the connectors properly. Make sure that the swing flap motor lead wire is not caught between the indoor unit and the decoration panel.
6)
Indoor unit side Decoration panel side
Wiring
Fig. 7
Install the service cover by sliding 4 latches to fit into the holes on the decoration panel.
Fig. 8
126
ED24-631A
2 pieces
1 piece
5 kinds
J : 1P012222B
127
ED24-631A
(1) Installation to the side plate Adhere insulation for side plate
26 class
When adhering insulation, align its edge with the bottom line of casing.
When adhering insulation, align its edge with the bottom line of casing.
(2) Installation to the top plate Adhere insulation for top plate
(3) Adhere the moisture absorber for horizontal vane to the edge of the horizontal vane of air outlet (Fig. 2). (Choose the same color as panel.)
Horizontal vane Moisture absorber for horizontal vane Fig. 2
Fig. 1
(4) Adhere the moisture absorber in accordance with the reference surface without wrinkles. (Fig. 4) Adhere the moisture absorber in accordance with the reference line . (Fig. 5)
Reference surface Adhere it from the edge of switch box. Switch box Swing connector Swing motor Sticking reference (Fig. 3)
Bellmouth
128
ED24-631A
1P136564E
129
ED24-631A
1P136564E
130
ED24-631A
SkyAir
FHC18~48NU
18~26NU 36~48NU
240 298
C : 3K011144A
131
ED24-631A
3K011144A
132
ED24-631A
133
ED24-631A
Dimension
J : D3K2175
Installation
2P066796C
134
ED24-631A
2P066796C
135
ED24-631A
16.1.6 KAFP556D80 160 HighEfficiency Filter (Including Filter Chamber) KAFP557D80 160 HighEfficiency Filter (Including Filter Chamber)
Combination table
HighEfficiency Filter (Set) KAFP556D80 KAFP557D80 KAFP556D160 KAFP557D160 Replacement HighEfficiency Filter KAFP552H80 KAFP553H80 KAFP552H160 KAFP553H160 HighEfficiency Filter Chamber KDDFP55D160
16.1.7 KAFP552H80 160 Replacement HighEfficiency Filter KAFP553H80 160 Replacement HighEfficiency Filter
Specifications
Replacement HighEfficiency Filter HighEfficiency Filter Chamber Collecting Efficiency (%) Initial Pressure Loss (Pa) Final Pressure Loss (Pa) Filter Life (h) Models to be Applied KAFP552H80 KAFP552H160 KAFP553H80 KAFP553H160 KDDFP55D160 65% (NBS Colorimetric method) 90% (NBS Colorimetric method) 34 or less 98 or less Nonwoven Fabric of Synthetic Fiber Nonwoven Fabric of Synthetic Fiber 2,500 h (Dust Concentration 0.15 mg / m3) 1,800 h (Dust Concentration 0.15 mg / m3) 18~26NU 36~48NU 18~26NU 36~48NU
Precaution at use 1. The highefficiency filter, and the other filter can not be installed together. 2. The unit should be operated with 4-way discharge when the highefficiency filter is installed. It can not be applied to the high ceiling room. 3. Field setting by remote controller is necessary when the highefficiency filter is installed. Dimension
560
AA 25 45
J : D3K04256A
136
AA
D3K2169
10
0 540 -2
10
560
ED24-631A
SkyAir
FHC18~26NU
SkyAir
FHC36~48NU
C : 3K011148B
137
ED24-631A
3K011148B
138
ED24-631A
16.1.11 KAFP55D160, KAFJ55K160H (Replacement) Ultra LongLife Filter (Including Filter Chamber)
Specifications
Ultra LongLife Filter Replacement Ultra LongLife Filter HighEfficiency Filter Chamber Collecting Efficiency (%) Initial Pressure Loss (Pa) Final Pressure Loss (Pa) Filter Life (h) Models to Be Applied
Precaution at use 1. The Ultra longlife filter, and other filter can not be installed together. KDDFP55D160 2. Field setting by remote controller is necessary when the Ultra 50 (Gravity Method) long life filter is installed. 8 or less Refer to the installation manual of Ultra longlife filter for 49 or less setting. MildewProof Resin Net 3. Filter cleaning period can not be displayed on the monitor when 5,000 h the Ultra longlife filter is installed. (Dust Concentration 0.3 mg / m3) Refer to the left table and clean (with water) the filter 18~48NU periodically.
KAFJ55K160H
J : D3K2174A
KAFP55D160
Installation Iocation Filter Cleaning Period Dirty Area Not Dirty Area Every 5,000 hrs Every 10,000 hrs
139
ED24-631A
J : D3K2186
Installation
3P089651C
140
ED24-631A
141
ED24-631A
142
ED24-631A
16.2
KHFJ5F50~160
Installation
143
ED24-631A
16.3
FDBG182126NUV1
C : 1P067376A
144
ED24-631A
16.4
Outdoor Unit
Use this plug to connect a drain hose to an outdoor unit. Outlook KIS95
1. This is the joint for attaching a vinyl hose (field supplied). This is used between the drain hole which is on the bottom plate of outdoor unit and vinyl hose. 2. Drain water accumulate to the bottom of outdoor unit it depends on the situation of operation. But it is necessary to connect drain hose not to be spread the drain water over the neighbors, when it is installed on the wall. 3. The position of holes are unfit to connect with outdoor units in some models. In this case, use it without Y joint.
145
Warning
Daikin Industries, Ltd.s products are manufactured for export to numerous countries throughout the world. Daikin Industries, Ltd. does not have control over which products are exported to and used in a particular country. Prior to purchase, please therefore confirm with your local authorized importer, distributor and/or retailer whether this product conforms to the applicable standards, and is suitable for use, in the region where the product will be used. This statement does not purport to exclude, restrict or modify the application of any local legislation. Ask a qualified installer or contractor to install this product. Do not try to install the product yourself. Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion. Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or contractor to install those parts and accessories. Use of unauthorized parts and accessories or improper installation of parts and accessories can result in water or refrigerant leakage, electrical shock, fire or explosion. Read the User's Manual carefully before using this product. The User's Manual provides important safety instructions and warnings. Be sure to follow these instructions and warnings. If you have any inquiries, please contact your local importer, distributor and/or retailer.
JMI-0107
JQA-1452
EC99J2044
JQA-E-90108
Dealer
Head Office: Umeda Center Bldg., 2-4-12, Nakazaki-Nishi, Kita-ku, Osaka, 530-8323 Japan Tokyo Office: JR Shinagawa East Bldg., 2-18-1, Konan, Minato-ku, Tokyo, 108-0075 Japan
http://www.daikin.com/global/
c All rights reserved
Specifications, designs and other content appearing in this brochure are current as of July 2006 but subject to change without notice.