Documente Academic
Documente Profesional
Documente Cultură
Fans
Systemair Fans
Product catalogue
Systemair 2012. Systemair reserves the right to make technical changes. For updated documentation, please refer to www.systemair.com.
Contents
Systemair..................................................................................4-5 Fans Overview........................................................................6-7 Product range...........................................................................8-9 A good indoor climate is vital................................................... 10 Selection tools........................................................................... 11
Technical data
Circular duct fans......................................................... 16-63 Rectangular duct fans............................................... 64-121 Roof fans................................................................. 122-165 Axial fans................................................................. 166-199 Explosion proof fans............................................... 200-235 Smoke extract fans................................................. 236-273 Fans for aggressive media...................................... 274-285 Centrifugal fans....................................................... 286-311 Domestic fans.......................................................... 312-317 Electrical accessories.............................................. 318-345
Accessories.............................................................. 346-390
Systemair
The straight way
The straight way was our first production idea and led to the circular duct fan. Today it represents our ambition to simplify the life of our customers. Stocked products are delivered in Europe within 24 hours from local warehouses and within 72 hours from distribution centres. High product quality, correct technical data and fast deliveries are always our main focus.
Technical data
Our development centre in Skinnskatteberg is one of the most modern in Europe for airflow, acoustic, efficiency and low velocity measurements on air terminal devices, etc. All measurements are performed in compliance with applicable standards as set out in AMCA and ISO.
Systemair
Systemair was established in Sweden in 1974 and is today the parent company in an international group with 60 subsidiaries and approximately 2800 employees. The Group's head office and largest production plant is located in Skinnskatteberg, Sweden with some 400 employees and a floor area of 50000 m2.
Production
We are proud of our production units. The aim has been to have both effective production of bulk products and, at the same time, an efficient and flexible approach to producing small volumes. This has steered our choice of machinery and how we plan our production, with focus on the working environment. Our premises are light and pleasant and we invest in tools that facilitate work and provide our employees with a safe and efficient workplace.
Systemair is certified according to ISO Bouctouche Canada 9001 and ISO 14001. Our quality system allows us to continuously improve our In Bouctouche, Canada we primarily products and our customer service. Certi- produce ventilation products for the fication means that we have undertaken North American market. to minimise our environmental impact. We always take the environment into consideration when choosing sub-suppliers, materials, production methods, etc. An important factor is that we continuously work to reduce our energy consumption and reduce waste. Through increased recovery and heightened awareness we have been able to reduce our waste by 90%. Quality and environment management systems are under continuous development. These are audited twice a year by the certification body BVQI (Bureau Veritas Quality International). Detailed product information can be found on our website, www.systemair.com.
Production in Skinnskatteberg is virtually fully automated with modern machinery featuring advanced computer support. Also located here is the company's most advanced test facility for measuring.
Skinnskatteberg Sweden
Main plant The main plant in Skinnskatteberg houses one of the company's three central warehouses and the largest production facility as well as the group's head office. Fans and accessories are produced here as stock items. Klockargrden Systemair's compact air handling units are made at Klockargrden in Skinnskatteber g. Frico's central warehouse of approximately 8000 m2 is also located here.
Hssleholm - Sweden
VEAB VEAB in Hssleholm manufactures heating and cooling coils as well as fan heaters.
Ukmerge Lithuania
Production of air handling units.
Bratislava Slovakia
The factory in Bratislava manufactures air distribution products and fire dampers.
Maribor Slovenia
The factory in Maribor, Slovenia specialises in high temperature centrifugal fans for flue gas ventilation.
Madrid Spain
The factory in Madrid, Spain produces air handling units mainly for the southern European, Asian, and African market.
Hasselager Denmark
The factory in Hasselager, Denmark manufactures large air handling units to Eurovent standards.
Windischbuch Germany
In Windischbuch, Germany a broad assortment of fans are manufactured, of which the majority are stock items. One of Systemair's central warehouses is located here.
Fans Overview
Systemair has a wide range of fans for use in various applications from small office premises to larger industrial applications. Common to all items in the range is that components have been developed to satisfy stringent demands for low energy consumption. The fans have all undergone extensive testing, both in the laboratory and out in the field, in order to comply with current and future demands for low energy consumption. All products are also manufactured to comply with environmental requirements.
Jet fans
Systemair jet fans for Car Park Ventilation, axial or centrifugal solutions, certified in accordance with EN 12101-3. Complete solutions including control systems and CFD. Technical data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 194-196
300C 120min
Systemair offers different types of smoke and heat extract fans: Centrifugal roof and box fans, centrifugal wall/ duct fans and axial fans. All fans are approved for dual purpose ventilation, i.e. for normal daily ventilation and for emergency ventilation in case of a fire.
400C 120min
300C 120min
Horizontal units
A broad range of horizontal air handling units with or without heat recovery. Useable everywhere from minor premises to schools, stores and larger offices. Air flow: 20-1500 l/s
Vertical units
A broad range of vertical air handling units with or without heat recovery. Useable everywhere from minor premises to schools, stores and larger offices. Air flow: 20-1500 l/s
residential Ventilation
Complete energy-efficient air handling units with heat recovery and built-in control systems. Designed to be mounted over the cooker, on walls or horizontally in attics.
Residential units
For homes with living areas of 60-320 m .
2
Cooker hoods
Ideal for capturing odours even at low airflows.
Nozzle diffusers
Optimum flexibility and comfort in air distribution for rooms
Volume control
Dampers, plenum boxes, VAV/CAV and duct accessories.
Heat recovery
In areas with a relatively low average annual temperature, ventilation systems employ effective heat recovery that returns energy from extract air to the supply air. A good rotating heat exchanger can recover up to 90% of the energy present.
Pressure
The design of the duct system and the unit has an impact on required system pressure. There are often tens, sometimes hundreds, of Pascals to be saved here. Systemair we are going one step further and working hard to ensure that our products maintain a high standard and are approved by various bodies. For units, this may mean Eurovent certification or other local certification for the country in question. To achieve this, you need resources and expertise. Within the Group, you will find, among other things, one of Europes most modern development centres, which is AMCA-certified. Systemair "sileo" ranges: The new generation of Systemair products with high efficiency and at the same time drastically reduced sound levels. A new impeller generation, introduced in our roof fans DVS/ DHS and our axial fans AW/AR. Read more in our online-catalogue.
Cool recovery
In warmer parts of the world, energy savings may be possible by drawing cool night-time supply air into premises, thus cooling the building structure.
Energy-efficient fans
Today, there is a new generation of fan motors that contribute to a dramatic reduction in energy consumption, as much as 50% in some cases. The new EC motors are better suited to speed control functions, which is where considerable energy savings can be made. Further benefits are of quieter operation as well as extended product life.
Quality-certified products
How can you choose the right solution and product when there are so many alternatives? Nowadays, most major suppliers are ISO-certified and have CEmarked products, but is that enough? At
10
Selection tools
We have developed this overview to make it easier for you to get an idea of which product best suits your specific needs. More detailed analysis or planning usually requires additional information, which is where the following tools come in.
Personal support
Systemair aims to have local expertise close to the customer. You can find up-to-date information and contact details for each country on our website, www.systemair.com.
11
IE2
2009/640/EG
In the EEA (European Economic Area) this standard was the base for the guideline 2009/640/EU, which defines minimum efficiencies for motors being sold, installed and operated in this area. Since 16.6.2011 the minimum efficiency class for those motors is IE2. Those motors combine the benefits of a higher efficiency with a longer lifetime. This guideline has had an influence on the Systemair product range. All three phase IEC motors, used for example in Multibox MUB, roof fans DVN, axial fans AXC and other Systemair products, covered by the EU guideline have been replaced by high efficiency IE2 motors. IE2 motors cannot be speed controlled by voltage, i.e. voltage transformers.
Systemair is offering a newly developed range of frequency inverters, FRQ, to fill this gap, offering a real plug and play solution no need for time consuming configuration at site, and when choosing the FRQ-S models, no need to install expensive shielded cable. Read more on www. systemair.com. Another excellent alternative to IE2 high efficiency motors are Systemair fans with EC-motors, offering up to 50% energy saving. All EC fans are fully speed controllable by a simple 0-10V signal. Full technical details on www.systemair.com.
12
100C
120C
200C
300C 120min
400C 120min
600C 120min
Workshops/Industries
Warehouses/Storage facilitiies
Car parks
Laboratories
Battery rooms
Kitchens/Bakeries
13
In combination with energy efficient ECdriven fans, EC-Vent offers an intelligent yet easy-to-install climate solution for new buildings as well as retrofit projects.
14 14
EC-fans
K EC. . . . . . . . . . . . . . . . . . . . 18
KVKE EC. . . . . . . . . . . . . . . . . 56
DVC/DVCI . . . . . . . . . . . . . . 132
MUB EC. . . . . . . . . . . . . . . . . 94
KBR/KBT EC . . . . . . . . . . . . 300
15 15
FK Fast clamp FGR Filter cassette KD K FK Fast clamp LDC Silencer KVK
VBC Water heating battery CB/CBM Electrical heating FK battery Fast clamp SPI CWK cooling battery Iris damper water based
RVK
Elegant Diffuser
General
Systemair circular duct fans have been developed for use in compact exhaust and supply air systems. The Systemair circular duct fan was the first in-line duct fan available on the market in this design. The availability of a comprehensive range of accessories, including heating and cooling coils, filters, silencers and more, offers solutions for complete systems for almost all applications. Our experience over the past 35 years and continuous research and development of new products and technologies has resulted in the Systemair circular duct fan system being a market leader. Our motto the straight way is revealed in the straight routing of the air in a ducted system.
Systemair range
Systemair offers different variants of circular duct fans. For systems with higher pressure losses we are offering the ranges K and RVK. The KV range can be installed directly on the wall. For higher air volumes we are offering the KD range with mixed flow impellers. When a low noise level is required, we are offering the ranges KVK, KVKE and KVO, all with sound absorbent insulation.
Motors
Systemair circular duct fans are all equipped with external rotor motors, speed controllable by voltage. All motors are equipped with thermal contacts (TK) for effective thermal motor protection. The TK is internally wired in the ranges K, KV, RVK and KVKE. Manual re-setting of the TK is in accordance with EN 60335-2-80. The KD, KVK and KVO ranges are partly equipped with internally wired TK, partly with TK with extended leads. The TK leads have to be connected to an external motor protection device. (See Electrical Accessories) NB! Failure to connect the TK provided will result in all warranties being null and void.
16
K EC. . . . . . . . . . . . . . . . . . . . 18 Circular metal duct fans with EC-motors: up to 0.48 m3/s, backward curved impeller, 1 phase.
KVK . . . . . . . . . . . . . . . . . . . . 46 Insulated box fans: up to 1.49 m3/s, forward curved impeller, 1 phase.
K/KV. . . . . . . . . . . . . . . . . . . 22 Circular metal duct fans: up to 0.45 m3/s, backward curved impeller, 1 phase.
KVK DUO. . . . . . . . . . . . . . . . 52 Insulated twin box fans: up to 1.49 m3/s, forward curved impeller, 1 phase.
RVK . . . . . . . . . . . . . . . . . . . . 28 Circular duct fan in plastic: up to 0.47 m3/s, backward curved impellers, 1 phase.
KVKE EC. . . . . . . . . . . . . . . . . 56 Insulated box fans with Ecmotors: up to 0.52 m3/s. With backward curved impeller, 1 phase.
KVO. . . . . . . . . . . . . . . . . . . . 34 Box fans: up to 0.8 m3/s. With backward curved impeller, 1 phase.
KVKE . . . . . . . . . . . . . . . . . . . 60 Insulated box fans: up to 0.6 m3/s. With backward curved impeller, 1 phase.
KD . . . . . . . . . . . . . . . . . . . . . 38 Circular mixflow duct fans: up to 2.3 m3/s, mixflow impeller, 1 and 3 phase.
17
EC technology is intelligent technology; using integral electronic control which eliminates the slip losses in the motor and ensures that the motor always runs at optimal load and guarantees that the proportion of energy utilised effectively is many times higher and that the energy usage is considerably lower compared to AC motors. Another special feature of EC fans is their energy-saving potential not only at full load, but especially at part-load. When operating at part-load, the energy used is much lower than with an asynchronous motor of equivalent output. Reduced energy usage guarantees a drop in operating costs. The K EC series is designed for installation in ducts. All the K fans have minimum 25 mm long spigot connections. The fans have backward-curved blades and external rotor motors (EC). The FK mounting clamp facilitates easy installation and removal, and prevents the transfer of vibration to the duct. The fans are delivered with a pre-wired potentiometer (0-10V) which allows you to easily set the desired working point. Motor protection is integrated in the electronics of the motor. The casing is manufactured from galvanised sheet steel with the seams folded to give the fan a close to air tight casing. Outdoor mounting and wet room applications are possible due to the fans air tight casing. By using an EC fan you eliminate the need for an electrical protection unit and speed controller. This should be considered when doing a cost comparison with a standard AC fan model. It also simplifies the process when commissioning.
EC-Vent p. 329-330
Technical data
K Art no. Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 3 m Weight Insulation class, motor Enclosure class, motor Motor protection Speed control, stepless Wiring diagram p. 391-400 Electronic V/50 Hz W A m3/s min-1 C C dB(A) kg 160 EC 2580 230 1~ 79.4 0.628 0.151 3105 60 60 47 3 B IP 44 Integral MTP 10 41 200 EC 2581 230 1~ 78.6 0.626 0.215 2468 60 60 51 3.3 B IP 44 Integral MTP 10 41 250 EC 2583 230 1~ 120 0.921 0.287 2628 40 40 46 3.5 B IP 44 Integral MTP 10 41 315 M EC 2584 230 1~ 166 1.14 0.393 2113 40 40 50 6 B IP 44 Integral MTP 10 41 315 L EC 2585 230 1~ 340 2.08 0.481 2719 55 55 57 7.2 B IP 44 Integral MTP 10 41
18
Ventilation accessories
FK p. 355
(F)
88
SG p. 357
C
VK p. 356
A K 160 EC K 200 EC K 250 EC K 315 L EC 159 199 249 314 B 286 336 336 408 408 C 25 30 30.5 32.5 37.5 D 147 148 144.5 160.5 160.5 E 26 27 27 27 27 (F) 198 205 202 220 225
K 315 M EC 314
RSK p. 355
LDC p. 348
FFR p. 349
CB p. 350
Quick selection
1 2 3 4 5
19
dB(A) LwA Duct LwA Surrounding With LDC 160-900 LwA Duct
Tot 63 78 54 69 53 22 51 125 72 28 68
dB(A) LwA Duct LwA Surrounding With LDC 200-900 LwA Duct
Tot 63 77 58 67 51 24 49 125 70 38 66
dB(A) LwA Duct LwA Surrounding With LDC 250-900 LwA Duct
Tot 63 74 53 52 16 125 65 36
dB(A) LwA Duct LwA Surrounding With LDC 315-900 LwA Duct
Tot 63 76 57 69 53 24 52 125 70 33 67
64
49
61
60
48
40
38
43
35
20
dB(A) LwA Duct LwA Surrounding With LDC 315-900 LwA Duct
Tot 63 82 64 74 67 47 66 125 74 45 71
21
RE p. 320
The K series is designed for installation in ducts and the KV is designed to be used as a wall mounted duct-connected extract fan. All the K/ KV-fans have a minimum 25 mm long spigot connections. The fans have backward-curved blades and external rotor motors. To simplify installation the K-fan has a fixing bracket together with screws for mounting the bracket included as standard. The FK mounting clamp facilitates easy installation and removal, and prevents the transfer of vibration to the duct. The fans can be speed-controlled via a stepless thyristor or a 5-step transformer. To protect the motor from overheating K/KV 100 M and 125 M is impedance protected, K/KV 100 XL-315 L has integral thermal contacts with electrical reset. The casing is manufactured from galvanised sheet steel and folded which gives the fan an air tight casing. Duct connected outdoor and wet room applications of the fan are possible due to the air tight casing. Quick selection
REU p. 320
REE p. 321
1 2 3 4 5 6 7 8
K/KV 100M K/KV 100XL K/KV 125M K/KV 125XL K/KV 150 M K/KV 150 XL K/KV 160M K/KV 160XL
1 2 3 4 5 6
K/KV 200M K/KV 200L K/KV 250M K/KV 250L K/KV 315M K/KV 315L
4 3 1 2 5 6
3 1
Technical data
K/KV Art no. Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 3 m Weight Insulation class, motor Enclosure class, motor Capacitor Motor protection Speed control, five-step Speed control, five step high/low Speed control, stepless Wiring diagram p. 391-400 100 M 1001/1205 V/50 Hz 230 1~ W 29.9 A 0.171 m3/s 0.051 min-1 2443 C 70 C 70 dB(A) 38 kg 2.5 B IP 44 F Integral Transformer RE 1.5 Transformer REU 1.5 Thyristor REE 1 1 100 XL 1004/1207 230 1~ 58.6 0.253 0.074 2425 70 70 48 2.5 B IP 44 2 Integral RE 1.5 REU 1.5 REE 1 2 125 M 1002/1208 230 1~ 29.1 0.172 0.057 2483 70 70 34 2.5 B IP 44 Integral RE 1.5 REU 1.5 REE 1 1 125 XL 1003/1210 230 1~ 62 0.271 0.0978 2390 70 70 50 2.5 B IP 44 2 Integral RE 1.5 REU 1.5 REE 1 2 150 M 1017/1211 230 1~ 61 0.264 0.122 2412 70 70 42 3.5 B IP 44 2 Integral RE 1.5 REU 1.5 REE 1 2 150 XL 1018/1212 230 1~ 104 0.458 0.199 2567 70 70 55 4.5 B IP 44 3 Integral RE 1.5 REU 1.5 REE 1 2 160 M 1005/1213 230 1~ 59 0.259 0.136 2499 70 70 44 3 B IP 44 2 Integral RE 1.5 REU 1.5 REE 1 2
22
Ventilation accessories
K 100 M 100 XL 125 M
88
A 99 99 124 124 149 149 159 159 199 199 249 249 314 314
B 218 246 218 246 286 336 286 336 336 336 336 336 408 408
D 166 161 142 151 152 171 147 166 148 174 119.5 144.5 160.5 160.5
E 26 26 27 26 25 26 26 26 27 27 27 27 27 27
F 218 213 196 203 202 226 198 221 205 231 177 202 220 225
FK p. 355
(F)
SG p. 357
VK p. 356
40 5
A 99 99 124 124 149 149 159 159 199 199 249 249 314 314
B 218 246 218 246 286 336 286 336 336 336 336 336 408 408
D 143 125 131 127 113 147 113 147 134 158 135 159 145 145
E 254 304 254 304 344 394 344 394 394 394 394 394 458 458
F 284 334 284 334 374 425 374 425 425 425 425 425 489 489
RSK p. 355
LDC p. 348
A B E F
FFR p. 349
CB p. 350
K/KV Art no. Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 3 m Weight Insulation class, motor Enclosure class, motor Capacitor Motor protection Speed control, five-step Speed control, five step high/low Speed control, stepless Wiring diagram p. 391-400
160 XL 1006/1214 V/50 Hz 230 1~ W 105 A 0.457 m3/s 0.214 min-1 2553 C 70 C 70 dB(A) 53 kg 4.5 B IP 44 F 3 Integral Transformer RE 1.5 Transformer REU 1.5 Thyristor REE 1 2
200 M 1007/1215 230 1~ 106 0.463 0.216 2551 70 70 51 4.5 B IP 44 3 Integral RE 1.5 REU 1.5 REE 1 2
200 L 1008/1216 230 1~ 158 0.709 0.269 2630 50 50 50 4.5 B IP 44 4 Integral RE 1.5 REU 1.5 REE 1 2
250 M 1009/1217 230 1~ 103 0.448 0.216 2579 70 70 49 4.5 B IP 44 3 Integral RE 3 REU 3 REE 1 2
250 L 1010/1218 230 1~ 157 0.699 0.267 2641 70 70 49 5 B IP 44 4 Integral RE 3 REU 3 REE 1 2
315 M 1011/1219 230 1~ 202 0.893 0.347 2578 51 51 47 6 F IP 44 5 Integral RE 1.5 REU 1.5 REE 2 2
315 L 1012/1220 230 1~ 318 1.39 0.48 2318 51 45 50 7 F IP 44 7 Integral RE 1.5 REU 1.5 REE 2 2
23
dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 100-600 LwA Inlet LwA Outlet
Tot 63 63
60 45
dB(A) 4k 40
38 29
Tot 63 125 65 63 28 62 60 72 69 55 63 61 49 49 28 45 45
250 56
55 23
500 58
54 36
1k 50
49 41
2k 47
44 42
8k 28
27 17
50
35 21
LwA Inlet LwA Outlet LwA Surrounding With LDC 100-600 LwA Inlet LwA Outlet
57 52
46 31
56 51
45 44
34 30
14 13
0 0
6 4
11 10
dB(A)
LwA Inlet LwA Outlet LwA Surrounding
Tot 63 59 60 41 50 50 33 40 12 30 37 125 51 46 9 48 43
dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 125-600 LwA Inlet LwA Outlet
Tot 63 73 73 57 64 64 56 55 35 53 52 125 65 64 31 62 61
24
dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 150-600 LwA Inlet LwA Outlet
Tot 63 70 69 49 63 63 45 46 24 45 46 125 63 63 25 60 60
dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 150-600 LwA Inlet LwA Outlet
Tot 63 78 76 62 70 68 56 51 26 56 51 125 67 67 28 64 64
dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 160-900 LwA Inlet LwA Outlet
Tot 63 70 68 51 62 60 43 44 13 41 42 125 65 62 23 61 58
dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 160-900 LwA Inlet LwA Outlet
Tot 63 77 75 60 65 65 49 47 24 47 45 125 65 65 31 61 61
25
dB(A)
LwA Inlet LwA Outlet LwA Surrounding
Tot 63 75 74 58 65 64 47 45 16 45 43 125 67 65 40 63 61
dB(A)
LwA Inlet LwA Outlet LwA Surrounding
Tot 63 75 74 57 66 66 49 51 17 47 49 125 68 66 30 64 62
dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 250-900 LwA Inlet LwA Outlet
Tot 63
70 70 56 45 46 18
dB(A) 4k
62 62 52
Tot 63 125 66 64 33 62 60 74 75 56 65 65 59 58 34 56 55
250
61 62 31
500
65 64 48
1k
62 61 44
2k
60 63 51
8k
53 51 39
LwA Inlet LwA Outlet LwA Surrounding With LDC 250-900 LwA Inlet LwA Outlet
59 59
42 43
55 54
53 54
45 44
36 35
37 40
52 52
45 43
26
dB(A)
LwA Inlet LwA Outlet LwA Surrounding
Tot 63 73 70 54 63 60 51 49 22 50 48 125 60 56 28 57 53
dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 315-900 LwA Inlet LwA Outlet
Tot 63 76 77 57 68 69 55 63 24 54 62 125 67 67 37 64 64
27
RE p. 320
The RVK series is designed for installation in ducts. The casing is manufactured from PA6 fibreglass reinforced plastic which gives the fan a low leakage casing. Duct connected wet room applications of the fan are possible due to a close to air tight casing and the IP 44 rated terminal box.The fans have backward-curved blades and external rotor motors. The FK mounting clamp facilitates easy installation and removal, and prevents the transfer of vibration to the duct. The fans can be speed-controlled via a stepless thyristor or a 5-step transformer. The RVK fans have integral thermal contacts with automatic reset.
REU p. 320
REE p. 321
Quick selection
1 2 3 4 5 6 7
RVK 100E2-A1 RVK 125E2-A1 RVK 125E2-L1 RVK 150E2-A1 RVK 150E2-L1 RVK 160E2-A1 RVK 160E2-L1
1 2 3 4 5 6 7
RVK 200E2-A1 RVK 200E2-L1 RVK 250E2-A1 RVK 250E2-L1 RVK 250E2-XL RVK 315E2-A1 RVK 315E2-L1
1 2
5 6
2 4
Technical data
RVK Art no. Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 3 m Weight Insulation class, motor Enclosure class, motor Capacitor Motor protection Speed control, five-step Speed control, five step high/low Speed control, stepless Wiring diagram p. 391-400 100E2-A1 5755 V/50 Hz 230 1~ W 29.1 A 0.171 m3/s 0.0512 min-1 2482 C 70 C 70 dB(A) 35 kg 2 B IP 44 F Impedans Transformer RE 1.5 Transformer REU 1.5 Thyristor REE 1 1 125E2-A1 5756 230 1~ 29.2 0.172 0.0612 2469 70 70 38 2 B IP 44 Impedans RE 1.5 REU 1.5 REE 1 1 125E2-L1 9775 230 1~ 61.2 0.26 0.0947 2436 70 70 43 2 B IP 44 2 Integral RE 1.5 REU 1.5 REE 1 2 150E2-A1 5757 230 1~ 59.9 0.261 0.118 2418 70 70 48 3 B IP 44 2 Integral RE 1.5 REU 1.5 REE 1 2 150E2-L1 5758 230 1~ 115 0.5 0.185 2497 70 70 50 2.7 B IP 44 3 Integral RE 1.5 REU 1.5 REE 1 2 160E2-A1 5759 230 1~ 57.8 0.257 0.125 2429 70 70 43 3 B IP 44 2 Integral RE 1.5 REU 1.5 REE 1 2 160E2-L1 5760 230 1~ 112 0.485 0.202 2530 70 70 48 2.7 B IP 44 3 Integral RE 1.5 REU 1.5 REE 1 2
28
Ventilation accessories
FK p. 355
E
SG p. 357
I B J G F
RVK 100E2-A1 125E2-A1 125E2-L1 150E2-A1 150E2-L1 160E2-A1 160E2-L1 200E2-A1 200E2-L1 250E2-A1 250E2-L1 250E2-XL 315E2-A1 315E-L1
A 99 124 124 149 149 159 159 199 199 249 249 249 315 315
B 99 124 124 149 149 159 159 199 199 249 249 249 315 315
C 251 251 251 340.5 340.5 340.5 340.5 340.5 340.5 340.5 340.5 340.5 405 405
D 30 30 30 30 30 30 30 30 30 30 30 30 30 30
E 230 230 230 230 230 230 230 230 250 230 230 230 275 275
F 30 30 30 30 30 30 30 30 30 30 30 30 30 30
G 271.5 271.5 271.5 271.5 271.5 271.5 271.5 271.5 271.5 271.5 271.5 271.5 271.5 271.5
I 60 60 60 60 60 60 60 60 60 60 60 60 60 60
J 200 200 200 200 200 200 200 200 200 200 200 200 200 200
VK p. 356
RSK p. 355
LDC p. 348
FFR p. 349
CB p. 350
RVK Art no. Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 3 m Weight Insulation class, motor Enclosure class, motor Capacitor Motor protection Speed control, five-step Speed control, five step high/low Speed control, stepless Wiring diagram p. 391-400
200E2-A1 5761 V/50 Hz 230 1~ W 107 A 0.47 m3/s 0.216 min-1 2550 C 70 C 70 dB(A) 45 kg 3.3 B IP 44 F 3 Integral Transformer RE 1.5 Transformer REU 1.5 Thyristor REE 1 2
200E2-L1 5762 230 1~ 160 0.705 0.273 2581 70 55 46 3.7 B IP 44 4 Integral RE 1.5 REU 1.5 REE 1 2
250E2-A1 5763 230 1~ 109 0.476 0.234 2546 70 70 48 3.3 B IP 44 3 Integral RE 1.5 REU 1.5 REE 1 2
250E2-L1 5764 230 1~ 159 0.706 0.302 2595 57 57 44 4 B IP 44 4 Integral RE 3 REU 3 REE 1 2
250E2-XL 30901 230 1~ 213 0.935 0.341 2415 51 38 49 6 B IP 44 5 Integral RE 1.5 REU 1.5 REE 1 2
315E2-A1 5765 230 1~ 176 0.773 0.369 2387 70 70 40 5.0 F IP 44 5 Integral RE 1.5 REU 1.5 REE 1 2
315E2-L1 5766 230 1~ 318 1.39 0.51 2433 38 38 45 5.2 F IP 44 7 Integral RE 1.5 REU 1.5 REE 2 2
29
dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 100-600 LwA Inlet LwA Outlet
Tot 63 62 57 41 39 42 1 125 57 52 11
dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 125-600 LwA Inlet LwA Outlet
Tot 63 63 60 45 54 53 36 36 12 33 33 125 56 54 15 53 51
55 50
35 38
54 49
46 40
33 27
15 11
0 0
5 5
10 11
dB(A)
LwA Inlet LwA Outlet LwA Surrounding
Tot 63 70 69 50 64 62 49 50 23 46 47 125 66 64 37 63 61
dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 150-600 LwA Inlet LwA Outlet
Tot 63 70 69 54 62 62 43 44 23 43 44 125 61 60 32 58 57
30
dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 150-600 LwA Inlet LwA Outlet
Tot 63 74 73 57 66 67 42 43 19 42 43 125 67 68 35 64 65
dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 160-900 LwA Inlet LwA Outlet
Tot 63 69 66 50 58 57 40 39 23 38 37 125 58 58 18 54 54
dB(A)
LwA Inlet LwA Outlet LwA Surrounding
Tot 63 71 70 55 59 61 41 42 18 39 40 125 62 63 35 58 59
dB(A)
LwA Inlet LwA Outlet LwA Surrounding
Tot 63 70 69 52 57 58 43 45 17 41 43 125 58 58 26 54 54
31
dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 200-900 LwA Inlet LwA Outlet
Tot 63 73 73 53 49 48 14 125 64 64 27
dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 250-900 LwA Inlet LwA Outlet
Tot 63 69 69 55 58 58 43 47 16 40 44 125 59 58 31 55 54
63 64
47 46
60 60
59 61
44 41
31 30
27 29
45 45
39 39
dB(A)
LwA Inlet LwA Outlet LwA Surrounding
Tot 63 71 73 51 63 65 49 52 19 46 49 125 65 64 41 61 60
dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 250-900 LwA Inlet LwA Outlet
Tot 63 75 75 56 66 68 58 58 31 55 55 125 68 70 53 64 66
32
dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 315-900 LwA Inlet LwA Outlet
Tot 63 69 70 47 60 61 43 46 12 42 45 125 57 59 25 54 56
dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 315-900 LwA Inlet LwA Outlet
Tot 63 73 74 52 65 66 47 47 17 46 46 125 62 63 29 59 60
33
KVO has a single-inlet centrifugal fan (size 100-160 and size 355400 with forward curved blades, size 200-315 with backward curved blades) and a maintenance-free external rotor motor. In all KVO models, the motor and impeller are mounted on the cover for easy cleaning and maintenance. To protect the motor from overheating, the KVO 100-315 have integral thermal contacts with electrical reset, size 355-400 with integral thermal contact with external leads for connection to a motor protection device. The fans can be installed in any position, and are easy to connect to spiral ducts using FK mounting clamps. The lid is insulated with 40 mm rockwool. The casing is manufactured from galvanised sheet steel.
RTRE p. 320
RE p. 320
1 2 3 4
1 2 3 4
REE p. 321
Technical data
KVO Art no. Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 3 m Weight Insulation class, motor Enclosure class, motor Capacitor Motor protection Speed control, five-step Speed control, five step high/low Speed control, stepless Wiring diagram p. 391-400 100 2075 V/50 Hz 230 1~ W 77.9 A 0.346 m3/s 0.0778 min-1 2438 C 60 C 60 dB(A) 40 kg 6 B IP 44 F 2 Integral Transformer RE 1.5 Transformer REU 1.5 Thyristor REE 1 2 125 2020 230 1~ 89 0.393 0.101 2175 64 64 38 6 B IP 44 2 Integral RE 1.5 REU 1.5 REE 1 2 160 2024 230 1~ 135 0.59 0.138 2544 70 70 43 7 B IP 44 4 Integral RE 1.5 REU 1.5 REE 1 2 200 2025 230 1~ 151 0.681 0.244 2632 70 70 51 12.5 F IP 44 4 Integral RE 1.5 REU 1.5 REE 1 2 250 2027 230 1~ 301 1.33 0.417 2480 70 70 52 20 F IP 44 7 Integral RE 1.5 REU 1.5 REE 2 2 315 2029 230 1~ 549 2.38 0.592 2227 48 41 56 27.2 F IP 44 10 Integral RE 3 REU 5 REE 4 2
34
FK p. 355
315
E
355 400
D A F
SG p. 357
VK p. 356
RSK p. 355
LDC p. 348
FGR p. 348
CB p. 350
KVO Art no. Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 3 m Weight Insulation class, motor Enclosure class, motor Capacitor Motor protection Speed control, five-step Speed control, five step high/low Speed control, stepless Wiring diagram p. 391-400 * + S-ET 10
355 2030 V/50 Hz 230 1~ W 1196 A 5.69 m3/s 0.882 min-1 1118 C 65 C 65 dB(A) 53 kg 38.6 F IP 54 F 20 S-ET 10 Transformer RTRE 7 Transformer REU 7* Thyristor 6
400 2031 230 1~ 1257 5.95 0.893 1075 58 58 56 38.6 F IP 54 20 Integral RTRE 7 REU 7* 6
35
dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 100-600 LwA Inlet LwA Outlet
Tot 63 63 68 47 47 55 21 125 60 61 36
dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 125-600 LwA Inlet LwA Outlet
Tot 63 65 66 45 58 55 44 46 19 41 43 125 61 56 36 58 53
58 59
43 51
57 58
46 47
31 36
16 27
0 9
9 17
21 28
dB(A)
LwA Inlet LwA Outlet LwA Surrounding
Tot 63 68 75 50 52 55 31 125 62 63 39
dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 200-900 LwA Inlet LwA Outlet
Tot 63 73 76 58 64 64 53 56 34 51 54 125 61 60 42 57 56
60 63
50 53
58 59
53 59
33 39
16 25
14 26
36 43
38 44
36
dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 250-900 LwA Inlet LwA Outlet
Tot 63 73 78 59 61 63 55 57 37 52 54 125 60 60 41 56 56
dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 315-900 LwA Inlet LwA Outlet
Tot 63 78 86 63 72 79 56 64 42 55 63 125 73 75 53 70 72
KVO 355
KVO 400
dB(A)
LwA Inlet LwA Outlet LwA Surrounding
Tot 63 77 83 60 72 74 57 66 41 57 66 125 73 72 55 70 69
dB(A)
LwA Inlet LwA Outlet LwA Surrounding
Tot 63 80 84 63 75 77 61 68 39 60 67 125 75 73 56 72 70
37
S-ET p. 341
The KD series have external rotor motors with a mixed flow impeller which reduces the external dimensions of the fans. These fans have high flow capacity in relation to their compact design. Brackets are supplied with the fans to make installation easier. The FK mounting clamp facilitates easy installation and removal and prevents the transfer of vibration to the duct. To protect the motor from overheating KD 200 L1, 250 M, 315 M1, 315 L1 and and 355 S1 have integral thermal contacts with electrical reset, and the remaining sizes have integral thermal contacts with leads to a motor protection device. The casing is manufactured from galvanised sheet steel.
RTRE p. 320
RE p. 320
REE p. 321
1 2
3 4 5
1 2
tECHNICAL DATA
KD Art no. Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 3 m Weight Insulation class, motor Enclosure class, motor Capacitor Motor protection Speed control, five-step Speed control, five step high/low Speed control, stepless Wiring diagram p. 391-400 *+ S-ET 10 200 L 1284 V/50 Hz 230 1~ W 257 A 1.14 m3/s 0.37 min-1 2562 C 55 C 46 dB(A) 53 kg 7 F IP 44 F 6 Integral Transformer RE 1.5 Transformer REU 1.5 Thyristor REE 2 2 250 M 1285 230 1~ 254 1.13 0.40 2572 55 46 54 6.5 F IP 44 6 Integral RE 1.5 REU 1.5 REE 2 2 250 L 1286 230 1~ 369 1.60 0.55 2604 70 70 55 9.5 F IP 44 10 Integral RE 3 REU 3 REE 2 2 315 M 1287 230 1~ 252 1.12 0.39 2573 55 46 59 5.5 F IP 44 6 Integral RE 1.5 REU 1.5 REE 2 2 315 L 1288 230 1~ 372 1.62 0.59 2595 70 70 54 9 F IP 44 10 Integral RE 3 REU 3 REE 2 2 315 XL 1289 230 1~ 276 1.29 0.77 1375 70 70 52 15.5 B IP 54 6 S-ET 10 RTRE 3 REU 1.5* REE 2* 6 355 S 1291 230 1~ 371 1.61 0.60 2597 70 70 54 8 F IP 44 10 Integral RE 3 REU 3 REE 2 2 355 M 1292 230 1~ 275 1.30 0.85 1375 70 70 50 15 B IP 54 6 S-ET 10 RTRE 1.5 REU 1.5* REE 2* 6 355 XL1 1294 230 1~ 431 1.90 1.10 1309 70 70 56 20.5 F IP 54 10 S-ET 10 RTRE 3 REU 3* REE 4* 6 355 XL3 1296 400 3~ 451 0.96 1.16 1399 70 70 58 18 F IP 54 STDT 16 RTRD 2 RTRDU 2 8
38
155
25
D/2
102,5
180 310
10
25
C A
25
248 313
25
10 353 31
10
60 205
B D
30
FK p. 355
SG p. 357
VK p. 356
45
45
45
B 205 205
C 248 313 315 355 355 400 400 450 450 500
D 385 305 484 435 516 480 602 559 742 699
KD 250 M
KD 355 S
RSK p. 355
LDC p. 348
FFR p. 349
CB p. 350
KD Art no. Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 3 m Weight Insulation class, motor Enclosure class, motor Capacitor Motor protection Speed control, five-step Speed control, five step high/low Speed control, stepless Wiring diagram p. 391-400 *+ S-ET 10
400 M1 1297 V/50 Hz 230 1~ W 432 A 1.90 m3/s 1.16 min-1 1307 C 70 C 70 dB(A) 54 kg 19.5 F IP 54 F 10 S-ET 10 Transformer RTRE 3 Transformer REU 3* Thyristor REE 4* 6
400 M3 1300 400 3~ 456 0.952 1.22 1397 70 70 57 17.5 F IP 54 STDT 16 RTRD 2 RTRDU 2 8
400 XL1 1301 230 1~ 855 4.24 1.62 1298 65 65 64 28.5 F IP 54 16 S-ET 10 RTRE 5 REU 5* 6
400 XL3 1302 400 3~ 792 1.53 1.65 1304 67 67 61 25.5 F IP 54 STDT 16 RTRD 2 RTRDU 2 8
450 M1 1303 230 1~ 857 4.21 1.60 1308 65 65 61 28 F IP 54 16 S-ET 10 RTRE 5 REU 5* REE 2* 6
450 M3 1304 400 3~ 778 1.53 1.64 1307 70 70 63 25.5 F IP 54 STDT 16 RTRD 2 RTRDU 2 8
450 XL1 1305 230 1~ 1392 6.16 2.35 1289 60 60 61 36.5 F IP 54 30 S-ET 10 RTRE 7 REU 7* 6
450 XL3 1307 400 3~ 1246 2.22 2.07 1325 61 30 61 35 F IP 54 STDT 16 RTRD 4 RTRDU 4 8
500 M1 1309 230 1~ 1386 6.12 2.37 1290 62 57 64 39 F IP 54 30 S-ET 10 RTRE 7 REU 7* 6
500 M3 1310 400 3~ 1243 2.20 2.18 1315 62 51 65 34.5 F IP 54 STDT 16 RTRD 4 RTRDU 4 8
39
dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 200-900 LwA Inlet LwA Outlet
Tot 63 79 84 60
68 72
dB(A) 4k 64 75 48
51 62
Tot 63 125 66 70 27 49 66 79 79 61 73 68 55 55 22 73 52
250 71 75 46
63 67
500 75 76 55
51 52
1k 71 76 56
39 44
2k 64 78 52
30 44
8k 57 73 39
47 63
60 57 27
58 55
LwA Inlet LwA Outlet LwA Surrounding With LDC 250-900 LwA Inlet LwA Outlet
dB(A)
LwA Inlet LwA Outlet LwA Surrounding
Tot 63
82 81 62 56 56 28
dB(A) 4k
71 71 49
Tot 63 125 64 69 33 61 66 79 81 66 67 70 54 58 32 53 57
250
75 71 46
500
78 75 61
1k
75 74 50
2k
71 76 48
8k
64 64 37
LwA Inlet LwA Outlet LwA Surrounding With LDC 315-900 LwA Inlet LwA Outlet
72 70
53 53
69 67
67 63
58 55
49 48
48 53
61 61
56 56
40
dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 315-900 LwA Inlet LwA Outlet
Tot 63 80 81 61 71 71 58 54 32 57 53 125 69 68 36 66 65
dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 315-900 LwA Inlet LwA Outlet
Tot 63 74 75 59 65 68 60 59 33 59 58 125 63 69 42 60 66
dB(A)
LwA Inlet LwA Outlet LwA Surrounding
Tot 63 80 83 61 71 73 57 58 32 57 58 125 68 68 35 65 65
dB(A)
LwA Inlet LwA Outlet LwA Surrounding
Tot 63 73 75 57 67 68 62 57 40 62 57 125 65 69 40 62 66
41
dB(A)
LwA Inlet LwA Outlet LwA Surrounding
Tot 63 78 78 63 73 73 55 50 26 55 50 125 75 75 48 72 72
dB(A)
LwA Inlet LwA Outlet LwA Surrounding
Tot 63 79 79 65 75 74 55 50 29 55 50 125 77 76 52 74 73
dB(A)
LwA Inlet LwA Outlet
Tot 63 77 77 60 72 72 52 48 27 51 47 125 73 73 45 70 70
dB(A)
LwA Inlet LwA Outlet LwA Surrounding
Tot 63 78 79 64 74 73 54 51 24 53 50 125 76 74 47 73 71
42
dB(A)
LwA Inlet LwA Outlet
Tot 63 84 85 71 78 79 55 55 21 54 54 125 79 79 62 76 76
dB(A)
LwA Inlet LwA Outlet
Tot 63 83 85 68 77 79 53 55 18 52 54 125 78 78 44 75 75
dB(A)
LwA Inlet LwA Outlet LwA Surrounding
Tot 63 83 83 68 57 51 25 125 77 75 47
dB(A)
LwA Inlet LwA Outlet LwA Surrounding
Tot 63 83 84 70 53 52 15 125 78 77 45
43
KD 450 XL3
dB(A)
LwA Inlet LwA Outlet LwA Surrounding
Tot 63 82 82 68 69 69 35 125 76 75 54
dB(A)
LwA Inlet LwA Outlet LwA Surrounding
Tot 63 84 86 68 64 61 34 125 76 76 48
KD 500 M3
dB(A)
LwA Inlet LwA Outlet LwA Surrounding
Tot 63 82 83 71 69 70 41 125 75 75 58
dB(A)
LwA Inlet LwA Outlet LwA Surrounding
Tot 63 84 86 71 66 62 26 125 77 78 47
44
Project: EON Kharadi Type of Building: SEZ IT Park City/Country: Pune, India Products/ Solution: MUB, Inline (K, KD), Axial, Jet Nozzles, Grilles
45
The KVK 125-160 models have a single-inlet centrifugal fan, size 200500 have double-inlet centrifugal fans. All sizes have forward-curved blades and a maintenance-free external rotor motor. To protect the motor from overheating the KVK 125-160 has integral thermal contacts with electrical reset, and size 200-500 has leads for connection to a motor protection device. The fans can be installed in any position, and are easy to connect to spiral ducts using FK mounting clamps. The KVK models are manufactured from galvanised sheet steel and are thermally and acoustically insulated with a 50 mm layer of rockwool with a surface liner which prevents the migration of fibres into the airstream.
RTRE p. 320
RE p. 320
1 2 3 4 5
KVK 125 KVK 160M KVK 160L KVK 200 KVK 250
1 2 3 4 2 3
REE p. 321
1
1 2 3 4 5
Technical data
KVK Art no. Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 3 m Weight Insulation class, motor Enclosure class, motor Capacitor Motor protection Speed control, five-step Speed control, five step high/low Speed control, stepless Wiring diagram p. 391-400 * + S-ET 10 125 2430 V/50 Hz 230 1~ W 92.7 A 0.409 m3/s 0.106 min-1 1978 C 68 C 68 dB(A) 38 kg 11 B IP 44 F 2 Integral Transformer RE 1.5 Transformer REU 1.5 Thyristor REE 1 2 160 M 2433 230 1~ 111 0.48 0.123 2062 70 70 39 11 B IP 44 2 Integral RE 1.5 REU 1.5 REE 1 2 160 L 2434 230 1~ 134 0.59 0.138 2519 70 70 39 11.8 B IP 44 4 Integral RE 1.5 REU 1.5 REE 1 2 200 1337 230 1~ 172 0.75 0.197 1807 57 57 40 12.9 B IP 44 4 S-ET 10 RTRE 1.5 REU 1.5* REE 1* 5 250 1347 230 1~ 308 1.34 0.311 1833 50 50 43.2 17 F IP 44 8 S-ET 10 RTRE 1.5 REU 1.5* REE 2* 5
46
Ventilation accessories
FK p. 355
D E
KVK 125 160 A 230 230 B 266 266 C 151 134 D 114 132 E 367 367 F 415 415 G 464 464 H 125 160 I 40 40
SG p. 357
VK p. 356
IGK p. 357
I A H B
D E
RSK p. 355
LDC p. 348
I
I 20 40 40 40 50 80
FFR p. 349
CB p. 350
KVK Art no. Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 3 m Weight Insulation class, motor Enclosure class, motor Capacitor Motor protection Speed control, five-step Speed control, five step high/low Speed control, stepless Wiring diagram p. 391-400 * + S-ET 10 315 M 1357 V/50 Hz 230 1~ W 335 A 1.49 m3/s 0.542 min-1 1324 C 70 C 70 dB(A) 35 kg 30 B IP 54 F 10 S-ET 10 Transformer RTRE 3 Transformer REU 3* Thyristor REE 2* 5 315 L 1365 230 1~ 643 2.82 0.789 1201 53 53 36 32.2 B IP 54 20 S-ET 10 RTRE 3 REU 3* REE 4* 5 355 1370 230 1~ 614 2.69 0.72 1220 40 40 36 32.1 B IP 54 20 S-ET 10 RTRE 3 REU 3* REE 4* 5 400 1375 230 1~ 603 2.64 0.73 1186 40 40 39 32 B IP 54 20 S-ET 10 RTRE 3 REU 3* REE 4* 5 500 4506 230 1~ 1452 6.27 1.49 1235 68 68 56 66.9 F IP 54 25 S-ET 10 RTRE 7 REU 7* 3
47
KVK 125
KVK 160 M
dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 125-900 LwA Inlet LwA Outlet
Tot 63 57 70 45 51 58 37 50 17 33 46 125 55 61 33 51 57
dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 160-900 LwA Inlet LwA Outlet
Tot 63 62 72 46 57 61 39 53 10 37 51 125 61 64 43 57 60
KVK 160 L
dB(A)
LwA Inlet LwA Outlet LwA Surrounding
Tot 63 63 75 46 58 64 48 56 25 46 54 125 62 66 43 58 62
dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 200-900 LwA Inlet LwA Outlet
Tot 63 66 73 47 60 63 47 59 19 45 57 125 63 63 38 59 59
48
dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 250-900 LwA Inlet LwA Outlet
Tot 63 67 76 50 46 61 27 125 66 68 46
dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 315-900 LwA Inlet LwA Outlet
Tot 63 60 71 42 57 63 55 59 36 54 58 125 56 63 35 53 60
62 67
43 58
62 64
52 60
36 49
21 42
26 46
34 55
28 50
dB(A)
LwA Inlet LwA Outlet LwA Surrounding
Tot 63 63 73 43 61 64 61 59 31 60 58 125 55 61 35 52 58
dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 355-900 LwA Inlet LwA Outlet
Tot 63 62 72 43 61 64 60 58 31 60 58 125 55 60 35 52 57
49
dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 400-900 LwA Inlet LwA Outlet
Tot 63 63 73 46 60 62 33 125 58 61 37
Tot 63 71 78 63 53 64 31 125 68 68 59
50
Project: Ukraine hotel complex Type of Building: The hotel Ukraine is not only one of the best hotels but also an integral part of the architectural and historical view in Moscow. City/Country: Moscow, Russia Products/Solution: 98 modular air handling units, type DV, including 15 DV Coolers 81 duct and roof fans; K, KD, KT, RSI, DVSI 4 Compact heat recovery units; Topvex 4 Compact supply units; TLP 2 Residential heat recovery units; VR
51
KVK DUO models are designed for applications where a standby fan is required. The fans have double inlet centrifugal fans with forward-curved impellers and maintenance-free external rotor motors. To protect the motors from overheating the fans have integral thermal contacts with leads for connection to a motor protection device. The fans are easy to connect to spiral ducts using FK mounting clamps. The KVK DUO models are manufactured from galvanised sheet steel and are thermally and acoustically insulated with a 50 mm layer of mineral wool. Internal surfaces are protected with perforated galvanised sheet steel.
AWE-SK p. 342
RTRE p. 320
1 2 3 4
KVK DUO 125 KVK DUO 160 KVK DUO 200 KVK DUO 250
KVK DUO 315M KVK DUO 315L, 355 KVK DUO 400
REE p. 321
tECHNICAL DATA
KVK DUO Art no. Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 3 m Weight Insulation class, motor Enclosure class, motor Capacitor Motor protection Speed control, five-step Speed control, five step high/low Speed control, stepless Wiring diagram p. 391-400 * + AWE-SK, ** + S-ET 10 125 5341 V/50 Hz 230 1~ W 41.4 A 0.171 m3/s 0.0528 min-1 1724 C 69 C 69 dB(A) 29 kg 18.3 B IP 44 F 1.5 AWE-SK Transformer RTRE 1.5 Transformer REU 1.5* Thyristor REE 1* 5 160 5127 230 1~ 69.1 0.301 0.105 1943 35 35 37 19.5 B IP 22 2 AWE-SK RTRE 1.5 REU 1.5* REE 1* 5 200 5030 230 1~ 172 0.75 0.197 1807 56 56 40 27.9 B IP 44 4 S-ET 10 RTRE 1.5 REU 1.5** REE 1** 5 250 5031 230 1~ 304 1.31 0.316 1962 50 55 42 45 F IP 44 8 S-ET 10 RTRE 1.5 REU 1.5** REE 2** 5 315M 5032 230 1~ 335 1.49 0.542 1324 69 69 35 66 B IP 54 10 S-ET 10 RTRE 3 REU 3** REE 2* 5 315L 5773 230 1~ 643 2.82 0.789 1201 53 53 36 74 B IP 54 20 S-ET 10 RTRE 3 REU 3** REE 4** 5
52
Ventilation accessories
D E
H A
FK p. 355
SG p. 357
VK p. 356
KVK DUO 125 160 200 250 315M 315L 355 400
RSK p. 355
LDC p. 348
FGR p. 348
CB p. 350
KVK DUO Art no. Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 3 m Weight Insulation class, motor Enclosure class, motor Capacitor Motor protection Speed control, five-step Speed control, five step high/low Speed control, stepless Wiring diagram p. 391-400 * + S-ET 10
355 5774 V/50 Hz 230 1~ W 614 A 2.69 m3/s 0.72 min-1 1220 C 40 C 40 dB(A) 36 kg 67 B IP 54 F 20 S-ET 10 Transformer RTRE 3 Transformer REU 3* Thyristor REE 4* 5
400 5775 230 1~ 603 2.64 0.73 1186 40 40 39 72 B IP 54 20 S-ET 10 RTRE 3 REU 3* REE 4* 5
53
dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 125-900 LwA Inlet LwA Outlet
Tot 63 52 61 36 47 50 49 46 30 45 42 125 47 53 32 43 49
dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 160-900 LwA Inlet LwA Outlet
Tot 63 59 68 44 53 56 39 49 6 37 47 125 56 57 32 52 53
dB(A)
LwA Inlet LwA Outlet LwA Surrounding
Tot 63 66 73 47 60 63 47 59 19 45 57 125 63 63 38 59 59
dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 250-900 LwA Inlet LwA Outlet
Tot 63 69 77 49 64 67 50 62 22 47 59 125 67 68 42 63 64
54
dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 315-900 LwA Inlet LwA Outlet
Tot 63 60 71 42 55 59 36 125 56 63 35
dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 315-900 LwA Inlet LwA Outlet
Tot 63 63 73 43 61 64 61 59 31 60 58 125 55 61 35 52 58
57 63
54 58
53 60
44 50
26 47
20 44
29 50
33 53
29 50
dB(A)
LwA Inlet LwA Outlet LwA Surrounding
Tot 63 62 72 43 61 64 60 58 31 60 58 125 55 60 35 52 57
dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 400-900 LwA Inlet LwA Outlet
Tot 63 63 73 46 61 67 60 62 33 59 61 125 58 61 37 55 58
55
MTP 10 p. 341
EC-Vent p. 329-330
tECHNICAL DATA
KVKE Art no. Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 3 m Weight Insulation class, motor Enclosure class, motor Motor protection Speed control Wiring diagram p. 391-400 125 EC 2570 V/50 Hz 230 1~ W 68.7 A 0.536 m3/s 0.104 min-1 3339 C 60 C 60 dB(A) 41 kg 13.2 B IP 44 Integral Electronic MTP 42 160 EC 2571 230 1~ 67.7 0.531 0.151 2592 60 60 39 17 B IP 44 Integral MTP 42 200 EC 2575 230 1~ 156 1.10 0.24 3033 60 60 46 18.8 B IP 44 Integral MTP 42 250 EC 2577 230 1~ 265 1.64 0.321 2821 55 55 49 28.1 B IP 44 Integral MTP 42 315 EC 2578 230 1~ 308 1.89 0.492 2215 45 45 47 38.8 B IP 44 Integral MTP 42
56
50 * C B *
FK p. 355
SG p. 357
F 27 A 47 D
VK p. 356
A KVKE 125 EC KVKE 160 EC KVKE 200 EC KVKE 250 EC KVKE 315 EC 125 160 200 250 315 B 433 482 482 578 680 C 479 528 534 700 802 D 125 145,5 150,5 176 208.5 E 128,5 132,5 149 174 207.5 F 442 505 505 596 705.5 G 246 266 303 359 430 H 470 530 530 620 730
IGK p. 357
* Handle 315M/L
RSK p. 355
LDC p. 348
FFR p. 349
1 2 3 4 5
KVKE 125 EC KVKE 160 EC KVKE 200 EC KVKE 250 EC KVKE 315 EC
57
dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 125-900 LwA Inlet LwA Outlet
Tot 63 60 76 48 54 61 46 54 18 42 50 125 57 63 40 53 59
dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 160-900 LwA Inlet LwA Outlet
Tot 63 57 72 46 51 57 42 50 19 40 48 125 54 59 39 50 55
dB(A)
LwA Inlet LwA Outlet LwA Surrounding
Tot 63 64 80 53 58 66 52 57 27 50 55 125 59 64 43 55 60
dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 250-900 LwA Inlet LwA Outlet
Tot 63 67 83 56 61 70 53 64 32 50 61 125 64 70 49 60 66
58
dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 315-900 LwA Inlet LwA Outlet
Tot 63 66 85 54 53 62 36 125 64 71 48
62 77
52 61
61 68
54 76
35 59
27 50
33 55
35 56
29 47
59
RE p. 320
The KVKE models have a single inlet centrifugal fan with backwardcurved blades and a maintenance-free external rotor motor. These fans develop relatively high static pressure and have a high efficiency. The KVKE motor and impeller are mounted on the access cover for ease of maintenance. The service cover can be easily removed by withdrawing the hinge pin. To protect the motor from overheating, the fans have integral thermal contacts with automatic reset. The fans can be installed in any position and are easy to connect to spiral ducts using FK mounting clamps. The KVKE models are manufactured from galvanised sheet steel and are thermally and acoustically insulated with a 50 mm layer of rockwool with a surface liner which prevents the migration of fibres into the airstream.
REU p. 320
REE p. 321
tECHNICAL DATA
KVKE Art no. Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 3 m Weight Insulation class, motor Enclosure class, motor Capacitor Motor protection Speed control, five-step Speed control, five step high/low Speed control, stepless Wiring diagram p. 391-400 125 1406 V/50 Hz 230 1~ W 55.1 A 0.244 m3/s 0.0854 min-1 2548 C 70 C 70 dB(A) 34 kg 14 B IP 44 F 2 Integral Transformer RE 1.5 Transformer REU 1,5 Thyristor REE 1 4 160 1409 230 1~ 97.6 0.422 0.148 2687 70 70 36 18 B IP 44 3 Integral RE 1.5 REU 1.5 REE 1 4 200 1412 230 1~ 152 0.67 0.211 2661 70 70 47 19.5 F IP 44 4 Integral RE 1.5 REU 1.5 REE 1 4 250 M 1416 230 1~ 186 0.841 0.27 2655 58 58 38 26.5 B IP 44 5 Integral RE 1.5 REU 1.5 REE 1 4 250 L 1419 230 1~ 258 1.10 0.317 2578 60 56 45 28.5 F IP 44 7 Integral RE 1.5 REU 1.5 REE 2 4 315 M 1421 230 1~ 285 1.23 0.44 2505 60 60 41 40.5 F IP 44 7 Integral RE 1.5 REU 1.5 REE 2 4 315 L 1423 230 1~ 496 2.15 0.61 2364 59 49 50 42 F IP 44 12 Integral RE 3 REU 3 REE 4 4
60
Free area
H 50
FK p. 355
Handle
E
size 315M/L
D
C B
SG p. 357
F 60
VK p. 356
IGK p. 357
705.5* 430
* + handle
RSK p. 355
LDC p. 348
1 2 3
1 2 3 4
61
dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 125-900 LwA Inlet LwA Outlet
Tot 63 56 70 41 35 50 6 125 50 59 35
dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 160-900 LwA Inlet LwA Outlet
Tot 63 57 71 43 54 57 55 53 32 53 51 125 48 58 30 44 54
48 58
31 46
46 55
43 55
9 30
0 18
0 11
0 26
0 19
dB(A)
LwA Inlet LwA Outlet LwA Surrounding
Tot 63 67 79 54 60 68 44 56 12 42 54 125 58 61 40 54 57
dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 250-900 LwA Inlet LwA Outlet
Tot 63 60 73 45 52 59 44 56 17 41 53 125 54 56 37 50 52
62
dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 250-900 LwA Inlet LwA Outlet
Tot 63 65 78 52 51 60 28 125 60 62 44
dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 315-900 LwA Inlet LwA Outlet
Tot 63 61 76 47 56 65 46 60 21 45 59 125 57 59 38 54 56
58 65
48 57
56 58
53 61
37 55
26 45
22 47
35 52
33 46
dB(A)
LwA Inlet LwA Outlet LwA Surrounding
Tot 63 70 85 57 65 77 58 62 37 57 61 125 66 71 48 63 68
63
DS
RSI
DS
SRKG Damper
WSG
SRKG
FGV
General
Systemair rectangular and square duct fans have been developed for use in compact exhaust and supply air systems. Covering a wide performance spectrum and availability of a comprehensive range of accessories, including heating and cooling coils, filters, silencers and more, offers solutions for complete systems for almost all applications. Our experience over the past 35 years and continuous research and development of new products and technology have made the Systemair duct fan a market leader. Our motto the straight way is revealed in the straight routing of airflow in a ducted system. For instance, the flexibility offered by removable panels allows the MUB Range to be adapted to all installation positions and airflow directions, which can still be decided during installation. The MUB Range is suited for outdoor applications (complete with Systemair weather protection accessories).
Systemair range
Systemair rectangular duct fans are available in 3 different versions. Where high pressure losses occur in a system we offer the KE/KT range. The RS and RSI Range is ideal for installing where the ease of maintenance or comfort is a requirement. The RSI Range is perfectly suited where low noise levels are a pre-requisite. The casings are manufactured from galvanized steel. The RSI Models have double skin with mineral wool insulation (40-60 kg/m). Systemair Multiboxes, MUB, are offered in four box sizes with varying capacities available within one size. The casing consists of a self supporting aluminium profiled frame, with either aluminium or PA6 plastic corner pieces. The double skin panels have 20 mm acoustic and thermal insulation, consisting of mineral wool with a density of 25 kg/m3. The MUB/T Therma Multibox has the motor out of the airstream which enables temperatures of up to 100C to be
exhausted. The bottom panel serves as a drain pan and is complete with a drain plug. The motor and impeller can easily be removed from the unit for cleaning and servicing.
Motors
All Systemair rectangular duct fans have external rotor motors which are suitable to control by means of voltage control. All motors have thermal motor protection embedded in the windings. The MUB Range of square duct fans is equipped with powerful external rotor motors up to size 499 and from size 500 with IEC standard motors. All MUB/T versions are equipped with IEC standard motors separated from the airstream. By combining a Systemair motor protection device optimum operational reliability is guaranteed.
64 64
KE, KE(I) . . . . . . . . . . . . . . . . 66 Rectangular duct fans: up to 0.81 m3/s, forward curved impeller, 1 phase. (I) insulated version.
MUB EC. . . . . . . . . . . . . . . . . 94 Multibox fan with EC-motor: up to 3.62 m3/s, 1 and 3 phase.
KT, KT(I) . . . . . . . . . . . . . . . . . 70 Rectangular duct fans: up to 2.47 m3/s, forward curved impeller, 3 phase. (I) insulated version.
MUB. . . . . . . . . . . . . . . . . . 102 Multibox fans: up to 4.80 m3/s, backward curved impeller, 1 and 3 phase.
IE2
2009/640/EG
KDRE/KDRD . . . . . . . . . . . . 114 Mixed flow square duct fans: up to 4.12 m3/s, mixed flow impeller, 1 and three phase.
IE2
2009/640/EG
RSI. . . . . . . . . . . . . . . . . . . . . 84 Insulated rectangular duct fans: up to 3.35 m3/s, backward-curved impeller, 1 and 3 phase.
MUB/T . . . . . . . . . . . . . . . . . 118 Thermo Multibox: up to 4.4 m3/s, backward curved impeller, 1 phase and 3 phase.
100C
KVD. . . . . . . . . . . . . . . . . . . . 90 Box fans: up to 2.0 m3/s, 1 and 3 phase, forward curved impeller, direct driven.
65 65
S-ET p. 341
Quick selection
The KE models have impellers with forward-curved blades and external rotor motors. The motor and impeller are mounted on the access cover to facilitate easy maintenance. The casing is manufactured from galvanised sheet steel. To protect the motor from overheating the fans have integral thermal contacts with external leads for connection to a motor protection device. The fans can be installed in any position and are simple to couple using DS flexible connections. The KE fans have a prewired, integral terminal box. KE(I) versions have double skin side panels, manufactured from galvanised steel with 25 mm mineral wool insulation.
RTRE p. 320
RE p. 320
1 2 3 4
1 2 3
REU p. 320
REE p. 321
2 3 1
Technical data
KE 40-20-4 Art no. KE Art no. KE(I) Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 3 m Weight Insulation class, motor Enclosure class, motor Capacitor Motor protection Speed control, five-step Speed control, five step high/low Speed control, stepless Wiring diagram p. 391-400 * + S-ET 10 1463 68560 V/50 Hz 230 1~ W 248 A 1.08 m3/s 0.293 min-1 1059 C 45 C 45 dB(A) 55/49 kg 13.8/15 F IP 44 F 6 S-ET 10 Transformer RTRE 1,5 Transformer REU 1,5 Thyristor REE 2 * 5 KE 50-25-4 1467 68562 230 1~ 533 2.51 0.479 1298 70 69 55/51 19.8/33 F IP 54 8 S-ET 10 RTRE 3 REU 3 REE 4 6 KE 50-30-4 1473 68565 230 1~ 819 3.67 0.64 1193 70 70 59/55 24.8/39 F IP 54 14 S-ET 10 RTRE 5 REU 5 REE 4 6 KE 50-30-6 1471 230 1~ 294 1.48 0.404 676 70 70 49 23.3 F IP 54 6 S-ET 10 RTRE 3 REU 3 REE 2 6 KE 60-30-4 1478 68569 230 1~ 1261 5.93 0.847 1046 43 43 58/56 32/55 F IP 54 20 S-ET 10 RTRE 7 REU 7 6 KE 60-30-6 1476 68570 230 1~ 493 2.30 0.659 898 70 70 55/50 33/36 F IP 54 14 S-ET 10 RTRE 3 REU 3 REE 4 6 KE 60-35-6 1480 68573 230 1~ 554 2.63 0.68 565 41 41 51/44 34.5/54 F IP 54 8 S-ET 10 RTRE 3 REU 3 REE 4 6
66
Ventilation accessories
DS p. 363
10,0(x8)
H 28 30 32 34 47
VK p. 368
LDR p. 358
FFK p. 355
C A D
RB p. 359
VBR p. 365
67
dB(A) LwA Inlet LwA Outlet LwA Surr. KE(I) With LDR 40-20 LwA Inlet LwA Outlet
Tot 63
69 72 54 55 42
dB(A) 4k
55 61 46
Tot 63 125 69 64 50 47 53 46 73 77 62 58 59 77 62 56 35 26 55 77
250
62 66 58
500
61 65 55
1k
57 66 55
2k
56 63 49
8k
49 54 41
LwA Surrounding 62 56 63 62
30 54 55
42 61 58
54 53 57
47 46 50
46 34 43
43 40 47
38 43 49
32 39 44
dB(A)
LwA Inlet LwA Outlet LwA Surrounding LwA Surr. KE(I)
Tot 63 76 80 66 62 77 66 66 60 38 33 77 60 125 71 68 57 54 48 60
dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDR 50-30 LwA Inlet LwA Outlet
Tot 63 67 70 56 59 57 58 55 50 58 55 125 61 58 48 53 50
68
dB(A) LwA Inlet LwA Outlet LwA Surrounding LwA Surr. KE(I) With LDR 60-30 LwA Inlet LwA Outlet
Tot 63
77 82 65 63 63 46
dB(A) 4k
68 75 55
Tot 63 125 65 65 51 49 57 57 71 75 62 57 65 61 64 55 56 41 64 55
250
66 68 55
500
65 74 55
1k
70 77 59
2k
69 74 56
8k
63 69 49
63 68 68
28 63 63
51 65 63
53 51 53
55 45 54
57 39 46
57 52 57
54 54 61
44 52 58
dB(A)
LwA Inlet LwA Outlet LwA Surrounding LwA Surr. KE(I)
Tot 63 67 72 58 51 61 61 60 56 52 42 60 56 125 60 60 49 45 53 53
69
STDT p. 342
The KT models have impellers with forward-curved blades and external rotor motors. The motor and impeller are mounted on the access cover to facilitate easy maintenance. The casing is manufactured from galvanised sheet steel. To protect the motor from overheating the fans have integral thermal contacts with external leads for connection to a motor protection device. The fans can be installed in any position and are simple to couple using DS flexible connections. The KT fans have a prewired, integral terminal box. KT(I) versions have double skin side panels, manufactured from galvanised steel with 25 mm mineral wool insulation.
RTRD p. 321
RTRDU p. 321
Quick selection
1 2 3 4 5
6 4
6 7 8 9
2 1 5 3 7
1 2 3 4 4 5 1 6 7 7 5 2 3 6 8 8
Technical data
KT Art no. KT Art no. KT(I) Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 3 m Weight KT/KT(I) Insulation class, motor Enclosure class, motor Motor protection Speed control, five-step Speed control, five step high/low Wiring diagram p. 391-400 40-20-4 1482 68561 V/50 Hz 400 3~ W 289 A 0.519 m3/s 0.368 min-1 1303 C 63.4 C 63.4 dB(A) 52/49 kg 13.5/25 B IP 44 STDT 16 Transformer RTRD 2 Transformer RTRDU 2 7 50-25-4 1487 68563 400 3~ 565 0.969 0.544 1287 66.3 51.3 55/50 18.5/32 F IP 54 STDT 16 RTRD 2 RTRDU 2 8 50-25-6 1485 400 3~ 220 0.44 0.381 826 70 70 44 17.5 B IP 54 STDT 16 RTRD 2 RTRDU 2 8 50-30-4 1489 68567 400 3~ 935 1.64 0.72 1223 41 41 57/53 23/23 F IP 54 STDT 16 RTRD 2 RTRDU 2 8 50-30-6 1491 68568 400 3~ 330 0.66 0.509 804 49.9 49.9 51/48 21.5/36 F IP 54 STDT 16 RTRD 2 RTRDU 2 8 60-30-4 1494 68571 400 3~ 1362 2.36 0.953 1279 62.5 62.5 58/55 33.2/36 F IP 54 STDT 16 RTRD 4 RTRDU 4 8 60-30-6 1493 68572 400 3~ 418 0.855 0.598 837 39.9 39.9 48/43 26.5/36 F IP 54 STDT 16 RTRD 2 RTRDU 2 8 60-35-4 1499 68575 400 3~ 2478 4.15 1.32 1244 42.3 42.3 61/58 40.5/61 F IP 54 STDT 16 RTRD 7 RTRDU 7 8 60-35-6 1497 68574 400 3~ 935 1.84 1.08 777 44.3 44.3 52.5/48 34.5/40 F IP 54 STDT 16 RTRD 2 RTRDU 2 8
70
Ventilation accessories
DS p. 363
10,0(x8)
H 32 68 68 89 92 92 92 113 113
VK p. 368
LDR p. 358
FFK p. 355
KT (I) 50-30-4 60-30-4 60-30-6 60-35 70-40-4 70-40-6 80-50 100-50 A 562 642 642 717 787 787 880 980 B 561 661 661 661 761 761 861 1061 C 361 361 361 411 461 461 560 560 D 383.7 383.7 433.7 470.3 470.3 587.3 588.8 E 396 418.5 399 473.5 523.5 506.5 625 626.5 F 385.5 408 388.5 463 513 496 614.5 616
RB p. 359
VBR p. 365
KT Art no. KT Art no. KT(I) Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 3 m Weight KT/KT(I) Insulation class, motor Enclosure class, motor Motor protection Speed control, five-step Speed control, five step high/low Wiring diagram p. 391-400
70-40-4 1506 68576 V/50 Hz 400 3~ W 4186 A 7.15 m3/s 1.84 min-1 1250 C 48.5 C 48.5 dB(A) 66/60 kg 57.7/65 F IP 54 STDT 16 Transformer RTRD 14 Transformer 8
70-40-6 1504 68577 400 3~ 1628 3.02 1.46 805 60.8 60.8 57/51 46.7/72 F IP 54 STDT 16 RTRD 4 RTRDU 4 8
70-40-8 1502 68578 400 3~ 951 1.89 1.28 661 68.7 68.7 51/50 45.5/65 F IP 54 STDT 16 RTRD 4 RTRDU 4 8
80-50-4 1513 400 3~ 5639 9.22 2.15 1266 41 41 67 73.5 F IP 54 STDT 16 RTRD 14 8
80-50-6 1511 400 3~ 2799 5.12 2.1 828 70 70 59 67.5 F IP 54 STDT 16 RTRD 7 RTRDU 7 8
80-50-8 1509 400 3~ 1167 2.44 1.52 548 62 62 59 60.5 F IP 54 STDT 16 RTRD 4 RTRDU 4 8
100-50-6 1516 68582 400 3~ 4450 7.82 2.73 794 43 43 62/61 83.5/100 F IP 54 STDT 16 RTRD 14 8
100-50-8 1514 68583 400 3~ 2287 4.68 2.30 614 70 70 58/58 81.5/100 F IP 54 STDT 16 RTRD 7 RTRDU 7 8
71
dB(A) LwA Inlet LwA Outlet LwA Surrounding LwA Surr. KT(I) With LDR 40-20 LwA Inlet LwA Outlet
Tot 63 70 72 59 56 64 62 56 53 34 28 56 53 125 67 63 46 42 62 58
dB(A) LwA Inlet LwA Outlet LwA Surrounding LwA Surr. KT(I) With LDR 50-25 LwA Inlet LwA Outlet
Tot 63 72 76 62 57 58 61 60 56 39 32 53 56 125 67 63 50 46 53 53
Tot 63 63 66 51 54 52 52 50 33 52 50 125 59 55 41 49 45
Tot 63 75 79 64 60 68 66 66 62 45 36 66 62 125 70 68 55 53 62 60
72
dB(A) LwA Inlet LwA Outlet LwA Surrounding LwA Surr. KT(I) With LDR 50-30 LwA Inlet LwA Outlet
Tot 63 66 73 58
55
dB(A) LwA Inlet LwA Outlet LwA Surrounding LwA Surr. KT(I) With LDR 60-30 LwA Inlet LwA Outlet
Tot 63 78 81 65 61 72 67 71 59 39 33 71 59 125 71 70 59 55 63 62
57 58
Tot 63 66 69 55 50 60 57 59 53 35 25 59 53 125 60 62 49 44 52 54
73
dB(A)
Tot 63 84 86 73 67 81 78 80 73 55 52 80 73 125 77 75 64 60 70 68
dB(A)
LwA Inlet LwA Outlet LwA Surrounding LwA Surr. KT(I)
Tot 63 72 76 64 58 68 68 67 65 46 44 67 65 125 64 66 57 50 57 59
Tot 63 69 73 58 57 63 63 62 56 35 35 62 56 125 60 59 49 48 53 52
74
Tot 63 68 73 66 63 65 59 55 50 59 55 125 59 59 51 53 53
dB(A) LwA Inlet LwA Outlet LwA Surrounding LwA Surr. KT(I) With LDR 100-50 LwA Inlet LwA Outlet
Tot 63 79 84 69 68 74 71 71 69 59 55 71 69 125 68 71 63 61 62 65
75
dB(A) LwA Inlet LwA Outlet LwA Surrounding LwA Surr. KT(I) With LDR 100-50 LwA Inlet LwA Outlet
Tot 63 73 78 65 65 67 70 64 62 52 47 64 62 125 61 63 55 53 55 57
76
Project: Ice Hockey Stadium City/Country: Bratislava, Slovakia Products/Solutions: K, KD, KT to ventilate different premises at stadium + air distribution products (grilles, diffusers).
77
The RS models have impellers with backward-curved blades and external rotor motors. The motor and impeller are mounted on the access cover to facilitate easy maintenance. To protect the motor from overheating RS 30-15 to 50-25 have an integral thermal contact with electrical reset, RS 60-35 M to 100-50 have integral thermal contacts with external leads for connection to a motor protection device. The fans can be installed in any position and are simple to couple using DS flexibleconnections. The casing is manufactured from galvanised sheet steel.
RTRE p. 320
1 2 3 4 5 6
1 2 3 4 5 6 7
REU p. 320
REE p. 321
3 1 2 4 5 6 1 2 4 3 5 6 7
RTRD/RTRDU p. 321
Technical data
RS Art no. Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 3 m Weight Insulation class, motor Enclosure class, motor Capacitor Motor protection Speed control, five-step Speed control, five step high/low Speed control, stepless Wiring diagram p. 391-400 * + S-ET 10 30-15 1435 V/50 Hz 230 1~ W 59.9 A 0.264 m3/s 0.135 min-1 2431 C 70 C 70 dB(A) 48 kg 6.8 B IP 44 F 2 Integral Transformer RE 1.5 Transformer REU 1.5 Thyristor REE 1 2 40-20 M 1439 230 1~ 106 0.461 0.238 2597 70 70 52 11.8 B IP 44 3 Integral RE 1.5 REU 1.5 REE 1 2 40-20 L 1443 230 1~ 208 0.926 0.342 2556 65 65 53 12.8 F IP 44 5 Integral RE 1.5 REU 1.5 REE 1 2 50-25 1447 230 1~ 138 0.604 0.411 1362 53 53 46 17 B IP 44 5 Integral RE 1.5 REU 1.5 REE 1 2 60-35 M1 1795 230 1~ 401 1.91 0.941 1365 70 70 58 33.4 F IP 54 8 S-ET 10 RTRE 3* REU 3 REE 2* 6 60-35 M3 1796 400 3~ 399 0.795 0.974 1371 70 70 58 32.2 F IP 54 STDT 16 RTRD 2 RTRDU 2 8 60-35 L1 2046 230 1~ 626 2.80 1.12 1308 70 70 58 37.2 F IP 54 14 S-ET 10 RTRE 3* REU 3 REE 4* 6
78
Ventilation accessories
DS p. 363
B D c/c F H
A L
G c/c E C 8,0
RS 30-15 40-20 M 40-20 L 50-25 A 402 502 502 532 B 217 267 267 317 C 340 440 440 540 D 190 240 240 290 E 320 420 420 520 F 170 220 220 270 G 298 398 398 498 H 148 198 198 248 I 79 99 99 125 J 120 125 125 85.5 K 230 310 366 L 254 352 423
VK p. 368
LDR p. 358
310.5 352.5
FFK p. 355
~1300
10,0 (x8)
I J
RB p. 359
B D c/c F H
VBR p. 365
G c/c E C 7,5
I 128
J 145
RS Art no. Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 3 m Weight Insulation class, motor Enclosure class, motor Motor protection Speed control, five-step Speed control, five step high/low Speed control, stepless Wiring diagram p. 391-400
60-35 L3 2047 V/50 Hz 400 3~ W 667 A 1.59 m3/s 1.21 min-1 1408 C 70 C 70 dB(A) 61 kg 37 F IP 54 STDT 16 Transformer RTRD 2 Transformer RTRDU 2 Thyristor 8
70-40 L1 1797 230 1~ 623 2.84 1.59 1308 67 67 60 41.8 F IP 54 S-ET 10 RTRE 5 REU 5* REE 4* 6
70-40 L3 1798 400 3~ 704 1.70 1.39 1410 70 70 61 41.4 F IP 54 STDT 16 RTRD 2 RTRDU 2 8
80-50 M3 1799 400 3~ 1089 1.97 1.96 1335 70 55 60 59.5 F IP 54 STDT 16 RTRD 4 RTRDU 4 8
80-50 L3 1800 400 3~ 1893 3.60 2.60 1385 70 64 63 71.5 F IP 54 STDT 16 RTRD 7 RTRDU 7 8
100-50 L3 1801 400 3~ 2962 5.09 3.36 1361 70 51 65 96.5 F IP 54 STDT 16 RTDR 7 RTRDU 7 8
79
dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDR 30-15 LwA Inlet LwA Outlet
Tot 63 69 72 55 47 51 29 125 59 56 36
dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDR 40-20 LwA Inlet LwA Outlet
Tot 63 71 74 59 62 62 52 51 37 52 51 125 64 62 49 59 57
56 57
47 51
52 49
52 54
41 48
33 39
31 36
31 35
22 27
dB(A)
LwA Inlet LwA Outlet LwA Surrounding
Tot 63 73 77 60 61 63 53 51 34 53 51 125 58 57 42 53 52
dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDR 50-25 LwA Inlet LwA Outlet
Tot 63 68 69 53 61 58 59 54 40 59 54 125 66 65 48 56 55
80
RS 60-35 M1
RS 60-35 M3
dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDR 60-35 LwA Inlet LwA Outlet
Tot 63 73 81 65 57 60 41 125 61 68 54
dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDR 60-35 LwA Inlet LwA Outlet
Tot 63 74 79 65 63 66 59 57 44 59 57 125 62 65 54 55 58
62 68
57 60
54 61
57 65
50 57
46 55
50 57
46 51
39 42
RS 60-35 L3
dB(A)
LwA Inlet LwA Outlet LwA Surrounding
Tot 63 75 80 65 66 67 63 61 47 63 61 125 67 68 56 60 61
dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDR 60-35 LwA Inlet LwA Outlet
Tot 63 78 82 68 68 69 64 60 50 64 60 125 68 70 57 61 63
81
dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDR 70-40 LwA Inlet LwA Outlet
Tot 63 77 80 67 67 70 62 62 46 62 62 125 65 66 56 58 59
dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDR 70-40 LwA Inlet LwA Outlet
Tot 63 78 81 68 68 70 60 63 44 60 63 125 67 66 59 60 59
dB(A)
LwA Inlet LwA Outlet LwA Surrounding
Tot 63 78 83 67 70 75 60 60 47 60 60 125 68 69 56 62 63
dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDR 80-50 LwA Inlet LwA Outlet
Tot 63 82 88 70 73 79 64 70 51 64 70 125 73 74 62 67 68
82
dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDR 100-50 LwA Inlet LwA Outlet
Tot 63 83 91 72 69 73 61 125 73 78 66
76 83
69 73
67 72
66 76
67 75
66 76
68 74
66 69
63 63
83
The RSI models have impellers with backward-curved blades and external rotor motors. The motor and impeller are mounted on the access cover to facilitate easy maintenance. The RSI models are thermally and acoustically insulated with 50 mm mineral wool, with perforated sheet steel on the inner surface. To protect the motor from overheating the RSI fans have integral thermal contacts with external leads for connection to a motor protection device. The fans can be installed in any position and are simple to couple using DS flexible connections. The casing is manufactured from galvanised sheet steel.
RTRE p. 320
REU p. 320
1 2 3 4 5
RSI 60-35 M1 RSI 60-35 M3 RSI 60-35 L1 RSI 60-35 L3 RSI 70-40 L1
1 2 3 4
RTRD/RTRDU p. 321
3 1 2
Technical data
RSI Art no. Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 3 m Weight Insulation class, motor Enclosure class, motor Capacitor Motor protection Speed control, five-step Speed control, five step high/low Speed control, stepless Wiring diagram p. 391-400 * + S-ET 10 60-35 M1 1788 V/50 Hz 230 1~ W 401 A 1.91 m3/s 0.941 min-1 1365 C 70 C 70 dB(A) 50 kg 61 F IP 54 8 S-ET 10 Transformer RTRE 3 Transformer REU 3* Thyristor REE 2* 6 60-35 M3 1789 400 3~ 399 0.795 0.974 1371 70 70 48 60.5 F IP 54 STDT 16 RTRD 2 RTRDU 2 8 60-35 L1 2042 230 1~ 626 2.80 1.12 1308 70 70 52 65 F IP 54 14 S-ET 10 RTRE 3 REU 3* REE 4* 6 60-35 L3 2043 400 3~ 667 1.59 1.21 1408 70 70 57 65 F IP 54 STDT 16 RTRD 2 RTRDU 2 8 70-40 L1 1790 230 1~ 623 2.84 1.59 1308 67 67 51 82.5 F IP 54 14 S-ET 10 RTRE 2 REU 3* REE 4* 6 70-40 L3 1791 400 3~ 704 1.70 1.39 1410 70 70 51 81.2 F IP 54 STDT 16 RTRD 2 RTRDU 2 8
84
Ventilation accessories
~1200
DS p. 363
c/c F
D B
G c/c E C A
VK p. 368
I 55
J 92.5
N 532
LDR p. 358
640.5 391
139.5 99.5
1108 662
1020 520
FFK p. 355
RB p. 359
VBR p. 365
RSI Art no. Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 3 m Weight Insulation class, motor Enclosure class, motor Motor protection Speed control, five-step Speed control, five step high/low Speed control, stepless Wiring diagram p. 391-400
80-50 M3 1792 V/50 Hz 400 3~ W 1089 A 1.97 m3/s 1.96 min-1 1335 C 70 C 55 dB(A) 53 kg 109 F IP 54 STDT 16 Transformer RTRD 4 Transformer RTRDU 4 Thyristor 8
80-50 L3 1793 400 3~ 1893 3.60 2.60 1385 70 64 56 122 F IP 54 STDT 16 RTRD 7 RTRDU 7 8
100-50 L3 1794 400 3~ 2962 5.09 3.36 1361 70 51 62 159 F IP 54 STDT 16 RTRD 7 RTRDU 7 8
85
RSI 60-35 M3
dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDR 60-35 LwA Inlet LwA Outlet
Tot 63 65 79 57 52 65 43 48 29 43 48 125 53 61 47 46 54
dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDR 60-35 LwA Inlet LwA Outlet
Tot 63 67 79 55 59 66 55 57 29 55 57 125 62 65 47 55 58
RSI 60-35 L1
RSI 60-35 L3
dB(A)
LwA Inlet LwA Outlet LwA Surrounding
Tot 63 71 82 59 63 70 60 66 40 60 66 125 66 69 54 59 62
dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDR 60-35 LwA Inlet LwA Outlet
Tot 63 72 83 64 63 69 55 60 26 55 60 125 67 70 56 60 63
86
dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDR 70-40 LwA Inlet LwA Outlet
Tot 63 67 80 58 57 62 41 125 61 66 46
dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDR 70-40 LwA Inlet LwA Outlet
Tot 63 68 81 57 61 70 57 63 39 57 63 125 62 66 46 55 59
60 70
57 62
54 59
51 64
46 60
43 60
46 62
43 57
40 51
dB(A)
LwA Inlet LwA Outlet LwA Surrounding
Tot 63 71 83 60 64 75 58 59 40 58 59 125 64 68 51 58 62
dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDR 80-50 LwA Inlet LwA Outlet
Tot 63 74 88 63 68 79 63 70 43 63 70 125 69 74 56 63 68
87
dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDR 100-50 LwA Inlet LwA Outlet
Tot 63 79 91 69 72 83 68 73 53 68 73 125 73 78 62 67 72
88
Project Bolshoi Ice Palace City/Country: Sochi, Russia The building has been constructed for the Olympic Games in 2014. It is located in Olympic Park near the sea. It will be a major hockey stadium during the Games in 2014. Arena is designed for 12,000 visitors. The architecture of Arena resembles the famous Faberg egg, based on the concept of the image of frozen droplets. The arena is equipped with 75 AXC fans for smoke pressurization. TA units and duct fans are used for supply and extract air. Completion date of construction is 2012. Total building area is around 55,000 m2.
89
REV p. 340
Direct driven box fan for in-line operation and suitable for outdoor installation. The unit is fitted with a forward curve double inlet fan and IP54 F class motor.The casing is manufactured from 1mm galvanized steel.The fan is mounted on 4 anti-vibration rubber mounts and the outlet connected to the casing via an 18mm flexible connection. An IP 55 connection box is fitted on the casing for easy access. Belt driven box fan for in-line operation and suitable for outdoor installation. The units are fitted with either forward curved or backward curved belt driven centrifugal fans and IP 55 Class F IE2 motors. Selection programme available as a download from www.systemair.com
DTV p. 343
tECHNICAL DATA
KVD Art no. Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air Sound pressure level at 1 m Weight Insulation class, motor Enclosure class, motor Wiring diagram p. 391-400 7-7-E4 645348 V/50 Hz 230 1~ W 146 A 2.20 m3/s 0.47 min-1 1410 C 50 dB(A) 58 kg 20 F IP 54 1 7-7-E6 645327 230 1~ 73 1.10 0.47 960 50 54 20 F IP 54 1 9-7-E4 645329 230 1~ 370 4.00 0.76 1410 50 61 30 F IP 54 1 9-7-E6 645328 230 1~ 237 2.5 0.70 950 50 59 30 F IP 54 1 9-9-E4 645349 230 1~ 550 5.90 0.88 1450 50 64 32 F IP 54 1 9-9-E6 645330 230 1~ 237 2.40 0.72 950 50 61 31 F IP 54 1 10-8-E6 645332 230 1~ 237 3.00 0.71 950 50 63 35 F IP 54 1
90
A'
LDC p. 348
A'' A
B'
FK p. 355
RSK p. 355
ORH p. 357
KVD Art no. Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air Sound pressure level at 3 m Weight Insulation class, motor Enclosure class, motor Wiring diagram p. 391-400
10-10-E4 645351 V/50 Hz 230 1~ W 550 A 6.00 m3/s 0.90 min-1 1375 C 50 dB(A) 66 kg 37 F IP 54 1
91
92
E6
E6 (525W) E6 (237W)
E6 (237W) E6 (525W)
E6
E6 (1100W)
E6 (736W)
E6 (525W)
E6 (525W)
E6 (1100W) E6 (736W)
93
MTP 10 p. 341
The MUB-EC fans are driven by EC-external rotor motors. These are energy saving motors with high efficiency. The power electronics are integrated in the motor housing. All models have one potential-free terminal for error message. All motors are suitable to be used for 50/60Hz. The input voltage for single phase units can vary between 200 and 277V, for three phase units between 380 and 480V. Speed control by a 0-10V signal. From size 450 the motor has an output voltage of 10V and 20V for an external potentiometer. MUB-EC is equipped with impellers with backward curved blades, manufactured from aluminium. The Mini MUB 200EC box is equipped with impellers with backward curved blades, manufactured from plastic PA6 25GV. The casing consists of an aluminium frame with fibreglass reinforced plastic corners of PA6; highly shock-resistant. The double skin panels are manufactured from galvanized steel with 20 mm mineralwool insulation. To avoid condensation the profile is provided with a separate chamber to fix the screws. The
CXE/AVC p. 322
EC-Vent p. 329-330
panels are removable, any outlet side can be chosen, allowing flexible ventilation solutions. Installation in any mounting position is possible.
Mini MUB
Technical data
MUB Art no. Techn.data is relating to 90 outlet Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 3 m Weight Insulation class, motor Enclosure class, motor Speed control, electronic Speed control, electronic Wiring diagram p. 391-400 Mini MUB 33032 200 EC V/50/60 Hz 230 1~ W 89.1 A 0.701 m3/s 0.174 min-1 3965 C 40 C 40 dB(A) 47 kg 8.1 B IP 44 CXE/AVC MTP 10 23a 025 315 30676 EC-A2 230 1~ 180 1.40 0.685 1870 60 60 44 30 B IP 44 CXE/AVC MTP 10 23b 025 355 30670 EC-A2 230 1~ 388 2.37 0.884 1639 60 60 53 28 B IP 44 CXE/AVC MTP 10 23b 042 400 30209 EC-A2 230 1~ 378 2.26 1.08 1339 60 60 51 58 B IP 44 CXE/AVC MTP 10 23b 042 450 30610 EC-A2 400 3~ 1170 1.95 1.75 1560 60 60 56 65 B IP 54 CXE/AVC MTP 10 28 042 450 31380 EC-A2-K 230 1~ 597 2.71 1.41 1297 60 60 56 65 B IP 54 CXE/AVC MTP 10 28
94
Ventilation accessories
A 500 500 670 670 670 670 800 800 B 500 500 670 670 670 670 800 800 C 420 420 590 590 590 590 720 720 D 315 355 400 454 450 504 560 630 E 200 224 253 286 286 321 360 407 F 40 40 40 70 70 70 70 70
042 450EC-A2 042 450EC-A2-K 042 500EC-A2 062 560EC-A2 062 630EC-A2
FGV p. 370
SRKG p. 370
E D C B
UGS p. 370
1 2 3 4 5
1 2 3 4
Mini MUB EC MUB 025 315EC-A2 MUB 025 355EC-A2 MUB 042 400EC-A2
MUB 042 450EC-A2 MUB 042 450EC-A2-K MUB 042 500EC-A2 MUB 062 560EC-A2 MUB 062 630EC-A2
1 3
MUB Art no. Techn.data is relating to 90 outlet Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 3 m Weight Insulation class, motor Enclosure class, motor Speed control, electronic Speed control, electronic Wiring diagram p. 391-400
042 500 30314 EC-A2 V/50/60 Hz 400 3~ W 1100 A 2.18 m3/s 2.07 min-1 1340 C 60 C 60 dB(A) 56 kg 70 B IP 54 CXE/AVC MTP 10 28
062 560 30235 EC-A2 400 3~ 2000 3.10 3.00 1360 60 60 57 90 F IP 54 CXE/AVC MTP 10 28
062 630 30207 EC-A2 400 3~ 2560 3.90 3.63 1210 60 60 67 95 F IP 54 CXE/AVC MTP 10 28
95
Tot 63 75 80 54 55 59 32 125 65 65 43
Tot 63 68 72 54 35 48 22 125 62 70 51
96
Tot 63 75 77 60 43 43 35 125 64 69 53
Tot 63 70 74 59 41 49 31 125 60 67 51
97
Tot 63 78 83 70 46 68 29 125 68 76 67
Tot 63 78 77 64 42 47 33 125 60 63 51
98
Tot 63 77 80 65 46 49 35 125 71 70 55
Tot 63 80 77 71 51 57 40 125 71 70 66
99
Tot 63 82 83 76 54 59 47 125 75 75 74
100
101
IE2
2009/640/EG
MUB
The MUB fans have impellers with backward curved blades, manufactured from polyamide (size 355), aluminium (size 400-560), welded steel painted in RAL 5002 (size 100 630D4-L). The MUB 355-500 is equipped with external rotor motors, fully speed controllable. MUB 500-560DV, DS are driven by an IEC standard motor. For size 630D4-A2, 630D4-L and 710D6-A speed control is only possible by using a frequency converter. All single speed motors are in IE2 execution and possible to control via frequency converter. The three phase motors are D/Y connected for two speed operation. Motor protection is done by thermal contacts, which have to be connected to an external motor protection device. The casing consists of a corrosion-resistant aluminum frame with fiberglass reinforced plastic corners of PA6; highly shock resistant. The double skin panels are manufactured from galvanized steel with 20 mm mineral wool insulation. To avoid condensation the profile is provided with a separate chamber to fix screws. The Multibox fans are delivered for straight through airflow but can easily be rebuilt due to removable panels. This allows flexible ventilation solutions. The MUB can also be used as extract- or supply air unit in air handling units. Installation in any mounting position is possible.
Electrical accessories
S-ET/STDT p. 341-342
RTRE p. 320
REU p. 320
REE p. 321
6726, 6734, 6739, 6748, 6751, 6755, 6777, 6779
MUB 025 355 E4-A2 MUB 025 355 DV-A2 MUB 042 400 E4-A2 MUB 042 400 DV-A2 MUB 042 450 E4-A2 MUB 042 450 DV-A2 MUB 042 499 E4-A2 MUB 042 499 DV-A2
1 2 3 4 5 6 7 8 9 1
MUB 042 500 E4-A2 MUB 042 500 D4-A2 IE2 MUB 062 560 D4-A2 IE2 MUB 062 560 D6-A2 IE2 MUB 062 630 D4-A2 IE2 MUB 062 630 D6-A2 IE2 MUB 062 630 DV-B2 MUB 100 630 D4-L IE2 MUB 100 710 D6-A2 IE2
7 9 5
RTRD/RTRDU p. 321
1 2
FRQ p. 325
Technical data
MUB Art no. Techn.data is relating to 90 outlet Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air Sound pressure level at 3 m Weight Insulation class, motor Enclosure class, motor Capacitor Motor protection Speed control, five-step Speed control, five step high/low Speed control, 2-step Speed control, stepless Wiring diagram p. 391-400 * + S-ET 10 025 355 2104 E4-A2 V/50 Hz 230 1~ W 264 A 1.19 m3/s 0.741 min-1 1399 C 40 dB(A) 55 kg 37 B IP 44 8 S-ET 10 Transformer RTRE 1.5 Transformer REU 1.5* Thyristor REE 2* 5 025 355 2775 DV-A2 400 3~ 243 0.541 0.731 1349 40 55 37 B IP 44 STDT 16 RTRD 2 RTRDU 2 S-D2SKT 16 042 400 2116 E4-A2 230 1~ 467 2.13 1.01 1358 40 49 58 F IP 54 10 S-ET 10 RTRE 3 REU 3* REE 4* 5 042 400 2112 DV-A2 400 3~ 430 0.826 1.08 1339 40 49 57 F IP 54 STDT 16 RTRD 2 RTRDU 2 S-D2SKT 16 042 450 2124 E4-A2 230 1~ 756 3.33 1.48 1249 60 52 60 F IP 54 16 S-ET 10 RTRE 5 REU 5* REE 4* 5 042 450 2123 DV-A2 400 3~ 726 1.32 1.52 1277 40 52 62 F IP 54 STDT 16 RTRD 2 RTRDU 2 S-D2SKT 18 042 499 2134 E4-A2 230 1~ 1023 4.72 1.87 1270 40 48 66 F IP 54 20 S-ET 10 RTRE 5 REU 5 6 042 499 2133 DV-A2 400 3~ 1457 1.64 1.76 1210 40 48 64 F IP 54 STDT 16 RTRD 2 RTRDU 2 S-D2SKT 18 042 500 2141 E4-A2 230 1~ 1310 5.78 2.13 1332 40 56 68 F IP 54 30 S-ET 10 RTRE 7 REU 7 6
102
Ventilation accessories
FGV p. 370
SRKG p. 370
E D D C B
UGS p. 370
A MUB042 500DS-A2 MUB042 500DV-A2 MUB062 560DS-A2 MUB062 560DV-A2 MUB062 630DV-B2 MUB062 630DS-B2 MUB062 630D4-L MUB062 710D6-A2
E D D C B A
D 548 548 676 676 678 678 878 878 878 878
D 504 504 570 570 635 635 630 715 630 715
E 321 321 361 361 407 407 389 460 389 460
WSG p. 370
1000 1000 920 1000 1000 920 1000 1000 920 1000 1000 920
MUB Art no. Techn.data is relating to 90 outlet Voltage/Frequency Power at shaft (P2) Current Max air flow R.p.m. Max temp. of transported air Sound pressure level at 3 m Weight Insulation class, motor Enclosure class, motor Motor protection Speed control, five-step Speed control, 2-step Speed control, stepless Wiring diagram p. 391-400
042 500 33542 D4-A2 IE2 V/50 Hz 400 3~ W 1500 A 3.39 m3/s 2.15 min-1 1400 C 40 dB(A) 55 kg 68 F IP 55 FRQ5(S)-4A FRQ(S)-4A 13b Y
062 560 33543 D4-A2 IE2 400 3~ 2200 4.64 3.25 1420 40 56 99 F IP 55 FRQ5(S)-10A FRQ(S)-10A 13b Y
062 560 33544 D6-A2 IE2 400 3~ 750 1.98 2.19 905 40 47 117 F IP 55 FRQ5(S)-4A FRQ(S)-4A 13b Y
062 630 33545 D4-A2 IE2 400 3~ 4000 8.12 3.89 1450 40 68 135 F IP 55 FRQ(S)-10A 13b D
062 630 33546 D6-A2 IE2 400 3~ 1500 3.61 2.76 940 40 53 130 F IP 55 FRQ(S)-4A 13b Y
062 630 2150 DV-B2 400 3~ 3890 6.4 4.17 1370 40 69 145 F IP 54 STDT 16 S-D2SKT 18
100 630 33549 D4-L IE2 400 3~ 4000 8.12 5.07 1450 40 74 160 F IP 55 FRQ5(S)-10A FRQ(S)-10A 13b D
100 710 33548 D6-A2 IE2 230D/400 3~ 2200 5.1 4.47 945 40 59 160 F IP 55 FRQ5(S)-10A FRQ(S)-10A 13b Y
103
IE2
2009/640/EG
Tot 63 68 70 62 55 57 49 125 57 59 51
Tot 63 68 70 62 55 57 49 125 57 59 51
104
Tot 63 72 74 56 59 61 43 125 61 63 45
Tot 63 72 74 56 59 61 43 125 61 63 45
105
IE2
2009/640/EG
Tot 63 75 77 59 62 64 46 125 64 66 48
Tot 63 74 76 59 61 63 46 125 63 65 48
106
Tot 63 78 80 55 65 67 42 125 67 69 44
Tot 63 76 78 55 63 65 42 125 65 67 44
107
IE2
2009/640/EG
Tot 63 79 81 63 66 68 50 125 68 70 52
Tot 63 77 79 62 64 66 49 125 66 68 51
108
Tot 63 78 80 63 65 67 50 125 67 69 52
Tot 63 69 71 54 56 58 51 125 58 60 43
109
IE2
2009/640/EG
Tot 63 86 88 75 73 75 62 125 75 77 64
Tot 63 73 75 60 60 62 47 125 62 64 49
110
Tot 63 87 89 76 74 76 63 125 76 78 65
Tot 63 87 89 81 58 60 52 125 76 78 70
111
IE2
2009/640/EG
Tot 63 78 80 66 65 67 53 125 67 69 55
112
113
KDRE/KDRD fans have external rotor motors and mixed flow impeller. The KDRE/KDRD series is notable for its relatively high static pressure and high level of efficiency. The casing is manufactured from galvanised sheet steel. To protect the motor from overheating, the KDRE/KDRD fans have integral thermal contacts with leads for connection to a motor protection device. The fans can be installed in any position and are simple to couple using DS flexible connections.
RTRE p. 320
REU p. 320
1 2 3 4
1 2 3 4
RTRD/RTRDU p. 321
Technical data
KDRE 45 Art no. Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 3 m Weight Insulation class, motor Enclosure class, motor Capacitor Motor protection Speed control, five-step Speed control, five step high/low Speed control, stepless Wiring diagram p. 391-400 * + S-ET 10 1311 V/50 Hz 230 1~ W 325 A 1.55 m3/s 1.00 min-1 1387 C 70 C 70 dB(A) 45 kg 23.5 F IP 54 8 S-ET 10 Transformer RTRE 3 Transformer REU 3* Thyristor REE 2* 6 KDRE 50 1313 230 1~ 442 1.94 1.27 1297 70 70 52 31 F IP 54 10 S-ET 10 RTRE 5 REU 5* REE 4* 6 KDRD 50 1314 400 3~ 462 0.962 1.34 1397 70 70 54 29 F IP 54 STDT 16 RTRD 2 RTRDU 2 8 KDRE 55 1315 230 1~ 861 4.10 1.94 1280 45 45 51 41 F IP 54 16 S-ET 10 RTRE 5 REU 5* 6 KDRD 55 1316 400 3~ 789 1.52 1.87 1315 49 40 55 38 F IP 54 STDT 16 RTRD 2 RTRDU 2 8 KDRE 65 1317 230 1~ 1501 6.61 3.07 1315 70 70 61 54 F IP 54 30 S-ET 10 RTRE 7 REU 7* 6
114
DSK p. 370
45
LDK p. 365
A* c/c B
c/c 470 520 573 680 720 B 492 547 595 707 740 C 400 450 485 510 530
FFS p. 368
A KDRE 45 KDRE/D 50 KDRE/D 55 KDRE/D 65 KDRE 447 502 550 661 696
RBK p. 368
VBK p. 367
KDRD 65 Art no. Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 3 m Weight Insulation class, motor Enclosure class, motor Motor protection Speed control, five-step Speed control, five step high/low Speed control, stepless Wiring diagram p. 391-400 1318 V/50 Hz 400 3~ W 1250 A 2.23 m3/s 2.72 min-1 1341 C 70 C 56 dB(A) 53 kg 50 F IP 54 STDT 16 Transformer RTRD 4 Transformer RTRDU 4 Thyristor 8
KDRD 70 6690 400 3~ 2489 4.67 4.12 1383 70 69 62 62 F IP 54 STDT 16 RTRD 7 RTRDU 7 8
115
dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDK 45 LwA Inlet LwA Outlet
Tot 63 70 74 52 61 64 49 51 33 49 51 125 60 61 40 55 56
dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDK 50 LwA Inlet LwA Outlet
Tot 63 71 74 59 61 64 46 47 27 46 47 125 58 62 45 51 55
dB(A)
LwA Inlet LwA Outlet LwA Surrounding
Tot 63 75 79 61 66 69 59 57 30 59 57 125 65 68 51 58 61
dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDK 55 LwA Inlet LwA Outlet
Tot 63 75 80 58 65 69 58 58 43 58 58 125 62 64 48 53 55
With LDK 50
LwA Inlet LwA Outlet
116
dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDK 55 LwA Inlet LwA Outlet
Tot 63 76 80 62 66 70 56 59 57 56 59 125 61 65 48 52 56
dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDK 65 LwA Inlet LwA Outlet
Tot 63 78 86 68 69 76 56 55 36 56 55 125 65 67 53 59 61
dB(A)
LwA Inlet LwA Outlet LwA Surrounding
Tot 63 79 84 60 70 73 62 62 40 62 62 125 70 68 47 64 62
dB(A) LwA Inlet LwA Outlet With LDK 70 LwA Inlet LwA Outlet
Tot 63 84 89 75 74 44 75 74 125 74 76 54 69 71
LwA Surrounding 69 77 78
With LDK 65
LwA Inlet LwA Outlet
117
FRQ p. 325
100C
IE2
2009/640/EG
All MUB/T fans have impellers with backward curved blades, manufactured from aluminium, and IEC standard motors with efficiency class IE2 for all 400V three phase motors from 0.75 kW. Motors are outside the air stream. The casing consists of an aluminium frame with fiberglass reinforced plastic corners and double skin, galvanised steel panels with 20 mm mineral wool insulation. Panels are removable, allowing flexible ventilation solutions and including a quicklock access door. The MUB bottom panel is shaped as a grease tray and incorporates a premounted drain plug. An isolator switch is mounted on the casing. Motor protection by cold conductors or thermal contact, to be connected to an external motor protection device. Standard execution, seen in airflow direction: service door left, top outlet. NB! Outlet spigot to be ordered as an accessory.
S-ET/STDT p. 341-342
RTRE p. 320
REU p. 320
RTRD/RTRDU p. 321
Technical data
MUB/T Art no. Voltage/Frequency Power at shaft Current Max air flow R.p.m. Max temp. of transported air Sound pressure level at 3 m Weight Insulation class, motor Enclosure class, motor Capacitor Motor protection Speed control, five-step Speed control, five step high/low Speed control, stepless Speed control, electronic Wiring diagram p. 391-400 * + S-ET 10 042 400DV 33655 V/50 Hz 400 3~ W 370 A 1.4 m3/s 1.13 min-1 1370 C 100 dB(A) 47 kg 47 F IP 54 F STDT 16 RTRD 2 Transformer RTRDU 2 13b 042 400E4 33656 230 1~ 370 2.1 1.11 1370 100 47 62 F IP 54 12 S-ET 10 RTRE 3 REU 3* 21 042 450D4-IE2 33657 400 3~ 750 1.78 1.72 1400 100 49 64 F IP 55 U-EK 230E FRQ5(S)-4A FRQ(S)-4A 13b Y 042 450E4 33658 230 1~ 750 5.3 1.68 1430 100 50 62 F IP 54 30 S-ET 10 RTRE 7 REU 7* 21 042 500D4-IE2 33622 400 3~ 1500 3.39 2.23 1400 100 53 68 F IP 55 U-EK 230E FRQ5(S)-4A FRQ(S)-4A 13b Y FRQ(S)-10A FXDM 7 13b Y 062 560D4-IE2 33659 400 3~ 2200 4.2 3.25 1445 100 55 132 F IP 55 U-EK 230E FRQ5(S)-10A
U-EK230E p. 340
062 630D4-IE2 33660 400 3~ 4000 8.12 4.12 1450 100 67 137 F IP 55 U-EK 230E FRQ5(S)-10A FRQ(S)-10A FXDM 13 13b D
118
FGV p. 370
F E D
SRKG p. 370
1 inch
UGS p. 370
MUB/T MUB 042 400 MUB 042 450 MUB 042 500 MUB 062 560 MUB 062 630 A 670 670 670 800 800 B 670 670 670 800 800 C 590 590 590 720 720 D 548 548 548 678 678 E 404 454 504 564 635 F 253 286 321 361 407
WSD p. 370
WSG p. 370
Quick selection
1 2 3 4
MUB/T 042 400DV MUB/T 042 400E4 MUB/T 042 450D4-IE2 MUB/T 042 450E4
1 2 3
1 2
3 4
1 2 3
119
IE2
2009/640/EG
Tot 63 70 72 57 59 41 125 59 61 43
Tot 70 72 54
LwA Surrounding 54
dB(A)
LwA Inlet LwA Outlet LwA Surrounding
Tot 71 73 56
Tot 63 72 74 57 59 61 44 125 61 63 46
120
Tot 63 75 77 60 62 64 47 125 64 66 49
Tot 63 78 80 63 65 67 50 125 67 69 51
dB(A)
LwA Inlet LwA Outlet LwA Surrounding
Tot 63 86 88 75 73 78 62 125 75 77 64
121
Roof fans
DHS Also possible for DVS, DVN and DVC VKS Automatic shutter DVS/DVSI Also possible for DHS, DVN and DVC DVS/DVSI Also possible for DHS, DVN and DVC
Roof fans
VKM Motor driven shutter ASS Flexible connection ASF Inlet flange
FTG Tilting device TDA Adapter frame VKS Automatic shutter ASS Flexible connection ASF Inlet flange FDS Flat roof socket
ASK Inflow chamber ASS Flexible connection DVN/DVNI ASF Inlet flange VKS Automatic shutter SSD Socket silencer
FTG Tilting device TDA Adapter frame VKM Motor driven shutter
ASK Inflow chamber VKS Automatic shutter ASS Flexible connection ASF Inlet flange
120C
200C
IE2
2009/640/EG
General
Systemair roof fans have been developed for the use in effective exhaust air systems. Ranges DVS/DVSI/DHS/DVN/ DVNI/DVC are equipped with a sea water resistant aluminium casing. The integrated bird screen is manufactured from galvanized and powder coated steel. The impellers are manufactured either from compound material or from aluminium. Range TFSR/TFSK has a casing manufactured from galvanized steel, powder coated in black. The units are supplied with cord and plug.
Systemair range
Systemair roof fans are available for vertical discharge (ranges DVS, DVSI, DVC, DVN and DVNI up to size 900) and for horizontal discharge (ranges TFSR/TFSK and DHS up to size 710). The vertical discharge units are also available with sound insulated casing, having a 50 mm insulation (density 60 kg/m3). All of Systemair roof fans are equipped with self-cleaning impellers with backward curved blades. A comprehensive range of easy to install accessories is available.
Motors
Systemair roof fans DVS/DVSI/DHS and TFSR/TFSK are equipped with external rotor motors, speed controllable by voltage. DVN is driven by IEC standard motors in efficiency class IE2 as per guideline 2009/640/EC. DVEX have ATEX-certified external rotor motors (see Explosion proof fans page 188-223). DVC is equipped with electronically commutated EC-motor, either with automatic speed control by pressure (integrated pressure sensor) or with manual speed control by an external 0-10V signal. Most of the roof fans are equipped with thermal contacts or cold conductors for motor protection. DVS/DHS/DVN from size 355 have to be connected to an external motor protection unit.
122 122
Roof fans
TFSR/TFSK EC. . . . . . . . . . . 124 Roof fan with EC-motor, swing out: up to 0.39 m3/s, 1 phase.
DHS/DVS/DVSI . . . . . . . . . . 146 Roof fans: up to 4.00 m3/s, backward curved impeller, 1 and 3 phase. DVSI insulated version.
TFSR/TFSK . . . . . . . . . . . . . 126 Roof fans, swing out: up to 0.39 m3/s, backward curved impeller, 1 phase.
DVN/DVNI. . . . . . . . . . . . . . 152 Roof fans: up to 8.75 m3/s, backward curved impeller, 1 and 3 phase. DVNI insulated version.
IE2
2009/640/EG
120C
Roof fans
DHA sileo . . . . . . . . . . . . . . 130 Supply air roof fan: up to 4.4 m3/s, 1 and 3 phase, axial impeller.
DVV. . . . . . . . . . . . . . . . . . . 158 Roof fans: up to 15.20 m3/s, backward curved impeller, 3 phase. DVVI insulated version.
IE2
2009/640/EG
120C
DVC/DVCI . . . . . . . . . . . . . . 132 Roof fan with EC-motor: up to 3.8 m3/s, 1 and 3 phase. DVCI insulated version.
DHS/DVS/DVSI sileo. . . . . . 138 Roof fans: up to 4.00 m3/s, 1 and 3 phase. DVSI insulated version. New generation of backward curved sileo impellers with extremely low noise level from size 400 up to 630.
200C
123 123
CXE/AV p. 323
EC-vent p. 329-330
Roof fans
Technical data
TFSR/TFSK Art no Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 4m/10 m Weight Insulation class, motor Enclosure class, motor Speed control, electronic Wiring diagram p. 391-400 160 EC 1226/1223 V/50/60 Hz 230 1~ W 81.5 A 0.64 m3/s 0.161 min-1 3162 C 45 C 45 dB(A) 43 kg 4.2/4.6 B IP 44 MTP 10 41 200 EC 1227/1224 230 1~ 74.6 0.587 0.216 2501 45 45 43 5.4/6.2 B IP 44 MTP 10 41
124
Roof fans
Dimensions Ventilation accessories
C
TOB p. 372
A
A B
HC D
E c/c F
LDC p. 348
9(4x)
36
RSK p. 355
Roof fans
A 147 150
B 172 187
C 334 364
D 380 439
HC 205 250
A 147 150
B 172 187
C 334 364
E 421 421
Performance
Tot 63 79 74 52 37 125 77 61
Tot 63 74 74 49 27 125 66 61
125
RE p. 320
REU p. 320
REE p. 321
Roof fans
Quick selection
1 2 3 4 5 6
TFSK 125M TFSK 125XL TFSK 160 TFSR 200 TFSR 315M TFSR 315L
2 3
Technical data
TFSR/TFSK Art no. TFSK 125M, 160, 200, 315M are suitable for 60Hz Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 4m/10m Weight Insulation class, motor Enclosure class, motor Capacitor Motor protection Speed control, five step Speed control, five step high/low Speed control, stepless Wiring diagram p. 391-400 V/50 Hz 230 1~ W 24.8 A 0.13 m3/s 0.086 min-1 1965 C 70 C 70 dB(A) 23 kg 2.5 B IP 44 F 1.5 Aut. th. cont. Transf. RE 1,5 Transf. REU 1,5 Thyristor REE 1 29 230 1~ 53.9 0.26 0.106 2531 40 40 33 2.5/3.3 F IP 44 1.5 Aut. th. cont. RE 1,5 REU 1,5 REE 1 29 230 1~ 58.3 0.26 0.121 2461 70 70 36 3.3 B IP 44 2 Aut. th. cont. RE 1,5 REU 1,5 REE 1 29 230 1~ 108 0.47 0.208 2537 62 62 40 4.2 B IP 44 3 Aut. th. cont. RE 1,5 REU 1,5 REE 1 29 230 1~ 195 0.87 0.313 2628 47 47 46 8.0/9.7 F IP 44 5 Aut. th. cont. RE 1,5 REU 1,5 REE 1 29 50 Hz 230 1~ 329 1.43 0.444 2401 42 38 53 9.1/10.7 F IP 44 8 Aut. th. cont. RE 1,5 REU 1,5 REE 2 29 125 M 1330/1344 125 XL 1332/1346 160 1333/1348 200 1334/1349 315 M 1336/1350 315 L 1343/1352
126
Roof fans
Dimensions
c/c F
TOB p. 372
36
HC D
TG p. 373
c/c F C G (4x)
LDC p. 348
Roof fans
36 E
RSK p. 355
FDS p. 374
TFSR 125 M/XL 160 200 315 M/L A 119 120 123 160 B 144 145 160 206 C 284 334 364 404 D 315 380 439 485 HC 205 205 250 250 TFSK 125 M/XL 160 200 315 M/L A 119 120 123 160 B 144 145 160 206 C 284 334 364 404 E 321 421 421 521 c/cF 245 330 330 450 G 9 9 9 11
SSD p. 374
127
Roof fans
Performance
Roof fans
dB(A)
LwA Inlet LwA Outlet
Tot 63 58 54 38 20 125 50 41
dB(A)
LwA Inlet LwA Outlet
Tot 63 68 64 47 27 125 60 46
dB(A)
LwA Inlet LwA Outlet
Tot 63 68 67 50 26 125 63 53
dB(A)
LwA Inlet LwA Outlet
Tot 63 71 71 50 31 125 62 52
128
Roof fans
Roof fans
dB(A)
LwA Inlet LwA Outlet
Tot 63 74 77 49 29 125 65 57
dB(A)
LwA Inlet LwA Outlet
Tot 63 78 84 51 37 125 70 62
129
Electrical accessories
S-ET/STDT p. 341-342
RTRE p. 320
REU p. 320
Roof fans
398,95 225
RTRD p. 321
4xG D E A
216,5
RTRDU p. 321
E G
A 1100 1282
B 434 481.5
C 240 240
D 535 750
REE p. 321
130
Roof fans
Performance
1000 120 2000 3000
Ventilation accessories
2000 160 4000 6000 8000 10000 12000
DHA 400
100
75
DHA 500
130
81
FDS p. 374
80
104
78
40
52
dB(A) 400DV LwA Inlet LwA Outlet 400E4 LwA Inlet LwA Outlet
Tot 63 69 69 49 47 125 57 56
Tot 63 71 70 43 45 125 53 53
Roof fans
81
dB(A)
Tot 63 125
dB(A)
Tot 63 125
Measurement point: 1.8 m/s; 111 Pa 630DS/E6 LwA Inlet LwA Outlet 73 74 48 49 55 56 65 67 65 68 68 70 68 65 61 60 53 53
131
REV p. 340
Roof fans
The DVC roof fans are driven by EC-external rotor motors, so called energy saving motors with high efficiency. The input voltage for single phase units can vary between 200 and 277V, for three phase units between 380 and 480V. All motors are suitable for 50Hz and 60Hz and from size 355 up to 630 suspended on effective vibration dampers. Motor protection is integrated in the electronics of the motor, no additional external motor protection device is needed. The DVC-P versions have integrated pressure sensors and the electronics are programmed for a pressure constant operation. Two potentiometers in the electronics allow for 2 set values (day/night), one additional contact for an external setting. Casing from seawater-resistant aluminum. Backward curved impellers manufactured from polyamide PA 6 for size 190 and 315. From 355 up to 630 impellers manufactured from seawater resistant aluminium. Quick selection
MTP 10 p. 341
EC-vent p. 329-330
1 2 3 4 5
DVC/DVCI 225 DVC/DVCI 315 DVC/DVCI 355 DVC/DVCI 400 DVC/DVCI 450 PK/SK
1 2 3 4
3 4
1 2
Technical data
DVC/DVCI Art no. DVC-P/DVC-S Art no. DVC-P+REV/DVC-S +REV Art no. DVCI-P/DVCI-S Art no. DVC-P+REV/DVCI-S +REV Voltage/Frequency Fan power consumption (P1) Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 4 m/10 m, DVC Sound pressure level at 4 m/10 m, DVCI Weight, DVC/DVCI Insulation class, motor Enclosure class, motor Speed control, electronic Wiring diagram p. 391-400 225-P/225-S Tech. data is relating to DVC-S 30690/30667 30691/30725 30701/30693 30717/30709 V/50/60 Hz 230 1~ W 166 A 1.17 m3/s 0.261 min-1 3278 C 60 C 60 dB(A) 58/51 dB(A) 53/45 kg 8/13 B IP 44 MTP 10 23b/24 315-P/315-S 30634/30619 30684/30585 30702/30694 30718/30710 230 1~ 173 1.18 0.546 1867 60 60 47/39 41/33 11/16 B IP 44 MTP 10 23b/24 355-P/355-S 30635/30620 30692/30621 30703/30695 30719/30711 230 1~ 378 2.31 0.918 1657 60 60 50/42 46/38 25/30 B IP 44 MTP 10 23b/24 400-P/400-S 30682/30622 30685/30623 30704/30696 30720/30712 230 1~ 381 2.30 1.00 1348 60 60 49/41 43/35 29/34 B IP 44 MTP 10 23b/24 450-PK/450-SK 31327/31427 33195/32744 230 1~ 614 2.79 1.43 1300 60 60 53/45 40/32 45/38 B IP 54 MTP 10 28/25
132
Roof fans
Dimensions
A B
Ventilation accessories
F G H M20x1,5
SSD p. 374
D
I(4x)
D E
FDS p. 374
ASK p. 380
DVC/DVCI 190-225 315 355-400 450-500 A B C 330 D 285 E 335 435 595 665 F 245 330 450 535 G 105 146 200 237 H 6xM6 6xM6 6xM8 6xM8 I 10(4x) 10(4x) 12(4x) 12(4x) 370/497 295 560/690 470 720/874 618 170/179 213 390/439 438
VKS p. 380
Roof fans
ASF p. 375
30
605 939
14(4x)
DVC Art no. DVC-P/DVC-S Art no. DVC-P + REV/DVC-S + REV Art no. DVCI-P/DVCI-S Art no. DVCI-P + REV/DVCI-S + REV Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 4/10 m, DVC Sound pressure level at 4/10 m, DVCI Weight, DVC/DVCI Insulation class, motor Enclosure class, motor Speed control, electronic Wiring diagram p. 391-400
450-P/450-S Tech. data is relating to DVC-S 30683/30626 30686/30627 30705/30697 30721/30713 V/50/60 Hz 400 3~ W 1048 A 1.79 m3/s 1.70 min-1 1558 C 60 C 60 dB(A) 51/48 dB(A) 50/42 kg 45/43 B IP 54 MTP 10 26/27
293
500-P/500-S 30679/30628 30687/30629 30706/30698 30722/30714 400 3~ 984 1.66 1.84 1339 60 60 55/47 51/43 49/57 B IP 54 MTP 10 26/27
560-P/560-S 30680/30630 30688/30631 30707/30699 30723/30715 400 3~ 1873 2.88 2.99 1359 60 60 63/55 55/47 58/70 F IP 54 MTP 10 26/27
630-P/630-S 30681/30632 30689/30633 30708/30700 30724/30716 400 3~ 2444 3.72 3.59 1209 60 60 64/56 57/49 85/65 F IP 54 MTP 10 26/27
133
Roof fans
Performance
Roof fans
134
Roof fans
Roof fans
135
Roof fans
Roof fans
136
Roof fans
A completely new generation of modern Systemair roof fans which were developed and built consistently according to the companys set target: low noise level, high performance. Especially suited to all uses and areas of application sensitive to noise. You can see and hear the result: a reduction in sound of up to 50 % at the same system performance and an increased level of efficiency compared to its predecessors.
137
S-ET/STDT p. 341-342
DVS
DVSI DHS with horizontal outlet. DVS with vertical outlet. DVSI has a 50 mm mineral wool insulation for lower noise levels.
The DVS/DHS/DVSI sileo, in sizes from 400 up to 630, is well suited for applications requiring high air volumes at medium pressure and very low noise levels. These models have 3D profiled impellers with backward curved blades and external rotor motors. All motors are speed controllable by voltage. For speed controlling of the DVS/DHS/DVSI sileo roof fans with a frequency converter,an all pole sine filter is required. The motors are suspended on effective vibration dampers. DVS/DHS/DVSI ...E4 / E6: 1~ motor DVS/DHS/DVSI ...DV / DS: 3~ with Y/D-connection for 2-speeds To protect the motors from overheating the sileo range motors are equipped with thermal contacts with external leads for connection to a motor protection device. The casing is made from aluminum and the base frame from hot-dip galvanized steel. Suitable for coastal applications. The impellers of the sileo types are manufactured from high-performance composite material with highly efficient 3D fan blade profile technology.
RTRE p. 320
Roof fans
RTRD/RTRDU p. 321
REU p. 320
REE p. 321
Technical data
DHS/DVS/DVSI Art no. DHS Art no. DVS; tech. data is relating to DVS Art no. DVSI Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level DVS* Weight Insulation class, motor Enclosure class, motor Capacitor Wiring diagram p. 391-400 * at 4/10 m. DHS +2 dB, DVSI -9 dB 400DS 33348 33316 33332 V/50 Hz 400 3~ W 129 A 0.255 m3/s 0.684 min-1 797 C 60 C 60 dB(A) 33/25 kg 25/25/31 F IP 54 F 18 400DV 33347 33315 33331 400 3~ 209 0.564 1.11 1436 60 60 46/38 27/28/33 F IP 54 18 400E4 33349 33317 33333 230 1~ 466 2.25 1.1 1324 60 60 46/38 27/29/33 F IP 54 10 6 400E6 33350 33318 33334 230 1~ 169 0.84 0.739 890 60 60 37/29 27/27/33 F IP 54 5 6 450DV 33351 33319 33335 400 3~ 667 1.32 1.44 1238 60 60 49/41 39/39/45 F IP 54 18 450E4 33352 33320 33336 230 1~ 665 2.93 1.4 1259 60 60 49/41 39/41/45 F IP 54 16 6 450E6 33353 33321 33337 230 1~ 241 1.05 0.979 863 60 60 40/32 39/39/45 F IP 54 8 6
138
Roof fans
Dimensions DVS/DVSI
A B
DHS 400-499
J
Ventilation accessories
H G
SSD p. 374
D E
I(4x)
FDS p. 374
D E
DHS 560-630
J
ASK p. 380
K L
D E
Roof fans
DHS sileo 400E4/E6/DV/DS 450E4/499DV/500DV/DS/E6 560DV/DS/630DV/DS DVS sileo 400E4/E6/DV/DS 450E4/499DV/500DV/DS/E6 560DV/DS/630DV/DS DVSI sileo 400E4/E6/DV/DS 450E4/499DV/500DV/DS/E6 560DV/DS/630DV/DS
I 12 12 14 I 12 12 14 I 12 12 14
L 30 30 30 L L
VKS p. 380
ASS p. 381
ASF p. 375
139
Roof fans
Quick selection
1 2 3 4 5
DHS/DVS/DVSI sileo 400DS DHS/DVS/DVSI sileo 400DV,450E4 DHS/DVS/DVS sileo 400E6 DHS/DVS/DVS sileo 450DV DHS/DVS/DVS sileo 450E4
1 2 3 4 5
DHS/DVS/DVSI sileo 450E6 DHS/DVS/DVSI sileo 499DV DHS/DVS/DVSI sileo 500DV DHS/DVS/DVSI sileo 500DS DHS/DVS/DVSI sileo 500E6
5
5
Roof fans
1 2 3 4
DHS/DVS/DVSI sileo 560DV DHS/DVS/DVSI sileo 560DS DHS/DVS/DVSI sileo 630DV DHS/DVS/DVSI sileo 630DS
DHS/DVS/DVSI Art no. DHS Art no. DVS Tech. data is relating to DVS Art no. DVSI Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level DVS* Weight Insulation class, motor Enclosure class, motor Capacitor Wiring diagram p. 391-400 * at 4/10 m. DHS +2 dB, DVSI -9 dB
500DV 33356 33324 33340 V/50 Hz 400 3~ W 1241 A 2.24 m3/s 2.08 min-1 1337 C 60 C 60 dB(A) 53/45 kg 41/46/57 F IP 54 F 18
500DS 33357 33325 33341 400 3~ 428 0.931 1.34 860 60 60 42/34 41/49/57 F IP 54 18
500E6 33358 33326 33342 230 1~ 380 1.67 1.32 841 60 60 40/32 41/41/57 F IP 54 12 6
560DV 33359 33327 33343 400 3~ 1767 3.29 2.82 1195 55 55 54/46 58/58/70 F IP 54 18
560DS 33360 33328 33344 400 3~ 597 1.03 1.91 820 40 40 52/44 47/47/59 F IP 54 18
630DV 33361 33329 33345 400 3~ 3870 6.47 3.98 1361 50 50 68/60 85/85/99 F IP 54 18
630DS 33362 33330 33346 400 3~ 1110 2.2 3.00 846 60 60 56/48 65/65/79 F IP 54 18
140
Roof fans
sPEED CONTROL
DHS/DVS/DVSI sileo 400E4, 450E6, 500E6 400E6 450E4 400DV/DS, 499DV, 500DS, 560DS 500DV, 560DV 630DV + motor protection S-ET 10/STDT 16 Transformer Five step RTRE 3 RTRE 1.5 RTRE 5 RTRD 2 RTRD 4 RTRD 14 Transformer Five step high/low REU 3* REU 1.5* REU 5* RTRDU 2* RTRDU 4* Electronic Two step S-DT2SKT S-DT2SKT S-DT2SKT Thyristor Stepless REE 2 REE 1 REE 4
Roof fans
141
Roof fans
pERFORMANCE
Roof fans
dB(A) LwA Inlet LwA Surrounding DVSI LwA Surrounding With SSD LwA Inlet
Tot 63 56 56 47 45 45 35 26 35 125 49 43 34 39
dB(A) LwA Inlet LwA Surrounding DVSI LwA Surrounding With SSD LwA Inlet
Tot 63 73 73 64 62 49 50 41 39 125 69 71 62 59
dB(A) LwA Inlet LwA Surrounding DVSI LwA Surrounding With SSD LwA Inlet
Tot 63 67 69 60 57 37 38 29 27 125 59 58 49 49
dB(A) LwA Inlet LwA Surrounding DVSI LwA Surrounding With SSD LwA Inlet
Tot 63 57 61 52 47 37 45 36 27 125 51 54 45 41
142
Roof fans
Roof fans
dB(A) LwA Inlet LwA Surrounding DVSI LwA Surrounding With SSD LwA Inlet
Tot 63 67 71 62 57 41 41 32 31 125 58 56 47 48
dB(A) LwA Inlet LwA Surrounding DVSI LwA Surrounding With SSD LwA Inlet
Tot 63 70 73 64 60 43 48 39 33 125 57 59 50 47
dB(A) LwA Inlet LwA Surrounding DVSI LwA Surrounding With SSD LwA Inlet
Tot 63 58 63 54 48 38 39 30 28 125 46 50 41 36
dB(A) LwA Inlet LwA Surrounding DVSI LwA Surrounding With SSD LwA Inlet
Tot 63 70 73 64 58 43 49 40 38 125 60 61 51 46
143
Roof fans
Roof fans
dB(A) LwA Inlet LwA Surrounding DVSI LwA Surrounding With SSD LwA Inlet
Tot 63 76 77 73 71 48 47 52 50 125 62 64 64 62
dB(A) LwA Inlet LwA Surrounding DVSI LwA Surrounding With SSD LwA Inlet
Tot 63 63 65 62 60 47 42 45 43 125 56 51 52 50
dB(A) LwA Inlet LwA Surrounding DVSI LwA Surrounding With SSD LwA Inlet
Tot 63 64 63 59 51 43 42 43 41 125 56 49 51 49
dB(A) LwA Inlet LwA Surrounding DVSI LwA Surrounding With SSD LwA Inlet
Tot 63 74 76 67 65 45 47 60 59 125 63 65 60 58
144
Roof fans
Roof fans
dB(A) LwA Inlet LwA Surrounding DVSI LwA Surrounding With SSD LwA Inlet
Tot 63 64 66 57 55 35 37 50 44 125 53 55 50 43
dB(A) LwA Inlet LwA Surrounding DVSI LwA Surrounding With SSD LwA Inlet
Tot 63 83 85 76 74 54 56 69 68 125 72 74 69 67
dB(A) LwA Inlet LwA Surrounding DVSI LwA Surrounding With SSD LwA Inlet
Tot 63 67 69 60 58 38 40 53 52 125 56 58 53 51
145
The DVS/DHS/DVSI models have impellers with backward curved blades and external rotor motors. All motors are speed controllable by voltage. Frequency inverters must have an allpole sine filter. The motors are suspended on effective vibration dampers. DVS/DHS/DVSI...EZ/EV/ES: 1~ motor with connection for 2-speeds DVS/DHS/DVSI...E4:1-speed motor DVS/DHS/DVSI...DV/DS:3~ with Y/D-connection for 2-speeds To protect the motors from overheating the DVS/DHS/DVSI up to size 311 have integral thermal contacts, from size 355 with external leads for connection to a motor protection device. The casing is made from seawater resistant aluminum. Suitable for coastal applications. The impellers are manufactured from high-performance composite material. DVS with outlet vertical DHS with outlet horizontal DVSI with 50 mm mineral wool insulation for low noise level.
RTRE p. 320
DVS
RTRD/RTRDU p. 321
Roof fans
DVSI
REE p. 321
Technical data
DHS/DVS/DVSI Art no. DHS Art no. DVSI Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level DVS* Weight Insulation class, motor Enclosure class, motor Capacitor Wiring diagram p. 391-400 * at 4/10 m. DHS +2 dB, DVSI -9 dB 190EZ 5712 30273 V/50 Hz 230 1~ W 80 A 0.36 m3/s 0.155 min-1 2240 C 40 C 40 dB(A) 48/40 kg 5/5/12 B IP 44 F 2 20 225EZ 5713 5731 30275 230 1~ 113 0.5 0.228 2590 40 40 49/41 6/6/14 B IP 44 3 20 225EV 5714 5732 30274 230 1~ 48 0.227 0.142 1422 40 40 41/33 6/6/14 B IP 44 2 20 310EV 5703 5733 2347 230 1~ 116 0.53 0.406 1365 40 40 44/36 13/13/19 B IP 44 4 20 310ES 5704 5734 2350 230 1~ 70 0.30 0.369 1000 40 40 37/29 13/13/19 B IP 44 1.5 20 311EV 5705 5735 2352 230 1~ 135 0.6 0.46 1365 40 40 45/37 13/13/20 B IP 44 5 20 311ES 5715 5736 2381 230 1~ 100 0.38 0.439 940 40 40 38/30 13/13/16 B IP 44 2 20 355E4 5706 5737 2356 230 1~ 279 1.22 0.773 1401 40 40 47/39 25/25/38 B IP 44 8 5 355DV 5707 5710 2354 400 3~ 249 0.58 0.779 1350 40 40 47/39 25/25/37 B IP 44 16 710DS 5729 5752 2378 400 3~ 2475 4.0 4.58 883 40 40 58/50 88/88/104 F IP 54 18 65/57 88/88/104 F IP 54 18 Y 710D6-L 33181 33177 33179 Y400 3~ 2562 4.86 4.12 941 40
146
Roof fans
Dimensions DVS/DVSI
A B
DHS 190-355
J
Ventilation accessories
H G
SSD p. 374
D E
I(4x)
FDS p. 374
D E
DHS 710
J
ASK p. 380
K L D E
Roof fans
DHS 190EZ, 225EZ/EV 310EV/ES, 311EV/ES 355E4/DV 710DS DVS 190EZ, 225EZ/EV 310EV/ES, 311EV/ES 355E4/DV 710DS DVSI 190EZ, 225EZ/EV 310EV/ES, 311EV/ES 355E4/DV 710DS
D 213 285 438 647 D 213 285 438 647 D 213 285 438 674
E 335 435 595 1035 E 335 435 595 1035 E 335 435 595 1035
F 245 330 450 840 F 245 330 450 840 F 245 330 450 840
G 105 146 200 320 G 105 146 200 320 G 105 146 200 320
H 6xM6 6xM6 6xM8 8xM8 H 6xM6 6xM6 6xM8 8xM8 H 6xM6 6xM6 6xM8 8xM8
I 10 10 12 14 I 10 10 12 14 I 10 10 12 14
L 30 30 30 40 L L
VKS p. 380
ASS p. 381
ASF p. 375
Quick selection
5236, none, 5240, 5242, 6717, 8370
1 2 3 4 5
DHS /DVS/DVSI 190EZ DHS /DVS/DVSI 225EZ DHS /DVS/DVSI 225EV DHS /DVS/DVSI 310EV DHS /DVS/DVSI 310ES
1 2 3 4 5 6
DHS/DVS/DVSI 311EV DHS/DVS/DVSI 311ES DHS/DVS/DVSI 355E4 DHS/DVS/DVSI 355DV DHS/DVS/DVSI 710DS DHS/DVS/DVSI 710DS-L
2 1
147
Roof fans
pERFORMANCE
Roof fans
dB(A) LwA Inlet LwA Surrounding DVSI LwA Surrounding With SSD LwA Inlet
Tot 63 71 72 67 60 42 43 54 40 125 60 61 56 55
dB(A) LwA Inlet LwA Surrounding DVSI LwA Surrounding With SSD LwA Inlet
Tot 63 71 72 67 60 42 43 54 40 125 60 61 56 55
dB(A) LwA Inlet LwA Surrounding DVSI LwA Surrounding With SSD LwA Inlet
Tot 63 63 64 58 52 34 35 51 32 125 52 53 51 47
dB(A) LwA Inlet LwA Surrounding DVSI LwA Surrounding With SSD LwA Inlet
Tot 63 65 67 58 55 52 54 51 49 125 54 56 51 49
148
Roof fans
Roof fans
dB(A) LwA Inlet LwA Surrounding DVSI LwA Surrounding With SSD LwA Inlet
Tot 63 58 60 51 49 45 47 44 42 125 47 49 44 42
dB(A) LwA Inlet LwA Surrounding DVSI LwA Surrounding With SSD LwA Inlet
Tot 63 66 68 59 56 53 55 52 50 125 55 57 52 50
dB(A) LwA Inlet LwA Surrounding DVSI LwA Surrounding With SSD LwA Inlet
Tot 63 59 61 52 50 46 48 45 43 125 48 50 45 48
dB(A) LwA Inlet LwA Surrounding DVSI LwA Surrounding With SSD LwA Inlet
Tot 63 68 70 61 58 55 57 54 52 125 57 59 54 52
149
Roof fans
DHS/DVS/DVSI 710DS
Roof fans
dB(A) LwA Inlet LwA Surrounding DVSI LwA Surrounding With SSD LwA Inlet
Tot 63 68 70 61 58 55 57 54 52 125 57 59 54 52
dB(A) LwA Inlet LwA Surrounding DVSI LwA Surrounding With SSD LwA Inlet
Tot 63 79 81 72 69 66 68 65 63 125 68 70 65 62
dB(A) LwA Inlet LwA Surrounding DVSI LwA Surrounding With SSD LwA Inlet
Tot 63 82 88 79 72 66 62 59 63 125 73 69 70 67
150
Roof fans
North side
Project: Matrix Type of Building: Commercial office building City/Country: Pune, India Products/Solution: Jet Fans, Axial Fans, Roof Fans, Inline Fans (K) Motorized Fire Dampers with Actuators, Grilles, Louvres, Diffusers, VCDs.w
South side
151
IE2
2009/640/EG
120C
The casing and impeller with backward-curved blades is manufactured from seawater resistant aluminum. The base frame and the integrated protection guard consist of powder-coated galvanised steel. The motor is suspended on effective vibration dampers. The motors are speed-controllable via transformer or frequency converter. To protect the motor from overheating the fan has integral thermal contacts or PTC with external leads for connection to a motor protection device. The DVNI version has a 50 mm mineral wool insulation for lower sound level.
S-ET/STDT p. 341-342
REU p. 320
RTRDU p. 321
Roof fans
Quick selections
1 2
3 4 5 6 7
DVN/DVNI 400E4 DVN/DVNI 400DV DVN/DVNI 450D4 IE2 DVN/DVNI 500D4 IE2 DVN/DVNI 500DS
1 2 3 4 5
DVN/DVNI 560D4 IE2 DVN/DVNI 560D6 IE2 DVN/DVNI 630D4 IE2 DVN/DVNI 630D6 IE2 DVN/DVNI 710D6 IE2
FXDM p. 324
2 2 1 3 4 7 5 6
FRQ p. 325
Technical data
DVN/DVNI Art no. DVN Tech. data is relating to DVN Art no. DVNI Voltage/Frequency Power at shaft Current Max air flow R.p.m. Max temp. of transported air Sound pressure level at 4 m/10 m* Weight Insulation class, motor Enclosure class, motor Capacitor Motor protection Speed control, five-step Speed control, five step high/low Speed control, two step Speed control, stepless Wiring diagram p. 391-400 * DVNI -9 dB, ** + S-ET 10
355E4 30301 30446 V/50 Hz 230 1~ W 370 A 1.49 m3/s 0.846 min-1 1408 C 120 dB(A) 49/41 kg 27/33 F IP 54 F 12 S-ET 10 RTRE 3 Transformer REU 3** 21
355DV 30278 30313 400 3~ 370 1.20 0.839 1420 120 50/42 26/42 F IP 54 STDT 16 RTRD 2 RTRDU 2 S-DT2SKT FXDM 17
400E4 2630 3909 230 1~ 370 2.00 1.00 1420 120 52/44 33/39 F IP 54 12 S-ET 10 RTRE 3 REU 3** 21
400DV 2631 3396 400 3~ 370 1.37 1.1 1442 120 52/44 33/43 F IP 54 STDT 16 RTRD 2 RTRDU 2 S-DT2SKT FXDM 17
450D4 IE2 32184 33462 400 Y 3~ 750 1.78 1.85 1390 120 53/45 38/46 F IP 55 U-EK230E FRQ5(S)-4A FRQ(S)-4A 13 b Y
500D4 IE2 32185 33463 400 Y 3~ 1500 3.39 2.12 1400 120 56/48 49/57 F IP 55 FRQ5(S)-4A FRQ(S)-4A 13 b Y
500DS 9852 9857 400 3~ 550 1.86 1.41 936 120 47/39 48/55 F IP 54 STDT 16 RTRD 2 RTRDU 2 S-DT2SKT FXDM 20
152
Roof fans
Dimensions
A B
Ventilation accessories
DVN 355-400 450-500 560-630 710 A 720 900 B 618 730 C 600 675 900 936 D 390 465 560 660 E 438 438 605 674 F 595 665 939 1035 G 450 535 750 840 H I J 200 12(4x) 6xM8 237 12(4x) 6xM8 293 14(4x) 8xM8 320 14(4x) 8xM8
SSD p. 374
E F G H M20x1,5 J
A 874 970
B 648 730
FDS p. 374
200 12(4x) 6xM8 237 12(4x) 6xM8 293 14(4x) 8xM8 320 14(4x) 8xM8
ASK p. 380
E
I
VKS p. 380
Roof fans
VKM p. 380
ASS p. 381
ASF p. 375
DVN/DVNI Art no. DVN, Techn. data is relating to DVN Art no. DVNI Voltage/Frequency Power at shaft Current Max air flow R.p.m. Max temp. of transported air Sound pressure level at 4/10 m Weight Insulation class, motor Enclosure class, motor Motor protection Speed control, five-step Speed control, stepless Wiring diagram p. 391-400
560D4 IE2 32187 33465 V/50 Hz 400 Y 3~ W 2200 A 4.64 m3/s 3.00 min-1 1420 C 120 dB(A) 64/56 kg 58/70 F IP 55 U-EK230E FRQ5(S)-10A FRQ(S)-10A 13 b Y
560D6 IE2 32188 33466 400 Y 3~ 750 1.98 2.08 905 120 49/41 57/69 F IP 55 U-EK230E FRQ5(S)-4A FRQ(S)-4A 13 b Y
630D4 IE2 33554 33468 400 D 3~ 4000 8.12 4.07 1450 120 66/58 65/79 F IP 55 U-EK230E FRQ5(S)-10A FRQ(S)-10A 13b D
630D6 IE2 32189 33467 400 Y 3~ 1500 3.61 2.60 940 120 52/45 65/79 F IP 55 U-EK230E FRQ5(S)-4A FRQ(S)-4A 13 b Y
710D6 IE2 33555 33469 400 Y 3~ 2200 5.1 4.01 945 120 58/50 210/102 F IP 55 U-EK230E FRQ5(S)-10A FRQ(S)-10A 13 b Y
153
Roof fans
Performance
Roof fans
dB(A) LwA Inlet LwA Surrounding DVNI LwA Surrounding With SSD 355/400 LwA Inlet
Tot 63 70 72 63 60 41 43 34 31 125 59 61 52 49
dB(A) LwA Inlet LwA Surrounding DVNI LwA Surrounding With SSD 355/400 LwA Inlet
Tot 63 70 72 63 60 41 43 34 31 125 59 61 52 49
dB(A) LwA Inlet LwA Surrounding DVNI LwA Surrounding With SSD 355/400 LwA Inlet
Tot 63 73 75 66 63 60 62 59 57 125 62 64 59 57
dB(A) LwA Inlet LwA Surrounding DVNI LwA Surrounding With SSD 355/400 LwA Inlet
Tot 63 73 75 66 63 60 62 59 57 125 62 64 59 57
154
Roof fans
Roof fans
dB(A) LwA Inlet LwA Surrounding DVNI LwA Surrounding With SSD 450/ 499/500 LwA Inlet
Tot 63 74 76 67 61 63 60 125 63 65 60
dB(A) LwA Inlet LwA Surrounding DVNI LwA Surrounding With SSD 450/ 499/500
Tot 63 78 80 71 65 67 64 125 67 69 64
64
56
56
57
53
47
41
42
36
LwA Inlet
68
62
62
62
60
52
44
42
40
dB(A) LwA Inlet LwA Surrounding DVNI LwA Surrounding With SSD 450/ 499/500 LwA Inlet
Tot 63 68 70 61 55 57 54 125 57 59 54
dB(A) LwA Inlet LwA Surrounding DVNI LwA Surrounding With SSD 560/630 LwA Inlet
Tot 63 79 86 77 70 66 73 70 64 125 68 75 70 63
58
52
52
53
50
43
34
32
29
155
Roof fans
Roof fans
dB(A) LwA Inlet LwA Surrounding DVNI LwA Surrounding With SSD 560/630 LwA Inlet
Tot 63 70 72 63 61 57 59 56 55 125 59 61 56 54
dB(A) LwA Inlet LwA Surrounding DVNI LwA Surrounding With SSD 560/630 LwA Inlet
Tot 63 87 89 80 78 74 76 73 72 125 76 78 73 71
dB(A) LwA Inlet LwA Surrounding DVNI LwA Surrounding With SSD 560/630 LwA Inlet
Tot 63 74 76 67 65 61 63 60 59 125 63 65 60 58
dB(A) LwA Inlet LwA Surrounding DVNI LwA Surrounding With SSD 710 LwA Inlet
Tot 63 79 81 72 69 66 68 65 63 125 68 70 65 62
156
Roof fans
Project: Staatstheater Darmstadt Type of Building: The theatre in Darmstadt is one of the biggest theatres in Germany. It was built in the 1970s and refurbished in 2002 and 2006 for about 90 million Euros. City/Country: Darmstadt/Germany Products/Solution: - 11 smoke extract medium pressure axial fans, type HA 500 - 1 smoke extract medium pressure axial fan, type AXC 500 B - 8 smoke extract roof fans DVV 800 - Roof fans DVS/DVN.
157
120C
IE2
2009/640/EG
Note: article numbers in tables refer to items without PTC or thermal contact, with exception of items with IE2 motors, where PTC is serial built-in. Data related to motor and weight of delivered items can slightly vary from catalogue data. Technical data
DVV 120C Art no. Voltage/Frequency Power at shaft Current Starting current Max air flow R.p.m. Max temp. of transported air Sound pressure level at 4 m Sound pressure level at 10 m Weight Insulation class, motor Enclosure class, motor Wiring diagram p. 391-400
The octagonal casing is manufactured from seawater resistant aluminium (4 pole 1000-M and P from aluzinc steel sheet). The base frame is manufactured from galvanized steel. The impeller with backwardcurved blades is also manufactured from galvanised steel. The fan is equipped with IEC standard motors, according to 2009/640/EC guideline and IEC 60034-30, with protection class IP 54, insulation class F. Single speed or two speed Dahlander connected (4-8,6-12 pole) or with separate windings (6-8,4-6,8-12 pole). Motor cooling with fresh air via air duct. Thermal motor protection (PTC or thermal contact built-in) on request, in IE2 motors serial PTC built-in. For frequency controlled single speed units up to 0,55 kW PTC must be ordered (since IE1 motors built-in). Sizes 800 and 1000 with on/off switch, other sizes equipped with terminal box, on/off switch on request. The DVV fans can be factory fitted with sound attenuators at the outlet (DVVI). Sound attenuators are also available as HSDV accessories.
Roof fans
400D4-6 3506 V/50 Hz 400 3~ kW 0.55/0.18 A 1.7/0.8 A 6.8/2.4 m3/s 1.17/0.778 min-1 1420/940 C 120 dB(A) 62/53 dB(A) 52/43 kg 52/45 F IP 54 15a
450D4 IE2 95139 400 3~ 1.1 2.6 12.5 2.01 1435 120 66 56 65 F IP 54 15c
450D4-6 3530 400 3~ 1.1/0.37 3/1.4 10.8/5.9 2.01/1.35 1420/950 120 66/55 56/46 68 F IP 54 15a
560D4-6 3554 400 3~ 1.7/1.2 4.6/3.7 23.9/13.3 2.64/1.81 1450/940 120 69/60 59/52 75 F IP 54 15a
560 D4 IE2 95140 400 3~ 1.5 3.5 20.3 2.64 1420 120 69 59 69 F IP 54 15c
630 D4-K IE2 95141 400 3~ 3.0 6.6 36.7 3.5 1400 120 71 63 109 F IP 54 15c
630 D4-6-K 3582 400 3~ 3.0/0.9 6.9/3.3 38.0/13 3.5/2.28 1450/975 120 71/61 63/53 118 F IP 55 15a
630 D4 IE2 95142 400 3~ 5.5 11.6 95 5.36 1455 120 75 69 124 F IP 54 13b D
DVV 120C Art no. Voltage/Frequency Power at shaft Current Starting current Max air flow R.p.m. Max temp. of transported air Sound pressure level at 4 m Sound pressure level at 10 m Weight Insulation class, motor Enclosure class, motor Wiring diagram p. 391-400
630D4-6 3586 V/50 Hz 400 3~ kW 5.5/1.7 A 12/4.5 A 81.6/20.3 m3/s 5.36/3.36 min-1 1460/970 C 120 dB(A) 75/64 dB(A) 69/58 kg 124 F IP 55 15a
630D6 IE2 95143 400 3~ 2.2 5.5 25.3 3.36 935 120 64 58 114 F IP 54 15c
800D4-K IE2 95144 400 3~ 9.5 18 121 7.08 1445 120 76 70 224 F IP 55 13b D
800D6-K 95145 400 3~ 2.2 5.5 25.3 5 935 120 66 60 159 F IP 54 15c
800D4-8-K 3630 400 3~ 9.0/2.4 18.5/5.5 114/24 7.08/3.92 1420/720 120 76/55 70/48 243 F IP 55 14a
800D6 IE2 800D6-8 95146 400 3~ 5.5 12.6 76 7.08 960 120 72 64 179 F IP 55 13b D 3644 400 3~ 5.7/2.4 12.3/6.2 62.8/21.7 7.08/5.28 960/720 120 72/66 64/57 190 F IP 54 15a
800D4-M IE2 95148 400 3~ 15 29.8 265 9.58 1470 120 80 72 265 F IP 55 13b D
800D4-6-M 30040 400 3~ 15.0/5.0 33/13.5 198/76 9.58/6.22 1465/980 120 80/70 72/62 353 F IP 55 15a
158
Roof fans
Ventilation accessories
ASFV p. 384
ASK/F p. 380
ASSV p. 383
SSV p. 382
Roof fans
SSVE p. 377
FDV p. 381
DVV 120C Art no. Voltage/Frequency Power at shaft Current Starting current Max air flow R.p.m. Max temp. of transported air Sound pressure level at 4 m Sound pressure level at 10 m Weight Insulation class, motor Enclosure class, motor Wiring diagram p. 391-400 V/50 Hz kW A A m3/s min-1 C dB(A) dB(A) kg 800D4-8-M 800D4-P IE2 800D4-6-P 800D4-8-P 30044 400 3~ 16.2/3.7 36/13 290/64 9.58/4.79 1470/735 120 80/65 72/57 355 F IP 55 14a 95149 400 3~ 18.5 35 280 10.8 1465 120 83 75 353 F IP 55 13b D 30052 400 3~ 18.5/7.0 36/19 244/110 10.8/7.25 1460/985 120 83/71 75/64 335 F IP 55 15a 30056 400 3~ 18.5/4.5 40/15 335/75 10.8/5.42 1470/735 120 83/65 75/57 369 F IP 55 14a 1000D6 IE2 95147 400 3~ 11 22 156 12,4 955 120 74 66 333 F IP 55 13b D 1000D6-8 3663 400 3~ 11.0/5.0 22/15 154/82.5 12.4/9.44 970/730 120 74/66 66/58 400 F IP 55 15a 1000D8 3669 400 3~ 5.5 12.5 63.8 9.44 710 120 66 58 310 F IP 55 13a D
FDVE p. 382
VKV/F p. 383
VKVM p. 384
DVV 120C Art no. Voltage/Frequency Power at shaft Current Starting current Max air flow R.p.m. Max temp. of transported air Sound pressure level at 4 m Sound pressure level at 10 m Weight Insulation class, motor Enclosure class, motor Wiring diagram p. 391-400
1000D4-M IE2 1000D4-6-M 1000D4-8-M 95151 V/50 Hz 400 3~ kW 22 A 42 A 340 m3/s 14.2 min-1 1470 C 120 dB(A) 89 dB(A) 79 kg 469 F IP 55 13b D 32288 400 3~ 22.0/9.0 49/23 299/110 14.2/9.42 1460/985 120 89/77 79/67 495 F IP 55 15a 32289 400 3~ 22.0/5.5 45/17 338/85 14.2/7.08 1470/730 120 89/70 79/60 495 F IP 55 14a
1000D6-M IE2 1000D4-P IE2 95152 400 3~ 7.5 15.7 112 9.42 970 120 77 67 313 F IP 55 13b D 95150 400 3~ 28 56 420 15.2 1470 120 90 79 495 F IP 55 13b D
1000D4-6-P 31265 400 3~ 28.0/8.0 53.5/18 360/120 15.2/10.1 1470/980 120 90/78 79/67 595 F IP 54 15a
1000D6-P IE2 1000 D4-8-P 95212 400 3~ 8.5 18 126 10.1 965 120 78 67 313 F IP 54 13b D 31269 400 3~ 28.0/7.0 51/20 400/80 15.2/7.56 1470/730 120 90/71 79/60 595 F IP 55 14a
159
Roof fans
Dimensions
ds d
d1
nxM
Roof fans
H B C
G A
d2
d2 14 14 14 18 18 18 18 18
H 40 20 20 40 40 40 70 70
1100 958 1272 1165 1350 1280 1500 1350 1500 1479
160
Roof fans
Performance
81
71
84 75
dB(A) 4-pole LwA Inlet LwA Surrounding 6-pole LwA Inlet LwA Surrounding
Tot 63 81 83 54 56 125 66 68
Tot 63 84 86 57 59 125 69 71
Roof fans
2000
4000
6000
8000
10000
88
92
82
81
dB(A) 4-pole LwA Inlet LwA Surrounding 6-pole LwA Inlet LwA Surrounding
Tot 63 88 90 61 63 125 73 75
Tot 63 92 94 65 67 125 77 79
161
Roof fans
98
97 87
6-pole
75
dB(A) 4-pole LwA Inlet LwA Surrounding 6-pole LwA Inlet LwA Surrounding
Tot 63 125 79 87
dB(A) 4-pole
Tot 63 125 83 84
Roof fans
97 98
68 68
72 79
98 99
71 72
Measurement point: 5,6 m/s; 700 Pa LwA Inlet LwA Surrounding 8-pole LwA Inlet LwA Surrounding 75 77 58 60 64 66 66 68 70 72 68 70 68 70 60 62 49 51 84 86 60 62 71 73 73 75 80 82 75 77 74 76 70 72 57 59
6-pole 8-pole
101
93 82
90 82
dB(A) 6-pole LwA Inlet LwA Surrounding 8-pole LwA Inlet LwA Surrounding
Tot 63 93 95 70 72 125 79 81
Measurement point: 8,1 m/s; 740 Pa LwA Inlet LwA Surrounding 8-pole LwA Inlet LwA Surrounding 82 84 65 67 71 73 73 75 77 79 75 77 75 77 67 69 56 58 90 92 67 69 78 80 80 82 87 89 82 84 81 83 77 79 64 66
162
Roof fans
92
104
84
85
91
dB(A) 4-pole LwA Inlet LwA Surrounding 6-pole LwA Inlet LwA Surrounding 8-pole LwA Inlet LwA Surrounding
Tot 63 92 94 69 71 125 78 80
Roof fans
67 69
104
105
92 84 84
93
dB(A) 4-pole LwA Inlet LwA Surrounding 6-pole LwA Inlet LwA Surrounding 8-pole LwA Inlet LwA Surrounding
Measurement point: 9,2 m/s; 1580 Pa LwA Inlet LwA Surrounding 8-pole 93 98 75 80 81 86 84 89 88 93 85 90 85 90 80 85 69 74
163
Electrical accessories
Fans are supplied with 1 m armoured cable and a junction box. Steel cables are provided to give extra support for the fan during chimney sweeping and similar operations. The flue-gas fans have a casing of cast aluminium alloy. The ZRS 170 impeller is made of silumin alloy, while the ZRS 180 impeller is made of stainless steel. The ZRS 170 is suitable for smaller fireplaces with an aperture of less than 0.35 m2, and the ZRS 180 is intended for fireplaces with an aperture between 0.35 and 0.80 m2. Systemair flue-gas fans counteract drafts caused by stoves, ovens and open fireplaces. Flue-gas fans are positioned on the top of the chimney and fixed with four adjustable locating rods which are inserted down the chimney. This means that no fixing into the chimney itself is required. The fan is a discreet and compact unit with a low profile.
REU p. 320
REE p. 321
RE p. 320
Roof fans
Dimensions
300
180
132
Technical data
ZRS Art no. Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 10 m Weight Insulation class, motor Enclosure class, motor Capacitor Speed control, five step Speed control, stepless Wiring diagram p. 391-400 170 1665 V/50 Hz 230 1~ W 42.9 A 0.19 m3/s 0.0861 min-1 2566 C 200 C 200 dB(A) 37 kg 7.6 F IP 44 F 1.5 Transformer RE 1,5 Thyristor REE 1 2 180 1667 230 1~ 55.5 0.26 0.144 2746 200 200 41 8.6 F IP 44 2 RE 1,5 REE 1 2
164
Roof fans
Performance
Roof fans
Tot 63 72 68 54 38 125 66 64
Tot 63 64 72 44 42 125 47 50
165
Axial fans
VK Louvre shutter
VK Louvre shutter
Axial fans
SG Protection guard AR
SD Rubber mounts
SG Protection guard
RSA Silencer
GFL Counterflange MFA Mounting feet SD (4x) AV rubber mounts FSD (4x) AV spring mounts ZSD (4x) AV spring mounts for tensile load
166
Axial fans
AW sileo . . . . . . . . . . . . . . . 168 Axial wall fans: up to 9.70 m3/s, axial impeller, 1 and 3 phase.
AXCBF. . . . . . . . . . . . . . . . . 186 Thermo axial fans: up to 5.5 m3/s, axial impeller, 3 phase.
IE2
2009/640/EG
AR sileo. . . . . . . . . . . . . . . . 170 Axial duct fans: up to 9.70 m3/s, axial impeller, 1 and 3 phase.
IE2
2009/640/EG
IE2
2009/640/EG
Axial fans
General
Systemair axial fans have been developed for the installation in effective supply and exhaust air systems. Ranges AR and AW are designed for the use in low pressure systems. Sizes 200 up to 450 are equipped with an impeller made from black coloured high efficiency composite material. From size 450 up to 1000 the AR/AW series are equipped with profiled, pressure die-cast aluminium blades. The long casings for ducted installation as well as the wall plates for wall mounting are manufactured from galvanized, powder coated steel. The AXC range is designed for the use in medium/high pressure systems. Especially for industrial buildings the AXC range
offers a wide area of applications. AXC is equipped with profiled aluminium blades, hot dip galvanized casing. A comprehensive range of accessories is available.
Motors
The Systemair AR/AW range is equipped with external rotor motors, speed controllable by voltage. All external rotor motors have thermal contacts embedded in the motor windings. The TK-leads have to be connected to an external motor protection unit. Systemair also offers a range of explosion proof ATEX axial fans, (see chapter EX-fans). AXC is equipped with IEC standard motors, in IE2 according to the latest ENstandards with PTC thermistors for thermal motor protection. PTC thermistors have to be connected to an external motor protection unit.
Systemair range
The Systemair AR axial fan casings are designed for duct mounting, the AW fan casings for direct wall mounting. From sizes 200 up to 1000 mm. Due to adjustable fan blades and different motor options the Systemair AXC axial fans can be selected to match the exact duty points required for a project. Available from sizes 315 to 2000 mm.
167
S-ET/STDT p. 341-342
RTRE/REU p. 320
RE p. 320
Quick selection
Quick selection also on page 170 REE p. 321
9736, 9735, 9740, 9738, 9741, 7004, 10906, 9742
1 2 3 4 5 6 7 8
Axial fans
AW/AR 200E4 AW/AR 200E2 AW/AR 250E4 AW/AR 250E2 AW/AR 300E4 AW/AR 300E2-K AW/AR 315DV AW/AR 315E4
6
1 2 3 4 5 6 7 8
AW/AR 350E4 AW/AR 350DV AW/AR 400E4 AW/AR 400DV AW/AR 450DV-K AW/AR 450E4-K AW/AR 450E4 AW/AR 450DV
3 4 5 6
RTRD/RTRDU p. 321
4 2 3 1 5 7 8
Technical data
AW sileo Art no. Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 1 m Weight Insulation class, motor Enclosure class, motor Capacitor Wiring diagram p. 391-400 200 E4 34115 V/50 Hz 230 1~ W 30 A 0.15 m3/s 0.124 min-1 1425 C 70 C 70 dB(A) 46 kg 3.2 F IP 44 F 1 49 200 E2 34114 230 1~ 80 0.38 0.242 2550 60 60 59 3.2 F IP 44 1.5 49 250 E4 34117 230 1~ 50 0.24 0.273 1370 55 55 52 4 F IP 44 1.5 49 250 E2 34116 230 1~ 140 0.59 0.486 2240 70 70 64 4.2 F IP 44 3.5 49 300 E4 34119 230 1~ 100 0.41 0.584 1330 60 60 56 5.9 F IP 44 3 49 300 E2-K 5801 230 1~ 309 1.35 0.948 2730 50 50 72 6.6 B IP 44 8 5 315 DV 34120 400 3~ 120 0.616 0.39 1450 70 70 62 6.8 F IP 54 18 315 E4 34121 230 1~ 160 0.67 0.677 1300 50 50 59 6.7 F IP 44 5 49 350 E4 34123 230 1~ 170 0.75 0.91 1260 60 60 62 7.5 F IP 44 5 49 350 DV 34122 400 3~ 190 0.4 0.976 1390 70 70 64 7.6 F IP 54 18 400 E4 34125 230 1~ 240 1.1 1.07 1350 65 65 64 8.7 F IP 54 5 6a 400 DV 34124 400 3~ 230 0.44 1.08 1370 70 70 64 8.7 F IP 54 18 450 DV-K 34127 400 3~ 350 0.64 1.55 1250 70 70 66 10.1 F IP 44 18 450 E4-K 34129 230 1~ 390 1.75 1.59 1290 65 65 65 10.1 F IP 44 7 6a 450 E4 34128 230 1~ 550 2.5 1.98 1320 70 70 66 16.2 F IP 54 14 6a
Impeller material: put comp. in no. 1 to 14 put alu in no. 15 and full next page
168
Axial fans
Dimensions Ventilation accessories
Motor protection
Thyristor
AW
Transformer
VK p. 356
200E2 200E4 250E2 250E4 300E2 300E4 AW AW 200 AW 250E2 AW 250E4 AW 300E2 AW 300E4 AW 315DV AW 315E4 AW 350DV AW 350E4 AW 400 AW 450DV AW 450DV-K AW 450E4 AW 450E4-K AW 500 AW 560 AW 630 AW 710DV AW 710DS AW 710E6 AW 800DS AW 910DS AW 1000DS AW 1000DS-L A 260 320 320 380 380 380 380 435 435 490 535 535 535 535 615 675 750 810 810 810 910 B 46 50 50 65 69 69 63 68 68 88 96 96 96 96 104 119 130 150 150 150 193 B1 92 102 97 111 103 118 132 119 132 146 171 148 191 148 204 215 207 272 246 246 284 293 323 400 B2 6 6 6 12 11 11 11 12 12 12 14 14 14 14 16 16 20 20 20 20 17 20 20 20 B3 142 152 147 171 165 182 173 182 173 182 206 186 226 186 226 227 225 272 246 246 284 293 323 400 B4 30 30 30 46 28 19 48 22 49 54 47 40 47 40 62 96 52 37 37 37 34 40 40 47,5 D1 210 264 264 330 326 330 349 388 390 420 480 480 480 480 531 589 664 763 763 763 869 922 D4 7 7 7 9 9 9 9 9 9 9 11 11 11 11 11 11 11 L 312 370 370 430 430 430 430 485 485 540 575 575 575 575 655 725 805 315DV 315E4 350DV 350E4 400DV 400E4 450DV-K 450E4 450E4-K 500DV 500E4 560DV 560E4 630D4-2 630DS 630E6 710DV 710DS 710E6 800DS 910DS 1000DS 1000DS-L
S-ET S-ET S-ET S-ET S-ET S-ET STDT S-ET STDT S-ET STDT S-ET STDT S-ET S-ET STDT S-ET STDT S-ET STDT STDT S-ET STDT STDT S-ET STDT STDT STDT STDT
RTRE 1.5/REU 1.5 RTRE 1.5/REU 1.5 RTRE 1.5/REU 1.5 RTRE 1.5/REU 1.5 RTRE 1.5/REU 1.5 RTRE 1.5/REU 1.5 RTRD 2/RTRDU 2 RTRE 1,5/REU 1,5 RTRD 2/RTRDU 2 RTRE 1,5/REU 1,5 RTRD 2/RTRDU 2 RTRE 1,5/REU 1,5 RTRD 2/RTRDU 2 RTRE 3/REU 3 RTRE 3/REU 3 RTRD 2/RTRDU 2 RTRE 5/REU 5 RTRD 4/RTRDU 4 RTRE 7/REU 7 RTRD 4, RTRDU 4 RTRD 2, RTRDU 2 RTRE 5/REU 5 RTRD 7/RTRDU 7 RTRD 4/RTRDU 4 RTRE 5/REU 5 RTRD 4/RTRDU 4 RTRD 7/RTRDU 7 RTRD 7/RTRDU 7 RTRD 14
REE 1 REE1 REE 1 REE 1 REE 1 REE 1 REE 1 REE 1 REE 2 REE 4 REE 2 REE 4 REE 4 REE 4
SG AW p. 385
SG AW-D p. 386
Axial fans
14,5 850 14,5 850 14,5 850 14,5 970 14,5 1070
AW sileo Art no. Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 1 m Weight Insulation class, motor Enclosure class, motor Capacitor Wiring diagram p. 391-400
450 DV 34126 V/50 Hz 400 3~ W 540 A 1.1 m3/s 2.0 min-1 1350 C 70 C 70 dB(A) 67 kg 14.6 F IP 54 F 18
34139 34138
169
Electrical accessories
S-ET/STDT p. 341-342
RTRE p. 320
REU p. 320
Axial fans
AW/AR 500E4 AW/AR 500DV AW/AR 560DV AW/AR 560E4 AW/AR 630E6,DS AW/AR 630DV
1 2 3 4 5 6 7 3
AW/AR 710E6 AW/AR 710DS AW/AR 710DV AW/AR 800DS AW/AR 910DS AW/AR 1000DS AW/AR 1000DS-L
RTRD/RTRDU p. 321
2 1
4 5
4 5 6 7
Technical data
AR sileo Art no. Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 1 m Weight Insulation class, motor Enclosure class, motor Capacitor Wiring diagram p. 391-400 200 E4 34458 V/50 Hz 230 1~ W 30 A 0.15 m3/s 0.124 min-1 1425 C 70 C 70 dB(A) 46 kg 3.2 F IP 44 F 1 49 200 E2 34457 230 1~ 80 0.38 0.242 2550 60 60 59 3.2 F IP 44 1.5 49 250 E4 34460 230 1~ 50 0.24 0.273 1370 55 55 52 4 F IP 44 1.5 49 250 E2 34459 230 1~ 140 0.59 0.486 2240 70 70 64 4.2 F IP 44 3.5 49 300 E4 34462 230 1~ 100 0.41 0.584 1330 60 60 56 5.9 F IP 44 3 49 300 E2-K 5772 230 1~ 309 1.35 0.948 2730 50 50 72 6.6 B IP 44 8 5 315 DV 34464 400 3~ 120 0.616 0.39 1450 70 70 62 6.8 F IP 54 18 315 E4 34463 230 1~ 160 0.67 0.677 1300 50 50 59 6.7 F IP 44 5 49 350 E4 230 1~ 170 0.75 0.91 1260 60 60 62 7.5 F IP 44 5 49 350 DV 400 3~ 190 0.4 0.976 1390 70 70 64 7.6 F IP 54 18 400 E4 34468 230 1~ 240 1.1 1.07 1350 65 65 64 8.7 F IP 54 5 6a 400 DV 34470 400 3~ 230 0.44 1.08 1370 70 70 64 8.7 F IP 54 18 450 DV-K 34474 400 3~ 350 0.64 1.55 1250 70 70 66 10.1 F IP 44 18 450 E4-K 34472 230 1~ 390 1.75 1.59 1290 65 65 65 10.1 F IP 44 7 6a 450 E4 34471 230 1~ 550 2.5 1.98 1320 70 70 66 16.2 F IP 54 14 6a
34465 34466
Impeller material: put comp. in no. 1 to 14 put alu in no. 15 and full next page
170
Axial fans
Dimensions
B E A I H
AR Motor protection
Ventilation accessories
Transformer
Thyristor
200E2 200E4 250E2 250E4 300E2 300E4 315DV 315E4 350DV G 4x90 4x90 8x45 8x45 8x45 8x45 8x45 8x45 8x45 12x30 12x30 12x30 H 10 10 10 10 12 12 12 12 12 12 12 12 I 225 280 355 395 450 500 500 500 500 560 620 690 770 860 970 1070 1070 350E4 400DV 400E4 450DV-K 450E4 450E4-K 500DV 500E4 560DV 560E4 630D4-2 630DS 630E6 710DV 710DS 710E6 800DS 910DS 1000DS 1000DS-L
S-ET S-ET S-ET S-ET S-ET S-ET STDT S-ET STDT S-ET STDT S-ET STDT S-ET S-ET STDT S-ET STDT S-ET STDT STDT S-ET STDT STDT S-ET STDT STDT STDT STDT
RTRE 1.5/REU 1.5 RTRE 1.5/REU 1.5 RTRE 1.5/REU 1.5 RTRE 1.5/REU 1.5 RTRE 1.5/REU 1.5 RTRE 1.5/REU 1.5 RTRD 2/RTRDU 2 RTRE 1,5/REU 1,5 RTRD 2/RTRDU 2 RTRE 1,5/REU 1,5 RTRD 2/RTRDU 2 RTRE 1,5/REU 1,5 RTRD 2/RTRDU 2 RTRE 3/REU 3 RTRE 3/REU 3 RTRD 2/RTRDU 2 RTRE 5/REU 5 RTRD 4/RTRDU 4 RTRE 7/REU 7 RTRD 4, RTRDU 4 RTRD 2, RTRDU 2 RTRE 5/REU 5 RTRD 7/RTRDU 7 RTRD 4/RTRDU 4 RTRE 5/REU 5 RTRD 4/RTRDU 4 RTRD 7/RTRDU 7 RTRD 7/RTRDU 7 RTRD 14
REE 1 REE1 REE 1 REE 1 REE 1 REE 1 REE 1 REE 1 REE 2 REE 4 REE 2 REE 4 REE 4 REE 4
VK p. 356
SG AR p. 385
AR 200 250 300-315 350 400 450DV 450DV-K 450E4 450E4-K 500 560 630 710 800 910 1000DS 1000DS-L
A 85 95
C 204 254 319 356 400 451 451 451 451 503 559 634 711 797 914 1001 1003
D 255 306 382 421 466 515 515 515 515 567 636 709 785 875 1005 1085 1079
130 135 155 160 25 160 175 25 160 174 6 210 220 260 33 280 33 330 376 44.5 330 44.5
AR sileo Art no. Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 1 m Weight Insulation class, motor Enclosure class, motor Capacitor Wiring diagram p. 391-400
450 DV 34473 V/50 Hz 400 3~ W 540 A 1.1 m3/s 2.0 min-1 1350 C 70 C 70 dB(A) 67 kg 14.6 F IP 54 F 49
G
E 72 72 72 72 72 72 72 73 63 63 16x22.5 12 16x22.5 12 16x22.5 15 16x22.5 15 16x22.5 15 500 E4 34475 230 1~ 750 3.35 2.48 1230 70 70 68 20.1 F IP 54 16 49 500 DV 34476 400 3~ 770 1.7 2.54 1300 70 70 67 20.1 F IP 54 49 560 DV-2 5789 400 3~ 993 1.8 3.43 1216 60 60 74 23.5 F IP 54 16 560 E4 5790 230 1~ 1449 6.49 3.72 1287 50 50 77 31.7 F IP 54 30 6a 630 E6 730 3.4 3.1 910 70 70 67 27 F 16 49
EV-AR p. 387
GFL-AR p. 389
MFA-AR p. 386
Axial fans
34479 230 1~
IP 54
171
Axial fans
Performance
4 3 1 2
5 2
Tot 63 51 51 28 26 125 39 38
Tot 63 66 65 36 34 125 47 46
Axial fans
Tot 63 59 59 30 29 125 46 47
Tot 63 71 71 39 37 125 50 50
172
Axial fans
Tot 63 63 62 39 37 125 48 48
dB(A)
Tot 63 125 71 70
LwA Inlet/Outlet 79
Axial fans
Tot 63 68 68 49 47 125 54 53
Tot 63 66 66 39 39 125 55 55
173
Axial fans
Tot 63 65 65 40 39 125 52 51
Tot 63 69 70 50 49 125 53 52
Axial fans
Tot 63 68 69 48 46 125 56 56
Tot 63 69 69 49 47 125 57 56
174
Axial fans
Tot 63 73 73 52 50 125 64 63
Tot 63 71 71 53 51 125 61 60
Axial fans
Tot 63 70 69 42 46 125 53 54
Tot 63 70 70 47 49 125 54 55
175
Axial fans
Tot 63 72 72 45 45 125 59 60
Tot 63 71 70 43 45 125 53 53
Axial fans
AW/AR 560E4
dB(A)
Tot 63 125 63 41
dB(A)
Tot 63 125 68 46
LwA Inlet/Outlet 80
LwA Inlet/Outlet 83
176
Axial fans
Tot 63 73 74 48 49 125 55 56
Tot 63 71 71 50 50 125 54 54
Axial fans
dB(A)
Tot 63 125 65 54
Tot 63 74 74 52 52 125 62 62
LwA Inlet/Outlet 86
177
Axial fans
Tot 63 73 72 45 46 125 55 55
Tot 63 82 81 51 52 125 64 64
Axial fans
Tot 63 80 80 50 50 125 63 63
Tot 63 79 79 56 57 125 62 62
178
Axial fans
AW/AR 1000DS
Tot 63 79 79 58 58 125 63 63
Tot 63 92 93 34 36 125 54 57
Axial fans
179
REV p. 340
IE2
2009/640/EG
FRQ p. 325
Axial fans
Dimensions
Zx D
Da
Di
s L
TK
Di AXC 315 AXC 355 AXC 400 AXC 450 AXC 500 AXC 560 AXC 630 AXC 710 AXC 800 AXC 900 AXC 1000 AXC 1120 AXC 1250 315 355 400 450 500 560 630 710 800 900 1000 1120 1250
Da 395 435 480 530 590 650 720 800 890 1005 1105 1260 1390
TK 355 395 450 500 560 620 690 770 860 970 1070 1190 1320
ZxD 8x10 8x10 8x12 8x12 12x12 12x12 12x12 16x12 16x12 16x15 16x15 20x15 20x15
L 375 375 450 500 540 500/750 500/750 500/700/800 500/700 640/850 640/850 700/1000 850/1050
180
For higher pressure drops two stage fans are offered. Two fans in series increase the available static pressure drop.
ESD-F p. 388
Sturdy casing
AXC/AXR axial fan casings are heavy gauge, hot dip galvanized, with spun flanges for high rigidity. Long cased execution as standard stock range. Also available with short casing and with an acoustically insulated box.
Quality
Systemair is ISO 9001 approved. The Systemair quality is regularly monitored by TV Sd.
EV-AXC p. 387
FSD p. 386
Warranty
Systemair offers a three year warranty on all AXC fan models. The Systemair warranty conditions apply. Performance curves and technical details for the required fan duties are available from our selection software, which can be downloaded or used online from our homepage: www.systemair.de. You can, of course, also order it directly from our customer support. GFL-AXC p. 389
Motors
The built-in motors are equipped with PTC thermistors for optimum motor protection. Single or two speed motors. Speed controllable by frequency converter. Efficiency class IE2 as per 2009/640/EC guidelines.
LRK(F) p. 385
MFA-AXC p. 386
Axial fans
RSA p. 384
SD p. 385
MP p. 387
q [m/h]
2000
10 15
4000
6000
8000
10000
12000
SG p. 357
L W dB(A)
30 25 20 40 35
150
76
78
80
83
84 dB(A)
100
76 78 80 82 84 dB(A)
50
76
Pd
78
80
82
83 dB(A)
0 1 2 3 m/s
Hz dB
63 7
125 7
250 6
500 7
1k 10
2k 14
4k 18
8k 23
Table 1: Correction values dependent on the frequency Mid octave band frequency Lw oct Hz 63 125 72 250 73 500 72 1k 69 2k 65 4k 61 8k 56
dB(A) 72
181
Axial fans
P [kW]
2000
4000
6000
2000
6000
10000
14000
18000
600 500 400 300 200 100 0 1 6,0 P [kW] 4,0 2,0 0 2
4,0 P [kW] 3,0 2,0 1,0 0 Item no CAX4002001 CAX4002002 CAX4002003 CAX4002004 CAX4002005 Model AXC 400-10-2 (0.75 kW) AXC 400-10-2 (1.1 kW) AXC 400-10-2 (1.5 kW) AXC 400-10-2 (2.2 kW) AXC 400-10-2 (3.0 kW)
Model AXC 450-10-2 (1.1 kW) AXC 450-10-2 (1.5 kW) AXC 450-10-2 (2.2 kW) AXC 450-10-2 (3.0 kW) AXC 450-10-2 (4.0 kW)
182
10,0 P [kW] P [kW] Item no CAX5002001 CAX5002002 CAX5002003 CAX5002004 CAX5002005 Model AXC 500-10-2 (1.1 kW) AXC 500-10-2 (1.5 kW) AXC 500-10-2 (2.2 kW) AXC 500-10-2 (3.0 kW) AXC 500-10-2 (4.0 kW)
12,0 8,0 4,0 0 Item no CAX5602019 CAX5602020 CAX5602021 CAX5602022 CAX5602023 CAX5602024 CAX5602025 CAX5602026 CAX5602027 Model AXC 560-9-2 (1.1 kW) AXC 560-9-2 (1.5 kW) AXC 560-9-2 (2.2 kW) AXC 560-9-2 (3.0 kW) AXC 560-9-2 (4.0 kW) AXC 560-9-2 (5.5 kW) AXC 560-9-2 (7.5 kW) AXC 560-9-2 (11 kW) AXC 560-9-2 (15 kW)
5,0
Axial fans
20000
30000
40000
8000
12000
16000
20000
600 400 200 0 5 20,0 P [kW] 12,0 8,0 4,0 0 P [kW] 16,0 10 2,5 2,0 1,5 1,0 0,5 0 100 50 0 2 3 4 5 6
Model AXC 630-9-2 (2.2 kW) AXC 630-9-2 (3 kW) AXC 630-9-2 (4 kW) AXC 630-9-2 (5.5 kW) AXC 630-9-2 (7.5 kW) AXC 630-9-2 (11 kW) AXC 630-9-2 (15 kW) AXC 630-9-2 (18.5 kW)
183
10
4,0
Model AXC 710-9-4 (2.2 kW) AXC 710-9-4 (3 kW) AXC 710-9-4 (4 kW) AXC 710-9-4 (5.5 kW)
Model AXC 800-9-4 (2.2 kW) AXC 800-9-4 (3 kW) AXC 800-9-4 (4 kW) AXC 800-9-4 (5.5 kW) AXC 800-9-4 (7.5 kW)
Axial fans
15000
25000
35000
45000
55000
20000
40000
60000
80000
5 16,0 P [kW]
10
15
10
30,0 P [kW] Item no CAX9004008 CAX9004009 CAX9004010 CAX9004011 CAX9004012 CAX9004013 CAX9004014 Model AXC 900-10-4 (2.2 kW) AXC 900-10-4 (3 kW) AXC 900-10-4 (4 kW) AXC 900-10-4 (5.5 kW) AXC 900-10-4 (7.5 kW) AXC 900-10-4 (11 kW) AXC 900-10-4 (15 kW) 20,0 10,0 0 Item no CAX10004007 CAX10004008 CAX1000409 CAX10004010 CAX10004011 CAX10004012 CAX10004013 CAX10004014 Model AXC 1000-10-4 (4 kW) AXC 1000-10-4 (5.5 kW) AXC 1000-10-4 (7.7 kW) AXC 1000-10-4 (11 kW) AXC 1000-10-4 (15 kW) AXC 1000-10-4 (18.5 kW) AXC 1000-10-4 (22 kW) AXC 1000-10-4 (30 kW)
184
40000
60000
60000
10000
14000
180000
28
10
20
30
40
50
P [kW]
P [kW]
36 24 28 32
12
16
20
Model AXC 1120-10-4 (5.5 kW) AXC 1120-10-4 (7.5 kW) AXC 1120-10-4 (11 kW) AXC 1120-10-4 (15 kW) AXC 1120-10-4 (18.5 kW)
Model AXC 1250-12-4 (11 kW) AXC 1250-12-4 (15 kW) AXC 1250-12-4 (18.5 kW) AXC 1250-12-4 (22 kW) AXC 1250-12-4 (30 kW) AXC 1250-12-4 (37 kW) AXC 1250-12-4 (45 kW) AXC 1250-12-4 (55 kW)
Axial fans
185
Aerofoil impeller with adjustable pitch angle. Die cast aluminium hub and blades. Bifurcated casing, hot dip galvanized steel, to EN ISO 1461 flange holes according Eurovent 1/2. Three phase motors, IP55, insulation class F, in accordance with EN 60034-5, IEC 85. Terminal box mounted directly onto the IE2 motor Suitable for operating temperatures of up to 200C continuously Inspection hole to verify correct direction of rotation. The Systemair AXCBF range of bifurcated medium pressure axial fans has been developed for applications with an atmosphere which would either require special motors or reduce the lifetime of a standard motor. The motors of AXCBF are outside of the airstream. Available in sizes from 250 up to 800 mm impeller diameter. AXCBF bifurcated axial fan casings are heavy gauge, hot dip galvanized. The motor compartment allows easy access to the motor terminal box for wiring. Three phase B3 foot mounted motors, totally enclosed and fan cooled. The three phase motors are equipped with PTC thermistors for optimum motor protection.
IE2
2009/640/EG
Quick selection
1 2 3
AXCBF 250D2-32 AXCBF 250D4-32 AXCBF 315D2-30 AXCBF 315D4-32 AXCBF 400D2-22
1 2 3 4 5
AXCBF 400D4-32 AXCBF 500D2-20 AXCBF 500D4-32 AXCBF 630D4-26 AXCBF 800D4-18
Axial fans
4 5
4 2
Technical data
AXCBF Art no. Voltage/Frequency Power Rated current Max air flow R.p.m. Max temp. of transported air Weight Insulation class, motor Enclosure class, motor Wiring diagram p. 391-400 250D4-32 32458 V/50 Hz 400 3~ kW 0.25 A 0.80 m3/s 0.23 min-1 1400 C 200 kg 30 F IP 55 13b 250D2-32 32456 400 3~ 0.37 1.0 0.49 2690 200 30 F IP 55 13b 315D4-32 32462 400 3~ 0.25 0.8 0.54 1390 200 32 F IP 55 13b 315D2-30 IE2 34146 400 3~ 0.75 1.68 0.951 2875 200 35 F IP 55 13b 400D4-32 32483 400 3~ 0.55 1.5 1.00 1370 200 42 F IP 55 13b
186
Ventilation accessories
LRK(F) p. 385
F
AXCBF 250 315 400 500 long version 500 short version A 535 535 625 710 660 B 448 452 585 695 695 C 328 385 480 590 590 D 250 315 400 500 500 F 302 355 450 560 560 G 22.5 22.5 22.5 15 15 H 10 10 10 12 12 I 8x45 8x45 8x45 12x30 12x30
MFA-AXCBF p. 388
ESD-F p. 388
G H
EVH p. 388
FSD p. 386
Axial fans
E
AXCBF 630 800 A 790 880 B 728 890 C 630 800 E 690 860 G 15 11.25 H 12 12 I 12x30 16x22,5
GFL-AR/AXC p. 389
SG AR/AXC p. 385
Note: Accessories LRK, ESD-F and SG not available for size 250
AXCBF Art no. Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air Weight Insulation class, motor Enclosure class, motor Wiring diagram p. 391-400
400D2-22 IE2 34147 V/50 Hz 400 3~ kW 2.20 A 4.48 m3/s 1.65 min-1 2890 C 200 kg 49 F IP 55 13b
500D2-20 IE2 34148 400 3~ 4.00 7.64 3.06 2914 200 87 F IP 55 13b
500D4-32 IE2 34152 400 3~ 1.10 2.53 1.91 1445 200 66 F IP 55 13b
630D4-26 IE2 34155 400 3~ 2.20 4.64 3.44 1440 200 106 F IP 55 13b
800D4-18 IE2 34156 400 3~ 4.00 8.12 5.63 1445 200 155 F IP 55 13b
187
Axial fans
188
Axial fans
189
Jet fans
Jet fans
Green ventilation Contemporary ventilation for underground car parks
Underground car park ventilation without compromise: Systemairs Green Ventilation jet fan system is the contemporary solution for energy efficiency and high safety standard requirements. The result is setting standards: 80% energy saving in Green Ventilation mode*, combined with a guaranteed safety promise of a worldwide acting system partner. The Green Ventilation jet fan system combines low operation cost and competitive initial investment by complying with legal requirements.
% 0 8
g avinn mode s y g tilatio n Ener
in G reen Ve
Jet fans
All Systemair products and systems, marked with the Green Ventilation label, meet highest requirements for energy and economic efficiency.
Components
The Green Ventilation jet fan system replaces the duct system of a car park. According to the ventilation concept, it may include exhaust fans as well as potential supply fans . In addition to jet fans, Systemair offers axial supply fans (AXC series) as well as temperature resistant exhaust fans as axial or roof fans (AXC (B), AXC (F) or DVV series) according to EN 12101-3. Systemair is able to supply all necessary dampers, flaps and other ventilation elements.
An effective system requires good planning, beginning with physical values such as the underground car parks dimensions, its occupancy, its usage profile and taking peak loads in consideration. The dimensioning of the ventilation is normally based on the air change rate (depending on air pollution) or an air volume load which is multiplied with the amount of parking places.
190
Jet fans
Advantages and benefits of Systemair Green Ventilation jet fan systems For investors
Reduction of investment cost, because bulky and complex duct systems can be omitted. This is a great advantage in particular for renovation projects. The flexible positioning of the jet fans enables the creation of modern and aesthetic buildings. The whole design of the underground car park gets optically more attractivity, there is no line-of-sight obstruction coming from the ductwork.
For users
The Green Ventilation jet fan system provides an 80% reduced energy consumption. This leads to considerably reduced operational cost. The center-piece is an intelligent control unit for highest energy efficiency of demand controlled ventilation. Furthermore, no resistance for the duct system in the car park has to be overcome. Selective ventilation for specific areas in the underground car park. CO (carbon monoxide) car exhaust sensors make sure that only really needed fans will be activated. This, again, helps to lower the running cost. In comparison to conventional systems, the concentration of pollutants is lower, providing a better air quality. The air moves constantly all over the activated car park area which allows better air mixture. Jet fan ventilation systems for smoke extraction avoid costintensive secondary damages: building ceilings are exposed to lower heat, smoke will be quickly exhausted out of the building. Optimised safety in case of fire. Faster smoke and heat extraction, smoke spreading is avoided and a better smoke control is possible to facilitate the work of fire-services.
Jet fans
For planners
More flexible fan positioning, in particular for redesign or renovation of parking decks. Faster design of complete systems, because no complex duct system is needed inside the car park. Possibility to have functional demonstration of the installation by the Systemair CFD analysis and by a warm smoke test.
For installers
Easy and fast fan installation to the car park ceiling - therefore less mounting work. Less points of contact with other crafts, because the fans can be installed at the end. Flexible fan positioning.
191
Jet fans
Customized solutions
System description
Driveway, ramp or other fresh air openings can supply natural fresh air. The supply air is designed to guarantee an almost laminar air flow. If no natural supply air can be provided, a supply air fan is needed. The Green Ventilation jet fan system supports the natural air flow between supply and exhaust air and helps accelerate the airflow in areas where it is too low to guarantee a sufficient air change all over the car park. According to safety regulations, virtual smoke sectors are created by aerodynamic loads in case of fire. This allows the design of wide and spacious car parks which normally need to be separated by gates or other installation elements. This always includes the aspect of efficiency and energy efficiency without losing sight of investment costs. A project-related switching matrix ensures that legal requirements are observed and individual safety objectives are followed. These are e.g. maximum CO and smoke gas concentration, required sight distances for personal rescue and preparation of fire-fighting operations by fire services. In case of an exhaust air fan failure, it is important that the control detects and indicates this failure automatically and finally switches over to the second fan.
Jet fans
Different versions of axial, radial and roof fans are available, for standard temperature up to temperature class F600 (600 C/120 min.). An optimised operation is provided by the project designed Green Ventilation control system. It analyses measurements of CO exhaust sensors and/or fire/smoke detectors and controls single, virtual smoke and CO zones according to the requirements. Jet fans in not affected smoke and CO zones are controlled according to the stored control matrix. The system will be designed in accordance with the requirements given in the specifications. Complete documentation can be found within the control cabinet.
Exhaust air
Exhaust air
Supply air
Supply air
192
Jet fans
The space required by different ventilation systems has a direct impact on the investment cost of a project. Jet fans do only punctually reduce the available ceiling height and need often many other installation systems like electric wiring and water pipes less than 0.5% ceiling surface. The extra ceiling space can be used for technical appliances and/or allows to reduce the ceiling height during the planning stage already. Another advantage is a higher safety of an active system which, depending on the fire location, reacts in accordance with the defined fire scenario matrix and offers best possible protection to human beings and buildings. Systemair remains your partner from the car park's planning to the commissioning and designs Green Ventilation garage exhaust systems according to your requirements.
Green Ventilation and smoke extraction function Many systems provide an opportunity either to save energy or to extract smoke out of your garage. But why should you choose the one or the other? Systemair educated smoke extraction car park systems in energy saving.
Jet fans
Reduction
% 100 80 60 40 20 0
Jet System EFF2 motor Jet System IE2 motor Green Ventilation mode
Case study
kW 40 20 0 Jet System EFF2 motor Jet System IE2 motor Green Ventilation mode
193
IE2
2009/640/EG
FRQ p. 325
Technical data
Jet fan AJR-TR 400V/50Hz N AJR 315-2-TR AJR 315-2/4-TR AJR 355-2-TR AJR 355-2/4-TR AJR 400-2-TR 22 22/6 37 37/9 55 55/14 22 22/6 37 37/9 55 55/14 m/h 4400 4400/2200 6400 6400/3200 8700 8700/4350 4400 4400/2200 6400 6400/3200 8700 8700/4350 Thrust Air volume Motor rated power kW 0,75 0,75/0,17 1,5 1,4/0,3 1,5 1,9/0,4 0,75 0,75/0,12 1,5 1,5/0,25 1,5 1,5/0,25 Motor rated current A 1,8 1,74/0,63 3,3 3,13/1,11 3,3 4,18/1,47 1,65 1,8/0,4 3,6 3,6/0,7 3,6 3,6/0,7 rpm 2900 2860/1420 2840 2880/1440 2840 2885/1435 2880 2880/1440 2880 2880/1440 2880 2880/1440 Speed Sound level 3 m, from center of casing LpA dB 60 60/45 66 66/51 72 72/57 60 60/45 66 66/51 72 72/57 kg 50 52 65 67 83 85 50 52 65 67 83 85 55C 55C 55C 55C 55C 55C 300C/120 Min. 300C/120 Min. 300C/120 Min. 300C/120 Min. 300C/120 Min. 300C/120 Min. Weight Temperature
Jet fans
AJR 400-2/4-TR AJR 315-2 (B)-TR AJR 315-2/4 (B)-TR AJR 355-2 (B)-TR AJR 355-2/4 (B)-TR AJR 400-2 (B)-TR AJR 400-2/4 (B)-TR
Dimensions
F E C 344
Da
194
Technical data
Jet fan AJ8 400V/50Hz N AJ8 315-2 AJ8 315-2/4 AJ8 355-2 AJ8 355-2/4 AJ8 400-2
476
Thrust
Air volume
Motor rated current A 1,99 2,14/0,75 2,5 3,13/1,11 3,3 4,18/1,47 1,8 1,6/0,4 2,5 3,1/0,68 3,2 3,9/0,95
Speed
Weight
Temperature
m/h 4400 4400/2200 6300 6300/3150 7700 7700/3850 4400 4400/2200 6300 6300/3150 8700 8700/4350
kW 0,75 0,75/0,17 1,1 1,4/0,3 1,5 1,9/0,4 0,75 0,75/0,15 1,1 1,3/0,25 1,5 1,8/0,37
rpm 2900 2860/1420 2900 2880/1430 2840 2885/1435 2900 2880/1450 2870 2905/1460 2870 2880/1455
LpA dB 62 62 / 47 69 69 / 54 73 73 / 58 62 62 / 47 69 69 / 54 73 73 / 58
Jet fans
AJ8 400-2/4 AJ8 315-2 (B) AJ8 315-2/4 (B) AJ8 355-2 (B) AJ8 355-2/4 (B) AJ8 400-2 (B) AJ8 400-2/4 (B)
55C 300C/120 Min. 300C/120 Min. 300C/120 Min. 300C/120 Min. 300C/120 Min. 300C/120 Min.
2200 2213
Dimensions
F E C
476
476
2200 2213
2200 2213
F E
E 635
C
635 684
195
Technical data
Centrifugal Jet fan IV Voltage/Frequency Motor rated power Current Thrust Max. air volume R.p.m. 50-4 (B) V/50 Hz 400 3~ kW 1,5 A 3,4 N 52 m/h 6196 min-1 1435 C 55 C 300 dB (A) 73 kg 105 H IP 55 50-4/6 (B) 400 3~ 1,5/0,7 3,5/1,9 52/20 6196/4190 1445/955 55 300 73/56 102 H 55 50-4/8 (B) 400 3~ 1,5/0,25 3,8/1,15 52/14 6138/3100 1430/715 55 300 73/52 105 H 55 85-4 (B) 400 3~ 2,2 4,7 85 9950 1435 55 300 78 140 H 55 85-4/6 (B) 400 3~ 2,2/0,75 4,9/2,6 85/28 9950/5875 1450/965 55 300 78/66 141 H 55 85-4/8 (B) 400 3~ 2,2/0,37 5,2/1,6 85/22 9950/5098 1425/715 55 300 78/62 142 H 55
Jet fans
Max. temp. of transported air Max. temp. of transported air 120 min. Sound pressure level at 3 m Weight Insulation class, motor Enclosure class, motor
Dimensions
6x K
H F D
Size IV 50 IV 85
A 790 1140
B 834 1184
C 870 1220
D 1248 1900
E 300 340
F 370 420
H 185 210
I 210 230
196
Jet fans
Every building has individual requirements for ventilation and smoke extraction concepts. Safety and efficiency are not in contradiction. In case of a fire, the control disregards energy consumption. It is important to guarantee the safety of the people and the building, to enable the personal rescue and assist the fire brigade and other action forces in their work, which minimizes fire and smoke gas damages. However, the systems generally run 24/24 and 365 days a year. Therefore each kilowatt of electrical energy used by the system counts for the operator or owner of the building. Compared to conventional systems a Green Ventilation Car Park System considerably reduces the energy use. For an optimal function, the control system has to be designed individually to meet all requirements of the project. Ideally, this must be done in line with all other crafts during basic conception and coordinated with the ventilation system of the building. Air quality requirements for desk spaces are different from those for underground car parks. Because of the duration of stay and other factors, harmful substances influence the human health. The factor time/duration of stay in the car park is responsible for different legal demands to average time values concerning CO exposure (half-hourly average value, quarter-hourly average value, ). Therefore, you can specify some areas of your building with different air quality that allows to provide exhaust air from the air conditioning unit to other areas as supply air. Normally, the windows of energy optimised, modern buildings are not permanently in a tilted position. In fact, air quality in modern buildings is monitored and can be changed when preset maximum values are achieved. Systemair implements this concept also for underground car parks. On demand, the parameters can be changed and customised by the user. All legal requirements can be accomplished.
Jet fans
The control system includes fan control for ventilation and smoke extraction of underground car parks, equipped with supply and exhaust fans, jet fans and sensors. Single- or double-speed fans and unidirectional or reversible fans can be controlled. Each jet fan can be separately switched on or off for maintenance and commissioning. In normal ventilation mode, the control system works either in accordance with the CO alarm system, or the timer, or the BMS system data. The fan will run either in high or low speed in the selected flow direction. In case of fire, the control system acts dependent on the fire alarm system. Virtual fire zones with different flow directions can be formed for smoke extraction. Being activated in the fire zone operate automatically in the selected speed and airflow direction. The built-in motor overload protection will be deactivated in the control cabinet. The fan permanently runs until mechanically demolished by the fire.
197
Jet fans
A CFD simulation is needed to confirm that there is enough air movement in all areas of the car park to secure the required number of air exchanges, to confirm the proposed number of jet fans and to determine the location where the jet fans have to be installed. In order to be able to perform a CFD analysis, it is essential to have a 3-D model of the building site, giving all openings, slab height, surface of the ceiling (flat or with drop beams, dimensioning of the drop beams, etc.) and all other details required to carry out a simulation. A CFD analysis is used to simulate the airflows, to ensure that the distribution of the air is sufficient to effectively ventilate the cark park under normal conditions as well as in emergency situations. Systemair offers this service meaning everything from one source and firsthand truly tailored solutions.
Jet fans
198
Jet fans
Project handling
Electrical planning, commissioning, final approval test, handing over. Everyone knows the problems on the building site when ventilation crafts and electrical crafts meet with different requirements. Two crafts with different requirements for your team. Systemair helps you to handle the project successfully and on schedule. From the conception of the complete system with CFD analysis to the detailed technical planning of the ventilation system and the creation of cable lists and the delivery of components to the points of commissioning and supervised final approval test including warm smoke gas test. Thus, all planning phases and crafts are in our focus, we coordinate the interfaces and give you support according to your needs.
Jet fans
Commissioning
Systemair offers a smoke gas extraction test while commissioning your car park system. This simulates a case of emergency.
199
General
Systemair explosion proof fans have been developed to be used in effective supply and exhaust air systems allocated to category 2 (zone 1) and category 3 (zone 2) in explosion hazardous areas. All fans are manufactured in accordance with ATEX guideline 94/9/EG certified for EC countries. Certificates can be downloaded from our homepage. The fans are suitable for mounting in above mentioned explosion hazardous zones, for extraction of gases.
II, allowing an application in zone 1 and zone 2. In the industry, explosion hazardous areas are classified in zones. ATEX classifies the fans in categories, corresponding to the zones. Categories are independent from the substance causing the explosion hazard. The classification in categories (or zones) is related to the temporal appearance (frequency of occurrence) of explosion hazard ous atmosphere (gas/vapour/ fog-air mixture in ignitable condition). The categories or zones do not define the concentration! Category 1 (zone 0) covers areas, where there is a permanent or long lasting occurrence of explosion hazardous atmosphere (more than 1000h/year). Example: inside a fuel tank. Category 2 (zone 1) covers areas, where there is a regular occurrence of explosion hazardous atmosphere (10-1000 h/year). Example: Filling machine Category 3 (zone 2) covers areas, where there is a non-regular or short time appearance of explosion hazardous atmosphere (up to 10h/year). Example: defective gas pipe, accidents. The categories show the occurrence of an explosion hazardous area as a probability. It is important to know: In all categories (zones) there is the same momentary hazard (same substance and same concentration) when explosion hazardous atmosphere occurs. Example: zone 0, empty and non-cleaned fuel tank, concentration 20Vol%; zone 2, leaked fuel, concentration 20Vol%. If an explosion hazardous atmosphere occurs, the hazard potential is the same in all zones! The last decision has to be made regarding the ignition protection class. All Systemair explosion proof fans correspond to ignition protection class Ex e = increased safety. The following table shows possible ignition protection classes.
Systemair ranges
The materials used in Systemair EX fans are in accordance with DIN EN 60079. The fans of series DVEX, DVV-Ex and RVK-Ex are equipped with self-cleaning impellers with backward curved blades. EX, KTEX and DKEX are equipped with impellers with forward curved blades. AW-EX is equipped with profiled steel axial impellers with additional painting.
AXC-EX and AXCBF-EX is equipped with either single or two speed motors in Ex d. This motor type can be speed controlled by frequency. All DVEX, KTEX, DKEX, AW-EX and RVK EX fan motors are equipped with a cold conductor for motor protection. The motor protection has to be connected with a motor protection device, described in the certificate and also certified. Motors of series DVV-Ex and EX do not have a thermal motor protection. Those motors have to be supervised by a suitable over-current device. The ignition temperature of the medium, but also the classification in explosion groups is important. Both classifications have to be considered when selecting a suitable fan.
Group (IEC)
group II A
group II B group II C
Motors
DVEX, AW-EX, KTEX, RVK and DKEX are equipped with speed controllable, certified external rotor motors in Ex e execution. EX is equipped with non speed controllable IEC motors, Exe execution. DVV-EX,
200
RVK 315Y4. . . . . . . . . . . . . 202 ATEX certified circular duct fan: 0.28 m3/s, backward curved impeller, 3 phase. Ex e, T1-T3, IIA and IIB, Zone 1 and 2.
DVV-EX . . . . . . . . . . . . . . . . 220 ATEX certified roof fan: up to 11.9 m3/s, backward curved impeller. Motor Ex d, T1-T4, IIA and IIB, Zone 1 and 2.
EX . . . . . . . . . . . . . . . . . . . . 204 ATEX certified centrifugal fans: up to 0.33 m3/s, forward curved impeller, 1-3 phase. Ex e, T1-T3, IIA and IIB, Zone 1 and 2
AW-EX. . . . . . . . . . . . . . . . . 226 Axial wall fans: up to 3.19 m3/s, 3 phase. Ex e, T1-T4, IIA and IIB, Zone 1 and 2.
KTEX . . . . . . . . . . . . . . . . . . 208 ATEX certified rectangular fans: up to 1.375 m3/s, forward curved impeller, 3 phase. Ex e, T1-T3, IIA and IIB, Zone 1 and 2.
AXC-EX . . . . . . . . . . . . . . . . 230 ATEX certified axial fan, up to 12.36 m3/s, 3~ version. Motor Ex d, T1-T3, IIA, IIB and IIC, Zone 1 and 2.
DKEX. . . . . . . . . . . . . . . . . . 212 ATEX certified centrifugal fans: up to -1.39 m3/s, forward curved impeller, 3 phase. Ex e, T1-T3, IIA and IIB, Zone 1 and 2.
AXCBF-EX . . . . . . . . . . . . . . 234 ATEX certified axial fan, up to 5.88 m3/s, 3~ versions. Motor Ex d, T1-T3, IIA, IIB and IIC, Zone 1 and 2.
DVEX. . . . . . . . . . . . . . . . . . 216
ATEX certified roof fan: 0.412.39 m3/s, backward curved impeller. Ex e, T1-T3, IIA and IIB, Zone 1 and 2.
CE labelling
CE 0820
201
The RVK fans are designed for installation in ducts. The fans have backward curved blades and external rotor motors. The RVK 315 Y4 can be controlled by reducing voltage via 5-step controller in combination with the Systemair Standard tripping unit UEK230E EX. The fans is supplied with flying leads. The RVK 315Y4 fan complies with the ATEX regulation. The fans can be used for zone 1 and zone 2; Field of application II, for gases of groups IIA and IIB, temperature class T1, T2 and T3. The casing is made from conducting plastic. The fans are certified under the no ZELM 03 ATEX 0198x. Improved safety in accordance with Ex e II T3. Attention: Motor protection device U-EK230E EX must always be connected.
R-DK4 KT p. 323
EX e p. 339
The explosion proof terminal box is supplied as an accessory to the RVK 315Y4, ordered seperately.
Technical data
RVK Art no. Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 4/10 m Weight Insulation class, motor Enclosure class, motor Motor protection Certificate Wiring diagram p. 391-400 315Y4 30271 V/50 Hz 400 3~ W 90 A 0.25 m3/s 0.311 min-1 1385 C 40 C 40 dB(A) 41.2 kg 6.7 B IP 44 U-EK230E EX ZELM 03 ATEX 0198X 43
202
Ventilation accessories
FK p. 355
200
60
SG p. 357
314
Performance
Tot 63 67 68 48 44 49 18 125 61 61 27
203
Quick selection
1 2
3 4 5
Technical data
EX Art no. Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 3 m Weight Insulation class, motor Enclosure class, motor Capacitor Motor protection Certificate Wiring diagram p. 391-400 9 9 10 140-4C 1557 V/50 Hz 230 1~ W 113 A 0.63 m3/s 0.154 min-1 1465 C -20... +40 C -20... +40 dB(A) 43 kg 8 F IP 54 8 MSEX 0.4-0.63 140-2C 1559 230 1~ 674 3.00 0.326 2885 -20... +40 -20... +40 49 9.8 F IP 54 25 MSEX 2.5-4.0 140-4 1560 400 3~ 131 0.38 0.162 1465 -20... +40 -20... +40 41 7.3 F IP 54 MSEX 0.25-0.4 140-2 1562 400 3~ 696 1.28 0.327 2890 -20... +40 -20... +40 47 9 F IP 54 MSEX 1.0-1.6 10 SP 03ATEX3103X 9 10 180-4C 1558 230 1~ 185 0.91 0.236 1415 -20... +40 -20... +40 41 8.3 F IP 54 8 MSEX 0.63-1.0 180-4 1561 400 3~ 188 0.43 0.217 1435 -20... +40 -20... +40 42 7.5 F IP 54 MSEX 0.4-1.0
204
Ventilation accessories
FKX p. 355
E D
IS p. 371
8/ 11
49
/ 58
HC
94
US p. 371
A 92 92 92 92 109 109
B 94 94 94 94 86 86
G 6 6 6 6 7 7
I 50 50 50
205
Tot 63 59 67 50 23 45 19 125 38 54 22
Tot 63 72 79 56 34 63 22 125 52 66 34
dB(A)
LwA Inlet LwA Outlet LwA Surrounding
Tot 63 60 65 48 23 43 13 125 42 57 23
Tot 63 72 78 54 32 63 21 125 50 67 31
206
Tot 63 62 67 48 24 47 23 125 41 57 25
Tot 63 62 70 49 24 52 13 125 47 63 30
207
R-DK4 KT p. 323
Quick selection
RTRD p. 321
1 2 3 4 5
KTEX 50-25-4 KTEX 50-30-4 KTEX 60-30-4 KTEX 60-35-4 KTEX 70-40-6
RTRDU p. 321
208
Ventilation accessories
DS-EX p. 363
FFK p. 357
10,0(8x)
LDR p. 358
8,0
KTEX 50-25-4 50-30-4 60-30-4 60-35-4 70-40-6 A 498 498 598 598 698 B 248 298 298 348 398 C 270 320 320 370 420 D 520 520 620 620 721 E 540 540 640 640 740 F 290 340 340 390 440 G 299 351 366 421 466 H 532 562 642 717 787
209
210
dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDR 70-40 LwA Inlet
Tot 63 71 77 62 63 51 52 42 51 125 58 59 54 51
211
R-DK4 KT p. 323
RTRD p. 321
DKEX 225-4 DKEX 250-4 DKEX 280-4 DKEX 315-4 DKEX 355-6
212
USE p. 371
D C E
ISE p. 371
L A G B
F
A 280 315 357 400 450
213
LwA Surrounding
LwA Surrounding 68
LwA Surrounding
214
Tot 63 76 78 65 49 47 37 125 62 60 47
215
R-DK4 KT p. 323
1 2 3 4
1 2
RTRDU p. 321
Technical data
DVEX Art no Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 4/10 m Weight Insulation class, motor Enclosure class, motor Motor protection Certificate Speed control, five step Speed control, five step high/low Wiring diagram p. 391-400 315D4 32813 V/50 Hz 400 3~ W 120 A 0.23 m3/s 0.411 min-1 1340 C -20... +40 C -20... +40 dB(A) 44/36 kg 18 F IP 44 U-EK230E EX SP 07ATEX3129X Transformer RTRD 2* Transformer RTRDU 2* 11 355D4 32814 400 3~ 260 0.47 0.689 1340 -20... +40 -20... +40 49/41 28 F IP 44 U-EK230E EX SP 07ATEX3130X RTRD 2* RTRDU 2* 11 400D4 32815 400 3~ 390 0.76 0.847 1350 -20... +40 -20... +40 54/46 29 F IP 44 U-EK230E EX SP 07ATEX3131X RTRD 2* RTRDU 2* 11 450D4 32816 400 3~ 720 1.42 1.26 1360 -20... +40 -20... +40 57/49 40 F IP 44 U-EK230E EX SP 07ATEX3132X RTRD 2* RTRDU 2* 11
* + U-EK230E EX. NB! When using the RTRD or RTRDU together with an EX motor protection type U-EK230E EX, the two terminals in the transformer marked TK must be bridged.
216
Ventilation accessories
ASF p. 375
ASK p. 380
E K I (4x)
ASS-EX p. 381
DVEX 315D4 355D4 400D4 450D4 560D6 630D6 A 560 720 720 900 B 382 442 442 517 C 470 618 618 730 955 955 D 192 226 255 289 364 410 E 330 450 450 535 750 750 F 146 199 199 237 293 293 I 12 12 12 12 12 12 K 406 566 566 636 939 939 L 304 466 466 490 M 330 390 390 465 560 560
BTG p. 374
1150 1150
FDS p. 374
FTG p. 371
SSD p. 374
TDA p. 371
VKS-EX p. 380
DVEX Art no Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 3 m Weight Insulation class, motor Enclosure class, motor Motor protection Certificate Speed control, five step Speed control, five step high/low Wiring diagram p. 391-400 560D6 32818 V/50 Hz 400 3~ W 620 A 1.23 m3/s 1.62 min-1 900 C -20... +40 C -20... +40 dB(A) 52/44 kg 62 F IP 44 U-EK230E EX SP 07ATEX3134X Transformer RTRD 2* Transformer RTRDU 2* 11 630D6 32819 400 3~ 1070 2.15 2.20 880 -20... +40 -20... +40 55/47 78 F IP 44 U-EK230E EX SP 07ATEX3135X RTRD 4* RTRDU 4* 11
* + U-EK230E EX. NB! When using the RTRD or RTRDU together with an EX motor protection type U-EK230E EX, the two terminals in the transformer marked TK must be briged.
217
Tot 63 64 67 48 48 125 53 53
Tot 63 68 72 61 50 51 50 125 58 58 55
Tot 63 72 77 67 58 57 57 125 62 62 60
Tot 63 76 80 71 58 58 57 125 64 67 62
218
Tot 63 70 75 66 58 57 58 125 59 61 57
Tot 63 73 78 68 53 53 53 125 64 65 62
219
Quick selection
1 2
3 4 5 6
1 2 3 4 5 6
DVV-EX 800D6 DVV-EX 800D6-K DVV-EX 800D8 DVV-EX 800D8-K DVV-EX 1000D6 DVV-EX 1000D8
5 2 6
Technical data
DVV-EX Art no Voltage/Frequency Power Current Starting current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 4/10 m Weight Insulation class, motor Enclosure class, motor Certificate Wiring diagram p. 391-400 560D4 30841 V/50 Hz 400 3~ W 1500 A 3.35 A 17.4 m3/s 2.64 min-1 1415 C 40 C 40 dB(A) 69/61 kg 72 F IP 55 Ex d 13b Y 560D6 30844 400 3~ 750 2.10 7.80 1.81 915 40 40 60/52 69 F IP 55 Ex d 13b Y 630D4 30852 400 3~ 5500 10.8 55.1 5.36 1435 40 40 75/69 161 F IP 55 Ex d 13b D 630D4-K 30847 400 3~ 3000 6.5 32.5 3.5 1415 40 40 71/63 120 F IP 55 Ex d 13b Y 630D6 30854 400 3~ 2200 5.0 30.5 3.36 960 40 40 64/58 133 F IP 55 Ex d 13b Y 630D6-K 30850 400 3~ 1100 3.0 12.3 2.28 915 40 40 61/53 107 F IP 55 Ex d 13b Y
220
Ventilation accessories
VKSV-EX p. 380
ASFV p. 384
ASSV-EX p. 383
FDVE/F p. 382
E F
DVV-EX 560D4/D6 630D4/D4-K/D6/D6-K 800D6/D6-K/D8/D8-K 1000D6/D8 A 808 B 750 C 20 40 40 70 D 438 541 674 751 E 600 880 880 F 706 990 990 G 12XM8 12XM8 H 14 18
SSV/F p. 382
SSVE/F p. 377
16xM10 18
ASK/F p. 380
DVV-EX Art no Voltage/Frequency Power Current Starting current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 4/10 m Weight Insulation class, motor Enclosure class, motor Certificate Wiring diagram p. 391-400
800D6 30856 V/50 Hz 400 3~ W 5500 A 11.80 A 72 m3/s 7.08 min-1 955 C 40 C 40 dB(A) 72/66 kg 205 F IP 55 Ex d 13b D
800D6-K 30859 400 3~ 2200 5.0 30.5 5.0 960 40 40 66/60 171 F IP 55 Ex d 13b Y
800D8 30858 400 3~ 2200 5.5 23.7 5.28 710 40 40 66/57 189 F IP 55 Ex d 13b Y
800D8-K 30861 400 3~ 1100 3.25 12.4 3.92 695 40 40 59/53 157 F IP 55 Ex d 13b Y
1000D6 30862 400 3~ 11000 23.5 141 12.4 965 40 40 73/66 370 F IP 55 Ex d 13b D
1000D8 30863 400 3~ 5500 13.4 64.3 9.44 715 40 40 66/58 348 F IP 55 Ex d 13b D
221
DVV-EX 560D4 dB(A) LwA Inlet Tot 88 Frequency bands [Hz] 63 61 63 LwA Surrounding 90 125 73 75 250 81 83 500 82 84 1k 81 83 2k 79 81 4k 76 78 8k 68 70
DVV-EX 630D4 dB(A) LwA Inlet LwA Surrounding Tot 97 98 Frequency bands [Hz] 63 68 68 125 79 87 250 91 88 500 90 91 1k 92 91 2k 87 91 4k 81 89 8k 72 79
DVV-EX 560D6 dB(A) LwA Inlet LwA Surrounding Tot 81 83 Frequency bands [Hz] 63 58 60 125 67 69 250 73 75 500 77 79 1k 72 74 2k 70 72 4k 68 70 8k 56 58
DVV-EX 630D6 dB(A) LwA Inlet LwA Surrounding Tot 90 92 Frequency bands [Hz] 63 67 69 125 76 78 250 82 84 500 86 88 1k 81 83 2k 79 81 4k 77 79 8k 65 67
DVV-EX 560D8 dB(A) Tot 76 78 Frequency bands [Hz] 63 LwA Inlet LwA Surrounding 58 60 125 64 66 250 67 69 500 71 73 1k 68 70 2k 68 70 4k 63 65 8k 52 54
222
DVV-EX 630D4-K dB(A) LwA Inlet LwA Surrounding Tot 92 94 Frequency bands [Hz] 63 65 67 125 77 79 250 85 87 500 86 88 1k 85 87 2k 83 85 4k 80 82 8k 72 74
DVV-EX 800D6 dB(A) LwA Inlet LwA Surrounding Tot 93 95 Frequency bands [Hz] 63 70 72 125 79 81 250 85 87 500 89 91 1k 84 86 2k 82 84 4k 80 82 8k 68 70
DVV-EX 630D6-K dB(A) LwA Inlet LwA Surrounding Tot 82 84 Frequency bands [Hz] 63 58 60 125 69 71 250 71 73 500 78 80 1k 73 75 2k 72 74 4k 68 70 8k 55 57
DVV-EX 800D8 dB(A) LwA Inlet LwA Surrounding Tot 82 84 Frequency bands [Hz] 63 64 66 125 70 72 250 73 75 500 77 79 1k 74 76 2k 74 76 4k 69 71 8k 58 60
223
DVV-EX 800D6-K dB(A) LwA Inlet LwA Surrounding Tot 84 86 Frequency bands [Hz] 63 60 62 125 71 73 250 73 75 500 80 82 1k 75 77 2k 74 76 4k 70 72 8k 57 59
DVV-EX 1000D6 dB(A) LwA Inlet LwA Surrounding Tot 92 94 Frequency bands [Hz] 63 69 71 125 78 80 250 84 86 500 88 90 1k 83 85 2k 81 83 4k 79 81 8k 67 69
DVV-EX 800D8-K dB(A) LwA Inlet LwA Surrounding Tot 75 77 Frequency bands [Hz] 63 58 60 125 64 66 250 66 68 500 70 72 1k 68 70 2k 68 70 4k 60 62 8k 49 51
DVV-EX 1000D8 dB(A) LwA Inlet LwA Surrounding Tot 84 86 Frequency bands [Hz] 63 66 68 125 72 74 250 75 77 500 79 81 1k 76 78 2k 76 78 4k 71 73 8k 60 62
224
225
R-DK4 KT p. 323
1 2 3 4
RTRDU p. 321
Technical data
AW Art no Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 3 m Weight Insulation class, motor Enclosure class, motor Motor protection Certificate Speed control, five step Speed control, five step high/low Wiring diagram p. 391-400 * + U-EK230E EX 355 D4-2-EX 5969 V/50 Hz 400 3~ W 286 A 0.27 m3/s 0.694 min-1 1420 C 40 C 40 dB(A) 62 kg 9 F IP 44 U-EK230E EX ZELM 05 ATEX0279X Transformer RTRD 2* Transformer RTRDU 2* 19 420 D4-2-EX 5970 400 3~ 536 0.943 1.23 1269 40 40 69 10 F IP 44 U-EK230E EX ZELM 05 ATEX0279X RTRD 2* RTRDU 2* 19 550 D6-2-EX 5971 400 3~ 579 1.15 1.84 697 40 40 67 13 F IP 44 U-EK230E EX ZELM 05 ATEX0279X RTRD 2* RTRDU 2* 19 650 D6-2-EX 5972 400 3~ 1077 1.78 3.04 790 40 40 72 20 F IP 44 U-EK230E EX ZELM 05 ATEX0279X RTRD 2* RTRDU 2* 19
226
A B C D 1,5
B 48 71 72 66
C 70 70 55 78
D 16 16 18 18
227
Tot 63 69 69 36 36 125 56 56
Tot 63 76 76 43 43 125 64 64
4 3
Tot 63 74 74 58 58 125 59 59
Tot 79 79
228
Project: Choren Industries Type of Building: Choren is an internationally leading supplier of technologies for the production of synthesis gas from carbonaceous solids. City/Country: Freiberg (Sachsen), Germany Products/Solution: Explosion proof roof fans, type DVV-EX 800 Explosion proof axial fans, AW 200-EX
229
Technical data
AXC-EX Art no Voltage/Frequency Max. power load Power Max current Current Max air flow R.p.m. Max temp. of transported air Weight Insulation class, motor Enclosure class, motor Certificate Wiring diagram p. 391-400 44 44 44 44 355-7 32-4 33007 V/50 Hz 400 3~ kW 0.37 W 225 A A 0.837 m3/s 0.92 min-1 1471 C 40 kg 40 F IP 55 400-7 32-4 33008 400 3~ 0.37 337 0.845 1.28 1461 40 75 F IP 55 450-7 24-2 33001 400 3~ 2.2 2532 4.8 4.81 2.81 2924 40 63 F IP 55 450-7 32-4 33009 400 3~ 0.55 473 1.6 1.16 1.8 1441 40 55 F IP 55 500-9 16-2 33002 400 3~ 3.0 3396 7.3 5.61 2.78 2905 40 82 F IP 55 44 500-9 22-4 33010 400 3~ 0.55 546 1.6 1.21 1.75 1428 40 65 F IP 55 44 SIRA 07ATEX6341X 44 44 44 44 500-9 26-2 33003 400 3~ 5.5 4753 12 7.87 4.03 2945 40 130 F IP 55 500-9 28-4 33011 400 3~ 0.75 662 2.0 1.55 2.23 1439 40 65 F IP 55 560-9 18-2 33004 400 3~ 5.5 5502 12 8.76 4.52 2932 40 155 F IP 55 560-9 20-4 33012 400 3~ 0.75 779 2 1.68 2.46 1428 40 90 F IP 55
230
Ventilation accessories
I
ESD-F p. 388
C D
GFL-AR/AXC p. 389
E F
AXC-EX 355 400 450 500 560 630 710 800 900 A 400 400 480 480 700 700 540 700 700 B 438 484 534 584 664 734 812 904 1004 C 359 401 450 504 565 634 711 797 894 D 346 388 436 490 551 618 694 778 869 E 395 438 487 541 605 674 751 837 934 F 505 552 605 659 730 803 883 973 1075 H 9.5 9.5 9.5 9.5 12 12 12 12 12 I 8x45 12x30 12 x 30 12 x 30 16 x 22.5 16 x 22.5 16 x 22.5 24 x 15 24 x 15
EV-EX/AXC p. 387
FSD p. 386
MFA-AR/AXC p. 386
SG AR/AXC p. 385
AXC-EX Art no Voltage/Frequency Max. power load Power Max current Current Max air flow R.p.m. Max temp. of transported air Weight Insulation class, motor Enclosure class, motor Certificate Wiring diagram p. 391-400
560-9 24-2 33005 V/50 Hz 400 3~ kW 7.5 W 6977 A 15 A 11.5 m3/s 5.43 min-1 2944 C 40 kg 155 F IP 55 44
560-9 26-4 33013 400 3~ 1.1 1088 2.8 2.04 3.18 1434 40 93 F IP 55 44
630-9 16-2 33006 400 3~ 7.5 7862 15 12.6 6.18 2936 40 155 F IP 55 44
630-9 18-4 33014 400 3~ 1.1 1156 2.8 2.15 3.44 1429 40 95 F IP 55 44
630-9 30-4 33015 400 3~ 3.0 2181 6.83 4.69 5.14 1465 40 105 F IP 55 44
710-9 30-4 33016 400 3~ 4.0 3360 8.2 6.03 6.7 1457 40 130 F IP 55 44
800-9 18-4 33017 400 3~ 4.0 2716 8.2 5.27 6.57 1467 40 130 F IP 55 44
800-9 28-4 33018 400 3~ 7.5 5339 16.5 11.8 9.1 1480 40 158 F IP 55 44
900-10 18-4 33019 400 3~ 7.5 6212 16.5 12.5 10 1476 40 255 F IP 55 44
SIRA 07ATEX6341X
231
1 2 3
4 5
1 2 3 4 5
AXC-EX 500-9/22-4 AXC-EX 500-9/26-2 AXC-EX 500-9/28-4 AXC-EX 560-9/18-2 AXC-EX 560-9/20-4
5 3
1
1 2 4
1 2
4 5
1 2 3
4 5
2 1 2 4 5 3 1 3 4 5
Frequency bands [Hz] 250 101 88 104 91 94 500 103 87 106 90 93 1k 101 86 104 89 92 2k 100 83 103 86 89 4k 96 78 99 81 84 8k 90 72 93 75 78
232
233
The Systemair AXCBF-EX range of bifurcated medium pressure axial fans has been developed for applications with an atmosphere which would either require special motors or reduce the lifetime of a standard motor. The Ex d motors of AXCBF-EX are out of the airstream. Available in sizes from 250 up to 800 mm impeller diameter. The stock range offers a stand-
ard selection with maximum airflow for the installed motor power. The fans can be used for zones 1 or 2, field of application II, for gases of groups IIA, IIB and IIC and for temperature classes T1 to T4. The fans are classified to category 2G. The fans are certified under Sira 07ATEX6341X. The Ex d motors are equipped with PTC thermistors for optimum motor protection. The motor
is speed controllable by frequency converter. AXCBF-EX bifurcated axial fan casings are heavy gauge, hot dip galvanized, with spun flanges for high rigidity. The motor compartment allows easy access to the motor terminal box for wiring. Single or three phase B3 foot mounted motors, totally enclosed and fan cooled.
Quick selection
1 2 3 4 5
AXCBF-EX 250-6/28-2 AXCBF-EX 250-6/28-4 AXCBF-EX 315-7/30-2 AXCBF-EX 315-7/32-4 AXCBF-EX 400-7/22-2
1 2 3 4 5
AXCBF-EX 400-7/32-4 AXCBF-EX 500-9/18-2 AXCBF-EX 500-9/30-4 AXCBF-EX 630-9/26-4 AXCBF-EX 800-9/18-4
Technical data
AXCBF-EX Art no Voltage/Frequency Max. power load Power Max current Current Max air flow R.p.m. Max temp. of transported air Weight Insulation class, motor Enclosure class, motor Certificate Wiring diagram p. 391-400 45 45 250-6/28-2 33021 V/50 Hz 400 3~ kW 0.37 W 309 A 1.1 A 0.79 m3/s 0.463 min-1 2916 C 40 kg 30 F IP 55 250-6/28-4 33025 400 3~ 0.25 93.4 0.8 0.563 0.225 1487 40 30 F IP 55 315-7/30-2 33022 400 3~ 0.75 693 1.9 1.43 0.911 2885 40 72 F IP 55 SIRA 07ATEX6341X 45 45 45 315-7/32-4 33026 400 3~ 0.25 155 0.8 0.609 0.459 1476 40 65 F IP 55 400-7/22-2 33023 400 3~ 2.20 1911 4.8 3.16 1.71 2918 40 64 F IP 54
234
22.5
H
FSD p. 386
B C D E
MFA-AXCBF p. 388
F
AXCBF-EX 250 315 400 500 short version 500 long version A 535 535 625 660 710 B 448 452 585 695 695 C 328 385 480 590 590 D 250 320 401 504 504 E 238 308 388 490 490 F 302 355 450 560 560 H I 10 10 10 12 12 8 x 45 8 x 45 8 x 45 12 x 30 12 x 30
EV-EX/AXC p. 387
GFL-AR/AXC p. 389
B C D
A 790 880
B 728 890
C 634 797
D 618 778
E 690 860
H 12 12
I 12 x 30 16 x 22,5
AXCBF/EX Art no Voltage/Frequency Max. power load Power Max current Current Max air flow R.p.m. Max temp. of transported air Weight Insulation class, motor Enclosure class, motor Certificate Wiring diagram p. 391-400
400-7/32-4 33027 V/50 Hz 400 3~ kW 0.55 W 444 A 1.6 A 1.1 m3/s 1.08 min-1 1444 C 40 kg 58 F IP 55 45
500-7/30-4 33028 400 3~ 1.1 863 2.8 1.85 1.85 1450 40 77 F IP 55 SIRA 07ATEX6341X 45
630-9/26-4 33029 400 3~ 2.2 2187 5.25 4.27 3.4 1459 40 112 F IP 55 45
800-9/18-4 33030 400 3~ 4.0 3403 8.2 6.02 5.88 1457 40 185 F IP 55 45
235
300C 120min
400C 120min
600C 120min
General
Fire develops smoke and heat. Within buildings these two factors represent a substantial danger for human beings, animals and the inventory. Constantly rising temperatures might lead to a so-called flash-over, where the fire spreads like an explosion. Buildings must be designed in a way that spreading of smoke and flames in case of a fire can be kept as small as possible. Escape routes have to be kept free of smoke to a largest possible extent, and fire fighting routes for the fire brigade have to be created. Contrary to natural smoke outlets (i.e. roof openings), mechanical smoke and heat extract systems immediately provide full capacity. Mechanical smoke and heat extract systems are particularly important for: High rooms without windows Underground floors and rooms Buildings with a constantly high wind load Large rooms with a high fire load Rooms with sprinkler systems, working against the thermal lift.
Systemair range
Systemair offers different types of smoke and heat extract fans: Centrifugal roof fans, centrifugal wall/duct fans and axial fans. All fans are approved for dual purpose ventilation, i.e. for normal daily ventilation and for emergency ventilation in case of a fire.
Multibox MUB/F
Casing Steel frame and double skin panels from galvanized steel, 20 mm rock wool insulation. Motor High temperature IEC motor for 400C/120 min. Impeller Impellers with backward curved blades.
Typical applications
In mechanical smoke and heat extract systems installed in shopping centres, airports, industrial buildings, big cinemas and theatres, warehouses etc. For industrial process air with increased temperatures. Car park ventilation.
236
400C 120min
400C 120min
MUB/F. . . . . . . . . . . . . . . . . 260 Smoke extract axial fans: 300C/2h, up to 19.16 m3/s, 3 phase, EN12101-3.
DVG/F . . . . . . . . . . . . . . . . . 250 Smoke extract roof fans 400C/2h: up to 7,5 m3/s, 3 phase.
400C 120min
600C 120min
AXC(B) . . . . . . . . . . . . . . . . . 266 Smoke extract fan for wall mounting, up to 11.1 m3/s, 3 phase. (I) insulated version.
300C 120min
400C 120min
600C 120min
WVA/WVI. . . . . . . . . . . . . . 268
400C 120min
400C 120min
600C 120min
237
REV p. 340
400C 120min
200C
The KBR/F fans smoke extract unit are used in case of fire to extract smoke gases from rooms, and also during normal working conditions for standard temperature up to 200C. The KBR/F units have backward curved impellers made of galvanized steel except size 355 which is a steel impeller painted RAL 9005.The units have a swing out door for easy inspection and service. The direction of the door opening can easily be changed from left to right at site. The fans have a double isolated casing with 50 mm rockwool inside. To protect the motors from overheating the KBR fans have integral thermal contacts with external leads for connection to a motor protection device. (Except size KBR 280 D2 and D2-4 which have integral cold conductors). In case of fire all protective devices must be bridged to guarantee functional capability. Single speed three phase units can also be delivered with motors according to IE2 standard on request.
RTRD p. 321
RTRDU p. 321
S-DT2 p. 340
Quick selection
1 2 3 4 5
KBR/F 280D2 KBR/F 280D2-4 KBR/F 280DV KBR/F 315DV KBR/F 315D2 IE2
1 2 3 4 5 6
KBR/F 355E4 KBR/F 355E4/K KBR/F 355DV KBR/F 355DV/K KBR/F 355K D2 IE2 KBR/F 355D2 IE2
STDT p. 342
Technical data
KBR/F Art no. Voltage/Frequency Power at shaft Power Current Max air flow R.p.m. Max temp. of transported air Max temp. of transported air for 120 min Sound pressure level at 4 m Sound pressure level at 10 m Weight Insulation class, motor Enclosure class, motor Wiring diagram p. 391-400 280D2 31586 V/50 Hz 400 3~ W 550 W 730 A 1.24 m3/s 0.824 min-1 2820 C 200 C 400 dB(A) 44 dB(A) 36 kg 48 F IP 55 13b Y 280D2-4 31588 400 3~ 480/120 1.2/0.33 0.806/0.422 2800/1410 200 400 44/33 36/25 49 F IP 55 14b 280DV 31587 400 3~ 370 1.39 0.422 1360 200 400 33 25 49 F IP 54 17 315DV 31590 400 3~ 370 1.39 0.611 1360 200 400 36 28 77 F IP 54 17 315D2 IE2 34509 400 3~ 1500 1218 2.33 1.09 2928 200 400 50 42 57 F IP 54 17 355E4 31554 230 370 2.1 0.972 1330 200 400 44 33 81 F IP 54 21
238
Ventilation accessories
A I 78
EVH p. 388
G B C
LRK(F) p. 385
E 38 E L 50 D 50
RSA p. 384
WBK p. 389
35 H
I 142,5 153,5
WSD-KBT p. 371
KBR/F Art no. Voltage/Frequency Power at shaft Current Max air flow R.p.m. Max temp. of transported air Max temp. of transported air for 120 min Sound pressure level at 4 m Sound pressure level at 10 m Weight Insulation class, motor Enclosure class, motor Wiring diagram p. 391-400
355E4/K 32891 V/50 Hz 230 1~ W 370 A 2.1 m3/s 0.778 min-1 1330 C 200 C 400 dB(A) 42 dB(A) 31 kg 80 F IP 54 21
355K D2 IE2 34511 400 3~ 2200 3.85 1.63 2909 200 400 53 45 75 F IP 55 17
239
qv [m3/h]
2000 350 300 250
ps [Pa]
ps [Pa]
KBR/F 280D2-4
KBR/F 280DV
74
800
200
2-pole
600 400 200 0 0 0 200 400 600 800 0,1 0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1
0 200 400 600 800 150 100
74
4-pole
72 84
72
0,5
qv [m3/s] p1 [W]
p1 [W]
qv [m3/s]
0,6
dB(A) 2-pole LwA Inlet LwA Outlet LwA Surrounding 4-pole LwA Inlet LwA Outlet LwA Surrounding
Tot 63 86 88 67 80 82 61 125 78 80 59
Tot 63 74 76 56 125 68 70 50
KBR/F 315DV
0 0 0 100 200 300 0,1 0,2 0,3 0,4 0,5 0,6 0,7 qv [m3/s]
p1 [W]
Tot 63 77 79 59 125 75 77 57
Tot 63 91 93 73 125 89 31 71
240
500
3500
KBR/F 355E4
KBR/F 355E4/K
p1 [W]
Tot 63 82 84 64 125 80 82 62
Tot 63 80 82 62 125 78 80 60
1000
2000
3000
4000
600 ps [Pa]
KBR/F 355DV
500
KBR/F 355DV/K
0,2
0,4
0,6
0,8
0,8
0,9
p1 [W]
Tot 63 82 84 64 125 80 82 62
Tot 63 82 84 125 80 82 62
LwA Surrounding 64
241
Tot 63 94 96 76 125 92 94 74
Tot 63 97 96 76 125 92 94 74
242
243
The DVV/F smoke extract fans are used in case of fire to extract smoke gases from rooms, and also during normal working conditions for standard ventilation. For installation only over heated rooms. For non-heated buildings flaps FSL for classification snow load SL1000 is available as accessories for sizes 450 up. The casing is manufactured from seawater resistant aluminium (DVV/F 1000 M and P 4 pole from aluzinc steel sheet). The base frame consists of galvanised steel. The impeller with backward-curved blades is manufactured from galvanised steel (type F400) respectively from stainless steel (type F600). The fan is equipped with IEC standard motors according to the 2009/640/EC guideline and IEC 60034-30, with protection class IP 54 or 55, insulation class F. Motor cooling with fresh air via air duct. Thermal motor protection (PTC or thermal contact built-in) on request, in IE2 motors serial PTC built-in. For frequency controlled single speed units up to 0,55 kW PTC must be ordered (since IE1 motors built-in). For speed control use only combination of frequency inverter and appropriate filter to motor side (sine or du/dt), observing installation conditions (e.g. cable
type, lenght). Operating over 50Hz is not allowed. Service switch serial on cooling duct at sizes 800 and 1000. Other sizes equipped with terminal box, service switch on request. In case of fire any speed control, frequency inverter and all motor protective devices must be bridged to guarantee functional capability (connection directly to mains). Frequency controlled units can have additional EMC protection (available on request). For additional sound reduction an outlet silencer HSDV is available as an accessory for all DVV/F fans. If factory mounted, the item reference is DVVI (sound insulated) fan. FSL is not dimensionally suitable for DVVI. Available also as DVV/120 for continuous exhaust of medium up to 120C (see online catalogue). Note: article numbers in tables refer to items without PTC or thermal contact, with exception of items with IE2 motors, where PTC is serial built-in.
400C 120min
600C 120min
Technical data
DVV/F Art no. F400 Art no. F600 Voltage/Frequency Power at shaft Current Starting current Max air flow R.p.m. Max. temp. of transp. air Max. temp. of transp. air for 120 min Sound pressure level at 4 m Sound pressure level at 10 m Weight Enclosure class, motor efficiency Thermal prot. PTC serial built-in Wiring diagram p. 391-400 400D4 3501 3500 V/50 Hz 400 3~ kW 0.55 A 1.6 A 6.6 m3/s 1.17 min-1 1390 C 55 C 400/600 dB(A) 62 dB(A) 52 kg 49 IP 54 15b 400D4-6 3505 3504 400 3~ 0.55/0.18 1.7/0.8 6.8/2.4 1.17/0.78 1420/940 55 400/600 62/53 52/43 49 IP 54 15a 450D4 IE2 95176 95175 400 3~ 1.1 2.6 12.5 2.01 1435 55 400/600 66 56 69 IP 54 IE2 yes 15c 3529 3528 400 3~ 1.1/0.370 3/1.4 10.8/5.9 2.01/1.35 1420/950 55 400/600 66/55 56/46 72 IP 54 15a 450D4-6 560D4 IE2 95178 95177 400 3~ 1.5 3.5 20.3 2.64 1420 55 400/600 69 59 78 IP 54 IE2 yes 15c 560D6 IE2 95180 95179 400 3~ 0.75 2 5.8 1.81 880 55 400/600 60 52 78 IP 54 IE2 yes 15c 3553 3552 400 3~ 1.7/1.2 4.6/3.7 23.9/13.3 2.64/1.81 1450/940 55 400/600 69/60 59/52 84 IP 54 15a 560D4-6 630D4-K IE2 95182 95181 400 3~ 3.0 6.6 36.7 3.5 1400 55 400/600 71 63 129 IP 54 IE2 yes 15c 630D6-K IE2 95186 95185 400 3~ 1.1 2.9 10.8 2.28 910 55 400/600 61 53 121 IP 54 IE2 yes 15c 3589 3588 400 3~ 3.6/0.9 8.0/3.2 44/10 3.5/1.72 1430/710 55 400/600 71/55 63/47 138 IP 54 14a 630D4-8-K
244
Ventilation accessories
DVV
ASFV p. 384
ASK/F p. 380
ASSV/F p. 383
FDV/F p. 381
DVV/F Art no. F400 Art no. F600 Voltage/Frequency Power at shaft Current Starting current Max air flow R.p.m. Max. temp. of transp. air Max. temp. of transp. air for 120 min Sound pressure level at 4 m Sound pressure level at 10 m Weight Enclosure class, motor efficiency Thermal prot. PTC serial built-in Wiring diagram p. 391-400
3
630D4 IE2 95184 95183 V/50 Hz 400 3~ kW 5.5 A 11.6 A 95 m /s 5.36 min-1 1455 C 55 C 400/600 dB(A) 75 dB(A) 69 kg 144 IP 54 IE2 yes 13b D
630D6 IE2 95188 95187 400 3~ 2.2 5.5 25.3 3.36 935 55 400/600 64 58 134 IP 54 IE2 yes 15c
630D4-6 3585 3584 400 3~ 5.5/1.7 12/4.5 81.6/20.3 5.36/3.36 1460/970 55 400/600 75/64 69/58 154 IP 55 15a
800D4-K 95199 95200 400 3~ 9.5 18 121 7.08 1445 55 400/600 76 70 262 IP 54 13b D
800D4-8-K 30064 30065 400 3~ 9.0/2.4 18.5/5.6 114/24 7.08/3.92 1420/720 55 400/600 76/55 70/48 281 IP 55 14a
800D6-K IE2 95190 95189 400 3~ 2.2 5.5 25.3 5.0 935 55 400/600 66 60 189 IP 54 IE2 yes 15c
800D6 IE2 95192 95191 400 3~ 5.5 12.6 76 7.08 950 55 400/600 72 64 213 IP 54 IE2 13b D
FDVE/F p. 382
FSL-DVV p. 379
VKV/F p. 383
VKVE/F p. 383
DVV/F Art no. F400 Art no. F600 Voltage/Frequency Power at shaft Current Starting current Max air flow R.p.m. Max. temp. of transp. air Max. temp. of transp. air for 120 min Sound pressure level at 4 m Sound pressure level at 10 m Weight Enclosure class, motor efficiency Thermal prot. PTC serial built-in Wiring diagram p. 391-400
800D4-8-M 30045 30046 400 3~ 16.2/3.7 36/13 290/64 9.58/4.79 1470/735 55 400/600 80/65 72/57 399 IP 55 14a
800D6-M 800D4-P IE2 95209 95210 400 3~ 4.0 9 48.6 6.22 955 55 400/600 70 62 209 IP 55 IE2 yes 13b D IE2 95197 95198 400 3~ 18.5 35 280 10.8 1465 55 400/600 83 75 397 IP 55 IE2 yes 13b D
800D4-8-P 30057 30058 400 3~ 18.5/4.5 40/15 335/75 10.8/5.42 1470/735 55 400/600 83/65 75/57 413 IP 55 14a
1000D6 IE2 95194 95193 400 3~ 11.0 22 156 12.4 955 55 400/600 74 66 378 IP 55 IE2 yes 13b D
1000D6-8 3766 3765 400 3~ 11.0/5.0 22/15 154/82.5 12.4/9.44 970/730 55 400/600 74/66 66/58 445 IP 55 15a
1000D6-12 3768 3767 400 3~ 12.0/2.4 23/7.5 140/23.3 12.4/6.67 960/480 55 400/600 74/63 66/54 445 IP 55 14a
A 62.8/21.7 265 m3/s 7.08/5.28 9.58 min-1 960/720 C 55 C 400/600 dB(A) 72/66 dB(A) 64/57 kg 224 IP 54 15a 1470 55 400/600 80 72 309 IP 55 IE2 yes 13b D
245
Ventilation accessories
E
HSDV p. 379
G H
ESDV p. 384
SSV/F p. 382
d1
d 35 B A
SSVE/F p. 377
DVV/F 400 450 560 630 800 800-M, P 1000 1000D4-M 1000D4-P
B 460 600 600 880 880 880 1040 1040 1040 1040
C 557 706 706 990 990 990 1154 1154 1154 1154
d 315 355 400 500 630 630 710 710 710 710
d1 356 395 438 541 674 674 751 751 751 751
d2 14 14 14 18 18 18 18 18 18 18
E 250 270 270 225 310 280 325 325 394 394
F 635 808 808 1100 1272 1350 1500 1500 1500 1500
G 630 700 750 958 1165 1280 1350 1350 1479 1479
H 40 20 20 40 40 40 70 70 70 70
nxM 8xM8 8xM8 12xM8 12xM8 16xM10 16xM10 16xM10 16xM10 16xM10 16xM10
1000D6-M, P 1160
DVV/F Art no. F400 Art no. F600 Voltage/Frequency Power at shaft Current Starting current Max air flow R.p.m. Max. temp. of transp. air Max. temp. of transp. air for 120 min Sound pressure level at 4 m Sound pressure level at 10 m Weight Enclosure class, motor efficiency Thermal prot. PTC serial built-in Wiring diagram p. 391-400
1000D8 3668 3667 V/50 Hz 400 3~ kW 5.5 A 12.5 A 63.8 m3/s 9.44 min-1 710 C 55 C 400/600 dB(A) 66 dB(A) 58 kg 355 IP 55 13a D
1000D4-M IE2 95205 95206 400 3~ 22.0 42 340 14.2 1470 55 400/600 89 79 539 IP 55 IE2 yes 13b D
1000D6-M IE2 95207 95208 400 3~ 7.5 15.7 112 9.42 970 55 400/600 77 67 358 IP 55 IE2 yes 13b D
1000D4-8-M 33126 33127 400 3~ 22.0/5.5 45/17 338/85 14.2/7.08 1470/730 55 400/600 89/70 79/60 575 IP 55 14a
1000D4-P IE2 95203 95204 400 3~ 28 56 420 15.2 1470 55 400/600 90 79 565 IP 55 IE2 yes 13b D
1000D4-8-P 31270 31271 400 3~ 28.0/7.0 51/20 400/80 15.2/7.56 1470/730 55 400/600 90/71 79/60 590 IP 55 14a
1000D6-P IE2 95201 95213 400 3~ 8.5 18 126 10.1 965 55 400/600 78 67 358 IP 55 IE2 yes 13b D
246
DVV/F 400D4-6
DVV/F 450D4-6
81
71
84
75
dB(A) 4-pole LwA Inlet LwA Surrounding 6-pole LwA Inlet LwA Surrounding
Tot 63 81 83 54 56 125 66 68
Tot 63 84 86 57 59 125 69 71
2000
4000
6000
8000
10000
DVV/F 560D4-6
DVV/F 630-K
88
82
92
81
76
dB(A) 4-pole LwA Inlet LwA Surrounding 6-pole LwA Inlet LwA Surrounding
Tot 63 88 90 61 63 125 73 75
Tot 63 92 94 65 67 125 77 79
Measurement point: 2,8 m/s; 400 Pa LwA Inlet LwA Surrounding 8-pole LwA Inlet LwA Surrounding 76 78 59 61 65 67 67 69 71 73 69 71 69 71 61 63 50 52 82 84 58 60 69 71 71 73 78 80 73 75 72 74 68 70 55 57
247
DVV/F 630
DVV/F 800-K
98
97 87 84
79
75
dB(A) 4-pole LwA Inlet LwA Surrounding 6-pole LwA Inlet LwA Surrounding 8-pole LwA Inlet LwA Surrounding
Tot 63 97 98 68 68 125 79 87
Tot 63 98 99 71 72 125 83 84
Measurement point: 5,6 m/s; 700 Pa LwA Inlet LwA Surrounding 8-pole 84 86 60 62 71 73 73 75 80 82 75 77 74 76 70 72 57 59
DVV/F 800
DVV/F 800-M
6-pole 8-pole
101
93 82
12-pole
71
82
90
dB(A) 6-pole LwA Inlet LwA Surrounding 8-pole LwA Inlet LwA Surrounding 12-pole LwA Inlet LwA Surrounding
Tot 63 93 95 70 72 125 79 81
Measurement point: 7,2 m/s; 740 Pa LwA Inlet LwA Surrounding 8-pole 90 92 67 69 78 80 80 82 87 89 82 84 81 83 77 79 64 66
248
DVV/F 800-P
DVV/F 1000
92
104
84
85
91
81
dB(A) 4-pole LwA Inlet LwA Surrounding 6-pole LwA Inlet LwA Surrounding 8-pole LwA Inlet LwA Surrounding
Tot 63 92 94 69 71 125 78 80
Measurement point: 6,94 m/s; 650 Pa LwA Inlet LwA Surrounding 12-pole 84 86 66 68 72 74 75 77 79 81 76 78 76 78 71 73 60 62
DVV/F 1000-M
104
DVV/F 1000-P
105
92 84 84
93
dB(A) 4-pole LwA Inlet LwA Surrounding 6-pole LwA Inlet LwA Surrounding 8-pole LwA Inlet LwA Surrounding
Measurement point: 9,2 m/s; 1580 Pa LwA Inlet LwA Surrounding 8-pole 93 98 75 80 81 86 84 89 88 93 85 90 85 90 80 85 69 74
249
Smoke and heat extract unit + normal ventilation Up to 400C/120 min (F400/120, F400/90, F300, F200) Normal ventilation up to 120C continuous operation Vertical exhaust DVG-V or horizontal DVG-H Includes pre-wired isolator Suitable for coastal applications Wide range of accessories Tested acc. to EN 12101-3 at LGAI, Barcelona CE-certified acc. to EN 12101-3, 2002-06 at TV Sd
The DVG/F smoke extract fans are used in case of fire to extract smoke gases from rooms, and also during normal working conditions for standard ventilation. Smoke-free escape ways increase the chances to rescue people in case of a fire. The casing is manufactured from seawater resistant aluminium. The base frame consists of galvanised steel. The impeller with backward-curved blades is manufactured from galvanised steel. Motor outside air stream is air cooled. The fan is equipped with IEC standard motors according to the 2009/640/EC guideline and IEC 60034-30, with protection class IP 54, insulation class F. Thermal motor protection (PTC or thermal contact built-in) on request, in IE2 motors serial PTC built-in, in DVG 400D4V serial thermal
contact built-in. For frequency controlled single speed units up to 0,55 kW PTC must be ordered (since IE1 motors built-in). For two speed fans (up to 4 kW) two speed switch, S-DT2 SKT/S-DT2 GKT is available as accessory (in this case thermal contact must be ordered; not suitable for PTC or without thermal contact). In case of fire two speed switch, eventual speed controller at DVG 400D4V and motor protective devices must be bridged to guarantee functional capability (connection direct to mains). For speed control use only combination of frequency inverter and appropriate all pole sine filter (hot tested at LGAI with inverter and sine filter). If frequency inverter used in case of fire, PTC must be bridged and switching on max. speed even after eventual short sup-
ply cut off assured. Operating over 50 Hz is not allowed. Frequency controlled units can have additional EMC protection (available on request). Note: article numbers in tables refer to items without PTC or thermal contact, with exception of items with IE2 motors, where PTC is serial built-in. Note: diagrams and data of max. airflow and sound level refer to items with vertical exhaust DVG-V; diagrams and data of DVG-H are available on-line. Data related to motor and weight of delivered items can vary from catalogue data due to different suppliers.
Technical data
DVG/F Art no. DVG-V (vertical) Art no. DVG-H (horizontal) Voltage/Frequency Power at shaft Current Starting current Max air flow R.p.m. Max. temp. of transp. air* Sound pressure level at 4 m Sound pressure level at 10 m Weight vertical/horizontal Enclosure class, motor PTC serial built-in motor S-DT2DKT, S-DT2GKT FXDM Wiring diagram p. 391-400 *for 120 min 15b 14a 15b 14a 15b 14a 15b 14a 15c ...DKT ...DKT ...DKT ...DKT 315D4 32306 95001 V/50 Hz 400 3~ kW 0.37 A 0.95 A 4.1 m3/s 0.71 min-1 1405 C 400 dB(A) 55 dB(A) 49 kg 41/39 IP 54 315D4-8 32307 95002 400 3~ 0.37/0.12 1.3/0.6 3.4/1.3 0.71/0.36 1350/680 400 55/39 49/33 41/39 IP 54 355D4 32308 95003 400 3~ 0.37 0.95 4.1 0.81 1405 400 56 50 43/41 IP 54 355D4-8 32309 95004 400 3~ 0.37/0.12 1.3/0.6 3.4/1.3 0.76/0.38 1350/680 400 56/41 50/35 43/41 IP 54 400D4-S 32310 95005 400 3~ 0.37 1.6 6.6 0.97 1390 400 59 53 45/41 IP 54 400D4-8-S 32311 95006 400 3~ 0.37/0.12 1.3/0.6 3.4/1.3 0.97/0.49 1350/680 400 59/43 53/37 45/41 IP 54 400D4 32312 95007 400 3~ 0.55 1.6 6.6 1.31 1390 400 62 55 46/44 IP 54 400D4-8 32313 95008 400 3~ 0.50/0.12 1.6/0.6 5.8/1.3 1.31/0.66 1410/670 400 62/46 55/40 46/44 IP 54 450D4 IE2 95164 95153 400 3~ 0.75 2.1 10.1 1.52 1425 400 65 58 56/52 IP 54 PTC
250
1 2 3 4
5 6 7
1 2 3
4 5 6 7 8
DVG/F 450D8 DVG/F 500D4 IE2 DVG/F 500D4-S IE2 DVG/F 500D8-S DVG/F 500D8
ASFV p. 384
5 6 3 1
4 1 6
ASK/F p. 380
2 3 5 7
2 4 7 8
ASSG/F p. 383
FDGE/F p. 378
8171, 8187, 8191, 8161, 8170, 8194, 8195
1 2 3
4 5 6 7
DVG-F 630D4 IE2 DVG-F 630D4-S DVG-F 630D8-S DVG-F 630D6 IE2
1 2 3
4 5 6 7
DVG-F 800D6-S IE2 DVG-F 800D8-S DVG-F 800D6 IE2 DVG-F 800D8
SSG/F p. 378
4 1 5
6 4
1
3 2 6 7
5 2 3
FDG/F p. 377
VKG/F p. 383
DVG/F Art no. V (vertical) Art no. H (horizontal ) Voltage/Frequency Power at shaft Current Starting current Max air flow R.p.m. Max. temp. of transp. air* Sound pressure level at 4 m Sound pressure level at 10 m Weight vertical/horizontal Enclosure class, motor PTC serial built-in motor S-DT2DKT, S-DT2GKT FXDM... Wiring diagram p. 391-400 *for 120 min
450D4-8 32315 95010 V/50 Hz 400 3~ kW 1.1/0.25 A 3.1/1.2 A 12.4/3 m3/s 1.52/0.76 min-1 1400/690 C 400 dB(A) 65/48 dB(A) 58/42 kg 58/55 IP 54 ...DKT
500D4 IE2 95165 95154 400 3~ 1.5 3.5 20.3 2.64 1420 400 70 63 86/82 IP 54 PTC ...5AM
500D4-S IE2 95166 95155 400 3~ 1.1 2.6 12.5 2 1435 400 66 60 87/83 IP 54 PTC
500D4-8-S 32317 95012 400 3~ 1.1/0.25 3.1/1.25 12.4/3.0 2.0/1.0 1400/690 400 66/49 60/44 87/83 IP 54 ...DKT
500D4-8 32319 95014 400 3~ 1.4/0.35 3.5/1.4 14.4/3.5 2.64/1.32 1400/680 400 70/52 63/45 86/82 IP 54 ...DKT
560D4 IE2 95169 95158 400 3~ 2.2 4.9 28.9 3.24 1425 400 72 67 104/99 IP 54 PTC
560D4-8 32323 95018 400 3~ 2.5/0.6 5.9/2.4 30.7/7.4 3.24/1.6 1430/710 400 72/51 67/46 107/102 IP 54 ...DKT
560D6 IE2 95170 95159 400 3~ 0.75 2 5.8 2.11 880 400 58 52 96/91 IP 54 PTC ...5AM
630D4 IE2 95171 95160 400 3~ 4 8.7 51 4.91 1445 400 75 69 128/123 IP 54 PTC ...14AM 15c
14a
15c
15c
251
DVG-H/F
Max 240 df (nxM)
E
Max 240
DVG/F 315
G
G 594
df (n x M)
H1 H
12 891
438 (6xM8) 30 520 438 (6xM8) 30 567 438 (6xM8) 30 557 438 (6xM8) 30 637 605 (8xM8) 30 696
14 1540 1078 605 (8xM8) 30 773 14 1573 1072 674 (8xM8) 40 858 14 2024 1280 872 (8xM8) 40 999
H1
DVG/F Art no. DVG-V (vertical) Art no. DVG-H (horizontal Voltage/Frequency Power at shaft Current Starting current Max air flow R.p.m. Max. temp. of transp. air* Sound pressure level at 4 m Sound pressure level at 10 m Weight Enclosure class, motor PTC serial built-in motor S-DT2DKT, S-DT2GKT FXDM... Wiring diagram p. 391-400 * for 120 min DVG/F Art no. DVG-V (vertical) Art no. DVG-H (horizontal Voltage/Frequency Power at shaft
630D4-S IE2 95172 95161 V/50 Hz 400 3~ kW 3 A 6.6 A 36.7 m3/s 3.82 min-1 1400 C 400 dB(A) 71 dB(A) 65 kg 119/114 IP 54 PTC
630D4-8-S 32328 95023 400 3~ 3.6/0.9 8.0/3.2 44.0/10.0 3.82/1.89 1430/710 400 71/55 65/49 128/123 IP 54 ...DKT
630D6 IE2 95173 95162 400 3~ 1.5 3.8 18.6 3.19 945 400 66 60 115/110 IP 54 PTC ...5AM
H1
630D6-S IE2 95174 95163 400 3~ 1.1 2.9 10.8 2.45 890 400 62 56 111/106 IP 54 PTC
630D6-8-S 32326 95021 400 3~ 1.0/0.4 3.3/1.35 14.2/4.7 2.45/1.89 950/710 400 62/55 55/49 117/112 IP 54 ...GKT
630D4-8 32333 95028 400 3~ 4.6/1.1 9.5/3.5 57/12.3 4.91/2.47 1450/720 400 75/59 69/54 144/139 IP 54 ...DKT 14a
15c
15c
15a
800D6-S IE2 95131 95126 V/50 Hz 400 3~ kW 3 A 6.8 A 34.7 m3/s 5.28 min-1 950 C 400 dB(A) 71 dB(A) 64 kg 202/195 IP 54 PTC
800D6-8-S 95132 95127 400 3~ 2.8/1.1 7.5/3.8 38.3/15.6 5.28/3.96 970/730 400 71/63 64/56 208/201 IP 54 ...GKT
800D6 IE2 95128 95122 400 3~ 5.5 12.6 76 7.03 960 400 74 66 212/205 IP 54 PTC
800D6-8 95130 95125 400 3~ 5.7/2.4 12.3/6.2 62.8/21.7 7.08/5.28 960/720 400 74/68 66/60 219/212 IP 54 ...GKT
Current Starting current Max air flow R.p.m. Max. temp. of transp. air* Sound pressure level at 4 m Sound pressure level at 10 m Weight vertical/horizontal Enclosure class, motor PTC serial built-in motor S-DT2DKT, S-DT2GKT FXDM... Wiring diagram p. 391-400 *for 120 min
252
DVG-V 315/F
DVG-V 355/F
4-pole
4-pole
8-pole
8-pole
qv [m/s]
dB(A) 4-pole LwA Inlet LwA Outlet 8-pole LwA Inlet LwA Outlet 62 60 40 44 58 52 54 53 54 53 53 55 53 50 45 42 36 33 78 76 51 54 72 65 72 72 69 67 71 69 69 67 64 61 61 51 Tot 63 125 Frequency bands [Hz] 250 500 1k 2k 4k 8k 4-pole LwA Inlet LwA Outlet 8-pole LwA Inlet LwA Outlet 65 62 43 46 61 54 57 55 57 55 81 77 55 55 75 67 75 74 73 69 dB(A) Tot 63 125 250 500
qv [m/s]
Frequency bands [Hz] 1k 74 71 2k 73 68 4k 67 62 8k 64 52
qv [m/h]
qv [m/h]
DVG-V 400-S/F
DVG-V 400/F
4-pole
4-pole
6-pole 8-pole
8-pole
qv [m/s]
dB(A) 4-pole LwA Inlet LwA Outlet 8-pole LwA Inlet LwA Outlet 66 66 44 50 62 58 58 59 58 59 57 61 57 56 49 48 40 39 82 82 55 60 76 71 76 78 73 73 75 75 73 73 68 67 65 57 Tot 63 125
Tot 63 85 85 58 63 125 79 74
Measurement point: 1,1 m/s; 125 Pa 6-pole LwA Inlet LwA Outlet 8-pole LwA Inlet LwA Outlet 69 68 47 52 65 60 61 61 61 61 60 63 60 58 52 50 43 41 76 76 46 55 69 66 69 70 69 69 68 71 69 67 61 59 53 49
253
DVG-V 450/F
4-pole
4-pole
DVG-V 500-S/F
8-pole
8-pole
qv [m/s]
dB(A) 4-pole LwA Inlet LwA Outlet 8-pole LwA Inlet LwA Outlet 71 69 50 52 61 58 63 63 61 62 67 63 62 59 62 56 50 39 88 87 56 57 71 73 73 77 78 81 86 84 74 73 67 67 63 60 Tot 63 125 Frequency bands [Hz] 250 500 1k 2k 4k 8k 4-pole LwA Inlet LwA Outlet 8-pole LwA Inlet LwA Outlet 72 69 53 52 62 59 64 62 63 63 88 88 61 63 81 76 81 81 79 80 dB(A) Tot 63 125 250 500
qv [m/s]
Frequency bands [Hz] 1k 81 84 2k 78 78 4k 79 73 8k 66 62
qv [m/h]
qv [m/h]
DVG-V 500/F
4-pole
DVG-V 560/F
4-pole
6-pole
8-pole
8-pole
qv [m/s]
qv [m/s]
dB(A)
Tot 63 125 74 75
dB(A) 4-pole
Tot 63 125 85 84
90 91
61 64
74 65
94 94
59 67
Outlet
Measurement point: 2,1 m/s; 300 Pa 8-pole LwA Inlet LwA Outlet 72 73 50 57 68 65 64 66 64 66 63 68 63 63 55 55 46 46
Measurement point: 2,5 m/s; 400 Pa LwA Inlet LwA Outlet 8-pole LwA Inlet LwA Outlet 76 74 55 58 65 64 68 69 66 67 72 69 67 65 67 61 55 44 87 82 57 61 80 73 80 77 80 74 79 75 80 74 71 66 64 58
254
DVG-V 630-S/F
4-pole
DVG-V 630/F
4-pole
6-pole
qv [m/s]
DVG-V 800-S/F
DVG-V 800/F
6-pole
8-pole
Tot 63 125
dB(A) 6-pole
Tot 63 125
250
500
1k
2k
4k
8k
88 91
48 56
64 70
69 76
78 84
81 88
84 84
83 79
70 64
96 94
55 42
65 65
81 75
87 87
89 91
93 87
86 77
83 67
Measurement point: 4,2 m/s; 300 Pa 8-pole LwA Inlet LwA Outlet 82 83 34 45 58 61 64 68 70 77 76 79 79 75 70 68 67 69
90 87
48 42
62 59
70 70
79 82
88 84
84 77
77 69
71 63
255
RTRD p. 321
STDT 16 p. 342
The DVG smoke extract fans are used in case of fire to extract smoke gases from rooms, and also during normal working conditions for standard ventilation. Smoke-free escape ways increase the chances to rescue people in case of a fire. For installation only on top of heated buildings. The casing is manufactured from seawater resistant aluminium.
The base frame consists of galvanised steel. The impeller with backward-curved blades is manufactured from galvanised steel. Motor outside air stream of IE1 standard efficiency is cooled with fresh air. Thermal contact built-in motor. In case of fire eventual transformer and all protective devices must be bridged to guarantee functional capability (connection direct to mains).
Technical data
DVG/F DVG-V 400D4V Art no. V (vertical) 95220 Voltage/Frequency V/50 Hz 400 3~ kW 0.55 A 1.5 A 5.4 m3/s 1.32 min
-1
DVG-H 400D4V Art no. H (horizonal) 95221 400 3~ 0.55 1.5 5.4 1.42 1290 120 400 63 56 44 F IP 55 7
Power at shaft Current Starting current Max air flow R.p.m. Max. temp. of transp. air Max. temp. of transp. air* Sound pressure level at 4 m Sound pressure level at 10 m Weight Insulation class, motor Enclosure class, motor Wiring diagram p. 391-400 *for 120 min
1290
256
38
38
ASFV p. 384
12
6xM
535 724
12
535 724
6xM
ASK/F p. 380
557
557
ASSG/F p. 383
289 379 670
251
668 1053
668
240 max
240 max
FDG/F p. 377
FDGE/F p. 378
SSG/F p.378
SSGE/F p. 379
VKG/F p. 383
Tot 63 82 82 55 60 125 76 71
Tot 63 82 83 55 61 125 76 72
257
DVG-V
DVG-V
VKG/F Automatic shutter SSG/F Silencer ASG/F Inlet chamber ASSG/F Flexible connection
VKG/F Automatic shutter SSGE/F (FDGE/F) Silencer ASG/F Inlet chamber ASSG/F Flexible connection
258
259
400C 120min
The smoke extract units MUB/F are used in case of fire to extract smoke gases from rooms, and also during normal working conditions for standard temperature up to 55C continuously. The MUB/F units have backward curved impellers made of galvanized steel. The outlet can be easily changed on site from straight to side outlet. The unit is made of a profiled steel frame design. All materials are galvanized and seawater resistant. Motors are high temperature motors for temperature classification F 400/120 min. The fan has a double skinned panel with smooth surface to protect against dust and dirt. Motor can be wired for either single speed or 2-speed execution.
Quick selection
1 2 3 4 5 6
MUB/F 042 400D4 MUB/F 042 400D6 MUB/F 042 450D4 MUB/F 042 450D6 MUB/F 062 500D4 MUB/F 062 500D6
1 2 3 4
MUB/F 062 560D4 MUB/F 062 560D6 MUB/F 062 630D4 MUB/F 062 630D6
Technical data
MUB/F Art no. Voltage/Frequency Power at shaft Current Max air flow R.p.m. Max temp. of transported air Max temp. of transported air for 120 min Sound pressure level at 3 m Sound pressure level at 4 m Sound pressure level at 10 m Weight Insulation class, motor Enclosure class, motor Wiring diagram p. 391-400 042 400D4 33290 V/50 Hz 400 3~ W 550 A 1.32 m3/s 1.49 min-1 1461 C 55 C 400 dB(A) 31 dB(A) 39 dB(A) 55 kg 98 HC IP 55 10 042 400D4-6 33292 400 3~ 550/180 1.32/0.80 1.49/0.99 1461/980 55 400 31/23 39/31 55/47 105 HC IP 55 15a 042 450D4 33293 400 3~ 750 1.63 1.58 1446 55 400 33 41 57 105 HC IP 55 10 042 450D4-6 33295 400 3~ 750/250 1.63/0.90 1.58/1.04 1446/971 55 400 33/25 41/33 57/49 111 HC IP 55 15a 062 500D4 33296 400 3~ 1500 3.26 2.27 1440 55 400 42 50 66 134 HC IP 55 10 062 500D4-6 33298 400 3~ 1500/550 3.26/1.76 2.27/1.53 1440/967 55 400 42/31 50/39 66/55 136 HC IP 55 15a
260
FGV p. 370
A J
SDM p. 369
SRKG p. 370
I H E D C B
UGS p. 370
WSD p. 370
MUB/F Art no. Voltage/Frequency Power at shaft Current Max air flow R.p.m. Max temp. of transported air Max temp. of transported air for 120 min Sound pressure level at 3 m Sound pressure level at 4 m Sound pressure level at 10 m Weight Insulation class, motor Enclosure class, motor Wiring diagram p. 391-400
062 560D4 33299 V/50 Hz 400 3~ W 2200 A 4.58 m3/s 2.66 min-1 1440 C 55 C 400 dB(A) 45 dB(A) 53 dB(A) 69 kg 154 HC IP 55 10
062 560D4-6 33301 400 3~ 2200/750 4.58/2.47 2.66/1.77 1440/972 55 400 45/34 53/42 69/58 155 HC IP 55 15a
062 630D4 33302 400 3~ 4000 8.58 3.83 1459 55 400 51 59 75 163 HC IP 55 10
062 630D6 33303 400 3~ 1500 3.93 2.52 979 55 400 40 48 64 158 HC IP 55 10
062 630D4-6 33304 400 3~ 4000/1500 8.58/3.93 3.83/2.52 1459/979 55 400 51/40 59/48 75/64 190 HC IP 55 15a
261
Tot 63 77 73 61 63 62 35 125 72 64 50
Tot 63 77 79 62 62 64 42 125 69 72 49
Tot 63 81 76 65 63 42 49 125 69 60 56
Tot 63 80 79 64 45 53 31 125 69 67 58
262
Tot 63 84 79 68 55 50 125 77 64 65
Tot 63 85 80 73 69 57 51 125 78 68 65
LwA Surrounding 73
Tot 63 75 71 62 62 59 42 125 69 61 57
Tot 63 74 71 62 60 55 41 125 69 65 57
263
Tot 63 85 82 76 71 72 52 125 80 74 74
Tot 63 85 86 76 75 65 55 125 81 84 74
Tot 63 75 81 65 61 68 44 125 70 73 59
Tot 63 76 73 65 63 56 46 125 71 64 60
264
Tot 63 93 93 83 79 82 62 125 85 84 74
Tot 63 92 94 82 74 85 58 125 83 83 72
Tot 63 83 80 71 67 63 48 125 76 68 68
Tot 63 82 81 71 65 68 46 125 76 74 67
265
300C 120min
The Systemair AXC (B), AXR (B) range of long cased smoke extract axial fans is available in sizes from 315 up to 1600 mm impeller diameter. The adjustable pitch angle setting offers a wide performance and maximum flexibility to match precisely individual airflow requirements. The AXC (B) and AXR (B) axial fans have been performance tested in accordance with DIN ISO 5801, DIN 24163 and AMCA 210-99 on the Systemair fan test rig. High temperature testing at Technical University Munich, Germany. All AXC (B) fans are labeled with CE-mark and they are DIBt approved.
Sturdy casing
AXC and AXR axial fan casings are heavy gauge, hot dip galvanized, with spun flanges for high rigidity. Long cased execution as standard stock range.
Motors
Motors are air stream mounted. Frequency converter controllable only for standard ventilation on request. Single or two speed motors.
Axial fan reversible Two stage, two fans in series Sound insulated 300/120 min. 2-pole motor Pitch angle Number of blades Nominal diameter Axial fan unidirectional
266
267
400C 120min
600C 120min
The WVI smoke extract fans are used in case of fire to extract smoke gases from rooms, and also for daily ventilation (dual purpose fans). Smoke-free escape ways increase the chances to rescue people in case of fire. The casing is manufactured from steel, powder coated RAL 7032. The base frame consists of galvanised steel. The impeller with backward-curved blades is manufactured from galvanised steel resp. stainless steel (type F600). Thermal motor protection on request (PTC or thermal contact). In case of fire all motor protective devices must be bridged to guarantee functional capability.
WVA For installation only outside the building. Fans are certified for horizontal installation on a wall, motor pointing downwards. WVI With insulated motor for installation inside the building and inside the fire zone. Cooling of motor via air duct (accessories). Fans are certified for horizontal installation on a outer wall, motor facing downwards. Note: Article numbers in tables refer to items without PTC or thermal contact. IE2 single speed motors are available with PTC built-in. Data related to motor and weight of delivered items can vary from catalogue data due to different suppliers.
Quick selection
1 2 3
4 5 6 7 8
WVA/WVI 630D4 WVA/WVI 630D6 WVA/WVI 800D6-K WVA/WVI 800D8-K WVA/WVI 800D12-K
1 2 3
4 5 6 7 8
WVA/WVI 630D4 WVA/WVI 630D6 WVA/WVI 800D6-K WVA/WVI 800D8-K WVA/WVI 800D12-K
3 8
3 5 7 6 8
Technical data
WVA/WVI Art no. WVA F400 Art no. WVA F600 Art no. WVI F400 Art no. WVI F600 Voltage/Frequency Power at shaft Current Starting current Max air flow R.p.m. Max. temp. of transported air Max. temp. of transported air* Sound pressure level 4 m Sound presssure level 10 m Weight Insulation class, motor Enclosure class, motor Wiring diagram p. 391-400 * for 120 min 400D4 30736 30789 30763 30815 V/50 Hz 400 3~ kW 0.55 A 1.6 A 6.6 m3/s 1.22 min-1 1390 C 55 C 400/600 dB(A) 68 dB(A) 57 kg 48 F IP 54 15b 400D4-6 30737 30790 30764 30816 400 3~ 0.55/0.18 1.7/0.8 6.8/2.4 1.22/0.778 1420/940 55 400/600 68/54 57/43 48 F IP 54 15a 400D4-8 95099 95100 95105 95106 400 3~ 0.5/0.12 1.6/0.6 5.8/1.3 1.22/0.61 1410/670 55 400/600 68/48 57/37 48 F IP 54 14a 450D4 30739 30792 30766 30818 400 3~ 1.1 2.7 11.8 1.81 1390 55 400/600 75 64 64 F IP 54 15b 450D4-6 30740 30793 30767 30819 400 3~ 1.1/0.37 3/1.4 10.8/5.9 1.81/1.15 1420/950 55 400/600 75/63 64/52 67 F IP 54 15a 450D4-8 95101 95102 95107 95108 400 3~ 1.1/0.25 3.1/1.2 12.4/3.0 1.81/0.89 1400/690 55 400/600 75/56 64/45 67 F IP 54 14a 560D4 30742 30795 30769 30821 400 3~ 1.5 3.6 17.3 2.5 1390 55 400/600 77 66 81 F IP 54 15b 560D4-6 30743 30796 30770 30882 400 3~ 1.7/1.2 4.6/3.7 23.9/13.3 2.5/1.56 1450/940 55 400/600 77/66 66/55 87 F IP 54 15a 560D4-8 95103 95104 95109 95110 400 3~ 2.0/0.5 5.0/2.0 22.5/6.0 2.5/1.19 1420/700 55 400/600 77/59 66/48 89 F IP 54 14a
268
WVI
A M8 D C B
Ventilation accessories
D C B
EPSN/EPIN p. 389
max. F
E R
IN p. 390
P G
SN p. 390
WBK-W p. 389
J K
J K
ZHZ p. 389
M 356 (8xM8) 395 (8xM8) 438 (12xM8) 541 (12xM8) 674 (16xM10) 751 (16xM10)
1120 43 1400 43
WVA/WVI Art no. WVA F400 Art no. WVA F600 Art no. WVI F400 Art no. WVI F600 Voltage/Frequency Power at shaft Current Starting current Max air flow R.p.m. Max. temp. of transported air Max. temp. of transported air* Sound pressure level 4 m Sound presssure level 10 m Weight Insulation class, motor Enclosure class, motor Wiring diagram p. 391-400 * for 120 min
630D4-K 30750 30802 30776 30828 V/50 Hz 400 3~ kW 3.0 A 6.9 A 38.0 m3/s 3.28 min-1 1400 C 55 C 400/600 dB(A) 78 dB(A) 67 kg 169 F IP 54 15b
630D4-6-K 30751 30803 30777 30829 400 3~ 3.0/0.9 6.9/3.3 38.0/13 3.28/2.17 1450/975 55 400/600 78/69 67/58 176 F IP 54 15a
630D4-8-K 30752 30804 30778 30830 400 3~ 3.6/0.9 8.0/3.2 44.0/10.0 3.28/1.61 1430/710 55 400/600 78/62 67/51 175 F IP 54 14a
630D4 30746 30798 30772 30824 400 3 ~ 5.5 11.0 75.5 4.75 1440 55 85 74 179 F IP 54 13a D
630D4-6 30747 30799 30773 30825 400 3~ 5.5/1.7 12.0/4.5 81.6/20.3 4.75/3.06 1460/970 55 85/77 74/66 183 F IP 54 15a
800D6-K 30757 30809 30783 30835 400 3~ 2.2 5.7 30.2 4.28 930 55 400/600 74 63 204 F IP 54 15b
800D6-8-K 30758 30810 30784 30836 400 3~ 2.2/0.9 6.0/3.3 27.7/11.7 4.28/3.31 965/730 55 400/600 74/65 63/54 220 F IP 54 15a
800D6-12-K 30759 30811 30785 30837 400 3~ 2.5/0.5 7.5/2.7 38.0/5.2 4.28/2.17 970/465 55 400/600 74/55 63/44 211 F IP 54 14a
800D6 30754 30806 30780 30832 400 3~ 5.5 13.0 75.4 6.19 950 55 400/600 78 67 231 F IP 54 13a D
400/600 400/600
269
1 2 3 4 5 6
WVA/WVI 800D6 WVA/WVI 800D8 WVA/WVI 800D12 WVA/WVI 1000D6 WVA/WVI 1000D8 WVA/WVI 1000D12
4
2 6 3
Installation examples
Flexible connection EPSN Outer wall Inlet duct SN Air direction Inlet duct SN Outlet duct in Air direction Cooling duct ZHZ Cooling air Supports WBK-W Supports WBK-W
WVA/WVI Art no. WVA F400 Art no. WVA F600 Art no. WVI F400 Art no. WVI F600 Voltage/Frequency Power at shaft Current Starting current Max air flow R.p.m. Max. temp. of transported air Max. temp. of transported air* Sound pressure level 4 m Sound presssure level 10 m Weight Insulation class, motor Enclosure class, motor Wiring diagram p. 391-400 * for 120 min 800D6-8 30755 30807 30781 30833 V/50 Hz 400 3~ kW 5.7/2.4 A 12.3/6.2 A 62.8/21.7 m3/s 6.19/4.72 min-1 960/720 C 55 C 400/600 dB(A) 78/68 dB(A) 67/57 kg 231 F IP 54 15a 800D6-12 30756 30808 30782 30834 400 3~ 5.1/1.0 13.5/4.4 75.0/12.0 6.19/3.06 960/470 55 400/600 78/57 67/46 249 F IP 54 14a 1000D6 30760 30812 30786 30838 400 3~ 11.0 22.0 154 11.1 965 55 400/600 83 72 407 F IP 54 13a D 1000D6-8 30761 30813 30787 30839 400 3~ 11.0/5.0 22.0/15.0 154/82.5 11.1/8.11 970/730 55 400/600 83/75 72/64 472 F IP 54 15a 1000D6-12 30762 30814 30788 30840 400 3~ 12.0/2.4 23.0/7.5 140.0/23.3 11.1/5.42 960/480 55 400/600 83/67 72/56 472 F IP 54 14a
Outer wall
Environment
Environment
WVI
Fire zone
Air direction
270
4-pole
61
6-pole
62
8-pole
dB(A) 4-pole LwA Inlet LwA Outlet 6-pole LwA Inlet LwA Outlet 8-pole LwA Inlet LwA Outlet
Tot 63 125
dB(A) 4-pole
Tot 63 125 60 71
80 87
41 51
56 66
72 79
76 82
74 81
69 78
69 74
58 64
84 92
45 56
Measurement point: 1,25 m/s; 400 Pa 6-pole LwA Inlet LwA Outlet 74 79 35 44 53 60 67 71 70 74 67 73 62 70 64 67 50 55
Measurement point: 0,8 m/s; 150 Pa 8-pole LwA Inlet LwA Outlet 67 72 31 42 48 59 60 65 63 67 60 65 60 64 51 57 38 46
4-pole
6-pole 8-pole
dB(A) 4-pole LwA Inlet LwA Outlet 6-pole LwA Inlet LwA Outlet 8-pole LwA Inlet LwA Outlet
Tot 63 125
dB(A) 4-pole
Tot 63 125
89 97
50 61
65 76
81 89
85 93
83 90
78 88
78 84
67 74
91 98
57 68
75 88
85 92
86 91
83 93
83 88
81 87
62 71
Measurement point: 2,0 m/s; 750 Pa LwA Inlet LwA Outlet 8-pole 82 89 49 60 66 79 77 83 77 83 74 82 73 78 71 77 52 61
271
4-pole
6-pole 8-pole
6-pole
12-pole
dB(A) 4-pole LwA Inlet LwA Outlet 6-pole LwA Inlet LwA Outlet
Tot 63 125
dB(A) 6-pole
Tot 63 125 69 84
97 102
59 68
74 83
89 94
93 98
92 96
87 95
87 91
76 81
85 94
52 65
Measurement point: 3,3 m/s; 350 Pa LwA Inlet LwA Outlet 12-pole LwA Inlet LwA Outlet 69 75 43 55 52 62 63 68 64 69 61 70 61 66 55 56 40 53 79 85 50 63 65 74 73 79 74 79 71 78 72 75 66 70 49 56
6-pole
dB(A)
Tot 63 125 71 79
dB(A) 6-pole
Tot 63 125
6-pole LwA Inlet LwA Outlet 8-pole LwA Inlet LwA Outlet 12-pole LwA Inlet LwA Outlet 70 77 40 49 53 61 63 68 64 71 59 72 67 70 57 64 36 47 81 88 45 58 62 75 74 81 77 83 74 81 74 80 65 73 52 62 92 98 53 63 68 74
LwA Inlet LwA Outlet 8-pole LwA Inlet LwA Outlet 12-pole LwA Inlet LwA Outlet
95 103
62 74
79 93
90 96
90 97
87 96
86 92
84 91
65 75
272
SG Protection guard
MP (4x angle 90) Mounting brackets RSA Silencer EV-AXC Flexible connection AXC
REV (60) on/off switch REV (F) suitable for high temperature
SD (4x)
273
General
PRF . . . . . . . . . . . . . . . . . . . 276 Plastic fan: up to 1.83 m3/s, backward curved impeller, 1 phase and 3 phase.
DVP. . . . . . . . . . . . . . . . . . . 280 Plastic roof fan: up to 2.11 m3/s, backward curved impeller, 1 phase and 3 phase.
274
Installation example
PRF VP Splinter protection
ASSP Flexible connection ASS-P Flexible connection VKA-P Adjustable damper SD Anti vibration mounts
275
REU p. 320
The PRF fans have been developed especially for the exhaust of aggressive media. This is the right fan when corrosive gases, contaminated air or other aggressive components are part of the exhaust air. Typical applications are medical facilities, the food-, electrical- or chemical industry. The sintered casing from UV-resistant PE is absolutely waterproof and offers a variety of applications with its connectors from 125-250 mm. The casing can be easily adjusted through turning it (standard position is LG270, see picture).
RTRE p. 320
REV p. 340
3.000
1 2 3 4 5 6
PRF 125D2 PFR 160D2 PRF 160D4 PRF 160E4 PRF 180D2 PRF 180DV
2.500
PRF 180E4 PRF 200D2 PRF 200DV PRF 250D2 PRF 250D4 PRF 250D2-L
2.000
1.500
1 2 5
6
1.000
6
500
4 3
3 1
0 0 0,2 0,4 0,6 0,8 1 1,2 1,4 1,6 1,8 2,0 2,2
Technical data
PRF Art no. Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 3 m Weight Insulation class, motor Enclosure class, motor Capacitor Motor protection Speed control, five-step Speed control, five-step high/low Speed control, stepless Wiring diagram p. 391-400 125D2 31525 V/50 Hz 400 3~ W 250 A 0.579 m3/s 0.197 min-1 2806 C 70 C 70 dB(A) 59 kg 9 F IP 55 F Transformer Transformer 13b Y 160D2 IE2 33562 400 3~ 750 1.68 0.464 2825 70 70 67 13 F IP 55 FRQ5(S)-4A FRQ(S)-4A 13b Y 160D4 31495 400 3~ 142 0.571 0.228 1467 70 50 14 F IP 55 13b Y 160E4 31545 230 1~ 171 0.75 0.213 1427 70 46 14 F IP 54 6 S-ET 10 RTRE 1.5 REU 1.5 21 180D2 IE2 33563 400 3~ 1100 2.37 0.635 2825 70 70 68 19 F IP 55 FRQ5(S)-4A FRQ(S)-4A 13b Y 180DV 31497 400 3~ 229 1.01 0.32 1365 70 70 49 14 F IP 54 STDT 16 RTRD 2 RTRDU 2 13b D
276
Ventilation accessories
L E
ASS-P p. 285
D
A H
SD-PRF p. 285
N P Q D
PRF 125D2 160D2 160D4/E4 180D2 180E4/DV 200D2 200DV 250D2 250D2-L 250DV
A 140 183 183 208 208 240 240 290 290 290
C 40 40 40 40 40 40 40 40 40 40
D 125 160 160 180 180 200 200 250 250 250
E 150 180 180 190 190 200 200 240 240 240
H 250 310 310 350 350 410 410 495 495 495
N 200 255 255 277 277 320 320 330 330 330
P 100 100 100 120 120 150 150 170 170 170
Q 140 140 140 190 190 230 230 250 250 250
R 235 290 290 320 320 355 355 370 370 370
VKA-P p. 285
VKS-P p. 285
VP p. 285
PRF Art no. Voltage/Frequency Power Current Max air flow R.p.m. Min. back pressure Max temp. of transported air when speed controlled Sound pressure level at 3 m Weight Insulation class, motor Enclosure class, motor Capacitor Motor protection Speed control, five step Speed control, five step high/low Wiring diagram p. 391-400
180E4 31564 V/50 Hz 230 1~ W 140 A 1.11 m3/s 0.32 min-1 1365 Pa C 70 C 70 dB(A) 49 kg 15 F IP 54 F 6 S-ET 10 Transformer RTRE 1.5 Transformer REU 1.5 21
200D2 IE2 33564 400 3~ 1500 3.16 0.937 2840 400 70 70 74 29 F IP 55 13b Y
200DV 31499 400 3~ 250 0.95 0.47 1413 70 70 60 19 F IP 54 STDT 16 RTRD 2 RTRDU 2 13b D
250D2 IE2 33566 400 3~ 4000 7.64 1.83 2890 2000 70 70 95 50 F IP 55 13b D
250D2-L IE2 34531 400 3~ 5500 10.4 1.87 2855 600 70 70 95 60 F IP 54 13b D
277
Tot 63 77 80 66 69 71 48 125 61 68 25
Tot 63 82 87 74 71 73 53 125 73 77 45
PRF 160D4
PRF 160E4
Tot 63 67 70 57 57 58 17 125 59 64 25
Tot 63 67 67 53 63 55 32 125 62 59 40
PRF 180DV
278
PRF 200DV
279
STDT p. 342
The DVP fans have been developed especially for the exhaust of aggressive media. This is the right fan when corrosive gases, contaminated air or other aggressive components are part of the exhaust air. Typical applications are medical facilities, the food-, electrical-or chemical industry. The casing from PP offers a variety of applications with its connectors from 200 - 400 mm. Motor protection by protection switch.
Quick selection
1 2 3 4 5 6
DVP 200D 2-pole DVP 200D 4-pole DVP 250D 2-pole DVP 250D 4-pole DVP 315D 4-pole DVP 315D 8-pole
1 2 3 4
DVP 400D 4-pole DVP 400D 8-pole DVP 400D-L 4-pole DVP 400D-L 8-pole
2 6
Technical data
DVP Art no. Voltage/Frequency Power P2 Current Max air flow R.p.m. Max temp. of transported air Sound pressure level at 4 m/10 m Weight 200D2-4 2-pole 32295 V/50 Hz 400 3~ W 1500 A 3.4 m3/s 0.628 min-1 2885 C 60 dB(A) 62/54 kg 25 F IP 55 14a 400 3~ 370 0.84 0.316 1468 60 43/35 25 F IP 55 14a 200D2-4 4-pole 250D2-4 2-pole 32296 400 3~ 3600 7.7 1.27 2874 60 69/61 35 F IP 55 14a 400 3~ 900 2.0 0.649 1468 60 51/43 35 F IP 55 14a 250D2-4 4-pole 315D4-8 4-pole 32297 400 3~ 2200 4.8 1.28 1494 60 55/47 45 F IP 55 14a 400 3~ 500 1.98 0.647 732 60 40/32 45 F IP 55 14a 315D4-8 8-pole
280
Ventilation accessories
SSD p. 374
FDS p. 374
M
K D
C E
A DVP 200 DVP 250 DVP 315 DVP 400 435 595 665 939
L 30 30 30 30
M 4x10 4x12 4x12 4x14 DVP 200 = SSD/FDS 310/311 DVP 250 = SSD/FDS 355/400 DVP 315 = SSD/FDS 450/500 DVP 400 = SSD/FDS 560/630
DVP Art no. Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air Sound pressure level at 4 m/10 m Weight Insulation class, motor Enclosure class, motor Wiring diagram p. 391-400
400D4-8 4-pole 32299 V/50 Hz 400 3~ W 2000 A 4.8 m3/s 1.31 min-1 1445 C 60 dB(A) 60/52 kg 55 F IP 55 14a
400D4-8-L 4-pole 32298 400 3~ 3600 7.9 2.11 1447 60 61/53 55 F IP 55 14a
281
Tot 63 90 85 71 61 125 74 65
Tot 63 73 66 57 46 125 64 54
Tot 63 82 81 66 70 125 77 75
Tot 63 68 63 55 45 125 65 52
282
Tot 63 98 95 78 83 125 81 80
Tot 63 80 78 60 69 125 73 68
Tot 63 89 87 65 72 125 86 81
Tot 63 73 76 57 62 125 72 75
283
Tot 63 88 86 69 72 125 84 77
Tot 63 78 76 62 63 125 78 75
284
Additional weather protection for the motor, if the fan is outdoor mounted. Manufactured from seawater resistant aluminium. The WSD PRF is painted in RAL 5015.
2xM6
D 60 60 70 70 70 VKS-P 125 160 180 200 250 A 205 240 260 280 330 B 125 160 180 200 250 ASS-P 125 160 180 200 250 A 155 155 155 155 155 B 125 160 180 200 250
VP
VKA-P
SD-PRF
D SW C
A 45 70 F
B 35 50 G 60 90
C 30 45 SW 11 17
D 6 9
E 20 32
M6 M10
B 125 160
285
Centrifugal fans
General
Motors
All fans in this series are equipped with speed controllable external rotor motors. To protect the motor from overheating, the fans have integral thermal contacts with external leads for connection to a motor protection device. The casings are manufactured from galvanised sheet steel.
Centrifugal fans
286
Centrifugal fans
Centrifugal fans
CE . . . . . . . . . . . . . . . . . . . . . 288 Single-inlet centrifugal fan with forward-curved blades: up to 0.8 m/s, 1 phase.
CKS . . . . . . . . . . . . . . . . . . . 296 Centrifugal fans: up to 3.00 m3/s, backward curved impeller, 1-3 phase.
KBR/KBT EC. . . . . . . . . . . . 300 Thermo Box: up to 1.86 m3/s, KBT-EC with forward curved impeller, KBR-EC with backward curved impellers, 1 phase and 3 phase.
120C
KBT/KBR . . . . . . . . . . . . . . . 304 Thermo Box: up to 1.97 m3/s KBT with forward curved, KBR with backward curved impellers, 1 phase and 3 phase.
IE2
2009/640/EG
120C
287
Centrifugal fans
RE p. 320
1 2 3 4 5 6
CE 140 S-125 CE 140 S-160 CE 140 M-125 CE 140 M-160 CE 140 L-125 CE 140 L-160
1 2 3 4
3 2 4 5 6
Technical data
CE Art. no Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 3 m Weight Insulation class, motor Enclosure class, motor Capacitor Motor protection Speed control, five-step Speed control, five-step high/low Speed control, stepless Wiring diagram p. 391-400 CE 140 S-125 1525 V/50 Hz 230 1~ W 104 A 0.45 m3/s 0.11 min-1 1633 C 50 C 50 dB(A) 43 kg 2.7 B IP 44 F 2 Integral Transformer RE 1.5 Transformer REU 1.5 Thyristor REE 1.5 2 CE 140 S-160 1528 230 1~ 105 0.451 0.114 1498 54 54 45 2.7 B IP 44 2 Integral RE 1.5 REU 1.5 REE 1.5 2 CE 140 M-125 1526 230 1~ 121 0.529 0.115 1833 68 68 44 3.1 B IP 44 4 Integral RE 1.5 REU 1.5 REE 1.5 2 CE 140 M-160 1529 230 1~ 125 0.54 0.121 1807 65 65 42 3.1 B IP 44 4 Integral RE 1.5 REU 1.5 REE 1.5 2 CE 140 L-125 1527 230 1~ 147 0.64 0.14 2459 70 70 44 3.5 B IP 44 4 Integral RE 1.5 REU 1.5 REE 1.5 2 CE 140 L-160 1530 230 1~ 153 0.661 0.151 2406 70 70 42 3.5 B IP 44 4 Integral RE 1.5 REU 1.5 REE 1.5 2
288
REE p. 321
Centrifugal fans
VK p. 356
RSK p. 355
CE/CT 200-280
A
LDC p. 348
K E
FFR p. 349
CWK p. 354
Only CE 280-4
VBR p. 365
C 26 25 26 26
D 26 25 26 26
E 4 6 8 50
CE Art. no Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 3 m Weight Insulation class, motor Enclosure class, motor Capacitor Motor protection Speed control, five-step Speed control, five-step high/low Speed control, stepless Wiring diagram p. 391-400
CE 200-4 1577 V/50 Hz 230 1~ W 230 A 1.0 m3/s 0.302 min-1 1202 C 51 C 51 dB(A) 51 kg 8.5 F IP 44 F 6 S-ET 10 Transformer RTRE 1.5 Transformer REU 1.5 Thyristor REE 2 5
CE 225-4 1582 230 1~ 509 2.45 0.489 1301 70 70 61 13 F IP 54 8 S-ET 10 RTRE 3 REU 3 REE 4 6
CE 250-4 1585 230 1~ 836 3.75 0.693 1183 70 70 55 16.7 F IP 54 14 S-ET 10 RTRE 5 REU 5 REE 4 6
CE 280-4 1534 230 1~ 1259 5.96 0.828 1074 59 59 57 21.8 F IP 54 20 S-ET 10 RTRE 7 REU 7 6
289
Centrifugal fans
Q [m3/s]
dB(A) CE 140 S-125 LwA Inlet LwA Outlet LwA Surrounding CE 140 M-125 LwA Inlet LwA Outlet LwA Surrounding CE 140 L-125 LwA Inlet LwA Outlet LwA Surrounding
Tot 63 70 70 50 49 49 7 125 65 65 38
dB(A) CE 140 S-160 45 48 37 LwA Inlet LwA Outlet LwA Surrounding CE 140 M-160
Tot 63 69 69 52 49 50 39 125 64 64 37
71 71 49
50 50 26
67 66 32
67 66 41
62 63 43
60 63 45
58 59 38
56 54 35
50 51 29
Measurement point: 0,076 m/s; 267 Pa LwA Inlet LwA Outlet LwA Surrounding 73 73 49 56 53 27 66 65 37 69 69 35 64 66 43 62 65 44 60 63 41 59 58 38 53 56 35
290
Centrifugal fans
dB(A) CE 200-4 LwA Inlet LwA Outlet LwA Surrounding CE 225-4 LwA Inlet LwA Outlet LwA Surrounding
Tot 63 68 69 58 51 44 47 125 52 45 43
Tot 63 73 76 62 51 49 45 125 58 53 50
Measurement point: 0,338 m/s; 332 Pa LwA Inlet LwA Outlet LwA Surrounding 78 80 64 52 50 40 66 60 50 70 66 60 66 72 52 72 75 57 72 73 56 69 73 53 64 66 41
291
Centrifugal fans
CT fans are easy to install. Fans in this series have impellers with forward-curved blades and external rotor motors. The casing is manufactured from galvanised sheet steel. To protect the motor from overheating, the fans have integral thermal contacts with external leads for connection to a motor protection device. CT 200 fans are electrically connected via a junction box. CT 225 450 fans electrical cable is directly connected to the motor without junction box.
RTRDU p. 321
STDT p. 342
Quick selection
1 2 3 4 5 6 7
1 2 3 4 5 6 7
7 4 3 1 5 2 7 4 6 2 1 6 3
Technical data
CT Art. no Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 3 m Weight Insulation class, motor Enclosure class, motor Motor protection Speed control, five-step Speed control, five-step high/low Wiring diagram p. 391-400 200-4 1579 V/50 Hz 400 3~ W 310 A 0.551 m3/s 0.392 min-1 1304 C 61 C 61 dB(A) 44 kg 8.5 B IP 44 STDT 16 Transformer RTRD 2 Transformer RTRDU 2 7 225-4 1583 400 3~ 504 0.892 0.534 1319 70 56 53 11.5 F IP 54 STDT 16 RTRD 2 RTRDU 2 8 225-6 1581 400 3~ 198 0.42 0.386 857 70 70 45 10.6 F IP 54 STDT 16 RTRD 2 RTRDU 2 8 250-4 1574 400 3~ 788 1.4 0.68 1266 60 60 60 14.5 F IP 54 STDT 16 RTRD 2 RTRDU 2 8 250-6 1584 400 3~ 297 0.624 0.5 832 55 55 51 12.3 F IP 54 STDT 16 RTRD 2 RTRDU 2 8 280-4 1586 400 3~ 1333 2.35 0.906 1307 70 70 59 22.5 F IP 54 STDT 16 RTRD 4 RTRDU 4 8 280-6 1575 400 3~ 407 0.863 0.587 825 60 60 45 16 F IP 54 STDT 16 RTRD 2 RTRDU 2 8
292
Centrifugal fans
Ventilation accessories
VK p. 356
K E
RSK p. 355
LDR p. 358
A CT 200-4 CT 225-4 CT 225-6 CT 250-4 CT 250-6 CT 280-4 CT 280-6 CT 315-4/6 CT 355-4 CT 355-6 CT 400-4/6 CT 450-6 404 445 445 492 492 547 547 615 689 689 768 859
B 250 280 280 315 315 357 357 400 450 450 500 560
C 26 25 25 26 26 26 26 26 26 26 26 26
D 26 25 25 26 26 26 26 26 26 26 26 26
E 4 6 40 8 42 50 46 58 70 53 72 76
F 132 147 147 167 167 182 182 203 227 227 252 283
G 183 198 198 218 218 233 233 254 278 278 304 335
H 332 369 369 412 412 455 455 517 574 574 643 721
J 187 211 211 239 239 257 257 298 325 325 365 412
K 164 180 180 198 198 221 221 247 287 287 310 348
L 186 234 234 261 261 293 293 326 367 367 413 463
FFR p. 349
CWK p. 354
VBR p. 365
CT Art. no Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 3 m Weight Insulation class, motor Enclosure class, motor Motor protection Speed control, five-step Speed control, five-step high/low Wiring diagram p. 391-400
315-4 1587 V/50 Hz 400 3~ W 2365 A 3.95 m3/s 1.21 min-1 1233 C 40 C 40 dB(A) 65 kg 28.4 F IP 54 STDT 16 Transformer RTRD 7 Transformer RTRDU 7 8
315-6 1576 400 3~ 843 1.69 0.98 782 55 55 55 22.6 F IP 54 STDT 16 RTRD 2 RTRDU 2 8
355-4 1589 400 3~ 3716 6.16 1.73 1291 70 70 63 42.4 F IP 54 STDT 16 RTRD 7 RTRDU 7 8
355-6 1588 400 3~ 1538 2.88 1.45 818 70 70 56 31 F IP 54 STDT 16 RTRD 4 RTRDU 4 8
400-4 1536 400 3~ 4984 8.12 2.01 1312 70 70 70 54.9 F IP 54 STDT 16 RTRD 14 8
400-6 1591 400 3~ 2624 4.84 2.07 843 70 70 58 51 F IP 54 STDT 16 RTRD 7 RTRDU 7 8
450-6 1593 400 3~ 3821 6.76 2.56 842 59 59 61 59.8 F IP 54 STDT 16 RTRD 7 RTRDU 7 8
293
Centrifugal fans
dB(A) CT 200-4 LwA Inlet LwA Outlet LwA Surrounding CT 225-4 LwA Inlet LwA Outlet LwA Surrounding
Tot 63 67 69 51 44 44 37 125 50 46 31
Tot 63 62 64 51 38 39 34 125 45 39 35
Measurement point: 0,194 m/s; 125 Pa LwA Inlet LwA Outlet LwA Surrounding 64 67 58 41 41 46 46 41 33 54 54 42 55 62 50 58 60 53 58 59 53 55 58 47 47 49 35
dB(A) CT 250-4 LwA Inlet LwA Outlet LwA Surrounding CT 280-4 LwA Inlet LwA Outlet LwA Surrounding
Tot 63 75 77 67 51 50 53 125 57 52 43
Tot 63 67 70 52 44 42 41 125 51 46 31
71 72 62
49 47 38
57 52 37
59 60 48
63 68 57
66 65 57
64 64 53
63 64 50
56 55 41
294
Centrifugal fans
dB(A) CT 315-4 LwA Inlet LwA Outlet LwA Surrounding CT 355-4 LwA Inlet LwA Outlet LwA Surrounding CT 400-4 LwA Inlet LwA Outlet LwA Surrounding
Tot 63 81 83 72 59 56 51 125 68 64 49
Tot 63 75 79 63 52 63 39 125 59 63 42
Measurement point: 0,688 m/s; 355 Pa LwA Inlet LwA Outlet LwA Surrounding CT 450-6 79 81 65 56 51 40 63 60 43 62 67 48 75 76 60 73 75 60 72 74 58 69 72 49 65 66 42
Measurement point: 1,0 m/s; 442 Pa LwA Inlet LwA Outlet LwA Surrounding 81 85 67 60 55 39 66 64 49 64 70 51 77 80 64 75 79 63 74 78 59 70 74 48 67 69 45
295
Centrifugal fans
Swing-out cover for easy cleaning and servicing. Maintenance- free and reliable. CKS fans are easy to install. Fans in this series have impellers with backward-curved blades and external rotor motors. The casing is manufactured from galvanised sheet steel. To protect the motor from overheating, the fans have integral thermal contacts with external leads for connection to a motor protection device.
RTRE p. 320
1 2 3
1 2 3
REE p. 321
RTRD/RTRDU p. 321
STDT p. 342
Technical data
CKS Art. no Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 3 m Weight Insulation class, motor Enclosure class, motor Capacitor Motor protection Speed control, five-step Speed control, five-step high/low Speed control, stepless Wiring diagram p. 391-400 355-1 1518 V/50 Hz 230 1~ W 410 A 1.96 m3/s 0.868 min-1 1356 C 70 C 70 dB(A) 54 kg 26.4 F IP 54 F 8 S-ET 10 Transformer RTRE 3 Transformer REU 3 Thyrisor REE 4 6 355-3 1519 400 3~ 353 0.73 0.856 1380 70 70 50 25.2 F IP 54 STDT 16 RTRD 2 RTRDU 2 8 400-1 1520 230 1~ 611 2.77 1.18 1314 70 70 56 33 F IP 54 14 S-ET 10 RTRE 3 REU 3 REE 4 6 400-3 1521 400 3~ 687 1.6 1.27 1404 70 70 48 32.6 F IP 54 STDT 16 RTRD 2 RTRDU 2 8 450-3 1522 400 3~ 1048 1.88 1.75 1333 70 68 60 43.6 F IP 54 STDT 16 RTRD 4 RTRDU 4 8 500-3 1523 400 3~ 1726 3.34 2.32 1393 66 62 65 60.6 F IP 54 STDT 16 RTRD 4 RTRDU 4 8 560-3 1524 400 3~ 2801 4.86 2.98 1360 70 70 68 74.1 F IP 54 STDT 16 RTRD 7 RTRDU 7 8
296
Centrifugal fans
G B
ISE p. 371
LDC p. 348
K F
USE p. 371
C 283 317 355 393 440 D 243 266 294 317 342 E 193 216 244 267 292 F 590 658 734 810 900 G 530 530 650 650 650 H 668 748 837 926 J 196 219 247 270 K 250 283 312 343 380 L 329 370 415 469 515
1033 295
297
Centrifugal fans
dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 355-900 LwA Inlet LwA Outlet
Tot 63 71 72 61 62 63 45 46 32 45 46 125 60 58 46 57 55
dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 355-900 LwA Inlet LwA Outlet
Tot 63 69 73 57 61 64 44 44 25 44 44 125 58 57 41 55 54
dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 400-900 LwA Inlet LwA Outlet
Tot 63 72 76 63 66 69 49 45 38 48 44 125 63 65 47 60 62
dB(A) LwA Inlet LwA Outlet LwA Surrounding With LDC 400-900 LwA Inlet LwA Outlet
Tot 63 71 77 55 64 70 41 48 15 40 47 125 60 61 37 57 58
298
Centrifugal fans
Tot 63 72 79 67 42 51 28 125 62 64 48
Tot 63 82 87 72 55 56 33 125 69 68 56
Tot 63 86 89 75 61 65 37 125 72 72 58
299
Centrifugal fans
MTP 10 p. 341
120C
EC technology is intelligent technology; using integral electronic control which eliminates the slip losses in the motor and ensures that the motor always runs at optimal load and guarantees that the proportion of energy utilized effectively is many times higher and the energy usage considerably lower compared with AC motors. EC fans are notable for their economical use of energy and excellent ease of control. They can be varied in speed to match the airflow demand, and operate at high efficiency levels. For the same air volume, they consume distinctly less energy than AC fan drives. Another special feature of EC fans is their energy-saving potential not only at full load, but especially at part-load. When operating at partload, the energy used is much lower than with an asynchronous motor of equivalent output. Reduced energy usage guarantees a drop in operating costs. The power electronics are integrated in the motor housing. All models have one potential-free terminal for error message. All motors are suitable to be used for 50/60Hz. The input voltage for single phase units can vary between 200 and 277V. Speed control by a 0-10V signal. Every motor has an output voltage of 10V for an external potentiometer or sensor. The KBR-EC fans have impellers manufactured from aluminium with backward-curved blades. The casing is manufactured from double-skinned galvanized sheet steel and is insulated with 50 mm mineral wool. The KBR-EC fans have a swing-out door for easy inspection and service. The direction of the door opening can easily be changed from left to right at site. The fan is isolated from the casing via connectors and anti-vibration dampers are incorporated into the base frame.
MTV 1 p. 341
REV p. 340
EC-Vent p. 329-330
Technical data
KBR-EC KBT-EC Art. no Voltage/Frequency Fan power consumption (P1) Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 4/10 m Weight Insulation class, motor Enclosure class, motor Speed control, stepless Wiring diagram p. 391-400 33396 V/50/60 Hz 230 1~ W 107 A 0.502 m3/s 0.426 min-1 1512 C 120 C 120 dB(A) 31/23 kg 47 F IP 55 MTP 10 46 33397 230 1~ 173 0.771 0.579 1512 120 120 34/26 75 F IP 55 MTP 10 46 33653 230 1~ 1268 5.53 1.12 3025 120 120 49/41 75 F IP 55 MTP 10 48 33400 230 1~ 498 2.17 0.997 1495 120 120 39/31 81 F IP 55 MTP 10 48 33398 230 1~ 296 1.3 0.822 1514 120 120 39/31 81 F IP 55 MTP 10 46 33665 400 3~ 2567 3.92 1.86 2610 120 120 52/44 83 F IP 55 MTP 10 47 280 315 315-L 355 355-K 355-L 200 33231 230 1~ 535 2.43 0.554 1498 70 70 36/28 35.6 F IP 55 MTP 10 48 250 33259 400 3~ 1252 2.01 0.925 1370 120 120 37/29 52.5 F IP 55 MTP 10 47
300
Centrifugal fans
Ventilation accessories
ALS-KBT p. 371
33
50
50
ASF/KB p. 371
38
WBK p. 389
KBR-EC 280 315 355 A 171.5 187.5 206.7 B 537 600 655 C 295 339 372 D 360 398 451 E 625 690 770 G 280 315 355 H 234 249 273 J 291 307 331 L 600 800 770
35
E 38
KBT-EC 200
G
A 142.7 160
B 445 500
50
50
C 249 285
D 292 333
E 510 576
F 130 130
G 200 250
H 174 213
J 232 272
K 78 78
L 450 600
M 35 35
250
Quick selection
9748, 9771, 10701, 10699, 10707, 9749
1 2 3 4 5 6
KBR 280 EC KBR 315 EC KBR 315 EC-L KBR 355 EC KBR 355 EC-K KBR 355EC-L
1 2
8361, 8453
301
Centrifugal fans
KBR 280EC
KBR 315EC
Tot 63 63 64 53 31 34 28 125 45 47 41
Tot 63 69 70 49 46 46 16 125 58 58 39
KBR 315EC-L
KBR 355EC
Tot 63 87 90 61 63 64 42 125 74 72 54
Tot 63 74 76 54 55 60 26 125 65 65 42
302
Centrifugal fans
KBR 355EC-K
KBR 355EC-L
Tot 63 71 71 47 60 56 31 125 62 59 35
Tot 63 90 92 72 125 88 90 70
KBT 200EC
KBT 250EC
Tot 63 75 77 59 60 63 26 125 59 69 23
Tot 63 78 80 60 51 58 12 125 68 68 45
303
Centrifugal fans
IE2
2009/640/EG
120C
The fans have impellers manufactured from galvanised sheet steel, KBT with forward-curved blades, KBR with backward-curved blades. The casing is manufactured from double-skinned galvanised sheet steel and is insulated with 50 mm mineral wool. KBT/KBR fans have a swing-out door for easy inspection and service. The direction of the door opening can easily be changed from left to right at site. The fan is isolated from the casing via connectors and antivibration dampers are incorporated into the base frame. To protect the motors from overheating the fans have integral thermal contacts with external leads for connection to a motor protection device.
RTRD p. 321
RTRDU p. 321
1 2 3 4 5
KBT 160DV KBT 160E4 KBT 180E4 KBT 200DV KBT 200E4
6 7 8 9 10
KBT 225D4 IE2 KBT 225E4 KBT 250D4 IE2 KBT 250E4 KBT 280D4 IE2
5201, 5196, 5211, 5239, 6599, 9774, 5246, 9773, 5274, 9769
1 2
3 4 5 6 7 8
KBR 355DV KBR 355DV/K KBR 355D2 IE2 KBR 355D2/K IE2 KBR 355E4 KBR 355E4/K
STDT p. 342
1 4 5 6 7 9 8 10
3 3 1 8 4 7
FRQ p. 325
Technical data
KBT Art no. Voltage/Frequency Power at shaft Current Max air flow R.p.m. Max temp. of transported air Sound pressure level at 4/10 m Weight Insulation class, motor Enclosure class, motor Capacitor Motor protection Speed control, five step Speed control, five step high/low Speed control, D/Y two step 400V Speed control, stepless Wiring diagram p. 391-400 *+ S-ET 10 160DV 5823 V/50 Hz 400 3~ kW 0.16 A 0.57 m3/s 0.248 min-1 1120 C 120 dB(A) 31/23 kg 24 F IP 54 F STDT 16 RTRD 2 RTRDU 2 S-DT2 FXDM 17 160E4 5976 230 1~ 0.14 1.1 0.231 1476 120 31/23 25 F IP 54 6 S-ET 10 RTRE 1.5 REU 1.5* 21 180E4 5824 230 1~ 0.14 1.11 0.345 1490 120 34/26 29 F IP 54 6 S-ET 10 RTRE 1.5 REU 1.5* 21 200DV 5825 400 3~ 0.55 1.88 0.583 1360 120 37/29 35.6 F IP 54 STDT 16 RTRD 2 RTRDU 2 S-DT2 FXDM 17 200E4 5826 230 1~ 0.75 5.1 0.541 1370 120 37/29 40.2 F IP 54 30 S-ET 10 RTRE 7 REU 7* 21 225D4 IE2 33556 400 3~ 0.75 1.78 0.747 1390 120 39/31 40.3 F IP 55 U-EK 230E FRQ5(S)-4A FRQ(S)-4A 13b Y 225E4 5828 230 1~ 0.88 5.5 0.653 1417 120 38/30 43 F IP 54 30 S-ET 10 RTRE 7 REU 7* 21 250D4 IE2 33557 400 3~ 1.5 3.39 1.2 1400 120 44/36 52.5 F IP 55 U-EK 230E FRQ5(S)-4A FRQ(S)-4A 13b Y 250E4 5830 230 1~ 1.84 10.5 1.08 1400 120 45/37 52 F IP 54 50 S-ET 10 RTRE 12 21 280D4 IE2 33558 400 3~ 2.2 4.64 1.41w 1420 120 47/39 63 F IP 55 U-EK 230E FRQ5(S)-10A FRQ(S)-10A 13b Y
304
Centrifugal fans
FK p. 355
LDC p. 348
L
RSK p. 355
SG p. 357
KBT 160 180 200 225 250 280 KBR 315 355
WSD-KBT p. 371
187.5 206.7
600 655
339 372
398 451
690 770
315 355
249 273
307 331
800 770
KBR Art no. Voltage/Frequency Power at shaft Current Max air flow R.p.m. Max temp. of transported air Sound pressure level at 4/10 m Weight Insulation class, motor Enclosure class, motor Capacitor Motor protection Speed control, five step Speed control, five step high/low Speed control, D/Y two step 400V Speed control, stepless Wiring diagram p. 391-400 * + S-ET 10
315DV 5833 V/50 Hz 400 3~ kW 0.37 A 1.39 m3/s 0.611 min-1 1360 C 120 dB(A) 36/28 kg 75 F IP 54 F STDT 16 RTRD 2 RTRDU 2 S-DT2 FXDM 17
315D2 IE2 33559 400 3~ 1.5 3.16 1.14 2840 120 50/42 67.1 F IP 55 U-EK 230E FRQ5(S)-4A FRQ(S)-4A 13b Y
355DV 5835 400 3~ 0.37 1.39 1.06 1360 120 41/33 81 F IP 54 STDT 16 RTRD 2 RTRDU 2 S-DT2 FXDM 17
355DV/K 5977 400 3~ 0.37 1.39 0.82 1434 120 41/33 81 F IP 54 STDT 16 RTRD 2 RTRDU 2 S-DT2 FXDM 17
355D2 IE2 33560 400 3~ 3.0 5.86 1.97 2890 120 53/45 83.3 F IP 55 U-EK 230E FRQ5(S)-10A FRQ5(S)-10A 13b Y
355D2/K IE2 33561 400 3~ 2.2 4.48 1.53 2880 120 53/45 78.3 F IP 55 U-EK 230E FRQ5(S)-10A FRQ5(S)-10A 13b Y
355E4 5980 230 1~ 0.37 2.1 0.972 1330 120 41/33 70.1 F IP 54 12 S-ET 10 RTRE 3 REU 3* 21
355E4/K 5978 230 1~ 0.37 2.1 0.778 1330 120 41/33 80 F IP 54 12 S-ET 10 RTRE 3 REU 3* 21
305
Centrifugal fans
Tot 63 72 74 54 125 70 72 52
Tot 63 72 74 54 125 70 72 52
Tot 63 75 77 125 73 75 55
Tot 63 78 80 60 125 76 78 58
LwA Surrounding 57
306
Centrifugal fans
Tot 63 78 80 60 125 76 78 58
Tot 63 81 83 63 125 79 81 61
Tot 63 82 84 64 125 80 82 62
Tot 63 85 87 67 125 83 85 65
307
Centrifugal fans
Tot 63
86 88
dB(A) 4k
67 69
Tot 63 125 86 88 68 88 90 70 -
250
80 82
500
77 79
1k
73 75
2k
71 73
8k
63 65
68
66
62
59
55
53
49
45
Tot 63 77 79 59 125 75 77 57
Tot 63 91 93 73 125 89 31 71
308
Centrifugal fans
Tot 63 82 84 64 125 80 82 62
Tot 63 82 84 64 125 80 82 62
Tot 63 94 96 76 125 92 94 74
Tot 63 94 96 76 125 92 94 74
309
Centrifugal fans
Tot 63 82 84 64 125 80 82 62
Tot 63 80 82 62 125 78 80 60
310
Centrifugal fans
311
Domestic fans
Domestic fans
General
Domestic fans for the ventilation of bathrooms,toilets and storage rooms. Can be wall or window mounted and in some cases duct mounted.
312
Domestic fans
BF-W. . . . . . . . . . . . . . . . . . 314 Fans for bathrooms, toilets and store rooms, up to 0.06 m3/s.
Domestic fans
IF. . . . . . . . . . . . . . . . . . . . . 316 Fans for bathrooms, toilets and store rooms. 0,03 m3/s.
BF . . . . . . . . . . . . . . . . . . . . 316 Fans for bathrooms, toilets and shower rooms, up to 0.07 m3/s.
CBF . . . . . . . . . . . . . . . . . . . 316 Window or wall mounted fans for bathrooms, toilets and store rooms, up to 0.19 m3/s.
313
BVK p. 390
Domestic fans
BF-W 230A
BDS p. 390
BF-W 120A
BF-W
C 30 32 23 25 29
tECHNICAL DATA
BF-W Art no. Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 3 m Weight Insulation class, motor Enclosure class, motor Capacitor 100A 7200 V/50 Hz 230 1~ W 14.8 A 0.0899 m3/s 0.0191 min-1 2468 C 70 C 70 dB(A) 45 kg 1 B IP 44 F 120A 7202 230 1~ 13.9 0.0899 0.023 2198 57.4 57.4 48 1.2 B IP 44 150A 7204 230 1~ 30.8 0.19 0.0641 2253 63.9 63.9 54 1.5 B IP 44 230A 7206 230 1~ 41.7 0.197 0.124 1155 61.1 61.1 53 3.1 B IP 44 2 300A 7219 230 1~ 70.8 0.32 0.192 1035 70 70 55 5.2 B IP 44 3.15
314
Domestic fans
performance
BF-W 100 BF-W 120
Domestic fans
Tot 63 52 59 12 40 125 42 54
Tot 63 55 62 18 42 125 48 57
BF-W 150
BF-W 230
Tot 63 60 66 17 42 125 50 59
Tot 63 60 61 37 37 125 47 47
BF-W 300
Tot 63 65 66 55 54 125 59 61
315
Domestic fans
B 98 118 150
C 60 40 81
IF
IF in-line axial fan, suitable for bathrooms, toilets and shower rooms. The IF series are in-line extractor fans designed for the safe ventilation of bathrooms, toilets and shower rooms. Manufactured from high impact ABS thermoplastic. The series comprises of a fan unit only and is suitable for boosting a BF fan where a longer run of ducting is used. The IF fans have single-phase induction motors with sealed for life bearings.
IF
B 90 99 110
tECHNICAL DATA
BF 100 Art no. standard Art no BF + timer Art no + timer and humidity sensor Voltage/Frequency Power Current Max air flow R.p.m. Max temp. of transported air when speed controlled Sound pressure level at 3 m Weight Insulation class, motor Enclosure class, motor
3
BF 120 5951 5954 5957 230 1~ 13.9 0.09 0.023 2198 57.4 57.4 48 0.8 B IP 44
BF 150 5952 5955 5958 230 1~ 30.8 0.19 0.0641 2253 63.9 63.9 54 1.0 B IP 54
CBF 100L 5959 5960 5961 230 1~ 29.1 0.19 0.0291 2403 57.3 57.3 52 1.2 B IP 54
5950 5953 5956 V/50 Hz 230 1~ W 14.8 A 0.09 m /s 0.0191 min-1 2468 C 70 C 70 dB(A) 45 kg 0.7 B IP 44
316
Domestic fans
BF 100
BF 120
Domestic fans
Tot 63 52 59 12 40 125 42 54
Tot 63 55 62 18 42 125 48 57
BF 150
Tot 63 60 66 17 42 125 50 59
CBF 100L
IF
15
IF
12
IF 0 10
Tot 63 59 61 17 40 125 40 54
Tot 63 55 62 18 42 125 48 57
317
Electrical accessories
Electrical accessories
Motor protection
Electrical actuators
318
Electrical accessories
Electrical actuators
RVAZ4-24. . . . . . . . . . . . . . . 339 RVAZ4-24A . . . . . . . . . . . . . . 339 SF 24A . . . . . . . . . . . . . . . . . . 344 SF 24A-S2. . . . . . . . . . . . . . . 344 SF 24A-SR. . . . . . . . . . . . . . . 344 SF 230A. . . . . . . . . . . . . . . . . 344 SM 230A. . . . . . . . . . . . . . . . 344
Motor protection
AWE-SK. . . . . . . . . . . . . . . . . 342 MSEX. . . . . . . . . . . . . . . . . . . 342 S-ET 10, S-ET 10E. . . . . . . . . 341 STDT 16, STDT 16E. . . . . . . . 342 U-EK 230E EX. . . . . . . . . . . . 338
Electrical accessories
Heat controls
AQUA 24TF. . . . . . . . . . . . . . 341 Pulser . . . . . . . . . . . . . . . . . . 334 Pulser M. . . . . . . . . . . . . . . . 334 TTC . . . . . . . . . . . . . . . . . . . . . 335 TT-S1. . . . . . . . . . . . . . . . . . . 335 TT-S4/D. . . . . . . . . . . . . . . . . 336
319
Electrical accessories RE
Manual five-step transformer
RTRE
REU
Electrical accessories
A single-phase transformer which controls the fan speed by altering the supply voltage in five fixed steps. The steps are adjusted manually, using the control knob on the front of the unit. The transformer has 230V terminals for operating dampers, electric heater batteries or other external equipment. When the transformer knob is in position 0, the outlet has no current. The indicator lamp on the front shows that the transformer is in operation. The fuse may be reset from outside. The RE has a self extinguishing thermoplastic casing. NOTE! Fans with external contact leads (TK) must always be connected to a motor protection device.
Output voltages for each of the 5 steps: Step Voltage 1 80 2 105 3 130 4 160 5 230
RE 1.5 3 5 7
Current 1.5 3 5 7
Enclosure 54 54 54 54
REU 1.5 3 5 7
Current 1.5 3 5 7
Enclosure IP 54 IP 54 IP 54 IP 54
RTRE 1.5 3 RE 1.5 3 5 7 Width 105 105 105 147 Height 200 200 200 257 Depth 105 105 105 145 Weight, kg 1.5 2.5 4.1 7.5 RTRE 1.5 3 5 7 12
Transmisson Supply voltage Earth Fan
Current 1.5 3 5 7 12
Enclosure IP 54 IP 54 IP 54 IP 54 IP 54 REU 1.5 3 5 7 Width 105 105 105 105 Height 200 275 275 275 Depth 105 145 145 145 Weight, kg 2.0 4.05 4.9 7.05
5 7 12
Transmisson: between ~ and N is always 230V when the transformer handle is in pos. 1-5
Earth
Fan
Thermostat
Motor protection
Transmisson
Supply voltage
Earth
Fan
Thermostat
Motor protection
320
RTRDU
REE
- only surface mounting For the manual control of speed and air flow of electrical fans, AC-induction motors of universal motorand permanent-capacitor type. The jetproof IP 54 enclosure is achieved with the included surface mounting case. (Flushmounting without the surfase mounting case, gives a splash proof IP 44 enclosure also suitable for highly demanding enviroments as bathrooms etc.) Several motors can be connected in parallel as long as the total current does not exceed current range. Starting currents must be considered when choosing speed controller type. Fans to be used with this controller require a built-in overheating protection and should be designed for thyristor speed control.
Electrical accessories
REE 1 Voltage Frequency Current Fuse Enclosure WxHxD V 230 ~ Hz 50 A 0.1-1.0 A 1.25 IP 54 kg 0.25
Output voltages for each of the 5 steps: Step Voltage RTRD 2 3 4 5.2 7 14 RTRD 2 3 4 5.2 7 14 Width 240 270 270 270 270 450 1 95 2 145 Current 2 3 4 5.2 7 14 Height 284 323 323 323 323 290 Depth 132 172 173 172 172 174 3 190 4 240 5 400
Output voltages for each of the 5 steps: Step Voltage RTRDU 2 4 7 RTRDU 2 4 7 Width 270 270 270 1 95 2 145 Current 2 4 7 Height 323 323 323 Depth 163 163 163 3 190 4 240 5 400
Weight
Line L state connection with cutting function on the speed control. Broken line (L) state connection without cutting function.
321
REE S0
Stepless phase cutting contoller for 1~230V/50Hz motors. It has a connection for an external control signal 0...10V or 4...20mA. The control signal can be choosen by an internal switch. Internal potentiometer to set a min speed. On/off switch with control lamp. White plastic casing IP54. Several motors can be connected in parallel as long as the total current does not exceed the current range. Fans to be used with this controller require a build-in overheating protection and should be designed for thyristor speed control. NOTE: phase cutting controller can cause electrical noise interference!
REE Voltage Current Fuse Enclosure V A A IP 030S0 230 ~ 0.3-3.0 FF4 54 050S0 230~ 0.5-5.0 FF8 54 100S0 230~ 1.0-10.0 FF14 54
V. min ADJUST
0-10VDC 4-20mA
Electrical accessories
Control signal
0...10VDC/4...20mA
L1
FT
FT
TK
TK
U1
N Pe
Alarm out
T
L1-N: Input to bypass the on/off contact 230 V non-controlled output FT-FT Connection for thermostat, timer, frostprotection, on/off-switch at a distance N-A Alarm output in case of motor fault 230 VAC, 2A TK-TK Input thermal contacts of the motor
L Pe
L1
+ 0-10VDC 4-20mA
Analog Out 1
Digital In 1
Digital In 3
Digital In 2
Digital In 4
Digital In 5 31 32
Analog In TF..1
Analog In TF..2
Universal module with timer function. Controlled 0-10 V output e.g. for electronic speed controllers of fans. Applications: Pressure control, outdoor temperature control, outdoor temperature compensated pressure control, etc.
CXE/AVC Voltage Frequency Phase Output 0-10 V, Imax Enclosure class Weight Dimensions V 230 Hz 50/60 ~ 1 mA 10 IP 54 kg 1.3 mm 213x185x102
Analog Out 2
Regulator
CXE/AVC
Unicon CXE/AVC(E)
GND DD+ B A
7 PE N L1 1 2 K1 3 4 5 K2 + 6 8
9 10
11 12
13 14
15 16
17 18
19 20
21 22
23 24
25 26
27 28
29 30
+ 24 V DC 24 V DC Out Out + Input TF..(KTY) E2 + + Input 4...20 mA (0...20 mA) E2 Eingang Input 0...10 V E2
Data Data GND
PE N
L1
Input TF..(KTY) E1
+ RS-485
+ Input 0...10 V E1
MCRE09K4 22.04.2009
322
T2
T1
12
11
14
RT 1*
RT
L1
L2
L3
250 V AC max. 2 A
230 V AC max. 1 A
230 V AC
PE
0 1
L1
L2
L3
U V M 3~
TP TP
PE
3 ~ 400 V 50/60 Hz
Y/
Electrical accessories
SR171K13 27.11.2007
On/off
R-DK4 KT Voltage Frequency Current Max. ambient temp. Enclosure WxHxD Weight V 400 3~ Hz 50/60 A 4.0 C 40 IP 21 mm 270x323x163 kg 11.5
CXE/AV
CXE/AV
Switch or jumper
C mA V C V 24 V DC mA C V E1 E1 mA 11 14 K1 12 21 24 K2 22
Universal regulator
Digital Analog A1 A2 Analog
Regulator with multifunction display constant temperature or constant pressure in duct systems with 0...10V output signal to control external devices (power units, frequency inverters, EC-motors etc.). Two setpoints are possible. 3 digital inputs, 2 analogue inputs, 2 analogue outputs 0...10V and 2 relays with changeover contact. All in-/outputs are programable. With preprogram modes also for outdoor compensation for easy setup. Menu languages are English, German, Swedish,... 24VAC/ Imax 70mA power supply for sensors.
Out
In 1/2/3
24V D1 D2 D3
Out 1/2
GND GND
In 1/2
E1 E2
E2
E2
D+ L1 (+) N (-) PE D-
24V GND
Line
+
Data Data 24 V GND
+ RS-485
Output
0...10 V (Imax = 10 mA)
Input
0...10 V 0...20 mA 4...20 mA TF..(KTY)
CXE/AVC Voltage Frequency Phase Output 0-10 V, Imax Switching capacity Ambient temp. Enclosure class Weight Dimensions V 230 Hz 50/60 ~ 1 mA 10 5A/250VAC C 0...40 IP 54 kg 0.9 mm 166x160x87
Output
0...10 V (Imax = 10 mA)
Input
0...10 V 0...20 mA 4...20 mA TF..(KTY)
323
PXDM5A
Electrical accessories
Frequency inverter with integrated allpole sine filter. Frequency regulator with multifunction display for constant temperature or constant pressure in duct systems with integrated process controller (PID free programmable) or with 0...10V control signal. Two setpoints or manual mode is possible. 2 digital inputs, 2 analogue inputs, 1 analogue output 0...10V and 2 relays with change-over contact. All inputs and outputs are programmable. Total motor protection using thermocontact/ thermistor connection. Menu languages are English, German, Swedish,... +24VAC/Imax 120mA power supply for sensors. Masking up to three settable speed ranges. Min. and max. speed limitation. Integrated allpole sine filter for external rotor motors. NB! Absolute parallel operation of fans, no risk of damage to motor. Screened motor cables are not required! Wiring diagram on page 326.
Internal display
Universal regulator, three phase. Regulator with multifunction display constant temperature or constant pressure in duct systems for 3~400V motors. Connection for thermal contacts. Two setpoints are possible. 2 digital inputs, 2 analogue inputs, 1 analogue output 0...10V and 2 relays with change-over contact. All in-/outputs are programmable. With preprogram modes also for outdoor compensation for easy setup. Menu languages are English, German, Swedish,... 24VDC/Imax 70mA power supply for sensors. Permitted relative humidity, non condensating 85%. Wiring on page 326.
PKDM12
PXDM5A Voltage Phase Frequency Current Recommended fuse Output voltage approx. Max. power dissipation Perm. ambient temp. Enclosure class Weight WxHxD V 400 ~ 3 Hz 50/60 A 5 A 10 % 20...100 W 40 C 0...40 IP 54 kg 2.9 mm 240x284x131
PKDM12 Voltage Phase Frequency Current Min. motor current Output voltage appr. Max. power dissipation Control signal Recom. fuse Ambient temperature Enclosure class Weight WxHxD V 208...415 ~ 3 Hz 50/60 A 12 A 0,2 % 0...100 W 55 0...10V/4...20mA A FF30A 10x38mm C 40 IP 54 kg 3.4 mm 270x323x146
FXDM Voltage Phase Frequency Max. current Recom.fuse Ambient temp. Enclosure Weight Width Height Depth
FXDM Voltage Phase Frequency Max. current Recom.fuse Ambient temp. Enclosure Weight Width Height Depth
324
FRQ(5)S
Speed controller with 0-10V(or 5-step) Input for 3~ fan with all pole sine filter
The FRQS/FRQ5S frequency inverters have integrated all pole sine filters as standard. Therfore there is no need for shielded cables for the installation. This makes the unit also perfectly suited to retrofit into existing systems. The sine filters enable existing non-shielded cables to be retained. This units also reliably control motors which, due to their design, are not usually considered suitable for frequency inverter operation i.e. external rotor motors. - Save and trouble free motor operation with integrated, all pole effective sine filter - Enable contact section for a stand-by switch or electronic reset - Motor protection by connecting thermostat or thermistors - Interference emission EN 61000-6-3 - Interference immunity EN 61000-6-2 - Complete range in IP54 - Trouble free parallel operation of motors - - No danger to the motors through voltage peaks, bearing current, etc. - No limit of motor cable length - Retrofit in installations with existing wiring (unshielded cables) - Operation without electromagnetic motor noise - Wide voltage range 3~ 208V-480V, 50/60Hz. Wiring diagram on page 328
FRQ5S Voltage Phase Frequency Max. current Max. power load Recom.fuse 4A V 208...480 ~ 3 Hz 50...60 A 4 kW 1.5 A 10 C 40 % 85 IP 54 kg 5.4 mm 250+2 mm 302 mm 212 4A V 208...480 ~ 3 Hz 50...60 A 4 kW 1.5 A 10 C 40 % 85 IP 54 kg 5.4 mm 250+2 mm 302 mm 195.5 10A 208...480 3 50...60 10 4 16 40 85 54 5.4 250+2 302 212 10A 208...480 3 50...60 10 4 16 40 85 54 5.4 250+2 302 195.5
Electrical accessories
FRQ Voltage Phase Frequency Max. current Max. power load Recom.fuse Ambient temp. Hum, non cond. Enclosure Weight Width Height Depth
FRQ5 Voltage Phase Frequency Max. current Max. power load Recom.fuse Ambient temp. Hum, non cond. Enclosure Weight Width Height Depth
Ambient temp. Hum, non cond. Enclosure Weight Width Height Depth FRQS Voltage Phase Frequency Max. current Max. power load Recom.fuse Ambient temp. Hum, non cond. Enclosure Weight Width Height Depth
325
Electrical accessories
Wiring diagram FXDM
Fcontrol FXDM(A)M
Switch or jumper
C V C V E2 mA E1.1 E1.2 E2.1 E2.2 C Analog In 1 Analog In 2 Digital In 2 D2 V
Addressing Normal
DD+ GND 24 V
Contact rating
max. 2 A / 250 V AC TB / TP In 11 14 K1 12 21 24 K2 22 GND Digital In 1 D1
E1 Analog Out 1
mA
24V DC Out
TK / PTC D1
mA
L1
L2
L3
Output
0 .. 10 V (Imax = 10 mA)
10 mm / 2x
Input
0 ..10 V 0 .. 20 mA 4 .. 20 mA TF.. (KTY) + 1
V M 3~
PE
TB
TB
Input
0..10 V 0 .. 20 mA 4 .. 20 mA TF.. (KTY) GND D+ D-
PE L1 L2 L3
Electrical accessories
Line
Y/
Terminal
AXG-1A(E)
C V E2 mA C
Jumpers
Contact raiting
max. 5A/250VAC GND N L1 L2 L3 U V W 11 14 K1 12
mA E1 TK TK 1*
Digital IN 1
RS-485
E1.1 E1.2
mA
J2
D1 D1 1*
A GND
24V 24V
E1 GND
E2 GND
D2 D2
0 1
1 0
U A+
On/of
Output
0...10V TF..
Input
PE N
L1 L2 L3
U V M 3~ W PE
(Imax=10mA)
Line
3~ 208 .. 415 V 50/60 Hz (3~ 208 .. 500V 50/60 Hz)
Temp. sensor
4-20mA
bzw. Y or
Special version
3~ Motor
D TB TB
braun grn BN GN
MBG..
10K
Pressure sensor
Input
0...10V (Ri>100k)
D1 D1
A GND
24V 24V
E1 GND
E2 GND
D2 D2
B A
N L1 L2 L3 U
11 14 12 21 24 22
K1
K2
+
NET_ A B DATA DATA GND optional + (LON) RS-485
PE N L1 L2 L3
Line
Output
0...10V (Imax=10mA)
3 ~ 208V...400V 50/60Hz
U1 V1 W1 TK TK
1
+ GND D+ D-
Input Terminal
bzw. or
2
Input
AXG-1A(E)
PDUN16K6
326
Electrical accessories
Wiring diagram FRQ 4/10A
Electrical accessories
327
Electrical accessories
Wiring diagram FRQ5S 4/10A
Electrical accessories
328
EC-Vent offers the option to simultaneously connect multiple sensors (Temp, Humidity, CO2, PIR etc) that will detect the actual ventilation requirements and in this way speed control the EC fan so that it ventilates exactly as much as is needed, not more, not less. This way an energy efficient ventilation solution is obtained while a good indoor climate is achieved. EC-Vent consists of two units, a central unit placed near the fan and a room unit that can be placed in the occupied zone. These two are connected to each other with a low voltage cable.
CB Voltage Phase Frequency Current Recommended fuse Supply to sensor, 24V DC Ambient temp. Enclosure class Weight V 230 ~ 1 Hz 50/60 A 6 A 10 mA 150 C -20...50 IP 44 kg 0.95
Electrical accessories
Restaurant
Wiring EC-Vent
Room unit
Control board
329
EC-Vent room unit that can be placed in the occupied zone. Room unit are connected to EC-vent control board with a low voltage cable.
WC Voltage Phase Ambient temp. Enclosure class Weight V 24 DC = C 0...50 IP 20 kg 0.2
CO2RT CO2RT-R-D
CO2-sensor for wall mounting
CO2RT is a room sensor for measuring carbondioxide, CO2 concentration in indoor environments. Measuring range 0...2000ppm. Output signal 0...10 V for the full measuring range. CO2RT also has a temperature signal, 0...10 V DC for 0...50C. Apart from the above mentioned temperature signal CO2RT also has a PT1000 temperature sensor with separate terminals CO2RT is intended for wall mounting. The display models (D) have an LCD-display showing both actual values by regularly alternating.
CO2RT, CO2RT-R-D Voltage Frequency Power consumption V 24 Hz 50/60 W 3 C -5...+55 % 90 ppm 0...2000 IP 30 kg 0.1 mm 85x100x30
Electrical accessories
Enclosure Current Press. range 200 Press. range 500 Press. range 1000 Brown Yellow White
Output
Ambient temperature Re. humidity, non condens. Working range Enclosure class Weight Dimension
Pressure connection 5 mm
Residential
CO2RT-R-D
1 2 3 4 5
CO2RT
Spa
1 2 3 4 5 6 7 8
Supply voltage 24 V AC System neutral 24 V AC Output 0...10 V (humidity) Output 0...10 V (temperature) Output 0...10 V (CO2) Signal neutral Output, PT1000-sensor Output, PT1000-sensor
330
REPT
RETP
Electrical accessories
SC2/D
Weight
R1 1 10A 230V ~ 2 3 Not connected 4 Not connected R2 5 10A 230V ~ 6 7 Input signal 0-10V DC 8 Signal neutral 9 Not connected 10 Not connected 11 Sys.neutral Supply voltage 12 24V ~ in
331
Electrical accessories
Wiring REPT 6/10
...6 F1=M10 A / ...10 F1=FF20 A
REPT6/10
Auto 0 100 %
mA
E2
Analog Out 1 Analog In 2 Didital In 1 Digital In 2
E1
Analog In 1
24V GND D+
D-
PE
PE
L1
L1
U1
U1
U2
U2
11
12
K1
14
21
22
K2
24
(D2) (D2)
A3 GND
2
Input
24 V GND Data Data
PE
L1
+ RS-485
Analog Out 1
PE
PE
L1
L1
U1
U1
U2
U2
11
12
K1
14
TB
TB
D1
Didital In 1
D1
+
Input
PE
L1
PE
U1 M 1~
q
U2
TB
TB
332
Analog In 1
Electrical accessories
U2
TB
TB
+
Output
1
Input
RETP6/10
Hand/auto 0 100 %
mA
E1
Electrical accessories
5-step-transformer with control input
A three-phase transformer which controls the fan speed by altering the supply voltage in five fixed steps. The steps are adjusted by an external 0..10V control signal or by a potentiometer. Supply voltage +10V. Main switch on the front of the unit. An integral motor protection device is included which cuts the supply voltage to the fan if the thermal contact in the fan motor is activated. The unit is reset by turning the knob to 0 for 10 seconds, after which the unit restarts. Input terminals for on/off cut supply voltage to the fan when the circuit is broken. The indicator lamp on the front shows that the transformer is in operation. The transformer has 230V terminals for operating dampers, electric heater batteries or other external equipment. These terminals have no current when the transformer knob is in position 0, or when the on/off input is open. Max. ambient temp 40C. Dimensions: W 270, H 323, D 163 mm.
Step
RADT
RADT
D1 2*
D1
TB 2*
TB
L1
L2
L3
230VAC max. 1A
Contact rating
SRE5 J1...J4 D 1 2 3 4 5 6
>
1*
N
5 step thermostat
L1 L2 L3 PE
Line
3~ 400V 50/60Hz
Output
+10V (Imax=10mA) J1...J4
10K
Input
0...10V (Ri>100k)
0 1
V M 3~
PE
E 1*
TB TB
Y bzw. or D
On/off
RDNT07K1 21.06.2006
270x323x163
333
Electrical accessories
Pulser M
G G
Switch setting and wiring for internal set-point and external sensor
Electrical accessories
Pulser Voltage Frequency Current Heating power Temp. range of adjustment Temp. reduction at night Ambient temperature Ambient humidity Enclosure WxHxD Weight V 230/400 Hz 50 A 16 W max 3600/6400 C 0...30 C 0...10 C 0...30 %RH 0...90 IP 20 mm 94x150x43 kg 0.3
Pulser M Voltage V 230/400 Hz 50/60 A 16 W max 3600/6400 C 0...30 C 0...10 C 0...30 %RH 0...90 IP 20 mm 94x150x43 kg 0.32 Frequency Current
G G TG-K3xx* TG-G1xx*
Heating power Temp. range of adjustment Temp. reduction at night Ambient temperature Ambient humidity Enclosure WxHxD
Switch setting and wiring for room control using TG-R430 as sensor and set-point
G G
TG-R430 1 3
Weight
Switch setting and wiring using external separate sensor and TG-R430 as set-point
Circuit diagram for supply voltage and adjustment of change-over switch with external sensor. See Pulser. Adjustment of change-over switch with min. limit sensor.
TG-K330
G G
TG-R430 2 3
*Various temp. ranges available, for example TG-G150 = 20...50C, TG-K370 = 40...70C etc.
334
TTC-2000 automatically adapts control mode to suit the dynamics of the controlled object. Supply air temperature control For rapid temperature changes, TTC-2000 will work as a PI-controller with a fixed proportional band of 20K and a fixed reset time of 6 minutes. Room temperature control For slow temperature changes, TTC-2000 will work as a P-controller with a fixed proportional band of 1.5 K. When running room temperature control the supply air temperature can be maximum and/or minimum limited. Controlling larger electric heaters At larger loads TTC-2000 can be combined with ancillary board TT-S1.
TT-S1
Control board
TT-S1 is a control board for use when you need to control larger loads with a TTC-2000. TT-S1 is used to control a contactor that activates and deactivates a basic heating load. For best function the load connected to TT-S1 should be of equal size to the load connected to the TTC-2000. TT-S1 and TTC-2000 must have separate loads. Easy to install The TTC-2000 is prepared to plug-in the TTS1 module. TTC-2000 detects if a TT-S1 is installed and automatically adapts the control function accordingly. No settings are necessary. Connect in series with the control voltage for the heating load contactor. The supply should be wired via the fan stat, the high temperature limit switch etc. TTC-2000 and TT-S1 must have separate, equal-sized loads.
Electrical accessories
1 2 TT-S1
335
Optigo OP 5
Multi purpose controller
Temperature CO2 Pressure Humidity Domestic hot water
Optigo OP 10
Multi purpose controller
Temperature CO2 Pressure Humidity Domestic hot water
Electrical accessories
TT-S4/D Voltage supply Voltage Regulating ratio Working range Enclosure class WxHxD V 24 VAC V Out signal max 250V AC, 2A Outgoing 4 sequence steps 15 binary steps IP 20 mm 101x85x74
Language independent, simple configuration via the backlit display. Input for an external set point device. Optigo 5 is a preprogrammed, configurable controller for DIN-mounting that is intended to control temperature, CO2, pressure, humidity and domestic hot water in HVAC applications. The controller is extremely easy to install and use. It is mainly intended for small applications. Optigo has a knob with an encoder which makes the menu system very easy to use. You can read and set values shown in the back-lit display. A value is approved by pressing the knob. Optigo is suitable for DINrail or cabinet mounting. Since the terminals are detachable all connections can be made before Optigo is installed. Number of inputs/outputs OP5:
TTC25 TTC40F 7
8 9
13 19 21
TT-S4/D
1 analogue input, PT1000 1 SPI input for external set-point device 1 universal input, PT1000 or digital 1 digital input 2 analogue outputs, 0...10V DC
OP5 Voltage Frequency V 24 Hz 50...60 W 3 %RH 90 C 0...50 IP 20 mm 122x120x64 kg 0.215
OP10 has 10 inputs/outputs and can be configured to control temperature (ventilation control with heating and cooling), waterheated radiator heating with outdoor temperature dependent control-curve or domestic hot-water control. The controller is extremely easy to install and use. It is mainly intended for small applications. Optigo has a knob with an encoder which makes the menu system very easy to use. You can read and set values shown in the back-lit display. A value is approved by pressing the knob. Optigo is suitable for DINrail or cabinet mounting. Since the terminals are detachable all connections can be made before Optigo is installed. OP10 is available in two versions, OP10 with 24 V AC supply voltage and OP10-230 with 230 V AC supply voltage. Number of inputs/outputs OP10: AI 2 DI 2 UI 1 AO 2 DO 3
OP10 Voltage Frequency Power Perm. max. amb. humidity Perm. ambient temp. Enclosure class WxHxD Weight V 24 Hz 50...60 W 6 %RH 90 C 0...50 IP 20 mm 122x120x64 kg 0.215 OP10-230 Voltage supply Power consump. Perm. max. amb. humidity Perm. ambient temp. Enclosure class WxHxD Weight V 230V AC W 4 %RH 90 C -40...+50 IP 20 mm 122x120x64 kg 0.215
Fig 1
+ 0 - 10V DC in 0 8 9
TTC25X TTC40FX
13 15 19 21
TT-S4/D
Power Perm. max. amb. humidity Perm. ambient temp. Enclosure class WxHxD Weight
Fig 2
336
TM 10
Mechanical thermostat
K-FST1
Mechanical thermostat with change contact to switch fans or for the connection to controllers with thermostat or release connection. The setpoint is at the rotary button from 0 to 40C adjustable.
TM 10 Temp. range Ambient temp. Differential Contact Switching capacity Enclosure class Weight WxHxD C 0...40 C -20...+50 1.5K 1 Wechler 250V/max 4A 54 IP kg 0.35 mm 86 (+27)x126x58 (+13)
RT 0-30 Voltage Phase Frequency Temp. range of adjustment Enclosure class Power consumption Perm. ambient temp. Perm. max. ambient humidity Circuit-breaking relay WxHxD V 230 ~ 1 Hz 50/60 C 0...30 IP 30 W 1 C 0...50 %RH 90 A 16, 250 VAC mm 86x86x30
Electrical accessories
K-FST1 Sensor Contact Curcuit-breaking Temp. range of adjustm. 1 change-over A 15(8)A, 24-250V~ C -10...+12 C 200 C -10...+55 IP 40 mm 112x105x55
3 2 1
Cooling Heating
L N PE
External sensor
337
TG-A 130
Surface sensor
Surface sensor TG-A 130 to be used together with AQUA 24TF when frost protection or shut down function is required. Cannot be used together with the PULSER series.
TG-A130 mm 1500 C 0...30 IP IP 65
U-EK 230E EX
mm 85x90x35 85x90x35
Electrical accessories
TG-K330
Duct sensor
Duct sensor which is mounted inside the duct, with a sensor diameter of 9 mm, a circular flange 40 mm and adjustable length from 15 to 130 mm. The connecting cable is 1.5 m. To be used with the TTC, Pulser or RT 0-30.
TG-K Temp. range Enclosure 330 C 0...30 IP 20 350 20...50 20 360 0...60 20
TG-R4/R5/ PT1000
Room sensor
Room sensor with setpoint. For measuring room temperature, -R4 with setpoint adjustment, -R5 without setpoint adjustment.
TG-R4/PT1000 Temperature range Control signal Enclosure class WxHxD C 0...50 PT1000 IP 30 mm 86x86x30
U-EK 230E EX
Voltage Frequency Max. current Switching capacity Ambient temperature Enclosure class Weight WxHxD
Duct sensor
mm 86x86x30
TG-UH/PT1000
Outdoor sensor
For measuring outdoor temperature.
338
T 120
Timer
Timer with 120-minute operating time. Supplied with flange for fitting into equipment housing. Casing for surface mounting is available Frame for as an extra. A switch wallmounting for closing and breaking circuits. A link can be used to produce a change-over function. The timer makes a quiet ticking sound when connected. This timer is suitable for controlling the REU and RTRDU five step transformers.
The EX-connection box is of dark grey, glass fibre polyester resin and will be delivered with 2 cable connections and 1 stopping plug in Ex-execution. There are 8 clamps in the connection box.
EX connection box Explosion proof Certificate Voltage Max. current Enclosure, motor WxHxD Ambient temperature Ex II 2G EX e II T6 PTB 99 ATEX 3103 V 690 A 32 IP 66 mm 115x115x64 C -50...+55
T 120 Voltage Frequency Max. current load Connection time WxHxD V 230 Hz 50 A 10 (2) min 0...120 mm 80x80x25
Electrical accessories
RVAZ4-24 RVAZ4-24A
Valve actuator
RVAZ4 24A is a valve actuator for 0...10 V DC control signal. 24 V AC supply voltage. Suitable for controlling ZTV/ZTR valves, kvs <= 6,0. This product conforms with the EMC requirements of European harmonised standards EN60730-1:2000 and EN60730-28:2002 and carries the CE mark.
RVAZ4-24/24A Voltage supply Power consumption Frequency Max. stroke Full stroke time Stem force Max. ambient humidity Ambient temperature Enclosure class V 24 V AC +/- 15% max 6 W Hz 50/60 mm 5.5 121 sec Nm 400 %RH 95 C 0...50 IP 44
Trafo 15/D
Transformer 230/24
The transformer mounted in a 3-module casing for DIN-mounting in a cabinet or other tight enclosure.
Trafo 15/D Voltage supply Voltage output Enclosure class Power output WxHxD V 230 AC V 24 AC IP 20 VA 15 mm 53x85x74
339
Electrical accessories
166x230x129
S5S 100T1
S2S 160
S5S 100T3
REV DVV
For fans DVV/F400, F600 and DVV/120. Available on request for sizes 400 to 630 (serial at sizes 800 and 1000). The REV DVV is mounted outside on the cooling duct placed instead of terminal box outside on the cooling duct (DVV/F), while with DVV/120 it is mounted on the casing. Service switch is 8 pole with 1 x NC and 1 x NO. Locking in OFF position possible (lock not supplied). Connection of max. 7x2.5 mm2 silicon cable on the switch is possible. Equipped with cable gland max. M25x1.5, size depending on cable from electric motor to service switch. If electric motor ordered with PTC or thermal relay, service switch is supplied with additional cable gland M16x1.5.
340
MTV 1/010
Controller
Speed controller with 0-10V input. Combined flush or surface mounting. For the manual control of speed and air flow of electrical fans with 0-10V input. The jetproof IP 54 enclosure is achieved with the included surface mounting case. (Flush-mounting without the surface mounting case, gives a splash proof IP 44 enclosure).
Motor protection, 1~
The S-ET 10 (for wall mounting) and S-ET 10E (for rail mounting) switches off the supply voltage to the motor when the thermal contact in the motor windings is tripped. The motor protector is connected to a 230V supply and also to the thermal contact in the motor. The motor protector is reset by pressing the black button as soon as the motor windings have cooled sufficiently. The motor protector can also be used in conjunction with a transformer. The S-ET has an alarm contact as an accessory. The alarm contact has a built-in potentialfree contact for an external signal to indicate when the contact relay has been tripped.
MTV 1/010 Voltage supply Output 0-10 V, Imax Enclosure class Weight Colour V 230 V mA 8 IP 44 kg 0.2 white
Electrical accessories
S-ET Voltage Current range Rec. fuse Ambient temp. Enclosure class Weight Width Height Depth
MTP 10
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 Alarm relay 1 2 A 240 V AC Alarm relay 2 2 A 24 V AC Sensor neutral Main sensor Sensor neutral Limiting sensor Sensor neutral Frost protection sensor Night setback Supply voltage 24 V AC System neutral Run mode indication Run mode indication Actuator, Common pole Actuator, Increase heat Actuator, Reduce heat
Controller
Potentiometer 10k. Combined flush or surface mounting. For the manual control of speed and air flow of electrical fans with 0-10V output. The jetproof IP 54 enclosure is achieved with the included surface mounting case. (Flush-mounting without the surface mounting case, gives a splash proof IP 44 enclosure). NB! EC only.
MTP 10 Voltage supply Control signal Working range Contact Switching capacity Enclosure class Weight V DC 10 k 0...10 V 0...10 1 NO 4A/250V IP 44 kg 0.2
1~ 60V...250V 50/60Hz
L N PE
max. 25A
S -E T 1 0 E
1 5
ZB *
24 12
ZK(2S) *
24 14
I> 2 4 6 23 11 23 13
TB
TB
U1 U2 M 1~
PE
Us 1 2 3
+ 4
341
AWE-SK
Motor protection
Thermal contact motor protection device for placing on a control panel. The AWE-SK is connected to the motor relay control circuit.
Motor protection, 3~
The STDT 16 (for wall mounting) and the STDT 16E (for rail mounting) and switches off the supply voltage to the motor when the thermal contact in the motor windings is tripped. The motor protector is connected to a 400V supply and also to the thermal contact in the motor. The motor protector is reset by pressing the black button as soon as the motor windings have cooled sufficiently. The motor protector can also be used in conjunction with a transformer. An alarm contact (K) is available as an accessory. The alarm contact has an integral potential-free contact producing an external signal when the relay has been tripped.
STDT Voltage Phase Current range Rec. fuse Ambient temp. Enclosure class Weight Width Height Depth 16 V 60...400 ~ 3 A 10...16 A 80 C -25...+40 IP 55 kg 0.6 mm 80 mm 150 mm 98 16E 60...400 3 10...16 80 -25...+40 20 0.35 54 80 76
Electrical accessories
Function If the thermal contact in the motor is tripped, the AWE-SK contact relay breaks the control circuit connecting with the motor, the warning light illuminates and the fan stops. The motor will still be without current after the thermal contact in the motor is closed. The motor protector is reset by pressing the red button marked Reset on the front panel, or by closing an external contact connected to the Reset connection block. The AWE-SK does not trip in the event of a mains power supply interruption. The 14-11 connection block provides a potential-free alarm contact producing an external signal when the relay is tripped.
MSEX Max. power load Adjustm. range Ambient temp. Enclosure MSEX Max. power load Adjustm. range Ambient temp. Enclosure MSEX Max. power load Adjustm. range
0.25-0.4 kW 0,09 A 0.25...0,4 C -25...+55 IP 20 0.63-1.0 0.25 0.63-1.0 -25...+55 20 2.5-4.0 0.9 2.54 -25...+55 20
0.4-0.63 0.12 0.40.63 -25...+55 20 1.0-1.6 0.57 1.01.6 -25...+55 20 Voltage Recommended fuse Max. current Ambient temperature Enclosure class Weight WxHxD
Single phase
Alarm contact
Three phase
Fan
342
IR24-P
Presence detector
A detector that gives a signal when someone is present in the room under supervision. The detector has a pulse detecting function that minimizes the risk for false alarm. Settable output on/ off delay. Intended for wall or ceiling mounting. IR24-P is a presence detector designed for automatic ventilation control of HVAC systems.
IR24-P Voltage supply Ambient temperature Max. ambient humidity Enclosure class Circuit-breaking relay Switching capacity Dimensions V 24 V AC/DC C -20...+50 %RH 95 IP 40 A NC/NO 24V DC/0,2A mm 112x66x45
Electrical accessories
HR1 Setpoint Differential Switching capacity Max. operating temp. Enclosure class Weight WxHxD %RH 10...95 %RH 4% at 45 250V/5A C 40 IP 21 kg 0.1 mm 83x136x37
DTV
Pressure switch
Differential pressure switch for air and non-corrosive gasses.Relay contact data 250 V AC 5 A, change-over.
DTV Pressure range Media Air temperature Switch. diff. press. Max. current load Enclosure class WxHxD
DTV 1 2 3
343
Damper actuator
SF 230A, SF 24A
For air dampers up to approx. 4 m2 Torque 20 Nm Nominal voltage AC 230 V Control: Open-close Spring return actuator with emergency function for adjusting air dampers in ventilation and air conditioning systems in buildings.
1 = black 2 = red
SF 24A-SR
+
Electrical accessories
SF 24A 24 50/60 5 20 75s/20s 54 -30...+50 2.1 SF24A-S2 24 50/60 5 20 75s/20s 54 -30...+50 2.3
1 2
L1
L1
3 0 1
2 0 1
Voltage Frequency Power consump. Torque Full stroke time Enclosure class Ambient temp. Weight
SF 230A, SF 24A
+
344
~
Y U Y 1 DC 0 10 V U DC 2 10 V 2 3 5
1 = black 2 = red 3 = white 5 = orange 1 = black 2 = red S1 = violet S2 = red S3 = white S4 = orange S5 = pink S6 = grey
S1 S2 S3 S4 S5 S6
A = 10% <A >A <B >B B = 10 ... 90%
Electrical accessories
Electrical accessories
345
Accessories
Coolers
Accessories
Mounting clamps/feet
Filter boxes
Heaters
Roofs
346
Accessories Contents
Flanges
ASF . . . . . . . . . . . . . . . . . . . . . . . . . . . 375 ASFV . . . . . . . . . . . . . . . . . . . . . . . . . . 384 GFL . . . . . . . . . . . . . . . . . . . . . . . . . . . 364 GFL-AR/AXC . . . . . . . . . . . . . . . . . . . . 389 GFL-AR/AXCBF. . . . . . . . . . . . . . . . . . 389 IS/US. . . . . . . . . . . . . . . . . . . . . . . . . . 371 STG . . . . . . . . . . . . . . . . . . . . . . . . . . . 372 TDA DV . . . . . . . . . . . . . . . . . . . . . . . . 371 TUB/TUS. . . . . . . . . . . . . . . . . . . . . . . 372
Filter boxes
FFK . . . . . . . . . . . . . . . . . . . . . . . . . . . . 357 FFR . . . . . . . . . . . . . . . . . . . . . . . . . . . 349 FFS . . . . . . . . . . . . . . . . . . . . . . . . . . . . 368 FGR. . . . . . . . . . . . . . . . . . . . . . . . . . . 348
Coolers
CWK . . . . . . . . . . . . . . . . . . . . . . . . . . . 354 DXRE. . . . . . . . . . . . . . . . . . . . . . . . . . 362 PGK. . . . . . . . . . . . . . . . . . . . . . . . . . . 360
Anti-vibration mounts
FSD . . . . . . . . . . . . . . . . . . . . . . . . . . . 386 SD . . . . . . . . . . . . . . . . . . . . . . . . . . . . 385 ZSD . . . . . . . . . . . . . . . . . . . . . . . . . . . 386
Roof sockets
FDG/F . . . . . . . . . . . . . . . . . . . . . . . . . 377 FDS . . . . . . . . . . . . . . . . . . . . . . . . . . . 374 FDGE/F . . . . . . . . . . . . . . . . . . . . . . . . 378 FDVE, FDVE/F. . . . . . . . . . . . . . . . . . . 382 FDV, FDV/F . . . . . . . . . . . . . . . . . . . . . 381 TG . . . . . . . . . . . . . . . . . . . . . . . . . . . . 373 TG 300-800, 400-800. . . . . . . . . . . . 372 THB. . . . . . . . . . . . . . . . . . . . . . . . . . . 373 THS . . . . . . . . . . . . . . . . . . . . . . . . . . . 373 TOB. . . . . . . . . . . . . . . . . . . . . . . . . . . 372 TOS . . . . . . . . . . . . . . . . . . . . . . . . . . . 372
Flexible connections
ASF/KB . . . . . . . . . . . . . . . . . . . . . . . . 371 ASS . . . . . . . . . . . . . . . . . . . . . . . . . . . 381 ASS-P . . . . . . . . . . . . . . . . . . . . . . . . . 380 ASSG/F . . . . . . . . . . . . . . . . . . . . . . . . 383 ASSV, ASSV/F, ASSV-EX . . . . . . . . . . . 383 CCM inlet comm. . . . . . . . . . . . . . . . . 375 CCM cirkular comm. outlet . . . . . . . . 375 CCMI comm. isolated outlet . . . . . . . . 375 DSK . . . . . . . . . . . . . . . . . . . . . . . . . . . 370 DS . . . . . . . . . . . . . . . . . . . . . . . . . . . . 363 DS-EX . . . . . . . . . . . . . . . . . . . . . . . . . 363 EPSN/EPIN . . . . . . . . . . . . . . . . . . . . . 389 EV-AR/AXC, EV-EX/AXC. . . . . . . . . . . 387 EVH . . . . . . . . . . . . . . . . . . . . . . . . . . . 388 FGV . . . . . . . . . . . . . . . . . . . . . . . . . . . 370 ISE/USE. . . . . . . . . . . . . . . . . . . . . . . . 371 UGS. . . . . . . . . . . . . . . . . . . . . . . . . . . 370
Silencers
HSDV. . . . . . . . . . . . . . . . . . . . . . . . . . 379 LDC . . . . . . . . . . . . . . . . . . . . . . . . . . . 348 LDK . . . . . . . . . . . . . . . . . . . . . . . . . . . 365 LDR . . . . . . . . . . . . . . . . . . . . . . . . . . . 358 RSA (F). . . . . . . . . . . . . . . . . . . . . . . . 384 SSD . . . . . . . . . . . . . . . . . . . . . . . . . . . 374 SSG/F. . . . . . . . . . . . . . . . . . . . . . . . . .378 SSVE/SSVE-F. . . . . . . . . . . . . . . . . . . . 377 SSV, SSV/F. . . . . . . . . . . . . . . . . . . . . . 382 SSGE/F . . . . . . . . . . . . . . . . . . . . . . . . 379
Mounting clamps/feet
FK . . . . . . . . . . . . . . . . . . . . . . . . . . . . 355 FKX . . . . . . . . . . . . . . . . . . . . . . . . . . . 355 MFA-AR/AXC . . . . . . . . . . . . . . . . . . . . 386 MFA-AXCBF . . . . . . . . . . . . . . . . . . . . . 388 MP. . . . . . . . . . . . . . . . . . . . . . . . . . . . 387 WBK . . . . . . . . . . . . . . . . . . . . . . . . . . . 389 WBK-W . . . . . . . . . . . . . . . . . . . . . . . . 389
Accessories
Others
ALS-KBT . . . . . . . . . . . . . . . . . . . . . . . 371 ASK, ASK/F, ASG/F. . . . . . . . . . . . . . . 380 BVK. . . . . . . . . . . . . . . . . . . . . . . . . . . 390 Cable gland set . . . . . . . . . . . . . . . . . . 386 ESDV. . . . . . . . . . . . . . . . . . . . . . . . . . 384 ESD-F . . . . . . . . . . . . . . . . . . . . . . . . . . 388 FSL. . . . . . . . . . . . . . . . . . . . . . . . . . . . 379 FTG . . . . . . . . . . . . . . . . . . . . . . . . . . . 371 IN. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 390 LGV/LGH. . . . . . . . . . . . . . . . . . . . . . . 376 RED. . . . . . . . . . . . . . . . . . . . . . . . . . . 364 SN. . . . . . . . . . . . . . . . . . . . . . . . . . . . 390 ZHZ . . . . . . . . . . . . . . . . . . . . . . . . . . . 389 ZTV/ZTR . . . . . . . . . . . . . . . . . . . . . . . 390
Shutters, dampers
BDS . . . . . . . . . . . . . . . . . . . . . . . . . . . 390 BTG . . . . . . . . . . . . . . . . . . . . . . . . . . . 374 EFD, circular . . . . . . . . . . . . . . . . . . . . 355 EFD, rectangular. . . . . . . . . . . . . . . . . 363 LRK(F). . . . . . . . . . . . . . . . . . . . . . . . . 385 RSK . . . . . . . . . . . . . . . . . . . . . . . . . . . 355 SRK . . . . . . . . . . . . . . . . . . . . . . . . . . . 364 SRKG . . . . . . . . . . . . . . . . . . . . . . . . . . 370 VK, square . . . . . . . . . . . . . . . . . . . . . 356 VK, rectangular . . . . . . . . . . . . . . . . . . 368 VKV/F, VKVE/F, VKG/F. . . . . . . . . . . . 383 VKK . . . . . . . . . . . . . . . . . . . . . . . . . . . 356 VKS, VKM, VKS-EX, VKSV-EX . . . . . . 380 VKVM . . . . . . . . . . . . . . . . . . . . . . . . . 384
Roofs
WSD . . . . . . . . . . . . . . . . . . . . . . . . . . . 370 WSD-KBT . . . . . . . . . . . . . . . . . . . . . . . 371
Heaters
CB . . . . . . . . . . . . . . . . . . . . . . . . . . . . 350 CBM. . . . . . . . . . . . . . . . . . . . . . . . . . . 351 RB. . . . . . . . . . . . . . . . . . . . . . . . . . . . 359 RBK. . . . . . . . . . . . . . . . . . . . . . . . . . . 368 RBM . . . . . . . . . . . . . . . . . . . . . . . . . . . 360 VBC. . . . . . . . . . . . . . . . . . . . . . . . . . . 352 VBF . . . . . . . . . . . . . . . . . . . . . . . . . . . 353 VBK. . . . . . . . . . . . . . . . . . . . . . . . . . . 367 VBR. . . . . . . . . . . . . . . . . . . . . . . . . . . 365
347
Accessories LDC
Silencer Filter cassette for circular ducts
The FGR filter cassette is fitted with a standard type G3 panel filter. The cassette housing is manufactured from galvanised sheet steel with rubber-sealed circular connections, toggle locks and disposable filters. Replacement PFR filters are sold in packs of five. The filter cassette is suitable for use as a supply-air filter in industrial workshops. The recommended final pressure drop is 170 Pa for the G3 filter.
FGR
Easily-fitted silencer for circular ducts, fitted with a connection that complies with the spiral duct standard. The LDC effectively reduces noise in the duct. Two silencers can be used together in installations where noise reduction is critical. For the most effective noise reduction, the silencer should be fitted immediately behind a fan or bend. The silencer should be used together with an insulated fan where there is a requirement for noise reduction both in the duct and in the surroundings as a whole. Insulation thickness 50 mm.
G3
G3
d0 di
LDC 100-300 100-600 100-900 100-1200 125-600 125-900 125-1200 150-600 160-600 160-900 200-600 200-900 250-600 250-900 315-600 315-900 355-900 400-900
L nom d1 300 600 900 1200 600 900 1200 600 600 900 600 900 600 900 600 900 900 900 100 100 100 100 125 125 125 150 160 160 200 200 250 250 315 315 355 400
d0 200 200 200 200 224 224 224 250 260 260 300 300 355 355 415 415 560 600
l 360 660 960 665 965 600 670 970 685 985 600 900 600 900 900 900
kg 2.28 4.09 5.18 4.39 6.2 5.37 5.37 7.48 6.9 9.74 8.55 11.7 11.8 16.3 25.2 24.3 Filter mounting
Accessories
1260 6.46
1265 7.47 FGR 100 125 150 160 200 250 315 355 400 100 125 150 160 200 250 315 355 400 A 123 123 123 123 123 123 123 123 123 B 199 199 199 199 199 239 239 239 259 C 205 205 205 205 302 302 350 454 454 D 201 201 201 201 297 297 345 450 450 E 190 190 190 190 280 280 330 435 435
Noise suppression dB (mid-frequency Hz) LDC 63 125 250 500 1k 2k 4k 100-300 2 2 6 14 21 25 20 100-600 4 100-900 5 100-1200 6 125-600 125-900 3 4 3 4 5 3 4 5 3 3 4 3 4 2 4 2 3 3 3 11 15 19 9 12 15 7 7 10 7 8 7 8 6 7 6 5 24 34 45 23 33 43 20 19 28 16 24 13 20 11 16 13 10 36 50 50 30 45 50 27 27 42 21 32 17 26 14 22 18 13 49 50 50 40 50 50 31 29 43 23 34 16 23 9 12 10 7 34 48 50 22 30 38 16 14 20 9 13 8 10 4 6 6 5
8k 11 17 23 29 14 17 21 11 11 15 8 10 6 8 5 7 7 6 Filter cassette FGR 100 FGR 125 FGR 150 FGR 160 FGR 200 FGR 250 FGR 315 FGR 355 FGR 400 Panel filter (incl. in FGR) PFR 100-160 PFR 100-160 PFR 100-160 PFR 100-160 PFR 200 PFR 250 PFR 315 PFR 355 PFR 400 Filter media G3 G3 G3 G3 G3 G3 G3 G3 G3
125-1200 5 150-600 160-600 160-900 200-600 200-900 250-600 250-900 315-600 315-900 355-900 400-900 2 2 2 2 3 3 0 1 1
348
Accessories
Filter cassette for circular ducts
The FFR filter cassette is designed for bag filters of the G3, F5 or F7 standard filter types. The cassette is manufactured from galvanised sheet steel with rubber-sealed circular connections and locks with toggle fasteners. The cassette is fitted with connections for connecting to a pressure sensor. The filters for FFR are BFR bag filters. Available in various filter classes and are ordered separately and supplied individually. The recommended final pressure drop is 170 Pa for the G3 filter, 200 Pa for the F5 filter and 250 Pa for the F7 filter.
Free area for filter change
B D
FFR
C 203 203 203 203 248 298 348 448 448 Bag filter
E 450 450 450 450 450 500 550 650 650 Filter media G3, F5, F7 G3, F5, F7 G3, F5, F8 G3, F5, F9 G3, F5, F10 G3, F5, F11 G3, F5, F12 G3, F5, F13 G3, F5, F14
Accessories
Filter cassette FFR 100 FFR 125 FFR 150 FFR 160 FFR 200 FFR 250 FFR 315 FFR 355 FFR 400
BFR 100-160 BFR 100-160 BFR 100-160 BFR 100-160 BFR 200 BFR 250 BFR 315 BFR 355 BFR 400
A B
Dimensions for filter classes G3/F5/F7 in mm: BFR A B No. of filter bags 2/2/3 2/2/3 2/2/4 3/3/6 3/3/6
100-160 187/187/188 250/250/235 200 250 315 315 400 232/232/233 250/250/235 282/282/283 300/300/285 432/432/433 450/450/420 432/432/433 450/450/420
349
Accessories CB
CB Connection mm Power [kW] Voltage [V] Current [A] Min. airflow [m3/h] Weight [kg] Controlled by Wiring diagram CB Connection mm Power [kW] Voltage [V] Current [A] Min. airflow [m3/h] Weight [kg] Controlled by Wiring diagram CB Connection mm Power [kW] Voltage [V] Current [A] Min. airflow [m3/h] Weight [kg] Controlled by Wiring diagram 100-0.4 100 0.4 230 1~ 1.7 45 2 Pulser CB-1 150-5.0 150 5.0 400 2~ 12.5 100 3.8 Pulser CB-2 250-3.0 250 3.0 230 1~ 13 280 4.8 Pulser CB-1 355-9.0 355 9 400 3~ 13 550 8.2 TTC CB-3 100-0.6 100 0.6 230 1~ 2.6 45 2 Pulser CB-1 160-1.2 160 1.2 230 1~ 5.2 115 3 Pulser CB-1 250-6.0 250 6 400 2~ 16 280 5.2 Pulser CB-2 355-12.0 355 12 400 3~ 17.3 550 8.5 TTC CB-4 125-0.6 125 0.6 230 1~ 2.6 70 2.5 Pulser CB-1 160-2.1 160 2.1 230 1~ 9.1 115 3.2 Pulser CB-1 250-9.0 250 9 400 3~ 13 280 6.2 TTC CB-3 400-6.0 400 6 400 2~ 15 700 8 Pulser CB-2 125-1.2 125 1.2 230 1~ 5.2 70 2.5 Pulser CB-1 160-2.7 160 2.7 230 1~ 11.7 115 3.5 Pulser CB-1 315-3.0 315 3 230 1~ 13 430 6 Pulser CB-1 400-9.0 400 9 400 3~ 13 700 8.5 TTC CB-3 125-1.8 125 1.8 230 1~ 7.8 65 2.5 Pulser CB-1 160-5.0 160 5.0 400 2~ 12.5 115 4.0 Pulser CB-2 315-6.0 315 6 400 2~ 15 430 6.3 Pulser CB-2 400-12.0 400 12 400 3~ 17.3 700 9.2 TTC CB-4 150-1.2 150 1.2 230 1~ 5.2 100 2.5 Pulser CB-1 200-2.1 200 2.1 230 1~ 9.1 180 3.9 Pulser CB-1 315-9.0 315 9 400 3~ 13 430 7.3 TTC CB-3 150-2.1 150 2.1 230 1~ 9.1 100 3.2 Pulser CB-1 200-3.0 200 3.0 230 1~ 13 180 4.0 Pulser CB-1 315-12.0 315 12 400 3~ 17.3 430 7.6 TTC CB-4 150-2.7 150 2.7 230 1~ 11.7 100 3.0 Pulser CB-1 200-5.0 200 5.0 400 2~ 12.5 180 4.5 Pulser CB-2 355-6.0 355 6 400 2~ 15 550 7 Pulser CB-2
Duct heater with spigot connection for standard spiral ducts. Manufactured from alu-zinc coated sheet steel with a heating element in stainless steel. The heater has integral overheating protection with a manual reset function. The CB heater has rubber seals on the connecting spigots. Suitable for control by room thermostat or Pulser. The minimum air volume is based on a minimum air velocity of 1.5 m/s. These duct heaters are designed for a maximum output air temperature of 40C. The CB can be installed in a horizontal or vertical duct. In a horizontal duct, the connection box should be installed facing upwards, or rotated 90 to one side. Installation with the connection box facing downwards is not allowed.
Accessories
D = connection diameter A = Heating elements B = Overheat protection with automatic reset C = Overheat protection with manual reset E = Interlocking F = All phase breaker H = Thyristor type Pulser or TTC Pulser page 334 TTC page 335 Sensors 338 CB-1 230V~
CB Connection mm Power [kW] Voltage [V] Current [A] Min. airflow [m3/h] Weight [kg] Controlled by Wiring diagram
CB-2 400V 2~
350
Accessories CBM
CBM Connection mm Power [kW] Voltage [V] Current [A] Weight [kg] Wiring diagram CBM Connection mm Power [kW] Voltage [V] Current [A] Weight [kg] Wiring diagram 100-0.6 100 0.6 230 1~ 2.6 2.3 CBM-1 315-6.0 315 6 400 2~ 15 6.6 CBM-2 125-1.2 125 1.2 230 1~ 5.2 70 3 CBM-1 315-9.0 315 9 400 3~ 13 430 8 CBM-3 150-2.1 150 2.1 230 1~ 9.1 100 3.5 CBM-1 355-9.0 355 9 400 3~ 13 550 8.8 CBM-3 160-2.1 160 2.1 230 1~ 9.1 115 3.5 CBM-1 400-9.0 400 9 400 3~ 13 700 9.3 CBM-3 200-3.0 200 3.0 230 1~ 13.1 180 4.4 CBM-1 200-5.0 200 5.0 400 2~ 12.5 115 4.8 CBM-2 250-3.0 250 3.0 230 1~ 13.1 180 5 CBM-1 250-6.0 250 6.0 400 2~ 15 280 5.6 CBM-2
CBM-1 230V~
CBM-2 400V 2~
Accessories
D = connection diameter
CBM-3 400V 3~ A = Heating elements B = Overheat protection with automatic reset C = Overheat protection with manual reset E = Interlocking F = All phase breaker H = Thyristor type Pulser or TTC J = Sensor T = Air flow switch/Pressure switch
351
Accessories VBC
dy
Water-heating coil for heating air in ventilation systems with circular ducts. Aluzinc-coated casing, heat transmission element with copper tubes and aluminium fins. Removable cover for cleaning the unit. The water-heating coil can be installed in a horizontal duct. Max operating temperature 150C. Max operating pressure 1.6 MPa (16 Bar) 2- and 3-rows batteries.
K L
VBC 100-2 100-3 125-2 125-3 160-2 160-3 200-2 200-3 250-2 250-3 315-2 315-3 400-2 400-3 500-2
D 100 100 125 125 160 160 200 200 250 250 315 315 400 400 500
B 238 238 238 313 313 313 313 398 398 473 473 557 557 707 707
H 180 180 180 255 255 255 255 330 330 405 405 504 504 539 529
dy 10 10 10 10 10 10 10 22 22 22 22 22 22 22 22
F 137 100 137 175 212 175 212 250 250 325 325 400 400 425 425
G 40 40 40 40 40 40 40 40 40 40 40 40 65 65 65
K 276 276 276 276 276 276 276 276 276 276 276 276 276 330 330
L 356 356 356 356 356 356 356 356 356 356 356 356 406 460 460
kg 3.7 3.8 3.5 5.5 5.4 5.4 5.3 8.2 7.7 10.2 9.9 13.4 13.1 17.9 16.9
Water out
Water in
Accessories
352
Accessories VBF
Water heating coil
Water-heating coil with integral F5 bag filter for heating air in ventilation systems with circular ducts. Casing from galvanised sheet steel, with copper tubes and aluminium fins. Inspection cover which facilitates cleaning and replacing the filter. The water-heating coil must be installed in a horizontal duct. The bag filter must always be fitted vertically. The VBF is fitted with connections for connecting to a filter monitor. The Systemair fan selection programme includes a special selection programme for waterheating batteries. The recommended final pressure drop is 200 Pa.
dy 22 22 22 22 22 22 22 22
kg 8 8 8 8 12 17 17 17
Bag filter BFR 200 BFR 200 BFR 200 BFR 200 BFR 315 BFR 355 BFR 355 BFR 355
Filter class G3, F5, F7 G3, F5, F7 G3, F5, F7 G3, F5, F7 G3, F5, F7 G3, F5, F7 G3, F5, F7 G3, F5, F7
Accessories
Water out
Water in
353
Accessories CWK
dy
F H+8
G" *
K L
* Condensate drain
G 40 40 40 40 40 40 65
Coil calculation
Air flow CWK (m3/h) 100-3-2.5 54 54 100 100 145 145 125-3-2.5 85 85 150 150 215 215 160-3-2.5 145 145 250 250 355 355 200-3-2.5 225 225 390 390 555 555 250-3-2.5 360 360 630 630 900 900 315-3-2.5 560 560 985 985 1410 1410 400-3-2.5 900 900 1590 1590 2280 2280 Air velocity m/s 2 2 3.5 3.5 5 5 2 2 3 3 4.5 4.5 2 2 3.5 3.5 5 5 2 2 3.5 3.5 5 5 2 2 3.5 3.5 5 5 2 2 3.5 3.5 5 5 2 2 3.5 3.5 5 5 Air Pressure drop (Pa) 7 7 22 22 58 58 3 3 9 9 18 18 9 9 24 24 45 45 6 6 17 17 33 33 6 6 18 18 34 34 7 7 20 20 39 39 9 9 25 25 49 49 Air before (C) 25 30 25 30 25 30 25 30 25 30 25 30 25 30 25 30 25 30 25 30 25 30 25 30 25 30 25 30 25 30 25 30 25 30 25 30 25 30 25 30 25 30 Air before (% RH) 50 45 50 45 50 45 50 45 50 45 50 45 50 45 50 45 50 45 50 45 50 45 50 45 50 45 50 45 50 45 50 45 50 45 50 45 50 45 50 45 50 45 Air after (C) 14.3 15.8 16.4 18.5 17.5 20.0 12.6 13.5 14.5 15.7 15.6 17.0 14.4 15.6 16.1 17.4 17.0 18.4 14.1 15.3 15.9 17.3 16.9 18.4 14.2 15.4 16.0 17.3 17.0 18.2 14.5 15.4 16.1 17.2 17.0 18.1 15.2 16.3 16.8 17.8 17.6 18.6 Capacity (kW) 0.2 0.4 0.3 0.5 0.4 0.6 0.5 0.7 0.7 1.1 0.8 1.4 0.7 1.0 0.9 1.5 1.1 1.3 1.0 1.6 1.4 2.3 1.7 3.1 1.6 2.5 2.2 3.8 2.7 5.1 2.4 3.9 3.4 6.1 4.3 8.3 3.4 5.8 4.8 9.3 6.1 12.8 Water Flow (l/s) 0.01 0.01 0.01 0.02 0.02 0.02 0.02 0.03 0.03 0.04 0.03 0.05 0.03 0.04 0.04 0.06 0.04 0.08 0.05 0.06 0.06 0.09 0.07 0.12 0.06 0.10 0.09 0.15 0.11 0.20 0.10 0.16 0.13 0.24 0.17 0.33 0.14 0.23 0.19 0.37 0.24 0.51 Water Pressure drop (kPa) < 0.5 1 1 2 1 3 3 5 5 10 7 16 4 10 8 20 11 32 2 5 4 9 5 15 2 5 4 10 6 17 3 7 5 14 8 25 2 5 4 12 6 22
Accessories
VBF 355/400
VBF 355/400
VBF 355/400
354
Accessories FK
Fast clamps
RSK
EFD
Mounting clips which facilitate the installation and removal of fans for service and cleaning. Made from galvanised sheet steel and fitted with an 8 mm neoprene lining which suppresses vibration and ensures a tight fit. The mounting clips are clamped together by two screws which allows for connecting ducts with a marginal difference in diameter.
Hanging strap
Back draft damper for circular ducts, manufactured from galvanised sheet steel. The two blades are spring-loaded, which means that the damper can also be mounted vertically.
RSK 100 FK 100 125 150 160 200 250 315 355 400* 450* 500* D mm 100 125 150 160 200 250 315 355 400 450 500 125 150 160 200 250 315 355 400
B 24 33 34 42 55 54 50 75 75
C 33 44 43 55 62 62 65 75 75
Shutter damper EFD is a turn off damper. The damper is provided with 230 V motors with spring-return actuators. EFD are made in leakage performance class 3 according to EN 1751:1998 Annex C.2. Outdoor/exhaust air damper have the function to prevent the hot water coil to freeze. The EFD consists of a tubular housing equipped with a damper blade pivoting on an axle. The connection ends are equipped with silicon rubber sealing rings. The damper is made from hot-dip galvanised sheet steel. The EFD turn off damper is prepared for external insulation and has arrows showing the damper blade position. We recommend preventative maintenance of the damper twice a year for optimum performance. If the damper gets dirty, the blade should be cleaned. The gasket sealing should be checked and the blade axle lubricated as necessary.
95 25
210 130 73
170 100
Accessories
10
Pressure drop
45 175
45
FKX
Mounting feet
2 pcs mounting feet include plate and screw. For EX 140 and 180, manufactured in galvanised steel plate.
0 45 40 35 30 25 20 15 10 5 0 0 0,05 0,1 0,15 0,2 0,25 0,3 0,35 0,4 0,45 0,5 315 355/400 250 200 400 600 800 1000 1200 1400 1600 1800 200
Pressure drop
100
ps [Pa]
50 40 30 20 10 5 4 3 2 1 1
EFD
50 67
m/s
10
355
Accessories
Back draft damper
Back draft damper for installation in horizontal ducts. The profiled vanes produce a strong upward force which reduces the air resistance. This means that the vanes opens fully at low air velocities as well. The box is manufactured from galvanised sheet steel. The damper inside the box is manufactured in weather-resistant and shock-proof nylon material. The robust construction ensures that the vanes will not become deformed or loose. Air velocity should not exceed 12 m/s.
VKK
Louvre shutters for vertical mounting on a wall. The profiled vanes produce a strong upward force which reduces the air resistance. This means that the vanes opens fully at low air velocities as well. All the parts are manufactured in weatherresistant and shockproof nylon material (PVC containing special synthetic). The robust construction ensures that the vanes will not become deformed or loose. Above size 45, the vanes are fitted with a cast counterweight. Air velocity should not exceed 12 m/s. The louvre shutters are easy to install. Wall plugs and screws are included above size 15.
C
F
ps [Pa]
VK
Pressure drop
C E
B A
Accessories
VK 10 12 15 VKK 100 125 160 200 250 315 400 100 125 160 200 250 315 400 A 123 123 123 123 123 123 123 B 199 199 199 199 239 239 259 C 205 205 205 302 302 350 454 D 200 200 200 300 300 345 450 E 201 201 201 297 297 345 450 20 25 30 35 40 45 50
A 142 164 178 245 299 347 397 460 501 549
B 15 12 20 20 25 26 26 26 31 31 30 31 31
C 103 115 130 190 235 274 310 364 395 445 530 626 663 972
D 96 117 152 210 260 310 360 423 460 510 530 660 710 -
E 5 5 4 5 5 5 5 5 5 5 5 5 5 -
F 46 38 50 50 70 70 70 65 70 95 80 85 90 -
IGC
Intake grid
Intake grid for inside or outside installation. Connection diameters 100-315 mm, and is manufactured from die-cast aluminium and supplied with a wire mesh. D = outside diameter d = connection diameter
100 1040 40
Pressure drop
ps [Pa]
VK 80
B A F
C D H E
G I
356
Accessories SG
Protection guard
Protection grille for duct fans, mounted with three screws.
Intake grid
Intake grid manufactured from galvanised sheet steel with wall flange and wire mesh. Connection sleeve with rubber seal.
IGK
30 7.2
+0.8 0
12
A
2.8 C
Wire mesh
IGK
D
1020 520
B 37 37 37 41 Filter cassette FFK 30-15 FFK 40-20 FFK 50-25 FFK 50-30 FFK 60-30 FFK 60-35 FFK 70-40 FFK 80-50 FFK 100-50 Bag filter BFK 30-15 BFK 40-20 BFK 50-25 BFK 50-30 BFK 60-30 BFK 60-35 BFK 70-40 BFK 80-50 BFK 100-50 Filter media F5, F7 F5, F7 F5, F7 F5, F7 F5, F7 F5, F7 F5, F7 F5, F7 F5, F7
SG 100 125 150 160 200 250 315 355 400 450 500
A 100 125 150 160 200 250 315 355 400 450 500
B 90 110 150 150 190 250 310 350 390 450 490
C 3.4 3.4 3.4 3.4 3.4 3.4 3.8 3.8 3.8 3.8 3.8
D 11.8 11.8 11.8 11.8 11.8 11.8 12.6 12.6 12.6 12.6 12.6
E 24.3 24.3 24.3 24.3 24.3 24.3 24.7 24.7 24.7 24.7 24.7
Pressure drop
Accessories
ORH
No. of filer bags 2/5 3/5 4/7 4/7 4/8 4/8 5/9 6/10 7/14
Outlet hood
Outlet protection to avoid foreign objects to enter into the unit. It consists of a galvanized steel frame fitting into the outlet spigot with a grill of the same material covering the total outlet surface.
A C
286/287 142/143 386/387 192/193 486/487 242/243 486/487 292/293 586/587 292/293 586/587 342/343 686/687 392/393 785/785 490/490
FFK
Pos 1 2 3 4 5
KVD 7/7 9/7 & 9/9 10/8 & 10/10 12/9 & 12/12 5/8
C 52 52 52 52 52
357
Accessories
Pressure drop
LDR
Noise suppression dB (mid-frequency Hz) LDR 30-15 40-20 50-25 50-30 60-30 60-35 70-40 80-50 100-50 125 250 500 1k 7 5 10 8 8 7 7 6 6 15 9 15 15 15 13 11 8 8 18 15 25 20 20 17 14 10 10 25 23 25 31 31 18 14 11 11 2k 25 16 20 17 17 13 10 8 8 4k 19 12 15 14 14 10 8 6 6 8k 19 10 12 11 11 8 6 3 3
Accessories
c/c = B + 20
LDR 30-15 40-20 50-25 50-30 60-30 60-35 70-40 80-50 100-50 B 300 400 500 500 600 600 700 800 1000 H 150 200 250 300 300 350 400 500 500 kg 10 13 17 19 21 23 27 34 41
358
c/c = H + 20
Accessories
Duct heater for rectangular ducts
Manufactured from aluzinc coated sheet steel with a heating element in stainless steel. The heater has integral overheating protection with a manual reset function. Suitable for control by room thermostat or TTC. The minimum air volume is based on a minimum air velocity of 1.5 m/s. These duct heaters are designed for a maximum output air temperature of 40C.
RB
RB Power [kW] Voltage [V] Current [A] Weight [kg] RB Power [kW] Voltage [V] Current [A] Weight [kg] RB Power [kW] Voltage [V] Current [A] Weight [kg]
40-20/9 9 400 3~ 13 9.2 60-30/34 34 400 3~ 49.1 30.6 100-50/45 45 400 3~ 65 33.6
40-20/15 15 400 3~ 22 450 16 60-35/27 27 400 3~ 39 1000 23.1 100-50/68 68 400 3~ 98.2 2800 42.1
50-25/15 15 400 3~ 22 700 12.7 60-35/45 45 400 3~ 65 1000 30.6 100-50/80 80 400 3~ 116 2800 42.1
50-25/22 50-30/15 50-30/27 60-30/22 22 400 3~ 31.8 700 19.9 15 400 3~ 22 850 15.6 27 400 3~ 39 850 23.9 22 400 3~ 31.8 1000 24.9
70-40/27 70-40/45 80-50/45 80-50/68 27 400 3~ 39 1600 23.1 45 400 3~ 65 1600 30.3 45 400 3~ 65 1600 30.5 68 400 3~ 98.2 2200 39
RB 40-20/9-1 40-20/15-1 50-25/15-1 50-25/22-2 50-30/15-1 50-30/27-2 60-30/22-2 60-30/34-2 60-35/27-2 60-35/45-3 70-40/27-2 70-40/45-3 80-50/45-3 RB 80-50/68-4 RB 80-50/68-4 RB 100-50/68-4 RB 100-50/80-5
B 400 400 500 500 500 500 600 600 600 600 700 700 800 800 1000 1000 1000
H 200 200 250 250 300 300 300 300 350 350 400 400 500 500 500 500 500
D 370 500 370 500 370 500 500 500 370 500 370 370 370 370 370 370 370
Accessories
21 20 19
18 17 16
15 14 13
12 11 10
9 8 7
6 5 4 3 2 1
400V 3~
15 14 13
400V 3~
18 17 16
400V 3~
15 14 13
400V 3~
12 11 10
400V 3~
9 8 7 6 5 4 3 2 1
16 kW
16 kW
16 kW
16 kW
16 kW
RB 100-50/80-5
17 kW
17 kW
17 kW
17 kW
RB 100-50/68-4 RB 80-50/68-4
15 kW 19,9 22,6
19,9 22,6 A
15 kW 19,9 22,6
19,9 22,6 A
12 11 10
15 kW 19,9 22,6
19,9 22,6 A
9 8 7 6 5 4 3 2 1
17 kW
17 kW
13,5 kW
13,5 kW
11 kW
11 kW
RB 60-30/22-2 RB 50-25/22-2
15 kW
9 kW
RB 40-20/9-1
359
Accessories
Duct heater for rectangular ducts
Duct heater with integral control equipment. Manufactured from alu-zinc coated sheet steel with a heating element in stainless steel. The heater has integral overheating protection with a manual reset function. The unit is controlled by an integral electronic temperature regulator, using so-called time-proportional Pulse/Pause technology. This provides extremely precise temperature control. As a thyristor is used for adjusting the temperature, the unit has no moving parts. This means that it is silent and not susceptible to wear and tear. The RBM is supplied with a complete and fully-connected control system including contactors and alarm relays. This minimises the installation cost. The external installation requirements are: mains power supply, control circuit, dial for setting required temperature, sensor and a possible alarm circuit. The minimum air volume is based on a minimum air velocity of 1.5 m/s. These duct heaters are designed for a maximum output air temperature of 40C. All RBM are delivered with a TG-R430 room sensor with adjustment of desired value.
RBM
RBM Power [kW] Voltage [V] Current [A] Min. air flow [m3/h] Weight [kg] RBM Power [kW] Voltage [V] Current [A] Min. air flow [m3/h] Weight [kg] RBM Power [kW] Voltage [V] Current [A] Min. air flow [m3/h] Weight [kg]
50-25/15 15 400 3~ 22 700 20.2 60-30/27 27 400 3~ 39 1000 26.4 70-40/27 27 400 3~ 39 1600 29.7
PGK
9 10 (8x)
9 9
R K M
Accessories
19
200
200 + B + 19 B
19
c/c = B + 20
H + 38
330 395
PGK 40-20-3 B 438 538 538 638 638 738 838 H I K 176 176 176 176 176 170 170 170 M 43 43 43 43 43 55 55 55 N R 3/4 R 3/4 R 3/4 R 3/4 R 3/4 R1 R1 R1
238 70 288 120 338 175 338 170 388 220 438 250 538 340
19
10 (8x)
c/c = B + 20 D 35
35
A = B =
Heating elements Overheat protection with automatic reset C = Overheat protection with manual reset E = Flow control H = Thyristor ( or TTC) J = Sensor K = Set value adjustment K/J = Combined room sensor and set value adjustment T = Air flow switch/Pressure switch Sensors page 338
Calculation of required heating power P=qv x air density x delta t P = power in kW qv = air volume in m3/s air density = 1.2 kg/m3 at 20C delta T = temperature difference
NB! Droplet separator DE must be ordered extra. Recommended for air velocities from 2.5 m/s.
360
35
Accessories
Coil calculation, water temp 6/12C
PGK 40x20-3-2.0 Air flow [m3/h] 576 576 864 864 1152 1152 900 900 1350 1350 1800 1800 1080 1080 1620 1620 2160 2160 1296 1296 1944 1944 2592 2592 1512 1512 2268 2268 3024 3024 1920 1920 2880 2880 3840 3840 2743 2743 4115 4115 5486 5486 3429 3429 5144 5144 6858 6858 Air velocity m/s 2 2 3 3 4 4 2 2 3 3 4 4 2 2 3 3 4 4 2 2 3 3 4 4 2 2 3 3 4 4 2 2 3 3 4 4 2 2 3 3 4 4 2 2 3 3 4 4 Air pressure drop (Pa) 31 36 66 72 113 119 31 36 66 72 113 119 31 36 66 72 113 119 31 36 66 72 113 119 31 36 66 72 113 119 47 55 91 100 142 151 47 55 91 100 142 151 47 55 91 100 142 151 Air before (C) 25 30 25 30 25 30 25 30 25 30 25 30 25 30 25 30 25 30 25 30 25 30 25 30 25 30 25 30 25 30 25 30 25 30 25 30 25 30 25 30 25 30 25 30 25 30 25 30 Air before (% RH) 50 45 50 45 50 45 50 45 50 45 50 45 50 45 50 45 50 45 50 45 50 45 50 45 50 45 50 45 50 45 50 45 50 45 50 45 50 45 50 45 50 45 50 45 50 45 50 45 Air after (C) 17.0 19.0 18.4 20.2 19.2 20.8 17.0 18.6 18.2 19.4 18.9 19.8 17.1 18.8 18.4 19.7 19.1 20.1 17.3 19.0 18.6 19.8 19.3 20.1 17.3 19.0 18.6 19.8 19.3 20.1 17.1 18.1 18.5 18.8 19.3 19.0 17.1 17.6 18.4 18.0 19.0 18.6 17.5 17.9 18.7 18.0 19.3 18.6 Capacity (kW) 1.53 2.50 1.89 3.26 2.20 4.15 2.38 4.27 3.02 6.16 3.61 8.34 2.83 4.93 3.56 6.94 4.22 9.40 3.3 5.69 4.13 8.12 4.90 11.18 3.86 6.64 4.82 9.48 5.72 13.05 5.02 8.66 6.20 12.94 7.26 18.41 7.20 13.59 9.04 21.61 10.82 28.41 8.56 16.13 10.72 26.77 12.85 35.52 Water flow (l/s) 0.06 0.10 0.08 0.13 0.09 0.17 0.09 0.17 0.12 0.25 0.14 0.33 0.11 0.20 0.14 0.28 0.17 0.37 0.13 0.23 0.16 0.32 0.20 0.45 0.15 0.26 0.19 0.38 0.23 0.52 0.20 0.35 0.25 0.52 0.29 0.73 0.29 0.54 0.36 0.86 0.43 1.13 0.34 0.64 0.43 1.07 0.51 1.41 Water pressure drop (kPa) 1 3 2 5 2 7 2 5 3 9 4 15 1 4 2 7 3 12 1 3 2 6 3 11 1 3 2 6 3 11 1 3 1 4 2 8 1 3 1 6 2 10 1 2 1 6 2 10
50x25-3-2.0
50x30-3-2.0
60x30-3-2.0
60x35-3-2
70x40-3-2.0
Accessories
80x50-3-2.0
100x50-3-2.0
Air velocity in m2
361
Accessories
Rectangular duct cooling coil (DX)
Same model for left-hand or right-hand installation (reversible coil) Stainless steel condensate drip tray. A droplet eliminator can be fitted regardless of the direction of air flow Easily removable drip tray to simplify cleaning and inspection. DXRE is recommended for central or decentral (zones) cooling of individual rooms. The DXRE is intended for installation in a horizontal duct, with the air flow in either direction (reversible coil). We recommend that a DE droplet eliminator (accessory) should be installed on the outlet side of the coil if the air velocity is in excess of 2.5 m/s. This prevents water droplets being entrained by the air flow out into the duct system. Maximum operating pressure 2.4 MPa (24 Bar).
R S 9 10 (8x) B 9 9
DXRE
Coil calculation
Refrigerant R407C, 5 C Air flow DXRE 40x20-3-2.5 (m3/h) 575 575 865 865 1150 1150 900 900 1350 1350 1800 1800 1080 1080 1620 1620 2160 2160 1300 1300 1950 1950 2600 2600 1510 1510 2270 2270 3025 3025 2015 2015 3020 3020 4030 4030 2880 2880 4320 4320 5760 5760 3600 3600 5400 5400 7200 7200 Air pressure drop (Pa) 32 36 60 68 91 107 32 36 60 69 92 108 32 36 62 70 97 110 33 37 63 71 99 112 32 36 62 70 97 110 40 44 72 83 112 130 39 44 73 84 113 131 40 45 74 86 116 134 Air in Air in Air out Output Refrigerant flow (kW) 2,2 3,2 2,7 3,9 2,8 4,4 3,4 5 4,2 6,3 4,4 7,1 4,3 6,4 5,4 7,9 6,3 8,9 5,3 8,2 6,6 9,7 7,7 11 6 8,7 7,5 11 8,6 12,4 8,6 12,5 9,6 14,7 11,2 16,9 12,4 18,1 14,1 21,8 16,2 24,5 16,3 23,6 18,7 29,1 21,4 31,9 (kg/h) 51 75 63 90 65 104 80 118 99 147 103 165 101 149 126 186 147 208 116 180 145 213 170 241 131 192 164 242 189 272 188 274 211 323 246 370 272 398 309 477 356 538 356 517 411 638 470 699 Refrigerant Pressure drop (kPa) 3 6,1 4,3 8,7 4,9 11,3 3,2 6,6 5 9,8 5,2 12,1 6,1 11,9 8,8 17,6 11,6 21,7 8,4 18,5 12,6 25,2 16,7 31,5 7,5 12,8 10,1 18,6 12,5 22,6 7,6 13,3 9 17,4 11,3 20 8,8 15,7 10,6 21,2 13,2 25,9 15,1 28 19 40,2 23,8 47
50x25-3-2.5
50x30-3-2.5
60x30-3-2.5
60x35-3-2.5
Accessories
70x40-3-2.5
40
R"
K O
80x50-3-2.5
330 395
100x50-3-2.5
DXRE 400x200-3-2.5 500x250-3-2.5 500x300-3-2.5 600x300-3-2.5 600x350-3-2.5 700x400-3-2.5 800x500-3-2.5 1000x500-3-2.5 DXRE 400x200-3-2.5 500x250-3-2.5 500x300-3-2.5 600x300-3-2.5 600x350-3-2.5 700x400-3-2.5 800x500-3-2.5 1000x500-3-2.5
I 70 120 175 170 220 250 340 350 S 90 90 90 90 90 100 100 100
K 165 165 165 165 165 160 160 160 C 1/2" 1/2" 1/2" 5/8" 5/8" 5/8" 5/8" 5/8" Refrigerant Factor
(C) 25 30 25 30 25 30 25 30 25 30 25 30 25 30 25 30 25 30 25 30 25 30 25 30 25 30 25 30 25 30 25 30 25 30 25 30 25 30 25 30 25 30 25 30 25 30 25 30
(% RH) 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50
(C) 15,8 18,8 16,9 20,4 17,5 21,2 15,8 18,7 16,9 20,1 18 21,2 15,5 18,3 16,6 19,8 17,3 20,9 15,4 17,8 16,5 19,6 17,3 20,8 15,5 18,4 16,7 19,8 17,4 21 14,7 17,4 16,3 19,3 16,5 20,2 14,6 17,3 16,2 19,1 16,4 20,2 14,3 16,9 15,9 18,6 16,7 19,9
35
1038 538 M 60 60 60 60 60 75 75 75 N 19 22 22 22 22 35 35 35
362
Accessories EFD
Shutter damper for rectangular ducts
DS
DS-EX
120
60
EFD is a shut-off damper. The damper is provided with 24 V motors with spring-return actuators. EFD is manufactured to leakage performance class 3 according to EN 1751:1998 Annex C.2. Outdoor/exhaust air damper has the function to prevent the hot water coil from freezing and also prevent the cold air from cooling down the building if the unit stops. The EFD multi-leaf damper comprises a number of opposed blades, swivelling on nylon bearings in a sheet metal framework. The blades are connected via a system of linkages (protected) on the outside of the frame. Maximum air temperature is 100C.
B B+20 B+40
A A+20 A+40
20
80-50 100-50
60-30
50 70 140
A A+20 A+40
B B+20 B+40
50-30
Accessories
EFD 40-20 50-25 50-30 60-30 60-40 70-30 70-40 80-35 80-40 100-35
A 400 500 500 600 600 700 700 800 800 1000
B 200 250 300 300 400 300 400 350 400 350
120
Pressure drop
60
363
Accessories GFL
Counterflange
Used as a flange for mounting to the duct system. Manufactured from galvanised sheet steel. Suitable for rectangular ducts.
SRK
GFL
A1
50-25 500 50-30 500 60-30 600 60-35 600 70-40 700 80-50 800
20
20
B
140
40-20 400
15
Accessories
RED
Pressure drop
Reduction
Pa
Pressed, concentric reducer with female coupling,with a 45 angle. This reducer is designed to meet demands for short installation length with low pressure drop and low internal noise generation.
1000
2000
3000
5000
K SR
40
20
SR
50
25
150
300
500
1000
2000
48
160
364
Accessories VBR
Water-heating coil
VBR XX-XX-2 = Two pipe rows VBR XX-XX-4 = Four pipe rows VBR XX-XX-3 = Three pipe rows
LDK
Water-heating coil for heating air in ventilation systems with rectangular ducts. Hot dip galvanized casing, heat transmission element with copper tubes and aluminium fins. In cold conditions, a frost protection device with sensor should be fitted to reduce the risk of damage from freezing. The water-heating coil can be installed in a horizontal duct.
G H
F Thread G 1/4 G Airing H Water out I Connection for immersion sensor J Water in K Draining
LDK 45 50 55
C 50 50 50
I J K
c/c A 420 520 520 620 620 720 820 1020 c/c A 420 520 520 620 620 c/c A 720 820 1020
B 238 288 338 338 388 438 538 538 B 238 288 338 338 388 B 438 538 538
c/c B 220 270 320 320 370 420 520 520 c/c B 220 270 320 320 370 c/c B 420 520 520
E R'' R'' R'' R'' R'' R 1'' R 1'' R 1'' E R'' R'' R 1'' R 1'' R 1'' E R 1'' R 1'' R 1''
kg 5.5 kg 7 kg 8 kg 9 kg 10 kg 12.5 kg 16 kg 18.5 kg kg 7 kg 9 kg 10.5 kg 11.5 kg 13 kg kg 15.5 kg 19 kg 22.5 kg Noise suppression dB frequency band Hz LDK 45 50 55 65 70 125 5 7 9 6 5 250 8 8 9 7 7 500 13 13 13 14 19 1k 12 12 12 13 24 2k 8 9 10 9 23 4k 7 8 9 8 15 8k 7 7 8 7 10 LDK 65 70 b 661 696 B 703 740 C 50 50 D 100 100 E 93 110 F 175 176
Accessories
Pressure drop
Max. operating temperature Max. operating pressure, at water temp. 100C Max. operating pressure, at water temp. 150C Coil calculation on page 366
16 bar 10 bar
365
Accessories
Coil calculation
VBR 40-20-2 Air Flow (m3/h) 400 1000 40-20-4 400 1000 40-20-2 80/60C 400 1000 40-20-4 400 1000 50-25-2 60/40C 600 1200 50-25-4 600 1200 50-25-2 80/60C 600 1200 50-25-4 600 1200 50-30-2 60/40C 800 2000 50-30-4 800 2000 50-30-2 80/60C 800 2000 50-30-4 800 2000 60-30-2 60/40C 1000 2500 60-30-4 1000 2500 60-30-2 80/60C 1000 2500 60-30-4 1000 2500 60-35-2 60/40C 1200 3000 60-35-4 1200 3000 60-35-2 80/60C 1200 3000 60-35-4 1200 3000 70-40-2 60/40C 2000 4000 70-40-3 2000 4000 70-40-2 80/60C 2000 4000 70-40-3 2000 4000 80-50-2 60/40C 2500 5000 80-50-3 2500 5000 80-50-2 80/60C 2500 5000 80-50-3 2500 5000 100-50-2 60/40C 3000 6000 100-50-3 3000 6000 100-50-2 80/60C 3000 6000 100-50-3 3000 6000 Data based on supply air temperature of 0C. Water temp. (in/out) 60/40C Pressure drop (Pa) 9 48 18 96 9 48 18 96 8 29 16 59 8 29 16 59 10 54 20 109 10 54 20 109 11 58 22 117 11 58 22 117 11 61 23 123 11 61 23 123 31 94 46 139 31 94 46 139 25 77 37 113 25 77 37 113 23 72 35 106 23 72 35 106 T 18.5 12.7 29.5 19.5 32.8 24.5 46.3 38.9 21.7 18.2 33.1 28.4 36.5 28.6 54.5 45.9 18.2 13.5 32.5 27.2 33.6 24.3 53.8 41.7 19.2 15.4 34.1 28.2 34.3 24.4 53.9 41.8 18.7 15.0 34.2 28.1 33.9 24.1 53.6 41.5 20.1 16.0 24.7 21.1 34.7 25.1 45.4 34.4 21.1 17.2 28.0 24.0 36.8 26.9 48.4 37.1 24.8 18.4 32.3 25.6 38.4 28.2 50.1 38.7 Capacity (kW) 2.7 4.6 4.3 7.1 4.7 8.9 6.7 14.0 4.7 7.9 7.2 12.3 7.9 12.4 11.8 19.9 5.3 9.8 9.4 19.7 9.7 17.5 15.5 30.1 6.9 13.9 12.3 25.5 12.4 22.1 19.5 37.8 8.1 16.3 14.8 30.4 14.7 26.1 23.2 45.0 14.5 23.2 17.8 30.5 25.1 36.3 32.8 49.7 19.0 31.1 25.3 43.4 33.3 48.6 43.7 67.0 26.9 40.0 35.0 55.4 41.6 61.1 54.3 83.8 Water Flow (l/s) 0.03 0.06 0.05 0.09 0.06 0.11 0.08 0.17 0.06 0.10 0.09 0.15 0.10 0.15 0.14 0.24 0.06 0.12 0.11 0.24 0.12 0.21 0.19 0.37 0.08 0.17 0.15 0.31 0.15 0.27 0.24 0.46 0.10 0.20 0.18 0.37 0.18 0.32 0.28 0.55 0.18 0.28 0.22 0.37 0.31 0.44 0.40 0.61 0.23 0.38 0.31 0.52 0.41 0.59 0.53 0.82 0.32 0.48 0.42 0.67 0.51 0.75 0.66 1.02 Pressure drop (kPa) 0.5 1 0.5 0.5 1 2 0.5 1 1 2 0.5 1 2 4 1 3 0.5 1 1 2 1 2 1 4 1 2 1 4 1 4 2 7 0.5 2 1 4 1 3 3 8 1 1 0.5 1 1 3 1 2 0.5 1 0.5 1 1 2 1 2 1 2 1 2 2 4 2 4
Accessories
366
Accessories VBK
Water heating coil for square ducts
The casing is made of galvanised steel, the heat transmission elements are copper tubes with aluminium fins, and with copper pipes for connecting water inlet and outlet. If the VBK is to be used in very cold conditions it may be necessary to install a frost protection device. The VBK is designed for horizontal mounting with the water connection to the right. For best results the air and water must be going through the coil in opposite directions. The water must be flowing upwards in order to facilitate airing of the coil. Software for determining the required dimensions for the desired output is available.
Air
Draining
VBK 45 50 55 65
D 78 78 98 98
no. of rows 2 2 2 2
Air
Accessories
Water
The air flow should be going in the opposite direction of the water.
Coil calculation
VBK 45 Water temp in/out 60/40C Air flow m3/h Pressure drop Pa 10 38 57 11 38 58 10 35 53 10 36 54 18 64 96 18 65 98 27 99 150 28 101 152 DT C 30,1 23 20,9 44,7 34,5 31,5 31,5 24,2 22 46,1 35,8 32,7 26,1 19,5 17,7 39,5 29,9 27,2 24,6 18,2 16,5 36,8 27,7 25,1 Capacity kW 10,2 15,6 17,7 15,1 23,4 26,7 12,8 19,7 22,4 18,8 29,1 33,3 17,8 26,5 29,9 26,8 40,6 46,1 30 44,5 50,2 49 67,6 76,5 Water flow l/s 0,12 0,19 0,21 0,18 0,28 0,32 0,15 0,23 0,27 0,22 0,35 0,40 0,21 0,32 0,36 0,32 0,48 0,55 0,36 0,53 0,60 54 0,81 0,91 Pressure drop kPa 0,8 1,7 2,2 1,5 3,4 4,3 1,4 3,1 3,9 2,6 5,8 7,4 0,7 1,4 1,7 1,3 2,8 3,5 1,5 3 3,7 2,8 5,9 7,3
1000 2000 2500 80/60C 1000 2000 2500 50 60/40C 1200 2400 3000 80/60C 1200 2400 3000 55 60/40C 2000 4000 5000 80/60C 2000 4000 5000 65 60/40C 3600 7200 9000 80/60C 3600 7200 9000 Data based on supply air temperature of 0C
367
Accessories FFS
Filter cassette for square ducts
VK
Louvre shutter
Louvre shutters for vertical mounting on a wall. The profiled vanes produce a strong upward force which reduces the air resistance. This means that the vanes opens fully at low air velocities as well. All the parts are manufactured in weatherresistant and shockproof nylon material (PVC containing special synthetic). The robust construction ensures that the vanes will not become deformed or loose. Air velocity should not exceed 12 m/s. The louvre shutters are easy to install. Wall plugs and screws are included.
RBK
Filter cassette with a bag filter standard type F5 included. The cassette is made of galvanized steel with a hinged cover underneath fitted with a quick-release latch for easy change of filter. It can be connected directly to the duct. Connections for a pressure sensor are standard. The recommended final pressure drop is 200 Pa.
A F
C D E H
FFS 45 50 55 65 70
C 502 532 562 642 642 VK 40-20 50-25 50-30 60-30 60-35 70-40 80-50 100-50 A 455 555 555 655 655 755 846 1146 F 40-20 50-25 50-30 60-30 60-35 70-40 80-50 100-50 415 515 515 615 615 715 806 1097 B
G I
E 215 265 315 315 365 415 515 506 J* 44 44 44 44 44 44 44 42 RBK Power Voltage Phase Current Min. airflow 45/17 kW 17 V 400 ~ 3 A 24.5 m3/h 570 55/33 Power Voltage Phase Current Min. airflow kW 33 V 400 ~ 3 A 48 m3/h 890 50/21 21 400 3 30 910 66/39 39 400 3 56 1650 RBK 45 50 55 65 B 450 500 550 660 D 370 370 370 370
Accessories
15 15 15 15 15 15 15 15 G 30 30 30 30 28
Pressure drop
2x309 355 2x309 405 2x359 455 2x405 555 2x560 555 H 285 335 385 385 435 485 585 585 I 485 585 585 685 685 785 876 1176
*J = thickness of frame Filter cassette FFS 45 FFS 50 FFS 55 FFS 65 FFS 70 Bag filter (incl. in FFS) BFS 45 BFS 50 BFS 55 BFS 65 BFS 70 Filter media F5 F5 F5 F5 ps [Pa] F5
Pressure drop
Calculation of required power P = qv x air density x delta t P = power (kW) qv = air volume (m3/s) air density = 1.2 kg/m3 at 20C delta t= temperature difference
Air velocity in duct m/s
368
Accessories
Accessories
F1 = overheat protection, automatic reset (70C) F2 = overheat protection, manual reset (120C)
SDM
Service door
For Multibox (MUB) or Thermo-Box (MUB-T). The door consists of double skin galvanised steel panels with a 20mm mineral wool insulation inside.
b1 b2
h2
l2 l1
MUB 025 042 062 l1 417 587 717 l2 327 497 627 b1 417 587 717 b2 327 497 627 h1 40 40 40 h2 42 42 42
h1
369
Accessories DSK
Flexible connections
Flexible connections for KDRE and KDRD. The connections fit exactly to the fan and are easily bolted to fan and duct.
WSD
WSG
8 .5 (
x4 )
38
DSK 45 50 55 65 70
260
39 62
Accessories
FGV
UGS
Flexible connection
Manufactured from aluminium with neoprene coated fabric. For temperature up to 60C. On both sides there are holes for mounting to the duct system. Suitable for MUB.
SRKG
12
90 B c/c D A c/c C
15
120
UGS
A/C
025/315 378 025/355 378 025/400 378 042/355 548 042/400 548 042/500 548 062/500 678 062/630 678
370
Accessories WSD-KBT
Weather roof for motor
ISE/USE
Flexible connections
FTG
Additional weather protection for the motor of thermo fans KBT and KBR, if mounted outside. Manufactured from seawater resistant aluminium. WSD KBT-1 suitable for KBT 160 180, KBR 315/355 4-pole, WSD KBT-2 suitable for KBT 200 - 280, KBR 315/355 2-pole.
265/385
Flexible connections for the CE/CT, CKS and DKEX centrifugal radial fans. ISE supply connection is fixed with a strap to the spiral ducting. ISE: flex. length 100158mm. USE: flex. length 65-120mm.
CE/CT, DKEX Size 200 225 250 Supply ISE 200 Exhaust USE 200
ISE 225/250 USE 225 ISE 225/250 USE 250 ISE 280/315 USE 280 ISE 280/315 USE 315 ISE 355/400 USE 355 ISE 450 Supply ISE 500 ISE 500 ISE 500 ISE 560 USE 400 USE 450 Exhaust USE 400 CKS USE 355 USE 500 CKS
181,25
20
126
300
126
,2
(x7
200
500 560
60 10
Accessories
Adapter
TDA DV
Drain for liquids that accumulate in the casing. For KBT/KBR. Accessory to be ordered together with the fan, to be assembled in the factory.
ALS-KBT
Flexible connection
The ASF/KB is manufactured from galvanized steel, with neoprene coated fabric. It can be used for temperatures up to 120C. The ASF/KB has double sealing on each side. Suitable for KBT/KBR.
ASF/KB
Adapter framework TDA for mounting of accessories together with tilting frame FTG. The framework consists of galvanized steel.
4xi
nx
IS/US
d1
F E D
Inlet/outlet flange
Flange for EX 140 including washers and screws. Manufactured from galvanized steel. Makes it possible to connect the fans to spiral duct.
Inlet 125 160 200 Outlet 125 160 EX 140 IS 1412 IS 1416 EX 140 US 1412 EX 180 IS 1816 IS 1820 EX 180 US 1816 ASF 200/KB 225/KB 250/KB 280/KB 315/KB 355/KB da 200 225 250 280 315 355 h 196 199 200 200 205 210 310/311 315 TFSK 355/400 450/500 560/630 i 10 12 12 12 14 nxd 6x6.5 6x6.5 6x9 6x9 8x9 de 256 256 405 405 570 d1 285 285 438 438 605 TDA DV 310/311 315 TFSK 355/400 450/500 560/630 D 300 362 450 486 650 E 330 450 464 535 750 F 373 474 543 619 793 h 19 35 20 35 15
371
Accessories
Profiled roof cover plate
The cover plate is shaped like a roof tile so that it can be fitted on to a standard double-lap concrete roof tile (type TOB 125-160) or on to two single-lap roof tiles (TOB 200-315). It is fitted at right angles to the roof cladding and can therefore be used on different roof pitches. The cover plate is manufactured from powder-coated galvanised sheet steel. They are available in the standard colours of black, brick red and also uncoated. The spiral duct connected to the cover is insulated with 30 mm mineral fibre. The roof fan TFSR is fastened to the profiling plate with 4 screws, these screws are included in TOB. 3 m cable is included, as well as the TUB sealing-plate which is fitted on to the inside of the roof. This sealing-plate prevents water-damage via the roof aperture if there is leakage on the outside of the roof. The sealing-plate should not be used if the roof is only covered with roofing felt.
TOB
TOS
TG 300-800, 400-800
Roof curb
The brackets make it easy to fit the roof curb to the roof pitch. TG also has a silencer function. Manufactured from galvanised sheet steel and insulated with a 50 mm rockwool sheet and a perforated inner plate. The roof curb is fitted with plastic piping and conduits for electric cables. Weight 24 kg.
Accessories
TG
E D
A 800 800
B 293 393
C 245 330
300-800 400-800
STG
C D A A B
A 455 585
B 480 735
TOB
TUB/TUS
A
STG 125 160 200 A 125 160 200
372
Accessories THB
Profiled roof cowl
This cowl is shaped to fit over a standard double-lap concrete roof tile (THB 160), or over two tiles (THB 200). The cowl is fitted at right angles to the roof cladding and can therefore be used on different roof pitches. Manufactured from powder-coated, galvanised sheet steel, in the standard colours of black and brick red. The spiral pipe connected to the cover is insulated with 30 mm rockwool matting. The TUB sealing-plate, for fitting inside the roof, is included. This sealingplate prevents water-damage via the roof aperture if there is leakage on the outside of the roof. The sealing-plate should not be used if the roof is only covered with roofing felt.
THS
TG
Roof curb
The brackets make it easy to fit the roof curb to the roof pitch, and also function as a silencer. Manufactured from galvanised sheet steel and insulated with a 50 mm rockwool sheet and a perforated inner plate. The roof curb is fitted with plastic piping and conduits for electric cables. A roof curb with 100 mm insulation (corresponding to A60 insulation) is available on request.
Accessories
A
C D
TG 540-800 E 323 326 F 230 138 G 72 76 D 160 200 640-800 540-1230 640-1230 1140-800
THS
A B
A 455 585
B 480 735
160 200
C 448 430 G 72 76
TG 740-1200 940-1200
A 1200 1200
B 694 894
C 655 840
D 590 750
373
Accessories BTG
Back draft damper
Back draft damper designed for the TG 300-800, TG 400500, TG 400-800 and TG roof curbs, which can be fitted as long as the roof curb is installed vertically. The frame and damper vanes are manufactured from galvanised sheet steel. The frame is screwed or riveted on to the roof curbs perforated inner casing.
FDS
SSD
FDS is manufactured from seawater resistant aluminium and is supplied ready for assembly with insulation up to 100C. Suitable for DVS/DHS, DVSI, DVN, DVNI, DVC, DVEX. Supplied with washers and screws.
F E
h6
5 10
H D
F 730 817 898 977 997 h6 300 300 300 300 300
G 258 345 430 505 565 SSD 190/225* 310/311** 315M/L*** 355/400 450/499/500 560/630 710 800/900 D 245 330 450 450 535 750 840 1050 nut M 190/225* 310/311** 315M/L*** 355/400 450/499/500 560/630 710 800/900 M6 M6 M10 M10 M10 M10 M10 M12 E 294 395 478 555 625 895 985 1205 h7 400 500 650 650 650 700 800 1000 F 571 710 797 874 900 1200 1300 1540 G 258 345 430 505 565 835 925 1145
Accessories
450/499/500 535 H 190/225 310/311 315M/L TFSK 355/400 452 553 638 713
450/499/500 783
pressure drop no 1 2 3 3 4 5 6 7
* also suitable for TFSK 125 M/L ** also suitable for TFSK 160 and 200 *** suitable only for TFSK 315 M/L
374
Accessories
Pressure drop
ASF
SSD 190/225 SSD 310/311 SSD 315 TFSK SSD 355/400 SSD 450/499/500 SSD 560/630 SSD 710 SSD 800/900 1 2 3 3 4 5 6 7
Inlet flange
Counterflange for connection to a duct system. Manufactured from galvanized steel. Suitable for DVS/DVSI, DHS, DVN/ DVNI up to 120C.
SSD 190-500
Attenuation [dB]
SSD 560-900
h2 25 25 30 30 30 30
zxd 6 x 7 6 x 7 6 x 9 6 x 9 6 x 9 6 x 10
Frequency [Hz]
800/900
Accessories
CCM
CCM
CCMI
nx
n5
nx
n da
n di
nd
nd
1.5
ol
17.8
h 75 75 75 75
375
ol
Accessories LGV/LGH
Roof cowl
The roof cowl LGV/LGH as supply or exhaust cowl. Empty (no motor impeller) casing of model DVS/DHS/DVN roof fans. Dimensions are equivalent to the size of the roof fans.
Pressure drop characteristic curve no. LGV 190/225 LGV 310/311 LGV 355/400 LGV 450/499/500 LGV 560/630 LGV 710 LGV 800/900 1 2 3 4 5 6 7
1 2 3 4 5 6 7
1000 500 Pressure drop in Pa 300 200 100 50 20 200
1 2 3 4 5 6 7
1000 Pressure drop in Pa 500 300 200 100 50 20 200
Accessories
1 2 3 4 5 6
1000 500 Pressure drop in Pa 300 200 100 50 20 200
1 2 3 4 5 6
1000 500 Pressure drop in Pa 300 200 100 50 20 200
376
SSVE, SSVE/F 400 450/560 630/800 1000 SSVE, SSVE/F 400 450/560 630/800 1000
M 12 12 16 16
Noise reduction
Accessories
Frequency [Hz]
SSVE, kg 35 48 90 111
FDG/F
h6
Flat roof socket FDG/F is made of aluzinc steel sheet supplied with 40 mm mineral wool insulation with coated fabric. Additional guard for insulation protection. For use up to 400C medium temperature. Inclusive sealing between fan and socket. Suitable for DVG-H, DVG-V.
h6
F E
F E
10
D M10
H D M10
H 713 783 -
kg 17 20 35 39 45
377
Accessories FDGE/F
Roof socket for DVG
The roof sockets FDGE/F are suitable for pitched roof constructions up to a max. angle of 30. Angle of supports and height above roof can be adjusted on the socket - 3 positions to fasten and rotate the supports. Casing manufactured from aluzinc steel sheet, insulation of mineral wool with a textile lining. Insulation is secured with an additional metallic guard. The surface of insulation is abrasion resistant. Supplied with sealing between socket and fan.
SSG/F
F E
D M
E 555 625 895 985 1210 h7 650 650 700 800 1010
315/355 400/450 FDGE/F 315-355 400-450 500-560 630 800 A1 562 628 898 990 1210 A2 450 535 750 840 1050 A3 526 596 866 956 1174 H 1200 1200 1200 1200 1200 kg 43 48 68 74 92 500/560 630 800
Pressure drop
100
Accessories
SSG/F - SSGE/F
Pressure drop (Pa)
315 - 355
400 - 450
500 - 560
630
10 1000 10000
Sound attenuation
378
Accessories SSGE/F
Roof socket silencer for DVG
The socket silencers SSGE/F are suitable for pitched roof constructions up to a max. angle of 30. Angle of supports and height above roof can be adjusted on the silencer - 3 positions to fasten and rotate the supports. Casing manufactured from aluzinc steel sheet, insulation/baffles of mineral wool with a textile lining. The baffles are secured with an additional metallic guard. The surface of the baffles is abrasion resistant. Supplied with sealing between socket and fan. When ordered together with DVV fan, the marking of the fan is DVVI. Observe additional weight from table, when fitted to DVV. Fastened in the corners to the roof base (dimensions of roof base and position of bolts are the same as for DVV alone). HSDV can be mounted instead of ordinary casing afterwards too (exception: DVV-Ex), but connection box rsp. service switch should be dismounted to fit the casing to cooling duct. New labels are needed. Noise attenuating 7 to 8 dBA.
FSL
Suitable for DVV smoke and heat extract fans. Smoke and heat extract unit DVV with FSL for buildings with snow load requirement SL 1000. Suitable for temperatures from ambient up to 600C/2h. SL 1000 according to EN 12101-3. Flaps made from hot-dip galvanized steel sheet. Vertical exhaust. Tested according to EN 12101-3 at TU Munich for temperatures up to 600C/2h. Recommended to order factory mounted on the fan.
B
HSDV SSGE/F A1 A2 450 535 750 840 A3 526 596 866 956 H1 370 370 390 490 600 H kg 400 450/560 630 800 800 M,P 4 pole 1000
A 573 723
G 730 830
m kg
m1 kg
closed
18 14 25 19
1023 175 1200 1050 45 30 1023 230 1432 1163 66 44 1023 200 1516 1353 80 54 1183 245 1660 1480 96 68 FSL 450 560 A 800 800 910 1050 1050 1280 1420 B 550 550 550 700 700 927
HF
Accessories
opened
HF* E 210 305 235 305 285 400 285 428 285 428 295 446 kg** 26 27 35 47 50 59 66 67 68
Suitable for DVV/F400, F600, DVV/120, DVV-Ex DVV 400 DVV 450, 560, DVV-Ex 560 DVV 630-K, DVV 630, DVV-Ex 630-K, DVV-Ex 630 DVV 800-K, DVV 800, DVV 800 M, P 6 pole, DVV-Ex 800-K, DVV-Ex 800 DVV 800D4-M, P, 4-8-M, P, 4-6-M, P DVV 1000, DVV 1000D6-M, P, 6-8-M, P, DVV-Ex 1000 DVV 1000D4-M, P, 4-8-M, P, 4-6-M, P
HSDV 800 M,P 4 pole HSDV 1000 HSDV 1000 M,P 4 pole
Suitable for DVV/F400, F600 DVV 450 DVV 560 DVV 630, DVV 630-K DVV 800D4-K, 4-8-K, 4-6-K DVV 800D6, 6-8, 6-12, 6-K, 6-8-K, 6-12-K, 6-M DVV 800D4-M, P, 4-8-M, P, 4-6-M, P DVV 1000D6, 6-8, 6-12, 8, 8-12
HSDV
Note 1: m (kg) - weight of HSDV alone, without fan. Note 2: m1 (kg) - additional weight of fan, when HSDV mounted instead of original casing. Note 3: E* for 1000-P 4 pole only (2 cooling ducts). Note 4: E** for DVV 400 - 630 (cooling duct 45 to axis). Note 5: FSL snow load flaps for HSDV resp. DVVI on request. Note 6: DVVI-Ex without cooling ducts, connection box on casing.
1000 M, P 6 pole DVV 1000D6-M, P, 6-8-M, P 1000 M, P 4 pole DVV 1000D4-M, P, 4-8-M, P, 4-6-M, P
379
Plenum box
ASK, for mounting on SSD socket silencers to fix inlet accessories and duct system. Made of seawater resistant aluminium. The plenum box ASK/F is used for connection of inlet accessories and duct system. The ASK/F is manufactured from galvanised steel. ASK/F can be used together with roof sockets (SSVE-SSVE/F, SSV-SSV/F, FDV-FDV/F), flexible connections (ASSV-ASSV/F, ASSV-EX) and shutters (VKV/F, VKVE/F, VKVM, VKSVEX). The plenum box ASG/F is used for connection of inlet accessories and duct system. The ASG/F is manufactured from aluzinc steel sheet. ASG/F can be used together with roof socket SSG/F, SSGE/F, FDGE/F, flexible connections ASSG/F and shutter VKG/F.
di
h4
l1
zxd 6x8x12
235 217 183 306 286 255 464 438 406 639 605 573 910 872 801 da e di
115
156 210 6x10 220 290 6x10 255 375 8x10 340 500 8x10 h4 l1 zxd 6x7 6x9 8x9 zxd 12x12 16x12 16x12
560/630 710 800/900 VKS-EX 315 355-500 560/630 VKSV-EX 630 800 1000
Accessories
D 213 285 285 438 438 605 674 I 114 152 179 214 241 508
F 6x7 6xd7 6x8 6x9 6x9 8x9 8x9 L 110 110 110 110 110 110
G 4x7 4xd9 4x9 4x9 4x9 4x9 6x9 kg 0.9 1.2 2 2 2.2 3.9 5
584 541 504.5 255 708 674 638 255 814 751 711.5 350
E 322 360 404 507 636 713 L 200 250 250 300 350 350
G 10 10 10 10
16xM10 10 16xM10 10 n 1 1 1 2 2 2 kg 6 10 10 19 19 24
380
Accessories
Pressure drop VKS
VKV/VKM 190/225 VKV/VKM 310/311 VKV/VKM 355/400 VKV/VKM 560/630 VKV/VKM 710 VKV/VKM 800/900 1 2 3 4 5 6
ASS
Flexible connection
Manufactured from galvanised sheet steel, with neoprene coated fabric. For temperature up to 70C. Suitable for DVS/DHS, DVSI, DVN, DVNI, DVC, DVEX, DVV-EX.
Accessories
FDV, FDV/F
Pressure drop VKSV-EX
VKSV-EX 630 VKSV-EX 800/1000 4 6
A1 A2 M
E G B
4xM8
381
350
Accessories
FDV, FDV/F 400 450/560 630/800 1000 A1 535 685 975 1120 A2 460 600 880 1040 B 720 870 1160 1400 FDV kg 17 21 41 52 M 12 12 16 16 FDV/F kg 19 24 45 63
SSV, SSV/F
A1 A2
M8
B 720 870
30
480
FDV, FDV/F
M 12 12
1160 16
kg 35 48 95 123
Accessories
FDVE, FDVE/F
Roof socket for DVV/120, DVV/F
Flat or inclined roof socket up to 20 inclination. Manu factured from galvanized steel, supplied with insulation, mineral wool 40 mm with coated fabric. Sealing tape between fan and socket attached. Profiles adjustable up to 20, to be adjusted to inclination of the roof at site. Pressure drop
646
M 12 12 16 16
382
Noise reduction
d2 e d
n x d3
The flexible connections prevent transmission of eventual vibrations to the duct system. The flanges consist of galvanized steel. The smoke extract version ASSG/F consists of aluminium-foil coated high temperature resistant glass fibre. Suitable for the DVG range in accordance with EN 12101-3 (F400 - 400C, 2 hours).
VKVE/F
d2 e d
n x d3
kg 4 7.5 10.2 12
d2
nxd3
H kg 4.3 5 6 9 322 356 386 360 395 425 404 438 468 507 541 571 636 674 712 713 751 789 d e d2 160 8x9.5 175 8x9.5 180 12x9.5 250 12x9.5 290 16x11.5 15 350 16x11.5 20 H nxd3 kg 6 11 15 22
315-450 404 438 468 500-560 569 605 643 630 800 636 674 712 797 872 903
Accessories
Automatic shutter
VKV/F and VKVE/F for roof fans DVV F400, F600 and 120 (not DVV-Ex), VKG/F for roof fans DVG. The casing and blades are manufactured from galvanized steel. Pressure drop VKV/F - VKVE/F
Pressure drop (Pa)
VKV/F - VKVE/F
100
400 400
450
560
630 800
10000
1000
di
10
100
315 - 450
500 - 560
630
10 1000 10000
383
Accessories VKVM
Motorized shutter
VKVM motor driven shutter. Suitable for roof fans DVV/120. Temperature of use up to app. 70C. The flap of VKVM is made of galvanised steel. With direct coupled 230V/50Hz ONOFF spring return actuator. The flap opens when applying supply voltage. If the power supply is interrupted, the flap closes. Manually operating possible.
ESDV
RSA (F)
Silencer
The RSA effectively reduces noise in the duct. For the most effective noise reduction, the silencer should be fitted immediately behind a fan or bend. For axial fans AXC.
F I
d2 d1 B n x d3
kg 4,3 5 5,7 9 15 19
RSA (F) I 315 355 400 450 500 560 630 710 800 900 1000 1120 1250 315 355 400 450 500 560 630 710 800 900
L 315, 472.5, 630 355, 532, 710 400, 600, 600 450, 675, 900
12xM10 500, 750, 1000 12xM10 560, 840, 1120 12xM10 630, 945, 1260 16xM10 630, 945, 1260 16xM10 800, 1200, 1600 16xM12 900, 1350, 1800 1000, 1500, 2000 1120, 1680, 2240 1250, 1875, 2500
d1 356 395 438 541 674 751 C 190 190 190 250 250 250
d2 386 425 468 571 712 789 D 260 280 305 365 445 485
Accessories
16x11.5 170 16x11.5 210 H 250 250 250 395 395 395 kg 5.8 6.5 7.2 10.3 22 25
1000 1200 1070 16xM12 1120 1320 1190 20xM12 1250 1450 1320 20xM12
0 0 10 0 65 105
ASFV
Noise suppression dB frequency band Hz I/L 315/315 315/472.5 315/630 355/355 355/532 355/710 400/400 400/600 400/800 450/450 450/675 450/900 500/500 500/750 500/1000 560/560 560/840 560/1120 630/630 630/945 315-450 500-560 630 630/1260 710/710 710/1065 710/1420 800/800 800/1200 800/1600 125 250 500 1 k 1 2 6 0 0 2 0 1 2 1 1 1 0 1 2 0 2 1 1 2 2 1 2 4 3 5 6 3 5 6 3 5 6 4 5 7 4 6 7 4 6 8 4 7 9 5 7 9 5 7 9 7 10 13 8 12 16 9 12 15 10 14 18 12 17 21 13 18 23 14 20 24 14 20 25 12 18 24 9 13 22 14 19 26 14 21 25 13 19 24 12 17 21 11 17 21 11 15 19 10 14 17 9 11 14 8 12 14 2k 9 13 17 10 13 16 8 12 15 9 13 15 9 12 14 8 11 14 9 12 14 7 9 11 6 9 10 4k 8 11 13 8 11 12 8 10 12 6 9 10 6 9 11 5 8 10 5 8 10 5 6 8 5 7 9 8k 7 8 9 6 9 10 5 8 9 6 8 8 5 7 8 4 5 7 5 6 7 5 7 8 4 7 7
Inlet flange
Counter flange for connection to a duct system or to the accessories. Manufactured from galvanized steel. Suitable for DVV, DVG fans and accessories.
ASFV 400 450 630 G500-560 V800/G630 1000 ASFV 400 450 V560/G315-450 630 G500-560 V800/G630 1000
d 322 361 505 569 638 712 kg 0,8 0,9 1.3 1.8 2.1 2.4 2.8
e 356 395 438 541 605 674 751 for DVV 400 450 560 630 800 1000
V560/G315-450 402
384
Accessories
Noise suppression dB frequency band Hz I/L 900/900 900/1350 900/1800 125 250 500 1 k 3 5 6 7 11 14 8 12 16 8 12 15 9 12 17 13 16 23 12 17 23 13 18 23 13 17 22 8 11 13 8 10 12 7 8 10 7 8 10 2k 6 7 9 4 6 7 5 6 7 4 5 6 4k 5 7 7 4 6 7 4 5 6 4 5 6 8k 4 5 6 4 5 6 3 4 6 3 4 5
D SW C B
SD
Vibration damper
Rubber-metal-bearing for active and passive vibration- and impact sound isolation. Suitable for temperatures from -40C up to 70C.
G A F E
Protection guard
Finger protection guard for axial fans AR, AXC and sizes 710, 800 and 1000 for AW. Powder coated in black.
SD
A 45 70 105 E 15 27 45
B 35 50 80 F M6 M10 M16
C 30 45 70 G 60 90 140
D 6 9 13 SW 11 17 24 SG AR/AXC 315 355 400 450 500 560 630 710 800 900 1000 1120 1250 B 355 395 450 500 560 620 690 770 860 970 1070 1190 1250 45 45 45 45 30 30 30 22.5 22.5 22.5 22.5 18 18 kg 0.5 0.8 1.5 2 1.3 1.4 1.7 2.5 3 2.5 5 3 6
LRK(F)
Automatic shutter
The casing and flaps are manufactured from galvanized steel. For axial fans AXC up to temperatures of 400C/2h.
LK L U
z x d
Da Di
Accessories
LRK(F) 315 355 400 450 500 560 630 710 800 900 1000 1120 1250 LRK(F) 315 355 400 450 500 560 630 710 800 900 1000 1120 1250
da 398 438 484 534 584 664 734 812 904 1004 1105 1242 1350 L 250 250 250 250 250 250 250 350 350 350 350 350 400
di 320.5 359.5 401.5 450.5 504.5 565.5 634.5 711 797.5 894 1122
LK 355 395 450 500 560 620 690 770 860 970 1190
zxd 8x10 8x10 8x12 8x12 12x12 12x12 12x12 16x12 16x12 16x15 16x15 20x15 20x15 SG AW 710 800 900 1000 A d1 d2 856 979 d3 9 9 9 9 E 835 960 1115 1140 4x90 782 4x90 901
1003.5 1070 1250.5 1320 U 13.6 35 64.8 101.2 39.3 83 134 180 245 249 W 0 5 5 5 15 15 15 15 15 15 15 15 15
385
Accessories FSD
Spring-mount AXC/set
SG AW-D
Protection guard
For axial fans AW, to be mounted at the inlet side. Powder coated in black.
A B
D2
D1
D3
Spring damper for active and passive vibration- and impact sound isolation. Steel spring vibration isolators consist of two spring elements with M10 internal thread and a cylindrical screw spring designed according to DIN EN10270-1:2001. For the selection of FSD the weight-force (in N) at the point of support and the oscillation frequency (1/min) is needed.
Mounting feet
MFA-AR/ AXC
For axial fans of range AR sileo and AXC. The mounting feet MFA-AR/AXC are manufactured from hot dip galvanized steel. MFA 315-450
TK
2,5
hf
D1
D2
C A
D2
95
11
94
MFA AXC
120 150
B 60 60 60 60
D4
E 30 30 30 30
F 25 25 25 30
12
Spring damper
D2
D1 10 10 12 12
W 45 45 45 45
SG AW-D
95 11
B 95 64 131 83 120 127 152 D3 444 522 582 637 680 742 857
14 14 16 16
Accessories
Base plate
12
94
231 295 D2
150
MFA 500-1250
hf
TK
s W
D1
D2
C A
D2
ZSD
MFA AXC 500 560 630 710 800 900 1000 1120 1250 s 500 560 630 710 800 900 1000 1120 1250
B 70 70 70 70 80 80 80 80 100 TK 560 620 690 770 860 970 1070 1190 1320
E 35 35 35 35 40 40 40
F 45 35 35 35 40 40 40 50 50 hf
D2 16 16 16 18 18 18 18 18 18
120
M10
Suitable for use with normal unarmoured offshore and onshore cables. Included gasket and counter nut.
386
W1
zxd2
W2
MP
zxd1
Mounting brackets
Da (auen) Di (innen)
Flexible connections
For axial fans of range AR/AXC. The flexible connections consist of 2 counter flanges made of galvanized steel with flexible neoprene coated fabric in between.
Tk2 Tk1
For vertical mounting of axial fans. Manufactured from hot dip galvanized steel. Four piece needed.
Tk
TK1 355 395 438 487 541 605 674 751 837 934 W2 22.5 22.5
zxd1 8x10 8x10 12x9.5 12x9.5 12x9.5 16x12 16x12 16x12 24x12 24x12 L 154 154 154 154 154 154 154 154 154 154
W1 45 30 30 30 22.5 22.5 22.5 15 15 s 1.5 1.5 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.5 MP 315-355 400-450 500 560-630 710-800 900-1000 1120 1250 560-800 710 900-1250 1120 L
d
bM
45
T 128 128 133 133 133 140 157 157 136 133 155 157
d 17 17 17 17 17 17 17 17 17 17 17 17
369.5 444.5 535 743 693 629 695 1038 493 794 840 991
315 EV-AR 200 250 315 355 400 450 500 560 630 710 800 900 1000 1120 1250 Da 250 328 390 435 480 534 585 652 723 802 890 1005 1105 1225 1370 Di 201 251 322 361 402 455 505 569 638 712 797 903 1003 1122 1250 L 153 153 153 153 154 154 154 154 154 154 155 162 165 166 165 zxd 4x7 4x10 8x10 8x10 8x12 8x12 12x12 12x12 12x12 16x12 16x12 16x15 16x15 20x15 20x15 TK 225 280 355 395 450 500 560 620 690 770 860 970 1070 1190 1320 355 400 450 500 560 630 710 800 900
Accessories
387
Accessories EVH
Flexible connection EVH 400C
ESD-F
Inlet cone
The inlet cone is manufactured from galvanised steel
MFA-AXCBF
Mounting feet
For axial fans range AXCBF. The mounting feet MFA-AXCBF are manufactured from galvanized steel.
F
TK
da4 d1
n x d3
hf
9,
D
W
de
A
m x d4
Da
K L d
d2 da3
ESD-F
30 154
d1 355 395 450 500 560 620 690 770 860 970 1070 1190 1320 da4 398 438 484 534 584 664 734 812 904 1004 1105 1242 1370
de 320 359 401 450 504 565 634 711 797 894 1003 1122 1250 H 160 160 160 160 160 160 160 160 160 160 160 160 160
d2 395 450 500 560 620 690 770 860 970 1070 1190 1320 1470 nxd3 8x10 8x10 8x12 8x12 12x12 12x12 12x12 16x12 16x12 16x15 16x15 20x15 20x15
da3 438 484 534 584 664 734 812 904 1004 1105 1242 1370 1533 nxd4 8x10 8x10 8x12 12x12 12x12 16x12 16x12 16x15 16x15 20x15 20x15 20x15 12x12
MFA-AXCBF A 250 315 400 500 250 315 400 500 F 250 315 400 500 3 3 3 3
Da 390 435
d 322 361
LK 355 395
W 45 45
S
630 710 800 900 1000 1120 1250 ESD-F 315 355 400
W2
zxd1
Accessories
Da (auen)
Di (innen)
Tk2
Tk1
MFA 630-800
EVH 250 400 450 500 560 630 710 800 900
Di 251 402 455 505 569 638 712 797 903 1003 1122 1250 zxd2 8x10 8x12 8x12 12x12 12x12 12x12 16x12 16x12 16x15 16x15 20x15 20x15
TK1 280 438 487 541 605 674 751 837 934 1043 1174 1311 W2 90 22.5 22.5 15 15 15 11.25 11.25 11.25 11.25 9 9
zxd1 8x10 12x9.5 12x9.5 12x9.5 16x12 16x12 16x12 24x12 24x12 24x12 24x12 24x12 L 154 154 154 154 154 154 154 154 154 154 154 154
hf
450
TK
s W
D1
D2
F C A
D2
E
1000 1105 1120 1225 1250 1370 EVH 250 400 450 500 560 630 710 800 900 TK2 302 450 500 560 620 690 770 860 970
MFA -AXCBF A 630 800 s 630 800 3.0 5.0 630 800 TK 690 860
B 70 80 D1 12 12
C 570 730
E 35 40 W 30 22.5
F 35 40 hf 425 530
D2 16 18
388
Accessories GFL-AR/AXC
Counterflange
For axial fans of type AR and AXC. The counterflange GFL-AXC is manufactured from galvanized sheet steel.
EPSN/EPIN
Flexible connection (600C/2h) for WVA/WVI. The EPIN is a rectangular flexible connection for the outside of WVA/WVI smoke and heat extract fans. Fit to outlet connection IN. To avoid vibrations from the fan to the duct system. Applicable up to +/- 1000 Pa in cold condition and up to 600C/2h. Exclusive sealing tape and fasteners.
WBK
nxd3
2 x (13 x 16)
GFL-AR/AXC Da 315 355 400 450 500 560 630 710 800 900 1000 1120 1250 390 435 480 534 577 652 723 802 890 1005 1105 1225 1370
Di 322 361 402 455 505 569 638 712 797 903
Tk 355 395 450 500 541 620 690 770 860 970
A 30 30 30 30 35 35 35 35 35 52
9,5
180
Da Ea x250
Ca
GFL-AR/AXCBF
Counterflange
The counterflange is manufactured from galvanized steel.
s
1000
800 Db
836
H
400 450 560 630 800 1000 EPIN 400 450 560
536 536 666 746 936 1216 A 250 250 280 355 400 630 Db
Da
Di
n x D1 L
1 3 3 5
50
100
Da
Di
2 TK
W1
TK
50
n x D2
n x D1 L
40 200
L/2
d 14 14 18 18 18 18
B 80 80 80 80 80 100
kg 20 22 23 28 31 38
Di
Tk1
zxD1 8x10 L 30
389
A
8x12
B 30 Cb Eb x250 150 Db
ZHZ
Accessories
600 L
ZHZ 400/450 560/630 800/1000 Da 286 286 316 391 436 666
TK
WBK-W
Da Di
Tk1 nxD1
250 201
225
4x7
s
30
536 746
W2
Accessories
Outlet connection for WVA/WVI
The outlet connection IN is manufactured from hot-dip galvanized steel, with a protection guard. For mounting on the outlet of the fan WVI, if the outlet leads directly through the outside wall. For the type WVA as rain protection. Exclusive sealing tape and fasteners.
IN
9,5 A 30 D2 D2 B
ZTV/ZTR
E1 x250
C2
C1
E2 x250 D1
Cb
E2 x250 m n
D2 L
SN 400
9,5
C2 268 268 208 248 93 233 m 300 300 300 400 500 700
D1 351 391 391 486 666 836 n 150 150 150 200 300 400
Technical data Flow charac. Media temp. Media Stroke Leakage Pressure class Rangeability Mat. Body Spindle Seat O-ring Percental increase 1...+110C Hot, cold, glycol mixed (max. 30% glycol) 5 mm 0% in closed position PN16 (1.6MPa) 50:1 Brass Stainless steel Brass EPDM
D1 E1 x250
800
B 30
C1 C2
E2 x250
D2
45
1000 3
500
ZTV
C2 268 248 248 43 203 98 kg 15 19 20 24 32 53 D1 286 286 316 391 436 666 BDS 100 120 150 Length 55 mm 62 mm 77 mm
IN
Accessories
42
BDS
I 60
ZTR
BVK
SN
ZTV/ZTR Connection G 15-0.25 15-0.4 15-0.6 15-1.0 15-1.6 BVK 100 120 150 E 140 160 180 D 100 125 150 20-2.0 20-2.5 20-4.0 20-6.0 DN15 DN15 DN15 DN15 DN15 DN20 DN20 DN20 DN20
h (only ZTR) 40 40 40 40 40
390
9 1 6a
Blue Black/Brown Yellow/Green
Counter Clockwise rotation
TK TK Z2 Z1 U2 U1
N L PE
10
Brown Blue Blue Black Yellow/ green Brown Black Yellow/green
230V3~ (D)
Wiring diagram
Wiring diagram
391
Wiring diagram 11 12
White
13a
Delta connection
White
13b
Delta connection
W2 U1 U2 V1 V2 W1
L1
L2
L3
PE
PTC/TK
Star connection
Star connection
W2 U1
U2 V1
V2 W1
Wiring diagram
L1
L2
L3
PE
PTC/TK
14a
W2 U2 V1 V2 W1
14b
Low speed
U1
W2
U2 V1
V2 W1
Low speed
U1
PTC/TK PTC/TK
W2 U2 V1 V2 W1
High speed
U1
W2
U2 V1
V2 W1
High speed
U1
392
15b, c
Low speed connection
U1
L1
L2
Y
L3
PE
L1
W2 U1
L2
U2 V1
L3
V2 W1
PE
16
17
Delta connection
Star connection
Wiring diagram
18
19
Delta connection
Delta connection
Star connection
Star connection
393
Wiring diagram 20 21
High speed
Low speed
23a
23b
Net voltage
L N
L N PE
Net voltage
L N
Black
1-200-277V PE
1-200-277V PE
PE NC COM
White Red
+ 0-10V P1 10k
Red
P1
External signal
External signal
Potentiometer
Potentiometer
10k
Wiring diagram
394
Wiring diagram 24
Pressure control Operation
Fan EC-
PE N L
Fan EC-
motor
motor
Mains
Mains 1
1 2 3 1 2 3 1 2 1 2
PE N L
Input
mode
Night 9
GND 10
GND 8 Day 7 GND 6 0-10V in 5 +10V 4 GND 3 0-10V out 2 Tacho in 1 3 2 1 GND 2 1
Red Blue Yellow White1 White2 Blue Black Green/yellow
Fan EC-motor
074/084 +10V GND 0-10V NC COM L N PE
Alarm relay
+20V in
25
Pressure control
1 2 3 1 2 3 1 2 1 2
PE N L PE N L
Fan EC-
motor
Operation
Fan EC-motor
112
mode
Alarm relay
12 11 10 9 8 7 6 5 4 3 2 1
Input
Wiring diagram
Mains
Fan EC-
motor
3 NO 2 COM KL.2 1 NC 2 L 1 N PE
L N PE
KL.1
395
Wiring diagram 26
Pressure control GND 10 9 GND 8 7 GND 6 5 +10V 4 GND 3 2 1 3 2 1 GND 2 1
operation mode
fan (EC-motor)
112/150
1 2 3 1 2 3 1 2 1 2
PE N L PE N L
12 11 10 9 8 7 6 5 4 3 2 1
fan (EC-motor)
Input
Mains fan (EC-motor) alarm relay
L1 L2 L3 PE
3 2 1
KL.1
27
12 11 10 9 8 Kl. 3 / class 3 7 5 + 0-10V External signal
Interface RS485 for ebmBUS Interface RS485 for ebmBUS Interface RS485 for ebmBUS Interface RS485 for ebmBUS GND Control-/Actual value inlet Supply ext. sensor 50mA Supply ext. potentiometer 10mA Control/Actual value inlet GND Master exit 0-10V max 3mA Error signal relay, closes in case of fire Error signal relay, COMMON (2A, 250 VAC) Error signal relay, error signal relay, closes in case of fire Net, L1 Net, L2 Net, L3 Protective conductor
Wiring diagram
P1 10k Potentiometer
3 2 1 3
396
Wiring diagram 28
12 11 10 9 8 Kl. 3 / class 3 7 5 + 0-10V P1 10k 4 3 2 1 3 Kl. 2 / class 2 2 1 2 Kl. 1 / class 1 1 RS A RS B RS A RS B GND 0-10V +20V +10V 0-10V GND OUT NO COM NC L N PE
Interface RS485 for ebmBUS Interface RS485 for ebmBUS Interface RS485 for ebmBUS Interface RS485 for ebmBUS GND Control-/Actual value inlet Control-/Actual value inlet Supply ext. sensor 50mA Supply ext. potentiometer 10mA Control/Actual value inlet GND Master exit 0-10V max 3mA Error signal relay, closes in case of fire Error signal relay, COMMON (2A, 250 VAC) Error signal relay, closes in case of fire Net, L Net, N Protective conductor
6 4-20mA
29
Yellow/green
( ) ( (L) (N) (L) Black (N) Blue )
Wiring diagram
Brown
Art.-Nr.: 305386
397
Wiring diagram 41
230V 1~ N L
Internal potentiometer, default
42
Wiring power cable Internal potentiometer, default
Yellow C
White
Yellow
Blue
White
Red
Blue
2
1=Min
3 5
4
+
1=Min
10
43
44
U V W TP3/4 PE
X1
TP TP U V W
X2
Wiring diagram
L1
L2
L3
PE
L1
L2
L3
TP3/4 PTC
PE
45
U V W TP3 TP4 PE
R [L1
S L2
398
Red
+
10
Wiring diagram 46
Line 1 Line 2
COM
+10V
Black
Line 1
Blue
Green/yellow
White1
White2
Line 2
Red
Connection +10V 0-10V/PWM GND
Yellow
0-10V PWM
Assignment/function Mains 50/60 Hz, phase Mains 50/60 Hz, neutral Protective earth Alarm relay, break for failure Alarm relay, COMMON
Colour Assignment/function Red Yellow Blue Voltage output +10V max 1.1 mA Control input (Impendence 100 k W) Protective earth
47
KL3 KL2 KL1
Ain1 U Ain2 U
+20V
GND
Ain2 I
Din 2
Din 3
Ain1 I
Din 1
Aout
RS B
RS A
GND
+10V
COM
NC
PE
No
L1
L2
GND
Blue
NC
PE
Connector KL1
Connection L3 L2 L1
Assignment/function Mains, L3 Mains, L2 Mains, L1 Protective earth Alarm relay, break for failure Alarm relay, COMMON (2A, 250 VAC, AC1) Alarm relay, make for failure
Connector KL3
Connection Assignment/function Din1 Digital input (enabling/disabling of electronics). Enabling: Pin open or applied voltage 5...50 VDC. Disabling: Bridge to GND or applied voltage < 1 VDC. Analogue set value input, 4-20 mA (impedance 100 W) , only to be used as alternative to terminal Ain1 U Supply for external potentionmeter, 10 VDC (3%) max. 10 mA. Analogue set value input, 0-10V (impedance 100 k W) , only to be used as alternative to terminal Ain1 I. GND RS485 interface for MODBUS RTU; RS B RS485 interface for MODBUS RTU; RS A Analogue output 0-10V max 5 mA, reading of current motor speed/current motor control factor. Analogue actual value input, 4-20 mA (impedance 100 k W) , only to be used as alternative to terminal Ain2 U. Supply for external sensor, 20 VDC (+25%/10%) max 40 mA. Analogue actual valve input, 0-10 V (impedance 100k W), only to be used as alternative to terminal Ain2 I. GND Digital input 3 (switch normal/inverse). The preset effective direction of the integrated controller can be selected via BUS or via digital input normal//inverse. Normal: Pin open or applied voltage 5...50 VDC. Inverse: Bridge to GND or applied voltage < VDC. Digital input 2 (switch day/night). The preset set of parameters can be selected via BUS or digital input day/night. Day: Pin open or applied voltage 5...50 VDC. Night: Bridge to GND or applied voltage < 1 VDC.
PE KL2
PE NC COM NO
L3
Wiring diagram
Din3
Din2
399
Wiring diagram 48
KL3 KL2 KL1
4-20mA
0-10 V PWM
0-10 V PWM
+20 V
+10 V
RS B
RS B
RS A
RS A
GND
GND
OUT
COM
NO
NC
Connector KL3
Connection Assignment/function OUT GND 0-10V/PWM +10V +20V 4-20 mA 0-10V/PWM GND RSB RSA RSB RSA Master output 0-10 V max 3 mA. GND Control/Actual valve input (impedance 100 k W ). Supply for external potentiometer, 10 VDC (+10%) max 10 mA Supply for external sensor, 20 VDC (+20%/10%) max 50 mA Control/actual valve input Control/actual valve input GND RS485 interface for ebmBUS; RS B RS485 interface for ebmBUS; RS A RS485 interface for ebmBUS; RS B RS485 interface for ebmBUS; RS A
Connection OE N L NC COM NO
Assignment/function Protective earth Mains 50/60Hz, neutral Mains 50/60Hz, phase Alarm relay, break for failure Alarm relay, COMMON (2A, 250 VAC, AC1) Alarm relay, make for failure
Wiring diagram
49
TB TB U1 Z U2
PE
400
PE
Index A
ALS-KBT . . . . . . . . . . . . . . . . . . . . . . . . 371 AQUA 24TF. . . . . . . . . . . . . . . . . . . . . . 341 AR sileo. . . . . . . . . . . . . . . . . . . . . . . . . 170 ASF . . . . . . . . . . . . . . . . . . . . . . . . . . . . 375 ASF/KB . . . . . . . . . . . . . . . . . . . . . . . . . 371 ASFV. . . . . . . . . . . . . . . . . . . . . . . . . . . 384 ASK, ASK/F, ASG/F. . . . . . . . . . . . . . . . 380 ASS . . . . . . . . . . . . . . . . . . . . . . . . . . . . 381 ASSG/F . . . . . . . . . . . . . . . . . . . . . . . . . 383 ASS-P . . . . . . . . . . . . . . . . . . . . . . . . . . 285 ASSV, ASSV/F, . . . . . . . . . . . . . . . . . . . . 383 ASSV-EX . . . . . . . . . . . . . . . . . . . . . . . . 383 AWE-SK. . . . . . . . . . . . . . . . . . . . . . . . . 342 AW-EX. . . . . . . . . . . . . . . . . . . . . . . . . . 226 AW sileo . . . . . . . . . . . . . . . . . . . . . . . . 168 AXC . . . . . . . . . . . . . . . . . . . . . . . . . . . . 180 AXC(B) . . . . . . . . . . . . . . . . . . . . . . . . . . 266 AXCBF. . . . . . . . . . . . . . . . . . . . . . . . . . 186 AXCBF-EX . . . . . . . . . . . . . . . . . . . . . . . 234 AXC-EX . . . . . . . . . . . . . . . . . . . . . . . . . 230 DS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 363 DS-EX . . . . . . . . . . . . . . . . . . . . . . . . . . 363 DSG. . . . . . . . . . . . . . . . . . . . . . . . . . . . 330 DSK. . . . . . . . . . . . . . . . . . . . . . . . . . . . 370 DTV. . . . . . . . . . . . . . . . . . . . . . . . . . . . 343 DVC/DVCI . . . . . . . . . . . . . . . . . . . . . . . 132 DVEX. . . . . . . . . . . . . . . . . . . . . . . . . . . 216 DVG/F. . . . . . . . . . . . . . . . . . . . . . . . . . 250 DVG-V, H 400D4V/400 . . . . . . . . . . . . . 256 DVN/DVNI. . . . . . . . . . . . . . . . . . . . . . . 152 DVP. . . . . . . . . . . . . . . . . . . . . . . . . . . . 280 DVV. . . . . . . . . . . . . . . . . . . . . . . . . . . . 158 DVV-EX . . . . . . . . . . . . . . . . . . . . . . . . . 220 DVV/F . . . . . . . . . . . . . . . . . . . . . . . . . . 244 DXRE. . . . . . . . . . . . . . . . . . . . . . . . . . . 362
G
GFL . . . . . . . . . . . . . . . . . . . . . . . . . . . . 364 GFL-AR/AXC . . . . . . . . . . . . . . . . . . . . . 389 GFL-AR/AXCBF . . . . . . . . . . . . . . . . . . . 389
H
HR1. . . . . . . . . . . . . . . . . . . . . . . . . . . . 343 HSDV. . . . . . . . . . . . . . . . . . . . . . . . . . . 379
I
IF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 316 IGC. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 356 IGK. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 357 IN. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 390 IR24-P. . . . . . . . . . . . . . . . . . . . . . . . . . 343 ISE/USE. . . . . . . . . . . . . . . . . . . . . . . . . 371 IS/US. . . . . . . . . . . . . . . . . . . . . . . . . . . 371
E
EC-Vent control board . . . . . . . . . . . . . 329 EC-Vent room unit . . . . . . . . . . . . . . . . 330 EFD circular. . . . . . . . . . . . . . . . . . . . . . 355 EFD rectangular . . . . . . . . . . . . . . . . . . 363 EMC KIT REV. . . . . . . . . . . . . . . . . . . . . 340 EPSN/EPIN . . . . . . . . . . . . . . . . . . . . . . 389 ESD-F . . . . . . . . . . . . . . . . . . . . . . . . . . . 388 ESDV. . . . . . . . . . . . . . . . . . . . . . . . . . . 384 EV-AR/AXC . . . . . . . . . . . . . . . . . . . . . . 387 EV-EX/AXC . . . . . . . . . . . . . . . . . . . . . . 387 EVH. . . . . . . . . . . . . . . . . . . . . . . . . . . . 388 EX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 204 EX connection box. . . . . . . . . . . . . . . . 339
J
Jet Fan AJ8 . . . . . . . . . . . . . . . . . . . . . . 195 Jet Fan AJR-TR. . . . . . . . . . . . . . . . . . . . 194 Jet Fan IV. . . . . . . . . . . . . . . . . . . . . . . . 196
B
BDS . . . . . . . . . . . . . . . . . . . . . . . . . . . . 390 BF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 316 BF-W. . . . . . . . . . . . . . . . . . . . . . . . . . . 314 BTG . . . . . . . . . . . . . . . . . . . . . . . . . . . . 374 BVK . . . . . . . . . . . . . . . . . . . . . . . . . . . . 390
K
KBR/F . . . . . . . . . . . . . . . . . . . . . . . . . . 238 KBR/KBT EC. . . . . . . . . . . . . . . . . . . . . . 300 KBT/KBR . . . . . . . . . . . . . . . . . . . . . . . . 304 KD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38 KDRE/KDRD . . . . . . . . . . . . . . . . . . . . . 114 K EC. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 KE, KE(I) . . . . . . . . . . . . . . . . . . . . . . . . . 66 K-FST1. . . . . . . . . . . . . . . . . . . . . . . . . . 337 K/KV . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 KTEX . . . . . . . . . . . . . . . . . . . . . . . . . . . 208 KT, KT(I) . . . . . . . . . . . . . . . . . . . . . . . . . . 70 KVD. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90 KVK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46 KVK DUO. . . . . . . . . . . . . . . . . . . . . . . . . 52 KVKE . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60 KVKE EC. . . . . . . . . . . . . . . . . . . . . . . . . . 56 KVO. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
C
Cable gland set . . . . . . . . . . . . . . . . . . . 386 CB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 350 CBF . . . . . . . . . . . . . . . . . . . . . . . . . . . . 316 CBM. . . . . . . . . . . . . . . . . . . . . . . . . . . . 351 CCM. . . . . . . . . . . . . . . . . . . . . . . . . . . . 375 CCM. . . . . . . . . . . . . . . . . . . . . . . . . . . . 375 CCMI . . . . . . . . . . . . . . . . . . . . . . . . . . . 375 CE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 288 CKS . . . . . . . . . . . . . . . . . . . . . . . . . . . . 296 CO2RT. . . . . . . . . . . . . . . . . . . . . . . . . . 330 CO2RT-R-D . . . . . . . . . . . . . . . . . . . . . . 330 CT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 292 CWK . . . . . . . . . . . . . . . . . . . . . . . . . . . . 354 CXE/AV . . . . . . . . . . . . . . . . . . . . . . . . . 323 CXE/AVC . . . . . . . . . . . . . . . . . . . . . . . . 322
F
FDGE/F . . . . . . . . . . . . . . . . . . . . . . . . . 378 FDG/F . . . . . . . . . . . . . . . . . . . . . . . . . . 377 FDS . . . . . . . . . . . . . . . . . . . . . . . . . . . . 374 FDVE, FDVE/F . . . . . . . . . . . . . . . . . . . . 382 FDV, FDV/F . . . . . . . . . . . . . . . . . . . . . . 381 FFK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 357 FFR . . . . . . . . . . . . . . . . . . . . . . . . . . . . 349 FFS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 368 FGR. . . . . . . . . . . . . . . . . . . . . . . . . . . . 348 FGV. . . . . . . . . . . . . . . . . . . . . . . . . . . . 370 FK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 355 FKX . . . . . . . . . . . . . . . . . . . . . . . . . . . . 355 FRQ(5) . . . . . . . . . . . . . . . . . . . . . . . . . . 325 FRQ(5)S . . . . . . . . . . . . . . . . . . . . . . . . . 325 FSD . . . . . . . . . . . . . . . . . . . . . . . . . . . . 386 FSL. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 379 FTG . . . . . . . . . . . . . . . . . . . . . . . . . . . . 371 FXDM . . . . . . . . . . . . . . . . . . . . . . . . . . . 324
L
LDC . . . . . . . . . . . . . . . . . . . . . . . . . . . . 348 LDK . . . . . . . . . . . . . . . . . . . . . . . . . . . . 365 LDR . . . . . . . . . . . . . . . . . . . . . . . . . . . . 358 LGV/LGH . . . . . . . . . . . . . . . . . . . . . . . . 376 LRK(F). . . . . . . . . . . . . . . . . . . . . . . . . . 385
Index
D
DHA sileo . . . . . . . . . . . . . . . . . . . . . . . 130 DHS/DVS/DVSI . . . . . . . . . . . . . . . . . . . 146 DHS/DVS/DVSI sileo. . . . . . . . . . . . . . . 138 DKEX. . . . . . . . . . . . . . . . . . . . . . . . . . . 212
M
MFA-AR/AXC . . . . . . . . . . . . . . . . . . . . . 386 . . . . . . . . . . . . . . . . . . . . . . 388 MFA-AXCBF
401
Index
MicroREX D21 . . . . . . . . . . . . . . . . . . . . 339 MP. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 387 MSEX. . . . . . . . . . . . . . . . . . . . . . . . . . . 342 MTP 10. . . . . . . . . . . . . . . . . . . . . . . . . 341 MTV 1/010. . . . . . . . . . . . . . . . . . . . . . 341 MUB. . . . . . . . . . . . . . . . . . . . . . . . . . . . 102 MUB EC. . . . . . . . . . . . . . . . . . . . . . . . . . 94 MUB/F. . . . . . . . . . . . . . . . . . . . . . . . . . 260 MUB/T . . . . . . . . . . . . . . . . . . . . . . . . . . 118
S
S2S 160. . . . . . . . . . . . . . . . . . . . . . . . . 340 S5S 100T1 . . . . . . . . . . . . . . . . . . . . . . 340 S5S 100T3 . . . . . . . . . . . . . . . . . . . . . . 340 SC1/D . . . . . . . . . . . . . . . . . . . . . . . . . . 331 SC2/D . . . . . . . . . . . . . . . . . . . . . . . . . . 331 SD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 385 SDM. . . . . . . . . . . . . . . . . . . . . . . . . . . . 369 SD-PRF . . . . . . . . . . . . . . . . . . . . . . . . . 285 S-DT2 DKT. . . . . . . . . . . . . . . . . . . . . . . 340 S-DT2 GKT. . . . . . . . . . . . . . . . . . . . . . . 340 S-DT2 SKT. . . . . . . . . . . . . . . . . . . . . . . 340 S-ET 10, . . . . . . . . . . . . . . . . . . . . . . . . 341 S-ET 10E. . . . . . . . . . . . . . . . . . . . . . . . 341 SF 24A . . . . . . . . . . . . . . . . . . . . . . . . . . 344 SF 24A-S2. . . . . . . . . . . . . . . . . . . . . . . 344 SF 24A-SR. . . . . . . . . . . . . . . . . . . . . . . 344 SF 230A. . . . . . . . . . . . . . . . . . . . . . . . . 344 SG . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 357 SG AR/AXC, SG-AW . . . . . . . . . . . . . . . 385 SG AW-D. . . . . . . . . . . . . . . . . . . . . . . . 386 SM 230A. . . . . . . . . . . . . . . . . . . . . . . . 344 SN. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 390 SRK . . . . . . . . . . . . . . . . . . . . . . . . . . . . 364 SRKG. . . . . . . . . . . . . . . . . . . . . . . . . . . 370 SSD . . . . . . . . . . . . . . . . . . . . . . . . . . . . 374 SSGE/F . . . . . . . . . . . . . . . . . . . . . . . . . 379 SSG/F. . . . . . . . . . . . . . . . . . . . . . . . . . . 378 SSVE, SSVE/F . . . . . . . . . . . . . . . . . . . . 377 SSV, SSV/F. . . . . . . . . . . . . . . . . . . . . . . 382 STDT 16, STDT 16E. . . . . . . . . . . . . . . . 342 STG . . . . . . . . . . . . . . . . . . . . . . . . . . . . 372
TM 10 . . . . . . . . . . . . . . . . . . . . . . . . . . 337 TOB . . . . . . . . . . . . . . . . . . . . . . . . . . . . 372 TOS . . . . . . . . . . . . . . . . . . . . . . . . . . . . 372 Trafo 15/D . . . . . . . . . . . . . . . . . . . . . . 339 TTC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 335 TT-S1. . . . . . . . . . . . . . . . . . . . . . . . . . . 335 TT-S4/D. . . . . . . . . . . . . . . . . . . . . . . . . 336 TUB/TUS. . . . . . . . . . . . . . . . . . . . . . . . 372
O
Optigo OP 5 . . . . . . . . . . . . . . . . . . . . . 336 Optigo OP 10 . . . . . . . . . . . . . . . . . . . . 336 ORH. . . . . . . . . . . . . . . . . . . . . . . . . . . . 357
U
U-EK 230E EX. . . . . . . . . . . . . . . . . . . . 338 UGS. . . . . . . . . . . . . . . . . . . . . . . . . . . . 370
V
VBC . . . . . . . . . . . . . . . . . . . . . . . . . . . . 352 VBF . . . . . . . . . . . . . . . . . . . . . . . . . . . . 353 VBK. . . . . . . . . . . . . . . . . . . . . . . . . . . . 367 VBR. . . . . . . . . . . . . . . . . . . . . . . . . . . . 365 VK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 356 VK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 368 VKA-P . . . . . . . . . . . . . . . . . . . . . . . . . . 285 VKK . . . . . . . . . . . . . . . . . . . . . . . . . . . . 356 VKS-P . . . . . . . . . . . . . . . . . . . . . . . . . . 285 VKS, VKM, VKS-EX, VKSV-EX . . . . . . . . 380 VKV/F, VKVE/F, VKG/F . . . . . . . . . . . . . 383 VKVM . . . . . . . . . . . . . . . . . . . . . . . . . . 384 VP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 285
P
PGK . . . . . . . . . . . . . . . . . . . . . . . . . . . . 360 PKDM12 . . . . . . . . . . . . . . . . . . . . . . . . 324 PRF . . . . . . . . . . . . . . . . . . . . . . . . . . . . 276 Pulser . . . . . . . . . . . . . . . . . . . . . . . . . . 334 Pulser M . . . . . . . . . . . . . . . . . . . . . . . . 334 PXDM5A. . . . . . . . . . . . . . . . . . . . . . . . 324
R
RADT. . . . . . . . . . . . . . . . . . . . . . . . . . . 333 RB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 359 RBK . . . . . . . . . . . . . . . . . . . . . . . . . . . . 368 RBM . . . . . . . . . . . . . . . . . . . . . . . . . . . . 360 R-DK4 KT (EX) . . . . . . . . . . . . . . . . . . . . 323 RE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 320 RED . . . . . . . . . . . . . . . . . . . . . . . . . . . . 364 REE . . . . . . . . . . . . . . . . . . . . . . . . . . . . 321 REE S0. . . . . . . . . . . . . . . . . . . . . . . . . . 322 REE TR0. . . . . . . . . . . . . . . . . . . . . . . . . 322 REPT . . . . . . . . . . . . . . . . . . . . . . . . . . . 331 RETP . . . . . . . . . . . . . . . . . . . . . . . . . . . 331 REU . . . . . . . . . . . . . . . . . . . . . . . . . . . . 320 REV . . . . . . . . . . . . . . . . . . . . . . . . . . . . 340 REV DVV . . . . . . . . . . . . . . . . . . . . . . . . 340 RS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78 RSA (F) . . . . . . . . . . . . . . . . . . . . . . . . . 384 RSI. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84 RSK . . . . . . . . . . . . . . . . . . . . . . . . . . . . 355
W
WBK . . . . . . . . . . . . . . . . . . . . . . . . . . . . 389 WBK-W . . . . . . . . . . . . . . . . . . . . . . . . . 389 WSD . . . . . . . . . . . . . . . . . . . . . . . . . . . . 370 WSD-KBT . . . . . . . . . . . . . . . . . . . . . . . . 371 WSD PRF. . . . . . . . . . . . . . . . . . . . . . . . 285 WSG . . . . . . . . . . . . . . . . . . . . . . . . . . . . 370 WVA/WVI. . . . . . . . . . . . . . . . . . . . . . . 268
T
T 120. . . . . . . . . . . . . . . . . . . . . . . . . . . 339 TDA DV . . . . . . . . . . . . . . . . . . . . . . . . . 371 TFR . . . . . . . . . . . . . . . . . . . . . . . . . . . . 343 TFSR/TFSK . . . . . . . . . . . . . . . . . . . . . . 126 TFSR/TFSK EC. . . . . . . . . . . . . . . . . . . . 124 TG . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 373 TG 300-800, 400-800. . . . . . . . . . . . . 372 TG-A 130 . . . . . . . . . . . . . . . . . . . . . . . . 338 TG-K330. . . . . . . . . . . . . . . . . . . . . . . . 338 TG-KH/PT1000. . . . . . . . . . . . . . . . . . . 338 TG-R4/R5/PT1000. . . . . . . . . . . . . . . . 338 TG-R430/530. . . . . . . . . . . . . . . . . . . . 338 TG-R600/630. . . . . . . . . . . . . . . . . . . . 338 TG-UH/PT1000. . . . . . . . . . . . . . . . . . . 338 THB. . . . . . . . . . . . . . . . . . . . . . . . . . . . 373 THS . . . . . . . . . . . . . . . . . . . . . . . . . . . . 373
Z
ZHZ . . . . . . . . . . . . . . . . . . . . . . . . . . . . 389 ZRS . . . . . . . . . . . . . . . . . . . . . . . . . . . . 164 ZSD . . . . . . . . . . . . . . . . . . . . . . . . . . . . 386 ZTV/ZTR . . . . . . . . . . . . . . . . . . . . . . . . 390
Index
RT 0-30. . . . . . . . . . . . . . . . . . . . . . . . . 337 RTRD. . . . . . . . . . . . . . . . . . . . . . . . . . . 321 RTRDU. . . . . . . . . . . . . . . . . . . . . . . . . . 321 RTRE . . . . . . . . . . . . . . . . . . . . . . . . . . . 320 RVAZ4-24. . . . . . . . . . . . . . . . . . . . . . . 339 RVAZ4-24A . . . . . . . . . . . . . . . . . . . . . . 339 RVK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 RVK 315Y4. . . . . . . . . . . . . . . . . . . . . . 202
402