Documente Academic
Documente Profesional
Documente Cultură
M MURIITHI 1
Course content
DC motor and generator; equivalent coupled circuits for electrical & energy conversion,
performance, characteristics, testing and speed control.
Transformers; couple circuits & two winding transformers. Equivalent circuits & phase
diagrams of single-phase transformer. Transformer efficiency & regulation. Three-phase
winding, connecting, grouping & operation. Three phase induction motors; operation,
equivalent circuit, performance characteristics & control. Synchronous Motors. Adjusting The
Field Excitation
Course prerequisites
This course assumes a sound background in Circuit Theory
Methods of delivery(teaching)
Types and quantities of teaching activities: Lectures/Tutorial: 3hrs per week. Laboratory
experiments: Per Lab time table.
Teaching and learning materials: Lecture notes.
Type of student activities: Normal lecture attendance.
Feedback mechanisms to students: Strict attendance of lectures and tutorial classes.
(ii) Assessment & Grading
Final Exam 70%
CAT 1,2,3 10%
Homework Assignments 5%
1,2,3
Laboratory 15%
TOTAL 100%
EMM 214
EMM 214 ELECTRICAL ENGINEERING II DR C. M MURIITHI 2
1. ELECTROMAGNETISM: INTRODUCTION TO
MACHINE THEORY
1.1 Introduction
Electromagnetism is the energy conversion process whereby electrical energy is
converted to mechanical energy and vice-versa by means of an electromagnetic
system.
In this topic we’ll explain how mechanical forces can be developed by magnetic
attraction and alignment and how rotary motion therefore be realized
N N
Force of attraction
Force of attraction
Force of alignment
S S
(a) (b)
Fig 2.1 Force of attraction and alignment
In fig 2.1(a) the two poles are situated opposite one another and a flux passes from
one to the other and hence they are attracted towards one another.
The force of alignment acts in any direction that will increase the magnetic energy
stored in the arrangement. In fig 2.1(a) it will try to bring the poles together since
these decreases the reluctance of the air gap in the magnetic circuit and hence will
increase the flux and consequently stored energy.
In fig 2.1(b), poles are not situated opposite one another. The resultant forces tries
to achieve greater stored energy by two component:
2
EMM 214
EMM 214 ELECTRICAL ENGINEERING II DR C. M MURIITHI 3
Frotor
Fstator
(a)
(b)
The centrally pivoted rotor magnet position as in fig 2.2(a) will not have any
tendency to turn. Suppose that there is an angular displacement δ, between the two
magnetic axes, fig 2.2(b).
EMM 214
EMM 214 ELECTRICAL ENGINEERING II DR C. M MURIITHI 4
As indicated by the arrows, and also by the field lines round the conductors, forces
will be exerted both attractive and repulsive tending to bring the magnets into
alignment.
The total force and the corresponding turning moment (torque) will vary with the
angular position being a maximum when δ =90o.
If H is decreased and reversed, the curve does not retrace the same path.
Energy expended in domain changes is not all recoverable and the domains retain
their new magnetic axes. Consequently, when H=O, there is a residual value of
flux density the magnitude of which, Bres, depends on the material, its crystal
structure and the value of B.
To bring B=O requires a coercive field intensity, coersivity, HC, which is
negative.
EMM 214
EMM 214 ELECTRICAL ENGINEERING II DR C. M MURIITHI 5
Fig 2.5
1.3.1 IRON LOSSES
a) Hysteresis loss
If a ring of iron with cross-section area A, mean circumferential length l is
magnetized by a coil carrying i amperes through N turns, the supply must
(d )
provide a component of voltage e N to sustain a changing current and
dt
flux and to account for i*R work done against emf in time dt:
( B A) Hl
e i dt N dt............................2.2
dt N
where B- flux density
N i A
H ......................................................2.3
l m
(b) Eddy Current Loss
Since iron is a conductor, a changing flux induces emfs and currents within
the iron mass. These eddy current produce losses, heating and
demagnetisations.
1.4 Magnetic Circuit Calculation
Basically, there are two types of magnetic circuits, called series and
parallel.
Analogous to electric circuits a magnetic series circuit is one in which the flux
set up by the current-carrying coil, the excitation, is common throughout the
entire circuit. Parallel circuits are defined as those having more than one path
for the flux to close.
Air gaps may be present which have a significant influence on the excitation
requirements.
Air gaps may be introduced on purpose such as the air gap in rotating machine
to separate the rotating member from the stationary one.
Typical, in magnetic circuit calculations, it is desired to determine the required
MMF or flux density for a specific condition.
5
EMM 214
EMM 214 ELECTRICAL ENGINEERING II DR C. M MURIITHI 6
EMM 214
EMM 214 ELECTRICAL ENGINEERING II DR C. M MURIITHI 7
EMM 214
EMM 214 ELECTRICAL ENGINEERING II DR C. M MURIITHI 8
Eddy current tend to flow perpendicular to the flux and in such as to oppose
any changes in the magnetic field.(Lenz’s law)
Both Hysteresis and eddy current losses (core losses) greatly affect operating
temperatures, efficiencies and rating of magnetic devices.
Assume that the two cores have the same cross-sectional area of square meters
and are a small distance of l meters apart.
If the coil carries a current it will set up a flux density of B in the air gap.
Mathematically the attractive force Fm between the two-iron surfaces is equal
to:
B2 A
Fm ..N
2 o
8
EMM 214
EMM 214 ELECTRICAL ENGINEERING II DR C. M MURIITHI 9
To prove the above consider the force of alignment between two poles of a
magnetic circuit as shown:
2) Suppose that the poles can be separated by a small distance dx, with B,
Ф remaining constant.
The work done due to the forces between the poles will then be:
dWm F dx
3) Assume now that the magnetic core is ideal, that is, it is of infinite
permeability and therefore requires no MMF to create a magnetic field in it.
Thus the stored magnetic energy will be contained entirely in the air-gap.
When the contacts separate the air gap is increased by a volume A*dx but
since the flux density ,B, is constant the energy density is also constant.
The increase in stored energy will be given by:
B2
dW f A dx
2 o
And since the system is ideal,
dWm dW f
B2
F dx A dx
2 o
B2
F A
2 o
Example
The poles faces of a lifting magnet shown have an area of 200cm2 which is
also the cross sectional area of the 60 cm long flux path in the cast steel
magnet. The poles faces are 30 cm apart. Determine the coil current required
on the magnet to lift 267kg of cast iron plate separated by 1mm from the poles
faces.
EMM 214
EMM 214 ELECTRICAL ENGINEERING II DR C. M MURIITHI 10
2. Transformer Theory
2.1. General introduction
Bulk electrical energy is generated by medium voltages (e.g., 11-kV) at places, which
are often far away from the places of its consumption (e.g., urban centres,
industries, homes, etc.). This energy is transmitted with minimum loss over
these long distances by high voltages (e.g., 110, 132, 220 kV), but low
utilisation voltages (e.g., 415/240 V in Kenya) are necessary to operate most of
the end-use electrical appliances and/or applications, and also for safe handling
of electric circuits. The ―transformer‖ is the electrical device that allows
electrical energy to be received at one voltage and delivered at another voltage
(higher or lower). That is, a transformer is a piece of static electric device
designed to convert electric energy received at one voltage (current) into one at
another voltage (current) by means of electromagnetic induction. Remember
that according to law of electromagnetic induction, a changing magnetic field
flux linking or cutting a circuit will always induce a voltage in that circuit
whose magnitude is proportional to the rate of change of flux-linkages.
10
EMM 214
EMM 214 ELECTRICAL ENGINEERING II DR C. M MURIITHI 11
The power received and that delivered by a transformer is equal and has same
frequency but different values of voltage and current.
In its simplest form, a transformer consists of a core of sheet (laminated) steel and
two or several windings which are electrically separated but linked together by a
common magnetic flux (i.e., coupled electromagnetically) (see Fig. #1). The purpose
of the core is to enhance the inductive (magnetic) coupling between the windings
(coils), and the objective of using a laminated core is to reduce eddy currents. The
winding receiving the energy (i.e., the one in which electric energy is fed into from
the AC supply mains) is called primary winding. All the quantities associated with
this winding are also called primary (primary turns, primary voltage, primary current,
etc.), and their symbols are indexed ―1‖. The transformer winding delivering energy
to the load (i.e., from which energy is drawn out) is called secondary winding, and all
the quantities associated with it are referred to as secondary and indexed ―2‖.
A transformer with only two windings is called a double-wound transformer; a
transformer with three or more windings is termed multi-winding transformer.
Other transformer classifications include: (a) single- and poly-phase
transformers (depending on the type of circuit in which a transformer is used or
operated); (b) step-up [V1 V2] and step-down [V1 > V2] transformers; (c)
power and instrumentation transformers, depending on the application; (d)
core-type and shell-type transformers; (e) dry-type, liquid-filled and gas-filled
transformers, depending on the cooling medium used; (f) general-purpose and
special-purpose transformers; (g) indoor and outdoor transformers, depending
on installation environment; (h) transmission and distribution transformer,
depending on purpose in a power system.
Thus, the sphere of transformer application is very wide. The focus of this topic is on
the basic design features and operating principles of general-purpose, single-
phase, two-winding transformers.
EMM 214
EMM 214 ELECTRICAL ENGINEERING II DR C. M MURIITHI 12
winding and consequently through the load, which is connected to the secondary
terminals 2 – 2/.
In this way AC power (p1 = v1.i1) is transferred from the primary circuit to the
secondary circuit (i.e., p2 = eM2.i2). To improve the efficiency of this power transfer,
the electromagnetic linkage between the windings must be enhanced.
Electromagnetic linkage between the primary and secondary windings may be
enhanced by using a laminated core assembled from steel sheets. The transfer of
power from the primary to the secondary is also affected by the design of the primary
and secondary windings.
1 I1 I2
2
V1 E1 E2 V2
1/ 2/
Fig. 2 (b). Schematic diagram
12
EMM 214
EMM 214 ELECTRICAL ENGINEERING II DR C. M MURIITHI 13
through it. The resulting MMF i1N1 produces an alternating magnetic flux through the
iron core. As the current drawn by the primary winding is alternating at a frequency
of f, the flux produced will also have the same frequency. The flux produced by i1
and linking both the primary and secondary windings is called the mutual flux, and is
denoted 12 and its maximum value — m. That part of the flux produced by i1, but
linking only the primary winding is called primary leakage flux, and denoted 11. If
the secondary circuit is complete and current i2 flows, then a leakage magnetic flux
linking only the secondary winding, denoted 22, will be produced. In turn, the
alternating fluxes 12, 11 and 22 produces alternating EMFs of mutual- and self-
induction in the primary and secondary windings.
The polarity of the mutually induced voltages in a transformer reflects the reaction
against the changing flux that creates the voltages. That is, the polarity of a
mutually induced voltage in the secondary coil by the flux produced by a
current in the primary coil will be such that it will tend to establish a secondary
current that produces a flux directed opposite to the one that produces this
voltage (i.e., Lenz’s law). Mathematically, this may be expressed as follows:
di1
e2 M
dt
The polarities of voltages mutually induced in both the primary and the secondary
coils may also be indicated using a method known as dot convention (instead
of the reaction method). In the dot convention method, a dot is placed on one
terminal of each coil. These dots carry the sign information regarding the
mutually induced voltages.
There are two problems associated with polarity dots. One is to determine a proper
set of dot markings when the physical arrangement of the coupled coils is
given. The other is to determine how the dots are used in writing the circuit
equations that describe the two magnetically coupled windings of the
transformer.
13
EMM 214
EMM 214 ELECTRICAL ENGINEERING II DR C. M MURIITHI 14
(iii) Use right-hand rule to determine the direction of the magnetic field flux
established by the primary current i1 inside the coupled coils. This flux is
labelled 21.
(iv) Arbitrarily pick one terminal of the secondary coil and assign a current
into this terminal. For example the upper terminal 2, and label this
current i2.
(v) Use right-hand rule to determine the direction of the flux established by
the secondary current i2 inside the coupled coils. This flux is marked
12.
(vi) Compare the directions of the two fluxes 21 and 12. If the fluxes are
additive, a dot is placed on the terminal of the secondary coil where the
test secondary current enters. If the fluxes are subtractive, a dot is placed
on the terminal of the secondary coil where the test secondary current
leaves.
EMM 214
EMM 214 ELECTRICAL ENGINEERING II DR C. M MURIITHI 15
(t) = m sin (t ), then according to Faraday’s law of electromagnetic induction,
the instantaneous value of voltage or EMF induced in an ideal coil is equal to the time
rate of change of the flux linking the coil. That is,
d d d
e(t ) N N sint (2.1)
dt dt dt m
The differentiation of the above equation gives the following expression for the
induced EMF:
e(t ) N sint / 2 (2.2)
m
This last equation is in the form
e(t ) E m sint e (2.3)
Thus the maximum value of the induced voltage or EMF is Em = 2fNm, and its
phase is e = - /2 (i.e., the induced EMF lags the mutual flux by 900). Therefore,
the RMS value of the induced voltage (EMF) in a coil is
Em 2fN m
E 4.44 fN m (2.4)
2 2
The equation (2.4) is called the general transformer equation. This equation may
be written for the primary and secondary windings of a transformer having
respectively N1 and N2 number of turns as follows:
E1 4.44 fN 1 m (2.5)
E 2 4.44 fN 2 m (2.6)
It follows from the last set of equations that
E1 N 1
k (2.7)
E2 N 2
The constant k which is equal to the winding turns ratio is called the voltage
transformation ratio (or simply, transformation ratio) of a transformer.
As mentioned above, the currents i1 and i2 also produces alternating leakage
fluxes 11 and 22, which in turn produces alternating EMFs of self-induction in the
respective windings. The magnitude of the EMF of self-induction produced in the
windings can be determined thus:
di1 di 2
e s1 L11 ; e s 2 L22 (2.8)
dt dt
where L11 and L22 are leakage inductance of the primary and secondary windings,
respectively (i.e., inductance parameters relating the voltage induced in the primary
and secondary windings due to alternating currents in the respective windings). In
phasor form, these equations can be written as follows:
15
EMM 214
EMM 214 ELECTRICAL ENGINEERING II DR C. M MURIITHI 16
In general, the inductive and resistive voltage drops appearing in the above equation
are small and therefore can be neglected in most approximate analysis tasks. In
this case, the voltage across the terminals of the primary winding (i.e., source
voltage) will be equal to the EMF induced in it by the mutual flux. That is,
V ( E ) (2.12)
1 1
Using a similar analysis, the following voltage equation can be written for the
secondary winding when it is connected to an external load ZL:
E 2 E s2 I2 R2 I2 Z L (2.13)
or
I Z E jI X I R E I ( R jX ) E I Z (2.14)
V2 2 L 2 2 2 2 2 2 2 2 2 2 2 2
The voltage equations (2.11) and (2.14) are the fundamental transformer voltage
equations and are the widely used in transformer theory and analysis.
Having derived the transformer voltage equations, we now turn to its MMF and
hence current equation. In order to derive the transformer current equation it is
convenient to assume two working conditions: no-load (when a voltage v1 is applied
across the terminals of the primary winding with the secondary winding circuit open-
circuited), and on-load (when the secondary winding circuit is not open-circuited).
Under the no-load conditions, the current i1 flowing in the primary winding is called
exciting current and denoted i0. It is the current necessary to produce the mutual flux
in the magnetic core. The MMF produced by this exciting current, F0 is given by the
expression:
F0 = F12 = i0N1 = 12Rm, (2.14)
where Rm is the reluctance of the magnetic circuit of the transformer core.
If the transformer is now loaded (i.e., a load Z2 is connected across the terminals
of the secondary winding), a current i2 will now flow. This current flowing in the
secondary winding will create a MMF i2N2, which, according to Lenz’s law, tends to
16
EMM 214
EMM 214 ELECTRICAL ENGINEERING II DR C. M MURIITHI 17
reduce the amplitude of the same flux in the core. But, in a lossless transformer, the
amplitude of the core flux must not change, since it is responsible for always
inducing an emf equal to the applied voltage into the primary winding (see Eq. 2.12).
Therefore, when a load is connected to the secondary, additional primary current
must flow in order to develop a primary MMF component which exactly cancels the
secondary MMF. That is, the current flowing in the primary winding will increase
from i0 to i1 and the MMF, which produces the mutual flux, is now a summation of
the primary and secondary MMFs, F1 and F2. That is,
F12 = F1 + F2 = 12Rm = i1N1 + i2N2 (2.15)
If we assume a constant value for the mutual flux, then we can write down the
following phasor MMF equation:
F0 F12 F1 F2 (2.16)
or
I0 N 1 I1 N 1 I2 N 2 (2.17)
From this phasor MMF equation, it follows that
I1 N 1 I0 N 1 ( I2 N 2 ) (2.18)
Solving for I1 yields
I I N 2 I I I /
(2.19)
1 0 N 2 0 1
1
N
where I1/ 2 I2 is the load component of the primary current (i.e., the additional
N1
primary current that must flow in order to develop a primary MMF component which
exactly cancels the secondary MMF).
From the current equation (2.19), it follows that the primary current can be
considered as the sum of the two components: the exciting component, which
produces the mutual flux in the core, and load component, which produces a
MMF in the primary that compensates the demagnetising effect of the
secondary MMF. In good transformers, the exciting current is usually less than
5% of the current which the primary winding can be expected to pass when full
load is connected to the secondary.
As the transformer is loaded, the load component of the primary increases and
becomes much larger than the exciting current component. Therefore, under
load conditions, the above current equation reduces to
V1
I0x1
I I / - N 2 I I2 (2.20)
1 1 2
N1 k I0r1
- E1
The exciting current as described above, is composed of two components,
magnetising
V
current Im and current-supplying core losses Ic. The current-supplying
1
I0 m
I0 17
Ic
EMM 214 E2 = V2
m
Im
Fig. 3 E1
EMM 214 ELECTRICAL ENGINEERING II DR C. M MURIITHI 18
core losses is also composed of two components. One supplies the eddy-current
losses, and the other supplies hysteresis losses. The magnetising current being in
phase with the mutual flux, while the current-supplying core losses leading the
mutual flux by 90o (see Fig. #3)
The equations (2.11), (2.14), and (2.19) are the fundamental equations required to
carry out an analysis of transformer operation. For a phasor analysis of
transformer operation, these equations must all be represented as phasors
drawn on the same complex number plane. This, however, raises two main
computational difficulties. First, because of the generally large differences in
the numerical values of primary and secondary voltages and currents, drawing
their phasors on the same complex plane often raises a scaling difficulty. The
second difficulty is that of summing voltages and/or currents associated with
two electrically de-coupled circuits. This operation is complicated by the
difference in the number of turns in both the primary and secondary winding.
These difficulties complicate both the graphical and analytical study of
transformer operation. To overcome these difficulties, the parameters (EMF,
voltage, current, impedance) of the transformer are often scaled (or referred) to
the same number of winding turns. Generally, we refer (scale) secondary
parameters to the primary winding turns.
Scaling (referring) secondary circuit parameters to the primary side has the effect of
replacing a real transformer with a transformation ratio k = N 1/N2, with an
equivalent one having a transformation ratio k = N1/N2/ = 1, where N2/ = N1.
All the parameters associated with the scaled (referred) secondary
winding/circuit bear the same notation as in the real winding, but with a
superscript prime (/) sign: E2/, I2/, R2/, X2/, etc. This process replaces a real
transformer (in which the primary & secondary circuits are coupled
magnetically) with a system whose elements now have a voltaic (galvanic) or
electrical linkage. This system is what is generally referred to as transformer
equivalent circuit model (or simply as transformer equivalent circuit).
In scaling (referring) the secondary parameters of a transformer to its primary side it
is necessary to ensure:
(1) Invariance of secondary MMF, that is, equality of the real and scaled (referred)
secondary MMF: I2/N2/ = I2N2, whence I2/ = I2N2/N1 = I2/k.
(2) Invariance of power associated with the secondary winding, that is, equality of the
electromagnetic power of the real and scaled (referred) secondary: E2/I2/ = E2I2,
whence E2/ = E2I2/I2/ = kE2. Similarly, from the equality of apparent power V2/I2/ =
V2I2, we obtain V2/ = kV2.
18
EMM 214
EMM 214 ELECTRICAL ENGINEERING II DR C. M MURIITHI 19
(3) Invariance of resistive power losses in the secondary, that is equality of ohmic
power losses in the real and scaled (referred) secondary: (I22)/R2/ = I22R2, whence
R2/ = k2R2.
(4) Invariance of reactive losses in the secondary, that is equality of reactive power
losses in the real and referred (scaled) secondary: (I22)/X2/ = I22X2, whence X2/ =
k2X2.
The voltage and the current equations for the equivalent transformer obtained by
referring (scaling) the secondary to the primary can be written as follows:
V E I ( R jX ) E I Z (2.21)
1 1 1 1 1 1 1 1
V2 E 2 I2 ( R2 jX 2 ) E 2 I2 Z 2
/ / / / / / / /
(2.22)
I I I / I I / (2.23)
1 0 1 0 2
In the general case, the problem of deriving an equivalent circuit model for a
transformer may have several solutions, but each of which should satisfy the
fundamental voltage and current equations derived above.
According to the derived voltage and current equations, we can obtain the so-called
equivalent T-or exact circuit model of a transformer. In this model, the
transformer is represented as a combination of three branches, the primary one
with an impedance Z1 and current I1, the magnetising one with an impedance
Z0 and current Io, and the secondary branch connected in parallel with the
magnetising branch and with an impedance Z2/ + ZL/ and current I2/. This
transformer equivalent circuit model is shown in Fig. #4 (student to draw the
corresponding phasor diagram).
If we assume that the impedances R1 and X1 usually have relatively low values, then
the voltage drop across them can be ignored and the voltage induced in the
primary winding E1 taken as approximately equal to the supply voltage V1.
With this approximation the equivalent circuit called the gamma ( ) circuit is
obtained (student to draw this circuit and its phasor diagram). In this model,
the exciting current is not a function of the load on the transformer and makes
calculations much easier.
Another approximate transformer equivalent circuit can be obtained by assuming that
the exciting current is a very small percentage of the primary current, under
normal operating conditions. If this exciting current is ignored entirely, then
the circuit that results is called the series impedance approximate equivalent
circuit (student to draw the resulting circuit and its phasor diagram).
Since the leakage reactance of a transformer is usually significantly larger than the
winding resistances, the resistance in the equivalent series impedance circuit
model is often neglected. This gives a series reactance approximate circuit
model.
19
EMM 214
EMM 214 ELECTRICAL ENGINEERING II DR C. M MURIITHI 20
I1 - I/2
r1 jx1
r/2 jx/2
r0
I0
E V1 E1 = E/2 V/2 Z/L
jx0
EMM 214
EMM 214 ELECTRICAL ENGINEERING II DR C. M MURIITHI 21
by both the eddy-currents and hysteresis in the core. In such a case, the efficiency of a
transformer, may then be given by the expression:
P2 P2 V2 I 2 cos 2
(2.27)
P1 P2 Pc Pw V2 I 2 cos 2 Pc Pw
The winding losses Pw is normally given as the sum of the losses in the primary
and secondary windings: Pw I 12 R1 I 22 R2 . These losses depend on the loading of the
transformer and are, therefore, appropriately called variable losses.
The core losses depend not on the transformer load, but only on the magnitude
and frequency of the core magnetic flux. These losses are considered constant.
For a transformer operating under load conditions, the secondary voltage may be
taken as equal to its rated value, V2r, and the core losses taken as constant. In practice,
however, during transformer load operations, its secondary winding current may not
always be equal to its rated value, I2r. Therefore, a load factor, = I2/I2r is normally
introduced when calculating the efficiency. Thus, under load conditions, the
efficiency is determined by the equation:
.V2 r I 2 r cos 2 .S r cos 2
(2.28)
.V2 r I 2 r cos 2 I 2 r R Pc .S r cos 2 2 Pw Pc
2 2
If we depict the above expression as efficiency () versus load factor () function,
then its analysis would show that maximum efficiency results when the
Pc
winding losses are equal to the core losses. That is, if 2Pw = Pc or .
Pw
The transformer output power is measured using either a combination of an ammeter
and a voltmeter, or a single-phase wattmeter. Core losses can approximately be
determined from transformer no-load test data, while winding losses can be
estimated from the transformer short-circuit test data.
EMM 214
EMM 214 ELECTRICAL ENGINEERING II DR C. M MURIITHI 22
equal to the rated primary voltage, V1,rtd. The expression for regulation is then
written as:
V1, rtd . V2/
VR 100 (2.30)
V1, rtd
where V2/ is the secondary voltage referred to the primary side.
From the series impedance approximate equivalent transformer circuit and its phasor
diagram it follows that
V1, rtd V2/ I 1 Req cos 2 X eq sin 2 (2.31)
and the formula for percentage transformer regulation becomes
I 1 Req cos 2 X eq sin 2
VR % 100 (2.32)
V1, rtd
Just like the transformer efficiency, regulation can also be estimated from
transformer tests data. This can be done by recognising that the products I 1Req and
I1Xeq in the Eq. (2.32) gives the transformer resistive voltage drop Vp and inductive
voltage drop Vq, respectively. Since under short-circuit condition the whole of the
supply voltage is equal to the voltage drop in the transformer windings, then we can
express Vp and Vq in terms of the short-circuit voltage as:
Vp = V1,sc.cossc (2.33)
Vp = V1,sc.sinsc (2.34)
By substituting these voltage drop expressions into Eq. (2.32) and using the
trigonometric identity cos cos + sin sin = cos( - ), we can re-write
Eq. (2.32) in terms of the short-circuit test data as follows:
V1, sc cos sc 2
VR % 100 (2.35)
V1, rtd
where V1,sc — primary short-circuit voltage; sc — primary short-circuit power
factor angle; 2 — load power factor angle.
From Eqs. (2.32) and (2.35) it follows that, for a transformer of specified short-
circuit parameters, the VR% depends on the type of the load (i.e., resistive, inductive,
or capacitive) and its magnitude. If we depict either of these equations as a %VR vs.
load power factor angle function, it can be established that maximum %VR results
when the load power factor angle is equal to the power factor angle under short-
circuit conditions.
A plot of secondary terminal voltage against the load when the load power factor
angle and primary voltage are assumed constant is called a load or an external
characteristic of a transformer. It is also one more measure of transformer
effectiveness and hence performance.
22
EMM 214
EMM 214 ELECTRICAL ENGINEERING II DR C. M MURIITHI 23
The above formula for the voltage regulation is used only when the transformer is
operating at rated load. For any other load determined by the load factor = P2/P2r,
the regulation of the transformer varies practically in proportion to the load factor.
23
EMM 214
EMM 214 ELECTRICAL ENGINEERING II DR C. M MURIITHI 24
3. DC MACHINES:
3.1 Principles of D.C. Machines:
`
Fig. 3.1
Consider a conductor of length L at right angles to a uniform magnetic field of
density B.
If the conductor moves as shown, the flux linking the conductor will change.
According to Faradays’ law an EMF is induced in a circuit placed in a magnetic field
if either:
1. the flux linking the circuit changes
24
EMM 214
EMM 214 ELECTRICAL ENGINEERING II DR C. M MURIITHI 25
2. There is a relative motion between the circuit and the magnetic field such that
the conductors forming the circuit cut across the field lines.
In fig. 3.1, a voltage, e volts will be induced in the conductor and hence circuit
because the conductor cuts the flux. If the conductor moves with a relative velocity V
with respect to the field, then
e B l ..............................3.1
where B – Magnetic flux density, T
l – Conductor length in the field, m
υ– Relative velocity between the field and conductor, m/s and voltage
polarity as indicated.
The polarity is determined using the right hand rule (RHR). According to this rule if
the right hand is held such that the thumb, forefinger and middle finger are mutually
perpendicular, the forefinger points in the direction of the field, B, the thumb in the
direction of the conductor motion with respect to field, the middle finger represents
the direction of the generated EMF, i.e. toward the positive terminal. RHR is also
called the generator rule.
EMM 214
EMM 214 ELECTRICAL ENGINEERING II DR C. M MURIITHI 26
26
EMM 214
EMM 214 ELECTRICAL ENGINEERING II DR C. M MURIITHI 27
Fig 3.6
Commutator action
EMM 214
EMM 214 ELECTRICAL ENGINEERING II DR C. M MURIITHI 28
When the armature rotates the vertical position, induced EMF in side ab and cd are
reversed respectively, but the commutator segments to which they are connected
simultaneously change positions under the stationery brushes. Hence both polarity of
the brushes and the direction of the current in the load remain fixed. This is called the
commutation process.
EMM 214
EMM 214 ELECTRICAL ENGINEERING II DR C. M MURIITHI 29
from instant to instant and are unaffected by the rotation of the armature, hence the
voltage generated in the terminals is constant.
At one instant in time there are some contacts in the inter-pole region which do not
face either one of the poles mounted on the stationery member, the stator. These
conductors are in neutral zone.
The ends of each armature coil are connected to a multiple segmented commutator.
The commutator is a distinctive element in the construction of the machines. It has
major setbacks of limiting the output power of the dc generators and adding to its
costs.
When multiple coils are joined in series aiding, the terminal voltage will increase.
Consider the relationship between the number of commutator segments and generated
voltage wave.
Fig 3.10
b) Four segment commutator
29
EMM 214
EMM 214 ELECTRICAL ENGINEERING II DR C. M MURIITHI 30
30
EMM 214
EMM 214 ELECTRICAL ENGINEERING II DR C. M MURIITHI 31
Drum Winding
The Drum type winding is made of coils, one of which is illustrated in Figure 3.14.
The straight portions of the coil are the parts rotating through the magnetic field in
which the voltage is induced. Therefore, each single coil has two conductors. This has
the advantage over the Gramme Ring winding where only one side of each coil is
used as an active conductor. There are two classes of drum windings depending upon
how the coils are connected to the commutator.
EMM 214
EMM 214 ELECTRICAL ENGINEERING II DR C. M MURIITHI 32
alternate brushes being positive and negative. Any winding can be illustrated in one
of two forms, the circular form or the development form. A simplex lap winding is
shown in Figure 3.16 (circular form) and Figure 3.17 (development form.) In this
particular circular form, the flux cutting portions of the conductors are shown as
straight lines radiating from the center and are numbered for convenience in
connecting them to the commutator which is in the center of the diagram. The
outermost connecting lines represent the end connections on the back of the armature
and the inner connecting lines represent the connections on the front or commutator
end of the armature. The development form of winding represents the armature as if it
were split open and rolled out flat. It is somewhat simpler to understand but the
continuity of the winding is broken. The lap winding is best suited for low voltage,
high current ratings because of the number of parallel paths.
32
EMM 214
EMM 214 ELECTRICAL ENGINEERING II DR C. M MURIITHI 33
33
EMM 214
EMM 214 ELECTRICAL ENGINEERING II DR C. M MURIITHI 34
34
EMM 214
EMM 214 ELECTRICAL ENGINEERING II DR C. M MURIITHI 35
35
EMM 214
EMM 214 ELECTRICAL ENGINEERING II DR C. M MURIITHI 36
EMM 214
EMM 214 ELECTRICAL ENGINEERING II DR C. M MURIITHI 37
Counter EMF
The developed force on the armature conductor causes the armature to rotate,
resulting in a change of flux linking of those current carrying conductors. Thus, the
motor also acts as a generator.
The motor action is stronger than the generator action because the direction of the
current in the armature winding is forced by the voltage supply.
The generated EMF is opposed to the impressed voltage to such an extent as to limit
the armature current to the value required to drive the shaft load. The generated EMF
is called counter (back) EMF.
37
EMM 214
EMM 214 ELECTRICAL ENGINEERING II DR C. M MURIITHI 38
Torque Relations
Power developed internally by the motor is
Pd EC I A ……………………….3.7
This power must be sufficient to drive the mechanical load on the motor shaft and
overcome all mechanical losses which include core losses, windage (the resistance to
overcome air friction when rotating) and friction losses in the bearing supporting the
armature.
Since generally, torque T = Fl then;
T B I l r....[ Nm]
where ………………………..3.8
F B I l
From generator equation, the generated emf is given by
E B l v ………………………………….3.9
Dividing the torque equation by the generated emf equation gives
E Bl v
or EI T …………………..3.10
T B I l r I
That is, the developed electrical power is equal to the developed mechanical power.
Energy conservation law is thus reinforced: electromechanical energy (electro
mechanics) involves the interchange of energy between and electrical and mechanical
system.
Since,
ZP
Ec n
60a
then ……………………………………3.11 `
EI A ZP
T I A KmI A
60a 2
Where,
ZP
Km is the motor constant.
60a 2
IA – armature current
The torque, T, developed by the armature depends on the main pole field strength and
the current in the armature for a specific machine.
EMM 214
EMM 214 ELECTRICAL ENGINEERING II DR C. M MURIITHI 39
When a generator supplies an electrical load, the current carrying armature winding
creates a magnetic field which interacts with the main pole field existing in the
machine. This in turn sets up a resulting distorted field.
Consider a two pole generator:
The resultant distribution of flux is a combination of main pole flux and flux set up
by armature current. Over the loading halves of the pole faces the armature flux in
opposition to the main flux, thereby reducing the flux density. Over the trailing
halves the two fluxes are in the same direction, so the flux density is increased.
In a generator, the effect of armature reaction is to distort the field flux in the
direction of rotation. For the motor, the magnetic neutral axis shifts against the
direction of rotation.
Interpoles
During the short time that the commutator segments, to which the armature coils are
connected, are passing under the brush the current must be completely reversed in the
coil.
If this reversal is not complete an arc will occur at the commutator segment that
moves under the brush. Sparking at the brushes causes the commutator to pit,
increasing brush wear and commutator wear.
Illustration
39
EMM 214
EMM 214 ELECTRICAL ENGINEERING II DR C. M MURIITHI 40
coils c b a
Armature motion
Ic Ic Ic Ic
Commutator segments 3 2 1
2Ic
Stationery brush
(a)
c b a
Armature motion
Ic Ic Ic
3 2 1
2Ic
(b)
c b a
Armature motion
Ic Ic Ic Ic
3 2 1
2Ic
(c)
Fig 3.25 a,b,c
The two ends of any coil are connected to adjacent commutator segments.
As the armature rotates, the segments will move over the brush. The time it takes for
the brush to move across the insulation between segments 1 and 2, the current in coil
B must change from Ic in one direction to Ic in the opposite direction.
The process begins as soon as the brush makes contact with segment 2 i.e. when the
brushes are placed on the magnetic neutral because the coil is then not cutting any
flux and no EMF is induced in it.
But the insulated coils are placed in iron, hence their inductance is increased. As a
result with large armature current and short commutation times a large EMF,
reactance voltage, will be induced in the coil undergoing commutation.
40
EMM 214
EMM 214 ELECTRICAL ENGINEERING II DR C. M MURIITHI 41
To overcome this reactance voltage, the brushes may be moved ahead of the neutral
axis in the direction of rotation for a generator and backwards in a motor.
Generally inter poles are used. They are connected such that they alternately have the
same polarity as the following main pole in the direction of rotation for a generator,
or the same polarity as the trailing pole in a motor. Thus an armature coil undergoing
commutation [e.g. position b Fig 3.25] in a generator is cutting flux which is in the
same direction as that of the next main pole. The result is an independent EMF in the
coil that opposes the reactance voltage.
Note also that since the reactance voltage depends on the armature current, the
amount of commutation flux to counteract it is made to vary. In very large machines,
there are also compensating winding which consist of a few turns placed in the main
pole faces. The resulting field produced by this winding is opposite to that produced
by the current in the armature conductors, hence helping to counteract the effect of
armature reaction.
41
EMM 214
EMM 214 ELECTRICAL ENGINEERING II DR C. M MURIITHI 42
This relation is non linear due to magnetic saturation after the field current
reaches a certain value. The plot EG verses If is known as open-current characteristic
of a generator.
42
EMM 214
EMM 214 ELECTRICAL ENGINEERING II DR C. M MURIITHI 43
IA
+
If + IL
E
G V
t
R
A
-
-
IA=IL
Fig 3.29 Circuit diagram of a separately excited DC generator
Generally,
Vt EG I A R A ……………………………………3.11
Where Vt – terminal voltage
IA – armature current (or load current)
Voltage regulation is the measure of how much the terminal voltage and
changes from no-load condition and is given by
VNL VFL
VR 100% ……………………………..3.12
VFL
Where VNL – No-load terminal voltage
VFL – Full load terminal voltage
It is important to note that the generated voltage, EG, is not a constant voltage for with
increasing loads on the generator armature reaction sets in and the drop in the
armature winding resistance.
43
EMM 214
EMM 214 ELECTRICAL ENGINEERING II DR C. M MURIITHI 44
IL
If IA
+
E
G V
t
R
A
IA=IL+If
Fig 3.30 Circuit diagram of Shunt generator
Connecting the field for self exultation the small voltage in the generators due to
remnant magnetism will be applied to the shunt field and drive a small current
through the field circuit.
If this resulting small current in the shunt field is of a direction that it weakens the
residual flux, the voltage remains near zero and there is not Vt build up, that is, the
weak main pole opposes the residual flux. But if the weak main pole aids the residual
flux the induced voltage will become larger. This in turn means more voltage applied
to the main field and the terminal voltage increases rapidly to a large constant value.
In the steady state the generated voltage causes a field current to flow that is just
sufficient to develop a flux required for the generated EMF that causes the field
current to flow.
The circuit carries only DC current, hence the field current depends only on the
field circuit resistance. This may consist of a field winding resistance Rf plus a field
rheostat resistance R in series with it.
For a given value of field circuit resistance RF, the field depends on the
generated voltage in accordance to Ohm’s law.
44
EMM 214
EMM 214 ELECTRICAL ENGINEERING II DR C. M MURIITHI 45
Rf>Rf3>Rf2>Rf1
Rf3=Rcritical
Fig 3.32
When the field circuit resistance is increased to Rf2 it changes the slope of the
field resistance line and thereby the terminal voltage. The terminal voltage can thus
be controlled by adjusting the field current.
The following can be noted as causes preventing the building up of the generated
voltage:
1. In case of a new machine or an old machine where the residual flux is lost,
magnetism is created by connecting a field winding to a separate DC source
for a few seconds a process called flashing the field.
2. The value of EMF is extremely sensitive to variation of field resistance. The
resistance Rf3 is called critical resistance and exceeding this Rf3 = Rcritical results
in failure of the generated voltage to build up.
3. Low armature speed will prevent the generator voltage to build up. At a
reduced speed the magnetization curve is adjusted according to the speed.
4. If the resulting small current in the shunt field is of a direction that it weakens
the residual flux, the voltage remains near zero and there is not Vt build up, that
is, the weak main pole opposes the residual flux.
The variation of terminal voltage with load current for a shunt generators is
greater than that of the separately excited generators.
This is because apart from the voltage drop due to the armature resistance and
armature reaction effect is there is an additional drop due to the flux decreasing with
increased loading which in turn decreases the terminal voltage.
45
EMM 214
EMM 214 ELECTRICAL ENGINEERING II DR C. M MURIITHI 46
3.3 DC MOTORS
3.3.1 General review and introduction
46
EMM 214
EMM 214 ELECTRICAL ENGINEERING II DR C. M MURIITHI 47
D.C motors is similar to a DC generator. The only difference is that generators the
EMF is greater then the terminal voltage, whereas in a motor the generated EMF
counter EMF is less then the terminal voltage. The power flow is thus reversed, that
is, the motor converts electrical energy into mechanical energy.
DC motors are better suited for many industrial process that demand a high
degree of flexibility in the control of speed and torque.
DC motor can provide high starting torque as well as high decelerating torque for
application requiring quick stoppage or reversals.
47
EMM 214
EMM 214 ELECTRICAL ENGINEERING II DR C. M MURIITHI 48
S
1 S2 IL
+
A1
V
L
IA
A2
IL=IA
Fig 3.34
If the field is connected in parallel with the armature winding, we obtain a shunt
machine.
IL
+
A1
S
1
V
L
If IA
S2
A2
IL=IA+If
Fig 3.35
The compound motor has both field windings. These field windings may be
connected so that the fields aid one another giving rise to a cumulative compound
motor.
Alternatively they may be connected so that the resulting fluxes oppose, as in the
differentially compound motor.
A compound motor may have a long shunt or a small shunt connection depending
on whether the shunt field is connected before or after the series field winding.
48
EMM 214
EMM 214 ELECTRICAL ENGINEERING II DR C. M MURIITHI 49
S S2 IL
1 +
IS
A1
F
1
V
L
If IA
F2
A2
IS=IA
IL=IA+If
Fig 3.36
Starting Dc Motors
At the instant of start up the counter EMF Ec is zero because the armature is not
rotating. The counter EMF serves to limit the current in the armature winding to a
value just sufficient to take care of the developed power needed to drive the load.
Hence if we start motor directly across a supply line, it draws a large current that
would cause mechanical shock to the armature and blow the fuse in the mains. For
instance connecting directly to a 230 v mains line, a motor with an armature
resistance equal to 0.25Ω, it would draw an armature current equivalent to;
230
IA 920 A
0.25
To avoid this from occurring, a resistance is connected in series with the armature to
off set the absence of the counter EMF. As the motor comes up to speed, this
resistance is taken out in steps because the counter EMF rises as the motor comes up
to full speed.
49
EMM 214
EMM 214 ELECTRICAL ENGINEERING II DR C. M MURIITHI 50
To start the motor, the main switch is closed and the starter arm is moved to contact
1. The motor starts. After the armature has accelerated sufficiently on the first contact
the starter arm is slowly moved to the following contacts until the iron keeper on the
starter arm is held by the holding coil electromagnet. This occurs in a few seconds.
In the final position no added resistance is in the armature circuit.
When there is power failure or if the field circuit should be opened accidentally, the
spring will return the starter arm to the off position, thereby shutting down the motor.
IA
I1 1 2 3 4 Contact numbers
I2
Steady State
Start up t1 t t3 t4 t
2
Fig 3.38
50
EMM 214
EMM 214 ELECTRICAL ENGINEERING II DR C. M MURIITHI 51
In a compound motor, the armature current IA and the flux Ф affect the speed.
The effect of the series field is removed under no load conditions, thereby weakening
the overall field flux. The result is then a larger increase in speed, since the speed is
inversely proportional to the flux. The change is about 15- 20%.
In the case of series motor, speed rises rapidly because at no–load condition only
residual magnetism flux is left. Hence series motors are not used in instance where
the load can be disconnected accidentally.
The general relationship between the speed and the load current for various motor
types is shown below.
Speed,
rpm, n
Shunt motor
Compound motor
Series motor
Load current, I
L
51
EMM 214
EMM 214 ELECTRICAL ENGINEERING II DR C. M MURIITHI 52
Fig 3.39
Shunt motor
Armature current, I
A
Fig 3.40
For current exceeding rated current a series motor develops the largest torque.
52
EMM 214
EMM 214 ELECTRICAL ENGINEERING II DR C. M MURIITHI 53
Fig 3.41
Disadvantages
1. By adding R, the speed of the motor, compared to that without connecting
any resistance, is always lower.
2. Method is ineffective at no load
3. Adding a resistance means increased power losses, I2R.
4. Constant- speed characteristic of the motor is lost.
Speed control is limited to 50% of rated speed.
Rf2>Rf1>Rf
Fig 3.42
Disadvantages
1. We can only raise the speed at which the motor normally runs at a
particular load.
2. The speed is increased without a corresponding reduction in shaft load
leading to overloading of the motor,
53
EMM 214
EMM 214 ELECTRICAL ENGINEERING II DR C. M MURIITHI 54
At light loads or under no-load conditions speed can be varied about 300%
above normal operating speeds.
3. Changing the terminal voltage VL of the motor.
Voltage control method lowers the speed in a similar fashion as the
armature circuit resistance speed control method.
The no-load speed and full load speed can be reduced to zero.
Torque
V2 V1 Vrated
Speed
V2<V1<Vrated
Fig 3.43
The most effective way of speed control as seen from above will be a
combination of at least two methods.
54
EMM 214
EMM 214 ELECTRICAL ENGINEERING II DR C. M MURIITHI 55
Fig 4.1
There are no slip rings or carton brushes, making the constitution virtually
maintenance free.
EMM 214
EMM 214 ELECTRICAL ENGINEERING II DR C. M MURIITHI 56
Fig 4.2
Axis of
phase b
+ a
Axis of
. .
-b -c
phase a
+ +
c b
. -a
Axis of
phase c
=0
Fig 4.3 A simplified two pole three phase stator winding
EMM 214
EMM 214 ELECTRICAL ENGINEERING II DR C. M MURIITHI 57
+ a
Fc
+ +
-b -c
F Fa
. Fb
.
c b
. -a
Fig 4.4
At time t =t2
| ia|=| ib| and are equal to one half of their respective maximum values and are
positive. ic has maximum amplitude but is negative.
F
+ a
F
c
. Fb
+
-b -c
Fa
. +
b
c
. -a
Fig 4.5
The total MMF, F is rotated 60 mechanical degrees which follows the time increment
from t1 to t2.
At time t=t3
| ia|=| ic| and are equal to one half of their respective maximum values and are
negative. ib has maximum positive amplitude.
57
EMM 214
EMM 214 ELECTRICAL ENGINEERING II DR C. M MURIITHI 58
. a Fb
. Fc
+
-b -c
F
a
. +
b
c
+ -a
Fig 4.6
The total MMF,F is rotated an additional 60 mechanical degree clockwise, which
follows the time increment from t2 to t3.
At time t=t4
| ic|=| ib| and are equal to one half of their respective maximum values and are
positive. ia has maximum amplitude but is negative.
.a
. F
b
.
-b -c
F
F
a
+ +
F b
c c
+ -a
Fig 4.7
The resulting total MMF, F, is rotated by 180 mechanical degrees by the time the
ia changes from maximum positive amplitude to maximum negative amplitude after
half a cycle.
Thus the field will revolve a distance covered by 2 poles for each cycle of the supply
frequency. The speed of the rotating field is inversely proportional to the number of
pole pairs and proportional to the frequency of the supply f.
nS
P
120 f rev
min
……………………..(4.1)
58
EMM 214
EMM 214 ELECTRICAL ENGINEERING II DR C. M MURIITHI 59
Reversing the phase sequence of the supply by interchanging any of the two currents
will cause the field to rotate in the counter clockwise direction.
Hence, in practise, reversing the direction of rotation of an induction motor is done by
interchanging any two line connections at the motor terminals.
Fig 4.8
As the field sweeps through a coil (a-a’) on the rotor it will induce an EMF in it. An
induced current is created in this coil flowing in the direction show determined by
Lenz’s law. The developed torque on a-a’ is determined by LHR, following the main
field. There must be relative motion between rotating field and the rotor: otherwise
there will be no induced rotor current to develop the torque.
The difference between the synchronous speed ns and the rotor speed nr is called the
slip S and is expressed as a percentage of the synchronous speed.
ns nr
s 100
ns
or
nr (1 s ) n s ... rev
min
…………………….(4.2)
where
.sdecimal
4.2.5 Rotor Induced Voltage And Frequency
When nr=0, the rotating field sweeps the rotor bars at its maximum rate, and the
generated voltage in the rotor circuit will be maximum and determined by the number
of turns on the rotor.
59
EMM 214
EMM 214 ELECTRICAL ENGINEERING II DR C. M MURIITHI 60
As the field revolves a back EMF is generated in the stator winding which is nearly
equal to the impressed voltage, and the flux sweeps the stator turns at the same rate as
those in the motor.
The induced voltages in the rotor and stator turns on a per phase basis are related by
the turns ratio. The frequency of the rotor induced voltage equals the line frequency
when nr=0 (s=1).
As the slip decreases, the rate at which the flux sweeps across the conductors
decreases proportionately and the rotor EMF becomes
E R s E BR
rotor.. frequency ………………………….(4.3)
fR s f
Where ER – rotor induced voltage at slip
EBR – blocked rotor – induced voltage per phase (nr=0)
fR – Rotor frequency.
4.2.6 Rotor Circuit
The induced rotor voltage per phase sEBR acts in the short circuited rotor winding,
setting up currents that will be only limited by the rotor impedance.
Rotor impedance consists of:
1. Rotor resistance RR
2. Leakage reactance, sXBR, where XBR is the rotor reactance at stand still (nr=0)
Hence,
sEBR sEBR
IR …………………(4.4)
RR2 ( sX BR ) 2 2
RR X 2
s
BR
Applying mathematical manipulation we can derive the equivalent circuit from the
above equation.
Let
RR 1 1 s
RR RR RR RR RR 1 RR RR ……………….(4.5)
s s s s
From equation 4.5 we get the equivalent rotor circuit to be:
RR IR XBR
EBR RR 1-s
s
Fig 4.9
EMM 214
EMM 214 ELECTRICAL ENGINEERING II DR C. M MURIITHI 61
Im
V1 E1
Fig 4.10
For both circuits to be compatible the rotor parameters are referred to the stator side.
Hence we achieve the complete circuit diagram as shown below:
I1 RS RR IR XR +XS
Im
V1 RR 1-s
Xm s
Fig 4.11
61
EMM 214
EMM 214 ELECTRICAL ENGINEERING II DR C. M MURIITHI 62
EMM 214
EMM 214 ELECTRICAL ENGINEERING II DR C. M MURIITHI 63
be connected for either 4 or 8 poles, giving synchronous speeds of 1500 and 750
r.p.m, Four speed motors are equipped with two separate stator windings each of
which provides two speeds.
The disadvantages of this method are :
(i) It is not possible to obtain gradual continuous speed control.
(ii) Because of the complications in the design and switching of the
interconnections of the stator winding, this method can provide a
maximum of four different synchronous speeds for any one motor.
4.2.10 Methods of Starting Squirrel Cage Motors
The following four methods arc available for starting squirrel cage motors :
(i) Direct on line starting.
In this method the motor is started by connecting it directly to 3-phase supply. The
impedance of the motor at standstill is relatively low and when it is directly
connected to the supply system, the starting current will be high (4 to 10 times
the full-load current) and at a low power factor.
Consequently, this method of starting is only suitable for relatively small (upto
7.5kW) machines.
(ii) Stator resistance starting.
In this method, external resistances are connected in series with each phase of stator
winding during starting. This causes voltage to drop across the resistances so that
voltage available across the motor terminals is reduced and hence the reducing the
starting current. The starting resistances are gradually cut out in steps from the stator
circuit as the motor picks up speed. When the motor attains rated speed, the
resistances are completely cut out and full line voltage is applied to the motor.
Fig 4.12
Disadvantages
1. The reduced voltage applied to the motor during the starting period lowers
the starting torque and hence increases the accelerating time.
2. A lot of power is wasted in the starting resistances.
63
EMM 214
EMM 214 ELECTRICAL ENGINEERING II DR C. M MURIITHI 64
Fig 4.13
At the instant of starting, the change-over switch is thrown to "start" position. This
puts the auto transformer in the circuit and thus reduced voltage is applied to the
circuit. The starting current is limited to a safe value. When the motor attains about
80% of normal speed, the change-over switch is thrown to "run" position. This takes
out the auto-transformer from the circuit and puts the motor to full line voltage.
Advantages
1. low power loss,
2. low starting current and
3. less radiated heat.
Fig 4.14
The six leads of the stator windings are connected to the change-over switch as
shown. At the instant of starting, the change-over switch is thrown to "start" position
64
EMM 214
EMM 214 ELECTRICAL ENGINEERING II DR C. M MURIITHI 65
which connects the stator windings in star. Therefore, each stator phase gets V
3
volts where V is the line voltage. This reduces the starting current. When the motor
picks up speed, the change-over switch is thrown to "Run" position which connects
the stator windings in delta. Now each stator phase gets full line voltage V.
The disadvantages of this method are:
1. with star connection, stator phase voltage is 1 times the line voltage and
3
2
thus the starting torque is 1 1 times the value it would have been
3 3
with delta connection. ( low starting torque)
2. the reduction in voltage is fixed.
4.2.11 Conclusion
Most industrial electric machine are three-phase squirrel cage induction motors.
Advantages
1 Are relatively cheap
2 Required very little maintenance
3 Speed is nearly constant.
4 High efficiency and reasonably good power factor
5 Has self starting torque
Disadvantages
1 Speed is not easily controlled
2 They run at low leading power factors when lightly loaded.
3 Starting current is usually five to seven times full load rated current.
4 Starting torque is inferior to that of the shunt motor.
65
EMM 214
EMM 214 ELECTRICAL ENGINEERING II DR C. M MURIITHI 66
Fig 4.15
The armature winding is identical to that of the indication motor, hence when a three-
phase voltage source is applied to the armature winding, a rotating field of constant
magnitude is produced in the air gap. The speed of the rotating field depends on the
line frequency, f, and the number of poles, P, hence:
nS
P
120 f rev
min
ns =synchronous speed in rev/min
Unlike the induction motor a synchronous motor receives its excitation from two
different voltage sources, that is, three phase AC source to the stator winding and a
DC source for the rotor winding.
The interaction of the two fields in the air gap produce torque, provided those fields
revolve at the same speed.
4.3.2 Principle Of Operation.
A three-phase supply of constant frequency is connected to the armature winding. If a
field is provided with de excitation is provided to the rotor torque is developed.
Torque is developed at only one speed, the synchronous speed. At any other speed the
average developed torque is zero.
66
EMM 214
EMM 214 ELECTRICAL ENGINEERING II DR C. M MURIITHI 67
Fig 4.16
A three-phase AC voltage is applied to the stator winding and a DC source supplies
the rotor field. The rotor is assumed stationary. The stator field rotates at synchronous
speed but rotor field is stationary since we have made that assumption. It can be seen
that in order to develop a continuous torque the two fields must be stationery with
respect to one another. This occurs only when the rotor is also rotating at
synchronous speed, whereby the stator and rotor fields ―lock in‖.
Fig 4.17
67
EMM 214
EMM 214 ELECTRICAL ENGINEERING II DR C. M MURIITHI 68
There may be momentary fluctuations in speed, but on the average the speed is
constant. If the average speed of the rotor is different from ns, even by a small
amount the poles lose their grip and the machine will come to a stand still.
The bond between the stator and rotor poles is then lost which is the essential
criterion for the developed of torque.
4.3.3 Loading Synchronous Motors
Consider a two-pole machine.
68
EMM 214
EMM 214 ELECTRICAL ENGINEERING II DR C. M MURIITHI 69
With no-load on the motor shaft the rotor poles lock in with the opposite stator poles.
The whole arrangement rotates at synchronous speed and the torque angle δ is zero.
When a mechanical load is applied to the shaft the rotor tends to slow down, but the
entire arrangement at synchronous speed. The magnetic bond between rotor and
stator field is still maintained except that the rotor is displaced by the torque angle δ.
The developed torque, Td, depends on the angle δ and must be sufficient to overcome
the shaft torque applied Tload.
Synchronous motor runs at absolutely constant average speed regardless of the load.
The following fundamental difference in behaviour will be considered:
1. Counter EMF for a synchronous motor does not necessarily have to be
smaller then applied voltage.
2. The phase relation between Counter EMF and terminal voltage is not fixed
o
at 180 , that is, they are not directly opposite,
3. The armature current, IA, lags behind the resultant voltage by 90o.
69
EMM 214
EMM 214 ELECTRICAL ENGINEERING II DR C. M MURIITHI 70
Fig 4.19
Two salient poles are shown at an instant when they are opposite two conductors in
the stator. The counter EMF induced in the conductor is as shown being maximum
when that conductor is opposite the pole center and zero when midway in between.
Upon applying the increased load to the motor shaft a momentary slowing down of
the rotor is the result, since it takes time for a motor to take increased power from line
source. Hence, the rotor through rotating at ns will have slipped back in space as a
result of increased loading.
In phasor form the above may be represented as follows:
Fig 4.20
By using the analogy of dc shunt motor:
V ( EC )
IA
ZS
Zs – Impedance per phase for shunt winding.
The equivalent circuit diagram following the above equation will be:
70
EMM 214
EMM 214 ELECTRICAL ENGINEERING II DR C. M MURIITHI 71
Fig 4.21
By loading the machine the rotor assumes an angular position back from its no-load
position. This causes the motor to take increased power from line to compensate for
the increased shaft load, without changing its average speed.
Total power supplied to motor per phase is,
P VI A cos
where;
V – phase voltage in volts
Θ – angle between V and IA
Total mechanical power, (that is, the total air-gap power or developed power) is
Pd EC I A cos
where; α – phase angle between EC and IA
The difference between the total power supplied and the total mechanical power is
the copper power loss;
P Pd I A R A
2
The net shaft power is less then Pd by an amount equalling the frictional, rotational
and core losses;
Pout Pshaft Pd Pmech.losses
4.3.4 Adjusting The Field Excitation
When the dc excitation current is increased the speed of the synchronous motor
remains constant, but its induced EMF EC must increase because of the strengthened
rotor field.
The induced EMF becomes equal to or greater then the line voltage. In this condition
the motor operates overexcited with the result that it takes power from the line with a
leading power factor.
Let us consider three excitation positions:
71
EMM 214
EMM 214 ELECTRICAL ENGINEERING II DR C. M MURIITHI 72
Fig 4.22
(a) Motor is adjusted such that it is operating at unity power factor, that is, IA is
in phase with the line voltage V. In this case, the armature current is
proportional to the vector sum of the line voltage V And EC limited by an
impedance ZS.
(b) Increasing the field excitation increases EC. Since ZS is constant, being the
same machine windings, IA must increase. However the load power is
constant, which implies that the phase angle must change in such a manner
that the in-phase component of the armature current with the V is constant.
This can be accomplished only if the armature current assumes a leading
position.
(c) A decrease in field excitation causes the counter EMF EC to become
smaller. The in phase component of IA, IA cos Θ, with V must remain the
same since the power delivered is constant. The vector sum of V and Ec
becomes larger. The IA will increase depending on the voltage sum increase
and can only do this by changing its power factor to a lagging angle.
4.3.5 Self starting of a Synchronous Motor
A synchronous motor cannot start by itself. In order to make the motor self-
starting, a squirrel cage winding (also called damper winding) is provided on the
rotor. The damper winding consists of copper bars embedded in the pole faces of the
salient poles of the rotor as shown in Fig. 4.23. The bars are short-circuited at the
ends to form in effect a partial squirrel cage winding. The damper winding serves to
start the motor.
Fig 4.23
72
EMM 214
EMM 214 ELECTRICAL ENGINEERING II DR C. M MURIITHI 73
(i) To start with, 3-phase supply is given to the stator winding while the rotor field
winding is left unenergised. The rotating stator field induces currents in the damper or
squirrel cage winding and the motor starts as an induction motor.
(ii) As the motor approaches the synchronous speed, the rotor is excited with direct
current. Now the resulting poles on the rotor face poles of opposite polarity on the
stator and a strong magnetic attraction is set up between them. The rotor poles lock in
with the poles of rotating flux. Consequently, the rotor revolves at the same speed as
the stator field ns.
(iii) Because the bars of squirrel cage portion of the rotor now rotate at the same
speed as the rotating stator field, these bars do not cut any flux and, therefore, have
no induced currents in them. Hence squirrel cage portion of the rotor is, in effect,
removed from the operation of the motor.
Due to magnetic interlocking between the stator and rotor poles, a synchronous
motor can only run at synchronous speed. At any other speed, this magnetic
interlocking (i.e., rotor poles facing opposite polarity stator poles) ceases and the
average torque becomes zero. Consequently, the motor comes to a halt with a severe
disturbance on the line.
73
EMM 214
EMM 214 ELECTRICAL ENGINEERING II DR C. M MURIITHI 74
Fig 4.24
The maximum power or pull out power, Pmax, occurs when sin δ=1.0 (δ=90)
Beyond Pmax the motor looses synchronism. Losing synchronism implies that
the magnetic bond between stator and rotor fields is lost. The rotor will skip
poles and tries to run as an induction motor if the starting winding can support
this load. This continues until the excessive load is removed.
74
EMM 214