Volume of installation: Max. service pressure: Temperature range: ND of closed network: 0,5 to 40 m3 10 bar 0 to + 100C 15 to 250
APPLICATIONS
Basic role of KIDSON is to protect heating systems from sludge by constantly eliminating matter in suspension. KIDSON is especially suitable for: residential buildings; service sector.
Kidson 1, (mounted)
Kidson 4, (mounted)
KIDSON
ADVANTAGES
Evacuation of natural sludge that is NON-POLLUTING and DOES NOT HARM THE ENVIRONMENT. More efficient energy use: clean networks, no more blocked pipes or local overheating. Properties of the water and the flow capacity of the installation remain stable for a longer time. Separator made of 316 stainless steel. Automatic flow equalization valve. Circulators with wet rotors. Set factory-adjusted. Easy to install and maintain.
1 0
1 11
9 5
2 5 4
DESIGN
KIDSON is a complete set delivered as an easy-to-assemble kit including:
A separator, a non-moving stainless steel part with bar magnets mounted on guides. A hydraulic and electromechanical assembly having a wet-rotor circulator specific to each model, a drain valve, a dynamic equalization valve, and a breather valve, a degasser, a support foot or arm, depending on the model, and connecting hoses.
10
KEY
A control box.
IDENTIFICATION
KIDSON 0.5
size of set (0.5 - 1 - 2 - 3 - 4 - 5 )
01 Control box (wall mounting). 02 Circulator specific to each Kidson model. 03 Separator with sludge retention chamber. 04 Magnets. 05 Braid-reinforced hoses connected to separator inlet and outlet. 06 Flush valve.
07 Automatic degasser. 08 Isolating valve. 09 Equalization valve. 10 *Support foot. 11 Breather valve. 0A Delivered pre-assembled. * Support foot for Kidson 3 ; 4 and 5
Arm for Kidson 0.5, 1, and 2.
TECHNICAL DATA
CONTROL BOX For 230-V single-phase power. On/Off switch. CIRCULATOR Wet rotor; type MXL, MYL, or CXL. For 230-V single-phase power. Class F insulation. EQUALIZATION VALVE Flow regulation cartridge. Direct selection, without adjustment, of optimal flow. Dynamic equalization assured.
KIDSON
OPERATING PRINCIPLE
KIDSON efficiently removes sludge from heating systems by means of natural physical phenomena. It operates by physical separation through the combined actions of: GRAVITY + FILTRATION + THE MAGNETIC EFFECT + THE PRESSURE-RELIEVING EFFECT of the separator. Water from the system enters the separator through the lower pipe. The constant thrust of the circulator drives the water slowly first down, then up in the separator. Particles in suspension fall by gravity - their own weight - into the bottom of the settling chamber. A millimetric filter traps floating matter (oakum, polystyrene). The multipolar magnetic field causes ferromagnetic particles to condense on the inside wall of the separator. The separator acts as a "pressure reliever" in the fluid flow and promotes degassing through the automatic air bleed. The system is emptied by hand: the circulator is stopped, the quarter-turn valves are opened and closed, and the bar magnets are moved (to eliminate the magnetic field). When the system is drained, the bottom housing of the deconcentration chamber is cleaned automatically by a countercurrent flow.
deflector
SLUDGE REMOVAL
KIDSON 3 ; 4 and 5
CHOICE OF SET
Return pipe ND Max. installation vol. 0.5Vmax.1m3 01Vmax.3m3 03Vmax.10m3 10Vmax.15m3 15Vmax.20m3 20Vmax.40m3 nbr housing units 10 40 120 170 220 300
15
20
25
32
40
50
65
80
100
125
150
200
250
Kidson 0.5 Kidson 0.5 Kidson 0.5 Kidson 1 Kidson 1 Kidson 2 Kidson 2 Kidson 3
Kidson 3 Kidson 3 Kidson 4 Kidson 4 Kidson 4 Kidson 4 Kidson 4 Kidson 5 Kidson 5 Kidson 5 Kidson 5 Kidson 5 Kidson 5 Kidson 5 Kidson 5
KIDSON
DIMENSIONS
FEATURES
a) Electrical Uses single-phase, 230-V, 50-Hz power. Connections made in factory: Motor-circulator.
D1
Connections remaining to be made: Single-phase mains to terminals of the general switch on the box. Box-circulator. b) Installation Bypass-mounted on system circuit. Attached to wall, or to floor by anchor bolts (not supplied). Assembly by threaded ties. Three hydraulic connections: Set inlet. Set outlet. Sludge drain (provide with disconnection on vented outfall).
NOTE The installation must be topped up when sludge is removed.
L1
1m
1m 3 L2
H2
H3
D1
H4
c) Packaging Set delivered in kit form in cardboard packaging, with directions for installation. d) Maintenance Manual emptying (procedure described in maintenance manual). COMPULSORY SUPPLIES Isolating valves must be installed at the inlet and outlet of product.
H4 1m H2 1m 2 1 H3 3 H1 L1 L2
KIDSON 3, 4 and 5
ORDER REFERENCE
H1 mm
H2 mm
H3 mm
H4 mm
L1 mm
L2 mm
D1 mm
1 tapped inlet
2 tapped outlet
3 tapped blowoff
nbr. magnets
mass kg
capacity litres
**flow l/h
type of circulator
1 2 4 6 12 12
MYL 30-25 MXL 50-32 CXL 80-32 CXL 80-32 CXL 80-32 CXL 100-32
* wall mounting for these models. ** each of the six models of the line has its own operating flow. It is preset by the regulation valve. There is no manual adjustment.
4 53 bd de la Rpublique - Espace Lumire - Bt. 6 - 78403 Chatou Cedex FRANCE Tel: +33 (0) 820 873 624 - Fax: +33 (0)1 30 09 82 34 - www.salmson.com