DRAWING TITLE
SINGLELINE DIAGRAM COAL HANDLING SYSTEM SUB-CONTRACTOR FUNCTION DRWN CHKD APPD DOCUMENT No. VA1-FLS-00100-E-M2-DSL-0600 NAME M.Leinenbach A.Scholz T.Brwer SCALE REV C SIGN DATE 07.12.09 07.12.09
10
A Power Plant
MVA
10 kV 3Ph 50Hz
MVB
Substation TT2
D
I > IR=2500 A IR=1600 A I > IR=2500 A I> IR=630 A
I> IR=160 A
I>
IR=80 A
IR=250 A
IR=63 A
IR=100 A
IR=400 A
IR=125 A
IR=200 A
IR=80 A
IR=315 A
IR=80 A
IR=250 A
IR=63 A
IR=100 A
IR=400 A
IR=125 A
IR=200 A
IR=80 A
IR=315 A
IR=160 A
80 A I> IR=100 A
230V 50Hz
80 A I> IR=100 A
230V 50Hz
I=80 A*
I=250A*
I=58A*
I=95A*
I=400A*
I=114A*
I=80A*
I=200A*
I=80 A*
I=250A*
I=58A*
I=95A*
I=400A*
I=114A*
I=80A*
I=200A*
Capacitor bank
390m, 2 x 95mm
400m, 2 x 120mm
50m, 2 x 95mm
320m, 185mm
670m, 2 x 95mm
60m, 2 x 95mm
520m, 150mm
320m, 185mm
470m, 120mm
500m, 70mm
350m, 95mm
595m, 95mm
500m, 70mm
605m, 95mm
Capacitor bank
Capacitor bank
Capacitor bank
115m, 35mm
400m, 35mm
115m, 35mm
190m, 50mm
190m, 50mm
400m, 35mm
242m, 35mm
242m, 35mm
60m, 25mm
60m, 25mm
24V DC
24V DC
193m, 70mm
M 3~ M 3~ M 3~ M 3~ M 3~ M 3~ M 3~
217m, 120mm
M 3~ M 3~ M 3~ M 3~ M 3~ M 3~ M 3~
193m, 70mm
217m, 120mm
M 3~ M 3~
120m, 16mm
M 3~
00EAU01 49KW
Lighting Stockpile A 100A Lighting & Power sockets Transfer Towers 100A
120m, 16mm
AUX.
M 3~
00EAU02 49kW
Lighting Stockpile B 100A Lighting & Power sockets Transfer Towers 100A
AUX.
00EAD03 10 kW
00EAD04 10 kW
00EAC08 55 kW IN=58 A
00EAE01 75 kW IN=80 A
00EAC20 75 kW IN=80 A
00EAC18 00EAC12 00EAC11 00EAC07 400KW 90 kW 55 kW 110 kW IN=95 A IN=400 A IN=114 A IN=58 A
00EAE02 75 kW IN=80 A
00EAC03 37 kW IN=75 A
00EAC13 37 kW IN=75 A
10kV 1229 KW
10kV 1229 KW
00EAA01
00EAA02
NOTE:
** I
KMAX
if tie breaker is closed and one transformer supply both busbar, worsed case
Adapted according to CS-M2-E-00048 Deleted Substation Storage Adapted installed power Index / Rev. Mitteilung / Remark
Kunde / Client
Firma / Company
Zeichnung / Drawing
2.2040
Blatt / Page: von / of: 1 1
VA1-FLS-00100-E-M2-DSL-0600 Rev. C
10
11
12
C
Transformer 1.1A.1 Sn = 2.500 kVA ukr = 6 % 10/0,69 kV Dyn5 Transformer 1.1B.1 Sn = 2.500 kVA ukr = 6 % 10/0,69 kV Dyn5
3~
3~
3~
3~
3~
3~
3~
3~
3~
3~
3~
3~
3~
3~
3~
3~
10
10
11
12
C
Transformer 1.1A.1 In1 = 144 A In2 = 2.092 A u = 0,908 % Transformer 1.1B.1 In1 = 144 A In2 = 2.092 A u = 0,909 %
CB 1.1ABa IR =1.125 A
CB 1.1A.1a IR = 450 A
CB 1.1B.11a IR = 450 A
3~
3~
3~
3~
3~
3~
3~
3~
3~
3~
3~
3~
3~
3~
3~
3~
10
10
11
12
C
S =1.221,7 kVA P =1.200,8 kW Q = -224,5 kvar Ibs =1.022,2 A S =1.222,5 kVA P =1.201,5 kW Q = -225,1 kvar Ibs =1.022,9 A
3~
S = 92,7 kVA P = 80,6 kW Q = -45,7 kvar Ibs = 69,8 A (L1, L2, L3)
3~
S = 298,7 kVA P = 268,8 kW Q = -130,2 kvar Ibs = 224,9 A (L1, L2, L3)
3~
S = 68,0 kVA P = 59,1 kW Q = -33,5 kvar Ibs = 51,2 A (L1, L2, L3)
3~
S =111,2 kVA P = 96,8 kW Q = -54,8 kvar Ibs = 83,8 A (L1, L2, L3)
3~
S = 478,1 kVA P = 425,5 kW Q = -218,0 kvar Ibs = 160,0 A (L1, L2, L3)
3~
S =133,0 kVA P =117,0 kW Q = -63,2 kvar Ibs =100,1 A (L1, L2, L3)
S = 119,5 kVA P = 95,6 kW Q = -71,7 kvar Ibs =100,0 A (L1, L2, L3)
3~
S = 91,6 kVA P = 81,5 kW Q = -41,8 kvar Ibs = 7,7 A (L1, L2, L3)
S = 216,9 kVA P = 193,0 kW Q = -98,9 kvar Ibs = 181,5 A (L1, L2, L3)
3~
S =158,7 kVA P =139,7 kW Q = -75,4 kvar Ibs = 119,5 A (L1, L2, L3)
3~
S = 93,7 kVA P = 81,5 kW Q = -46,2 kvar Ibs = 70,6 A (L1, L2, L3)
3~
S = 298,7 kVA P = 268,8 kW Q = -130,2 kvar Ibs = 224,9 A (L1, L2, L3)
3~
S = 68,0 kVA P = 59,1 kW Q =-33,5 kvar Ibs = 51,2 A (L1, L2, L3)
3~
S =111,2 kVA P = 96,8 kW Q = -54,8 kvar Ibs = 83,8 A (L1, L2, L3)
3~
S = 478,1 kVA P = 425,5 kW Q =-218,0 kvar Ibs = 160,0 A (L1, L2, L3)
3~
S =133,0 kVA P =117,0 kW Q = -63,2 kvar Ibs =100,1 A (L1, L2, L3)
S =119,5 kVA P = 95,6 kW Q = -71,7 kvar Ibs =100,0 A (L1, L2, L3)
3~
S = 91,6 kVA P = 80,6 kW Q = -43,5 kvar Ibs = 7,7 A (L1, L2, L3)
S = 216,9 kVA P = 193,0 kW Q = -98,9 kvar Ibs = 181,5 A (L1, L2, L3)
3~
S =158,7 kVA P =139,7 kW Q = -75,4 kvar Ibs =119,5 A (L1, L2, L3)
10
U [V]
u dyn. [%]
U dyn. [V]
Summated absolute voltage drop at the starting motor with/without voltage drop over the transformer winding according to the selected settings Capacity factor Minimum/maximum voltage factor in accordance with IEC 60909-0 Power factor The indicated short-circuit current refers to a fault in the medium-voltage busbar The indicated short-circuit current refers to a fault at the primary side of the transformer The indicated short-circuit current refers to a fault at the secondary side of the transformer Reduction factor Nominal frequency Simultaneity factor Simultaneity factor Phase energizing current of overcurrent module of DMT relay Phase energizing current of high-current module of DMT relay Conventional fusing current Let-through energy Let-through energy downstream of the lower switching device or at the target distribution board / consumer Let-through energy upstream of the lower switching device Let-through energy downstream of the upper switching device Let-through energy at the output distribution board or upstream of the upper switching device Let-through energy of the switching device at the transition to the I-release Let-through energy of the switching device in the event of maximum short-circuit current Let-through energy of the switching device in the event of minimum short-circuit current Rated let-through energy of RCD Let-through energy of fuse
ai c min/max cos(), F1 F2 F3 ftot fn [Hz] gf gi I> [A] I> [A] I2 [A] I2t [kA2s] I2t a [kA2s]
I2t b [kA2s] I2t c [kA2s] I2t d [kA2s] I2t(Ii) [kA2s] I2t(Ikmax) [kA2s] I2t(Ikmin) [kA2s] I2t(RCD) [kA2s] I t(fuse) [kA s]
2 2
I2t(soll) [kA2s] I2t value Itmax(base) [kA2s] Ia/In Ib [A] Ibb [A] Ibel [A] Ibem [A] Ibs [A] Ibw [A] c value [kA]
Let-through energy requirement on the connecting line Let-through energy of the switching device at Ikmax from the characteristic curve file Permissible I2t value of the fuse base Starting current ratio Operating current Reactive load current Load current Rated set-point current of the switching device Apparent load current Active load current Cut-off current of the switching device at Ikmax from the characteristic curve file (instantaneous value) Cut-off current of the fuse Rated short-circuit making capacity Rated short-circuit current of the fuse base Rated short-circuit breaking capacity acc. to IEC 60898-1 Rated ultimate short-circuit breaking capacity acc. to IEC 60947-2 Requirement on the rated ultimate short-circuit breaking capacity downstream of the lower switching device or at the target distribution board (controlled short-circuit current) Requirement on the rated ultimate short-circuit breaking capacity upstream of the lower switching device (controlled short-circuit current) Requirement on the rated ultimate short-circuit breaking capacity downstream of the upper switching device (controlled short-circuit current) Requirement on the rated ultimate short-circuit breaking capacity at the output distribution board or upstream of the upper switching device (controlled short-circuit current) Rated ultimate short-circuit breaking capacity fuse Required short-circuit breaking capacity for the protective device at the mounting location Rated short-time withstand current 1s
Ic (fuse) [kA] Icm [kA] Icmax (base) [kA] Icn [kA] Icu [kA] Icu korr a [kA]
Ie [A] Ig [A] Igb [A] Igs [A] Igw [A] IHHmin [A] Ii [A] Ik1D [kA] Ik1max [kA] Ik1max(F1) [kA] Ik1maxph_n [kA] Ik1maxph_pe [kA] Ik1max [kA] Ik1min(F2) [kA] Ik1min(F3) [kA] Ik1minph_n [kA] Ik1minph_pe [kA] Ik2min [A] Ik2min(F2) [kA] Ik2min(F3) [kA] Ik3(F3) [kA] Ik3D [kA] Ik3max [kA] Ik3max(F1) [kA] Ik3min [kA]
Earth energizing current of the DMT relay Setting value of the release for earth fault detection Total reactive current Total apparent current Total active current Minimum tripping current of the high-voltage highrupturing capacity fuse Setting value of instantaneous short-circuit (I)release 1-pole continuous short-circuit current Maximum 1-pole short-circuit current Maximum 1-pole short-circuit current in the event of a fault in the medium-voltage busbar Maximum 1-pole short-circuit current phase to neutral conductor Maximum 1-pole short-circuit current phase to protective conductor Minimum 1-pole short-circuit current Minimum 1-pole short-circuit current in the event of a fault at the transformer primary side Minimum 1-pole short-circuit current in the event of a fault at the transformer secondary side Minimum 1-pole short-circuit current phase to neutral conductor Minimum 1-pole short-circuit current phase to protective conductor Minimum 2-pole short-circuit current Minimum 2-pole short-circuit current in the event of a fault at the transformer primary side Minimum 2-pole short-circuit current in the event of a fault at the transformer secondary side 3-pole short-circuit current in the event of a fault at the transformer secondary side 3-pole continuous short-circuit current Maximum 3-pole short-circuit current Maximum 3-pole short-circuit current in the event of a fault in the medium-voltage busbar Minimum 3-pole short-circuit current
Maximum short-circuit current of all short-circuit currents Maximum short-circuit current downstream of the lower switching device or at the target distribution board (uncontrolled short-circuit current) Maximum short-circuit current upstream of the lower switching device (uncontrolled short-circuit current) Maximum short-circuit current downstream of the upper switching device (uncontrolled short-circuit current) Maximum short-circuit current at the output distribution board or upstream of the upper switching device (uncontrolled short-circuit current) Ratio of maximum/minimum short-circuit current Minimum short-circuit current of all short-circuit currents 3-pole short-circuit current proportion of the motor Factor of energetic recovery short-circuit current Maximum rated current of busbar system Nominal/rated current Rated current of RCD Nominal/rated current of medium-voltage switchgear Nominal/rated current of medium-voltage fuse Rated device current at 40 C standard temperature Permissible switch load according to ambient temperature Rated current of transformer, primary side Rated current of transformer, secondary side Rated transformer current at nominal power Peak short-circuit current Conditional rated short-circuit current - motor starter combination Setting value for overload (L)-release Setting value of short-time delayed short-circuit (S)-release Calculated selectivity limit value between Ikmin and Ikmax
Ikmax b [kA]
Ikmax c [kA]
Ikmax d [kA]
Ikmax/Ikmin Ikmin [A] Ikmotor [kA] Ikre Imax [A] In [A] In (RCD) [mA] In (switch) [A] In (fuse) [A] In max [A] In zul [A] In1 [A] In2 [A] In [A] Ipk [kA] Iq [kA] IR [A] Isd [A] Isel-kurz [A]
Isel-ber [A] Iz, Izul [A] In [mA] L L1 L2 L3 max min MRPD MV N LV P [kW] PE Pk [kW] Pmech [kW] Pn [kW] P0, Pv [kW] pz Q [kvar] Qe [kvar] Qn [kvar] R/X R0 [m] R0 min/max [m] R0 N [m] R0 PE(N) [m] R0U [m] R0/R1
Calculated selectivity limit value in range less than Ikmin Permissible load current of a connecting line Rated earth-fault current RCD protection Phase Phase 1 Phase 2 Phase 3 Maximum Minimum Machine-readable product designation Medium voltage Neutral conductor Low voltage Active power, electric Protective conductor Short-circuit losses Active power, mechanical Nominal active power No-load losses, loss power (active) Number of poles, switchgear Reactive power Effective reactive capacitor power Nominal reactive power Ratio of resistance to reactance Resistance in the zero phase-sequence system Minimum/maximum resistance in the zero phasesequence system Resistance in the zero phase-sequence system Phase - N Resistance in the zero phase-sequence system Phase - PE(N) Resistance in the zero phase-sequence system for the voltage drop Resistance ratio of zero/positive phase-sequence system
r0ph-n [m/m]
Specific active resistance of the zero phasesequence system for the phase to neutral conductor loop Specific active resistance of the zero-phasesequence system for the phase to protective conductor loop Specific active resistance of positive phasesequence system Related resistance value in the positive phasesequence system Resistance in the positive phase-sequence system Resistance in the positive phase-sequence system for the voltage drop Minimum/maximum resistance in the positive phase-sequence system Sum of resistances of the earth electrode and possibly wired protective conductor between exposed conductive part and earth in the IT or TT network Minimum/maximum loop resistance Apparent power Thermal fault withstand capability of the cable Nominal apparent power Nominal apparent power of transformer Delay time for the overcurrent module of DMT relay Delay time for the high-current module of DMT relay Permissible switch disconnection time for the setting value of the I-release, without violating the condition k2S2>I2t Permissible switch disconnection time at maximum short-circuit current, without violating the condition k2S2>I2t Permissible switch disconnection time at minimum short-circuit current, without violating the condition k2S2>I2t Permissible disconnection time in compliance with DIN VDE 0100-410 (IEC 60364-4-41) Controlled permissible switch disconnection time Switchgear disconnection time for disconnect condition
r0ph-pe(n) [m/m]
r1 [m/m] r1 [%] R1 [m] R1U [m] R1 min/max [m] Ra+Rb max [m]
R0 min/max [m] S [kVA] S2K2 S [kVA] SnT [kVA] t> [s] t>> [s] ta zul (Ii) [s]
ta(min kzs) [s] ta_max [s] te [s] tg [s] tR [s] tsd [s] Tu [C] ukr [%] Umax [V] Un [V] Uprim [kV] Usec [V] LVSD V X0 min/max [m] X0 N [m] X0 PE(N) [m] X0U [m] X0/X1 x0ph-n [m/m]
Switchgear disconnection time for short-circuit protection Maximum disconnection time of the switchgear to be evaluated Delay time of the earth energizing current of the DMT relay Time value of the G-release (absolute) Time value of the L-release Time value of the S-release Ambient device temperature Short-circuit voltage Maximum rated voltage of the busbar system Nominal voltage Primary voltage Secondary voltage Low-voltage sub-distribution (system) Load Minimum/maximum reactance in the zero phasesequence system Reactance of phase-N in the zero phasesequence system Reactance of phase-PE(N) in the zero phasesequence system Reactance of the zero phase-sequence system for voltage drop, independent of temperature Reactance ratio of zero/positive phase-sequence system Specific reactive resistance of the zero phasesequence system for the phase to neutral conductor loop Specific reactive resistance of the zero-phasesequence system for the phase to protective conductor loop Specific reactive resistance of positive phasesequence system Reactance in the positive phase-sequence system Minimum/maximum reactance in the positive phase-sequence system Reactance in the positive phase-sequence system for the voltage drop
x0ph-pe(n) [m/m]
xd [%] Xs min/max [m] Z0 [m] Z0 min/max [m] Z0U [m] Z1 [m] Z1 min/max [m] Z1U [m] Zs Zs min/max
Subtransient reactance Minimum/maximum loop reactance Impedance of zero phase-sequence system Minimum/maximum impedance in the zero phasesequence system Impedance in the zero phase-sequence system for the voltage drop Impedance of positive phase-sequence system Minimum/maximum impedance in the positive phase-sequence system Impedance in the positive phase-sequence system for the voltage drop Loop impedance Minimum/maximum loop resistance