Sunteți pe pagina 1din 3

HBL POWER SYSTEMS LTD

COMPLIANCE SHEET FOR HVPNL

TECHNICAL SPECIFICATION FOR 220V-100 AH, 220V-200 AH AND 48V-300AH BATTERY BANKS

S. No

Clause No. 1.0

Compliance/ Deviation Cells are designed, Manufactured and tested (Acceptance Tests). Packing, forwarding and dispatch as per commercial terms and condition agreed up on. Accessories shall be supplied as per our regular supplies. Erection/maintenance tools and specific tools are not in scope of supply.

2 3 4 5 6 7 8 9 10 11

2.0 2.0.1

Complied. Noted.

2.0.2 2.1 3.1

Battery rating taken as per BOQ. Noted. Recommended operating temperature is 27deg.C. Complied. Scope of Supply is Battery bank and Standard Accessories. Safety equipment like front cover and PVC Sleeves for ICC's only will be given. For short durations not exceeding 30 45 minutes battery can be operated at 50deg.C. Complied Grid design as per our standards. Complied Complied Deviated .The Material used in Separator is AGM (Absorbent Glass Mat) Complied

3.2 3.3 3.4 3.5 3.6

12 13

3.7 3.8

Complied. The terminals Shall have Lead Plated Copper Alloy Inserts. Complied. Copper connectors with PVC Sleeves shall be given as per our regular supplies, Silicon sleeves shall not be given

14 15 16 17 18 19

3.9 3.10 3.11 3.12 3.13 3.14

Complied. Self resealing, pressure regulated and explosion proof vent plugs. VRLA batteries are supplied in M.S. Stackable modules and provided with acid resisting epoxy powder coating and modules are fitted with Stainless Steel Bolts & Nuts. Complied 20 Years Design Life at 27C on full float with recommended charging methods. Torque wrench and cell testing voltmeter are not in our scope of supply. Type test reports as per IEC 60896-21&22; 2005 standard of similar design/type shall be provided.

20 21 22 23 24 25 26 27 28 29 30 31

3.14.1 3.14.2 3.15 3.16 4.0 4.1 4.1 (c ) 4.1.1 4.2 5.0 6.0 7.0

Complied. Complied. Complied Complied. Tools & Tackles will not be provided. Complied Complied Will not be given Will not be given Complied Complied (Instructions Cards inbuilt with operational and Instructional manual). Only Acceptance tests shall be performed as per relevant standards Schematic layout attached

32 33 34

8.0 9.0 10.0

Complied. Type test reports of similar design type will be provided. Data Sheet Attached Separate Stands, multimeters will not be supplied. Inter-connectors, cell no. plates with stickers Shall be supplied as per our standards and spanners will be provided at extra cost.

35

11.0

Shall be furnished during detailed Engineering.

S-ar putea să vă placă și