INTERLOCKS
WHY
INTERLOCKS
ARE
REQUIRED
1. PREVENTS HUMAN MISTAKES

2. INDEPENDENCY OF REQUIREMENT BETWEEN


OPERATION OF CIRCUITS AND INTERLOCKING
SHOULD BE KEPT IN MIND TO ACHIEVE HIGHEST
POSSIBLE RELIABULITY.
INTERLOCKS
ISOLATOR
AND
EARTH SWITCH
INTERLOCKS
FOR

1. SINGLE MAIN BUS WITH TRANSFER BUS SYSTEM

2. DOUBLE MAIN BUS WITH TRANSFER BUS


SYSTEM

3. ONE AND HALF BREAKER SYSTEM


INTERLOCKS
STANDARD PRACTICE
1. FOR BUS ISOLATON: EACH BUS HAVING BUS ISOLATOR FOR
EACH BAY.
2. FOR CB ISOLATION: CIRCUIT BREAKER HAVING BOTH SIDES
ISOLATORS.
3. FOR LINE/ICT ISOLATION: LINE / ICT HAVING LINE ISOLATOR.
4. FOR BUS MAINTANENCE: EACH BUS HAVING BUS EARTH
SWITCH.
5. FOR CB MAINTANENCE: EACH ISOLATOR HAVING EARTH
SWITCH TOWARDS CB SIDE.
6. FOR LINE / ICT MAINTANENCE: EACH LINE / ICT HAVING LINE
EARTH SWITCH.
INTERLOCKS
ISOLATORS
1. ISOLATORS ARE NO LOAD SWITCHES. THEY ARE NOT PERMITTED TO
BREAK POWER CURRENT OR TO CONNECT DIFFERENT VOLTAGE SYSTEM.
2. MAKING OR BREAKING OF PARALLEL CIRCUITS IS PERMITTED.
3. AN ISOLATOR CONNECTED IN SERIES WITH A CB MAY BE OPERATED
WHEN CB IS OPEN AND IF NONE OF ADJACENT EARTH SWITCHES IS
CLOSED. EVEN IF ANOTHER ISOLATOR CONNECTED IN SERIES TO THE CB
IS OPEN THE ISOLATOR IS NOT ALLOWED TO OPERATED UNLESS THE CB
IS OPEN.
4. AN ISOLATOR CONNECTED TO A DUPLICATE BUSBAR OR AUXILIARY BUS
MAY BE OPERATED IF
i) NO LOAD IS CONNECTED AND NON OF THE EARTH SWITCH IS CLOSED.
ii) A PARALLELING CIRCUIT TO THE ISOLATOR IS PRESENT. (ONLY
THROUGH THE BUSCOUPLER FOR THE ISOLATORS THAT ARE CONNECTED
TO THE TRANSFER BUS.

EARTH SWITCH
1. OPERATED ONLY IF THE ISOLATORS ON BOTH THE SIDES ARE OPEN.
2. EARTH SWITCHES WHICH CAN EARTH AN INCOMING LINE DIRECTLY OR
THROUGH A CB CAN BE OPERATED IF AND ONLY IF THE LINE IS DEAD.
INTERLOCKS
INTERLOCKS
SINGLE BUS & TRANSFER BUS SYSTEM
T/F-1 T/F-2

TRANSFER BUS

TRANSFER BUS COUPLER


BUS
BAY1 BAY2 BAY3 BAY4 BAY5

FEEDER1 FEEDER2
INTERLOCKS LINE BAY
BB189E
MAIN BUS(A)
BB389E
TRANSFER BUS( C )
89-C 89-A
FOR 89-A/BAY ISOLATOR OPERATION:
1. 52 CB/BAY IN OPEN CONDITION.
89-AE
2. 89AE/BAY EARTH SWITCH OPEN CONDITION.
52-CB 3. 89LE1/BAY EARTH SWITCH OPEN CONDITION.
4. BB189E BUSEARTH SWITCH OPEN CONDITION.
89-LE1

OPEN
BB189E
89-L OPEN
52 CB/BAY
OPERATION
89-AE/BAY
OPEN & 89A/BAY

FEEDER OR 89-LE2 OPEN


89-LE1/BAY
ICT OR
REACTOR
BB189E 52 CB 89-AE 89-LE1 89-A/BAY

OPEN OPEN OPEN OPEN INTER


LOCK
CONTACTOR
INTERLOCKS LINE BAY
BB189E
MAIN BUS(A)
BB389E
TRANSFER BUS( C )
89-C 89-A
FOR 89-L ISOLATOR OPERATION:
1. 52 CB IN OPEN CONDITION.
89-AE
2. 89AE EARTH SWITCH OPEN CONDITION.
52-CB 3. 89LE1 EARTH SWITCH OPEN CONDITION.
4. 89LE2 LINE EARTH SWITCH OPEN CONDITION.
89-LE1

OPEN
52 CB
89-L OPEN
89-AE OPERATION
89-LE1
OPEN & 89L

FEEDER OR 89-LE2 OPEN


89-LE2
ICT OR
REACTOR
52 CB 89-AE 89-LE1 89-LE2 89-L

OPEN OPEN OPEN OPEN INTER


LOCK
CONTACTOR
INTERLOCKS LINE BAY
BB189E
MAIN BUS(A)
BB389E
TRANSFER BUS( C )
89-C 89-A
FOR 89-AE EARTH SWITCH OPERATION:
1. 89-A ISOLATOR OPEN CONDITION.
89-AE
2. 89-L ISOLATOR OPEN CONDITION.
52-CB

89-LE1

OPEN
89-L 89-A
OPERATION
OPEN
& 89-AE

89-LE2 89-L
FEEDER OR
ICT OR
REACTOR
89-A 89-L 89-AE

OPEN OPEN INTER


LOCK
CONTACTOR
INTERLOCKS LINE BAY
BB189E
MAIN BUS(A)
BB389E
TRANSFER BUS( C )
89-C 89-A
FOR 89-LE1 EARTH SWITCH OPERATION:
1. 89-A ISOLATOR OPEN CONDITION.
89-AE
2. 89-L ISOLATOR OPEN CONDITION.
52-CB

89-LE1

OPEN
89-L 89-A
OPERATION
OPEN
& 89-LE1

89-LE2 89-L
FEEDER OR
ICT OR
REACTOR
89-A 89-L 89-LE1

OPEN OPEN INTER


LOCK
CONTACTOR
INTERLOCKS LINE BAY
BB189E
MAIN BUS(A)
BB389E
TRANSFER BUS( C )
89-C 89-A
FOR 89-LE2 EARTH SWITCH OPERATION:
1. 89C BUS ISOLATOR OPEN CONDITION.
89-AE
2. 89L LINE ISOLATOR OPEN CONDITION.
52-CB 3. LINE DEAD CONDITION i.e U/V RELAY
OPERATED.
89-LE1

OPTD
U/V RELAY
89-L
OPEN
OPERATION
89-C
& 89-LE2

FEEDER OR 89-LE2 OPEN


89-L
ICT OR
REACTOR
U/V RELAY 89-C 89-L 89-LE2

OPTD OPEN OPEN INTER


LOCK
CONTACTOR
INTERLOCKS LINE BAY
BB189E
MAIN BUS(A)
BB389E
TRANSFER BUS( C )
89-C 89-A
FOR 52 CB CIRCUIT BREAKER FOR REMOTE OPERATION:
1. 86-GA HSTR/MTR RESET CONDITION.
89-AE 2. 86-GB HSTR/MTR RESET CONDITION.
3. 96-BB TBC HSTR/MTR RESET CONDITION.
52-CB

89-LE1

RESET
86-GA
89-L
RESET
REMOTE
86-GB
& OPERATION
52-CB

FEEDER OR 89-LE2 RESET


96-BB
ICT OR
REACTOR
86-GA 86-GB 96-BB 52-CB

RESET RESET RESET INTER


LOCK
CONTACTOR
INTERLOCKS LINE BAY
BB189E
MAIN BUS(A)
BB389E
TRANSFER BUS( C )
89-C 89-A
FOR 52 CB CIRCUIT BREAKER FOR LOCAL OPERATION:
1. 89-A ISOLATOR OPEN CONDITION.
89-AE 2. 89-L ISOLATOR OPEN CONDITION.
3. 89-AE TBC EARTH SWITCH CLOSED CONDITION.
52-CB
4. 89-LE1 EARTH SWITCH CLOSED CONDITION.
89-LE1

OPEN
89-A
89-L OPEN
89-L
LOCAL
89-AE CLOSE & OPERATION
52-CB

FEEDER OR 89-LE2 CLOSE


89-LE1
ICT OR
REACTOR
89A 89L 89-AE 89-LE1 52CB

OPEN OPEN CLOSE CLOSE INTER


LOCK
CONTACTOR
INTERLOCKS LINE BAY
BB189E
MAIN BUS(A)
BB389E
TRANSFER BUS( C )
89-C
89-C 89-A
89-A
52-CB

89-AE
89-CE 89-AE
52-CB

89-LE1
TRANSFER BUS COUPLER
FOR 89-C ISOLATOR OPERATION:
89-L 1. NO OTHER ISOLATOR IS CLOSED TO TRANSFER BUS C
2. BB389E EARTH SWITCH OPEN CONDITION.
3. 89LE2 EARTH SWITCH OPEN CONDITION.
FEEDER OR 89-LE2 4. 52 TBC CB IN OPEN CONDITION.
ICT OR OR
REACTOR 1. 52 CB IN CLOSED POSITION.
2. 89-A ISOLATOR CLOSED CONDITION.
3. 89-L ISOLATOR CLOSED POSITION.
4. 89-A/TBC BAY BUS-A ISOLATOR CLOSED POSITION.
5. 89-C/TBC BAY BUS-C ISOLATOR CLOSED POSITION.
6. NO OTHER ISOLATOR IS CLOSED TO TRANSFER BUS C
7. ADDITIONAL INTERLOCK PROTECTION TRANSFERRED
MAY ALSO PUT THROUGH PROTECTION TRANSFER
SWITCH.
INTERLOCKS LINE BAY
89-C/ LINE-1 89-C/ LINE-2 89-C/ ICT-1 89-C/ ICT-2

FUTURE BAYS
+ VE

89-LE2 89-LE2 89-TE2 89-TE2


LINE-1 LINE-2 ICT-1 ICT-2

89-C/ LINE-1 89-C/ LINE2 89-C/ ICT-1 89-C/ ICT-2 + VE

FOR LINE-1 FOR LINE-2 FOR ICT-1 FOR ICT-2

TO OBTAIN A CONTACT FOR NO OTHER ISOLATOR CLOSED TO BUSBAR’C’

1. TO OBTAIN CONTACTS OF TRANSFER BUS COUPLER CIRCUIT


CLOSSED IT IS PREFERED TO USE CONTACTS OF AUXILIARY RELAY
ENERGISED UNDER THESE CONDITIONS.
2. TO MAKE SURE THE PROTECTION IS TRANSFERRED TO TBC CIRCUIT
BREAKER BEFORE THE ISOLATOR IS CLOSSED, CONTACT OF TRIP
TRANSFER SWITCH MAY BE UTILISED.
INTERLOCKS LINE BAY
OPEN OPERATION
52CB/TBC 89-C/BAY
OPEN TTS
TRANSFER OR
89-LE2
CLOSE
BB389E
OPEN & 89-A/TBC
CLOSE
CLOSE 89-C/TBC
NO OTHER
CLOSE
ISOLATOR 52CB/BAY &
CLOSED TO CLOSE
BUSBAR-C 89-A
CLOSE
89L
NO OTHER CLOSE
ISOLATOR
CLOSED TO
BUSBAR-C

NO OTHER
52CB/TBC 89LE2 BB389E ISOLATOR
89-C/BAY
CLOSED TO
BUSBAR-C

OPEN OPEN OPEN CLOSE INTER


LOCK
CONTACTOR

NO OTHER
TTS ISOLATOR
N T CLOSED TO

.
89-A/TBC 89C/TBC 52CB/BAY 89A/BAY 89L/BAY BUSBAR-C

CLOSE CLOSE CLOSE CLOSE CLOSE CLOSE


INTERLOCKS TBC BAY
BB189E
MAIN BUS(A)
BB389E
TRANSFER BUS( C )
89-C 89-A
FOR 89-A / TBC ISOLATOR OPERATION:
1. 52 CB / TBC IN OPEN CONDITION.
2. 89AE / TBC EARTH SWITCH OPEN CONDITION.
89-CE 52-CB 89-AE
3. 89CE / TBC EARTH SWITCH OPEN CONDITION.
4. BB189E BUSEARTH SWITCH OPEN CONDITION.

TRANSFER BUS COUPLER OPEN


BB189E
OPEN
52 CB / TBC
OPERATION
89-AE / TBC
OPEN & 89A / TBC

OPEN
89-CE / TBC

BB189E 52 CB/TBC 89-AE/TBC 89-CE/TBC 89-A/TBC

OPEN OPEN OPEN OPEN INTER


LOCK
CONTACTOR
INTERLOCKS TBC BAY
BB189E
MAIN BUS(A)
BB389E
TRANSFER BUS( C )
89-C 89-A
FOR 89-C / TBC ISOLATOR OPERATION:
1. 52 CB / TBC IN OPEN CONDITION.
2. 89AE / TBC EARTH SWITCH OPEN CONDITION.
89-CE 52-CB 89-AE
3. 89CE / TBC EARTH SWITCH OPEN CONDITION.
4. BB389E BUSEARTH SWITCH OPEN CONDITION.

TRANSFER BUS COUPLER OPEN


BB389E
OPEN
52 CB / TBC
OPERATION
89-AE / TBC
OPEN & 89C / TBC

OPEN
89-CE / TBC

BB389E 52 CB/TBC 89-AE/TBC 89-CE/TBC 89-C/TBC

OPEN OPEN OPEN OPEN INTER


LOCK
CONTACTOR
INTERLOCKS TBC BAY
BB189E
MAIN BUS(A)
BB389E
TRANSFER BUS( C )
89-C 89-A
FOR 89-AE / TBC EARTH SWITCH OPERATION:
1. 89-A / TBC ISOLATOR OPEN CONDITION.
2. 89-C / TBC ISOLATOR OPEN CONDITION.
89-CE 52-CB 89-AE

TRANSFER BUS COUPLER


OPEN
89-A / TBC
OPERATION
OPEN
& 89-AE / TBC

89-C/TBC

89-A/TBC 89-C/TBC 89-AE/TBC

OPEN OPEN INTER


LOCK
CONTACTOR
INTERLOCKS TBC BAY
BB189E
MAIN BUS(A)
BB389E
TRANSFER BUS( C )
89-C 89-A
FOR 89-CE / TBC EARTH SWITCH OPERATION:
1. 89-A / TBC ISOLATOR OPEN CONDITION.
2. 89-C / TBC ISOLATOR OPEN CONDITION.
89-CE 52-CB 89-AE

TRANSFER BUS COUPLER


OPEN
89-A / TBC
OPERATION
OPEN
& 89-CE / TBC

89-C/TBC

89-A/TBC 89-C/TBC 89-CE/TBC

OPEN OPEN INTER


LOCK
CONTACTOR
INTERLOCKS TBC BAY
BB189E
MAIN BUS(A)
BB389E
TRANSFER BUS( C )
89-C 89-A
FOR 52 CB / TBC CIRCUIT BREAKER FOR REMOTE OPERATION:
1. 86-GA / TBC HSTR/MTR RESET CONDITION.
2. 86-GB / TBC HSTR/MTR RESET CONDITION.
89-CE 52-CB 89-AE 3. 96-BB / TBC HSTR/MTR RESET CONDITION.

TRANSFER BUS COUPLER RESET


86-GA/TBC

RESET
REMOTE
86-GB/TBC
& OPERATION
52-CB/TBC

RESET
96-BB/TBC

86-GA/TBC 86-GB/TBC 96-BB/TBC 52-CB/TBC

RESET RESET RESET INTER


LOCK
CONTACTOR
INTERLOCKS TBC BAY
BB189E
MAIN BUS(A)
BB389E
TRANSFER BUS( C )
89-C 89-A
FOR 52 CB / TBC CIRCUIT BREAKER FOR LOCAL OPERATION:
1. 89-A / TBC ISOLATOR OPEN CONDITION.
2. 89-C / TBC ISOLATOR OPEN CONDITION.
89-CE 52-CB 89-AE 3. 89-AE / TBC EARTH SWITCH CLOSED CONDITION.
4. 89-CE / TBC EARTH SWITCH CLOSED CONDITION.

TRANSFER BUS COUPLER


OPEN
89-A/TBC
OPEN
89-C/ TBC
LOCAL
89-AE / TBC CLOSE & OPERATION
52-CB / TBC

CLOSE
89-CE / TBC

89A/TBC 89C/TBC 89-AE/TBC 89-CE/TBC 52CB/TBC

OPEN OPEN CLOSE CLOSE INTER


LOCK
CONTACTOR
INTERLOCKS BUS BAY
BB189E
MAIN BUS(A)
BB389E
TRANSFER BUS( C )
89-C
89-C 89-A
89-A
52-CB

89-AE
89-CE 89-AE
52-CB

89-LE1
TRANSFER BUS COUPLER
FOR BB189E EARTH SWITCH OPERATION:
89-L 1. ALL BAYS BUS-A ISOLATORS OPEN CONDITION
OPEN
89-A/BAY1
FEEDER OR 89-LE2 OPEN
89-A/BAY2
OPERATION
ICT OR & BB189E
UP TO NO OF BAYS
REACTOR
OPEN
89-A/BAYn

89-A /BAY1 89-A/BAY2 89-A / BAY n BB189E

UP TO NO OF BAYS
OPEN OPEN OPEN INTER
LOCK
CONTACTOR
INTERLOCKS BUS BAY
BB189E
MAIN BUS(A)
BB389E
TRANSFER BUS( C )
89-C
89-C 89-A
89-A
52-CB

89-AE
89-CE 89-AE
52-CB

89-LE1
TRANSFER BUS COUPLER
FOR BB389E EARTH SWITCH OPERATION:
89-L 1. ALL BAYS BUS-C ISOLATORS OPEN CONDITION
OPEN
89-C/BAY1
FEEDER OR 89-LE2 OPEN
89-C/BAY2
OPERATION
ICT OR & BB389E
UP TO NO OF BAYS
REACTOR
OPEN
89-C/BAYn

89-C /BAY1 89-C/BAY2 89-C / BAY n BB389E

UP TO NO OF BAYS
OPEN OPEN OPEN INTER
LOCK
CONTACTOR
INTERLOCKS
INTERLOCKS
DOUBLE MAIN BUS & TRANSFER BUS SYSTEM
T/F-1 T/F-2

BUS-1

BUS COUPLER
BUS-2

TRANSFER BUS
COUPLER
BAY3 BAY4 BAY5
BAY1 BAY2 TRANSFER BUS BAY6 BAY7 BAY8

FEEDER1 FEEDER2 FEEDER3 FEEDER4


INTERLOCKS FEEDER BAY
BB189E
MAIN BUS-1(A) FOR 89-A/BAY ISOLATOR OPERATION:
OPEN
BB289E 52CB/BAY
MAIN BUS-2(B) OPEN
89-LE1/BAY
BB389E &
OPEN
TRANSFER BUS( C ) 89-AE/BAY
OPEN
89-AE 89-A 89-B 89-C 89-B/BAY

CLOSE
52-CB 89-B/BAY
CLOSE
52CB/BAY OPERATION
CLOSE OR BB189E & 89-A/BAY
89-LE1
89-A/BC
& OPEN
CLOSE
89-B/BC
89-L CLOSE
52CB/TBC

89-LE2 52CB/BAY 89LE1/BAY 89-AE/BAY 89-B/BAY BB189E 89-A/BAY

FEEDER OR
OPEN OPEN OPEN OPEN OPEN INTER
ICT OR LOCK
REACTOR 89-B/BAY 52CB/BAY 89-B/BC 52 CB/BC 89-A/BC
CONTACTOR

OF BAY
CLOSE CLOSE CLOSE CLOSE CLOSE
INTERLOCKS FEEDER BAY
BB189E
MAIN BUS-1(A) FOR 89-B/BAY ISOLATOR OPERATION:
OPEN
BB289E 52CB/BAY
MAIN BUS-2(B) OPEN
89-LE1/BAY
BB389E &
OPEN
TRANSFER BUS( C ) 89-AE/BAY
OPEN
89-AE 89-A 89-B 89-C 89-A/BAY

CLOSE
52-CB 89-A/BAY
CLOSE
52CB/BAY OPERATION
CLOSE OR BB289E & 89-B/BAY
89-LE1
89-A/BC
& OPEN
CLOSE
89-B/BC
89-L CLOSE
52CB/TBC

89-LE2 52CB/BAY 89LE1/BAY 89-AE/BAY 89-A/BAY BB289E 89-B/BAY

FEEDER OR
OPEN OPEN OPEN OPEN OPEN INTER
ICT OR LOCK
REACTOR 89-A/BC 52CB/BAY 89-B/BC 52 CB/BC 89-A/BAY
CONTACTOR

OF BAY
CLOSE CLOSE CLOSE CLOSE CLOSE
INTERLOCKS FEEDER BAY
OPEN OPERATION
52CB/TBC 89-C/BAY
OPEN TTS
TRANSFER OR
89-LE2/BAY
CLOSE
BB389E
OPEN & 89-C/TBC
CLOSE
52CB/BAY
CLOSE
NO OTHER CLOSE
ISOLATOR
89L/BAY &
CLOSED TO
BUSBAR-C NO OTHER CLOSE
CLOSE ISOLATOR
89-B/TBC
89-B/BAY
CLOSE & CLOSED TO
BUSBAR-C

OR
CLOSE
89-A/TBC FOR 89-C/BAY ISOLATOR OPERATION:
89-A/BAY
CLOSE &
NO OTHER
52CB/TBC 89LE2 BB389E ISOLATOR
89-C/BAY
CLOSED TO
BUSBAR-C

OPEN OPEN OPEN CLOSE INTER


89B/TBC 89B/BAY LOCK
CONTACTOR
NO OTHER
TTS ISOLATOR
CLOSE CLOSE CLOSED TO
N T

.
89-A/TBC 89A/BAY 89C/TBC 52CB/BAY 89L/BAY BUSBAR-C

CLOSE CLOSE CLOSE CLOSE CLOSE CLOSE


INTERLOCKS FEEDER BAY
BB189E
MAIN BUS-1(A)
BB289E
MAIN BUS-2(B)
BB389E
TRANSFER BUS( C )
89-AE 89-A 89-B 89-C
FOR 89-L/BAY ISOLATOR OPERATION:
OPEN
52-CB 52 CB/BAY
OPEN
89-LE1/BAY
OPEN OPERATION
89-LE1 89-LE2/BAY & 89L/BAY
OPEN
89-AE/BAY
89-L
OPEN
ICT HV TE
(FOR ICT ONLY)
89-LE2

FEEDER OR
ICT OR
REACTOR 52 CB/BAY ICT HV TE 89-AE/BAY 89-LE1/BAY 89-LE2/BAY 89-L
OF BAY
OPEN OPEN OPEN OPEN OPEN INTER
(FOR ICT ONLY) LOCK
CONTACTOR
INTERLOCKS FEEDER BAY
BB189E
MAIN BUS-1(A)
BB289E
MAIN BUS-2(B)
BB389E
TRANSFER BUS( C )
89-AE 89-A 89-B 89-C

FOR 89-AE/BAY ISOLATOR OPERATION:

52-CB

OPEN
89-L/BAY

89-LE1 OPEN
89-A/BAY & OPERATION 89-AE/BAY

89-L 89-B/BAY OPEN

89-LE2

FEEDER OR 89A/BAY 89-B/BAY 89-L/BAY 89-AE/BAY


ICT OR
REACTOR OPEN OPEN OPEN INTER
OF BAY LOCK
CONTACTOR
INTERLOCKS FEEDER BAY
BB189E
MAIN BUS-1(A)
BB289E
MAIN BUS-2(B)
BB389E
TRANSFER BUS( C )
89-AE 89-A 89-B 89-C

FOR 89-LE1/BAY ISOLATOR OPERATION:

52-CB

OPEN
89-L/BAY

89-LE1 OPEN
89-A/BAY & OPERATION 89-LE1/BAY

89-L 89-B/BAY OPEN

89-LE2

FEEDER OR 89A/BAY 89-B/BAY 89-L/BAY 89-LE1/BAY


ICT OR
REACTOR OPEN OPEN OPEN INTER
OF BAY LOCK
CONTACTOR
INTERLOCKS FEEDER BAY
BB189E
MAIN BUS-1(A)
BB289E
MAIN BUS-2(B)
BB389E
TRANSFER BUS( C )
89-AE 89-A 89-B 89-C

FOR 89-LE2/BAY ISOLATOR OPERATION:

52-CB

89-L/BAY OPEN

89-C/BAY OPEN
89-LE1 & OPERATION 1-89LE2
OPTD
LINE U/V
(FOR LINE)
89-L OPEN
LV-89T (FOR ICT)

89-LE2

FEEDER OR LV-89T LINE U/V 89-C/BAY 89-L/BAY 89-LE2


ICT OR
REACTOR OPEN OPTD OPEN OPEN INTER
(FOR ICT)
OF BAY (FOR LINE)
LOCK
CONTACTOR
INTERLOCKS FEEDER BAY
BB189E
MAIN BUS-1(A)
BB289E
MAIN BUS-2(B)
BB389E
TRANSFER BUS( C )
89-AE 89-A 89-B 89-C

FOR 52 CB/BAY CIRCUIT BREAKER FOR REMOTE OPERATION:


1. 86-GA HSTR/MTR RESET CONDITION.
52-CB 2. 86-GB HSTR/MTR RESET CONDITION.
3. 96-BB TBC HSTR/MTR RESET CONDITION.

89-LE1
RESET
86-GA
89-L
RESET
REMOTE
86-GB
& OPERATION
52-CB/BAY
89-LE2
RESET
96-BB
FEEDER OR
ICT OR
REACTOR 86-GA 86-GB 96-BB 52-CB/BAY
OF BAY
RESET RESET RESET INTER
LOCK
CONTACTOR
INTERLOCKS FEEDER BAY
BB189E
MAIN BUS-1(A)
BB289E
MAIN BUS-2(B)
BB389E
TRANSFER BUS( C )
89-AE 89-A 89-B 89-C
FOR 52 CB /BAYCIRCUIT BREAKER FOR LOCAL OPERATION:
1. 89-A ISOLATOR OPEN CONDITION.
2. 89-L ISOLATOR OPEN CONDITION.
52-CB 3. 89-AE TBC EARTH SWITCH CLOSED CONDITION.
4. 89-LE1 EARTH SWITCH CLOSED CONDITION.

89-LE1 OPEN
89-A
89-L OPEN
89-L
LOCAL
89-AE CLOSE & OPERATION
52-CB/BAY

89-LE2
CLOSE
89-LE1
FEEDER OR
ICT OR
REACTOR 89A 89L 89-AE 89-LE1 52-CB/BAY
OF BAY
OPEN OPEN CLOSE CLOSE INTER
LOCK
CONTACTOR
INTERLOCKS TBC BAY
BB189E
MAIN BUS-1(A)
BB289E
MAIN BUS-2(B)
BB389E
TRANSFER BUS( C )
89-AE 89-A 89-B 89-C
FOR 89-A / TBC ISOLATOR OPERATION:
1. 52 CB / TBC IN OPEN CONDITION.
2. 89AE / TBC EARTH SWITCH OPEN CONDITION.
52-CB
3. 89CE / TBC EARTH SWITCH OPEN CONDITION.
4. BB189E BUSEARTH SWITCH OPEN CONDITION.
5. 89-B/TBC ISOLATOR OPEN CONDITION
89-CE OPEN
BB189E
TRANSFER OPEN
52 CB / TBC
BUS
OPEN OPERATION
COUPLER 89-AE / TBC
OPEN
& 89A / TBC

89-CE / TBC
89-B / TBC OPEN

89-B/TBC BB189E 52 CB/TBC 89-AE/TBC 89-CE/TBC 89-A/TBC

OPEN OPEN OPEN OPEN OPEN INTER


LOCK
CONTACTOR
INTERLOCKS TBC BAY
BB189E
MAIN BUS-1(A)
BB289E
MAIN BUS-2(B)
BB389E
TRANSFER BUS( C )
89-AE 89-A 89-B 89-C
FOR 89-B / TBC ISOLATOR OPERATION:
1. 52 CB / TBC IN OPEN CONDITION.
2. 89AE / TBC EARTH SWITCH OPEN CONDITION.
52-CB
3. 89CE / TBC EARTH SWITCH OPEN CONDITION.
4. BB289E BUSEARTH SWITCH OPEN CONDITION.
5. 89-A/TBC ISOLATOR OPEN CONDITION
89-CE OPEN
BB289E
TRANSFER OPEN
52 CB / TBC
BUS
OPEN OPERATION
COUPLER 89-AE / TBC
OPEN
& 89B / TBC

89-CE / TBC
89-A / TBC OPEN

89-A/TBC BB289E 52 CB/TBC 89-AE/TBC 89-CE/TBC 89-B/TBC

OPEN OPEN OPEN OPEN OPEN INTER


LOCK
CONTACTOR
INTERLOCKS TBC BAY
BB189E
MAIN BUS-1(A)
BB289E
MAIN BUS-2(B)
BB389E
TRANSFER BUS( C )
89-AE 89-A 89-B 89-C FOR 89-C / TBC ISOLATOR OPERATION:
1. 52 CB / TBC IN OPEN CONDITION.
2. 89AE / TBC EARTH SWITCH OPEN CONDITION.
52-CB 3. 89CE / TBC EARTH SWITCH OPEN CONDITION.
4. BB389E BUSEARTH SWITCH OPEN CONDITION.

OPEN
89-CE BB389E
OPEN
TRANSFER 52 CB / TBC
OPERATION
BUS 89-AE / TBC
OPEN & 89C / TBC

COUPLER OPEN
89-CE / TBC

BB389E 52 CB/TBC 89-AE/TBC 89-CE/TBC 89-C/TBC

OPEN OPEN OPEN OPEN INTER


LOCK
CONTACTOR
INTERLOCKS TBC BAY
BB189E
MAIN BUS-1(A)
BB289E
MAIN BUS-2(B)
BB389E
TRANSFER BUS( C )
89-AE 89-A 89-B 89-C
FOR 89-AE / TBC EARTH SWITCH OPERATION:
1. 89-A / TBC ISOLATOR OPEN CONDITION.
2. 89-B / TBC ISOLATOR OPEN CONDITION.
52-CB
3. 89-C / TBC ISOLATOR OPEN CONDITION.

89-CE
OPEN
TRANSFER 89-A / TBC
BUS OPEN OPERATION
COUPLER
89-B / TBC
OPEN
& 89-AE / TBC

89-C/TBC

89-A/TBC 89-B/TBC 89-C/TBC 89-AE/TBC

OPEN OPEN OPEN INTER


LOCK
CONTACTOR
INTERLOCKS TBC BAY
BB189E
MAIN BUS-1(A)
BB289E
MAIN BUS-2(B)
BB389E
TRANSFER BUS( C )
89-AE 89-A 89-B 89-C
FOR 89-CE / TBC EARTH SWITCH OPERATION:
1. 89-A / TBC ISOLATOR OPEN CONDITION.
2. 89-B / TBC ISOLATOR OPEN CONDITION.
52-CB
3. 89-C / TBC ISOLATOR OPEN CONDITION.

89-CE
OPEN
TRANSFER 89-A / TBC
BUS OPEN OPERATION
COUPLER
89-B / TBC
OPEN
& 89-CE / TBC

89-C/TBC

89-A/TBC 89-B/TBC 89-C/TBC 89-CE/TBC

OPEN OPEN OPEN INTER


LOCK
CONTACTOR
INTERLOCKS TBC BAY
BB189E
MAIN BUS-1(A)
BB289E
MAIN BUS-2(B)
BB389E
TRANSFER BUS( C )
89-AE 89-A 89-B 89-C
FOR 52 CB / TBC CIRCUIT BREAKER FOR REMOTE OPERATION:
1. 86-GA / TBC HSTR/MTR RESET CONDITION.
52-CB 2. 86-GB / TBC HSTR/MTR RESET CONDITION.
3. 96-BB / TBC HSTR/MTR RESET CONDITION.

RESET
89-CE 86-GA/TBC
TRANSFER RESET REMOTE
BUS 86-GB/TBC
& OPERATION
52-CB/TBC
COUPLER RESET
96-BB/TBC

86-GA/TBC 86-GB/TBC 96-BB/TBC 52-CB/TBC

RESET RESET RESET INTER


LOCK
CONTACTOR
INTERLOCKS TBC BAY
BB189E
MAIN BUS-1(A)
BB289E
MAIN BUS-2(B)
BB389E
TRANSFER BUS( C )
89-AE 89-A 89-B 89-C
FOR 52 CB / TBC CIRCUIT BREAKER FOR LOCAL OPERATION:
1. 89-A / TBC ISOLATOR OPEN CONDITION.
2. 89-B / TBC ISOLATOR OPEN CONDITION.
52-CB
3. 89-C / TBC ISOLATOR OPEN CONDITION.
4. 89-AE / TBC EARTH SWITCH CLOSED CONDITION.
5. 89-CE / TBC EARTH SWITCH CLOSED CONDITION.
89-CE
OPEN
89-A/TBC
TRANSFER
OPEN
BUS 89-B/TBC
LOCAL
COUPLER 89-C/ TBC
OPEN
& OPERATION
52-CB / TBC

89-AE / TBC CLOSE


CLOSE
89-CE / TBC

89A/TBC 89B/TBC 89C/TBC 89-AE/TBC 89-CE/TBC 52CB/TBC

OPEN OPEN OPEN CLOSE CLOSE INTER


LOCK
CONTACTOR
INTERLOCKS BC BAY
BB189E
MAIN BUS-1(A)
BB289E
MAIN BUS-2(B)
89-A 89-B
FOR 89-A / BC ISOLATOR OPERATION:
1. 52 CB / BC IN OPEN CONDITION.
2. 89AE / BC EARTH SWITCH OPEN CONDITION.
89-AE 52-CB 89-BE
3. 89BE / BC EARTH SWITCH OPEN CONDITION.
4. BB189E BUSEARTH SWITCH OPEN CONDITION.

BUS COUPLER OPEN


BB189E
OPEN
52 CB / BC
OPERATION
89-AE / BC
OPEN & 89A / BC

OPEN
89-BE / BC

BB189E 52 CB/BC 89-AE/BC 89-BE/BC 89-A/BC

OPEN OPEN OPEN OPEN INTER


LOCK
CONTACTOR
INTERLOCKS BC BAY
BB189E
MAIN BUS-1(A)
BB289E
MAIN BUS-2(B)
89-A 89-B
FOR 89-B / BC ISOLATOR OPERATION:
1. 52 CB / BC IN OPEN CONDITION.
2. 89AE / BC EARTH SWITCH OPEN CONDITION.
89-AE 52-CB 89-BE
3. 89BE / BC EARTH SWITCH OPEN CONDITION.
4. BB289E BUSEARTH SWITCH OPEN CONDITION.

BUS COUPLER OPEN


BB289E
OPEN
52 CB / BC
OPERATION
89-AE / BC
OPEN & 89B / BC

OPEN
89-BE / BC

BB289E 52 CB/BC 89-AE/BC 89-BE/BC 89-B/BC

OPEN OPEN OPEN OPEN INTER


LOCK
CONTACTOR
INTERLOCKS BC BAY
BB189E
MAIN BUS-1(A)
BB289E
MAIN BUS-2(B)
89-A 89-B
FOR 89-AE / BC EARTH SWITCH OPERATION:
1. 89-A / BC ISOLATOR OPEN CONDITION.
2. 89-B / BC ISOLATOR OPEN CONDITION.
89-AE 52-CB 89-BE

BUS COUPLER
OPEN
89-A / TBC
OPERATION
OPEN
& 89-AE / BC

89-B/TBC

89-A/BC 89-B/BC 89-AE/BC

OPEN OPEN INTER


LOCK
CONTACTOR
INTERLOCKS BC BAY
BB189E
MAIN BUS-1(A)
BB289E
MAIN BUS-2(B)
89-A 89-B

FOR 89-BE / BC EARTH SWITCH OPERATION:


1. 89-A / BC ISOLATOR OPEN CONDITION.
89-AE 52-CB 89-BE 2. 89-B / BC ISOLATOR OPEN CONDITION.

BUS COUPLER

OPEN
89-A / BC
OPERATION
OPEN
& 89-BE / BC

89-B/BC

89-A/BC 89-B/BC 89-BE/BC

OPEN OPEN INTER


LOCK
CONTACTOR
INTERLOCKS BC BAY
BB189E
MAIN BUS-1(A)
BB289E
MAIN BUS-2(B)
89-A 89-B

89-AE 52-CB 89-BE FOR 52 CB / BC CIRCUIT BREAKER FOR REMOTE OPERATION:


1. 86-GA / BC HSTR/MTR RESET CONDITION.
2. 86-GB / BC HSTR/MTR RESET CONDITION.
BUS COUPLER 3. 96-BB / BC HSTR/MTR RESET CONDITION.

RESET
86-GA/BC

RESET REMOTE
86-GB/BC
& OPERATION
52-CB/BC

RESET
96-BB/BC

86-GA/BC 86-GB/BC 96-BB/BC 52-CB/BC

RESET RESET RESET INTER


LOCK
CONTACTOR
INTERLOCKS BC BAY
BB189E
MAIN BUS-1(A)
BB289E
MAIN BUS-2(B)
89-A 89-B
FOR 52 CB / BC CIRCUIT BREAKER FOR LOCAL OPERATION:
1. 89-A / BC ISOLATOR OPEN CONDITION.
2. 89-B / BC ISOLATOR OPEN CONDITION.
89-AE 52-CB 89-BE
3. 89-AE / BC EARTH SWITCH CLOSED CONDITION.
4. 89-BE / BC EARTH SWITCH CLOSED CONDITION.

BUS COUPLER
OPEN
89-A/BC
OPEN
89-B/BC LOCAL
89-AE/BC CLOSE
& OPERATION
52-CB / BC

CLOSE
89-BE/BC

89A/BC 89B/BC 89-AE/BC 89-BE/BC 52CB/BC

OPEN OPEN CLOSE CLOSE INTER


LOCK
CONTACTOR
INTERLOCKS BUS ES
BB189E
MAIN BUS-1(A)
BB289E
MAIN BUS-2(B)

BB389E TRANSFER BUS( C )

89-AE 89-A 89-B 89-C 89-AE 89-A 89-B 89-C 89-A 89-B

52-CB 52-CB 89-AE 52-CB 89-BE

89-LE1 89-CE BUS COUPLER


89-L TRANSFER
BUS
COUPLER
89-LE2

FEEDER OR
ICT OR
REACTOR
OF BAY
INTERLOCKS BUS EARTH SWITCH
BB189E BB289E BB389E
OPEN OPEN OPEN
89-A/BAY1 89-B/BAY1 89-C/BAY1
OPEN OPEN OPEN
89-A/BAY2 89-B/BAY2 89-C/BAY2
OPERATION OPERATION OPERATION
UP TO NO OF BAYS
& BB189E UP TO NO OF BAYS
& BB289E UP TO NO OF BAYS
& BB389E
OPEN OPEN OPEN
89-A/BAYn 89-B/BAYn 89-C/BAYn

89-A /BAY1 89-A/BAY2 89-A / BAY n BB189E

UP TO NO OF BAYS
OPEN OPEN OPEN INTER
LOCK
CONTACTOR

89-B /BAY1 89-B/BAY2 89-B / BAY n BB289E FOR BUS EARTH SWITCH
OPERATION, ALL ISOLATORS
OPEN OPEN
UP TO NO OF BAYS
OPEN INTER
CONNECTED TO CONCERNED
LOCK BUS ARE TO BE OPENED.
CONTACTOR
89-C /BAY1 89-C/BAY2 89-C / BAY n BB389E

UP TO NO OF BAYS
OPEN OPEN OPEN INTER
LOCK
CONTACTOR
INTERLOCKS
INTERLOCKS
I-CONFIGUARATION
FEEDER1 FEEDER3 FEEDER5 FEEDER7 FEEDER9 FEEDER11

BUS-1 DIA1 DIA2 DIA3 DIA4 DIA5 DIA6

BAY10

BAY13

BAY16
BAY4

BAY7
BAY1

BAY11

BAY14

BAY17
BAY8
BAY2

BAY5

BAY12

BAY18
BAY15
BAY9
BAY3

BAY6

BUS-2

FEEDER2 FEEDER4 FEEDER6 FEEDER8 FEEDER10 FEEDER12


INTERLOCKS
D-CONFIGUARATION
FEEDER1 FEEDER2 FEEDER5 FEEDER6 FEEDER9 FEEDER10

BAY2 BAY8 BAY14

BAY15
BAY13
BAY3

BAY9
BAY1

BAY7
DIA1 DIA3 DIA5

BUS-1

BUS-2

BAY18
BAY10

BAY12
BAY6

BAY16
BAY4

DIA2 DIA4 DIA6

BAY5 BAY11 BAY17

FEEDER3 FEEDER4 FEEDER7 FEEDER8 FEEDER11 FEEDER12


INTERLOCKS
ONE & HALF BREAKER SYSTEM
BB1-89E BUS-1 BUS-2 BB2-89E

1-89 3-89
1-89E 3-89E

1-52CB 3-52CB

1-89AE 3-89AE

1-89A 3-89A
1-89RE 1-89R 2-89A 2-89B

2-89AE 2-52CB 2-89BE


LINE 1-89L 3-89T
UUU

SHUNT
REACTOR
. 1-89LE 3-89TE
1-PH NEUTRAL
UUU

GROUNDING
REACTOR
LINE 1
T/F-1
INTERLOCKS BAY 1
BB1-89E BUS-1

1-89
1-89E

1-52CB
FOR 1-89 ISOLATOR OPERATION:

OPEN
1-89AE BB189E
OPEN
1-89AE
1-89A OPEN & OPERATION 1-89
1-89E
1-89RE 1-89R OPEN
1-52CB
LINE SHUNT REACTOR

1-89L
UUU

BB189E 1-89AE 1-89E 1-52 CB 1-89

. 1-89LE
OPEN OPEN OPEN OPEN INTER
UUU

LOCK
CONTACTOR
LINE 1
INTERLOCKS BAY 1
BB1-89E BUS-1

1-89
1-89E

1-52CB
FOR 1-89E ISOLATOR OPERATION:

OPEN
1-89AE 1-89A

1-89A
& OPERATION1-89E
OPEN
1-89RE 1-89R 1-89
LINE SHUNT REACTOR

1-89L
UUU

1-89A 1-89 1-89E

. 1-89LE
OPEN OPEN INTER
UUU

LOCK
CONTACTOR
LINE 1
INTERLOCKS BAY 1
BB1-89E BUS-1

1-89
1-89E

1-52CB
FOR 1-89A ISOLATOR OPERATION:
OPEN
1-89AE
1-89AE

1-89A
1-89E
OPEN
& OPERATION1-89A
1-89RE 1-89R OPEN
1-52CB
LINE SHUNT REACTOR

1-89L
UUU

1-89AE 1-89E 1-52 CB 1-89A

. 1-89LE
OPEN OPEN OPEN INTER
UUU

LOCK
CONTACTOR
LINE 1
INTERLOCKS BAY 1
BB1-89E BUS-1

1-89
1-89E

1-52CB
FOR 1-89AE EARTH SWITCH OPERATION:

OPEN
1-89AE 1-89A

1-89A
& OPERATION 1-89AE
OPEN
1-89RE 1-89R 1-89
LINE SHUNT REACTOR

1-89L
UUU

1-89A 1-89 1-89AE

. 1-89LE
OPEN OPEN INTER
UUU

LOCK
CONTACTOR
LINE 1
INTERLOCKS BAY 1
BB1-89E BUS-1
FOR 1-89L ISOLATOR OPERATION:
IL

INTER LOCK FACILITY:


1-89 WHEN 1-89R CLOSES ONLY
1-89E PERMIT TO CLOSE 1-89L AND
1-89L OPENS ONLY
PERMIT TO OPEN 1-89R.

1-52CB CLOSE
1-89R
PUSH OR
DC
INTERLOCK OPEN
2-52CB
1-89AE BYPASS
OPEN & OPERATION 1-89L
PB 1-89LE
OPEN
1-89A 1-52CB
1-89RE 1-89R DC INTERLOCK
BYPASS PB
IL
LINE SHUNT REACTOR

1-89L
UUU

PUSH
1-89R 2-52 CB 1-89LE 1-52 CB 1-89L

. 1-89LE
CLOSE OPEN OPEN OPEN INTER
UUU

LOCK
CONTACTOR
LINE 1
INTERLOCKS BAY 1
BB1-89E BUS-1

1-89
1-89E

1-52CB
FOR 1-89LE EARTH SWITCH OPERATION:

OPEN
1-89AE 1-89L

1-89A
& OPERATION 1-89LE
LINE U/V RELAY OPTD
1-89RE 1-89R
LINE SHUNT REACTOR

1-89L
UUU

LINE U/V
RELAY 1-89L 1-89LE

. 1-89LE
OPTD OPEN INTER
UUU

LOCK
CONTACTOR
LINE 1
INTERLOCKS BAY 1
BB1-89E BUS-1

1-89
1-89E
FOR 1-89R ISOLATOR OPERATION:

1-52CB
OPEN
1-89RE
OPEN
2-52CB
1-89AE OPEN & OPERATION 1-89L
1-89L
OPEN
1-89A 1-52CB
1-89RE 1-89R

IL
LINE SHUNT REACTOR

1-89L
UUU

1-89RE 2-52 CB 1-89LE 1-52 CB 1-89L

. 1-89LE
OPEN OPEN OPEN OPEN INTER
UUU

LOCK
CONTACTOR
LINE 1
INTERLOCKS BAY 1
BB1-89E BUS-1

1-89
1-89E

1-52CB
FOR 1-89RE EARTH SWITCH OPERATION:

1-89AE
OPEN OPERATION
1-89R 1-89RE
1-89A
1-89RE 1-89R
LINE SHUNT REACTOR

1-89L
UUU

1-89R 1-89RE

. 1-89LE
OPEN INTER
UUU

LOCK
CONTACTOR
LINE 1
INTERLOCKS 1-52 CB BAY1
BB1-89E BUS-1
LOCAL
1-89E
1-89 CLOSE
1-89E LOCAL
& OPERATION
1-52 CB

CLOSE
1-89AE
1-52CB

1-89 AE 1-89 E 1-52 CB


1-89AE
CLOSE CLOSE INTER
1-89A
REMOTE
LOCK
1-89RE 1-89R RESET CONTACTOR
86-GA/BAY1
LINE SHUNT REACTOR

RESET
REMOTE
1-89L 86-GB/BAY1
& OPERATION
1-52 CB
UUU

RESET
96-BB/BAY1
. 1-89LE
UUU

86-GA/BAY1 86-GB/BAY1 96-BB/BAY1 1-52 CB


LINE 1
RESET RESET RESET INTER
LOCK
CONTACTOR
INTERLOCKS BAY 2

2-89A 2-89B

2-89AE 2-52CB 2-89BE

FOR 2-89A ISOLATOR OPERATION:

OPEN
2-52 CB

OPEN OPERATION
289-AE & 2-89A

OPEN
289-BE

2-52 CB 289-AE 289-BE 2-89A

OPEN OPEN OPEN INTER


LOCK
CONTACTOR
INTERLOCKS BAY 2

2-89A 2-89B

2-89AE 2-52CB 2-89BE

FOR 2-89B ISOLATOR OPERATION:

OPEN
2-52 CB

OPEN OPERATION
289-AE & 2-89B

OPEN
289-BE

2-52 CB 289-AE 289-BE 2-89B

OPEN OPEN OPEN INTER


LOCK
CONTACTOR
INTERLOCKS BAY 2

2-89A 2-89B

2-89AE 2-52CB 2-89BE

FOR 2-89AE EARTH SWITCH OPERATION:

OPEN
289-A
OPERATION
289-B
OPEN & 2-89AE

289-A 289-B 2-89AE

OPEN OPEN INTER


LOCK
CONTACTOR
INTERLOCKS BAY 2

2-89A 2-89B

2-89AE 2-52CB 2-89BE

FOR 2-89BE EARTH SWITCH OPERATION:

OPEN
289-A
OPERATION
289-B
OPEN & 2-89BE

289-A 289-B 2-89BE

OPEN OPEN INTER


LOCK
CONTACTOR
INTERLOCKS 2-52 CB BAY2
LOCAL
2-89BE
2-89A 2-89B CLOSE
LOCAL
2-89AE 2-52CB 2-89BE
& OPERATION
2-52 CB

CLOSE
2-89AE

2-89 AE 2-89 BE 2-52 CB

CLOSE CLOSE INTER

REMOTE
LOCK
RESET CONTACTOR
86-GA/BAY2

RESET
REMOTE
86-GB/BAY2
& OPERATION
2-52 CB

RESET
96-BB/BAY2
FOR HALF DIA ONLY

86-GA/BAY2 86-GB/BAY2 96-BB/BAY2 2-52 CB

RESET RESET RESET INTER


FOR HALF DIA ONLY LOCK
CONTACTOR
INTERLOCKS BAY 3
BB2-89E BUS-2

3-89
3-89E

3-52CB

FOR 3-89 ISOLATOR OPERATION:


3-89AE
OPEN
BB289E
3-89A OPEN
3-89AE
OPEN & OPERATION 3-89
3-89E
OPEN
3-52CB
3-89T

3-89TE BB289E 3-89AE 3-89E 3-52 CB 3-89

OPEN OPEN OPEN OPEN INTER


LOCK
CONTACTOR
ICT
INTERLOCKS BAY 3
BB2-89E BUS-2

3-89
3-89E

3-52CB

FOR 3-89E EARTH SWITCH OPERATION:


3-89AE
OPEN
3-89A 3-89A

& OPERATION3-89E
OPEN
3-89
3-89T

3-89TE 3-89A 3-89 3-89E

OPEN OPEN INTER


LOCK
CONTACTOR
ICT
INTERLOCKS BAY 3
BB2-89E BUS-2

3-89
3-89E

3-52CB

FOR 3-89A ISOLATOR OPERATION:


3-89AE

3-89A OPEN
3-89AE
OPEN OPERATION
3-89E
OPEN
& 3-89A
3-52CB

3-89T

3-89TE 3-89AE 3-89E 3-52 CB 3-89A

OPEN OPEN OPEN INTER


LOCK
CONTACTOR
ICT
INTERLOCKS BAY 3
BB2-89E BUS-2

3-89
3-89E

3-52CB

FOR 3-89AE EARTH SWITCH OPERATION:


3-89AE
OPEN
3-89A 3-89A

& OPERATION3-89AE
OPEN
3-89
3-89T

3-89TE 3-89A 3-89 3-89AE

OPEN OPEN INTER


LOCK
CONTACTOR
ICT
INTERLOCKS BAY 3
BB2-89E BUS-2

3-89
3-89E

3-52CB

FOR 3-89T ISOLATOR OPERATION:


3-89AE
OPEN
LV89TE2
3-89A OPEN
2-52 CB
OPEN & OPERATION 3-89T
3-89TE
OPEN
3-52CB
3-89T

3-89TE LV89TE2 2-52CB 3-89TE 3-52 CB 3-89T

OPEN OPEN OPEN OPEN INTER


LOCK
CONTACTOR
ICT
INTERLOCKS BAY 3
BB2-89E BUS-2

3-89
3-89E

3-52CB

FOR 3-89TE EARTH SWITCH OPERATION:


3-89AE
OPEN
3-89A 3-89T

& OPERATION3-89TE
OPEN
LV89T
3-89T

3-89TE 3-89T LV89T 3-89TE

OPEN OPEN INTER


LOCK
CONTACTOR
ICT
INTERLOCKS 3-52 CB BAY3
BB2-89E BUS-2
LOCAL
3-89 3-89E
CLOSE
3-89E
LOCAL
& OPERATION
3-52 CB

CLOSE
3-89AE
3-52CB

3-89 AE 3-89 E 3-52 CB


3-89AE

3-89A CLOSE CLOSE INTER

REMOTE
LOCK
RESET CONTACTOR
86-GA/BAY3

RESET
3-89T REMOTE
86-GB/BAY3
& OPERATION
3-52 CB

RESET
96-BB/BAY3
3-89TE

86-GA/BAY3 86-GB/BAY3 96-BB/BAY3 3-52 CB

ICT RESET RESET RESET INTER


LOCK
CONTACTOR
INTERLOCKS BUS EARTH SWITCH
BB189E BB289E
OPEN
OPEN 3-89/ DIA1
1-89/ DIA1
OPEN
OPEN 6-89/ DIA2
4-89/ DIA2 OPERATION

7-89/ DIA3
OPEN
&
OPERATION
BB189E
9-89/ DIA3
OPEN
& BB289E
UP TO NO OF DIAS
UP TO NO OF DIAS
OPEN
OPEN DIA N
DIA N

FOR BUS EARTH SWITCH OPERATION, ALL ISOLATORS


CONNECTED TO CONCERNED BUS ARE TO BE OPENED.
1-89/DIA1 4-89/DIA2 7-89/DIA3 DIA N BB189E

UP TO NO OF DIAS
OPEN OPEN OPEN OPEN INTER
LOCK
CONTACTOR

3-89/DIA1 6-89/DIA2 9-89/DIA3 DIA N BB289E

UP TO NO OF BAYS
OPEN OPEN OPEN OPEN INTER
LOCK
CONTACTOR
ISOLATOR S.NO
ISOLATOR EQUIPMENT-1 EQUIPMENT-2 EQUIPMENT-3 EQUIPMENT-4

INTERLOCKS OPEN/CLOSE INTERLOCKS REQUIRED FOR CONCERNED ISOLATOR / EARTH SWITCH OPEN OR CLOSE
BAY - 1
1 1 - 89 ISO BB189 E O 189 AE O 189 E O 152 CB O
2 1 – 89 E ES 189 A O 189 O -- - -- -
3 1 – 89 A ISO 189 AE O 189 E O 152 CB O -- -
4 1 – 89 AE ES 189 A O 189 O -- - -- -
5 1 – 89 L ISO 189 LE O 152 CB O 252 CB O -- -
6 1 – 89 LE ES 189 L O UV RELAY A -- - -- -
BAY - 2
NOTE: All Earth Switches in
the Bay are towards Circuit 7 2 – 89 A ISO 289 BE O 289 AE O 252 CB O -- -
Breaker side only. The Line 8 2 – 89 AE ES 289 B O 289 A O -- - -- -
and Transformer
9 2 – 89 B ISO 289 BE O 289 AE O 252 CB O -- -
Earth Switches are towards
Line & Transformer. 10 2 – 89 BE ES 289 B O 289 A O -- - -- -
O: OPEN BAY - 3
C: CLOSE 11 3 – 89 ISO BB289 E O 389 AE O 389 E O 352 CB O
A: ACTED
12 3 – 89 E ES 389 A O 389 O -- - -- -
BB189E : BUSBAR-1 EARTH SWITCH .
13 3 – 89 A ISO 389 AE O 389 E O 352 CB O -- -
BB289E : BUSBAR-2EARTH SWITCH .
UV RELAY: UNDER VOLTAGE RELAY. 14 3 – 89 AE ES 389 A O 389 O -- - -- -
15 3 – 89 T ISO LV89 E2 O 389 TE O 252 CB O 352 CB O
16 3 – 89 TE ES 389 T O LV89 T O -- - -- -
BB189E
OPEN ISOLATOR & CB INTERLOCKS OPEN
BB289E
OPEN OPEN
1-89AE
OPEN & OPERATION 1-89 1-89E
CLOSE LOCAL
CLOSE 3-89
OPERATION
& OPEN
3-89AE
1-89E
OPEN 1-89AE
CLOSE & 1-52CB OPEN
3-89E
1-52CB 3-52CB
CLOSE LOCAL
1-52CB OPEN 2-89AE CLOSE OPEN 3-52CB
OPEN 2-89BE
CLOSE & 2-52CB OPEN
1-89AE & OPERATION 1-89A 3-89A
OPERATION
& 3-89AE
OPEN CLOSE OPEN
1-89E 3-89E
LOCAL 3-89E
CLOSE

3-89AE
CLOSE & 3-52CB
OPEN OPEN
1-52CB 3-52CB
RESET OPEN
OPEN 86GR-A
1-89LE & OPERATION 1-89L RESET
REMOTE
CLOSE
OPERATION 3-89TE
OPEN 86GR-B & 1-52CB 3-89T & OPEN
2-52CB
2-52CB RESET
96BB OPEN
LV89E2
OPEN
1-89 OPERATION RESET OPEN
3-89
OPEN & 1-89E 86GR-A
REMOTE
CLOSE
3-89E
OPERATION
& OPEN
1-89A
86GR-B
RESET & 2-52CB 3-89A
OPEN
1-89 OPERATION OPEN
3-89
1-89A
OPEN & 1-89AE
86GR-A
RESET
REMOTE 3-89AE
OPERATION
& OPEN
RESET CLOSE 3-89A
1-89L
OPEN 86GR-B & OPEN
OPERATION RESET 3-52CB 3-89T
U/V RLY
ACTED & 1-89LE 96BB 3-89TE
OPERATION
& OPEN
LV89T

OPEN
2-89A
OPEN 2-89B
OPEN & OPERATION
2-89AE
OPEN
2-52CB 2-52CB
OPEN OPEN
2-89AE & OPERATION 2-89A
OPEN 2-89AE & OPERATION
2-89A 2-89B
2-89BE
OPEN
2-89B
OPEN & OPERATION
2-89BE 2-89BE
OPEN