Heat-Shrink Terminations

HVT-G/SG 1/C

Shielded power cable (535 kV)

Superior High-contamination withstand and non-tracking The unique high-voltage insulating sleeve is a field-proven, nontracking, and erosion-resistant material that does not require periodic cleaning. The material properties have been formulated to be thermally stable and highly resistant to UV degradation, weathering and environmental pollution. Positive environmental seal The cable, along with external ground, is sealed from moisture ingress using

Tyco Electronics proven high-voltage, heat-activated sealing system. No field engineering or additional accessory kits are required. Rated to IEEE-48-1990, class 1. Indoor (in enclosures) or outdoor (weather-exposed) use. For use on copper tape, wire shield, lead sheath, and UniShield cables. 113

Selection information: (dimensions in inches/millimeters) Catalog number Indoor Outdoor Conductor size (AWG/kcmil) 58 kV HVT-80-G HVT-80-SG HVT-81-G HVT-81-SG HVT-82-G HVT-82-SG HVT-83-G HVT-83-SG HVT-84-G HVT-84-SG Installed length: 10.5 (267) 15 kV HVT-151-G HVT-151-SG HVT-152-G HVT-152-SG HVT-153-G HVT-153-SG HVT-154-G HVT-154-SG Installed length: 15 (381) 25 kV HVT-252-G HVT-252-SG HVT-253-G HVT-253-SG HVT-254-G HVT-254-SG HVT-255-G HVT-255-SG Installed length: 28 (711) 35 kV HVT-352-G HVT-352-SG HVT-353-G HVT-353-SG HVT-354-G HVT-354-SG HVT-355-G HVT-355-SG Installed length: 33 (838) 5 kV conductor size (AWG/kcmil) #4#1* 1/0250* 300500* 6001750* 15002500* 8 kV conductor size (AWG/kcmil) #6#2 #14/0 250500 6001750 20002500 Insulation diameter (min.max.) 0.350.60 0.600.95 0.801.25 1.101.75 1.602.45 (915) (1524) (2032) (2844) (4162) Jacket O.D. (max.) 0.95 1.20 1.50 2.10 2.75 (24) (30) (38) (53) (70)

#41/0 2/0350 4001000 12502500

0.600.95 0.801.25 1.101.65 1.602.45

(1524) (2032) (2842) (4162)

1.20 1.50 2.10 2.75

(30) (38) (53) (70)

#2250 300750 10001750 20002500

0.801.25 1.101.70 1.602.45 2.053.00

(2032) (2843) (4162) (5276)

1.50 2.10 2.75 3.45

(38) (53) (70) (88)

#11/0 2/0500 7501750 20002500

0.801.25 1.101.85 1.602.45 2.053.00

(2032) (2847) (4162) (5276)

1.50 2.10 2.75 3.45

(38) (53) (70) (88)

Ordering information: 1. Select the appropriate catalog number. Selections are based on the typical dimensions of 100% insulated cables manufactured in accordance with data contained in AEIC CS5-1987 and AEIC CS6-1987, as well as the dimensions of commonly used connectors. Nominal insulation thickness (100%): 5 kV: 90 mils 8 kV: 115 mils; 15 kV: 175 mils; 25 kV: 260 mils; 35 kV: 345 mils. Nominal insulation thickness (133%): 15 kV: 220 mils.

* 2. 3. 4. 5.

6.

If using 5 - 8 kV (115-mil) cable, use 8 kV selection. For cables manufactured to other specifications, confirm selection with cable dimensions. Kits do not contain connectors; order compression or solder connectors separately. All kits include a solderless ground connection. Outdoor (-SG) kits include skirts for outdoor use. To order skirts separately, see page125. Standard package: Three single-conductor kits/box.
USA: 800-327-6996

7. See page 104 for testing information. 8. Related test reports: EDR-5217 58 kV: EDR 5217 EDR-5218 15 kV: EDR 5218 EDR-5219 25 kV: EDR 5219 EDR-5222 35 kV: EDR 5222 9. See next page for 3/C modification kits. 10. Miscellaneous accessories are found on page 94. 11. Cable mounting brackets are available to accommodate cable diameter. See page 123.
Related installation instructions: HVT-5-35kV G/SG Outside US: 919.557.8903

Tyco Electronics Corporaton Issued 2004-2005 http://energy.tycoelectronics.com

Fax: 800.527.8350

Terminations Index

Main Index

Heat-Shrink Terminations

MOD3HVT

3/C modification kits for Tyco Electronics Raychem mediumvoltage terminations (535 kV)
MOD-3-HVT kits are available for both unsealed and sealed applications.

Use MOD-3-HVT kits in conjunction with three Tyco Electronics 1/C terminations to seal and rejacket the cable terminations.

115 Selection information: (dimensions in inches/millimeters) Indoor (without breakout boot) 1/C termination indoor 58 kV HVT-80-G HVT-Z-80-G HVT-81-G HVT-Z-81-G HVT-82-G HVT-Z-82-G HVT-83-G HVT-Z-83-G HVT-84-G HVT-Z-84-G 15 kV HVT-151-G HVT-Z-151-G HVT-152-G HVT-Z-152-G HVT-153-G HVT-Z-153-G HVT-154-G HVT-Z-154-G 25 kV HVT-252-G HVT-Z-252-G HVT-253-G HVT-Z-253-G HVT-254-G HVT-Z-254-G HVT-255-G HVT-Z-255-G 35 kV HVT-352-G HVT-Z-352-G HVT-353-G HVT-Z-353-G HVT-354-G HVT-Z-354-G HVT-355-G *Refer to Selection information (#3) below this table.

Outdoor/Indoor (includes breakout boot) MOD-3-HVT kit 1/C termination outdoor MOD-3X-HVT* MOD-3X-HVT MOD-3X-HVT MOD-3Y-HVT MOD-3Y-HVT MOD-3X-HVT MOD-3X-HVT MOD-3Y-HVT MOD-3Y-HVT MOD-3X-HVT MOD-3Y-HVT MOD-3Y-HVT MOD-3Y-HVT* MOD-3X-HVT MOD-3Y-HVT MOD-3Y-HVT MOD-3Y-HVT* HVT-80-SG HVT-81-SG HVT-82-SG HVT-83-SG HVT-84-SG HVT-151-SG HVT-152-SG HVT-153-SG HVT-154-SG HVT-252-SG HVT-253-SG HVT-254-SG HVT-255-SG HVT-352-SG HVT-353-SG HVT-354-SG HVT-355-SG HVT-Z-80-SG HVT-Z-81-SG HVT-Z-82-SG HVT-Z-83-SG HVT-Z-84-SG HVT-Z-151-SG HVT-Z-152-SG HVT-Z-153-SG HVT-Z-154-SG HVT-Z-252-SG HVT-Z-253-SG HVT-Z-254-SG HVT-Z-255-SG HVT-Z-352-SG HVT-Z-353-SG HVT-Z-354-SG -

MOD-3-HVT kit MOD-3A-HVT* MOD-3A-HVT MOD-3A-HVT MOD-3B-HVT MOD-3B-HVT* MOD-3A-HVT MOD-3A-HVT MOD-3B-HVT MOD-3B-HVT* MOD-3A-HVT MOD-3B-HVT MOD-3B-HVT* MOD-3B-HVT* MOD-3A-HVT MOD-3B-HVT MOD-3B-HVT* MOD-3B-HVT*

Catalog number MOD-3X-HVT (unsealed) MOD-3Y-HVT (unsealed) MOD-3A-HVT (sealed) MOD-3B-HVT (sealed)

Insulation diameter (min.max.) 0.501.35 (1334) 1.002.70 (2569) 0.501.25 (1332) 1.002.10 (2553)

Jacket diameter (min.max.)

1.253.85 (3298) 2.655.30 (67135)

Ordering information: 1. Select three HVT single-conductor terminations from pages 113 - 114. 2. To select the appropriate modification kit for the HVT terminations, use the MOD-3-HVT selection table above. 3. Use the MOD-3-HVT dimensions table to confirm the insulation and jacket diameters. If the diameters of your cable fall outside the MOD-3-HVT kits use range, you can purchase MOD-3-HVT components separately. 4. To order kit components separately or in bulk quantities, use the kit components and bulk ordering information table on page 116.
Related installation instructions: MOD-3-HVT Tyco Electronics Corporaton Issued 2004-2005 http://energy.tycoelectronics.com USA: 800-327-6996 Fax: 800.527.8350 Outside US: 919.557.8903

Terminations Index

Main Index

Heat-Shrink Terminations

116

3/C cable terminating MOD-3X-HVT and MOD-3Y-HVT are for jacketing of phases and ground conductors. MOD-3A-HVT and MOD-3B-HVT provide jacketing, plus an environmental crotch sealing boot. Tubing provided does not have sealant coating on the inner wall. This makes it easy to remove, like any cable jacket. Each kit includes three 4-feet long sleeves for the phases and three 4-feet long smaller sleeves for any ground conductors. (Tubing can be field-cut to appropriate length.) A unique six-legged cable breakout boot, provided in -3A and -3B kits, has an internal coating of a special adhesive to provide total environmental sealing of the cable crotch (breakout) area. It has three large legs for the phases and three smaller legs for ground conductors. Plugs are included for insertion into any unused ground legs to maintain the environmental seal integrity. 3/C mod kit for converting one 3/C cable to three 1/C cables. Ordering information: 1. Standard package: 1 kit/box. 2. Kit contents: Unsealed (-3X and -3Y) kits contain rejacketing tubes for phase and ground conductors, and sealant for indoor terminations that dont require environmental sealing. Sealed (-3A and -3B) kits contain rejacketing tubes, sealant, a cable breakout, and plugs for both outdoor and indoor terminations. 3. Kit components can be purchased in bulk quantities (see table below). 4. To order cable prep kits, see page 94.
Note: MOD-3-HVT kits should be installed prior to installing Tyco Electronics HVT kits.

HVBC kit, see page 157.

1/C HVT series termination.

Heat-shrink jacketing tubes for protection of the phases and any ground conductors.

Heat-shrink cable breakout boot for crotch seal.

MOD-3-HVT kit components and bulk ordering information Catalog number MOD-3X-HVT Kit components Uncoated tubing to rejacket each phase Uncoated tubing to rejacket each ground Sealant strip Uncoated tubing to rejacket each phase Uncoated tubing to rejacket each ground Sealant strip Uncoated tubing to rejacket each phase Uncoated tubing to rejacket each ground Sealant strip Cable breakout boot Cable breakout plugs Sealant-coated shim tubing Uncoated tubing to rejacket each phase Uncoated tubing to rejacket each ground Sealant strip Cable breakout boot Cable breakout plugs Ground wire shim tubing Component catalog number 3 each MWTM-35/12-1200/U 3 each MWTM-16/5-1500/U 1 each S1085-3-380 3 each MWTM-85/25-1500/U 3 each MWTM-16/5-1200/U 1 each S1085-3-380 3 each MWTM-35/12-1200/U 3 each MWTM-16/5-1200/U 1 each S1085-3-380 1 each CBR-6-1-A 3 each CBR-PLUG 1 each WCSM-70/21-150-S 3 each MWTM-85/25-1500/U 3 each MWTM-16/5-1200/U 1 each S1085-3-380 1 each CBR-6-2-A 3 each CBR-PLUG 3 each WCSM-20/6-150S Bulk ordering catalog number MWTM-35/12-A/U MWTM-16/5-A/U S1085-3-380 LVIT-75/25-A/U MWTM-16/5-A/U S1085-3-380 MWTM-35/12-A/U MWTM-16/5-A/U S1085-3-380 CBR-6-1-A CBR-PLUG WCSM-70/21-1200S LVIT-75/25-A/U MWTM-16/5-A/U S1085-3-380 CBR-6-2-A CBR-PLUG WCSM-20/6-150S (B50)

MOD-3Y-HVT

MOD-3A-HVT

MOD-3B-HVT

Tyco Electronics Corporaton Issued 2004-2005 http://energy.tycoelectronics.com