NHXHX FE 180
NHXHX FE 180

0.6/1 kV multi core, halogen free and re resistant cables

Description Application:
Used in energy networks in hotels,schools,tunnels,high constructions,hospitals,power plants,data processing centers,business centers where there is a risk of re.

Construction:
1. 2. 3. 4. 5. Conductor:Copper Fireproof:mica tape Insulation:XL-HFFR Filler:EVA/PE based Outer sheath:XL-HFFR (Halogene Free Flame Retartant)

Standards
National DIN VDE 0266

Marking
NEXANS VDE 0266 NHXHX FE-180 4x25 rm 0,6/1 kV 2012 (Meter) ALSECURE PLUS

Operating temp. range -20 .. 60 C

Maximum operating temperature 90 C

Bending factor when laying 12 (xD)

Smoke density IEC 61034

Gases corrosivity Low IEC 60754-2

Gases toxicity No toxicity to IEC 60754-1

Flame retardant IEC 60332-1&3

Version V2.0 Generated 9/16/12 - http://www.nexans.com.tr

Page 1 / 5

All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.

Contact
Power Cables Phone: +90 212 266 01 60 eservice-power.turkey@nexans.com

NHXHX FE 180
Characteristics
Usage characteristics Operating temperature, range Maximum operating temperature Short-circuit max. conductor temperature Bending factor when laying Smoke density Gases corrosivity Gases toxicity Flame retardant -20 .. 60 C 90 C 250 C 12 (xD) IEC 61034 Low IEC 60754-2 No toxicity to IEC 60754-1 IEC 60332-1&3

Characteristics
Conductor cross-section Permissible current rating in open air Max. DC resistance of the conductor at 20C Delivery reel size for 1000m Nominal outer diameter Permissible current rating when buried Approximate weight Conductor cross-section Permissible current rating in open air Max. DC resistance of the conductor at 20C Delivery reel size for 1000m Nominal outer diameter Permissible current rating when buried Approximate weight Conductor cross-section Permissible current rating in open air Max. DC resistance of the conductor at 20C Delivery reel size for 1000m Nominal outer diameter Permissible current rating when buried Approximate weight 1.5 24 12.1 90 13.0 30 240 4 42 4.61 110 17.0 52 440 16 96 1.15 120 20.0 111 800 1.5 24 12.1 100 15.0 30 280 6 53 3.08 110 17.0 64 460 16 96 1.15 120 22.0 111 950 2.5 32 7.41 100 14.0 40 300 6 53 3.08 110 18.0 64 550 16 96 1.15 130 22.0 111 1000 2.5 32 7.41 100 16.0 40 360 10 73 1.83 110 18.0 86 600 25 130 0.727 130 23.0 143 1200 4 42 4.61 100 16.0 52 380 10 73 1.83 120 20.0 86 750 25 130 0.727 150 25.0 143 1400 mm A Ohm/km cm mm A kg/km mm A Ohm/km cm mm A kg/km mm A Ohm/km cm mm A kg/km

Operating temp. range -20 .. 60 C

Maximum operating temperature 90 C

Bending factor when laying 12 (xD)

Smoke density IEC 61034

Gases corrosivity Low IEC 60754-2

Gases toxicity No toxicity to IEC 60754-1

Flame retardant IEC 60332-1&3

Version V2.0 Generated 9/16/12 - http://www.nexans.com.tr

Page 2 / 5

All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.

Contact
Power Cables Phone: +90 212 266 01 60 eservice-power.turkey@nexans.com

NHXHX FE 180
Conductor cross-section Permissible current rating in open air Max. DC resistance of the conductor at 20C Delivery reel size for 1000m Nominal outer diameter Permissible current rating when buried Approximate weight Conductor cross-section Permissible current rating in open air Max. DC resistance of the conductor at 20C Delivery reel size for 1000m Nominal outer diameter Permissible current rating when buried Approximate weight Conductor cross-section Permissible current rating in open air Max. DC resistance of the conductor at 20C Delivery reel size for 1000m Nominal outer diameter Permissible current rating when buried Approximate weight Conductor cross-section Permissible current rating in open air Max. DC resistance of the conductor at 20C Delivery reel size for 1000m Nominal outer diameter Permissible current rating when buried Approximate weight Conductor cross-section Permissible current rating in open air Max. DC resistance of the conductor at 20C Delivery reel size for 1000m Nominal outer diameter Permissible current rating when buried Approximate weight 25 130 0.727 150 26.0 143 1500 50 195 0.387 160 31.0 205 2500 95 305 0.193 210 38.0 303 3750 120 355 0.153 250 46.0 346 6000 185 469 0.099 220 56.0 441 9000 35 160 0.524 150 26.0 173 1600 50 195 0.387 180 33.0 205 2750 95 305 0.193 220 41.0 303 4500 150 407 0.124 210 50.0 390 7250 185 469 0.0991 210 50.0 441 7250 35 160 0.524 150 27.0 173 1800 70 247 0.268 180 33.0 252 3000 95 305 0.193 230 42.0 303 4750 150 407 0.124 240 45.0 390 5750 240 551 0.075 230 60.0 511 10500 35 160 0.524 160 28.0 173 1900 70 247 0.268 200 35.0 252 3250 120 355 0.153 230 41.0 346 4750 150 407 0.124 250 48.0 390 6500 240 551 0.075 240 63.0 511 12000 50 195 0.387 160 29.0 205 2000 70 247 0.268 200 37.0 252 3500 120 355 0.153 240 45.0 346 5500 185 469 0.099 220 54.0 441 8250 240 551 0.0754 230 57.0 511 9250 mm A Ohm/km cm mm A kg/km mm A Ohm/km cm mm A kg/km mm A Ohm/km cm mm A kg/km mm A Ohm/km cm mm A kg/km mm A Ohm/km cm mm A kg/km

Operating temp. range -20 .. 60 C

Maximum operating temperature 90 C

Bending factor when laying 12 (xD)

Smoke density IEC 61034

Gases corrosivity Low IEC 60754-2

Gases toxicity No toxicity to IEC 60754-1

Flame retardant IEC 60332-1&3

Version V2.0 Generated 9/16/12 - http://www.nexans.com.tr

Page 3 / 5

All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.

Contact
Power Cables Phone: +90 212 266 01 60 eservice-power.turkey@nexans.com

NHXHX FE 180
Conductor cross-section Permissible current rating in open air Max. DC resistance of the conductor at 20C Delivery reel size for 1000m Nominal outer diameter Permissible current rating when buried Approximate weight Conductor cross-section Permissible current rating in open air Max. DC resistance of the conductor at 20C Delivery reel size for 1000m Nominal outer diameter Permissible current rating when buried Approximate weight 300 638 0.06 210 70.0 580 14500 400 746 0.047 220 78.0 663 18500 300 638 0.06 250 66.0 580 13000 mm A Ohm/km cm mm A kg/km 300 638 0.0601 240 63.0 580 11500 400 746 0.047 210 70.0 663 14500 400 746 0.047 210 74.0 663 16500 mm A Ohm/km cm mm A kg/km

Product List Nexans ref. 45 A03B5V 3T40000732G000 45 A04B5V 3T40000732G000 45 A03C5V 3T40000732G000 45 A04C5V 3T40000732G000 45 A0304V 3T40000732G000 45 A0404V 3T40000732G000 45 A0306V 3T40000732G000 45 A0406V 3T40000732G000 45 A0310V 2T40000732G000 45 A0410V 2T40000732G000 45 A0316V 2T40000732G000 45 A3A16V 2T40000732G000 45 A0416V 2T40000732G000 45 A0325V 2T40000732G000 45 A3A25V 2T40000732G000 45 A0425V 2T40000732G000 45 A0335V 2T40000732G000 45 A3A35V 2T40000732G000 Name 3x1.5 mm 4x1,5 mm 3x2,5 mm 4x2,5 mm 3x4 mm 4x4 mm 3x6 mm 4x6 mm 3x10 mm 4x10 mm 3x16 mm 3x16/10 mm 4x16 mm 3x25 mm 3x25/16 mm 4x25 mm 3x35 mm 3x35/16 mm Nb. of cores 3 4 3 4 3 4 3 4 3 4 3 4 4 3 4 4 3 4

=Make to order, 1.5 1.5 2.5 2.5 4 4 6 6 10 10 16 16 16 25 25 25 35 35 = Make to order,

=Make to stock

Cross section (mm)

= Make to stock

Operating temp. range -20 .. 60 C

Maximum operating temperature 90 C

Bending factor when laying 12 (xD)

Smoke density IEC 61034

Gases corrosivity Low IEC 60754-2

Gases toxicity No toxicity to IEC 60754-1

Flame retardant IEC 60332-1&3

Version V2.0 Generated 9/16/12 - http://www.nexans.com.tr

Page 4 / 5

All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.

Contact
Power Cables Phone: +90 212 266 01 60 eservice-power.turkey@nexans.com

NHXHX FE 180
Nexans ref. 45 A0435V 2T40000732G000 45 A0350V 2T40000732G000 45 A3A50V 2T40000732G000 45 A0450V 2T40000732G000 45 A0370V 2T40000732G000 45 A3A70V 2T40000732G000 45 A0470V 2T40000732G000 45 A0395V 2T40000732G000 45 A3A95V 2T40000732G000 45 A0495V 2T40000732G000 45 A032DV 2T40000732G000 45 A3A2DV 2T40000732G000 45 A042DV 2T40000732G000 45 A035DV 2T40000732G000 45 A3A5DV 2T40000732G000 45 A045DV 2T40000732G000 45 A038DV 2T40000732G000 45 A3A8DV 2T40000732G000 45 A048DV 2T40000732G000 45 A034EV 2T40000732G000 45 A3A4EV 2T40000732G000 45 A044EV 2T40000732G000 45 A033FV 2T40000732G000 45 A3A3FV 2T40000732G000 45 A043FV 2T40000732G000 45 A034GV 2T40000732G000 45 A3A4GV 2T40000732G000 45 A044GV 2T40000732G000 Name 4x35 mm 3x50 mm 3x50/25 mm 4x50 mm 3x70 mm 3x70/35 mm 4x70 mm 3x95 mm 3x95/50 mm 4x95 mm 3x120 mm 3x120/70 mm 4x120 mm 3x150 mm 3x150/70 mm 4x150 mm 3x185 mm 3x185/95 mm 4x185 mm 3x240 mm 3x240/120 mm 4x240 mm 3x300 mm 3x300/150 mm 4x300 mm 3x400 mm 3x400/185 mm 4x400 mm Nb. of cores 4 3 4 4 3 4 4 3 4 4 3 4 4 3 4 4 3 4 4 3 4 4 3 4 4 3 4 4 Cross section (mm) 35 50 50 50 70 70 70 95 95 95 120 120 120 150 150 150 185 185 185 240 240 240 300 300 300 400 400 400 = Make to order, = Make to stock

Operating temp. range -20 .. 60 C

Maximum operating temperature 90 C

Bending factor when laying 12 (xD)

Smoke density IEC 61034

Gases corrosivity Low IEC 60754-2

Gases toxicity No toxicity to IEC 60754-1

Flame retardant IEC 60332-1&3

Version V2.0 Generated 9/16/12 - http://www.nexans.com.tr

Page 5 / 5

All drawings, designs, specications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.

S-ar putea să vă placă și