Relays

Sockets
RU/RR/RH/RM/RY & Latch Relays

General-purpose electromechanical relays Relay sockets for mounting in three ways

(04/10/25)

Relay Selection Guide


Category Type General DPDT, 10A contact Miniature size

Universal Relay
RU
4PDT, 6A contact Miniature size 4PDT, 3A contact Bifurcated contact type

Power Relay
RR
SPDT, 10A contact Heavy duty power relay

Appearance

Pin Terminal Type No. Blade Terminal PC Board Terminal Contact Configuration Contact Material 20 10 Contact 8 Maximum Capacity (A) 6 4 2 DPDT Silver alloy

RU2S RU2V 4PDT

RU4S RU4V 4PDT

RU42S RU42V SPDT Silver

RR1BA-U

Gold-clad silver

Gold-clad silver-nickel

10A

10A

6A 3A

Rated Load (resistive load)

250V AC, 10A 30V DC, 10A

250V AC, 3A 30V DC, 3A

250V AC, 3A 30V DC, 3A 24, 100 (100-110), 110 (110-120), 200 (200220), 220 (220-240)V AC 6, 12, 24, 48, 100, 110V DC

110V AC, 10A 220V AC, 7.5A 30V DC, 10A

Rated Voltage

24, 100 (100-110), 110 (110-120), 200 (200-220), 220 (220-240)V AC 6, 12, 24, 48, 110V DC

6, 12, 24, 50, 100, 110, 115, 120, 200, 220, 230, 240V AC 6, 12, 24, 48, 110V DC

Coil Power Consumption (approx.) Pickup Voltage (against rated values) Dropout Voltage (against rated values) Contact Resistance Operate Time Release Time Insulation Resistance Life Mechanical Electrical Dielectric Strength Between contact and coil Between same-pole contacts 1 2 2 1.2 VA (60Hz) 1W AC: 80% max., DC: 80% max. AC: 30% min., DC: 10% min. 50 m max. 20 ms max. 20 ms max. 100 M min. (500V DC megger) AC type: 50,000,000 operations min. DC type: 100,000,000 operations min. 100,000 operations min. 2500V AC, 1 minute 1000V AC, 1 minute Simple type: 55 to +70C, Others: 55 to +60C (no freezing) 5 to 85% RH (no condensation) SU2S-11L, SM2S-05A, SM2S-05C, SM2S-05D SM2S-51 SM2S-61 35 21 27.5 35g UL, c-UL, TV, CE 8 SU4S-11L, SY4S-05A, SY4S-05C, SY4S-05D 200,000 operations min. 2.5 VA (60Hz) 1.5W AC: 80% max., DC: 80% max. AC: 30% min., DC: 15% min. 30 m max. 25 ms max. 25 ms max. 100 M min. (500V DC megger) 50,000,000 operations min. 10,000,000 operations min. 100,000 operations min. 200,000 operations min. 2000V AC, 1 minute 1000V AC, 1 minute 25 to +40C (no freezing) 5 to 85% RH (no condensation) SR3B-05

Operating Temperature Operating Humidity DIN rail mount Applicable Sockets

Panel mount PC board mount

SY4S-51 SY4S-61

SR3B-51 47.5 36 36 82g UL, CSA 15

Dimensions (H W D mm) Weight (approx.) Approvals See Page

Note: The above table shows initial values. 1: Measured using 5V DC, 1A voltage drop method 2: Mearured at the rated voltage (25C)

(04/10/25)

Relay Selection Guide


Power Relay
RR
DPDT, 3PDT; 10A contact Heavy duty power relay SPDT, DPDT, 3PDT, 4PDT; 10A contact Miniature size

Power Relay
RH

RR2P-U RR2BA-U DPDT Silver 10A 3PDT

RR3P-U RR3PA-U RR3B-U SPDT

RH1B-U RH1V2-U DPDT

RH2B-U RH2V2-U 3PDT

RH3B-U RH3V2-U 4PDT

RH4B-U RH4V2-U

Silver cadmium oxide 10A

110V AC, 10A 220V AC, 7.5A 30V DC, 10A

110V AC/ 30V DC, 10A 220V AC, 7A 6, 12, 24, 50, 100, 110, 115, 120, 200, 220, 230, 240V AC 6, 12, 24, 48, 100, 110V DC
1 VA (60Hz) 0.8W AC: 80% max., DC: 80% max. AC: 30% min., DC: 10% min. 50 m max. 20 ms max. 20 ms max.

110V AC/30V DC, 10A 220V AC, 7.5A 6, 12, 24, 50, 100-110, 110-120, 200-220, 220-240V AC 6, 12, 24, 48, 100-110V DC
1.2 VA (60Hz) 0.9W

6, 12, 24, 50, 100, 110, 115, 120, 200, 220, 230, 240V AC 6, 12, 24, 48, 110V DC

6, 12, 24, 50, 100, 110, 115, 120, 200, 220, 230, 240V AC 6, 12, 24, 48, 100, 110V DC

2.5 VA (60Hz) 1.5W AC: 80% max., DC: 80% max. AC: 30% min., DC: 15% min. 30 m max. 25 ms max. 25 ms max. 100 M min. (500V DC megger) 10,000,000 operations min. 200,000 operations min. Pin terminal: Blade terminal: 1500V AC, 1 minute 2000V AC, 1 minute

1.7 VA (60Hz) 1.5W

2 VA (60Hz) 1.5W

25 ms max. 25 ms max.

100 M min. (500V DC megger) 50,000,000 operations min. 200,000 operations min. 2000V AC, 1 minute 1000V AC, 1 minute 25 to +50C (no freezing) 25 to +40C (no freezing) 500,000 operations min. 200,000 operations min.

1000V AC, 1 minute 25 to +40C (no freezing) 5 to 85% RH (no condensation)

5 to 85% RH (no condensation) SH2B-05A SH2B-05C SH2B-05D SH2B-51 SH2B-62 35.6 21 27.5 37g SH3B-05A SH3B-05C SH3B-51 SH3B-62 35.6 31 27.5 50g SH4B-05A SH4B-05C SH4B-51 SH4B-62 35.6 41 27.5 74g

SR2P-05A, SR2P-06A, SR3P-05A, SR3P-06A, SH1B-05A SR2P-05C SR3P-05C SH1B-05C SR3B-05 SR2P-511, SR2P-70 SR3B-51 55.5 29 36 90g (pin terminal) UL, CSA, TV, CE 15 SR3P-511, SR3P-70 SR3B-51 55.5 36 36 96g (pin terminal) SH1B-51 SH1B-62 35.6 14 27.5 24g UL, CSA, TV, CE

19

(04/10/25)

Relay Selection Guide


Category Type General

Miniature Relay
RM
DPDT, 5A contact Miniature lightweight relay

Miniature Relay
RY
DPDT, 4PDT; 3A or 5A contact 1A bifurcated contact also available

Appearance

Pin Terminal Type No. Blade Terminal PC Board Terminal Contact Configuration Contact Material 20 10 Contact 8 Maximum Capacity (A) 6 4 2 Rated Load (resistive load) 110V AC, 5A 220V AC, 5A 30V DC, 5A DPDT Silver

RM2S-U RM2V-U DPDT

RY2S-U RY2V-U 4PDT

RY4S-U RY4V-U

RY22S-U RY22V-U DPDT (bifurcated) Silver palladium

Gold-clad silver

5A 3A

5A

1A 110V AC/30V DC, 3A 220V AC, 3A 240V AC, 5A 30V DC, 5A 110V AC/30V DC, 1A 220V AC, 0.8A

Rated Voltage

6, 12, 24, 50, 100-110, 200220, 220-240V AC 6, 12, 24, 48, 100-110V DC
1.2 VA (60Hz) 0.9W AC: 80% max., DC: 80% max. AC: 30% min., DC: 10% min. 1 2 2 30 m max. 20 ms min. 20 ms min. 100 M min. (500V DC megger) 50,000,000 operations min.

DPDT: 6, 12, 24, 50, 100, 110, 115, 120, 200, 220, 230, 240V AC 6, 12, 24, 48, 100, 110V DC 4PDT: 6, 12, 24, 50, 100-110, 110-120, 200-220, 220-240V AC 6, 12, 24, 48, 100-110V DC
1 VA (60Hz) 0.8W 1.2 VA (60Hz) 0.9W 1 VA (60Hz) 0.8W

Coil

Power Consumption (approx.) Pickup Voltage (against rated values) Dropout Voltage (against rated values)

AC: 80% max., DC: 80% max. AC: 30% min., DC: 10% min. 50 m max. 20 ms min. 20 ms min. 100 M min. (500V DC megger) 50,000,000 operations min. 100,000 operations min. 200,000 operations min. (220V AC, 3A) 2000V AC, 1 minute 100 m max.

Contact Resistance Operate Time Release Time Insulation Resistance Mechanical Life Electrical Dielectric Strength

500,000 operations min. 2000V AC, 1 minute 1000V AC, 1 minute 25 to +50C (no freezing) 45 to 85% RH (no condensation) SM2S-05A SM2S-05C SM2S-05D SM2S-51 SM2S-61 SM2S-62 35.6 21 27.5 35g UL, CSA, TV, CE 26

200,000 operations min. 1500V AC, 1 minute 1000V AC, 1 minute 25 to +55C (no freezing)

200,000 operations min. 1500V AC, 1 minute

Between contact and coil Between same-pole contacts

Operating Temperature Operating Humidity DIN rail mount Applicable Sockets

45 to 85% RH (no condensation) SY2S-05A SY2S-05C SY2S-51 SY2S-61 35.6 14 27.5 23g UL, CSA, TV, CE 29 SY4S-05A SY4S-05C SY4S-05D SY4S-51 SY4S-61 SY4S-62 35.6 21 27.5 34g SY2S-05A SY2S-05C SY2S-51 SY2S-61 35.6 14 27.5 23g

Panel mount PC board mount

Dimensions (H W D mm) Weight (approx.) Approvals See Page

Note: The above table shows initial values. 1: Measured using 5V DC, 1A voltage drop method 2: Mearured at the rated voltage (25C)

(04/10/25)

Relay Selection Guide


Latch Relay
RR2KP
DPDT; 10A contact Dual coil latch relay

RH2L
DPDT; 10A contact Midget power latch relay With a mechanical operation indicator DPDT; 3A contact Dual coil latch relay

RY2KS

RR2KP-U DPDT Silver DPDT Silver cadmium oxide

RH2LB-U RH2LV2-U DPDT Gold-plated silver

RY2KS-U

10A

10A

3A

110V AC/10A, 220V AC/7.5A 30V DC/10A, 100V DC/0.5A

110V AC/10A, 220V AC/7.5A 30V DC/10A

110/220V AC, 3A 30V DC, 3A 100V DC, 0.2A

6, 12, 24, 50, 100, 110, 115, 120, 200, 220, 230, 240V AC 6, 12, 24, 48, 110V DC
2.2 VA (60Hz) 1.5W Set voltage: 80% max. Reset voltage: 80% max. 30 m max. Set time: 20 ms max. Reset time: 20 ms max. 100 M min. (500V DC megger) 5,000,000 operations min.

6, 12, 24, 50, 100, 120V AC 6, 12, 24V DC


Set coil: 1.2 VA (60Hz), 2W Reset coil: 0.5 VA (60Hz), 0.9W Set voltage: 80% max. Reset voltage: 80% max. 50 m max. Set time: 30 ms max. (AC) 20 ms max. (DC)

6, 12, 24, 50, 100, 120V AC 6, 12, 24, 48, 100, 110V DC
1.5 VA (60Hz) 1.2W Set voltage: 80% max. Reset voltage: 80% max. 50 m max. Set time: 25 ms max. Reset time: 25 ms max. 100 M min. (500V DC megger) 5,000,000 operations min.

Reset time: 30 ms max. (AC) 20 ms max. (DC) 100 M min. (500V DC megger) 10,000,000 operations min.

500,000 operations min. 1500V AC, 1 minute 1000V AC, 1 minute 5 to +40C (no freezing) 45 to 85% RH (no condensation) SR3P-05A SR3P-05C SR3P-06A SR3P-511 SR3P-70 80.5 36 36 170g UL, CSA 34

200,000 operations min. 2000V AC, 1 minute 1000V AC, 1 minute 5 to +40C (no freezing) 45 to 85% RH (no condensation) SH3B-05A SH3B-05C SH3B-51 SH3B-62 35.6 31 27.5 50g UL, CSA

200,000 operations min. 1500V AC, 1 minute 700V AC, 1 minute 5 to +40C (no freezing) 45 to 85% RH (no condensation) SY4S-05A SY4S-05C SY4S-51 SY4S-61 SY4S-62 55.3 21 27.5 67g UL, CSA

36

38

(04/10/25)

Operating Instructions
Operating Instructions
Driving Circuit for Relays
1. To make sure of correct relay operation, apply the rated voltage to the relay coil. 2. Input voltage for the DC coil: A complete DC voltage is best for the coil power to make sure of stable relay operation. When using a power supply containing a ripple voltage, suppress the ripple factor within 5%. When power is supplied through a rectication circuit, the relay operating characteristics, such as pickup voltage and dropout voltage, depend on the ripple factor. Connect a smoothing capacitor for better operating characteristics as shown below.
Pulsation Smoothing capacitor

Protection for Relay Contacts


1. The contact ratings show the maximum values. Make sure that these values are not exceeded at any instant. When an inrush current ows through the load, the contact may be welded. If this is the case, connect a contact protection circuit, such as a current limiting resistor. 2. Contact protection circuit: When switching an inductive load, arcing causes carbides to form on the contacts, resulting in an increased contact resistance. In consideration of contact reliability, contact life, and noise suppression, use of a surge absorbing circuit is recommended. Then, note that the release time of the load becomes slightly longer. Check the operation using the actual load. Incorrect use of a contact protection circuit will adversely affect the switching characteristics. Four typical examples of contact protection circuits are shown in the following table:
This protection circuit can be used when the load impedance is smaller than the RC impedance in an AC load power circuit. R: Resistor of approximately the same resistance value as the load C: 0.1 to 1 F This protection circuit can be used for both AC and DC load power circuits. R: Resistor of approximately the same resistance value as the load C: 0.1 to 1 F This protection circuit can be used for DC load power circuits. Use a diode with the following ratings. Reverse withstand voltage: Power voltage of the load circuit 10 Forward current: More than the load current This protection circuit can be used for both AC and DC load power circuits. For a best result, when using on a power voltage of 24 to 48V AC/DC, connect a varistor across the load. When using on a power voltage of 100 to 240V AC/DC, connect a varistor across the contacts.

R Relay

Emin Emax Emean

DC

Ripple factor (%) =

Emax Emin 100% Emean Emax = Maximum of pulsating current Emin = Minimum of pulsating current Emean = DC mean value

Power

3. Operating the relay in synchronism with AC load: If the relay operates in synchronism with the AC power voltage of the load, the relay life may be reduced. If this is the case, select a relay in consideration of the required reliability for the load. Or, make the relay to turn on and off irrespective of the AC power phase or near the point where the AC phase crosses zero voltage.
TE R
Load

C R

Ind. Load

RC

C Power R Ind. Load

EAC

Vin

EAC

Vin

Diode

+ Power D Ind. Load

4. Leakage current while relay is off: When driving an element at the same time as the relay operation, a special consideration is needed for the circuit design. As shown in the incorrect circuit below, a leakage current (Io) ows through the relay coil while the relay is off. The leakage current causes the coil release failure or adversely affects the vibration resistance and shock resistance. Design the circuit as shown in the correct example.
Incorrect
R Io TE

Varistor

Power

Varistor

Ind. Load

3. Do not use a contact protection circuit as shown below:


This protection circuit is very effective in arc suppression when opening the contacts. But, the capacitor is charged while the contacts are opened. When the contacts are closed, the capacitor is discharged through the contacts, increasing the possibility of contact welding. This protection circuit is very effective in arc suppression when opening the contacts. But, when the contacts are closed, a current ows to charge the capacitor, causing contact welding.

Correct
R C Power Load

5. Surge suppression for transistor driving circuits: When the relay coil is turned off, a high-voltage pulse is generated, causing the transistor to deteriorate and sometimes to break. Be sure to connect a diode to suppress the counter electromotive force. Then, the coil release time becomes slightly longer. To shorten the coil release time, connect a Zener diode between the collector and emitter of the transistor. Select a Zener diode with a Zener voltage slightly higher than the power voltage.
Counter emf suppressing diode + R Relay

Load

Power

Generally, switching a DC inductive load is more difcult than switching a DC resistive load. Using an appropriate arc suppressor, however, will improve the switching characteristics of a DC inductive load.

Soldering
1. When soldering the relay terminals, use a soldering iron of 30 to 60W, and quickly complete soldering within approximately 3 seconds. 2. Use a non-corrosive rosin ux.

(04/10/25)

Operating Instructions
Other Precautions
1. General notice: To maintain the initial characteristics, do not drop the relay or apply shocks to the relay. The relay housing cannot be removed from the base during normal operation. To maintain the initial characteristics, do not remove the relay housing. Use the relay in environments free from condensation of dust, sulfur dioxide (SO2), and hydrogen sulde (H2S). Make sure that the coil voltage does not exceed the applicable coil voltage range. 2. When connecting outputs to electronic circuits: When the output is connected to a load which responds very quickly, such as an electronic circuit, contact bouncing causes incorrect operation of the load. Take the following measures into consideration. Connect an integral circuit. Suppress the pulse voltage due to bouncing within the noise margin of the load. 3. UL- and CSA-approved ratings may differ from the product rated values determined by IDEC depending on approval agents and local situations. 4. Do not use the relays in the vicinity of strong magnetic eld sources, which may affect relay operation.

Safety Precautions
Turn off the power to the relay before starting installation, removal, wiring, maintenance, and inspection of the relays. Failure to turn power off may cause electrical shock or re hazard. Observe the specifications and rated values, otherwise electrical shock or re hazard may be caused. Use wires of the proper size to meet the voltage and current requirements. Tighten the terminal screws on the relay socket to a proper tightening torque. The surge absorbing element on AC relays with RC or DC relays with diode is provided to absorb the counter electromotive force generated by the coil. When the relay is subject to an excessive external surge voltage, the surge absorbing element may be damaged. Add another surge absorbing provision to the relay to prevent damage.

Precautions for the RU Relays


Before operating the latching lever of the RU relay, turn off the power to the RU relay. After checking the circuit, return the latching lever to the original position. Do not use the latching lever as a switch. The durability of the latching lever is a minimum of 100 operations. When using DC loads on 4PDT relays, apply a positive voltage to terminals of neighboring poles and a negative voltage to the other terminals of neighboring poles to prevent the possibility of short circuits. DC type relays with a diode have a polarity in the coil terminals. Apply the DC voltage to the correct terminals.

(04/10/25)

RU Series Universal Relays


Full featured universal miniature relays Designed with environment taken into consideration
Two terminal styles: plug-in and PCB mount Non-polarized LED indicator available on plug-in relays No internal wires, lead-free construction Cadmium-free contacts Mechanical flag indicator available on plug-in relays Manual latching lever with color coding for AC or DC coil Snap-on yellow marking plate; optional marking plates are available in four other colors Maximum contact ratings: 10A (RU2), 6A (RU4), 3A (RU42) UL, CSA, c-UL, EN compliant
Standard UL508 CSA C22.2 No. 14 CSA C22.2 No. 14 Mark Approval Organization / File No. UL/c-UL File No. E66043 CSA File No. LR35144 (CSA mark is printed on bifurcated contact types only) TV Product Service EN61810-1 Self declaration (EC Low Voltage Directive)

With Latching Lever


Mechanical Indicator The contact position can be conrmed through the le small windows. Latching Lever Using the latching lever, operation can be checked without energizing the coil. The latching lever is color coded for AC and DC coils. AC coil: Orange DC coil: Green

Lever in the Latched Position

Marking Plate Standard yellow marking plate is easily replaced with optional marking plates in four colors for easy identication of relays.

In Normal Operation

LED Indicator Non-polarized green LED indicator is standard provision for plug-in terminal, latching lever types

Note: Turn off the power to the relay coil when using the latching lever. After checking the operation, return the latching lever in the normal position.

Without Latching Lever


AC/DC Color Marking For identication of AC or DC coils. AC coil: Yellow DC coil: Blue

Mechanical Indicator

Marking Plate

LED Indicator Non-polarized green LED indicator is standard provision for plug-in terminal types, except for simple types.

AC Coil

DC Coil

(04/10/25)

RU Series Universal Relays


Types
Single Contact Type
Termination Latching Lever Standard With Latching Lever With RC (AC coil only) With diode (DC coil only) With diode (DC coil only) Reverse polarity coil Standard With RC (AC coil only) With diode (DC coil only) With diode (DC coil only) Reverse polarity coil Simple (Note 2) Simple (Note 2) Type Type No. DPDT RU2S- RU2S-R- RU2S-D- RU2S-D1- RU2S-C- RU2S-CR- RU2S-CD- RU2S-CD1- RU2S-NF- RU2V-NF- 4PDT RU4S- RU4S-R- RU4S-D- RU4S-D1- RU4S-C- RU4S-CR- RU4S-CD- RU4S-CD1- RU4S-NF- RU4V-NF- Coil Voltage Code A24, A100, A110, A200, A220 D6, D12, D24, D48, D110 A100, A110, A200, A220 D6, D12, D24, D48, D110 D24 A24, A100, A110, A200, A220 D6, D12, D24, D48, D110 A100, A110, A200, A220 D6, D12, D24, D48, D110 D24 A24, A100, A110, A200, A220 D6, D12, D24, D48, D110

Plug-in Terminal (Note 1)

Without Latching Lever

PCB Terminal

Without Latching Lever

Bifurcated Contact Type


Termination Latching Lever Standard With Latching Lever With RC (AC coil only) With diode (DC coil only) With diode (DC coil only) Reverse polarity coil Standard With RC (AC coil only) With diode (DC coil only) With diode (DC coil only) Reverse polarity coil Simple (Note 2) Simple (Note 2) Type Type No. 4PDT RU42S- RU42S-R- RU42S-D- RU42S-D1- RU42S-C- RU42S-CR- RU42S-CD- RU42S-CD1- RU42S-NF- RU42V-NF- Coil Voltage Code A24, A100, A110, A200, A220 D6, D12, D24, D48, D100, D110 A100, A110, A200, A220 D6, D12, D24, D48, D100, D110 D24 A24, A100, A110, A200, A220 D6, D12, D24, D48, D100, D110 A100, A110, A200, A220 D6, D12, D24, D48, D100, D110 D24 A24, A100, A110, A200, A220 D6, D12, D24, D48, D100, D110

Plug-in Terminal (Note 1)

Without Latching Lever

PCB Terminal

Without Latching Lever

Note 1: Plug-in terminal types, except for simple types, have an LED indicator and a mechanical indicator as standard. Note 2: Simple types do not have an LED indicator, a mechanical indicator, and a latching lever.

Ordering Information
Specify a coil voltage code in place of in the Type No. Coil Voltage Code A24 A100 A110 A200 A220 D6 D12 D24 D48 D100 D110 Coil Rating 24V AC 100-110V AC 110-120V AC 200-220V AC 220-240V AC 6V DC 12V DC 24V DC 48V DC 100V DC 110V DC

Accessory
Name Marking Plate Type No. RU9Z-P Ordering Type No. RU9Z-PPN10 Color Code A (orange), G (green), S (blue), W (white), Y (yellow) Package Quantity 10

Note: Specify a color code in place of the Type No. When ordering, specify the Ordering Type No. The marking plate can be removed from the relay by inserting a at screwdriver under the marking plate.

(04/10/25)

RU Series Universal Relays


Coil Ratings
Rated Voltage (V) 24 100-110 AC (50/60 Hz) 110-120 200-220 220-240 6 12 DC 24 48 100 110 Coil Voltage Code A24 A100 A110 A200 A220 D6 D12 D24 D48 D100 D110 Rated Current (mA) 15% (at 20C) 50 Hz 49.3 9.2-11.0 8.4-10.0 4.6-5.5 4.2-5.0 155 80 44.7 18 9.7 8.9 60 Hz 42.5 7.8-9.0 7.1-8.2 4.0-4.6 3.6-4.2 Coil Resistance () 10% (at 20C) 164 3,460 4,550 14,080 18,230 40 160 605 2,560 10,000 12,100 110% 80% maximum 10% maximum 110% 80% maximum 30% minimum Operating Characteristics (against rated values at 20C) Maximum Continuous Applied Voltage Minimum Pickup Voltage Dropout Voltage

Note 1: The rated current includes the current draw by the LED indicator. Note 2: Rated voltage 100V DC is available for the bifurcated contact type only.

Contact Ratings
Contact Continu- Allowable Contact Power ous Resistive Inductive Current Load Load 10A 6A 3A 2500VA AC 1250VA AC 300W DC 150W DC 1500VA AC 180W DC 750VA AC 90W DC 600VA AC 90W DC 200VA AC 45W DC Voltage (V) 250 AC 30 DC 250 AC 30 DC 250 AC 30 DC Rated Load Res. Load 10A 10A 3A 3A 3A 3A Ind. Load 5A 5A 0.8A 1.5A 0.8A 1.5A

Specications
Type (Contact) Contact Material Contact Resistance Minimum Applicable Load Operate Time Release Time Power Consumption Insulation Resistance 1 RU2 (DPDT) Silver alloy 50 m maximum RU4 (4PDT) Silver (gold clad) RU42 (4PDT) Silver-nickel (gold clad)

DPDT 4PDT 4PDT bifurcated

24V DC, 5 mA 1V DC, 1 mA 1V DC, 0.1 mA 2 (reference value) 3 20 ms maximum 3 20 ms maximum AC: 1.1 to 1.4VA (50 Hz), 0.9 to 1.2VA (60 Hz) DC: 0.9 to 1.0W 100 M minimum (500V DC megger)

Note 1: On 4PDT relays, the maximum allowable total current of neighboring two poles is 6A. At the rated load, make sure that the total current of neighboring two poles does not exceed 6A (3A + 3A = 6A). Note 2: Inductive load for the rated load cos = 0.3, L/R = 7 ms

UL and c-UL Ratings


Voltage 250V AC 30V DC Resistive 10A 10A 6A 3A 3A General Use 6A Horse Power Rating RU4 1/10HP RU42 RU2 RU4 RU42 RU2 RU4 RU42 RU2

CSA Ratings
Voltage 250V AC 30V DC Resistive RU42 3A 3A

TV Ratings
Voltage Resistive 6A 6A 3A 3A 5A 5A Inductive 0.8A 1.5A 0.8A 1.5A RU2 RU4 RU42 RU2 RU4 RU42 10A

Between contact and coil: 2500V AC, 1 minute Between contacts of different poles: 2500V AC, 2000V AC, 1 minute Dielectric Strength 1 minute Between contacts of the same pole: 1000V AC, 1 minute Operating Electrical: 1800 operations/h maximum Frequency Mechanical: 18,000 operations/h maximum Vibration Damage limits: 10 to 55 Hz, amplitude 0.5 mm Resistance Operating extremes: 10 to 55 Hz, amplitude 0.5 mm Damage limits: 1000 m/s2 Shock Resistance Operating extremes: 150 m/s2 AC: 50,000,000 operations 50,000,000 Mechanical Life DC: 100,000,000 operations operations Electrical Life 4 See table below Operating Simple types: 55 to +70C (no freezing) Temperature 5 Others: 55 to +60C (no freezing) Operating Humidity 5 to 85% RH (no condensation) Weight Approx. 35g Note: Above values are initial values. 1: Measured using 5V DC, 1A voltage drop method 2: Measured at operating frequency of 120 operations/min (failure rate level P, reference value) 3: Measured at the rated voltage (at 20C), excluding contact bouncing; Release time of AC relays with RC: 25 ms maximum Release time of DC relays with diode: 40 ms maximum 4: Contact Load and Electrical Life (at ambient temperature 20C)
Type Voltage 250V AC RU2 30V DC 110V DC 250V AC RU4 30V DC 110V DC RU42 250V AC 30V DC 110V DC Resistive Load 10A 5A 10A 5A 0.6A 6 3A 6A 3A 0.65A 0.33A 3A 3A 0.44A Inductive Load (cos = 0.3, L/R = 7 ms) 5A 2.5A 5A 2.5A 0.4A 2.6A 0.8A 2.7A 1.5A 0.33A 0.18A 0.8A 1.5A 0.22A Electrical Life (operations minimum) 100,000 500,000 100,000 500,000 100,000 50,000 200,000 50,000 200,000 50,000 200,000 100,000 100,000 100,000

250V AC 10A 30V DC

Surge Suppressor Ratings


Type AC Coil DC Coil With RC With Diode Ratings RC series circuit R: 20 k, C: 0.033 F Diode reverse voltage: 1000V Diode forward current: 1A

5: Measured at the rated voltage. Simple types include plug-in terminal simple types and all PCB terminal types.

10

(04/10/25)

RU Series Universal Relays


RU2 (DPDT Contact)
Plug-in Terminal Type
LED indicator, mechanical flag indicator, and marking plate are standard provisions, except on simple types. Available with or without a manual latching lever Simple types have a marking plate.

PCB Terminal Type


Marking plate is a standard provision. Not provided with an LED indicator, mechanical ag indicator, and manual latching lever.

Photo: RU2S-A100

Photo: RU2V-NF-A100

Dimensions
RU2S
Mechanical Indicator Window Marking Plate (yellow)

RU2S-C/RU2S-NF
Mechanical Indicator Window (RU2S-C only) Marking Plate (yellow) Color Marking AC: Yellow DC: Blue

RU2V
Marking Plate (yellow) Color Marking AC: Yellow DC: Blue

Latching Lever AC: Orange DC: Green

LED Indicator (green)

LED Indicator (green) (RU2S-C only)

35.0

35.0

Marking Plate Removal Slot

Marking Plate Removal Slot

35.0

Marking Plate Removal Slot

13.2
0.5

21.0

21.0

13

13

21.0

1.2 2.2 Hole

6.4

12

12

14

14

6.4

0.5

2.6

2.6

1.2 2.2 Hole

27.5
27.5 27.5

Mounting Hole Layout


7.0
1 8-

4.0

0.5

0.8 2.6

Ho

les

Marking plate removal slot is provided only on one side. Insert a at screwdriver into the slot to remove the marking plate.

4.1

6.4 12.7

All dimensions in mm.

Internal Connection (Bottom View)


RU2S- Standard
(1)12 (4)42 (5)14 (9)11 (8)44 (12)41

RU2S-R With RC
(1)12 (4)42 (5)14 (9)11 (8)44 (12)41

RU2S-D With Diode


(1)12 (4)42 (5)14 (9)11 (8)44 (12)41

RU2S-D1 With Diode Reverse Polarity Coil


(1)12 (4)42 (5)14 (9)11 (8)44 (12)41

(13)A1

(14)A2

(13)A1

(14)A2

(13)A1

(14)A2 (13)A1 (14)A2

24V AC/DC or less


(1)12 (4)42

24V DC or less 24V DC


(1)12 (4)42

(5)14 (9)11

(8)44 (12)41

(5)14 (9)11

(8)44 (12)41

RU2S-NF-/RU2V-NF-
(1)12 (4)42 (5)14 (9)11 (8)44 (12)41

(13)A1

(14)A2

(13)A1

(14)A2

Over 24V AC/DC


Blank or C comes in place of to represent types with or without a latching lever.

Over 24V DC
(13)A1 (14)A2

13.2

(04/10/25)

11

0.5

RU Series Universal Relays


Electrical Life Curves
RU2 (Resistive Load)
250V AC 30V DC 110V DC 1000 1000

RU2 (Inductive Load)


250V AC/30V DC 110V DC

( 10,000 operations)

100

10

( 10,000 operations)

100

10 AC: cos = 0.3 DC: L/R = 7 ms

1 0.1 0.5 1 5 10

1 0.1 0.5 1 5 10

Load Current (A)

Load Current (A)

Maximum Switching Current


RU2
10 5

AC resistive AC inductive (cos = 0.3)

Load Current (A)

DC resistive
1

0.1

DC inductive L/R = 7 ms

10

30

100 250 500

Load Voltage (V)

Ambient Temperature vs. Temperature Rise Curves


RU2 (AC Coil, 50 Hz)
120 110 100

RU2 (AC Coil, 60 Hz)


120 110 100

RU2 (DC Coil)


120 110 100

Temperature Rise (C)

Temperature Rise (C)

90 80 70 60 50 40 30 20 10 0 10 20 30 40 50 60 70 Load current 5A 2 poles No load current Load current 10A 2 poles

90 80 70 60 50 40 30 20 10 0 10 20 30 40 50 60 70 Load current 5A 2 poles No load current Load current 10A 2 poles

Temperature Rise (C)

90 80 70 60 50 40 30 20 10 0 10 20 30 40 50 60 70 Load current 5A 2 poles No load current Load current 10A 2 poles

Ambient Temperature (C)

Ambient Temperature (C)

Ambient Temperature (C)

The above temperature rise curves show the characteristics when 100% the rated coil voltage is applied. The heat resistance of the coil is 120C. The slant dashed line indicates the allowable temperature rise for the coil at different ambient temperatures.

12

(04/10/25)

RU Series Universal Relays


RU4 (4PDT Contact)
Plug-in Terminal Type
LED indicator, mechanical flag indicator, and marking plate are standard provisions, except on simple types. Available with or without a manual latching lever Simple types have a marking plate. (RU4) (RU42) Photo: RU42S-A100 Photo: RU4V-NF-D24

PCB Terminal Type


Marking plate is a standard provision. Not provided with an LED indicator, mechanical ag indicator, and manual latching lever.

Dimensions
RU4S/RU42S
Mechanical Indicator Window Marking Plate (yellow)

RU4S-C/RU4S-NF RU42S-C/RU42S-NF
Mechanical Indicator Window (RU4S-C/RU42S-C only) Marking Plate (yellow) Color Marking AC: Yellow DC: Blue

RU4V/RU42V
Marking Plate (yellow) Color Marking AC: Yellow DC: Blue

Latching Lever AC: Orange DC: Green

LED Indicator (green)

LED Indicator (green) (RU4S-C/ RU42S-C only) 35.0 Marking Plate Removal Slot
35.0

35.0

Marking Plate Removal Slot

4.0

0.5
6.4 0.5
12 14 4 8

3-4.4 0.8 2.6

2.6 6.4 0.5


12 14

1.2 2.2 Hole


4

2.6

21.0

10

1.2 2.2 Hole

21.0

13

10

11

13

21.0

11

27.5 27.5

27.5

Mounting Hole Layout


7.0
141

Ho

les

Marking plate removal slot is provided only on one side. Insert a at screwdriver into the slot to remove the marking plate.

4.1

6.4 12.7

All dimensions in mm.

Internal Connection (Bottom View)


RU4S-/RU42S- Standard
(1)12 (2)22 (3)32 (4)42 (5)14 (6)24 (7)34 (8)44

RU4S-R/RU42S-R With RC
(1)12 (2)22 (3)32 (4)42 (5)14 (6)24 (7)34 (8)44

RU4S-D/RU42S-D With Diode


(1)12 (2)22 (3)32 (4)42 (5)14 (6)24 (7)34 (8)44

RU4S-D1/RU42S-D1 With Diode Reverse Polarity Coil


(1)12 (2)22 (3)32 (4)42 (5)14 (6)24 (7)34 (8)44

(9)11 (10)21 (11)31 (12)41

(9)11 (10)21 (11)31 (12)41

(9)11 (10)21 (11)31 (12)41

(9)11 (10)21 (11)31 (12)41

(13)A1

(14)A2

(13)A1

(14)A2

(13)A1

(14)A2
(13)A1 (14)A2

24V AC/DC or less


(1)12 (2)22 (3)32 (4)42

24V DC or less
24V DC
(1)12 (2)22 (3)32 (4)42

(5)14 (6)24

(7)34 (8)44

(5)14 (6)24

(7)34 (8)44

RU4S-NF-/RU4V-NF- RU42S-NF-/RU42V-NF-
(1)12 (2)22 (3)32 (4)42 (5)14 (6)24 (7)34 (8)44

(9)11 (10)21 (11)31 (12)41

(9)11 (10)21 (11)31 (12)41

(13)A1

(14)A2

(13)A1

(14)A2

(9)11 (10)21 (11)31 (12)41

Over 24V AC/DC


Blank or C comes in place of to represent types with or without a latching lever.

Over 24V DC
(13)A1 (14)A2

4.4

13.2

(04/10/25)

0.5

Marking Plate Removal Slot

13

RU Series Universal Relays


Electrical Life Curves
RU4 (Resistive Load)
1000
250V AC 30V DC 110V DC
1000

RU4 (Inductive Load)


250V AC 30V DC 110V DC

( 10,000 operations)

100

( 10,000 operations)

100

10

10
AC: cos = 0.3 DC: L/R = 7 ms

1 0.1 0.5 1 3 6

1 0.1 0.5 1 3 6

Load Current (A)

Load Current (A)

RU42 (Resistive Load)


250V AC 30V DC 110V DC

RU42 (Inductive Load)


250V AC 30V DC 110V DC

( 10,000 operations)

( 10,000 operations)

100

100

10

10
AC: cos = 0.3 DC: L/R = 7 ms

1 0.02 0.1 0.5 1 3 6

1 0.02 0.1 0.5

Load Current (A)

Load Current (A)

Maximum Switching Current


RU4 (Rated Load)
AC resistive AC inductive (cos = 0.3)

RU4 (Maximum Load)

AC resistive AC inductive (cos = 0.3)

RU42
6 3

AC resistive AC inductive (cos = 0.3)

6 3

6 3

Load Current (A)

Load Current (A)

Load Current (A)

DC resistive DC inductive L/R = 7 ms

DC resistive DC inductive L/R = 7 ms

DC resistive DC inductive L/R = 7 ms

0.1

0.1

0.1

10

30

100

250 500

10

30

100 250 500

10

30

100

250 500

Load Voltage (V)

Load Voltage (V)

Load Voltage (V)

Ambient Temperature vs. Temperature Rise Curves


RU4/RU42 (AC Coil, 50 Hz)
120 110 100

RU4/RU42 (AC Coil, 60 Hz)


120 110 100

RU4/RU42 (DC Coil)


120 110 100

Temperature Rise (C)

Temperature Rise (C)

Temperature Rise (C)

90 80 70 60 50 40 30 20 10 0 10 20 30 40 50 60 70 Load current 3A 4 poles No load current Load current 6A 2 poles

90 80 70 60 50 40 30 20 10 0 10 20 30 40 50 60 70 Load current 3A 4 poles No load current Load current 6A 2 poles

90 80 70 60 50 40 30 20 10 0 10 20 30 40 50 60 70 Load current 3A 4 poles No load current Load current 6A 2 poles

Ambient Temperature (C)

Ambient Temperature (C)

Ambient Temperature (C)

The above temperature rise curves show the characteristics when 100% the rated coil voltage is applied. Load current 6A 2 poles is for the RU4 types only. The heat resistance of the coil is 120C. The slant dashed line indicates the allowable temperature rise for the coil at different ambient temperatures.

14

(04/10/25)

RR Series Power Relays


Heavy-duty power type relays Large capacity 10A 1, 2, and 3 poles
Available in pin and blade terminal styles. Options include an indicator, check button for test operation, and side ange. DIN rail, surface, and panel mount sockets are available for a wide variety of mounting applications.

Types
Termination Basic With Indicator Pin Terminal With Check Button With Indicator and Check Button Basic With Indicator Blade Terminal With Check Button With Indicator and Check Button Side Flange Type Type Type No. SPDT RR1BA-U RR1BA-UL RR1BA-UC RR1BA-ULC RR1BA-US DPDT RR2P-U RR2P-UL RR2P-UC RR3P-U RR3P-UL RR3P-UC 3PDT (Note) RR3PA-U RR3PA-UL AC6, AC12, AC24, AC50, AC100, AC110, AC115, AC120, AC200, AC220, AC230, AC240, DC6, DC12, DC24, DC48, DC110 Coil Voltage Code

RR3PA-UC RR3PA-ULC

RR2P-ULC RR2BA-U RR2BA-UL RR2BA-UC RR2BA-ULC RR2BA-US

RR3P-ULC RR3B-U RR3B-UL RR3B-UC RR3B-ULC RR3B-US

Note: Both RR3P and RR3PA are 3PDT relays and have different terminal arrangements. See Internal Connection on page 17. Type numbers marked with in the table above are UL-recognized, CSA-certied, and TV-approved. Others are UL-recognized and CSA-certied.

Ordering Information
When ordering, specify the Type No. and coil voltage code.
(Example) RR3P-U
Type No.

AC110
Coil Voltage Code

Coil Ratings
Rated Current (mA) 15% at 20C Rated Voltage (V) 50Hz 6 12 24 50 AC (50/60Hz) 100 110 115 120 200 220 230 240 6 12 DC 24 48 110 490 245 121 58 29 27 25 24 14.5 13.3 12.7 12.1 240 120 60 30 13 60Hz 420 210 105 50 25 23 21.5 20.5 12.5 11.5 11 10.5 Coil Resistance () 10% at 20C 4.9 18 79 350 1,370 1,680 1,800 2,100 5,740 7,360 7,830 8,330 25 100 400 1,600 8,460 110% 80% maximum 15% minimum 110% 80% maximum 30% minimum Operation Characteristics (against rated values at 20C) Max. Continuous Applied Voltage Minimum Pickup Voltage Dropout Voltage

(04/10/25)

15

RR Series Power Relays


Contact Ratings
Continuous Current Maximum Contact Capacity Allowable Contact Power Rated Load Resistive Load Inductive Load Voltage 110V AC 10A 1650VA AC 1100VA AC 300W DC 150W DC 220V AC 30V DC Resistive Load 10A 7.5A 10A Inductive Load 7.5A 5A 5A

CSA Ratings
Voltage 240V AC 120V AC 100V DC 30V DC Resistive 10A 10A 10A General use 7A 7.5A 0.5A 7.5A

TV Ratings
240V AC 30V DC AC: cos = 1.0, DC: L/R = 0 ms 10A 10A

Note: Inductive load for the rated load cos = 0.3, L/R = 7 ms

UL Ratings
Voltage 240V AC 120V AC 30V DC Resistive 10A 10A 10A General use 7A 7.5A 7A Horse Power Raging 1/3 HP 1/4 HP

Specications
Contact Material Contact Resistance Minimum Applicable Load Operate Time Release Time Power Consumption (approx.) Insulation Resistance 2 2 1 Silver 30 m maximum 24V DC, 10 mA; 5V DC, 20 mA (reference value) 25 ms maximum 25 ms maximum AC: 3 VA (50 Hz), 2.5 VA (60 Hz) DC: 1.5W 100 M minimum (500V DC megger) Pin Terminal Dielectric Strength Blade Terminal Between live and dead parts: Between contact and coil: Between contacts of different poles: Between contacts of the same pole: Between live and dead parts: Between contact and coil: Between contacts of different poles: Between contacts of the same pole: Electrical: Mechanical: Damage limits: Operating extremes: Damage limits: Operating extremes: 1500V AC, 1 minute 1500V AC, 1 minute 1500V AC, 1 minute 1000V AC, 1 minute 2000V AC, 1 minute 2000V AC, 1 minute 2000V AC, 1 minute 1000V AC, 1 minute

Operating Frequency Vibration Resistance Shock Resistance Electrical Life Mechanical Life Operating Temperature Operating Humidity Weight (approx.) (Basic type) 3

1800 operations/h maximum 18,000 operations/h maximum 10 to 55 Hz, amplitude 0.5 mm 10 to 55 Hz, amplitude 0.5 mm 1000 m/s2 100 m/s2

200,000 operations (220V AC, 5A) 10,000,000 operations 25 to +40C (no freezing) 5 to 85% RH (no condensation) RR2P: 90g, RR3P/RR3PA: 96g, RR1BA/RR2BA/RR3B: 82g

Note: Above values are initial values. 1: Measured using 5V DC, 1A voltage drop method 2: Measured at the rated voltage (at 20C), excluding contact bouncing 3: For use under different temperature conditions, refer to Continuous Load Current vs. Operating Temperature Curve.

16

(04/10/25)

RR Series Power Relays


Internal Connection (Bottom View)
Basic Type
RR2P-U
4 5

RR3P-U
5 6 7 (+) 4 3 2 () 1 11 6 7 8 9 10 (+) 4 3 2 ()

RR3PA-U
5 6 7 8 9 10 (+) 1 11 7

RR1BA-U
2 5 1 4 7 B (+)

RR2BA-U
3 6 9 B (+) 1 4 7 A ()

RR3B-U
2 5 8 3 6 9 B (+)

With Check Button


Front Pushbutton

3 2 () 1 8

A ()

A ()

Contacts can be operated by pressing the check button. Press the button quickly to prevent arcing.

With Indicator (-UL type)


Voltage
4

RR2P
5
5

RR3P
6 7 8 9 10 (+) 1 11

RR3PA
5 4 3 2 () 1 11 6 7 8 9 10 (+)

RR1BA
2 5 1 4 7 B (+) A ()

RR2BA
3 6 9 B (+) 1 4 7 A ()

RR3B
2 5 8 3 6 9 B (+)

6 7 (+) 1 8

4 3 2 ()

7 A ()

Below 100V AC/DC

2 ()

4 5 4 3 2 () 1 8 7 (+) 2 () 1 5 6

6 7 8 9 10 (+) 11

5 4 3 2 () 1 11 6 7 8 9 10 (+)
7 A ()

2 5 1 4 7 B (+) A () 3 6 9 B (+) 1 4 7 A ()

2 5 8 3 6 9 B (+)

100V AC/DC and above

When the relay is energized, the indicator goes on.

The LED protection diode is not contained in relays for below 100V DC.

Characteristics (Reference Data)


Maximum Switching Capacity
10.0 AC resistive 5.0 AC inductive

Electrical Life Curve


AC Load
1000 500

Load Current (A)

DC resistive
1.0

Life ( 10,000 operations)

DC inductive
0.5

100 110V AC resistive 50 220V AC resistive 110V AC inductive 20 220V AC inductive 10 0.1

1 5

10

30

50

100

200 300

Load Voltage (V)

0.5 1 Load Current (A)

10

Continuous Load Current vs. Operating Temperature Curve (Basic Type, With Check Button, and Side Flange Type)
100 90

DC Load
1000 500

Life ( 10,000 operations)

30V DC resistive

Operating Temperature (C)

80 70 60 50 40 30 20 10 0 1 2 3 4 5 6 7 8 9 10 Load Current (A)


AC Coil DC Coil

100 50 100V DC resistive 100V DC inductive 30V DC inductive 10 0.01 0.05 0.1 0.5 Load Current (A) 1 5 10

20

(04/10/25)

17

RR Series Power Relays


Dimensions
RR2P-U/RR2P-UL
Total length from panel surface including relay socket SR2P-05A: 84.5 (87.5) max., SR2P-511: 63 (68) max.

Applicable Socket and Hold-down Spring


Socket Mounting Style
3 2 1 8 6 7

35.6

4 5

DIN Rail Mount Socket w/Solder Terminals w/Wire Wrap Terminals

Type No. SR2P-05A SR2P-05C SR2P-06A SR2P-511

Hold-down Spring SR2B-02F1 SFA-202

9.9 55.5 max. 13

28.6
Dimensions in the ( ) include a hold-down spring.

Panel Mount Socket

SR3P-01F1 SR2P-70

(Photo: RR2P-U)

RR3P-U/RR3P-UL/ RR3PA-U/RR3PA-UL

Total length from panel surface including relay socket SR3P-05A: 84.5 (87.5) max., SR3P-511: 63 (68) max.

Applicable Socket and Hold-down Spring


Socket Mounting Style
6 5 7 8 9 2 1 11 10

4 3

DIN Rail Mount Socket


35.6

Type No. SR3P-05A SR3P-05C SR3P-06A SR3P-511

Hold-down Spring SR3B-02F1 SFA-202

9.9 55.5 max. 13

35.6
Dimensions in the ( ) include a hold-down spring.

Panel Mount Socket

w/Solder Terminals w/Wire Wrap Terminals

SR3P-01F1 SR3P-70

(Photo: RR3P-U)

RR1BA-U/RR1BA-UL/ RR2BA-U/RR2BA-UL/ RR3B-U/RR3B-UL

4.7

Applicable Socket and Hold-down Spring


3.0 2.0 oblong hole Total length from panel surface including relay socket SR3B-05: 73 (76) max., SR3B-51: 56 (60) max. 0.5

Socket Mounting Style DIN Rail Mount Socket Panel Mount Socket
2 5 8 3 6 9

Type No. SR3B-05 SR3B-51

Hold-down Spring SR3B-02F1 SFA-202 SR3B-02F1

1 4 7

(Photo: RR3B-U)
A B

36 47.5 max. 7.3


Dimensions in the ( ) include a hold-down spring.

RR1BA-US RR2BA-US RR3B-US

63.5 7.3

3.0 2.0 oblong hole

36

2-4.5 Mounting Holes


16.0 4.2 11.1 11.1

63.5

47.5 max. 73.5

16.1

0.5

(Photo: RR3B-US)

4.7

1 4 7

2 5 8

3 6 9

36

36

All dimensions in mm.

18

(04/10/25)

RH Series Power Relays


SPDT through 4PDT, 10A contacts Midget power type relays
The RH series are miniature power relays with a large capacity. The RH relays feature 10A contact capacity as large as the RR series and the same size as IDECs miniature relays. The compact size saves space.

PRODUCT SERVICE

Types
Termination Basic With Indicator With Check Button With Indicator and Check Button Top Bracket Mounting Plug-in Terminal With Diode (DC coil only) With Indicator and Diode (DC coil only) With Resistor and Capacitor (100V AC and over) With Indicator and RC (100V AC and over) Type SPDT Type No. RH1B-U RH1B-UL RH1B-UT RH1B-UD AC6, AC12, AC24, AC50, AC100, AC110, AC115, AC120, AC200, AC220, AC230, AC240 DC6, DC12, DC24, DC48, DC100, DC110 DC6, DC12, DC24, DC48, DC100, DC110 Coil Voltage Code Type No. RH2B-U RH2B-UL DPDT Coil Voltage Code

AC6, AC12, AC24, AC50, AC100-110, AC110-120, RH2B-UC AC200-220, AC220-240 RH2B-ULC DC6, DC12, DC24, DC48, DC100-110 RH2B-UT RH2B-UD DC6, DC12, DC24, DC48, DC100-110

RH2B-ULD

RH2B-R RH2B-LR

AC100-110, AC110-120, AC200-220, AC220-240

Basic PC Board Terminal With Indicator With Diode (DC coil only)

RH1V2-U

AC6, AC12, AC24, AC50, AC100, AC110, AC115, AC120, AC200, AC220, AC230, AC240 RH2V2-U DC6, DC12, DC24, DC48, DC100, DC110 DC6, DC12, DC24, DC48, DC100, DC110 RH2V2-UL

RH1V2-UD

AC6, AC12, AC24, AC50, AC100-110, AC110-120, AC200-220, AC220-240 DC6, DC12, DC24, DC48, DC100-110 DC6, DC12, DC24, DC48, DC100-110

RH2V2-UD

Type numbers marked with in the table above are UL-recognized, CSA-certied, and TV-approved.

Ordering Information
When ordering, specify the Type No. and coil voltage code.
(Example) RH2B-U
Type No.

AC100-110
Coil Voltage Code

(04/10/25)

19

RH Series Power Relays


Types
Termination Basic With Indicator With Check Button With Indicator and Check Button Top Bracket Mounting With Diode (DC coil only) With Indicator and Diode (DC coil only) Basic PC Board Terminal Type 3PDT Type No. RH3B-U RH3B-UL RH3B-UC Coil Voltage Code AC6, AC12, AC24, AC50, AC100, AC110, AC115, AC120, AC200, AC220, AC230, AC240 DC6, DC12, DC24, DC48, DC100, DC110 Type No. RH4B-U RH4B-UL RH4B-UC 4PDT Coil Voltage Code AC6, AC12, AC24, AC50, AC100, AC110, AC115, AC120, AC200, AC220, AC230, AC240 DC6, DC12, DC24, DC48, DC100, DC110

RH3B-ULC RH3B-UT RH3B-D RH3B-LD

RH4B-ULC RH4B-UT RH4B-UD

Plug-in Terminal

DC6, DC12, DC24, DC48, DC100, DC110

RH4B-LD

DC6, DC12, DC24, DC48, DC100, DC110

RH3V2-U

With Indicator With Diode (DC coil only)

RH3V2-UL RH3V2-D

AC6, AC12, AC24, AC50, AC100, AC110, AC115, AC120, AC200, AC220, AC230, AC240 DC6, DC12, DC24, DC48, DC100, DC110 DC6, DC12, DC24, DC48, DC100, DC110

RH4V2-U

RH4V2-UL

AC6, AC12, AC24, AC50, AC100, AC110, AC115, AC120, AC200, AC220, AC230, AC240 DC6, DC12, DC24, DC48, DC100, DC110 DC6, DC12, DC24, DC48, DC100, DC110

RH4V2-UD

Type numbers marked with in the table above are UL-recognized, CSA-certied, and TV-approved.

Ordering Information
When ordering, specify the Type No. and coil voltage code.
(Example) RH3B-U
Type No.

AC110
Coil Voltage Code

Coil Ratings
Rated Voltage (V) SPDT 6 12 24 50 AC (50/60Hz) 100 110 115 120 200 220 230 240 SPDT 6 12 DC 24 48 100 110 DPDT 6 12 24 50 100-110 110-120 200-220 220-240 DPDT 6 12 24 48 100-110 3PDT 4PDT 6 12 24 50 100 110 115 120 200 220 230 240 6 12 24 48 100 110 6 12 24 50 100 110 115 120 200 220 230 240 6 12 24 48 100 110 Rated Current (mA) 15% at 20C 50Hz SPDT 170 86 42 20.5 10.5 9.6 8.9 8.6 5.6 4.7 4.7 4.9 SPDT 128 64 32 18 10 8 DPDT 240 121 60.5 28.9 10.3-11.8 9.4-10.8 5.1-5.9 4.7-5.4 3PDT 330 165 81 39.5 20 18.1 17.1 16.4 9.8 8.8 8.5 8.2 DPDT 150 75 36.9 18.5 8.2-9.0 4PDT 387 196 98 47 23.5 21.6 20.8 19.5 11.8 10.7 10.3 9.8 SPDT 150 75 37 18 9 8.4 7.8 7.5 4.9 4.1 4.1 4.3 3PDT 240 120 60 30 14.5 12.8 200 100 50 24 9.1-10.0 8.0-9.2 4.3-5.0 4.0-4.6 60Hz DPDT 3PDT 280 140 70 34 17 15.5 14.8 14.2 8.5 7.7 7.4 7.1 4PDT 250 125 62 31 15 15 4PDT 330 165 83 40 20 18.2 17.5 16.5 10 9.1 8.7 8.3 SPDT 18.8 76.8 300 1,280 5,220 6,950 7,210 8,100 21,442 25,892 26,710 26,710 SPDT 47 188 750 2,660 10,000 13,800 Coil Resistance () 10% at 20C DPDT 9.4 39.3 153 680 3,360 4,290 13,690 18,820 DPDT 40 160 650 2,600 12,250 3PDT 6.4 25.3 103 460 1,940 2,200 2,620 2,770 8,140 10,800 11,500 12,100 3PDT 25 100 400 1,600 6,900 8,600 4PDT 5.4 21.2 84.5 340 1,560 1,800 1,910 2,220 6,360 7,360 8,520 9,120 4PDT 24 96 388 1,550 6,670 7,340 110% 80% maximum 10% minimum 110% 80% maximum 30% minimum Operation Characteristics (against rated values at 20C) Max. Continuous Min. Pickup Applied Voltage Voltage Dropout Voltage

3PDT 4PDT

20

(04/10/25)

RH Series Power Relays


Contact Ratings
Type Continuous Current Maximum Contact Capacity Allowable Contact Power Resistive Load 1540VA AC 300W DC Inductive Load 990VA AC 210W DC Rated Load Res. Load 10A 7A 10A 10A 7.5A 10A Ind. Load 7A 4.5A 7A 7.5A 5A 7.5A Voltage RH1 RH1 10A 10A RH2 10A 10A RH3 7.5A 10A RH4 7.5A 10A 240V AC 10A 120V AC 10A 30V DC 10A Resistive RH2 10A 10A 10A RH3 General use RH4 7.5A 10A 10A RH1 7A 7A RH2 7A 7.5A RH3 7A Voltage (V) 110 AC SPDT 10A 220 AC 30 DC DPDT 3PDT 4PDT 10A 1650VA AC 300W DC 110 AC 1100VA AC 220 AC 225W DC 30 DC

UL Ratings
Resistive Voltage 240V AC 120V AC 30V DC 28V DC RH1 RH2 10A RH3 7.5A 10A 10A RH4 7.5A 10A General use RH1 RH2 7A RH3 6.5A 7.5A RH4 5A Horse Power Rating RH1 RH2 RH3 RH4

10A

1/3 H P 1/3 H P

7A

10A

7.5A 1/6 H P 1/6 H P

CSA Ratings
Horse Power Rating RH4 RH1, 2, 3 5A 1/3 HP 1/6 HP

Note: Inductive load for the rated load cos = 0.3, L/R = 7 ms

TV Ratings
Voltage 240V AC 30V DC

10A 10A

7.5A 7.5A

AC: cos = 1.0, DC: L/R = 0 ms

7.5A

Specications
Contact Material Contact Resistance 1 Minimum Applicable Load Operate Time 2 SPDT DPDT 3PDT 4PDT SPDT DPDT 3PDT 4PDT SPDT DPDT 3PDT 4PDT Insulation Resistance SPDT Dielectric Strength DPDT 3PDT 4PDT Silver cadmium oxide 50 m maximum 24V DC, 30 mA; 5V DC, 100 mA (reference value) 20 ms maximum 25 ms maximum 20 ms maximum 25 ms maximum AC: 1.1 VA (50 Hz), 1 VA (60 Hz) DC: 0.8W AC: 1.4 VA (50 Hz), 1.2 VA (60 Hz) DC: 0.9W AC: 2 VA (50 Hz), 1.7 VA (60 Hz) DC: 1.5W AC: 2.5 VA (50 Hz), 2 VA (60 Hz) DC: 1.5W 100 M minimum (500V DC megger) Between live and dead parts: Between contact and coil: Between contacts of the same pole: Between live and dead parts: Between contact and coil: Between contacts of different poles: Between contacts of the same pole: Electrical: Mechanical: Damage limits: Operating extremes: Damage limits: Operating extremes: DPDT Electrical Life SPDT 3PDT 4PDT SPDT Operating Temperature 4 Operating Humidity Weight (approx.) DPDT 3PDT 4PDT 2000V AC, 1 minute 2000V AC, 1 minute 1000V AC, 1 minute 2000V AC, 1 minute 2000V AC, 1 minute 2000V AC, 1 minute 1000V AC, 1 minute 3

Release Time 2

Power Consumption (approx.)

Operating Frequency Vibration Resistance Shock Resistance

1800 operations/h maximum 18,000 operations/h maximum 10 to 55 Hz, amplitude 0.5 mm 10 to 55 Hz, amplitude 0.5 mm 1000 m/s2 200 m/s2 (SPDT, DPDT) 100 m/s2 (3PDT, 4PDT)

500,000 operations minimum (110V AC, 1A) 200,000 operations minimum (110V AC, 1A) 50,000,000 operations minimum 25 to +50C (no freezing) 25 to +40C (no freezing) 45 to 85% RH (no condensation) SPDT: 24g, DPDT: 37g, 3PDT: 50g, 4PDT: 74g

Mechanical Life

Note: Above values are initial values. 1: Measured using 5V DC, 1A voltage drop method 2: Measured at the rated voltage (at 20C), excluding contact bouncing Release time of relays with diode: 40 ms maximum 3: Relays with indicator or diode: 1000V AC, 1 minute 4: For use under different temperature conditions, refer to Continuous Load Current vs. Operating Temperature Curve. The operating temperature range of relays with indicator or doide is 25 to +40C.

(04/10/25)

21

RH Series Power Relays


Internal Connection (Bottom View)
Basic Type
SPDT DPDT 3PDT 4PDT With Check Button
Front Pushbutton

1 5 9 13 () 14 (+)

1 5 9 13( )

4 8 12 ( + )14

1 5 9 13 ( )

2 6 10

4 8 12 ( + )14

1 5 9 13( )

2 6 10

3 7 11

4 8 12 ( + )14

Contacts can be operated by pressing the check button. Press the button quickly to prevent arcing.

With Indicator (-L type)


SPDT
1 5 1 5 9 14 (+) 13 ( )

3PDT
2 6 10 4 8 12 ( + )14

4PDT

DPDT When the coil is energized, the indicator goes on. Relays for below 100V DC do not contain a protection diode (except DPDT).

1 5 9 13( )

2 6 10

3 7 11

4 8 12 ( + )14

1 5

4 8 12 ( + )14

Below 100V AC/DC

9 13 ()

Below 24V AC/DC

9 13( )

1 1 5 9 14 (+) 13( )

2 6 10

4 8 12 ( + )14

1 5 9 13( )

2 6 10

3 7 11

4 8 12 ( + )14

4 8 12

100V AC/DC and over

5 9 13 ()

24V AC/DC and over

5 9

13( )

( + )14

With Diode (-D type)


SPDT DPDT 3PDT 4PDT This type contains a diode to absorb the counter emf generated when the coil is deenergized. The release time is slightly longer. Available for DC coil only. Diode Characteristics Reverse withstand voltage: 1,000V Forward current: 1A

1 5 9 13 () 14 (+)

1 5 9 13( )

4 8 12 ( + )14

1 5 9 13 ( )

2 6 10

4 8 12 ( + )14

1 5 9 13( )

2 6 10

3 7 11

4 8 12 ( + )14

With Indicator and Diode (-LD type)


DPDT
1 5 4 8 12 ( + )14 1 5

3PDT
2 6 10 4 8 12 ( + )14 1 5 9 13( ) 2 6 10

4PDT
3 7 11 4 8 12 ( + )14

This type contains an operation indicator and a sure absorber, and has the same height as the basic type.

Below 24V DC

9 13( )

Below 100V DC

9 13( )

1 5

4 8 12 ( + )14

1 5

2 6 10

4 8 12 ( + )14

1 5 9 13( )

2 6 10

3 7 11

4 8 12 ( + )14

24V DC and over

9 13( )

100V DC and over

9 13( )

With Resistor and Capacitor (-R type)


DPDT
1 5 9 13() 4 8 12 (+)14

With Indicator and RC (-LR type)


DPDT
1 5 9 13() 4 8 12 (+)14

This type contains an RC circuit to absorb the surge voltage generated when the coil is deenergized. This type is approx. 17 mm higher than the basic type. Available for AC coils of 100V and over. R: 120 C: 0.033 F

This type contains an operation indicator and a surge absorber. This type is approx. 17 mm higher than the basic type. Available for AC coils of 100V and over.

22

(04/10/25)

RH Series Power Relays


Characteristics (Reference Data)
Maximum Switching Capacity
(RH1)
10.0 AC resistive 5.0 AC inductive 5.0

(RH2/RH3/RH4)
10.0 AC resistive AC inductive

Load Current (A)

Load Current (A)

DC resistive 1.0 DC inductive 0.5

DC resistive 1.0

0.5

DC inductive

0.1 1

10 Load Voltage (V)

50

100

200 300

0.1 1

10 50 Load Voltage (V)

100

200 300

Electrical Life Curve


AC Load
1000

DC Load
110V AC resistive

1000

(RH1)
500 Life ( 10,000 operations)

(RH1)
500 Life ( 10,000 operations)

30V DC resistive 100

100

50

50 100V DC resistive 30V DC inductive

20

220V AC inductive

20 110V AC inductive 4 5 6 7 Load Current (A) 220V AC resistive 8 9 10 10 100V DC inductive 1 2 3 4 5 6 Load Current (A) 7 8 9 10

10

(RH2) 1000
500 Life ( 10,000 operations)

110V AC resistive

(RH2) 1000
30V DC resistive 500 Life ( 10,000 operations)

100

100 30V DC inductive

50 220V AC inductive 20 220V AC resistive 110V AC inductive

50

100V DC resistive 100V DC inductive

20

10

5 6 7 Load Current (A)

10

10

4 5 6 Load Current (A)

10

(RH3/RH4) 1000
110V AC resistive 500 Life ( 10,000 operations)

(RH3/RH4) 1000
500 Life ( 10,000 operations) 30V DC resistive

30V DC inductive

100

100

50

50

20

220V AC inductive 220V AC resistive 110V AC inductive

20

100V DC resistive 100V DC inductive

10

4 5 6 Load Current (A)

10

10

4 5 6 Load Current (A)

10

(04/10/25)

23

RH Series Power Relays


Continuous Load Current vs. Operating Temperature Curve (Basic Type, With Check Button, and Top Bracket Mounting Type)
(RH1)
100 Operating Temperature (C) 90 80
DC Coil

Note: The rated voltage is applied to the coil.

(RH2)
100 90 Operating Temperature (C) 80 70 60 50 40 30 20 10

Note: The rated voltage is applied to the coil.

(RH3/RH4)
100 90 Operating Temperature (C) 80 70 60 50 40 30 20 10

Note: The rated voltage is applied to the coil.

70 60 50 40 30 20 10 0 1 2 3 4 5 6 7 8 9 10 Load Current (A)


AC Coil

DC Coil

AC/DC Coil

AC Coil

1 2 3 4 5 6 7 8 9 10 Load Current (A)

1 2 3 4 5 6 7 8 9 10 Load Current (A)

Dimensions
RH1B-U/RH1B-UL/RH1B-UD
Total length from panel surface including relay socket SH1B-05A: 61.5 (63.5) max., SH1B-51: 39.6 (41.6) max.
Dimensions in the ( ) include a hold-down spring.

Applicable Socket and Hold-down Spring


Socket Mounting Style Type No. DIN Rail Mount Socket SH1B-05A SH1B-05C SH1B-51 SH1B-62 Hold-down Spring SY2S-02F1 SFA-101 SFA-202 SY4S-51F1 SFA-301 SFA-302

2.6 hole

4.7

1
5

0.5

9
13 14

27.5

Panel Mount Socket PC Board Mount Socket

(Photo: RH1B-U)
5.4 35.6 max.
PRODUCT SERVICE

14

6.4

RH2B-U/RH2B-UL/RH2B-UD/RH2B-ULD

Total length from panel surface including relay socket SH2B-05A: 61.5 (63.5) max., SH2B-51: 39.6 (41.6) max.
Dimensions in the ( ) include a hold-down spring.

Applicable Socket and Hold-down Spring


Socket Mounting Style Type No. DIN Rail Mount Socket SH2B-05A SH2B-05C SH2B-05D Hold-down Spring SY4S-02F1 SFA-101 SFA-202 SFA-502 SY4S-51F1 (SY4S-02F1) SFA-301 SFA-302 SY4S-51F1 (SY4S-02F1)

2.6 hole

4.7

0.5

27.5

5 9 13

8 12 14

(Photo: RH2B-U)
35.6 max.
PRODUCT SERVICE

Panel Mount Socket PC Board Mount Socket

SH2B-51

6.4

21

SH2B-62

Note: (SY4S-02F1) is for the relay with check button.


Total length from panel surface including relay socket SH3B-05A: 61.5 (63.5) max., SH3B-51: 39.6 (41.6) max.
Dimensions in the ( ) include a hold-down spring.

RH3B-U/RH3B-UL/RH3B-D/RH3B-LD

Applicable Socket and Hold-down Spring


Socket Mounting Style Type No. DIN Rail Mount Socket SH3B-05A SH3B-05C SH3B-51 SH3B-62 Hold-down Spring SH3B-05F1 SFA-101 SFA-202 SY4S-51F1 (SH3B-05F1) SFA-301 SFA-302

4.7

2.6 hole

Panel Mount Socket


1 2 6 10 4

0.5

9 13

11

27.5

(Photo: RH3B-U)

PC Board Mount Socket

14

Note: (SH3B-05F1) is for the relay with check button.

PRODUCT SERVICE

35.6 max.

6.4

31

RH4B-U/RH4B-UL/RH4B-UD/RH4B-LD

Total length from panel surface including relay socket SH4B-05A: 61.5 (63.5) max., SH4B-51: 39.6 (41.6) max.
Dimensions in the ( ) include a hold-down spring.

Applicable Socket and Hold-down Spring


Socket Mounting Style Type No. DIN Rail Mount Socket Panel Mount Socket SH4B-05A SH4B-05C SH4B-51 SH4B-62 Hold-down Spring SH4B-02F1 SFA-101 SFA-202 SY4S-51F1 (SH4B-02F1) SFA-301 SFA-302

2.6 hole

4.7

27.5

(Photo: RH4B-U)
0.5

1 5 9 13

2 6 10

3 7 11

4 8 12 14

PC Board Mount Socket

Note 1: Use two SY4S-51F1 hold-down springs for the SH4B-51 and SH4B-62 sockets. Note 2: (SH4B-02F1) is for the relay with check button.

PRODUCT SERVICE

35.6 max.

6.4

41

24

(04/10/25)

RH Series Power Relays


RH2B-R/RH2B-LR
Total length from panel surface including relay socket SH2B-05A: 78.3 (80.3) max., SH2B-51: 56.4 (58.4) max.
Dimensions in the ( ) include a hold-down spring.

Applicable Socket and Hold-down Spring


Socket Mounting Style Type No. DIN Rail Mount SH2B-05A Socket SH2B-05C Panel Mount Socket SH2B-51 Hold-down Spring SFA-202 SFA-302

0.5

2.6 hole

1 5 9 13

12 14

(Photo: RH2B-R)

52.4 max.

6.4

4.7

21

RH1B-UT
0.5 2.6 hole

RH2B-UT
10

4.7

4.7

27.5

Note: Hold-down spring is not available for mounting the RH2B-R on a PC board mount socket.

1 5

5.9

0.5

4.7

2.6 hole

43.2 38

5.9

9 13 14

27.5

43.2 38

9 13

12 14

6.6

3.5 14.5

2 35.6 max.

5.4 6.4
PRODUCT SERVICE

3.5 21.5

2 35.6 max.

6.4

PRODUCT SERVICE

RH3B-UT
4.7 10 10

RH4B-UT
10 10

0.5 4.7

2 2.6 hole
1 2 6 10 4

4.7

3.5

2.6 hole

10

4.7

7.25

3.5 0.5 4.7

43.2 38

5.9

28

5 9 13

8 12 14

2 6 10

3 7 11

5.9

44 38

9 13

12 14

7.25

21.5 31.5
PRODUCT SERVICE

2 35.6 max.

6.4
PRODUCT SERVICE

35.6 max. 42 max.

6.4

7.25

28 41.5

RH1V2-U/RH1V2-UD
3-2.4 holes 2-2 holes

1.5

0.5
1 5

27.5

7.15

(Photo: RH1V2-U)
35.6 max.
PRODUCT SERVICE

0.5

9 13 14

4.6

14

4.4

0.5

0.5

7.25

RH2V2-U/RH2V2-UL/ RH2V2-UD

8-2.4 holes

4 8 12 14

5 9

13

27.5

(Photo: RH2V2-U)
2
35.6 max.
PRODUCT SERVICE

10
4.6 21

(RH2V2-U)
11-2.4 holes 10 10

14.2

6 10

8 11 14

0.5

9 13

0.5
PRODUCT SERVICE

31

(RH3V2-U)

35.6 max.

4.6

1 5

2 6 10

3 7 11

0.5

0.5
PRODUCT SERVICE

41 4.6

(RH4V2-U)

35.6 max.

7.25

(Photo: RH4V2-U)

9 13

12 14

27.5

7.8

All dimensions in mm.

13.15

4.7

RH4V2-U/RH4V2-UL/ RH4V2-UD

30 14-2.4 holes 10

7.25

(Photo: RH3V2-U)

27.5

7.8

13.15

4.7

RH3V2-U/RH3V2-UL/ RH3V2-D

13.15

7.8

4.7

0.5

6.6

12.5

4.7

(04/10/25)

25

28

27.5
4 8

RM Series Miniature Relays


DPDT contacts (5A) Plug-in and PC board terminal styles
Compact miniature size saves space Options include indicators and check buttons.

PRODUCT SERVICE

Types
Type Basic Plug-in Terminal Type No. RM2S-U RM2S-UL RM2S-UC Coil Voltage Code AC6, AC12, AC24, AC50, AC100-110, AC110-120, AC200-220, AC220-240 DC6, DC12, DC24, DC48, DC100-110 Type No. RM2V-U RM2V-UL DC6, DC12, DC24, DC48, DC100-110 PC Board Terminal Coil Voltage Code AC6, AC12, AC24, AC50, AC100-110, AC110-120, AC200-220, AC220-240 DC6, DC12, DC24, DC48, DC100-110

With Indicator With Check Button With Diode (DC coil only) With Indicator and Diode (DC coil only)

Top Bracket Mounting Type RM2S-UT RM2S-UD

RM2S-ULD

Type numbers marked with in the table above are UL-recognized, CSA-certied, and TV-approved.

Ordering Information
When ordering, specify the Type No. and coil voltage code.
(Example) RM2S-U
Type No.

AC100-110
Coil Voltage Code

Coil Ratings
Rated Current (mA) 15% at 20C Rated Voltage (V) 50Hz 6 12 AC (50/60Hz) 24 50 100-110 110-120 200-220 220-240 6 12 DC 24 48 100-110 240 121 60.5 28.9 10.3-11.8 9.4-10.8 5.1-5.9 4.7-5.4 150 75 36.9 18.5 8.2-9.0 60Hz 200 100 50 24 9.1-10.0 8.2-9.2 4.3-5.0 4.0-4.6 Coil Resistance () 10% at 20C 9.4 39.3 153 680 3,360 4,290 13,690 18,820 40 160 650 2,600 12,250 110% 80% maximum 10% minimum 110% 80% maximum 30% minimum Operation Characteristics (against rated values at 20C) Max. Continuous Applied Voltage Min. Pickup Voltage Dropout Voltage

26

(04/10/25)

RM Series Miniature Relays


Contact Ratings
Continuous Current Maximum Contact Capacity Allowable Contact Power Rated Load Resistive Load 1100VA AC 150W DC Inductive Load 440VA AC 75W DC Voltage 110V AC 5A 220V AC 30V DC Res. Load 5A 5A 5A Ind. Load 2.5A 2A 2.5A

Specications
Contact Material Contact Resistance Minimum Applicable Load Operate Time Release Time Power Consumption (approx.) Insulation Resistance Silver 30 m maximum 1 24V DC, 10 mA; 5V DC, 20 mA (reference value) 20 ms maximum 2 20 ms maximum 2 AC: 1.4 VA (50 Hz), 1.2 VA (60 Hz) DC: 0.9W 100 M minimum (500V DC megger) Between live and dead parts: 2000V AC, 1 minute 3 Between contact and coil: 2000V AC, 1 minute Between contacts of different poles: 2000V AC, 1 minute Between contacts of the same pole: 1000V AC, 1 minute Electrical: 1800 operations/h maximum Mechanical: 18,000 operations/h maximum Coil: 85C maximum, Contact: 65C maximum Damage limits: 10 to 55 Hz, amplitude 0.5 mm Operating extremes: 10 to 55 Hz, amplitude 0.5 mm Damage limits: 1000 m/s2 Operating extremes: 200 m/s2 500,000 operations (220V AC, 5A) 50,000,000 operations 25 to +45C (no freezing) 4 45 to 85% RH (no condensation) 35g

Note: Inductive load for the rated load cos = 0.3, L/R = 7 ms

UL Ratings
Voltage 240V AC 120V AC 100V DC 30V DC Resistive 5A 0.4A 5A General use 2A 2.5A Operating Frequency Temperature Rise Resistive 5A 5A 5A General use 2A 2.5A 0.4A 2.5A Shock Resistance Electrical Life Mechanical Life Operating Temperature Operating Humidity Weight (approx.) Vibration Resistance Dielectric Strength

CSA Ratings
Voltage 240V AC 120V AC 100V DC 30V DC

TV Ratings
240V AC 30V DC AC: cos = 1.0, DC: L/R = 0 ms 5A 5A

Note: Above values are initial values. 1: Measured using 5V DC, 1A voltage drop method 2: Measured at the rated voltage (at 20C), excluding contact bouncing Release time of relays with diode: 40 ms maximum 3: Relays with indicator or diode: 1000V AC, 1 minute 4: For use under different temperature conditions, refer to Continuous Load Current vs. Operating Temperature Curve. The operating temperature range of relays with indicator or doide is 25 to +40C.

Characteristics (Reference Data)


Maximum Switching Capacity
5
AC resistive

Electrical Life Curve


AC Load
110V AC resistive 220V AC resistive

DC Load
30V DC resistive

Load Current (A)

Life ( 10,000 operations)

Life ( 10,000 operations)

AC inductive

1000 500

1000 500

30V DC inductive

DC inductive

DC resistive

0.5

100 50 110V AC inductive

100 50 100V DC resistive 100V DC inductive 10

0.1 1

10

50

100

200 300 10 0 1 2 3

220V AC inductive 4 5 0 1

Load Voltage (V)

Load Current (A)

Load Current (A)

Continuous Load Current vs. Operating Temperature Curve (Basic Type, With Check Button, and Top Bracket Mounting Type)
100 90

Note: The rated voltage is applied to the coil.

Operating Temperature (C)

80 70 60 50 40 30 20 10 0 1 2 3 4 5 AC Coil DC Coil

Load Current (A)

(04/10/25)

27

RM Series Miniature Relays


Internal Connection (Bottom View)
Basic Type
1 5 9 13() 4 8 12 (+)14

With Check Button


Front Pushbutton

With Diode (-D type)


1 5 9 4 8 12 (+)14

This type contains a diode to absorb the counter emf generated when the coil is deenergized. The release time is slightly longer. Diode Characteristics Reverse withstand voltage: 1,000V Forward current: 1A

Contacts can be operated by pressing the check button. Press the button quickly to prevent arcing.

13()

With Indicator (-L type)


Below 24V AC/DC
1 5 9 13() 4 8 12 (+)14

24V AC/DC and over


1 5 9 4 8 12

When the coil is energized, the indicator goes on. is not contained in DPDT relays for below 100V DC.

With Indicator and Diode (-LD type)


Below 24V DC
1 5 9 13() 4 8 12 14(+) 13() (+)14

The LED protection diode

24V DC and over


1 5 9 4 8 12

This type contains an operation indicator and a surge absorber, and has the same height as the basic type.

13()

(+)14

Dimensions

Plug-in Type (Solder Terminal)


RM2S-U/RM2S-UL RM2S-UD/RM2S-ULD Applicable Socket and Hold-down Spring
Total length from the panel surface including relay socket. SM2S-05A: 61.5 (63.5) max., SM2S-51: 39.6 (41.6) max.
Dimensions in the ( ) include a hold-down spring.

Socket Mounting Style Type No. DIN Rail Mount Socket SM2S-05A SM2S-05C SM2S-05D

Hold-down Spring SY4S-02F1 SFA-101 SFA-202 SFA-502 SY4S-51F1 (SY4S-02F1) SFA-301 SFA-302 SY4S-51F1 (SY4S-02F1)

2.2 1.2 hole


1 5 4 8 12 14

2.6

0.5

9 13

27.5

Panel Mount Socket PC Board Mount Socket

SM2S-51 SM2S-61 SM2S-62

(Photo: RM2S-U)
35.6 max. 6.4 21

PRODUCT SERVICE

Note: (SY4S-02F1) is for the relay with check button.

PC Board Terminal Type


RM2V-U/RM2V-UL

2.6

0.5

0.8

8-1 hole

1 5

4 8

27.5

12 14

0.5

13

7.15

35.6 max.
PRODUCT SERVICE

21

13.2

Top Bracket Mounting Type (Solder Terminal)


RM2S-UT
13.2

2.2 1.2 hole

2.6

0.5

4.1

1 5

43.2

6.3

6.4
4 8 12 14 9 13

12.7

(Photo: RM2V-U)

4.1

3.5 21.5
PRODUCT SERVICE

2 35.6 max. 6.4

6.4

27.5

38

All dimensions in mm.

28

(04/10/25)

RY Series Miniature Relays


DPDT (3A) and 4PDT (5A) contacts Bifurcated contacts are also available
The RY series are general purpose miniature relays with a 3A or 5A contact capacity. A wide variety of terminals styles and coil voltages meet a wide range of applications. All 4PDT types have arc barriers.

PRODUCT SERVICE

Types
Plug-in Terminal Type
Contact Basic With Indicator With Check Button With Indicator and Check Button Standard Top Bracket Mounting With Diode (DC coil only) With Indicator and Diode (DC coil only) Basic With Indicator Bifurcated Top Bracket Mounting With Diode (DC coil only) Type DPDT Type No. RY2S-U Coil Voltage Code Type No. RY4S-U 4PDT Coil Voltage Code

RY2S-UL AC6, AC12, AC24, AC50, AC100, AC110, AC115, AC120, AC200, AC220, AC230, AC240 DC6, DC12, D24, DC48, DC100, DC110 RY2S-UT RY2S-UD DC6, DC12, DC24, DC48, DC100, DC110

RY4S-UL AC6, AC12, AC24, AC50, AC100-110, AC110-120, RY4S-UC AC200-220, AC220-240 RY4S-ULC DC6, DC12, DC24, DC48, DC100-110 RY4S-UT RY4S-UD RY4S-ULD DC6, DC12, DC24, DC48, DC100-110

RY22S-U AC6, AC12, AC24, AC50, AC100, RY22S-UL AC110, AC115, AC120, AC200, AC220, AC230, AC240 RY22S-UT DC6, DC12, DC24, DC48, DC100, DC110 RY22S-UD DC6, DC12, DC24, DC48, DC100, DC110

PC Board Terminal Type


Contact Type Standard With Indicator With Diode (DC coil only) Standard Bifurcated With Indicator With Diode (DC coil only) DPDT Type No. RY2V-U RY2V-UL Coil Voltage Code Type No. AC6, AC12, AC24, AC50, AC100, RY4V-U AC110, AC115, AC120, AC200, AC220, AC230, AC240 DC6, DC12, DC24, DC48, RY4V-UL DC100, DC110 DC6, DC12, DC24, DC48, DC100, DC110 4PDT Coil Voltage Code AC6, AC12, AC24, AC50, AC100-110, AC110-120, AC200-220, AC220-240 DC6, DC12, DC24, DC48, DC100-110

Standard

RY2V-UD RY22V-U

AC6, AC12, AC24, AC50, AC100, AC110, AC115, AC120, AC200, AC220, AC230, AC240 RY22V-UL DC6, DC12, DC24, DC48, DC100, DC110 RY22V-UD DC6, DC12, DC24, DC48, DC100, DC110

Type numbers marked with in the tables above are UL-recognized, CSA-certied, and TV-approved.

Ordering Information
When ordering, specify the Type No. and coil voltage code.
(Example) RY4S-U
Type No.

AC100-110
Coil Voltage Code

(04/10/25)

29

RY Series Miniature Relays


Coil Ratings
Rated Voltage (V) DPDT 6 12 24 50 AC (50/60Hz) 100 110 115 120 200 220 230 240 DPDT 6 12 DC 24 48 100 110 4PDT 6 12 24 50 100-110 110-120 200-220 220-240 4PDT 6 12 24 48 100-110 Rated Current (mA) 15% at 20C 50Hz DPDT 170 86 42 20.5 10.5 9.6 8.9 8.6 5.6 4.7 4.7 4.9 DPDT 128 64 32 18 10 8 4PDT 240 121 60.5 28.9 10.3-11.8 9.4-10.8 5.1-5.9 4.7-5.4 DPDT 150 75 37 18 9 8.4 7.8 7.5 4.9 4.1 4.1 4.3 4PDT 150 75 36.9 18.5 8.2-9.0 60Hz 4PDT 200 100 50 24 9.1-10.0 8.0-9.2 4.3-5.0 4.0-4.6 Coil Resistance () 10% at 20C DPDT 18.8 76.8 300 1,280 5,220 6,950 7,210 8,100 21,442 25,892 26,710 26,710 DPDT 47 188 750 2,660 10,000 13,800 4PDT 9.4 39.3 153 680 3,360 4,290 13,690 18,820 4PDT 40 160 650 2,600 12,250 110% 80% maximum 10% minimum 110% 80% maximum 30% minimum Operation Characteristics (against rated values at 20C) Max. Continuous Applied Voltage Min. Pickup Voltage Dropout Voltage

Contact Ratings
Contact Continuous Current Maximum Contact Capacity Allowable Contact Power Resistive Load 660 VA AC 90W DC Inductive Load 176 VA AC 45W DC Voltage 110V AC 3A 220V AC 30V DC 5A 1200 VA AC 150W DC 288 VA AC 60W DC 240V AC 30V DC 110V AC 1A 176 VA AC 30W DC 88 VA AC 15W DC 220V AC 30V DC Rated Load Resistive Load 3A 3A 3A 5A 5A 1A 0.8A 1A Inductive Load 1.5A 0.8A 1.5A 1.2A 2A 0.5A 0.4A 0.5A

Standard Contact DPDT Standard Contact 4PDT Bifurcated Contact DPDT

Note: Inductive load for the rated load cos = 0.3, L/R = 7 ms

UL Ratings (Standard Contact)


Voltage 240V AC 120V AC 100V DC 30V DC Resistive DPDT 3A 0.2A 3A 4PDT 5A 0.2A 5A General use DPDT 0.8A 1.5A 0.2A 3A 4PDT 5A 0.2A 5A

CSA Ratings (Standard Contact)


Voltage 240V AC 120V AC 100V DC 30V DC Resistive DPDT 3A 3A 3A 4PDT 5A 5A General use DPDT 0.8A 1.5A 0.2A 1.5A 4PDT 5A 0.2A 1.5A

TV Ratings (Standard Contact)


Voltage 240V AC 30V DC DPDT 3A 3A 4PDT 5A 5A

AC: cos = 1.0, DC: L/R = 0 msec

UL Ratings (Bifurcated Contact)


Voltage 240V AC 120V AC 30V DC Resistive 0.8A 1A 1A General use 0.4A 0.5A 0.5A

CSA Ratings (Bifurcated Contact)


Voltage 240V AC 120V AC 30V DC Resistive 0.8A 1A 1A General use 0.4A 0.5A

30

(04/10/25)

RY Series Miniature Relays


Specications
Contact Type Contact Material Contact Resistance Minimum Applicable Load Operate Time Release Time Power Consumption (approx.) Insulation Resistance 2 2 1 Standard Contact DPDT Gold-plated silver 50 m maximum 24V DC, 5 mA; 5V DC, 10 mA (reference value) 20 ms maximum 20 ms maximum AC: 1.1 VA (50 Hz), 1 VA (60 Hz) DC: 0.8W 100 M minimum (500V DC megger) Between live and dead parts: 1500V AC, 1 minute 3 Between contact and coil: 1500V AC, 1 minute Between contacts of different poles: 1500V AC, 1 minute Between contacts of the same pole: 1000V AC, 1 minute Electrical: Mechanical: Damage limits: Operating extremes: Damage limits: Operating extremes: Between live and dead parts: 2000V AC, 1 minute Between contact and coil: 2000V AC, 1 minute Between contacts of different poles: 2000V AC, 1 minute Between contacts of the same pole: 1000V AC, 1 minute Between live and dead parts: 1500V AC, 1 minute 3 Between contact and coil: 1500V AC, 1 minute Between contacts of different poles: 1500V AC, 1 minute Between contacts of the same pole: 1000V AC, 1 minute AC: 1.4 VA (50 Hz), 1.2 VA (60 Hz) DC: 0.9W AC: 1.1 VA (50 Hz), 1 VA (60 Hz) DC: 0.8W 4PDT Bifurcated Contact DPDT Silver-paradium alloy 100 m minimum 1V DC, 100 A (reference value)

Dielectric Strength

Operating Frequency Vibration Resistance Shock Resistance Electrical Life Mechanical Life Operating Temperature Operating Humidity Weight (approx.) 4

1800 operations/h maximum 18,000 operations/h maximum 10 to 55 Hz, amplitude 0.5 mm 10 to 55 Hz, amplitude 0.5 mm 1000 m/s2 100 m/s2 (DPDT), 200 m/s2 (4PDT) 100,000 operations (220V AC, 5A) 200,000 operations (220V AC, 3A) 25 to +55C (no freezing) 34g 5 200,000 operations (110V AC, 1A)

200,000 operations (220V AC, 3A) 50,000,000 operations 25 to +55C (no freezing) 45 to 85% RH (no condensation) 23g

25 to +55C (no freezing) 23g

Note: Above values are initial values. 1: Measured using 5V DC, 1A voltage drop method 2: Measured at the rated voltage (at 20C), excluding contact bouncing Release time of relays with diode: 40 ms maximum 3: Relays with indicator or diode: 1000V AC, 1 minute 4: For use under different temperature conditions, refer to Continuous Load Current vs. Operating Temperature Curve. The operating temperature range of relays with indicator or diode is 25 to +40C. 5: When the total current of 4 contacts is less than 15A, the operating temperature range is 25 to +70C.

Maximum Switching Capacity


(RY2)
5 3

Characteristics (Reference Data)


(RY22) (RY4)
5 0.5 AC resistive AC inductive 1 DC inductive 0.5 DC resistive 3 AC resistive AC inductive 1 AC resistive AC inductive

Load Current (A)

Load Current (A)

Load Current (A)

2 DC resistive 1

DC resistive DC inductive 0.1

0.5 0.3 0.2

DC inductive

0.05

0.1 1

10

50

100

200 300

10

20 30

50

100

200 300

Load Voltage (V)

Load Voltage (V)

0.01 1

10

50

100

200 300

Load Voltage (V)

Continuous Load Current vs. Operating Temperature Curve (Basic Type, With Check Button, and Top Bracket Mounting Type)
(RY2)
Operating Temperature (C)
100 90

Note: The rated voltage is applied to the coil.

(RY4)

100 90

Note: The rated voltage is applied to the coil.

Operating Temperature (C)

80 70 60 50 40 30 20 10 0 1 2 AC Coil

DC Coil

80 70 60 50 40 30 20 10 0 1 2 AC Coil

DC Coil

Load Current (A)

Load Current (A)

(04/10/25)

31

RY Series Miniature Relays


Electrical Life Curve
AC Load
(RY2)
1000

(RY22) (RY4)
Life ( 10,000 operations)
1000 500 200 100 240V AC inductive 50 20 110V AC inductive 220V AC inductive 1 2 3 10 0 1 2 3 4 5 240V AC resistive 1000 500 110V AC resistive 220V AC resistive 100 50 110V AC inductive 220V AC inductive

Life ( 10,000 operations)

500

110V AC resistive 220V AC resistive

200 100 50 20 10 0

Life ( 10,000 operations)

20 10

Load Current (A)

Load Current (A)

Load Current (A)

DC Load
(RY2)
30V DC resistive 1000 30V DC inductive

(RY22) (RY4)
1000 1000 500 30V DC resistive

Life ( 10,000 operations)

Life ( 10,000 operations)

500

500 200 100 30V DC inductive 50 20 10

Life ( 10,000 operations)

30V DC inductive

200 100 50 20 10 0 100V DC resistive 100V DC inductive 5 2 3

30V DC resistive

100 50

20 10 0 1 2 3 4 5

100V DC resistive 100V DC inductive 1

Load Current (A)

Load Current (A)

Load Current (A)

Internal Connection (Bottom View)


Basic Type
DPDT
1 5 9 13 ( ) 4 8 12 ( + )14 1 5 9 13 ( ) 2 6 10

With Check Button 4PDT


Front Pushbutton
3 7 11 4 8 12 ( + )14

With Indicator and Diode (-LD type)


This type contains an operation indicator and a surge absorber, and has the same height as the basic type. 4PDT Below 24V DC
1 5 9 2 6 10 3 7 11 4 8 12 (+)14

Contacts can be operated by pressing the check button. Press the button quickly to prevent arcing.

With Indicator (-L type)


DPDT Below 100V AC/DC
1 5 9 13() 4 8 12 (+)14

13()

4PDT Below 24V AC/DC


1 5 9 13() 2 6 10 3 7 11 4 8 12 (+)14

When the relay is energized, the indicator goes on. not contained in DPDT relays for below 100V DC.

The LED protection diode is

24V DC and over

1 5 9

2 6 10

3 7 11

4 8 12

100V AC/DC and over


1 5 9 13() 4 8 12 (+)14

13()

(+)14

24V AC/DC and over

1 5 9

2 6 10

3 7 11

4 8 12

13()

(+)14

With Diode (-D type)


DPDT
1 5 9 13() 4 8 12 (+)14 1 5 9 13() 2 6 10

4PDT
3 7 11 4 8 12 (+)14

This type contains a diode to absorb the counter emf generated when the coil is deenergized. The release time is slightly longer. Diode Characteristics Reverse withstand voltage: 1,000V Forward current: 1A

32

(04/10/25)

RY Series Miniature Relays


Dimensions
RY2S-U/RY2S-UL RY2S-UD

Plug-in Terminal Type


RY22S-U/RY22S-UL RY22S-UD
Total length from panel surface including relay socket SY2S-05A: 61.5 (63.5) max., SY2S-51: 39.6 (41.6) max.
3 1.2 oblong hole Dimensions in the ( ) include a hold-down spring.

Applicable Socket and Hold-down Spring


Socket Mounting Style Type No. DIN Rail Mount Socket Panel Mount Socket PC Board Mount Socket SY2S-05A SY2S-05C SY2S-51 SY2S-61 Hold-down Spring SY2S-02F1 SFA-101 SFA-202 SY4S-51F1 SFA-301 SFA-302

2.6

1 5

4 8 12 14

9 13

(Photo: RY2S-U)
PRODUCT SERVICE

(Photo: RY22S-U)
35.6 max.
PRODUCT SERVICE

5.4

14

27.5

0.5

RY4S-U/RY4S-UL/RY4S-UD/RY4S-ULD
Total length from the panel surface including relay socket SY4S-05A: 61.5 (63.5) max., SY4S-51: 39.6 (41.6) max.
2.2 1.2 oblong hole Dimensions in the ( ) include a hold-down spring.

Applicable Socket and Hold-down Spring


Socket Mounting Style Type No. DIN Rail Mount Socket SY4S-05A SY4S-05C SY4S-05D
1 5 2 6 10 3 7 11 4 8 12

Hold-down Spring SY4S-02F1 SFA-101 SFA-202 SFA-502 SY4S-51F1 (SY4S-02F1) SFA-301 SFA-302

(Photo: RY4S-U)
9

2.6

Panel Mount Socket


27.5

SY4S-51 SY4S-61 SY4S-62

PRODUCT SERVICE

0.5

13

14

35.6 max.

6.4

21

SY4S-51F1 (SY4S-02F1) Note: (SY4S-02F1) is for the relay with check button.

PC Board Mount Socket

PC Board Terminal Type


0.8 2.6

RY2V-U/RY2V-UL/RY2V-UD

RY22V-U/RY22V-UL/RY22V-UD

0.5

27.5

7.15

12

(Photo: RY2V-U)

(Photo: RY22V-U)
35.6 max. 4

13 14

14

4.4

PRODUCT SERVICE

PRODUCT SERVICE

0.5

RY4V-U/RY4V-UL
0.8

2.6

14-1 holes

6.6

6.4
7.15
4.4 4.4 4.4
1 5 4 8 12 9 13 14

12.7
12.7 4.1

0.5

2 6

3 7

4 8

9 13

10 11 12 14

27.5

0.5

(Photo: RY4V-U)

PRODUCT SERVICE

35.6 max.

21

Top Bracket Mounting Type (Plug-in Terminal)


RY2S-UT RY22S-UT
3 1.2 oblong hole

43.2

6.3

0.5 4.1

2.6 4.4

3.5 14.5
PRODUCT SERVICE

2 35.6 max. 5.4

PRODUCT SERVICE

RY4S-UT

2.6

4.4

6.4

2.2 1.2 oblong hole

0.5

4.1

4.4

4.4

1 5

2 6 10

3 7 11

43.2

6.3

27.5

38

4 8 12 14

9 13

PRODUCT SERVICE

3.5 21.5

2 35.6 max. 6.4

6.4

All dimensions in mm.

27.5

38

6.4

4.1

8-1 holes

(04/10/25)

33

RR2KP Series Latch Relays


Self-maintained Latch Relays DPDT 10A contact capacity
The RR2KP series latch relays have a self-holding function using permanent magnets in the magnetic circuit. Applying a voltage on the set (or reset) coil operates the armature and retains the contacts in that position until the opposite coil is energized, hence the latch relays are ideal for memory and ip-op circuit applications. Enhanced self-holding functions, and vibration and shock resistance. The self-holding mechanism is not subject to wear unlike mechanical latch relays. Recognized by UL and certified by CSA.

Types
Terminal Style Pin Terminal Basic Type Type No. RR2KP-U Coil Voltage Code AC6, AC12, AC24, AC50, AC100, AC110, AC115, AC120, AC200, AC220, AC230, AC240 DC6, DC12, DC24, DC48, DC110

Ordering Information
When ordering, specify the Type No. and coil voltage code.
(Example) RR2KP-U AC110
Type No. Coil Voltage Code

With Check Button RR2KP-UC

Coil Ratings
Rated Current (mA) 15% at 20C Rated Voltage (V) 50Hz 6 12 24 50 AC (50/60Hz) 100 110 115 120 200 220 230 240 6 12 DC 24 48 110 467 200 100 48 24 23 23 24 12 10.9 11.1 11.5 240 120 60 30 13.8 60Hz 429 184 92 44 22 21 21 22 11 10 10.2 10.6 Coil Resistance () 10% at 20C 3.5 23.8 95 400 1,600 1,900 2,200 2,200 6,400 7,740 9,190 9,190 25 100 400 1,600 7,960 110% 80% maximum 110% 80% maximum Operation Characteristics (against rated values at 20C) Maximum Continuous Applied Voltage Set and Reset Voltage

Contact Ratings
Switching Voltage Continuous Current Maximum Contact Capacity Allowable Contact Power Resistive Load Inductive Load Voltage 110V AC 250V AC 125V DC 10A 1650 VA AC 1100 VA AC 300W DC 225W DC 220V AC 30V DC 100V DC Note: Inductive load for rated load cos - 0.3, L/R = 7 ms Rated Load Res. Load 10A 7.5A 10A 0.5A Ind. Load 7.5A 5A 7.5A 0.3A

UL Ratings
Voltage 240V AC 120V AC 30V DC Resistive 10A 10A 10A General Use 7A 7.5A 7A Motor Load 1/3 HP 1/4 HP

CSA Ratings
Voltage 240V AC 120V AC 100V DC 30V DC Resistive 10A 10A General Use 7A 7.5A 0.5A 7.5A Motor Load 1/3 HP 1/4 HP

10A

34

(04/10/25)

RR2KP Series Latch Relays


Specications
Contact Material Contact Resistance Operate Time Power Consumption (approx.) Insulation Resistance Silver 30 m maximum (initial value) 25 ms maximum (at the rated voltage) AC: 2.4 VA (50 Hz), 2.2 VA (60 Hz) DC: 1.5W 100 M minimum (500V DC megger) Between live and dead parts: 1,500V AC, 1 minute Between contact and coil: 1,500V AC, 1 minute Between contacts of different poles: 1,500V AC, 1 minute Between contacts of the same pole: 1,000V AC, 1 minute Electrical: 1800 operations/h maximum Mechanical: 18,000 operations/h maximum Coil: 85C maximum, Contact: 65C maximum 0 to 60 m/s2 (maximum frequency: 55 Hz), Frequency: 5 to 55 Hz, Amplitude: 0.5 mm 100 m/s2minimum 500,000 operations minimum (110V AC, 10A) 5,000,000 operations minimum 5 to +40C (no freezing) 45 to 85% RH (no condensation) 170g

Dimensions
Total length from panel surface including relay socket SR3P-05A: 105 (108.5) max., SR3P-511: 87.5 (92) max.

6 5 4 7 8

3 2 1 11 10

Dielectric Strength

80.5 max.

36 Dimensions in the ( ) include a hold-down spring.

Operating Frequency Temperature Rise Vibration Resistance Shock Resistance Electrical Life Mechanical Life Operating Temperature Operating Humidity Weight (approx.)

All dimensions in mm.

Applicable Socket and Hold-down Spring


Socket Mounting Style DIN Rail Mount Socket Panel Mount Socket w/Solder Terminals w/Wire Wrap Terminals Type No. SR3P-05A SR3P-05C SR3P-06A SR3P-511 SR3P-70 Hold-down Spring SR3P-06F3

SR3P-511F3

Characteristics (Reference Data)


Electrical Life Curve
AC Load
5000 5000

DC Load

Life ( 10,000 operations)

1000 500

220V AC resistive 110V AC inductive 220V AC inductive

Life ( 10,000 operations)

110V AC resistive

1000 500

30V DC resistive 30V DC inductive

100 50

100 50 100V DC resistive 100V DC inductive

10 0 1 2 3 4 5 6 7 8 9 10

10 0 1 2 3 4 5 6 7 8 9 10

Load Current (A)

Load Current (A)

Internal Connection (Bottom View)


6(+) 5 4 RESET 3 () () 2 1 11 9 SET 10 (+) 7 8

36

(04/10/25)

35

RH2L Series Latch Relays


Midget Power Latch Relays DPDT 10A contact capacity
The RH2L series latch relays have a self-holding function by residual magnetism generated by a special magnetic material. The large 10A contact capacity equivalent to the RH and RR series is provided in a miniature relay package as small as the IDECs RH3 type. With a mechanical operation indicator to show the set/reset status. Power saving operation by pulse inputs eliminates the need of continuous control voltage. Available with plug-in or PC board mount terminals. All basic types are recognized by UL and certified by CSA.

RH2LB-U (Blade Terminal)

RH2LV2-U (PC Board Terminal)

Ordering Information Types


Terminal Style Plug-in Terminal PC Board Terminal Type No. Coil Voltage Code RH2LB-U AC6, AC12, AC24, AC50, AC100, AC120 RH2LV2-U DC6, DC12, DC24

When ordering, specify the Type No. and coil voltage code.
(Example) RH2LB-U AC120
Type No. Coil Voltage Code

Coil Ratings
Set Coil Rated Voltage (V) 6 AC (50/60Hz) 12 24 50 100 120 6 DC 12 24 Rated Current (mA) 15% at 20C 50Hz 227 103 51.2 24.7 12.3 10.3 333 167 83 60Hz 220 100 50 24 12 10 Coil Resistance () 10% at 20C 18 72 288 Reset Coil Rated Current (mA) 15% at 20C 50Hz 68.7 34.2 17.1 10.4 4.6 4.2 150 75 37.5 60Hz 68 34 17 10.3 4.6 4.2 Coil Resistance () 10% at 20C 40 160 640 110% 80% maximum 110% 80% maximum Operation Characteristics (against rated values at 20C) Maximum Continuous Applied Voltage Set and Reset Voltage

Contact Ratings
Switching Continuous Voltage Current Maximum Contact Capacity Allowable Contact Power Resistive Load Inductive Load Rated Load Voltage Res. Load Ind. Load 7.5A 5A 7.5A

Specications
Contact Material Contact Resistance Set Time Reset Time Power Consumption (approx.) Insulation Resistance Motor Load 1/3 HP 1/6 HP Dielectric Strength Silver cadmium oxide 50 m maximum (initial value) 30 ms maximum (AC) 20 ms maximum (DC) (at the rated voltage) 30 ms maximum (AC) 20 ms maximum (DC) (at the rated voltage) Set coil: Reset coil: 1.2 VA (AC), 2W (DC) 0.5 VA (AC), 0.9W (DC)

250V AC 125V DC

10A

110V AC 10A 1650 VA AC 1100VA AC 220V AC 7.5A 300W DC 225W DC 30V DC 10A

Note: Inductive load for rated load cos = 0.3, L/R = 7 ms

100 M minimum (500V DC megger) Between live and dead parts: 2,000V AC, 1 minute Between contact and coil: 2,000V AC, 1 minute Between contacts of different poles: 1,500V AC, 1 minute Between contacts of the same pole: 1,000V AC, 1 minute Electrical: 1800 operations/h maximum Mechanical: 18,000 operations/h maximum 0 to 60 m/s2 (maximum frequency: 55 Hz), Frequency: 5 to 55 Hz, Amplitude: 0.5 mm 100 m/s2 minimum 200,000 operations minimum 10,000,000 operations minimum 5 to +40C (no freezing) 50g

UL Ratings
Voltage 240V AC 120V AC 30V DC Resistive 7.5A 10A 10A General Use 6.5A 7.5A

CSA Ratings
Voltage 240V AC 120V AC 30V DC Resistive 7.5A 10A 10A General Use 5A 7.5A 7.5A Motor Load 1/3 HP 1/6 HP Vibration Resistance Shock Resistance Electrical Life Mechanical Life Operating Temperature Weight (approx.) Operating Frequency

36

(04/10/25)

RH2L Series Latch Relays


Operation Indicator
Operation Indicator

Instructions
1. Do not use the RH2L relays in environments where magnetic particles and dust are present in large quantities or external magnetic eld is strong, or in the vicinity of largecurrent circuits. 2. Do not use the RH2L relays in circuits whose power source contains heavy surges. 3. When two or more RH2L relays are mounted in a row, separate the relays by 6 mm or more. 4. Do not energize the set and reset coils at the same time. 5. Because of the polarity of the coil, connect the DC input voltage to correct terminals of the DC coil type.

The red ag appears when the contacts are set.

Internal Connection (Bottom View)


1 5 9( ) 13( ) 2 6 10 SET RESET 4 8 (+)12 (+)14

Dimensions
RH2LB (Plug-in Terminal)
Total length from panel surface including relay socket SH3B-05A: 61.5 (63.5) max., SH3B-51: 39.6 (41.6) max. Dimensions in the ( ) include a hold-down spring.

2.6 hole

4.7

1 5 6 10

4 8
11

0.5

9 13

14

35.6 max.

6.4

31

RH2LV2 (PC Board Terminal)


10-2.4 holes 2 10 10 4.7
5 6 10 8 11 14 9 13

27.5

0.5

27.5

7.8

35.6 max.

0.5 4.6

31

All dimensions in mm.

Applicable Socket and Hold-down Spring


Socket Mounting Style DIN Rail Mount Socket Panel Mount Socket PC Board Mount Socket Type No. SH3B-05A SH3B-05C SH3B-51 SH3B-62 SH3B-05F1 SFA-101 SFA-202 SY4S-51F1 SFA-301 SFA-302 Hold-down Spring

For details about sockets and hold-down springs, see page 40.

7.25

13.15

(04/10/25)

37

RY2KS Series Latch Relays


Self-maintained Latch Relays DPDT 3A contact capacity
The RY2KS series latch relays have a self-holding function using permanent magnets in the magnetic circuit. Applying a voltage on the set (or reset) coil operates the armature and retains the contacts in that position until the opposite coil is energized, hence the latch relays are ideal for memory and ip-op circuit applications. Mountable in the same space as other miniature relays using the same sockets. Recognized by UL and certified by CSA.

Types
Terminal Style Plug-in Terminal Basic With Check Button Type Type No. RY2KS-U RY2KS-UC Coil Voltage Code AC6, AC12, AC24, AC50, AC100, AC120 DC6, DC12, DC24, DC48, DC100, DC110

Ordering Information
When ordering, specify the Type No. and coil voltage code.
(Example) RY2KS-U AC120
Type No. Coil Voltage Code

Coil Ratings
Rated Current (mA) 15% at 20C Rated Voltage (V) 50Hz 6 12 24 50 100 120 6 12 24 48 100 110 260 120 58 27 13.5 11.2 200 100 50 25 12 11 AC (50/60Hz) 60Hz 250 115 56 26 13 10.8 Coil Resistance () 10% at 20C 6.3 30.3 132 606 2,630 3,840 30 120 480 1,920 8,330 10,000 Operation Characteristics (against rated values at 20C) Maximum Continuous Set and Reset Voltage Applied Voltage

110%

80% maximum

110%

80% maximum

Contact Ratings
Switching Continuous Voltage Current Maximum Contact Capacity Allowable Contact Power Resistive Load 660VA AC 90W DC Inductive Load Rated Load Voltage 110V AC 250V AC 125V DC 3A 176VA AC 220V AC 45W DC 30V DC Res. Load 3A 3A 3A Ind. Load 1.5A 0.8A 1.5

DC

Specifications
Contact Material Contact Resistance Set Time Reset Time Power Consumption (approx.) Insulation Resistance Gold-plated silver 50 m maximum (initial value) 25 ms maximum (at the rated voltage) 25 ms maximum (at the rated voltage) AC: 1.6 VA (50 Hz), 1.5 VA (60 Hz) DC: 1.2W 100 M minimum (500V DC megger) Between live and dead parts: 1,500V AC, 1 minute Between contact and coil: 1,000V AC, 1 minute Between contacts of different poles: 1,000V AC, 1 minute Between contacts of the same pole: 700V AC, 1 minute Electrical: 1800 operations/h maximum Mechanical: 18,000 operations/h maximum Coil: 85C maximum, Contact: 65C maximum 0 to 60 m/s2 (maximum frequency: 55 Hz), Frequency: 5 to 55 Hz, Amplitude: 0.5 mm 200 m/s2 minimum 200,000 operations minimum 5,000,000 operations minimum 5 to +40C (no freezing) 67g

100V DC 0.2A 0.12A Note: Inductive load for rated load cos = 0.3, L/R = 7 ms Dielectric Strength Resistive 3A 3A 3A General Use 0.8A 1.5A Temperature Rise Vibration Resistance Resistive 3A 3A 3A General Use 0.8A 1.5A 0.2A 1.5A Shock Resistance Electrical Life Mechanical Life Operating Temperature Weight (approx.) Operating Frequency

UL Ratings
Voltage 240V AC 120V AC 30V DC

CSA Ratings
Voltage 240V AC 120V AC 100V DC 30V DC

38

(04/10/25)

RY2KS Series Latch Relays


Characteristics (Reference Data)
Electrical Life Curve
AC Load
5000 5000 30V DC resistive

DC Load

Life ( 10,000 operations)

Life ( 10,000 operations)

1000 500 110V AC resistive 220V AC resistive

1000 500

30V DC inductive

100 50 110V AC inductive 220V AC inductive 2 3

100 50 100V DC resistive 100V DC inductive 1 2

10 0 1

10 0

Load Current (A)

Load Current (A)

Internal Connection (Bottom View)


1 5 9( ) 10 13( ) 4 8 11 ( + )12 ( + )14

SET RESET

Dimensions
Total length from the panel surface including relay socket SY4S-05A: 81.3 (83.3) max., SY4S-51: 59.3 (62.3) max. 2.6 Dimensions in the ( ) include a hold-down spring. 2.2 1.2 oblong hole

1 5

4 8 10 11 12 14

9 13

55.3 max.

6.4

21 All dimensions in mm.

Applicable Socket and Hold-down Spring


Socket Mounting Style DIN Rail Mount Socket Panel Mount Socket Type No. SY4S-05A SY4S-05C SY4S-51 SY4S-61 PC Board Mount Socket SY4S-62 SFA-202 SY4S-51F3 (SY4S-02F3) SFA-302 SY4S-51F3 (SY4S-02F3) Hold-down Spring

Notes: 1. For the relays with check button, use the parenthesized holddown springs shown in the above table. When the spring is used, sockets cannot be mounted closely side by side. 2. Leaf springs come in pairs. 3. Use the hold-down springs in environments where the relays are subject to vibrations or shocks. For details about sockets and hold-down springs, see page 40.

27.5

0.5

(04/10/25)

39

Relay Sockets
Socket Selection Guide
Mounting Style Series Type No. SR2P-05A SR2P-05C SR2P-06A SR SR3P-05A SR3P-05C SR3P-06A SR3B-05A SH1B-05A SH1B-05C SH2B-05A SH2B-05C SH SH2B-05D SH3B-05A SH3B-05C DIN Rail Mount SH4B-05A SH4B-05C SM2S-05A SM SM2S-05C SM2S-05D SY2S-05A SY2S-05C SY SY4S-05A SY4S-05C SY4S-05D SU2S-11L SU SU4S-11L SR2P-511 SR2P-70 SR SR3P-511 SR3P-70 SR3B-51 Panel Mount SH1B-51 SH SH2B-51 SH3B-51 SH4B-51 SM SY SM2S-51 SY2S-51 SY4S-51 SH1B-62 SH PC Board Mount SH2B-62 SH3B-62 SH4B-62 SM SM2S-61 SM2S-62 SY2S-61 SY SY4S-61 SY4S-62 PC board PC board PC board Solder Solder Solder Spring-clamp Solder Wire-wrap Solder Wire-wrap Solder 1 2 3 4 2 2 4 1 2 3 4 2 2 4 Black Black Black Black Black 3 4 2 Black Type Standard Finger-safe Standard Standard Finger-safe Standard Standard Standard 1 Finger-safe Standard Finger-safe Slim Standard Finger-safe Standard Finger-safe Standard Finger-safe Slim Standard Finger-safe Standard Finger-safe Slim Spring-clamp 2 Gray 4 2 2 3 4 2 3 3 2 No. of Color Poles Black Gray Black Black Gray M3.5 2 Black 2 mm max. Black Black M3.5 (coil terminal: M3) Gray 2 mm2 max. Black Gray Black Black Gray Black Gray Black Gray Black Black M3 2 Black 2 mm max. Gray Black M3, 1.25 mm2 (2 mm2 max.) Solid wire: 0.2 to 1.5 mm2 Stranded wire: 0.2 to 1.25 mm2 Gray M3 2 mm2 max. M3, 1.25 mm (2 mm2 max.)
2

Terminal Screw Applicable Wire M3.5 2 mm2 max.

Approvals UL, CSA, TV UL, CSA, TV UL, CSA, TV UL, CSA, TV

Rated Insulation Voltage/ Rated Current 250V, 10A

Applicable Relay, etc.

Page

RR2P, GT3 (8-pin), GT5P 43 RR3P, RR3PA, RR2KP, GT3 (11-pin) RR1BA, RR2BA, RR3B

250V, 10A

250V, 10A RH1B (coil terminal: 7A)

44

RH2B 250V, 10A 45

M3.5 2 mm2 max.

UL, CSA, TV UL, CSA, TV UL, CSA, TV UL, CSA, TV UL, CSA, TV

RH3B, RH2LB RH4B

250V, 7A 250V, 7A (UL, TV: 10A) 250V, 10A RY2S, RY22S 250V, 7A 47 RY4S, RY2KS, RU4S, RU42S, GT5Y-U 250V, 6A 250V, 10A RU2S, RM2S, GT5Y-2 RU4S, RU42S, RY4S, GT5Y-4 RR2P, GT3 (8-pin), GT5P 250V, 10A RR3P, RR3PA, RR2KP, RR1BA, RR2BA, RR3B 250V, 10A RH1B (coil terminal: 7A) RH2B 250V, 10A 250V, 10A 250V, 7A 250V, 7A (Note) RH3B, RH2LB RH4B RM2S, RU2S, GT5Y-2 RY2S, RY22S RY4S, RY2KS, RU4S, RU42S, GT5Y-U 50 49 RM2S, RU2S, GT5Y-2 46

UL, CSA, CE 250V, 6A UL, CSA UL, CSA UL, CSA UL, CSA UL, CSA UL, CSA UL, CSA UL, CSA UL, CSA UL, CSA UL, CSA UL, CSA UL, CSA UL, CSA UL, CSA UL, CSA UL, CSA UL, CSA UL, CSA 250V, 10A 250V, 7A 250V, 7A (Note) 250V, 7A 250V, 10A

48

250V, 10A RH1B (coil terminal: 7A) RH2B RH3B, RH2LB RH4B RM2S, RU2S, GT5Y-2 RM2S, RU2S RY2S, RY22S RY4S, RY2KS, RU4S, RU42S, GT5Y-U 52 51

Note: When using only 2 poles of the 4-pole sockets SY4S-51 and SY4S-61, the UL rated current is 10A.

Terminal Screw Tightening Torque for DIN Rail Mount Sockets


Socket Series SR SH Terminal Screw Tightening Torque 1.0 to 1.3 Nm 1.0 to 1.3 Nm Socket Series SM SY Terminal Screw Tightening Torque 0.6 to 1.0 Nm 0.6 to 1.0 Nm

40

(04/10/25)

Relay Sockets
Sockets and Applicable Hold-down Springs
DIN Rail Mount Sockets
Socket Type No. SR2P-05A SR2P-05C SR2P-06A SR3P-05A SR3P-05C Applicable Relays and Timers RR2P GT5P RR2P GT3 (8-pin), GT5P RR3P, RR3PA RR2KP GT3 (11-pin) RR3P, RR3PA SR3P-06A SR3B-05 SH1B-05A SH1B-05C SH2B-05A SH2B-05C SH2B-05D SH3B-05A SH3B-05C SH4B-05A SH4B-05C SM2S-05A SM2S-05C SM2S-05D SY2S-05A SY2S-05C SY4S-05A SY4S-05C SY4S-05D RR2KP GT3 (11-pin) RR1BA, RR2BA, RR3B RH1B RH2B RH2B-R RH2B RH2B-R RH3B, RH2LB RH4B RM2S, RU2S GT5Y-2 RM2S, RU2S GT5Y-2 RY2S, RY22S RY4S, RU4S, RU42S RY2KS, GT5Y-4 RY4S, RU4S, RU42S RY2KS, GT5Y-4 RU2S, RM2S GT5Y-2 SU4S-11L RU4S, RU42S, RY4S GT5Y-4 Hold-down Spring Wire Spring SR2B-02F1 SR2B-02F1 SR3B-02F1 SR3P-06F3 SR3B-02F1 SR3P-06F3 SR3B-02F1 SY2S-02F1 SY4S-02F1 SH3B-05F1 SH4B-02F1 SY4S-02F1 SY2S-02F1 SY4S-02F1 Leaf Spring SFA-203 SFA-202 SFA-202 SFA-203 SFA-202 SFA-202 SFA-202 SFA-101 SFA-202 SFA-101 SFA-202 SFA-202 SFA-502 SFA-511 SFA-101 SFA-202 SFA-101 SFA-202 SFA-101 SFA-202 SFA-202 SFA-502 SFA-511 SFA-101 SFA-202 SFA-101 SFA-202 SFA-202 SFA-502 SFA-511 SFA-101 SFA-202 SFA-202 SFA-101 SFA-202 SFA-202 SY4S-62 RY2KS SY4S-51 SY4S-61 SM2S-51 SM2S-61 SM2S-62 SY2S-51 SY2S-61 SH2B-51 SR3B-51 SH1B-51 SH1B-62 SR3P-511 SR3P-70 SR2P-511 SR2P-70

Panel Mount Sockets and PC Board Mount Sockets


Socket Type No. Applicable Relays and Timers RR2P GT3 (8-pin) GT5P RR3P, RR3PA RR2KP GT3 (11-pin) RR1BA, RR2BA, RR3B RH1B RH2B RH2B-R SH2B-62 SH3B-51 SH3B-62 SH4B-51 SH4B-62 RH2B RH3B, RH2LB RH4B RM2S, RU2S GT5Y-2 RM2S, RU2S RY2S, RY22S RY4S, RU4S, RU42S RY2KS GT5Y-4 RY4S, RU4S, RU42S Hold-down Spring Wire Spring SR3P-01F1 SR3P-01F1 SR3P-511F3 SR3B-02F1 SY4S-51F1 SY4S-51F1 (SY4S-02F1) SY4S-51F1 (SY4S-02F1) SY4S-51F1 (SH3B-05F1) SY4S-51F1 2 (SH4B-02F1) SY4S-51F1 (SY4S-02F1) SY4S-51F1 (SY4S-02F1) SY4S-51F1 SY4S-51F1 (SY4S-02F1) SY4S-51F3 (SY4S-02F3) SY4S-51F1 (SY4S-02F1) SY4S-51F3 (SY4S-02F3) Leaf Spring SFA-402 SFA-302 SFA-402 SFA-301 SFA-302 SFA-301 SFA-302 SFA-302 SFA-301 SFA-302 SFA-301 SFA-302 SFA-301 SFA-302 SFA-302 SFA-301 SFA-302 SFA-301 SFA-302 SFA-302 SFA-302

SU2S-11L

Note 1: When mounting relays with check button on panel mount or PC board mount sockets, use hold-down springs shown in ( ). Hold-down springs for relays with check button are not available for SR2P-511, SR2P-70, SR3P-511, and SR3P-70. Note 2: For close mounting of panel mount or PC board mount sockets, use wire springs or SFA-302 leaf springs. Note 3: SM2S-62 and SY4S-62 sockets cannot be used on GT5Y-2 and GY5Y-4 timers.

Hold-down Springs
Type Type No. SR2B-02F1 SR3B-02F1 SR3P-01F1 SR3P-06F3 Wire Spring SH3B-05F1 SH4B-02F1 SY2S-02F1 SY4S-02F1 SY4S-02F3 SY4S-51F1 SY4S-51F3 SFA-101 SFA-202 SFA-203 Leaf Spring SFA-301 SFA-302 SFA-402 SFA-502 SFA-511 Ordering Type No. SR2B-02F1PN10 SR3B-02F1PN10 SR3P-01F1PN10 SR3P-06F3PN10 SH3B-05F1PN10 SH4B-02F1PN10 SY2S-02F1PN10 SY4S-02F1PN10 SY4S-02F3PN10 SY4S-51F1PN10 SY4S-51F3PN10 SFA-101PN20 SFA-202PN20 SFA-203PN20 SFA-301PN20 SFA-302PN20 SFA-402PN20 SFA-502PN20 SFA-511PN20 SFA-301 SFA-302 SFA-402 SFA-502 SFA-511 20 (10 pairs) SY4S-51F1 SY4S-51F3 SFA-101 SFA-202 SFA-203 SH3B-05F1 SH4B-02F1 SY4S-02F1 SY2S-02F1 SY4S-02F3 SR2B-02F1 SR3B-02F1 SR3P-01F1 SR3P-06F3 SR3P-511F3 Package Quantity

SR3P-511F3 SR3P-511F3PN10 10

(04/10/25)

41

Relay Sockets
Accessories for Sockets
Name Appearance Specications Type No. Ordering Type No. BAA1000PN10 BAP1000PN10 Package Quantity 10 10 Remarks Aluminum BAA1000 Weight: Approx. 200g Steel BAP1000 Weight: Approx. 320g BNL5 Mounting Clip Zinc-plated steel Weight: Approx. 15g BNL6 BNL6PN10 10 Thickness: 5 mm Used for adjusting spacing between sockets mounted on a DIN rail

DIN Rail

Length: 1m Width: 35 mm

BNL5PN10

10 Used on a DIN rail to fasten relay sockets

DIN Rail Spacer

Plastic (black)

SA-406B

SA-406B

End Spacer Plastic (black) Intermediate Spacer

SA-203B

SA-203B

SA-204B

SA-204B

Used for mounting DIN rail mount sockets directly on a panel surface

Accessories for SU Sockets


Name Appearance Specications Type No. Ordering Type No. Package Quantity Remarks

2.5

Screwdriver

75 145

Weight: Approx. 20g

BC1S-SD0

BC1S-SD0

Used for wiring spring-clamp terminals on the SU sockets Used for interconnecting relay coil terminals on a maximum of ve SU sockets; can be cut to required lengths A1: A2: + A1: + A2: For absorbing surge voltages in DC coils

Jumper

Brass jumper with ABS sheath Rated current: 3A Weight: Approx. 3g

SU9Z-J5

SU9Z-J5PN10

10

SU9Z-D11 Diode Module 6 to 220V DC SU9Z-D12

SU9Z-D11PN10 SU9Z-D12PN10

10 10

RC Module

6 to 240V AC

SU9Z-R21

SU9Z-R21PN10

10

For absorbing surge voltages in AC coils

6 to 12V AC/DC LED Module 24 to 48V AC/DC 100 to 120V AC/DC 200 to 240V AC/DC

SU9Z-L31 SU9Z-L32 SU9Z-L33 SU9Z-L34

SU9Z-L31PN10 SU9Z-L32PN10 SU9Z-L33PN10 SU9Z-L34PN10

10 10 10 10 Non-polarized LED indicator; goes on when the relay coil is energized

42

(04/10/25)

Relay Sockets
DIN Rail Mount Sockets
SR Series
SR2P-05A
36 8 M3.5 Terminal Screw When using BAA/BAP: 32 DIN Rail (BAA/BAP) 2-4.2 Mounting Holes (or M4 Tapped Holes) 25 52 33

Terminal Arrangement
5 6 4 3

29 4.4 max. 16.5 5 min.

7 8

2 1

4.2 hole 3 29 20 28.5

(Top View)

7.9 max. 3.6 min.

SR2P-05C

36 7

When using BAA/BAP: 33.5

DIN Rail (BAA/BAP) 2-4.2 Mounting Holes (or M4 Tapped Holes)

Terminal Arrangement
5 6 4 3

58

29 4.2 hole
7 8 2 1

2.2

29

21.5 30

Ring type crimping terminals cannot be used.

(Top View)

PRODUCT SERVICE

SR2P-06A

40 8 M3.5 Terminal Screw 25

When using BAA/BAP: 25.5

DIN Rail (BAA/BAP) 2-4.2 Mounting Holes (or M4 Tapped Holes)

Terminal Arrangement
6 5 4 3

60

33 4.9 max. 18 22 7.9 max. 3.6 min. 5 min.


7 8 1 2

4.2 hole 33 1

(Top View)

SR3P-05A

42 8 M3.5 Terminal Screw

When using BAA/BAP: 32

DIN Rail (BAA/BAP Types) 2-4.2 Mounting Hole (or M4 Tapped Holes)

Terminal Arrangement
7 8 6 5 4

27

52

33

34 4.4 max. 16.5 20 28.5 7.9 max. 3.6 min. 5 min.

9 10 11 1

3 2

4.2 hole 34 3

(Top View)

SR3P-05C

42 7
5

When using BAA/BAP: 33.5

DIN Rail (BAA/BAP) 2-4.2 Mounting Holes (or M4 Tapped Holes)

Terminal Arrangement
7 8 6 5 4

58

4.2 hole

34

9 10 11 1

3 2

(Top View)
2.2 34 21.5 30

PRODUCT SERVICE

Ring type crimping terminals cannot be used.

(04/10/25)

43

Relay Sockets
SR3P-06A
59 8 M3.5 Terminal Screw When using BAA/BAP: 25.5 DIN Rail (BAA/BAP)

Terminal Arrangement
2-4.2 Mounting Holes (or M4 Tapped Holes)
8 7 6 5 4

27

60

33 4.9 max. 18 22 7.9 max. 3.6 min. 5 min.


9 10 11 1 2 3

4.2 hole 33 1

(Top View)

SR3B-05

36 8 M3.5 Terminal Screw 4.2

When using BAA/BAP: 28.5

DIN Rail (BAA/BAP) 2-4.2 Mounting Holes (or M4 Tapped Holes) 37

Terminal Arrangement
6 3 5 2 4 1

76

56

A 8

4.4 max.

5.5 min.

(Top View)
PRODUCT SERVICE

37 43

14.5 25

7.9 max. 3.6 min.

SH Series
SH1B-05A
17 8 M3.5 Terminal Screw 4.2 When using BAA/BAP: 28.5 18 DIN Rail (BAA/BAP) 2-4.2 Mounting Holes (or M4 Tapped Holes)

Terminal Arrangement
5 1

67

47

16 5.5 min. 4.4 max. 14.5 25 7.9 max. 5.9 max. 4.8 min. 4 max. 3.6 min. 3.2 min.
14 13

M3 Terminal Screw 16 2.5 20

(Top View)

(For terminals 1, 5, and 9)

(For terminals 13 and 14)

SH1B-05C
17 7 M3.5 Terminal Screw
5

When using BAA/BAP: 33 25 DIN Rail (BAA/BAP) 2-4.2 Mounting Holes (or M4 Tapped Holes) 48

Terminal Arrangement
5 1

69

4.2

16 M3 Terminal Screw 16 1.7 20 18.7 29.5


14 13

9
PRODUCT SERVICE

Ring type crimping terminals cannot be used.

(Top View)

SH2B-05A
22 8 M3.5 Terminal Screw 4.2

When using BAA/BAP: 28.5 18 DIN Rail (BAA/BAP) 2-4.2 Mounting Holes (or M4 Tapped Holes)

Terminal Arrangement
8 4 5 1

67

47

26 4.4 max. 5.5 min.


14 12 13

26 2.5 30

14.5 25

7.9 max. 3.6 min.

(Top View)

44

(04/10/25)

Relay Sockets
SH2B-05C
22 7 M3.5 Terminal Screw
5

When using BAA/BAP: 33 25 DIN Rail (BAA/BAP) 2-4.2 Mounting Holes (or M4 Tapped Holes) 49

Terminal Arrangement
8 4 5 1

69

4.2

26
14 12 13

PRODUCT SERVICE

26 30

18.7 29.5

SH2B-05D

1.7

Ring type crimping terminals cannot be used.

(Top View)

28 6.7

When using M3.5 Terminal BAA/BAP: 34.5 Screw 19.5

DIN Rail (BAA/BAP)

2-M3 or M4 (or 4.5 Mounting Holes)

Terminal Arrangement
4 1 8 5

4.3 max. 68 78 57 68

5.8 min.

6.6 max. 3.6 min. 4.5 19 30 When using BAA/BAP: 28.5 8 M3.5 Terminal Screw 4.2 18 DIN Rail (BAA/BAP) 2-4.2 Mounting Holes (or M4 Tapped Holes) 8 19

12 14 13

(Top View)

SH3B-05A
32

Terminal Arrangement
8 4 6 2 5 1

67

47

36 4.4 max. 5.5 min.


14 12 10 13

2.5

36 40

14.5 25

(Top View)
7.9 max. 3.6 min.

SH3B-05C

32 7

M3.5 Terminal Screw

When using BAA/BAP: 33 25 DIN Rail (BAA/BAP) 2-4.2 Mounting Holes (or M4 Tapped Holes)

Terminal Arrangement
8 4 6 2 5 1

5
4.2

69

49

36
14 12 10 13

1.7

PRODUCT SERVICE

36 40

18.7 29.5

Ring type crimping terminals cannot be used.

(Top View)

SH4B-05A
42 8 M3.5 Terminal Screw 4.2

When using BAA/BAP: 28.5 18 DIN Rail (BAA/BAP) 2-4.2 Mounting Holes (or M4 Tapped Holes)

Terminal Arrangement
8 4 7 3 6 2 5 1

67

47

46 4.4 max. 5.5 min.


14 12 11 10 13

46 2.5 50

14.5 25

(Top View)
7.9 max. 3.6 min.

(04/10/25)

45

Relay Sockets
SH4B-05C
42 7
When using BAA/BAP: 33

25
DIN Rail (BAA/BAP)
5
4.2

Terminal Arrangement
8 4 7 3 6 2 5 1

2-4.2 Mounting Holes (or M4 Tapped Holes)


49

69

46
14 12 11 10 13

PRODUCT SERVICE

1.7

46 50

18.7 29.5

Ring type crimping terminals cannot be used.

(Top View)

SM Series
SM2S-05A
30 When using BAA/BAP: 28.5 6 M3 Terminal Screw 18 DIN Rail (BAA/BAP) 2-4.2 Mounting Holes (or M4 Tapped Holes)

0.7

Terminal Arrangement
8 4 5 1

62

45

26

4.2

4 max. 18.5

4.8 min.

14 12

13 9

(Top View)
5.9 max. 3.2 min.

26

25

SM2S-05C

30 6 M3 Terminal Screw
5.5

When using BAA/BAP: 32.5 25 18

DIN Rail (BAA/BAP)

Terminal Arrangement
2-4.2 Mounting Holes (or M4 Tapped Holes)
8 4 5 1

64

4.2

46

26

14

13 9

1.6

PRODUCT SERVICE

26

18.2 29

Ring type crimping terminals cannot be used.

12

(Top View)

SM2S-05D
22 6

When using BAA/BAP: 33.5 18.4 M3 Terminal Screw

DIN Rail (BAA/BAP)

2-M3 or M4 (or 4.5 Mounting Holes)

Terminal Arrangement
4 8 1 5

3.7 max.

5.3 min.

69.5 59

52

59

5.9 max. 3.2 min.


12 14 13 9

4.5 15 30

15

(Top View)

46

(04/10/25)

Relay Sockets
SY Series
SY2S-05A
17 6 M3 Terminal Screw 18 When using BAA/BAP: 28.5 DIN Rail (BAA/BAP) 2-4.2 Mounting Holes (or M4 Tapped Holes)

Terminal Arrangement
8 4 5 1

62

45

16 4 max. 14.5 25 5.9 max. 3.2 min. 4.8 min.


14 12 13

4.2

16 20 2

(Top View)

SY2S-05C
17.2 6 M3 Terminal Screw

When using BAA/BAP: 32.5 25 DIN Rail (BAA/BAP)

Terminal Arrangement
2-4.2 Mounting Holes (or M4 Tapped Holes)
8 4 5 1

5
4.2 16

64

46

14 12

13

1.6

16 20 2

18.2 29

Ring type crimping terminals cannot be used.

(Top View)

PRODUCT SERVICE

SY4S-05A
0.7

30 6 M3 Terminal Screw

When using BAA/BAP: 28.5 18 DIN Rail (BAA/BAP) 2-4.2 Mounting Holes (or M4 Tapped Holes)

Terminal Arrangement
8 4 7 6 3 2 5 1

62

45

26 4 max. 4.8 min.


14 13

4.2

12 11 10 9

18.5 26 25 3

5.9 max. 3.2 min.

(Top View)

SY4S-05C
30 6 M3 Terminal Screw

When using BAA/BAP: 32.5 25 18 DIN Rail (BAA/BAP) 2-4.2 Mounting Holes (or M4 Tapped Holes)

Terminal Arrangement
8 4 7 6 3 2 5 1

5.5
4.2

64

46

26
14 13

12 11 10 9

PRODUCT SERVICE

1.6

26 2

18.2 29

Ring type crimping terminals cannot be used.

(Top View)

SY4S-05D
29 6 M3 Terminal Screw

When using BAA/BAP: 33.5 18.4 DIN Rail (BAA/BAP)

2-M3 or M4 (or 4.5 Mounting Holes)

Terminal Arrangement
3 8 7 2 6 1 5

3.7 max. 69.5 59 52 59

5.3 min.

5.9 max. 3.2 min. 5 4.5 22 30 6 22


12 4 11 14 10 13 9

(Top View)

(04/10/25)

47

Relay Sockets
SU Series
SU2S-11L
31

Terminal Arrangement
12 11 10 8 7 3 6 2 9 5 1

24.0 80

2-3.2 Mounting Holes

28.8

37.5

14

13

32 35.3 31

Ring type crimping terminals cannot be used.

SU4S-11L

4.4

(Top View)

Terminal Arrangement
12 11 10 8 7 3 6 2 9 5 1

24.0 80

2-3.2 Mounting Holes

28.8

37.5

14

13

32 35.3

Ring type crimping terminals cannot be used.

Panel Mount Sockets


SR Series
Panel Surfarface

SR2P-511
4.2 6

4.4

(Top View)

2-3.5 Mounting Holes (or M3 Tapped Holes)

Terminal Arrangement

29

38

50

2 1 8

34

2.5

10 11 2.5

(Bottom View)

Panel Surfarface

SR2P-70
4.2 6

2-3.5 Mounting Holes (or M3 Tapped Holes

Terminal Arrangement

29

38

50

2 1 8

34

2.5

10 17.5 2.5

(Bottom View)

Panel Surfarface

SR3P-511
4.2 6

2-3.5 Mounting Holes (or M3 Tapped Holes)

Terminal Arrangement

5 6 7

29

38

50

3 2 1 11

9 10

34

2.5

10 11 2.5

(Bottom View)

48

38

3 0

38

3 0

38

3 0

(04/10/25)

Relay Sockets
Panel Surfarface

SR3P-70
4.2 6

2-3.5 Mounting Holes (or M3 Tapped Holes)

Terminal Arrangement

5 6 7

29

38

50

3 2 1 11

9 10

34

2.5

10 17.5 2.5

(Bottom View)

SR3B-51
38 7.5 11 max.

Terminal Arrangement
1 4 7 A 2 5 8 3 6 9 B

6.75 11.5 min.

35.5 22

2-4.2 Mounting Holes (M4 Tapped Holes)

0.3

51.5

22

6.5

(Bottom View)

3.5
PRODUCT SERVICE

35

When two or more sockets are mounted side by side: L = 38 (N 1) + 35.5 N: No. of sockets mounted

SH Series
SH1B-51
Panel Thickness: 1 to 2 [18 (N1) + 12.4] +0.5 0

Terminal Arrangement
25.6 +0.2 0 1 5 9 13 14

0.3

25.4

31

11 18.7 3.5 2.4 12.2

SH2B-51

5.4 min.

18

(Bottom View)

N: No. of sockets mounted

10.4 min. when using hold-down springs

Panel Thickness: 1 to 2

[27 (N1) + 21.4]

Terminal Arrangement 1 4 5 8 9 12
13 14
+0.2 0

25.4

11 18.7 3.5 21.2

SH3B-51

5.4 min.

27

0.3

25.6

31

(Bottom View)

N: No. of sockets mounted

10.4 min. when using hold-down springs

Panel Thickness: 1 to 2

[36 (N1) + 30.4] +0.5 0

Terminal Arrangement 1 2 4 5 6 8 9 10 12
13 14

0.3

25.4

25.6

31

+0.2 0

11 18.7 3.5 30.2

10.4 min. when using hold-down springs

5.4 min.

36

(Bottom View)

N: No. of sockets mounted

32.5 43 (Tolerance 0.3)


+0.5 0

35 43

32

38

3 0

(04/10/25)

49

Relay Sockets
SH4B-51
Panel Thickness: 1 to 2 [45 (N1) + 39.4] +0.5 0

Terminal Arrangement 1 2 3 4 5 6 7 8 9 10 11 12
13 14

25.4

0.3

25.6

31

+0.2 0

11 18.7 3.5 39.2

10.4 min. when using hold-down springs

SM Series
SM2S-51
Panel Thickness: 1 to 2 [27 (N1) + 21.4] +0.5 0

Terminal Arrangement 1 5 9
13

25.4

31

4 8
12 1 4

0.3

25.6 +0.2 0

5.4 min.

45

(Bottom View)

N: No. of sockets mounted

(Bottom View)

11 18.7 2.4 21.2

SY Series
SY2S-51
Panel Thickness: 1 to 2 [18(N1)+12.4] +0.5 0

Terminal Arrangement
1 4 5 8 9 12
13 14

25.4

31

11 18.7 2.4 12.2

SY4S-51

Panel Thickness: 1 to 2

5.4 min.

18

0.3

25.6

+0.2

5.4 min.

27

N: No. of sockets mounted

10.4 min. when using hold-down springs

(Bottom View)

N: No. of sockets mounted

10.4 min. when husing hold-down springs

[27 (N1) + 21.4] + 0.5 0

Terminal Arrangement 1 2 3 4 5 6 7 8 9 10 11 12
13 14
+0.2

25.4

31

11 18.7

2.4 21.2

50

5.4 min.

27

0.3

(Bottom View)

25.6

N: No. of sockets mounted

10.4 min. when using hold-down springs

(04/10/25)

Relay Sockets
PC Board Mount Sockets
SH Series
SH1B-62
Terminal Arrangement
1 5 9
13 14

3-2.4 holes 4.7 6.95

6.8 4.4

18 min.

25.4

31

18

3 11 15 2 1.5

(Bottom View)

11.85 31 min. 5.95

0.3

2-2 holes

12.2

36 min. when using hold-down springs

(Tolerance 0.1)

SH2B-62
25.4 29

Terminal Arrangement
1 4 5 8 9 12
13 14

2.85 5.65 15.5 10

21.5 min.

0.3

21.2

11 15

29 min. 12.5

(Bottom View)

4.7

6.6

8-2.4 holes

34 min. when using hold-down springs

(Tolerance 0.1)

SH3B-62
25.4 31

Terminal Arrangement
1 2 4 5 6 8 9 10 12
13 14

36 min. 7.35 4.7 21.3 10 10

0.3

36

3 11 15 2

(Bottom View)

12.5 6.65 31 min. 6.6

11-2.4 holes

30.2

36 min. when using hold-down springs

(Tolerance 0.1)

SH4B-62
Terminal Arrangement
1 2 3 4 5 6 7 8 9 10 11 12
13 14

6.85 4.7 6.65

45 min. 31.3 10 10 10

11 15 2 39.2 36 min. when using hold-down springs

31 min.

12.5 6.6

45

0.3

25.4

31

(Bottom View)

14-2.4 holes (Tolerance 0.1)

SM Series
SM2S-61
Terminal Arrangement
1 5 9 13 4 8 12 1 4 25.4 10.4 4.1 13.2 13.8 min.

31

11 15 1.5 21.2

14.2 min.

27

0.3

(Bottom View)

16.8

9-2 holes 1.4 (Tolerance 0.1)

19.2 min. when using hold-down springs

(04/10/25)

51

Relay Sockets
SM2S-62
Terminal Arrangement
1 5 9 13 4 8 12 14 16.8 10.4 0.3 29 4.1
13.2

8.2 min.

21.2

3 11 15

(Bottom View)
12.2 min.

1.4

9-2 holes (Tolerance 0.1)

1.5

17.2 min. when using a hold-down spring. 13.2 min. when using a hold-down spring for the relay with check button.

SY Series
SY2S-61
Terminal Arrangement
25.4 1 4 5 8 9 12 13 14 0.3 18 3 11 15 1.5 12.2 10.4 4.4 4.1 13.6 min.

(Bottom View)

14.2 min.

16.8

31

8-2 holes (Tolerance 0.1)

19.2 min. when using hold-down springs

SY4S-61
8.8 10.4 4.1

13.2

13.8 min. 4.4

Terminal Arrangement
1 2 3 4 5 6 7 8 9 10 1112 13 14 25.4 31 16.8

9 15-2 holes (Tolerance 0.1)


13.2 8.8 4.4

27

3 11 15 1.5

(Bottom View)

14.2 min.

0.3

19.2 min. when using hold-down springs

21.2

SY4S-62
Terminal Arrangement
1 2 3 4 5 6 7 8 9 10 1112 13 14 16.8 10.4 0.3 29 4.1

1.4

8.2 min.

21.2

3 11 15

(Bottom View)
12.2 min.

1.4

15-2 holes (Tolerance 0.1)

1.5

17.2 min. when using a hold-down spring. 13.2 min. when using a hold-down spring for the relay with check button.

52

(04/10/25)

Relay Sockets
Accessories
DIN Rails
Material Aluminum Steel Type No. BAA1000 BAP1000 Ordering Type No. BAA1000PN10 BAP1000PN10 Package Quantity 10 10

BAA/BAP

BAA

BAP
5.5

12.5 12.5

1.7

The BAA is a 35-mm-wide DIN rail made of durable extruded aluminum. The BAP is a 35-mm-wide DIN rail made of rust proof sheet steel.

Mounting Clip
Application Example of Mounting Clip and DIN Rail Spacer
9-mm wide

Use DIN rail spacers for adding space between adjoining sockets to prevent miswiring and identify wiring groups.
BNL5
9-mm wide

BNL6

Use of the BNL5 or BNL6 mounting clip is recommended at the both ends of the socket row mounted on the DIN rail to prevent the sockets from moving sideways.
Type No. BNL5 BNL6 Ordering Type No. BNL5PN10 BNL6PN10 Package Quantity 10 10
DIN Rail (BAA/BAP)

10 mm Two spacers

5 mm Two spacers

10 mm Two spacers

Installation of Mounting Clip and DIN Rail Spacer

DIN Rail Spacer

Mounting Clip BNL5

Spacers of 5-mm thick are designed to provide spacing between DIN rail mount sockets when mounted on 35-mm wide DIN rails. The spacers snap on and off the rail like sockets.
Type No. SA-406B Package Quantity 1 Color Black

BAA:31 BAP:27 7.5

35

25

Spacer SA-406B

(04/10/25)

53

Relay Sockets
Surface Mounting of DIN Rail Mount Socket
End Spacer
Type No. SA-203B Package Quantity Color 1 Black Collective Mounting Single Mounting
For saving the need for screw tightening and drilling

Intermediate Spacer
Type No. SA-204B Package Quantity Color 1 Black
SA-204B SA-203B SA-203B

The end spacer and intermediate spacer are used for mounting DIN rail mount sockets on panel surfaces. In collective mounting using these spacers, screws can be eliminated at every other socket. Mounting centers are the same in single mounting and collective mounting.
Note: DIN rail mount sockets can also mount directly on panel surfaces without using these spacers, then the mounting centers are different from when using spacers.

18 mm 5 mm Hold-down Spring

M4 Screw Plain Washer

Socket
4.2 Mounting Holes or M4 Tapped Holes

A (mm) 44 21 31 41 51 31 21 31

SR3B-05A SH1B-05A SH2B-05A SH3B-05A SH4B-05A SM2S-05A SY2S-05A SY4S-05A

Collective Mounting of Panel Mount Sockets


The SY, SM, and SH series panel mount sockets are designed to mount in panel cut-outs collectively. These sockets can be mounted in the same panel cut-out due to the standardized size. Mounting into Panel Cut-out To mount, insert the sockets with mounting springs facing top and bottom edges of the panel cut-out. Push the mounting spring using a screwdriver until the mounting spring clicks into the panel.
A (Total width of the sockets mounted) W = A 5.6 +0 0.5

SY2S-51 SY4S-51

SY4S-51 SY2S-51

SM2S-51

SH1B-51 SH1B-51 SH2B-51

SY4S-51

Panel cut-out width W = 18 + 27 + 27 + 18 + 27 + 18 + 18 + 27 + 27 5.6 = 201.4 0.5 Push Spring Panel


+0

Socket Width
Socket SH1B-51 SH2B-51 SH3B-51 SH4B-51 SM2S-51 SY2S-51 SY4S-51 Width 18 mm 27 mm 36 mm 45 mm 27 mm 18 mm 27 mm

54

(04/10/25)

Relay Sockets
SU Series Sockets: General Instructions
Parts Description
COM Terminals NO Terminals NC Terminals Coil Terminals Wire Ports Screwdriver Ports Wire Ports Screwdriver Ports Wire Ports Screwdriver Ports Wire Ports Screwdriver Ports Screwdriver Port Wire Port for Terminal No. 9 Correct Incorrect Wire Port Two wire ports are provided for each terminal.

For photos and dimensions, see page 48.

Wiring Instructions
Wire Port for Terminal No. 10

Direction of Screwdriver Tip

1. Insert the optional screwdriver (BC1S-SD0) or an applicable screwdriver into the square-shaped port as shown, until the screw-driver tip touches the bottom of the spring. 2. Push in the screwdriver until it touches the bottom of the port. The wire port is now open, and the screwdriver is held in place. The screwdriver will not come off even if you release your hand. 3. While the screwdriver is retained in the port, insert the wire or ferrule into the round-shaped wire port. Each wire port can accommodate one wire or ferrule. When connecting two wires to one terminal, use the adjoining port of the same terminal. 4. Pull out the screwdriver. The connection is now complete.

Clamp

Marking Plate

: Spring slots for SFA-101 leaf springs : Spring slots for SFA-202 leaf springs

Applicable Wires
Wire Stranded Wire Solid Wire Wire Insulation Diameter 0.2 to 1.25 Size mm2 or AWG24 to16 0.2 to 1.5 mm2 or AWG24 to16 3.15 mm maximum

Strip the wire insulation 9 to 10 mm from the end.


9 to 10 mm

In applications using ferrules for stranded wires, choose the ferrule listed in the table below. Make sure that an insulation sheath is applied when using the ferrules. When using stranded wires without ferrules, make sure that the core wires have not been loosened.

Applicable Ferrules
Applicable Wire (stranded) mm2 0.25 0.5 AWG 24 22 20 AI 0.25-12BU AI 0.34-8TQ AI 0.5-8WH AI 0.5-10WH Phoenix Contact Type No. Manufacturer

When using thin wires with insulation diameter of 1.6 mm or less, do not insert the wire too deeply where the insulation inserts into the spring clamp opening. Make sure that the wire insulation is stripped 9 to 10 mm and the wire is inserted to the bottom.
Wire Port Bottom

Incorrect

Correct

Applicable Screwdriver
For wiring, use the optional screwdriver (BC1S-SD0) or the following applicable screwdriver.

Do not twist the screwdriver inserted into the screwdriver port in the socket, otherwise the socket may break.

All dimensions in mm.

(04/10/25)

55

Relay Sockets
Marking Plate
Write markings on the SU sockets using an oil-based marker, or glue printed mylar on the marking surface. The size of the printed mylar can be 8 9 mm maximum.
Marking Surface 8.0 9.0 8.0 Jumper off Center Jumper Jumper on Center

Installing the SU9Z-J5 Jumper on Two, Three, or Four SU Sockets As shown below, slide the jumper in the sheath so that the jumper aligns with the center of the sheath.
Sheath

Marking Plate

Maximum Size of Printed Mylar

Position of Printed Mylar on the Marking Surface

Installing the Marking Plate Because of its removable structure, the marking plate may have fallen from the socket or become loose in delivery. Make sure that the marking plate is securely installed before starting operation. The marking plate protects the conductive portion of the socket, located under the marking plate, by preventing metal fragments or pieces of wire from dropping inside. Should any such fragments enter the socket, they may cause re hazard, damage, or malfunction.
Marking Plate

With the sheath properly installed on the jumper, cut the sheath and jumper at the points shown below, using cutting pliers. Referring to the drawing on the below right, make sure that the sheath and jumper are cut within the cutting area. Dispose of unused portions according to local waste disposal requirements.
Y X Z Sheath Jumper Sheath

Cutting Area C A B CD

Cutting Area D

Cutting Area in Detail Cutting Area A, C A, B D Discard Y X Z

For Connecting Jumper Quantity 2 sockets 2 2 sockets 1 3 sockets 1 4 sockets 1

No Marking Plate

Loose Fit

Installed Securely

After cutting the jumper and sheath, slide the jumper as shown below, so that the ends of the jumper are not exposed.
Cut Surface

SU9Z-J5 Jumper for SU2S-11L and SU4S-11L


The SU9Z-J5 is used to install ve sockets. When installing less than ve sockets, cut the jumper according to the instructions described below. The SU9Z-J5 is for coil terminals only. SU9Z-J5 Jumper Specifications
Rated Current Material Conductor Sheath 3A Nickel-plated brass ABS resin

Jumper Wiring to Six or More SU Sockets To jumper wire six or more SU sockets, connect ve sockets using whole jumpers and the remaining sockets using a cut jumper. Then connect the two terminals on adjoining sockets using an applicable wire (see table below).
Proper Wire

Installing the SU9Z-J5 Jumper Loosen the marking plate on the socket. Making sure that the SU9Z-J5 jumper is correctly aligned, insert the blades into the ports in the groove of the SU socket.
Jumper Wiring of Terminal 14 between Adjoining Sockets Wire Stranded Wire Solid Wire AWG
Jumper Groove Jumper

Jumper Port for Terminal 14

Jumper Port for Terminal 13 Blade

Size 0.2 to 1.25 mm2 0.2 to 1.5 mm2 24 to 16

Note 1: Use a wire with cable insulation diameter of 3.15 mm maximum. Note 2: Strip the cable insulation 9 to 10 mm from the end.

Correct

Incorrect

Safety Precautions
Insertion Direction
Press down the marking plate to secure the jumper. The jumper installation is now complete.

Turn off the power to the SU9Z-J5 jumper before starting installation, removal, wiring, maintenance, or inspection of the jumper, failure to turn power off may cause an electrical shock or re hazard. To avoid a short circuit due to incorrect wiring, conrm which terminals are connected to the jumper before starting wiring.
(04/10/25)

56

Relay Sockets
Optional Function Modules
Module Type No. Ordering Type No. Rated Voltage Polarity A1: Negative A2: Positive 6 to 220V DC SU9Z-D12 SU9Z-D12PN10 A1: Positive A2: Negative 6 to 240V AC 6 to 12V AC/DC 24 to 48V AC/DC 100 to 120V AC/DC 200 to 240V AC/DC Non-polarized LED Non-polarized LED indicator; goes on when the relay coil is energized. Function For absorbing surge voltages in DC coils. Since the diode module has polarity, connect DC voltage to terminals A1 and A2 correctly, otherwise the relay does not operate. For absorbing surge voltages in AC coils. Package Quantity 10

SU9Z-D11 Diode Module

SU9Z-D11PN10

10

RC Module

SU9Z-R21 SU9Z-L31

SU9Z-R21PN10 SU9Z-L31PN10 SU9Z-L32PN10 SU9Z-L33PN10 SU9Z-L34PN10

10 10 10 10 10

LED Module

SU9Z-L32 SU9Z-L33 SU9Z-L34

The diode module and RC module are for absorbing the counter emf generated in the relay coil. If the relay coil is subjected to excessive external surge voltages, provide a separate surge protection device to prevent damage to the internal surge absorbing element. Do not disassemble the function module, otherwise the module may be damaged. Installing the Optional Function Module Turn power off to the SU socket before starting installation, removal, wiring, maintenance, and inspection. Otherwise the devices may be damaged or electrical shocks may occur.

Remove the marking plate from the socket.


IdecZ-L31 SU9 AC/DC 6-12V

A2

A1

With the marking surface outside, insert the


module to the bottom.

Incorrect
Rib (Two Sides) Without Gap

Correct

Rib Guide (Two Sides)

SU9Z-J5 Jumper

When using the SU9Z-J5 jumper, insert the jumper


before installing the module.

Loose Fit

Insertion Complete

(04/10/25)

57

Relay Sockets

58

(04/10/25)

Specifications and other descriptions in this leaflet are subject to change without notice.
7-31, Nishi-Miyahara 1-Chome, Yodogawa-ku, Osaka 532-8550, Japan Tel: +81-6-6398-2571, Fax: +81-6-6392-9731 www.idec.com

IDEC CORPORATION (USA)


1175 Elko Drive, Sunnyvale, CA 94089-2209, USA Tel: +1-408-747-0550, Toll Free: (800) 262-IDEC, Fax: +1-408-744-9055 E-mail: opencontact@idec.com, www.idec.com

IDEC IZUMI ASIA PTE. LTD.


No. 31, Tannery Lane #05-01, Dragon Land Building, Singapore 347788 Tel: +65-6746-1155, Fax: +65-6844-5995 E-mail: generalinfo@idecasia.com.sg

IDEC CANADA LIMITED


Unit 22-151, Brunel Road Mississauga, Ontario, L4Z 1X3, Canada Tel: +1-905-890-8561, Toll Free: (888) 317-4332, Fax: +1-905-890-8562

IDEC IZUMI (H.K.) CO., LTD.


Room 1409, Tower 1, Silvercord, 30 Canton Road, Tsimshatsui, Kowloon, Hong Kong Tel: +852-2-376-2823, Fax: +852-2-376-0790 E-mail: idec@idechk.com

IDEC ELECTRONICS LIMITED


Unit 2, Beechwood, Chineham Business Park, Basingstoke, Hampshire RG24 8WA, UK Tel: +44-1256-321000, Fax: +44-1256-327755 E-mail: idec@uk.idec.com

IDEC IZUMI (Shanghai) Co., Ltd.


Room E, 15F, Majesty Building, No. 138 Pudong Avenue, Shanghai 200120, P.R.C. Tel: +86-21-5887-9181, Fax: +86-21-5887-8930 E-mail: idec@cn.idec.com

IDEC ELEKTROTECHNIK GmbH


Wendenstrae 331, D-20537 Hamburg, Germany Tel: +49-40-25 30 54-0, Fax: +49-40-25 30 54-24 E-mail: service@idec.de, www.idec.de

IDEC TAIWAN CORPORATION


8F, No. 79, Hsin Tai Wu Road, Sec. 1, Hsi-Chih, Taipei County, Taiwan Tel: +886-2-2698-3929, Fax: +886-2-2698-3931 E-mail: service@idectwn.com.tw

IDEC AUSTRALIA PTY. LTD.


2/3 Macro Court, Rowville, Victoria 3178, Australia Toll Free: 1-800-68-4332, Fax: +61-3-9763-3255 E-mail: sales@au.idec.com