FMEA Number:
SJ51-000007-01
Prepared By: William Chai FMEA Date (Orig): 5th July 2006 (Rev) 0
Process Function
S e v
Requirements Return Control Valve PCW System fail - full close 1) Production tripped 2) No cooling at machine
C l a s s
O c c u r
D e t RPN e c
Recommended Action(s)
1) Half-yearly PM 2) Ten years 1 overhaul 3) Online monitoring 1) Rounds and readings (visual 1 inspection). 2) Replace when detect leaking
27
Tank leak
64
1) Use manual level meter. 2) Yearly calibration. 2 2 3) Interlock control. 4) Online monitoring with alarm
36
William July 06
1) LOTO the pot with authorized person to unLOTO. 8 1 7 2) Tighten chemical dosing procedure
56
SQ29-000002-01
Page 2 of 2
FMEA Number:
SJ51-000007-01
Prepared By: William Chai FMEA Date (Orig): 5th July 2006 (Rev) 0
Process Function
S e v
C l a s s
O c c u r
D e t RPN e c
Recommended Action(s)
Pump fail
27
Pump fail
Power dipped.
9 1 5
45
27
81
Filter choked
1) Production tripped Control limit for filter change is not sensitive 1) Change filter when DP at 0.5bar. 2 2) Flow, DP and 3 pressure online monitoring.
54
William July 06
Tighten DP level to 0.15bar for alert and 0.25bar trigger filter change.
9 1 2
18