Documente Academic
Documente Profesional
Documente Cultură
MEDICAL GASES
COMPRESSED GASES
VACUUM
NITROGEN
OXYGEN
NI
CALCULATION
GASES
GEN
OXYGEN
NITROUS OXIDE
Project No. Mechanical & Industrial Department CAIRO - EGYPT Subject Building DESIGN CALCULATION SHEET Sheet No. of Checked by
LABORATORY SYSTEMS
CLINICAL SYSTEMS
DENTAL SYSTEMS
`
CLINICAL SYSTEMS
COMPRESSED AIR SYSTEM VOLUME/OU NUMBER OF USE TLET (CFM) OUTLETS FACTOR 2 2(3bar)+1(7bar) 100 2 1/bed 100 1 1/bed 50 2 1/room 100 1/room 2 1/bed 50 2 1/bed 50 1 1/4 bassinets 20 1 3/bassinet 100 1 1/bed 10 1 1/room 10 ENTER NO. OF TOTAL OUTLETS CFM 8 16 8 16 1 0.5 0 10 18 3 6 1 10 18 0.6 6 0 0.1
LOCATION Major operating rooms Trauma rooms Plaster room Delivery rooms Endoscopy Recovery ICU rooms Nurseries Special care Nurseries Pre-OP room CT Scan
LOCATION Operating room open heart, organ transplant, etc. (2/room) Major operating room (2/room) Minor operating room Cystoscopy and special procedures (2/room) Emergencya Emergencya (Isolation) Trauma room Plaster (fracture room) Delivery room Recovery first inlet/bed Recovery second inlet/bed Recovery additional inlet/bed ICU&CCU first inlet/bed ICU&CCU second inlet/bed ICU&CCU additional inlet/bed Patient rooms surgicalb Sometimes one inlet/bed Sometimes one inlet/2 beds) b Patient rooms medical Sometimes one inlet/bed Sometimes one inlet/2 beds) Labor rooms Nurseries Special care Nurseries Endoscopy rooms
NUMBER OF USE OUTLETS FACTOR 100 100 100 40 100 100 100 100 100 100 50 10 100 50 10 50 50 1/bed 10 10 20 10 40 10
TOTAL CFM 0 0 72 0 102 36 8 0 0 6 1 1.6 3 0.5 1.6 0 0 0 0 19.8 0 0 1.3 2.2 1.6 256.6
6/room 3/room
1/bed 3/bed 2/bed 1/room 6/room 2/bed 2/bed 2/bed 2/bed 2/bed 2/bed
51 6 8
0 0
2 2 16 1 1 16
1 1 1 1 1 1
188
1 1 1
3 3 6
All outlets in the emergency department (area) should have 100% simultaneous use factor Where patient rooms are interchangeable (surgical or medical), use 50% simultaneous use factor for the first 4 rooms on the far end of the section of pipping and 20% thereafter
256.6
Go to
O2&N2O
Mechanical & Industrial Department CAIRO - EGYPT Subject CFM Estimation Building Adapazari Hospital
OXYGEN
SIMULTA NEOUS USE FACTOR 100 100 100 ENTER NO. OF ROOMS OR OUTLET S 1 1 2 1/bed 100 100 75 50 33 25 100 100 100 50 30 20 6/room 100 100 100 50 30 20 2/bed 100 60 50 45 100 100 20 20 20 20 20 20 20 20 10 10 10 10 10 1/room 100 100 75 50 33 25 100 100 75 50 33 25 100 100 75 50 33 25 100 100 75 50 33 25 100 100 75 50 33 25 100 100 75 50 33 25 20 10 10 10 10 10 1/4 bassinet 20 10 10 10 10 10 2/bassinet 20 10 10 10 10 10 1/bed 20 10 10 10 10 10 1/bed 20 10 10 10 10 10 1/bed 20 10 10 10 10 10 1/room 1 1 20 10 0 0 0 0 1 20 0 0 0 0 0 1 2 1 20 20 7.5 0 0 0 1 2 3 20 20 22.5 0 0 0 1 2 20 20 0 0 0 0 0 0 0 0 0 0 8 4 4 4 18 160 48 40 36 360 0 0 0 0 20 10 10 10 10 10 2/bed 1 1 2 50 30 40 1 2 8 8 20 17 20 20 60 40 66 42.5
***added
LOCATION Operating rooms First room (far end of a section of piping and all individual branches to rooms) Second room (on a section of piping) Each additional room (on a section of piping) b Emergency rooms First outlet 2nd&3rd 4--12 13--20 21--40 40 & up Trauma rooms First room (far end of a section of piping and all individual branches to rooms) Second room (on a section of piping) Each additional room (on a section of piping) Delivery rooms First room (far end of a section of piping and all individual branches to rooms) Second room (on a section of piping) Each additional room (on a section of piping) Recovery rooms 1--8 outlets 9--12 13--16 and up ICU rooms CCU rooms Other spaces such as Patient rooms (Medical and surgical)(beside outlets) First outlet 2nd&3rd 4--12 13--20 21--40 40 & up Labor rooms Sometimes one outlet/bed First outlet 2nd&3rd 4--12 13--20 21--40 40 & up Nurseries First outlet 2nd&3rd 4--12 13--20 21--40 40 & up Special care nurseries First outlet 2nd&3rd 4--12 13--20 21--40 40 & up Dyalisis First outlet 2nd&3rd 4--12 13--20 21--40 40 & up Anesthesia work rooms First outlet 2nd&3rd 4--12 13--20 21--40 40 & up MRI First outlet 2nd&3rd 4--12 13--20 21--40 40 & up CT-Scan
PER ROOM 50 30 20
PER OUTLET
PER BED
TOTAL 50 30 40
2/bed
First outlet 2nd&3rd 4--12 13--20 21--40 40 & up Endoscopy rooms First outlet 2nd&3rd 4--12 13--20 21--40 40 & up
20 10 10 10 10 10 20 10 10 10 10 10 1/room
20 0 0 0 0 0 40 0 0 0 0 0
Where Oxygen is used to power fluidicaly controlled anesthesia ventilators, increase LPM volume by 40% All outlets in the emergency dept. (area) should have 100% simultaneous use factors c Where Oxygen is used to power fluidically controlled ventilators, volume should be 40 LPM d Simultaneous-use factor for other spaces: the first outlet on the end section of piping 20 LPM, 100% use factor. For additional outlets on the section of piping 10 LPM with the use-factors used in the above table.
b
2450.2
LPM of Oxygen
NITROUS OXIDE
SIMULTA NEOUS USE VOLUME, LPM/ FACTOR ROOM 30 20 15 20 20 20 15 20 15
LOCATION First operating room (far end of piping and all individual branches to operating rooms Second operating room (on a section of piping) Each additional operating rom (on a section of piping) Delivery rooms Emerency rooms Trauma rooms Aneshtesia work room Plaster (fracture room) Endoscopy room
1 1 2
TOTAL 30 20 30 0 0 80 15 20 15
4 1 1 1
210
Go to
Mechanical & Industrial Department CAIRO - EGYPT Subject Medical Gases CFM estimation Building Adapazari Hosptial
PPDG
CFM COMPRESSED AIR VACUUM OXYGEN NITROUS OXIDE LPM
Mechanical & Industrial Department CAIRO - EGYPT Subject Oxygen tank capacity and reserve Building King Hussein Hospital
269
beds
Following the Practical plumbing guide for bulk systems: Allow 500 cu.ft/bed/month+reserve manifold for one day supply: # of beds*500= 134500 cu.ft/month 156.3953 cu.ft/momth Final Tank capacity
Convert to liquid status= The reserve for one day is: montn reserve/30= 4483.333 1 cylinder= 244 # of cylinders= 18.37432 so 20
Go to
Mechanical & Industrial Department CAIRO - EGYPT Subject Schedule of equipment Building Adapazari Hosptial
Medical Vacuum Unit Column NO. 1 Unit NO. System served Medical Vacuum Building Hospital Floor Basement Room Specification type Pressure (mm Hg) Capacity l/s per unit Quantity Packaged duplex 381 45 1
Medical Compressed Air Unit Column NO. 1 Unit NO. System served Medical Air Building Hospital Floor Basement Room Reciprocating packaged oilSpecification type less Quadraplex Discharge pressure Kpa 345 Capacity l/s per unit 20 Quantity 1
Pipe Sizing
Mechanical & Industrial Department CAIRO - EGYPT Subject Pressure loss/100 ft calculations Building Adapazari Hospital Oxygen Distance to the farthest outlet Taking fittings and elbows into accounts Converting to ft 697.18 ft
If 697.18 shouldn't exceed 5 PSI of total pressure drop Then the pressure drop per 100 ft will be 0.7172 .7 PSI/100ft Pressure drop = 34.85892 PSI
LPM
in 1-1/4
1-1/2
2-1/2
0.11 0.95
0.3 0.83
0.34 0.88
0.2 0.71
0.22 0.89
0.35 0.98
0.23 0.92
Vacuum Distance to the farthest outlet Taking fittings and elbows into accounts Converting to ft 697.18 ft 170 m 170 m x 1.25 = 212.5 m
If 697.18 shouldn't exceed 4 in Hg Then the pressure drop per 100 ft will be 0.5737 Pressure drop across pipe = 14.9352 PSI
1 8 15 30 50 100 175 250 450 700 1000 3/4 0.02 0.76 1 0.2 0.6 1-1/4 1-1/2 in 2 2-1/2
.6 in Hg
3 4 5 6
0.18 0.68
0.3 0.74
CFM
0.2 0.76
0.24 0.7
0.3 0.58
0.13 0.45
0.13 0.3
0.1 0.24
Medical air Distance to the farthest outlet Taking fittings and elbows into accounts Converting to ft 697.18 ft 170 m 170 m x 1.25 = 212.5 m
If 697.18 shouldn't exceed 5 in Hg Then the pressure drop per 100 ft will be 0.7172
in 1-1/4
.7 PSI/100ft
CFM
1/2 0.3
1 0.2 0.8
1-1/2
2-1/2
0.18 0.93
0.41 1
0.27 0.85
0.33 0.84
0.27 0.94
0.22 1
Nitrous Oxide
Distance to the farthest outlet Taking fittings and elbows into accounts Converting to ft 356.79 ft
87 m 87 m x 1.25 = 108.75 m
If 356.79 shouldn't exceed 5 in Hg Then the pressure drop per 100 ft will be 1.4014
in 1-1/4
1 PSI/100ft
1/2
3/4
1-1/2
2-1/2
LPM
0.04 0.99
0.11 0.45
0.11 0.95
0.3 0.83
0.34 0.88
0.2 0.71
0.22 0.89
0.35 0.98
0.23 0.92
Schedule of Equipment