CONSTRUCTION Model Rating Technology UPS Dimensions: W x D* x H (mm) Colour Weight (kg) ENVIRONMENTAL & SAFETY Ambient storage temperature Ambient service temperature Maximum service altitude Relative humidity Degree of protection Acoustic Noise Surge Suppression Safety Markings Electromagnetic Compatibility Agency Markings POWER CONNECTIONS Input Output USER INTERFACE Display Communication Ports Signal Inputs Relay Port Output Relay Specifications Optional Graphical LCD with blue backlight, 4x LEDs for notice and alarm 1 x USB (HID), 9600 bps, 1x RS232 (DB9, with 2 opto-coupled relay outputs), 1200-9600 bps, 1 x Communication Card Slot (Empty) (4) programmable signal inputs (one RS-232 input, two connectivity card inputs, and one inverter interlock port input) for indicating building alarms or other use (1) three-pole connector with (1) contact closure (Voltage Free Contact) 60VDC/2A Max, 30VAC/1A Max MS Slot cards; Web/SNMP, Relay C14 10 Amp (6) C13 10A C14 10 Amp (6) C13 10A C14 10 Amp (6) C13 10A C14 10 Amp (8) C13 10A, (1) C19 16A C20 16Amp (8) C13 10A, (1) C19 16A Hardwired, 2 10mm Max Hardwired, 2 10mm Max -20C to +40C with batteries and -25C to +55C without batteries Power electronics part: +0 to +40C, Battery part: +5 to 25C without reducing battery life 1000m above sea level. 5 to 90%, no condensation allowed IP20 (EN60529) <52 dBA (700-3000VA), <55dBA (6000VA) Normal mode, typical load and Battery mode EN61000-2-2, EN61000-4-2 Level 3 (air) Level 2 (contact), EN61000-4-3 Level 3, EN610000-4-4 Level 3 (power line) Level 4 (L-PE/N-PE), EN61000-4-6 Level 3 (10V), EN61000-4-8 Level 4 (30A/m), EN61000-4-11 CE, GS EN 620402 Emissions, category C1; Immunity, category C2 CE, CTick 160x355x250** PW9130G700T -XL 700VA/630W PW9130G1000T -XL 1000VA/900W 160x383x250** PW9130G1500T -XL 1500VA/1350W 160x435x250** PW9130G2000T -XL 2000VA/1800W 214x410x345** PW9130G3000T -XL 3000VA/2700W 214x410x345** PW9130G6000T -XL 6000VA/5400W 242x542x575
VFI-SS-111, on-line double conversion with power factor correction *Allow 150mm rear clearance for connections & air flow **Height includes rubber feet 12.2 14.5 Black, RAL9005 (PPC-18) 19.0 34.5 34.5 75.5
ELECTRICAL CHARACTERISTICS INPUT Rectifier : 230Vac nominal (200, 208, 220, 240V Selectable) 700-1500VA Tolerance: 120/140/160-276V (33%/66%/100% 0.7pf Load) 180-276V, (-22%, +20% at 0.8pf Load) 190-276V, (-17%, +20% at 0.9pf Load) 2000-3000VA Tolerance: 140/160/180-276V (33%/66%/100% 0.7pf Load) 190-276V, (-17%, +20% at 0.8pf Load) 200-276V, (-13%, +20% at 0.9pf Load) 6000VA Tolerance: 120/140/160/180-276V (25%/50%/75%//100% 0.9pf Load)
Bypass tolerance: 196 253V (-15%, +10% of nominal) Operating Frequency Input current distortion (Linear load condition at rated input current) Input power factor Inrush Current Rated Input Current @ 230V Dedicated Supply CB Rating 50 or 60Hz; Tolerance 40-70Hz 700-3000VA: <8% THDi. 6000VA: 5% THDi > 0.99pf 700-3000VA: < 45A (peak) decaying exponentially within 30 ms. 6000VA: 150A <1ms 3.0A 4.3A 7.2A 8.7A 13.0A 10A 10A 10A 10A 16A
28.6A 40A
Rev 0
Page 1 of 3
Dynamic Voltage variation Rated apparent/active power Waveform Rated output voltage Output voltage variation Crest factor Rated output frequency Output frequency regulation Total output voltage distortion Load power factor range Number of output phases Output Overload (Battery Mode)
Rev 0
Page 2 of 3
*Allow 100mm rear clearance for connections ** Height includes rubber feet
BATTERY RUN TIMES NOTE: Battery times are approximate and vary depending on age, temperature and load configuration. Internal Batteries 6 / 10 7 / 14 5 / 14 10 / 24 5 / 14 6 / 19 + 1 EBM 29 / 68 24 / 60 42 / 91 24 / 53 32 / 78 + 2 EBMs 51 / 113 44 / 68 78 / 145 45 / 95 64 / 148 + 3 EBMs 81 / 192 72 / 172 100 / 200 72 / 137 96 / 211 + 4 EBMs 98 / 246 89 / 190 134 / 270 90 / 170 130 / 266
Level 1: 100-110%: Activates Overload alarm Level 2: >110-130% UPS shuts down after 5 minutes Level 3: >130-150%: UPS shuts down after 15 seconds (700-3000VA), 30 seconds (6000VA) Level 4: >150%: UPS shuts down after 300ms