Split System Air Conditioners SkyAir NU-V1/Y1 Series Cooling Only [50Hz]

ED24-631A

SkyAir NU Series Cooling Only [50Hz] .................................... 1


1. External Appearance...............................................................................2 2. Model Name, Power Supply and Nomenclature .....................................3
2.1 Model Name and Power Supply...............................................................3 2.2 Nomenclature ...........................................................................................4

3. Functions.................................................................................................5
3.1 NU Series .................................................................................................5

4. Specifications ..........................................................................................6 5. Dimensions and Service Space ............................................................12


5.1 5.2 5.3 5.4 5.5 Indoor Unit..............................................................................................12 Wired Remote Controller........................................................................22 Wireless Remote Controller ...................................................................25 Outdoor Unit ...........................................................................................26 Installation Service Space for R26~56NU ..............................................30

6. Piping Diagrams....................................................................................32 7. Wiring Diagrams....................................................................................34


7.1 7.2 7.3 7.4 Indoor Unit..............................................................................................34 Remote Controller ..................................................................................38 Outdoor Unit ...........................................................................................40 Field Wiring ............................................................................................44

8. Electric Characteristics..........................................................................45
8.1 R18~26NUV1 / Y1..................................................................................45 8.2 R36~56NUV1 / Y1..................................................................................46

9. Capacity Tables ....................................................................................47


9.1 Capacity Tables......................................................................................47 9.2 Capacity Correction Factor by the Length of Refrigerant Piping ............51

10.Operation Limit......................................................................................52 11.Fan Performance ..................................................................................53


11.1 FDBG-NU ...............................................................................................53 11.2 FDMG-NU ..............................................................................................54

12.Sound Level ..........................................................................................56


12.1 Overall Sound Level ...............................................................................56 12.2 Octave Band Level .................................................................................58

13.Installation .............................................................................................61
13.1 Indoor Unit..............................................................................................61 13.2 Outdoor Unit .........................................................................................103

14.Accessories.........................................................................................116
14.1 Indoor Unit............................................................................................116 14.2 Outdoor Unit .........................................................................................118

15.Remote Controller ...............................................................................119


15.1 Operation..............................................................................................119

16.Detail Explanation of Options..............................................................124


16.1 16.2 16.3 16.4 Ceiling Mounted Cassette Type (Multi Flow) [FHC] .............................124 Ceiling Suspended Type [FH] ..............................................................143 Duct Connection Low Static Pressure Type [FDBG]............................144 Outdoor Unit .........................................................................................145

Table of Contents

ED24-631A

ii

Table of Contents

ED24-631A

SkyAir NU Series Cooling Only [50Hz]


Model Series
Class FHC FH Indoor Unit FDBG FDMG Outdoor Unit R 18NU

18 18NU

21 21NU 21NU 21NU

26 26NU 26NU 26NU 26NU 26NU

36 36NU 36NU

42 42NU 42NU

48 48NU 48NU

51

56

36NU 36NU

42NU 42NU

48NU 48NU

51NU 51NU

56NU 56NU

18NU

21NU

SkyAir NU Series Cooling Only

External Appearance

ED24-631A

1. External Appearance
Indoor Unit

FHC-NU

FH-NU

FDBG-NU

FDMG-NU

Wired Remote Controller

BRC1C61 (for FHC)

BRC1NU61 (for FH)

KRC47-1 (for FDBG, FDMG)

KRC47-2 KRC47-4 (for FDBG, FDMG)

Wireless Remote Controller

BRC7C613W (for FHC)

BRC7NU66 (for FH)

Outdoor Unit

R18NU

R21NU

R26NU

R36NU

R42NU

R48 51NU

R56NU

SkyAir NU Series Cooling Only

ED24-631A

Model Name, Power Supply and Nomenclature

2. Model Name, Power Supply and Nomenclature


2.1 Model Name and Power Supply
Indoor Unit FHC18NUV1 FHC21NUV1 FHC26NUV1 FHC36NUV1 FHC26NUV1 FHC36NUV1 FHC42NUV1 FHC48NUV1 FH21NUV1 FH26NUV1 FH36NUV1 FH26NUV1 FH36NUV1 FH42NUV1 FH48NUV1 FDBG18NUV1 FDBG21NUV1 FDBG26NUV1 FDBG26NUV1 FDMG26NUV1 FDMG36NUV1 FDMG26NUV1 FDMG36NUV1 FDMG42NUV1 FDMG48NUV1 FDMG51NUV1 FDMG56NUV1 Outdoor Unit R18NUV1 R21NUV1 1 phase 220~240V 50Hz R26NUV1 R36NUV1 R26NUY1 R36NUY1 R42NUY1 R48NUY1 R21NUV1 R26NUV1 R36NUV1 R26NUY1 R36NUY1 R42NUY1 R48NUY1 R18NUV1 R21NUV1 R26NUV1 R26NUY1 R26NUV1 1 phase 220~240V 50Hz R36NUV1 R26NUY1 R36NUY1 R42NUY1 R48NUY1 R51NUY1 R56NUY1 3 phase 380~415V 50Hz (4 wires) 1 phase 220~240V 50Hz 3 phase 380~415V 50Hz (4 wires) 1 phase 220~240V 50Hz 3 phase 380~415V 50Hz (4 wires) Power Supply

3 phase 380~415V 50Hz (4 wires)

Note:

1. : New Model or Changed Model 2. Power Supply Intake : Outdoor Unit

SkyAir NU Series Cooling Only

Model Name, Power Supply and Nomenclature

ED24-631A

2.2

Nomenclature

Indoor Unit

FDM

18

NU

V1
Power Supply Symbol V1 : 1 phase 220~240V 50Hz Indicates Major Design Category Capacity Indication DIT Products FHC : Ceiling Mounted Cassette Type -Multi FlowFH : Ceiling Suspended Type FDB : Duct Connection Low Static Pressure Type (Cooling Only) FDM : Duct Connection Middle Static Pressure Type (Cooling Only)

Outdoor Unit

18

NU

V1
Power Supply Symbol V1 : 1 phase 220~240V 50Hz Y1 : 3 phase 380~415V 50Hz Indicates Major Design Category Capacity Indication Outdoor Unit R : Cooling Only

SkyAir NU Series Cooling Only

ED24-631A

Functions

3. Functions
3.1
FHC-NU
Item Feature Auto swing Swing pattern selection Switchable fan speed Program "Dry" High ceiling application Wired type Two selectable thermo-sensors Wireless type Timer selector Mold resistant treatment for filter Drain water lift-up mechanism Pre-charged for up to 10 m Pre-charged for up to 15 m Long-life filter Filter sign Ceiling soiling prevention Auto-restart Ultra long-life filter High-efficiency filter Fresh air intake kit PE fin for outdoor unit Ceiling Mounted Casssete Type (FHC) { { { { { { { { { { (18~26) { (36~48) { { { { { { { {

NU Series

Comfort

Mildew prevention

Work & servicing

Control features Others

FH-NU
Item Comfort Feature Auto swing Switchable fan speed Program "Dry" Timer selector Mold resistant treatment for filter Mildew-proofing drain pan Pre-charged for up to 10 m Pre-charged for up to 15 m Long-life filter Auto-restart PE fin for outdoor unit Ceiling Suspended Type (FH) { { { { { { { (21 26) { (36~48) { { {

Mildew prevention Work & servicing Control features Others

FDBG-NU
Item Comfort Work & servicing Control features Others Feature Switchable fan speed Pre-charged for up to 10 m Auto-restart PE fin for outdoor unit Adjustable external static pressure Duct Connection Low Static Pressure Type (FDBG) { { (18~26) { { {

FDMG-NU
Item Comfort Work & servicing Control features Others Feature Switchable fan speed Pre-charged for up to 10 m Pre-charged for up to 15 m Auto-restart PE fin for outdoor unit Adjustable external static pressure Duct Connection Middle Static Pressure Type (FDMG) { { (26) { (36~51) { { {

{ : Functions exist. : No Functions

SkyAir NU Series Cooling Only

Specifications

ED24-631A

4. Specifications
FHC (Ceiling Mounted Cassette Type)
Indoor Unit Model Outdoor Unit V1 Y1 Btu/h kW kcal/h mm FHC21NUV1 FHC26NUV1 R21NUV1 R26NUV1 R26NUY1 21,200/21,000 26,300/26,000 6.2/6.2 7.7/7.6 5,340/5,290 6,630/6,550 FHC21NUV1 FHC26NUV1 230840840 230840840 Cross Fin Coil 281.5 281.5 281.5 0.331 0.331 0.331 QTS45B14M QTS45B14M QTS45B14M Turbo Fan 45 45 45 (H) 15 (L) 11 (H) 19 (L) 14 (H) 19 (L) 14 24 24 24 6.4 (Flare) 6.4 (Flare) 9.5 (Flare) 15.9 (Flare) 15.9 (Flare) 15.9 (Flare) I.D.25 O.D.32 I.D.25 O.D.32 I.D.25 O.D.32 BRC1C61 3 BRC7C613W BYC125KW1 BYC125KW1 BYC125KW1 White 40950950 40950950 40950950 Resin Net (with Mold Resistant) 5 5 5 R18NUV1 R21NUV1 R26NUV1 R26NUY1 Ivory White Ivory 540750270 685800300 770900320 Cross Fin Coil 2222.0 2282.0 2342.0 0.372 0.465 0.634 RC70AV1TRT NH41VMDT NH52VNHT NH52YDTT Hermetically Sealed Rotary Type 1.7 2.2 2.5 PZ380 PZ430 P47L11S Propeller 45 53 90 27 40 59 42 61 70 69 6.4 (Flare) 6.4 (Flare) 9.5 (Flare) 15.9 (Flare) 15.9 (Flare) 15.9 (Flare) 18.0 (Hole) 18.0 (Hole) 26.0 (Hole) Thermal Protector for Compressor, Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor. Outdoor Fan Motor and Indoor Fan Internal Protector of Compressor. Reverse Phase Protector (Y1). Fuse. Motor. Fuse. 1000 1000 1000 Capillary Tube 30 (Equivalent Length 50m) 30 (Equivalent Length 50m) 30 (Equivalent Length 50m) 15 15 20 R-22 R-22 R-22 1.20 (Charged for 10m) 1.50 (Charged for 10m) 2.3 (Charged for 10m) Refer to the name plate of compressor. 0.85 1.20 1.3 C : 4D054418A C : 4D054286A FHC18NUV1 R18NUV1 18,100/18,000 5.3/5.3 4,580/4,560 FHC18NUV1 230840840

1 2 Cooling Capacity (1) / (2) Indoor Unit Dimensions Coil

Fan

HWD Type RowStagesFin Pitch Face Area Model Type Motor Output Air Flow Rate Liquid Gas Drain Wired Wireless

Mass (Weight) Piping Connections

W m/min kg mm mm mm

Remote Controller (Option) Decoration Panel (Option)

Model Color Dimensions (HWD) Air Filter Weight

mm kg V1 Y1 mm

Outdoor Unit Color Dimensions Coil

HWD Type RowStagesFin Pitch Face Area Model

Comp.

m V1 Y1 kW

Fan

Type Motor Output Model Type Motor Output Air Flow Rate kg Liquid Gas Drain

Mass (Weight) Piping Connections Safety Devices

W m/min V1 Y1 mm mm mm

Capacity Step Refrigerant Control Max. Length Ref. Piping Max. Height Difference Model Refrigerant Charge (Factory Charge) Model Ref. Oil Charge Drawing No.

% m m kg L

Note:

1. The above data are based on the following conditions. Cooling (1) (2) Indoor: 27CDB, 19.5CWB Outdoor: 35CDB, 24CWB Indoor: 27CDB, 19.0CWB Outdoor: 35CDB, 24CWB Equivalent Piping Length 7.5m (Horizontal) 7.5m (Horizontal) Hz, Volts 50Hz, 220V (380V) 50Hz, 220V (380V)

Conversion Formulae kcal/h=kW860 Btu/h=kW3412 cfm=m/min35.3

2. Capacities are net, including a deduction for cooling for indoor fan motor heat. 3. Wire for remote controller : Field supplied.

SkyAir NU Series Cooling Only

ED24-631A

Specifications

FHC (Ceiling Mounted Cassette Type)


Indoor Unit Model Outdoor Unit V1 Y1 Btu/h kW kcal/h mm FHC42NUV1 FHC48NUV1 R42NUY1 R48NUY1 42,700/42,000 49,100/48,000 12.5/12.3 14.4/14.1 10,800/10,600 12,400/12,100 FHC42NUV1 FHC48NUV1 288840840 288840840 Cross Fin Coil 2121.5 2121.5 2121.5 0.497 0.497 0.497 QTS45A17M QTS45A17M QTS45A17M Turbo Fan 90 90 90 (H) 33 (L) 24 (H) 33 (L) 24 (H) 33 (L) 24 28 28 28 9.5 (Flare) 9.5 (Flare) 9.5 (Flare) 19.1 (Flare) 19.1 (Flare) 19.1 (Flare) I.D.25 O.D.32 I.D.25 O.D.32 I.D.25 O.D.32 BRC1C61 3 BRC7C613W BYC125KW1 BYC125KW1 BYC125KW1 White 40950950 40950950 40950950 Resin Net (with Mold Resistant) 5 5 5 R36NUV1 R36NUY1 R42NUY1 R48NUY1 Ivory 1,170900320 1,170900320 1,345900320 Cross Fin Coil 1521.4 1521.4 1601.4 1.015 1.015 1.172 JT125GA-V1@K JT125GA-Y1@K JT160GA-Y1@K JT170GA-Y1@K Hermetically Sealed Scroll Type 3.00 3.75 4.50 P47L11S P47L11S2 P47L11S2 Propeller 90 65+90 65+90 59 92 97 81 79 87 92 9.5 (Flare) 9.5 (Flare) 9.5 (Flare) 19.1 (Flare) 19.1 (Flare) 19.1 (Flare) 26.0 (Hole) 26.0 (Hole) 26.0 (Hole) Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor. High Pressure Switch. Low Pressure Switch. Internal Protector of Compressor. Reverse Phase Protector (Y1). Fuse. Thermo Switch (Discharge Pipe). 1000 1000 1000 Capillary Tube 30 (Equivalent Length 50m) 30 (Equivalent Length 50m) 30 (Equivalent Length 50m) 20 20 20 R-22 R-22 R-22 2.0 (Charged for 15m) 2.4 (Charged for 15m) 2.6 (Charged for 15m) Refer to the name plate of compressor. 1.4 1.4 1.4 C : 4D052554B FHC36NUV1 R36NUV1 R36NUY1 36,500/36,000 10.7/10.6 9,200/9,100 FHC36NUV1 288840840

1 2 Cooling Capacity (1) / (2) Indoor Unit Dimensions Coil

Fan

HWD Type RowStagesFin Pitch Face Area Model Type Motor Output Air Flow Rate Liquid Gas Drain Wired Wireless

Mass (Weight) Piping Connections

W m/min kg mm mm mm

Remote Controller (Option) Decoration Panel (Option)

Model Color Dimensions (HWD) Air Filter Weight

mm kg V1 Y1 mm

Outdoor Unit Color Dimensions Coil

HWD Type RowStagesFin Pitch Face Area Model

Comp.

m V1 Y1 kW

Fan

Type Motor Output Model Type Motor Output Air Flow Rate kg Liquid Gas Drain

Mass (Weight) Piping Connections Safety Devices

W m/min V1 Y1 mm mm mm

Capacity Step Refrigerant Control Max. Length Ref. Piping Max. Height Difference Model Refrigerant Charge (Factory Charge) Model Ref. Oil Charge Drawing No.

% m m kg L

Note:

1. The above data are based on the following conditions. Cooling (1) (2) Indoor: 27CDB, 19.5CWB Outdoor: 35CDB, 24CWB Indoor: 27CDB, 19.0CWB Outdoor: 35CDB, 24CWB Equivalent Piping Length 7.5m (Horizontal) 7.5m (Horizontal) Hz, Volts 50Hz, 220V (380V) 50Hz, 220V (380V)

Conversion Formulae kcal/h=kW860 Btu/h=kW3412 cfm=m/min35.3

2. Capacities are net, including a deduction for cooling for indoor fan motor heat. 3. Wire for remote controller : Field supplied.

SkyAir NU Series Cooling Only

Specifications

ED24-631A

FH (Ceiling Suspended Type)


Indoor Unit Model Outdoor Unit V1 Y1 Btu/h kW kcal/h FH36NUV1 FH42NUV1 FH48NUV1 R36NUV1 R36NUY1 R42NUY1 R48NUY1 36,500/36,000 42,700/42,000 49,100/48,000 10.7/10.6 12.5/12.3 14.4/14.1 9,200/9,100 10,800/10,600 12,400/12,100 FH36NUV1 FH42NUV1 FH48NUV1 White 1951,160680 1951,160680 1951,590680 1951,590680 1951,590680 Cross Fin Coil 3121.75 3121.75 3121.75 3121.75 3121.75 0.233 0.233 0.341 0.341 0.341 4D12K1AA1 4D12K1AA1 4D12K2AA1 4D12K2AA1 4D12K2AA1 Sirocco Fan 45 45 70 98 98 (H) 22-23 (L) 19-20 (H) 22-23 (L) 19-20 (H) 32-34 (L) 22-24 (H) 38-40 (L) 23-25 (H) 42-44 (L) 24-26 Resin Net (with Mold Resistant) 26 26 35 35 35 6.4 (Flare) 9.5 (Flare) 9.5 (Flare) 9.5 (Flare) 9.5 (Flare) 15.9 (Flare) 15.9 (Flare) 19.1 (Flare) 19.1 (Flare) 19.1 (Flare) I.D.20 O.D.26 I.D.20 O.D.26 I.D.20 O.D.26 I.D.20 O.D.26 I.D.20 O.D.26 BRC1NU61 4 BRC7NU66 R21NUV1 R26NUV1 R36NUV1 R26NUY1 R36NUY1 R42NUY1 R48NUY1 Ivory White Ivory 685800300 770900320 1,170900320 1,170900320 1,345900320 Cross Fin Coil 2282.0 2342.0 1521.4 1521.4 1601.4 0.465 0.634 1.015 1.015 1.172 NH41VMDT NH52VNHT JT125GA-V1@K NH52YDTT JT125GA-Y1@K JT160GA-Y1@K JT170GA-Y1@K Hermetically Sealed Rotary Type Hermetically Sealed Scroll Type 2.2 2.5 3.00 3.75 4.50 PZ430 P47L11S P47L11S P47L11S2 P47L11S2 Propeller 53 90 90 65+90 65+90 40 59 59 92 97 61 70 81 69 79 87 92 6.4 (Flare) 9.5 (Flare) 9.5 (Flare) 9.5 (Flare) 9.5 (Flare) 15.9 (Flare) 15.9 (Flare) 19.1 (Flare) 19.1 (Flare) 19.1 (Flare) 18.0 (Hole) 26.0 (Hole) 26.0 (Hole) 26.0 (Hole) 26.0 (Hole) Thermal Protector for Outdoor Fan Motor and Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor. High Indoor Fan Motor. Internal Protector of Pressure Switch. Low Pressure Switch. Internal Protector of Compressor. Reverse Phase Protector (Y1). Compressor. Reverse Phase Protector (Y1). Fuse. Thermo Switch Fuse. (Discharge Pipe). 1000 1000 1000 1000 1000 Capillary Tube 30 30 30 30 30 (Equivalent Length 50m) (Equivalent Length 50m) (Equivalent Length 50m) (Equivalent Length 50m) (Equivalent Length 50m) 15 20 20 20 20 R-22 R-22 R-22 R-22 R-22 1.50 (Charged for 10m) 2.3 (Charged for 10m) 2.0 (Charged for 15m) 2.4 (Charged for 15m) 2.6 (Charged for 15m) Refer to the name plate of compressor. 1.20 1.3 1.4 1.4 1.4 C : 4D054275A C : 4D052470B FH21NUV1 R21NUV1 21,200/21,000 6.2/6.2 5,340/5,290 FH21NUV1 FH26NUV1 R26NUV1 R26NUY1 26,300/26,000 7.7/7.6 6,630/6,550 FH26NUV1

1 2 Cooling Capacity (1) / (2) Indoor Unit Color Dimensions Coil

Fan

HWD Type RowStagesFin Pitch Face Area Model Type Motor Output Air Flow Rate 3

mm

W m/min kg mm mm mm

Air Filter Mass (Weight) Piping Connections Liquid Gas Drain Wired Wireless

Remote Controller (Option) Outdoor Unit Color Dimensions Coil

V1 Y1 HWD Type RowStagesFin Pitch Face Area Model mm

Comp.

m V1 Y1 kW

Fan

Type Motor Output Model Type Motor Output Air Flow Rate kg Liquid Gas Drain

Mass (Weight) Piping Connections

W m/min V1 Y1 mm mm mm

Safety Devices Capacity Step Refrigerant Control Ref. Piping Refrigerant Ref. Oil Drawing No. Max. Length Max. Height Difference Model Charge (Factory Charge) Model Charge % m m kg L

Note:

1. The above data are based on the following conditions. Cooling (1) (2) Indoor: 27CDB, 19.5CWB Outdoor: 35CDB, 24CWB Indoor: 27CDB, 19.0CWB Outdoor: 35CDB, 24CWB Equivalent Piping Length 7.5m (Horizontal) 7.5m (Horizontal) Hz, Volts 50Hz, 220V (380V) 50Hz, 220V (380V)

Conversion Formulae kcal/h=kW860 Btu/h=kW3412 cfm=m/min35.3

2. Capacities are net, including a deduction for cooling for indoor fan motor heat. 3. AFR (Air flow rate) is shown at 220~240V (380~415V). 4. Wire for remote controller : Field supplied.

SkyAir NU Series Cooling Only

ED24-631A

Specifications

FDBG (Duct Connection Low Static Pressure Type)


Indoor Unit Model Outdoor Unit V1 Y1 Btu/h kW kcal/h mm FDBG21NUV1 FDBG26NUV1 R21NUV1 R26NUV1 R26NUY1 21,200/21,000 26,300/26,000 6.2/6.2 7.7/7.6 5,340/5,290 6,630/6,550 FDBG21NUV1 FDBG26NUV1 2601,300580 2601,300580 Cross Fin Coil 3101.75 3101.75 3101.75 0.189 0.231 0.231 Sirocco Fan 45 65 65 (H) 13 (L) 11 (H) 18 (L) 15 (H) 18 (L) 15 23 31 31 6.4 (Flare) 6.4 (Flare) 9.5 (Flare) 15.9 (Flare) 15.9 (Flare) 15.9 (Flare) 3/4 B (I.D.21.6 O.D.27.2) 3/4 B (I.D.21.6 O.D.27.2) 3/4 B (I.D.21.6 O.D.27.2) KRC47-1 KRC47-2 KRC47-4 KRC47-1 KRC47-2 KRC47-4 KRC47-1 KRC47-2 KRC47-4 R18NUV1 R21NUV1 R26NUV1 R26NUY1 Ivory White Ivory 540750270 685800300 770900320 Cross Fin Coil 2222.0 2282.0 2342.0 0.372 0.465 0.634 RC70AV1TRT NH41VMDT NH52VNHT NH52YDTT Hermetically Sealed Rotary Type 1.7 2.2 2.5 PZ380 PZ430 P47L11S Propeller 45 53 90 27 40 59 42 61 70 69 6.4 (Flare) 6.4 (Flare) 9.5 (Flare) 15.9 (Flare) 15.9 (Flare) 15.9 (Flare) 18.0 (Hole) 18.0 (Hole) 26.0 (Hole) Thermal Protector for Compressor, Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor. Outdoor Fan Motor and Indoor Fan Internal Protector of Compressor. Reverse Phase Protector (Y1). Fuse. Motor. Fuse. 1000 1000 1000 Capillary Tube 30 (Equivalent Length 50m) 30 (Equivalent Length 50m) 30 (Equivalent Length 50m) 15 15 20 R-22 R-22 R-22 1.20 (Charged for 10m) 1.50 (Charged for 10m) 2.3 (Charged for 10m) Refer to the name plate of compressor. 0.85 1.20 1.3 C : 4D054295B C : 4D054288A FDBG18NUV1 R18NUV1 18,100/18,000 5.3/5.3 4,580/4,560 FDBG18NUV1 260900580

1 2 Cooling Capacity (1) / (2) Indoor Unit Dimensions Coil

Fan Mass (Weight) Piping Connections

HWD Type RowStagesFin Pitch Face Area Type Motor Output Air Flow Rate 3 Liquid Gas Drain Wired Wireless

m W m/min kg mm mm mm

Remote Controller (Option) Outdoor Unit Color Dimensions Coil

V1 Y1 HWD Type RowStagesFin Pitch Face Area Model mm

Comp.

m V1 Y1 kW

Fan

Type Motor Output Model Type Motor Output Air Flow Rate kg Liquid Gas Drain

Mass (Weight) Piping Connections Safety Devices

W m/min V1 Y1 mm mm mm

Capacity Step Refrigerant Control Max. Length Ref. Piping Max. Height Difference Model Refrigerant Charge (Factory Charge) Model Ref. Oil Charge Drawing No.

% m m kg L

Note:

1. The above data are based on the following conditions. Cooling (1) (2) Indoor: 27C(81F)DB, 19.5C(67F)WB Outdoor: 35C(95F)DB, 24C(75F)WB Indoor: 27C(81F)DB, 19.0C(66F)WB Outdoor: 35C(95F)DB, 24C(75F)WB Equivalent Piping Length 7.5m (Horizontal) 7.5m (Horizontal) Hz, Volts 50Hz, 220V (380V) 50Hz, 220V (380V)

Conversion Formulae kcal/h=kW860 Btu/h=kW3412 cfm=m/min35.3

2. Capacities are net, including a deduction for cooling for indoor fan motor heat. 3. Refer to "11. Fan Performance" in detail.

SkyAir NU Series Cooling Only

Specifications

ED24-631A

FDMG (Duct Connection Middle Static Pressure Type)


Indoor Unit Model Outdoor Unit V1 Y1 Btu/h kW kcal/h mm FDMG26NUV1 R26NUV1 R26NUY1 26,300/26,000 7.7/7.6 6,630/6,550 FDMG26NUV1 3051,350680 3121.75 0.290 125 23 8.5 43 9.5 (Flare) 15.9 (Flare) 3/4 B (I.D.21.6 O.D.27.2) KRC47-1 KRC47-2 KRC47-4 R26NUV1 R26NUY1 770900320 2342.0 0.634 NH52VNHT NH52YDTT Hermetically Sealed Rotary Type 2.5 P47L11S 90 59 70 69 9.5 (Flare) 15.9 (Flare) 26.0 (Hole) Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor. Internal Protector of Compressor. Reverse Phase Protector (Y1). Fuse. 1000 30 (Equivalent Length 50m) 20 R-22 2.3 (Charged for 10m) 1.3 C : 4D054287A FDMG36NUV1 FDMG42NUV1 R36NUV1 R36NUY1 R42NUY1 36,500/36,000 42,700/42,000 10.7/10.6 12.5/12.3 9,200/9,100 10,800/10,600 FDMG36NUV1 FDMG42NUV1 3051,550680 3051,550680 Cross Fin Coil 3121.75 3121.75 0.340 0.340 Sirocco Fan 225 225 37 42 9.8 8.0 52 52 9.5 (Flare) 9.5 (Flare) 19.1 (Flare) 19.1 (Flare) 3/4 B (I.D.21.6 O.D.27.2) 3/4 B (I.D.21.6 O.D.27.2) KRC47-1 KRC47-2 KRC47-4 KRC47-1 KRC47-2 KRC47-4 R36NUV1 R36NUY1 R42NUY1 Ivory 1,170900320 1,170900320 Cross Fin Coil 1521.4 1521.4 1.015 1.015 JT125GA-V1@K JT125GA-Y1@K JT160GA-Y1@K Hermetically Sealed Scroll Type 3.00 3.75 P47L11S P47L11S2 Propeller 90 65+90 59 92 81 79 87 9.5 (Flare) 9.5 (Flare) 19.1 (Flare) 19.1 (Flare) 26.0 (Hole) 26.0 (Hole) Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor. High Pressure Switch. Low Pressure Switch. Internal Protector of Compressor. Reverse Phase Protector (Y1). Fuse. Thermo Switch (Discharge Pipe). 1000 1000 Capillary Tube 30 (Equivalent Length 50m) 30 (Equivalent Length 50m) 20 20 R-22 R-22 2.0 (Charged for 15m) 2.4 (Charged for 15m) Refer to the name plate of compressor. 1.4 1.4 C : 3D052567B

1 2 Cooling Capacity (1) / (2) Indoor Unit Dimensions Coil

Fan

HWD Type RowStagesFin Pitch Face Area Type Motor Output Air Flow Rate 3 Rated Ext. Static Pressure 3 Liquid Gas Drain Wired Wireless

m W m/min mmH2O kg mm mm mm

Mass (Weight) Piping Connections

Remote Controller (Option) Outdoor Unit Color Dimensions Coil

V1 Y1 HWD Type RowStagesFin Pitch Face Area Model mm

Comp.

m V1 Y1 kW

Fan

Type Motor Output Model Type Motor Output Air Flow Rate kg Liquid Gas Drain

Mass (Weight) Piping Connections

W m/min V1 Y1 mm mm mm

Safety Devices Capacity Step Refrigerant Control Max. Length Ref. Piping Max. Height Difference Model Refrigerant Charge (Factory Charge) Model Ref. Oil Charge Drawing No. % m m kg L

Note:

1. The above data are based on the following conditions. Cooling (1) (2) Indoor: 27C(81F)DB, 19.5C(67F)WB Outdoor: 35C(95F)DB, 24C(75F)WB Indoor: 27C(81F)DB, 19.0C(66F)WB Outdoor: 35C(95F)DB, 24C(75F)WB Equivalent Piping Length 7.5m (Horizontal) 7.5m (Horizontal) Hz, Volts 50Hz, 220V (380V) 50Hz, 220V (380V)

Conversion Formulae kcal/h=kW860 Btu/h=kW3412 cfm=m/min35.3

2. Capacities are net, including a deduction for cooling for indoor fan motor heat. 3. Refer to "11. Fan Performance" in detail.

10

SkyAir NU Series Cooling Only

ED24-631A

Specifications

FDMG (Duct Connection Middle Static Pressure Type)


Model Indoor Unit Outdoor Unit Btu/h kW kcal/h mm FDMG51NUV1 FDMG56NUV1 R51NUY1 R56NUY1 52,200/51,000 57,000/56,000 15.3/15.0 16.7/16.4 13,200/12,900 14,400/14,100 FDMG51NUV1 FDMG56NUV1 3051,900680 3051,900680 Cross Fin Coil 3121.75 3121.75 3121.75 0.340 0.428 0.428 Sirocco Fan 225 225 225 42 42 42 8.0 9.8 9.8 52 58 58 9.5 (Flare) 9.5 (Flare) 9.5 (Flare) 19.1 (Flare) 19.1 (Flare) 19.1 (Flare) 3/4 B (I.D.21.6 O.D.27.2) 3/4 B (I.D.21.6 O.D.27.2) 3/4 B (I.D.21.6 O.D.27.2) KRC47-1 KRC47-2 KRC47-4 KRC47-1 KRC47-2 KRC47-4 KRC47-1 KRC47-2 KRC47-4 R48NUY1 R51NUY1 R56NUY1 Ivory 1,345900320 1,345900320 1,345880370 Cross Fin Coil 1601.4 1601.4 2602.0 1.172 1.172 1.088 JT170GA-Y1@K JT170GA-Y1@K JT200B-YE Hermetically Sealed Scroll Type 4.50 4.50 4.50 P47L11S2 P47L11S2 P45J11S2 Propeller 65+90 65+90 64+56 97 97 101 92 93 114 9.5 (Flare) 9.5 (Flare) 9.5 (Flare) 19.1 (Flare) 19.1 (Flare) 19.1 (Flare) 26.0 (Hole) 26.0 (Hole) 26.0 (Hole) Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor. High Pressure Switch. Low Pressure Switch. Internal Protector of Compressor. Reverse Phase Protector (Y1). Fuse. Thermo Switch (Discharge Pipe). 1000 1000 1000 Capillary Tube 30 (Equivalent Length 50m) 30 (Equivalent Length 50m) 50 (Equivalent Length 70m) 20 20 30 R-22 R-22 R-22 2.6 (Charged for 15m) 2.7 (Charged for 15m) 2.8 (Charged for 5m) Refer to the name plate of compressor. 1.4 1.4 1.6 C : 3D052567B FDMG48NUV1 R48NUY1 49,100/48,000 14.4/14.1 12,400/12,100 FDMG48NUV1 3051,550680

1 2 Cooling Capacity (1) / (2) Indoor Unit Dimensions Coil

Fan

HWD Type RowStagesFin Pitch Face Area Type Motor Output Air Flow Rate 3 Rated Ext. Static Pressure 3 Liquid Gas Drain Wired Wireless

m W m/min mmH2O kg mm mm mm

Mass (Weight) Piping Connections

Remote Controller (Option)

Outdoor Unit Color Dimensions HWD Type Coil RowStagesFin Pitch Face Area Model Comp. Type Motor Output Model Type Fan Motor Output Air Flow Rate Mass (Weight) Liquid Piping Gas Connections Drain Safety Devices Capacity Step Refrigerant Control Max. Length Ref. Piping Max. Height Difference Model Refrigerant Charge (Factory Charge) Model Ref. Oil Charge Drawing No.

mm

kW

W m/min kg mm mm mm

% m m kg L

Note:

1. The above data are based on the following conditions. Cooling (1) (2) Indoor: 27C(81F)DB, 19.5C(67F)WB Outdoor: 35C(95F)DB, 24C(75F)WB Indoor: 27C(81F)DB, 19.0C(66F)WB Outdoor: 35C(95F)DB, 24C(75F)WB Equivalent Piping Length 7.5m (Horizontal) 7.5m (Horizontal) Hz, Volts 50Hz, 220V (380V) 50Hz, 220V (380V)

Conversion Formulae kcal/h=kW860 Btu/h=kW3412 cfm=m/min35.3

2. Capacities are net, including a deduction for cooling for indoor fan motor heat. 3. Refer to "11. Fan Performance" in detail.

SkyAir NU Series Cooling Only

11

Dimensions and Service Space

ED24-631A

5. Dimensions and Service Space


5.1
5.1.1

Indoor Unit
FHC (Ceiling Mounted Cassette Type)

FHC18NU + BYC125K-W1 FHC21NU + BYC125K-W1

Unit (mm)

4. When the temperature and humidity in the ceiling exceed 30C and RH 80% or the fresh air is inducted into the ceiling or the unit continues 24 hour operation, an additional insulation (thickness 10mm or more of glasswool or polyethylene form) is required.

C : 3D054367

FHC26NU + BYC125K-W1

Unit (mm)

4. When the temperature and humidity in the ceiling exceed 30C and RH 80% or the fresh air is inducted into the ceiling or the unit continues 24 hour operation, an additional insulation (thickness 10mm or more of glasswool or polyethylene form) is required.

C : 3D054368

12

SkyAir NU Series Cooling Only

ED24-631A

Dimensions and Service Space

FHC36NU + BYC125K-W1 FHC42NU + BYC125K-W1 FHC48NU + BYC125K-W1

Unit (mm)

4. When the temperature and humidity in the ceiling exceed 30C and RH 80% or the fresh air is inducted into the ceiling or the unit continues 24 hour operation, an additional insulation (thickness 10mm or more of glasswool or polyethylene form) is required.

C : 3D052528

5.1.2

FHC with High-Efficiency Filter

KAFP556D80 557D80 for FHC18~26NU


Note:When other optional kit is installed, refer to the installation drawing of its optional kit.

Unit (mm)

290

6 5 4 3 2 1 Number

Drain pipe connection Gas pipe connection Liquid pipe connection High efficiency filter Decoration panel Indoor unit Description Name JC : 3D032975C

SkyAir NU Series Cooling Only

13

Dimensions and Service Space

ED24-631A

KAFP556D160 557D160 for FHC36~48NU


Note:When other optional kit is installed, refer to the installation drawing of its optional kit.

Unit (mm)

6 5 4 3 2 1 Number

Drain pipe connection Gas pipe connection Liquid pipe connection High efficiency filter Decoration panel Indoor unit Description Name J : 3D032976C

5.1.3

FHC with Fresh Air Intake Kit (Without T Joint, Duct Fan)

KDDP55D160 for FHC18~26NU


Service Access Panel : 450450mm or more Refer to Note 2 Refrigerant Piping

Unit (mm)

View
Service Access Panel : 450450mm or more Refer to Note 2

Note 4

Installation Service Access Panel

Connection Chamber (Right) Note:1.When installing this kit, Service Access Panel is necessary. (It is necessary when servicing.) 2.Either one of Service Access Panel must be installed. 3.Field construction. 4.In case of using wireless remote controller kit, this part will be the infrared receiver. 5.When both side intakes can not be ensured due to the obstacles, one side intake is acceptable. 6.When installing the wireless infrared reciever to the unit, air inlet must be on the right side as shown. How to connect Chamber 4 Independently(Refer to Note 5,6)

5 4 3 2 1 Number

Connection chamber(Left) Connection chamber(Right) Suction chamber Decoration panel Indoor unit Description Name JC : 3D032981D

14

SkyAir NU Series Cooling Only

ED24-631A

Dimensions and Service Space

KDDP55D160 for FHC36~48NU


Service Access Panel : 450450mm or more Refer to Note 2

Unit (mm)

Refrigerant Piping

Service Access Panel : 450450mm or more Refer to Note 2

View

Note 4

Installation Service Access Panel

Connection Chamber (Right) How to connect Chamber 4 Independently(Refer to Note 5,6) Note:1.When installing this kit, Service Access Panel is necessary. (It is necessary when servicing.) 2.Either one of Service Access Panel must be installed. 3.Field construction. 4.In case of using wireless remote controller kit, this part will be the infrared receiver. 5.When both side intakes can not be ensured due to the obstacles, one side intake is acceptable. 6.When installing the wireless infrared reciever to the unit, air inlet must be on the right side as shown.

5 4 3 2 1 Number

Connecting chamber(Left) Connecting chamber(Right) Suction chamber Decoration panel Indoor unit Description Name JC : 3D032984D

5.1.4

FHC with Fresh Air Intake Kit (With T Joint, Without Duct Fan)

KDDP55D160K for FHC18~26NU


Service Access Panel : 450450mm or more Refer to Note 2

Unit (mm)
Flexible Duct (Accessory)

Service Access Panel : 450450mm or more Refer to Note 2

Suction Duct (K-KFD9A) Optional (Accessory) T Joint Plate Band (Accessory) (Accessory)

Installation Service Access Panel

Connecting Chamber (Right) How to connect Chamber 4 Independently(Refer to Note 5)


Note:1.When installing this kit, inspection hatch is necessary. (It is necessary when servicing.) 2.Either one of inspection hatch must be installed. 3.Field construction. 4.This kit does not take together with Wireless Remoto Controller kit. 5.When both side intakes can not be ensured due to the obstacles, one side intake is acceptable. 5 4 3 2 1 Number Connecting chamber(Left) Connecting chamber(Right) Suction chamber Decoration panel Indoor unit Description Name

JC : 3D032987D

SkyAir NU Series Cooling Only

15

Dimensions and Service Space

ED24-631A

KDDP55D160K for FHC36~48NU


Service Access Panel : 450450mm or more Refer to Note 2

Unit (mm)
Flexible Duct (Accessory)

Service Access Panel : 450450mm or more Refer to Note 2

Installation Service Access Panel


Plate Band (Accessory) T Joint (Accessory)

Suction Duct (K-KFD9A) Optional (Accessory)

Connecting Chamber (Right) How to connect Chamber 4 Independently(Refer to Note 5) Note:1.When installing this kit, inspection hatch is necessary. (It is necessary when servicing.) 2.Either one of inspection hatch must be installed. 3.Field construction. 4.This kit does not take together with Wireless Remoto Controller kit. 5.When both side intakes can not be ensured due to the obstacles, one side intake is acceptable. 5 4 3 2 1 Number Connecting chamber(Left) Connecting chamber(Right) Suction chamber Decoration panel Indoor unit Description Name

J : 3D032990D

5.1.5

FHC with Panel Spacer

KDBP55H160WA for FHC18~26NU


Unit (mm)

View

Note:When other optional kit is installed, refer to the installation drawing of its optional kit

Dimension between the bottom surface of box and the surface of ceiling

3 Panel spacer 2 Decoration panel 1 Indoor unit Number Name

Thickness of panel spacer

Description JC : 3D005390E

16

SkyAir NU Series Cooling Only

ED24-631A

Dimensions and Service Space

KDBP55H160WA for FHC36~48NU

Unit (mm)

View

Note:When other optional kit is installed, refer to the installation drawing of its optional kit

Dimension between the bottom surface of box and the surface of ceiling

3 Panel spacer 2 Decoration panel 1 Indoor unit Number Name

Thickness of panel spacer

Description JC : 3D005391D

5.1.6
FH21NU

FH (Ceiling Suspended Type)

Unit (mm)

3D054277

SkyAir NU Series Cooling Only

17

Dimensions and Service Space

ED24-631A

FH26NU

Unit (mm)

3D027538F

FH36NU FH42NU FH48NU

Unit (mm)

3D052469

18

SkyAir NU Series Cooling Only

ED24-631A

Dimensions and Service Space

5.1.7

FDBG (Duct Connection Low Static Pressure Type)

FDBG18NU

Unit (mm)

3D048541A

FDBG21NU

Unit (mm)

3D048542A

SkyAir NU Series Cooling Only

19

Dimensions and Service Space

ED24-631A

FDBG26NU

Unit (mm)

3D048543A

5.1.8

FDMG (Duct Connection Middle Static Pressure Type)

FDMG26NU

Unit (mm)

3D048933B

20

SkyAir NU Series Cooling Only

ED24-631A

Dimensions and Service Space

FDMG36NU FDMG42NU FDMG48NU

Unit (mm)

3D048934B

FDMG51NU FDMG56NU

Unit (mm)

3D048935B

SkyAir NU Series Cooling Only

21

Dimensions and Service Space

ED24-631A

5.2

Wired Remote Controller

BRC1C61 (for FHC-NU)

Unit (mm)

3D028952

BRC1NU61 (for FH-NU)

Unit (mm)

3D052351

22

SkyAir NU Series Cooling Only

ED24-631A

Dimensions and Service Space

KRC47-1 (for FDBG-NU and FDMG-NU)

KRC47-2 (Digital Remote Controller) (for FDBG-NU and FDMG-NU)


KRC47-2 contains the following parts, and they are packed in one carton. 1. Digital Remote Controller

2. Holder

SkyAir NU Series Cooling Only

23

Dimensions and Service Space

ED24-631A

3. Control Board (Box)

4. Wire Cable Cable length : 4m Connecting cable between 1. Digital Remote Controller and 3. Control Board (Box).

KRC47-4 (Digital Remote Controller for Duct Heater Use) (for FDBG-NU and FDMG-NU)
1. Digital Remote Controller

AUTO HIGH MED LOW

HEAT

COOL

POWER TEMP +

FAN TEMP -

For other parts 2. Holder, 3. Control Board (Box), 4. Wire Cable will be the same as KRC 47-2.
(P0007)

24

SkyAir NU Series Cooling Only

ED24-631A

Dimensions and Service Space

5.3

Wireless Remote Controller

BRC7C613W (for FHC-NU)

Unit (mm)

3D005912D

BRC7NU66 (for FH-NU)

Unit (mm)

3D052347

SkyAir NU Series Cooling Only

25

Dimensions and Service Space

ED24-631A

5.4
R18NU

Outdoor Unit

Unit (mm)

3D053564

R21NU

Unit (mm)

3D053561

26

SkyAir NU Series Cooling Only

ED24-631A

Dimensions and Service Space

R26NU

Unit (mm)

3D054206

R36NU

Unit (mm)

3D052425

SkyAir NU Series Cooling Only

27

Dimensions and Service Space

ED24-631A

R42NU

Unit (mm)

3D052426

R48NU R51NU

Unit (mm)

3D052427

28

SkyAir NU Series Cooling Only

ED24-631A

Dimensions and Service Space

R56NU

Unit (mm)

C : 3D052527

SkyAir NU Series Cooling Only

29

Dimensions and Service Space

ED24-631A

5.5

Installation Service Space for R26~56NU

3D052620A

30

SkyAir NU Series Cooling Only

ED24-631A

Dimensions and Service Space

3D052620A

SkyAir NU Series Cooling Only

31

Piping Diagrams

ED24-631A

6. Piping Diagrams
R18 21NU

4D050891B

R26NU

3D053984

32

SkyAir NU Series Cooling Only

ED24-631A

Piping Diagrams

R36~56NU

3D052278

SkyAir NU Series Cooling Only

33

Wiring Diagrams

ED24-631A

7. Wiring Diagrams
7.1 Indoor Unit
FHC18NUV1 FHC21NUV1 FHC26NUV1 FHC36NUV1 FHC42NUV1 FHC48NUV1

3D052066A

34

SkyAir NU Series Cooling Only

ED24-631A

Wiring Diagrams

FH21NUV1 FH26NUV1 FH36NUV1 FH42NUV1 FH48NUV1

3D052046A

SkyAir NU Series Cooling Only

35

Wiring Diagrams

ED24-631A

FDBG18NUV1 FDBG21NUV1 FDBG26NUV1

3D046565A

36

SkyAir NU Series Cooling Only

ED24-631A

Wiring Diagrams

FDMG26NUV1 FDMG36NUV1 FDMG42NUV1 FDMG48NUV1 FDMG51NUV1 FDMG56NUV1

3D052109A

SkyAir NU Series Cooling Only

37

Wiring Diagrams

ED24-631A

7.2

Remote Controller

KRC47-1

TEMPERATURE CONTROL

CONTROL BOARD ELECTRONIC CONTROL

When select the high ESP,


connect the wire as shown below.

OFF

ON

P2

P3

P4

P1

P2

P3

P4

P5

P6

FDBG FDMG

D Comp. (THERMOSTAT)

A H

B M FAN

C L

E (ON/OFF) L

F N

(P0008-631A)

KRC47-2

REMOTE CONTROLLER

THERMISTOR

CONTROL BOARD P8 P9

When select the high ESP,


connect the wire as shown below.

P3

P2

P1

P4

P3

P2

P1

P7

FDBG FDMG

F N

E L (ON/OFF)

A H

B M FAN

C L

D Comp. (THERMOSTAT)
(P0009-631A)

38

SkyAir NU Series Cooling Only

ED24-631A

Wiring Diagrams

KRC47-4

REMOTE CONTROLLER

THERMISTOR

CONTROL BOARD P8 P9

When select the high ESP,


connect the wire as shown below.

P3

P2

P1

P4

P3

P2

P1

P7

P6

FDBG FDMG

F N

E L (ON/OFF)

A H

B M

C L

D Comp. (THERMOSTAT) DUCT HEATER (FIELD SUPPLIED)

FAN

(P0010-631A)

SkyAir NU Series Cooling Only

39

Wiring Diagrams

ED24-631A

7.3

Outdoor Unit

R18NUV1

3D032199B

R21NUV1

3D032200A

40

SkyAir NU Series Cooling Only

ED24-631A

Wiring Diagrams

R26NUV1

3D053671A

R26NUY1

3D053670A

SkyAir NU Series Cooling Only

41

Wiring Diagrams

ED24-631A

R36NUV1

3D051564A

R36NUY1

3D051536A

42

SkyAir NU Series Cooling Only

ED24-631A

Wiring Diagrams

R42NUY1 R48NUY1 R51NUY1

3D051535A

R56NUY1

3D052107

SkyAir NU Series Cooling Only

43

Wiring Diagrams

ED24-631A

7.4

Field Wiring

C : 4D054220 C : 4D052570

44

SkyAir NU Series Cooling Only

ED24-631A

Electric Characteristics

8. Electric Characteristics
8.1 R18~26NUV1 / Y1

3D054360A 3D054365A

SkyAir NU Series Cooling Only

45

Electric Characteristics

ED24-631A

8.2

R36~56NUV1 / Y1

3D052523 3D052524 3D052525 3D052526 3D052573

46

SkyAir NU Series Cooling Only

ED24-631A

Capacity Tables

9. Capacity Tables
9.1 Capacity Tables
FHC18NUV1 / FDBG18NUV1 + R18NUV1

3D054363A

FHC21NUV1 / FH21NUV1 / FDBG21NUV1 + R21NUV1

3D054364A

SkyAir NU Series Cooling Only

47

Capacity Tables

ED24-631A

FHC26NUV1 / FH26NUV1 / FDBG26NUV1 / FDMG26NUV1 + R26NUV1 FHC26NUV1 / FH26NUV1 / FDBG26NUV1 / FDMG26NUV1 + R26NUY1

3D054484A

FHC36NUV1 / FH36NUV1 / FDMG36NUV1 + R36NUV1 FHC36NUV1 / FH36NUV1 / FDMG36NUV1 + R36NUY1

3D052745A

48

SkyAir NU Series Cooling Only

ED24-631A

Capacity Tables

FHC42NUV1 / FH42NUV1 / FDMG42NUV1 + R42NUY1

3D052746A

FHC48NUV1 / FH48NUV1 / FDMG48NUV1 + R48NUY1

3D052747A

SkyAir NU Series Cooling Only

49

Capacity Tables

ED24-631A

FDMG51NUV1 + R51NUY1

3D052751A

FDMG56NUV1 + R56NUY1

3D052754A

50

SkyAir NU Series Cooling Only

ED24-631A

Capacity Tables

9.2

Capacity Correction Factor by the Length of Refrigerant Piping


The cooling capacity of the unit has to be corrected in accordance with the length of refrigerant piping. (The distance between the indoor unit and the outdoor unit) Reference Data

3D052761A

SkyAir NU Series Cooling Only

51

Operation Limit

ED24-631A

10. Operation Limit

3D049550B

52

SkyAir NU Series Cooling Only

ED24-631A

Fan Performance

11. Fan Performance


11.1 FDBG-NU
FDBG18NU

3D048561A

FDBG21NU FDBG26NU

3D048562A

SkyAir NU Series Cooling Only

53

Fan Performance

ED24-631A

11.2

FDMG-NU

FDMG26NU

4D049493A

FDMG36NU

4D049488A

54

SkyAir NU Series Cooling Only

ED24-631A

Fan Performance

FDMG42NU FDMG48NU

4D049489A

FDMG51NU FDMG56NU

4D049490A

SkyAir NU Series Cooling Only

55

Sound Level

ED24-631A

12. Sound Level


12.1 Overall Sound Level
dB(A) Model FHC18NUV1 FHC21NUV1 FHC26NUV1 FHC36NUV1 FHC42NUV1 FHC48NUV1 FH21NUV1 FH26NUV1 FH36NUV1 FH42NUV1 FH48NUV1 FDBG18NUV1 FDBG21NUV1 FDBG26NUV1 FDMG26NUV1 FDMG36NUV1 FDMG42NUV1 FDMG48NUV1 FDMG51NUV1 FDMG56NUV1 220V H 33 35 35 42 42 42 44 44 46 48 49 41 43 43 42 45 46 46 47 47 L 29 30 30 36 36 36 40 40 40 42 43 38 40 40 38 37 37 37 37 37 H 35 37 37 44 44 44 46 46 48 50 51 43 45 45 43 46 47 47 48 48 240V L 31 32 32 38 38 38 42 FH-NU 42 42 44
4D054245 4D054296

12.1.1 Indoor Unit


Measuring Location

FHC-NU

45 40 42 42 39 40 40 40 39 39
4D049441A

FDBG-NU

4D054358

FDMG-NU

Note:

Operation sound is measured in an anechoic chamber. Sound level will vary depending on a range of factors such as the construction (acoustic absorption coefficient) of the particular room in which the equipment installed.

56

SkyAir NU Series Cooling Only

ED24-631A

Sound Level

12.1.2 Outdoor Unit


dB(A) Model R18NUV1 220 V 49 240 V R18 21NU 50 Measuring Location

R21NUV1

54

55

R26NUV1

57

57
4D054355

R36NUV1 Model R26NUY1

55 380 V 57

56 415 V 57

R26~51NU

R36NUY1

55

56
4D054333

R42NUY1

57

58

R56NU

R48NUY1

59

60

R51NUY1

59

60
4D049423B

R56NUY1

56

58

Note:

Operation sound is measured in an anechoic chamber. Sound level will vary depending on a range of factors such as the construction (acoustic absorption coefficient) of the particular room in which the equipment installed.

SkyAir NU Series Cooling Only

57

Sound Level

ED24-631A

12.2

Octave Band Level


FHC21NUV1 FHC26NUV1 FHC36NUV1 FHC42NUV1 FHC48NUV1

12.2.1 Indoor Unit

FHC18NUV1

4D054296

4D054293

4D052541A

FH21NUV1 FH26NUV1

FH36NUV1

FH42NUV1

4D054245

4D052455

4D052456

FH48NUV1

Note: 220V 240V

4D052458

58

SkyAir NU Series Cooling Only

ED24-631A

Sound Level

FDBG18NUV1

FDBG21NUV1 FDBG26NUV1

FDMG26NUV1

4D054358

4D054357A

4D049441A

FDMG36NUV1

FDMG42NUV1 FDMG48NUV1

FDMG51NUV1 FDMG56NUV1

4D049427B

4D049431B

4D049433B

Note: 220V 240V

SkyAir NU Series Cooling Only

59

Sound Level

ED24-631A

12.2.2 Outdoor Unit


R18NUV1 R21NUV1 R26NUV1 R26NUY1

4D054355

4D054356

4D054333

R36NUV1 R36NUY1

R42NUY1

R48NUY1 R51NUY1

4D052428

4D052429

4D052430

R56NUY1

Note: V1 : 220V, Y1 : 380V V1 : 240V, Y1 : 415V

4D049423B

60

SkyAir NU Series Cooling Only

ED24-631A

Installation

13. Installation
13.1 Indoor Unit
13.1.1 FHC-NUV1

Names and functions of parts

k a

j i h f g d e b d c e f R18 21 26 36

R42 48

a Indoor unit b c d e Outdoor unit Remote controller Inlet air Discharged air

i j

Drain pipe Air inlet The built-in air filter removes dust and dirt.

f Air outlet g Air flow flap (at air outlet) h Refrigerant piping, connection electric wire

Drain pumping out device(built-in) k Drains water removed from the room during cooling. l Ground wire Wire to ground from the outdoor unit to prevent electrical shocks.
3PN07217-2A

SkyAir NU Series Cooling Only

61

Installation

ED24-631A

3PN07218-2B-5

62

SkyAir NU Series Cooling Only

ED24-631A

Installation

3PN07218-2B-6

SkyAir NU Series Cooling Only

63

Installation

ED24-631A

3PN07218-2B-7

64

SkyAir NU Series Cooling Only

ED24-631A

Installation

3PN07218-2B-8

SkyAir NU Series Cooling Only

65

Installation

ED24-631A

3PN07218-2B-9

66

SkyAir NU Series Cooling Only

ED24-631A

Installation

3PN07218-2B-10

SkyAir NU Series Cooling Only

67

Installation

ED24-631A

3PN07218-2B-11

68

SkyAir NU Series Cooling Only

ED24-631A

Installation

3PN07218-2B-12

SkyAir NU Series Cooling Only

69

Installation

ED24-631A

3PN07218-2B-13

70

SkyAir NU Series Cooling Only

ED24-631A

Installation

C : 3PN07218-2B-14

SkyAir NU Series Cooling Only

71

Installation

ED24-631A

3PN07218-2B-15

72

SkyAir NU Series Cooling Only

ED24-631A

Installation

3PN07218-2B-16

SkyAir NU Series Cooling Only

73

Installation

ED24-631A

3PN07218-2B-17

74

SkyAir NU Series Cooling Only

ED24-631A

Installation

3PN07218-2B-18

SkyAir NU Series Cooling Only

75

Installation

ED24-631A

3PN07218-2B-19

76

SkyAir NU Series Cooling Only

ED24-631A

Installation

3PN07218-2B-20

SkyAir NU Series Cooling Only

77

Installation

ED24-631A

3PN07218-2B-21

78

SkyAir NU Series Cooling Only

ED24-631A

Installation

3PN07218-2B-22

SkyAir NU Series Cooling Only

79

Installation

ED24-631A

3PN07218-2B-23

80

SkyAir NU Series Cooling Only

ED24-631A

Installation

13.1.2 FH-NUV1

Names and functions of parts

f e e

g d j b d c e f d h

a b c d e f g h i j k

Indoor unit Outdoor unit Remote controller Inlet air Discharged air Air outlet Air flow flap (at air outlet) Refrigerant piping, connection electric wire Drain pipe Air inlet The built-in air filter removes dust and dirt. Ground wire Wire to ground from the outdoor unit to prevent electrical shocks.
3PN07087-1A

SkyAir NU Series Cooling Only

81

Installation

ED24-631A

1PN07240B

82

SkyAir NU Series Cooling Only

ED24-631A

Installation

1PN07240B

SkyAir NU Series Cooling Only

83

Installation

ED24-631A

1PN07240B

84

SkyAir NU Series Cooling Only

ED24-631A

Installation

1PN07240B

SkyAir NU Series Cooling Only

85

Installation

ED24-631A

1PN07240B

86

SkyAir NU Series Cooling Only

ED24-631A

Installation

1PN07240B

SkyAir NU Series Cooling Only

87

Installation

ED24-631A

1PN07241A

88

SkyAir NU Series Cooling Only

ED24-631A

Installation

1PN07241A

SkyAir NU Series Cooling Only

89

Installation

ED24-631A

1PN07241A

90

SkyAir NU Series Cooling Only

ED24-631A

Installation

1PN07241A

SkyAir NU Series Cooling Only

91

Installation

ED24-631A

1PN07241A

92

SkyAir NU Series Cooling Only

ED24-631A

Installation

13.1.3 FDBG-NUV1

1PN07524

SkyAir NU Series Cooling Only

93

Installation

ED24-631A

1PN07524

94

SkyAir NU Series Cooling Only

ED24-631A

Installation

1PN07524

SkyAir NU Series Cooling Only

95

Installation

ED24-631A

1PN07524

96

SkyAir NU Series Cooling Only

ED24-631A

Installation

1PN07524

SkyAir NU Series Cooling Only

97

Installation

ED24-631A

13.1.4 FDMG-NUV1

1PN06319D

98

SkyAir NU Series Cooling Only

ED24-631A

Installation

1PN06319D

SkyAir NU Series Cooling Only

99

Installation

ED24-631A

1PN06319D

100

SkyAir NU Series Cooling Only

ED24-631A

Installation

1PN06319D

SkyAir NU Series Cooling Only

101

Installation

ED24-631A

1PN06319D

102

SkyAir NU Series Cooling Only

ED24-631A

Installation

13.2

Outdoor Unit

13.2.1 R18 21NUV1

1PN07605

SkyAir NU Series Cooling Only

103

Installation

ED24-631A

1PN07605

104

SkyAir NU Series Cooling Only

ED24-631A

Installation

1PN07605

SkyAir NU Series Cooling Only

105

Installation

ED24-631A

1PN07605

106

SkyAir NU Series Cooling Only

ED24-631A

Installation

1PN07605

SkyAir NU Series Cooling Only

107

Installation

ED24-631A

13.2.2 R26~56NUV1/Y1

1PN07127A

1PN07128B

108

SkyAir NU Series Cooling Only

ED24-631A

Installation

1PN07128B

SkyAir NU Series Cooling Only

109

Installation

ED24-631A

1PN07128B

110

SkyAir NU Series Cooling Only

ED24-631A

Installation

1PN07128B

SkyAir NU Series Cooling Only

111

Installation

ED24-631A

1PN07128B

112

SkyAir NU Series Cooling Only

ED24-631A

Installation

1PN07128B

SkyAir NU Series Cooling Only

113

Installation

ED24-631A

1PN07128B

114

SkyAir NU Series Cooling Only

ED24-631A

Installation

1PN07128B

SkyAir NU Series Cooling Only

115

Accessories

ED24-631A

14. Accessories
14.1 Indoor Unit
14.1.1 FHC-NU
Standard Accessories

3PN07218-2B-3

Optional Accessories

Name of Option Decoration Panel Sealing Member of Air Discharge Outlet Panel Spacer Fresh Air Intake Kit 3

Remark

Kit Name FHC18~26NU FHC36~48NU BYC125KW1 KDBHJ55K160 KDBP55H160WA KDDP55D160 KDDP55D160K KDDJ55X160 KKSJ55K160 KAFP556D80 KAFP557D80 KAFP552H80 KAFP553H80 KAFP556D160 KAFP557D160 KAFP552H160 KAFP553H160

Chamber Type Without T Joint With T Joint Direct Installation Type

Chamber Connection Kit 4 HighEfficiency Filter (Colorimetric Method 65%) (Colorimetric Method 90%) Replacement HighEfficiency (Colorimetric Method 65%) Filter (Colorimetric Method 90%) HighEfficiency Filter Chamber Replacement LongLife Filter Resin Net (Gravimetric Method 50%) Ultra LongLife Filter Replacement Ultra LongLife Filter Branch Duct Chamber Remote Controller Wired Type 2 Wireless Type Wired LCD Remote Controller with Weekly Schedule Timer Central Remote Controller Unified ON/OFF Controller Schedule Timer intelligent Touch Controller Adaptor for Wiring (Interlock for Fresh Air Intake Fan) 1 Wiring Adaptor for Electrical Appendices 1 Interface Adaptor for SkyAir Series Installation Box for Adaptor PCB

KDDFP55D160 KAFJ551K160 KAFP55D160 KAFJ55K160H KDJ55K80 KDJ55K160 BRC1C61 BRC7C613W BRC1D61 DCS302CA61 DCS301BA61 DST301BA61 DCS601C51 KRP1B57 KRP4A53 DTA102A52 KRP1B98
C : 3D054362 C : 3D052565

Note:

1. Installation box for adaptor PCB (KRP1B98) is necessary. 2. Wire for remote controller : Field supplied. 3. Refer to the Option Handbook for the detail. 4. When using the filter (HighEfficiency Filter or Ultra LongLife Filter) and the Fresh Air Intake Kit together, this kit is necessary.

116

SkyAir NU Series Cooling Only

ED24-631A

Accessories

14.1.2 FH-NU
Standard Accessories

1PN07240B

Optional Accessories
Name of Option Replacement LongLife Filter LType Piping Kit Remote Controller For Upward Direction Wired Type 1 Wireless Type Remark Kit Name FH21 26NU KAFJ501D80 KHFJ5F80 BRC1NU61 BRC7NU66
3D054225 3D052467

FH36~48NU KAFJ501D160 KHFJ5F160

Note:

1. Wire for remote controller : Field supplied.

14.1.3 FDBG-NU
Standard Accessories

1PN07524

Optional Accessories
Name of Option Remark Kit Name FDBG18NU KRC47-1 KRC47-2 KRC47-4 KDGF19A45 KKD19A1
4D048550A

FDBG21 26NU

Remote Controller with 3 Minutes Timer Digital Remote Controller with 3 Minutes Timer Digital Remote Controller With Switch for Duct Heater with 3 Minutes Timer Suction Grille Drain Pan Cover

KDGF19A71

Note:

1. If you use local remote controller, 3 minutes timer is necessary for the recycling guard of compressor. 2. Central controls using with VRV controller are available on request. Please consult DAIKIN.

SkyAir NU Series Cooling Only

117

Accessories

ED24-631A

14.1.4 FDMG-NU
Standard Accessories

1PN06319D

Optional Accessories
Name of Option Remark Kit Name FDMG26~56NU KRC47-1 KRC47-2 KRC47-4
4D054400 4D052569

Remote Controller with 3 Minutes Timer Digital Remote Controller with 3 Minutes Timer Digital Remote Controller With Switch for Duct Heater with 3 Minutes Timer

Note:

1. If you use local remote controller, 3 minutes timer is necessary for the recycling guard of compressor. 2. Central controls using with VRV controller are available on request. Please consult DAIKIN.

14.2

Outdoor Unit

14.2.1 R-NU
Optional Accessories
Drain Piping Kit Central Drain Plug

Name of Option

Kit Name R18NU R21NU KIS95 R26~56NU KKPJ5F180


4D052475B

118

SkyAir NU Series Cooling Only

ED24-631A

Remote Controller

15. Remote Controller


15.1 Operation
5 4 2 1

15.1.1 Wired Remote Controller : BRC1C61 (for FHC)

3 7 6 8 13 9 11 10 12 20 19 18

15

14

16

17

21

3PN07217-2A

SkyAir NU Series Cooling Only

119

Remote Controller

ED24-631A

15.1.2 Wired Remote Controller : BRC1NU61 (for FH)

3PN07204-2

120

SkyAir NU Series Cooling Only

ED24-631A

Remote Controller

15.1.3 Wireless Remote Controller : BRC7C613W (for FHC)

Fig.1

Fig.2

C : 3PA63363-4P

SkyAir NU Series Cooling Only

121

Remote Controller

ED24-631A

15.1.4 Wireless Remote Controller : BRC7NU66 (for FH)


FIgure 1

3PN07204-1-4

122

SkyAir NU Series Cooling Only

ED24-631A

Remote Controller

FIgure 2 (Explanation of Receiver)

3PN07204-1-5

SkyAir NU Series Cooling Only

123

Detail Explanation of Options

ED24-631A

16. Detail Explanation of Options


16.1 Ceiling Mounted Cassette Type (Multi Flow) [FHC]
16.1.1 BYC125KW1S Decoration Panel

BEFORE INSTALLATION
PRECAUTIONS Refer also to the installation manual attached to the indoor unit. ACCESSORIES Installation manual. NOTE TO INSTALLER Be sure to instruct the customer how to properly operate the system showing him/her the attached operation manual.

PREPARATION OF DECORATION PANEL


<<For this unit, you are able to select air flow directions. To discharge air in 2 or 3 directions, it is necessary to purchase optional blocking pad kit.>> HANDLING OF DECORATION PANELS Never place the panel facing down nor lean it against a wall nor leave it on a projecting object. Never touch or put pressure on the swing flap. (The swing flap may malfunction.) (1) Remove the suction grille from the decoration panel. 1) Push the suction grille lever inward and lift up the lever side. (Refer to Fig. 1.) 2) Detach the suction grille from the decoration panel by lifting the grille up approximately 45 degrees. (Refer to Fig. 2.)

45 Lever

Fig. 1 (2) Remove the service cover on the corner. Slide the service cover outward to remove. (Refer to Fig. 3.) Fig. 2

Fig. 3

124

SkyAir NU Series Cooling Only

ED24-631A

Detail Explanation of Options

INSTALLATION OF THE DECORATION PANEL TO THE INDOOR UNIT BODY


<<Refer to the installation manual attached to the indoor unit for the installation of the indoor unit.>> (1) Set the decoration panel to the indoor unit body by matching the position of the swing flap motor of the decoration panel to the piping position of the indoor unit as shown in Fig. 4. (2) Install the decoration panel. 1) Temporarily install the decoration panel to the indoor unit by hanging the latch on the opposite side of the swing flap motor of the decoration panel to the hook of the indoor unit body. (2 positions) 2) Temporarily hang the remaining 2 latches to the hooks on the sides of the indoor unit. (Be careful not to let the swing motor lead wire get caught in the sealing material.) 3) Screw all 4 hexagon head screws located right beneath the latches in approximately 5 mm. (Panel will rise.) 4) Adjust the decoration panel by turning it to the arrowed direction in Fig. 4 so that the ceiling opening is completely covered. 5) Tighten the screws until the thickness of the sealing material between the decoration panel and the indoor unit body reduces to 58 mm. Sealing material Indoor unit Ceiling material 5 ~ 8 mm

Air outlet

Decoration panel

Hook

Latch

1)

2) Piping position

2)

Swing flap motor 3)

4)

Fig. 4 PRECAUTIONS Improper screwing of the screws may cause the troubles shown in Fig. 5. Screw properly. Air leak

Air leak from ceiling

Contamination

Dew formation, dew dripping Fig. 5

SkyAir NU Series Cooling Only

125

Detail Explanation of Options

ED24-631A

If gap is still left between the ceiling and the decoration panel after screwing the screws, readjust the indoor unit body height. (Refer to Fig. 6.)

Adjustment of the indoor unit body height from the holes in the corner of the decoration panel is possible if the indoor unit is kept leveled and the drain piping, etc. is unaffected.

No gaps is allowed. Fig. 6 (3) Wiring of the decoration panel (Refer to Fig. 7.) 6) Connect the connectors for swing flap motor lead wire installed on the decoration panel. If connectors are not connected, the malfunction display (A7) appears on the remote controller. Connect the connectors properly. Make sure that the swing flap motor lead wire is not caught between the indoor unit and the decoration panel.

6)
Indoor unit side Decoration panel side

Wiring

Fig. 7

Instruction Diagram (It differs from the actual state.)

INSTALLATION OF SUCTION GRILLE AND SERVICE COVER


(1) Install the suction grille. Install by reversing the procedure shown in PREPARATION OF DECORATION PANEL. It is possible to install the suction grille in 4 directions by turning the suction grille. Change the direction when adjusting the direction of the suction grille of multiple units or in meeting customers demands. NOTE) Be careful not to get swing flap motor lead wire get caught when installing the suction grille. (2) Install the service cover on the corner. 1) Attach the string of the service cover to the pin of the decoration panel as in Fig. 8. Pin 2) Install the service cover over the decoration panel.

Install the service cover by sliding 4 latches to fit into the holes on the decoration panel.

Fig. 8

126

SkyAir NU Series Cooling Only

ED24-631A

Detail Explanation of Options

16.1.2 KDBHJ55K160 Sealing Member of Air Discharge Outlet


Caution
zRefer to the installation manual for both indoor unit and the decoration panel. zWhen you install other optional kit, it may not be possible to select the 3-way or 2-way air discharge. For details, refer to the manual for the optional kit or the catalogue. zContents of Kit Prior to installation make sure you have the complete kit of parts.
Name Quantity Shape and marking Sealing material(A) 1 piece Sealing material(B) 1 piece Sealing material(C) 1 piece Sealing material(D) 1 piece

Name Quantity Shape and marking

Insulation for top plate 1 piece 1 piece

Insulation for side plate 1 piece 2 pieces 1 piece

Moisture absorber for bell-mouth

Moisture absorber for horizontal vane

2 pieces

1 piece

5 kinds

J : 1P012222B

SkyAir NU Series Cooling Only

127

Detail Explanation of Options

ED24-631A

Installation of the insulation


to the side of indoor unit.
48 class

(1) Installation to the side plate Adhere insulation for side plate
26 class

Put the wire through the slit of the insulation.

When adhering insulation, align its edge with the bottom line of casing.

When adhering insulation, align its edge with the bottom line of casing.

(2) Installation to the top plate Adhere insulation for top plate

to the top of the indoor unit.

(3) Adhere the moisture absorber for horizontal vane to the edge of the horizontal vane of air outlet (Fig. 2). (Choose the same color as panel.)
Horizontal vane Moisture absorber for horizontal vane Fig. 2

Align it with the upper edge of horizontal vane.


Horizontal vane Moisture absorber for horizontal vane

Fig. 1

(4) Adhere the moisture absorber in accordance with the reference surface without wrinkles. (Fig. 4) Adhere the moisture absorber in accordance with the reference line . (Fig. 5)
Reference surface Adhere it from the edge of switch box. Switch box Swing connector Swing motor Sticking reference (Fig. 3)

Bellmouth

Sticking reference Fig. 4 Fig. 5 JC : 1P012222B

128

SkyAir NU Series Cooling Only

ED24-631A

Detail Explanation of Options

16.1.3 KDBP55H160WA Panel Spacer


Installation

1P136564E

SkyAir NU Series Cooling Only

129

Detail Explanation of Options

ED24-631A

1P136564E

130

SkyAir NU Series Cooling Only

ED24-631A

Detail Explanation of Options

16.1.4 KDDP55D160(K) Fresh Air Intake Kit (Chamber Type)


Installation

SkyAir

FHC18~48NU

18~26NU 36~48NU

240 298

C : 3K011144A

SkyAir NU Series Cooling Only

131

Detail Explanation of Options

ED24-631A

3K011144A

132

SkyAir NU Series Cooling Only

ED24-631A

Detail Explanation of Options

SkyAir NU Series Cooling Only

133

Detail Explanation of Options

ED24-631A

16.1.5 KDDJ55X160 Fresh Air Intake Kit (Direct Installation Type)


The fresh air is taken into the unit by the indoor unit fan or duct fan, which is field supplied. The location of fresh air intake port will be changeable by installing the duct fan.

Dimension

J : D3K2175

Installation

2P066796C

134

SkyAir NU Series Cooling Only

ED24-631A

Detail Explanation of Options

2P066796C

SkyAir NU Series Cooling Only

135

Detail Explanation of Options

ED24-631A

16.1.6 KAFP556D80 160 HighEfficiency Filter (Including Filter Chamber) KAFP557D80 160 HighEfficiency Filter (Including Filter Chamber)
Combination table
HighEfficiency Filter (Set) KAFP556D80 KAFP557D80 KAFP556D160 KAFP557D160 Replacement HighEfficiency Filter KAFP552H80 KAFP553H80 KAFP552H160 KAFP553H160 HighEfficiency Filter Chamber KDDFP55D160

16.1.7 KAFP552H80 160 Replacement HighEfficiency Filter KAFP553H80 160 Replacement HighEfficiency Filter
Specifications
Replacement HighEfficiency Filter HighEfficiency Filter Chamber Collecting Efficiency (%) Initial Pressure Loss (Pa) Final Pressure Loss (Pa) Filter Life (h) Models to be Applied KAFP552H80 KAFP552H160 KAFP553H80 KAFP553H160 KDDFP55D160 65% (NBS Colorimetric method) 90% (NBS Colorimetric method) 34 or less 98 or less Nonwoven Fabric of Synthetic Fiber Nonwoven Fabric of Synthetic Fiber 2,500 h (Dust Concentration 0.15 mg / m3) 1,800 h (Dust Concentration 0.15 mg / m3) 18~26NU 36~48NU 18~26NU 36~48NU

Precaution at use 1. The highefficiency filter, and the other filter can not be installed together. 2. The unit should be operated with 4-way discharge when the highefficiency filter is installed. It can not be applied to the high ceiling room. 3. Field setting by remote controller is necessary when the highefficiency filter is installed. Dimension
560

Model KAFP552H80, KAFP553H80 KAFP552H160, KAFP553H160

AA 25 45
J : D3K04256A

16.1.8 KRP1B98 Installation Box for Adaptor PCB


Dimension
Model No. Item Applicable Model Adaptor for Wiring KRP1B98 FHC18~48NU KRP1B57 KRP4A53

136

AA
D3K2169

10

0 540 -2

10

560

SkyAir NU Series Cooling Only

ED24-631A

Detail Explanation of Options

16.1.9 KDDFP55D160 HighEfficiency Filter Chamber


Installation

SkyAir

FHC18~26NU

SkyAir

FHC36~48NU

C : 3K011148B

SkyAir NU Series Cooling Only

137

Detail Explanation of Options

ED24-631A

3K011148B

138

SkyAir NU Series Cooling Only

ED24-631A

Detail Explanation of Options

16.1.10 KAFJ551K160 Replacement LongLife Filter for Decoration Panel


Specifications
Collecting Efficiency (%) Initial Pressure Loss (Pa) Final Pressure Loss (Pa) Filter Number of Sheets Included Life (h) Models to Be Applied 65 (Gravity Method) 8 or less 49 or less MildewProof Resin Net 1 2,500 h (Dust Concentration 0.15 mg / m3) 18~48NU
J : D3K2170C

16.1.11 KAFP55D160, KAFJ55K160H (Replacement) Ultra LongLife Filter (Including Filter Chamber)
Specifications
Ultra LongLife Filter Replacement Ultra LongLife Filter HighEfficiency Filter Chamber Collecting Efficiency (%) Initial Pressure Loss (Pa) Final Pressure Loss (Pa) Filter Life (h) Models to Be Applied

Precaution at use 1. The Ultra longlife filter, and other filter can not be installed together. KDDFP55D160 2. Field setting by remote controller is necessary when the Ultra 50 (Gravity Method) long life filter is installed. 8 or less Refer to the installation manual of Ultra longlife filter for 49 or less setting. MildewProof Resin Net 3. Filter cleaning period can not be displayed on the monitor when 5,000 h the Ultra longlife filter is installed. (Dust Concentration 0.3 mg / m3) Refer to the left table and clean (with water) the filter 18~48NU periodically.
KAFJ55K160H
J : D3K2174A

KAFP55D160

Installation Iocation Filter Cleaning Period Dirty Area Not Dirty Area Every 5,000 hrs Every 10,000 hrs

SkyAir NU Series Cooling Only

139

Detail Explanation of Options

ED24-631A

16.1.12 KKSJ55K160 Chamber Connection Kit


Dimension

J : D3K2186

Installation

3P089651C

140

SkyAir NU Series Cooling Only

ED24-631A

Detail Explanation of Options

16.1.13 KDJ55K80 160 Branch Duct Chamber


Installation

SkyAir NU Series Cooling Only

141

Detail Explanation of Options

ED24-631A

142

SkyAir NU Series Cooling Only

ED24-631A

Detail Explanation of Options

16.2

Ceiling Suspended Type [FH]

16.2.1 KAFJ501D80 160 Replacement LongLife Filter


Specifications
Model Item Effective Life, Average Efficiency Initial Pressure Loss (Pa) Final Pressure Loss (Pa) Filter Materials Nos. Required Applicable Model Mold Prevention Resin Net 2 pieces 21 26NU KAFJ501D56 KAFJ501D80 KAFJ501D112 mg/m3 KAFJ501D160 2,500 hours (at Dust Particle Concentration of 0.15 10 or less 59 or less Mold Prevention Resin Net 3 pieces 36~48NU
J : D3K3074A

), 45% (by Weight Method)

16.2.2 KHFJ5F80 160 LType Piping Kit


Application purpose This kit must be bent inside the unit as shown below, when the refrigerant piping is carried out in a ceiling space. This L shape kit is an optional accessory which has been developed for improving the work of the processing on site.
Model Item Applicable Model KHFJ5F50 KHFJ5F60 KHFJ5F80 21 26NU KHFJ5F160 36~48NU

KHFJ5F50~160

Installation

SkyAir NU Series Cooling Only

143

Detail Explanation of Options

ED24-631A

16.3

Duct Connection Low Static Pressure Type [FDBG]

16.3.1 KKD19A1Drain Pan Cover


Installation

FDBG182126NUV1

C : 1P067376A

144

SkyAir NU Series Cooling Only

ED24-631A

Detail Explanation of Options

16.4

Outdoor Unit
Use this plug to connect a drain hose to an outdoor unit. Outlook KIS95

16.4.1 KIS95 Drain Piping Kit

Drain hose connection dia 16ID. Note:

KIS95 Drain piping (With Y joint) plug (3 pcs.)

1. This is the joint for attaching a vinyl hose (field supplied). This is used between the drain hole which is on the bottom plate of outdoor unit and vinyl hose. 2. Drain water accumulate to the bottom of outdoor unit it depends on the situation of operation. But it is necessary to connect drain hose not to be spread the drain water over the neighbors, when it is installed on the wall. 3. The position of holes are unfit to connect with outdoor units in some models. In this case, use it without Y joint.

16.4.2 KKPJ5F180 Central Drain Plug

SkyAir NU Series Cooling Only

145

Warning

Daikin Industries, Ltd.s products are manufactured for export to numerous countries throughout the world. Daikin Industries, Ltd. does not have control over which products are exported to and used in a particular country. Prior to purchase, please therefore confirm with your local authorized importer, distributor and/or retailer whether this product conforms to the applicable standards, and is suitable for use, in the region where the product will be used. This statement does not purport to exclude, restrict or modify the application of any local legislation. Ask a qualified installer or contractor to install this product. Do not try to install the product yourself. Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion. Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or contractor to install those parts and accessories. Use of unauthorized parts and accessories or improper installation of parts and accessories can result in water or refrigerant leakage, electrical shock, fire or explosion. Read the User's Manual carefully before using this product. The User's Manual provides important safety instructions and warnings. Be sure to follow these instructions and warnings. If you have any inquiries, please contact your local importer, distributor and/or retailer.

Cautions on product corrosion


1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced. 2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided.
About ISO9001 ISO 9001 is a plant certification system defined by the International Organization for Standardization (ISO) relating to quality assurance. ISO 9001 certification covers quality assurance aspects related to the design, development, manufacture, installation, and supplementary service of products manufactured at the plant. About ISO 14001 ISO 14001 is the standard defined by the International Organization for Standardization (ISO) relating to environmental management systems. Our group has been acknowledged by an internationally accredited compliance organisation as having an appropriate programme of environmental protection procedures and activities to meet the requirements of ISO 14001.

JMI-0107

JQA-1452

EC99J2044

JQA-E-90108

Dealer
Head Office: Umeda Center Bldg., 2-4-12, Nakazaki-Nishi, Kita-ku, Osaka, 530-8323 Japan Tokyo Office: JR Shinagawa East Bldg., 2-18-1, Konan, Minato-ku, Tokyo, 108-0075 Japan

http://www.daikin.com/global/
c All rights reserved

Specifications, designs and other content appearing in this brochure are current as of July 2006 but subject to change without notice.

Printed on 100% recycled paper with soy ink.

ED24-631A Printed in Japan 08/2006 K FS