4090-9001 Supervised IAM Installation Instructions


Mechanically Installing the Supervised IAM Install the Supervised IAM into a UL Listed single-gang, 4-inch square, or 4-inch octagonal electrical box (not supplied) using Figure 4 as a reference. Mount the Supervised IAM to the electrical box as follows: 1. 2. Insert the Supervised IAM into the electrical box; the attached field wiring holds the Supervised IAM in place inside the electrical box. Secure the cover to the back box using the two #6/32 flathead screws.

Cautions and Warnings


DO NOT INSTALL ANY SIMPLEX PRODUCT THAT APPEARS DAMAGED. Upon unpacking your Simplex product, inspect the contents of the carton for shipping damage. If damage is apparent, immediately file a claim with the carrier and notify Simplex. ELECTRICAL HAZARD - Disconnect electrical power when making any internal adjustments or repairs. Servicing should be performed by qualified Simplex Representatives. STATIC HAZARD - Static electricity can damage components. Ground yourself before opening or installing components.
Field Wiring

Cover (Not Supplied)

UL Listed Single-Gang Electrical Box (Not Supplied)

Introduction IDNet The 4090-9001 Supervised Individual Addressable Module (IAM) provide four-state status information (NORMAL, OPEN, CURRENT-LIMITED, and SHORT) to the 4010 Fire Alarm Control Panel (FACP) via the IDNet channel. The IDNet channel provides the communication link between Supervised IAM and 4010 FACP and powers the entire IAM circuitry. A typical application for this module would be to monitor a waterflow switch. MAPNET II The 4090-9001 Supervised IAM provides three-state status information (NORMAL, OPEN, and ALARM) to the host FACP via the MAPNET II channel. Applications that require current limit sensing are not compatible with MAPNET II channels (Tamper/Waterflow on the same IAM, Manual release/abort, etc.). The MAPNET II channel provides the communication link between the Supervised IAM and host 4100, or 4120, or 4020 FACP and powers the entire IAM circuitry. Installation
#6/32 Flathead Screw (Not Supplied)
Label LED

4090-9001 Supervised IAM Assembly

Supervised IAM installation consists of the following: Setting the Supervised IAMs address Making electrical connections to the Supervised IAM Mechanically installing the Supervised IAM
DIP Switch (Under Re-sealable Label)
Front View

Note: Simplex offers semi-flush and surface covers (ordered separately) with a light pipe. The cover(s) with light pipe allow viewing of the communications LED without taking the cover off. Installation of the 4090-9806 semi-flush cover and 4090-9807 surface cover are detailed in publication 4090 IDNet Semi-Flush/Surface Covers and IAM Bracket Installation Instruction (574-796). Figure 4. Supervised IAM Back Box Installation

Terminal

Rear View

Note: The LED flashes approximately once every three seconds to indicate valid communications with the FACP.

Figure 1. Supervised IAM Installation 574-331 Rev. E


2000 Simplex Time Recorder Co., Westminster, MA 01441-0001 All specifications and other information shown were current as of publication, and are subject to change without notice. IDNet is a trademark of the Simplex Time Recorder Company. MAPNET II Communication Net is protected by U.S. Patent No.4,796,025.

574-331 Rev. E

Technical Manuals Online! - http://www.tech-man.com

Setting the Supervised IAMs Address Note: The IDNet channel (4010 FACP only) supports address codes 1 through 250. The MAPNET II channel (4100, or 4120, or 4020 FACP) supports address codes 1 through 127. Each Supervised IAM has a unique address. The address of the IAM is set via an eight position DIP switch (Figure 1), DIP switch position 1 is the least significant bit (LSB) and position 8 is the most significant bit (MSB). Set the IAMs address using Figure 2 as reference. Use a small screwdriver or pen to set the switches. The device address for the Supervised IAM should be written on the re-sealable label, this information provides an aid in troubleshooting the system. Note: DIP switch in 1 position is ON while DIP switch in 0 position is OFF.
LSB
1 ON OFF 2 3 4 5 6 7

Making Electrical Connections to the Supervised IAM Input and output signals connect to the Supervised IAM via the terminals (1-4) as illustrated in Figure 1. Terminal connections for the IAM are illustrated in Figure 3. CAUTION: Do not loop wire under terminals. Break wire runs to provide supervision.
MAPNET II/IDNET To Next Device

MSB
8

DIPSWITCH IS SHOWN SET AT ADDRESS 7.

1 = ON

0 = OFF

DIP SWITCHES 5 THRU 8 0000 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 1000 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 0100 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 1100 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 0010 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 1010 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 0110 96 97 98 99 100 101 102 103 104 105 106 107 108 109 110 111 1110 112 113 114 115 116 117 118 119 120 121 122 123 124 125 126 127 0001 128 129 130 131 132 133 134 135 136 137 138 139 140 141 142 143 1001 144 145 146 147 148 149 150 151 152 153 154 155 156 157 158 159 0101 160 161 162 163 164 165 166 167 168 169 170 171 172 173 174 175 1101 176 177 178 179 180 181 182 183 184 185 186 187 188 189 190 191 0011 192 193 194 195 196 197 198 199 200 201 202 203 204 205 206 207 1011 208 209 210 211 212 213 214 215 216 217 218 219 220 221 222 223 0111 224 225 226 227 228 229 230 231 232 233 234 235 236 237 238 239 1111 240 241 242 243 244 245 246 247 248 249 250 251 252 253 254 255

MAPNET II/IDNET (See Notes)

0000 1000 0100 1100 0010 1010 0110 1110 0001 1001 0101 1101 0011 1011 0111 1111

(See Note 5)

See Note 4

Notes: 1. 2. 3. 4. 5. When connecting two wires to one terminal, position one wire on each side of the terminal screw. IDNet and MAPNET II lines are 18 AWG twisted pair (shield recommended). Maximum allowable run from FACP to farthest device not to exceed 2500 feet. Maximum total wire (including all T-Taps) from FACP is 10000 feet. Maximum wire length is 400 feet, #18 AWG. Refer to Field Wiring Diagram 842-073 for further information on wiring Supervised IAMs to IDNet. Refer to Field Wiring Diagrams 841-804 or 841-996 for further information on wiring Supervised IAMs to MAPNET II. IDNet and MAPNET II wiring are supervised and power-limited. Figure 3. Supervised IAM Connections

MAPNET II supports address codes 1 through 127 only.

Figure 2. Supervised IAM Address Chart 4010 FACP (IDNet Channel) Configure the Supervised IAM to the 4010 panel using the 4010 Fire Alarm - Installation and Programming (574-187) and 4010 Fire Alarm - Installing, Operating, and Programming Instructions (574-052). Refer to 4010 panel label 526-444 for appropriate revision of the instructions to be used. 4100/4120/4020 FACP (MAPNET II Channel) Configure the Supervised IAM to the host FACP using the 4100, 4120, or 4020 Programmers Report. The Supervised IAM address and location must match up with the address listed in the specification sheets of the 4100, 4120, or 4020 Programmers Report.