Utility Communications TEBIT for FOX515/512 Teleprotection and binary interface

Teleprotection is a key application demanded by any utility communications system. Distance protection relays need to exchange information in order to operate correctly and provide fast reaction times in case of any fault on the power line. Reaction times within milliseconds are essential to prevent damage to industrial assets worth millions of investment. The relays exchange trip signals between each other which allows the relays to localize a fault faster and more selectively. Such critical applications ask for very fast signal transmission on one hand and for very high dependability (probability to miss a command) and security (probability of a false, unwanted command) on the other. The communications service needs to be guaranteed at any time, so accordingly highest availability of the teleprotection interfaces and communications channel needs to be ensured.

The TEBIT Teleprotection interface module provides four command inputs and outputs for distance protection applications and guaranties highest reliability and dependability of the communications channel. Continuous supervision of the availability of the data channel, fastest switchover from main to protecting channel (< 5 ms) and automatic loop test for delay measurement make the TEBIT interface the ideal solution for distance protection signal transmission. Accordingly the FOX515 can be directly interconnected with the protection relay and be used for teleprotection signal transmission via WAN network. FOX515 can be used as a combined communication/teleprotection equipment and thus provides a unique solution optimised for power utilities. The FOX515/TEBIT solution helps to save costs by providing several benefits such as less space requirements, fully integrated solution with one configuration tool and management system for all services.

TEBIT outstanding features for ABB's demanding customers

Specially designed for utilities The TEBIT interface has been specifically designed for distance protection applications. Therefore it provides exactly the features required by power utilities. Having a fibre optic multiplexer integrated solution allows to provide optimized end to end solutions for your mission critical application. Besides, TEBIT also saves space and ensures full supervision by the network management system (FOXMAN). TEBIT at a glance 4 x command inputs for trip signals 4 x outputs for solid state trip signals 2 x programmable auxiliary relay which can be used e.g. for alarm outputs 8 x inputs and outputs for binary signal transmission Nonvolatile event recorder with GPS synchronization and trip counter All inputs and outputs are galvanically isolated and with high EMC immunity for harsh environment 1+1 path protection with very fast switchover time (< 5 ms) Supports point to point and Tee-line configuration The command inputs of TEBIT have been designed for direct connection to the protection relay. They are software configurable for trip voltage levels from 24 to 250 VDC. TEBIT complies to Teleprotection standard IEC 60834-1 and can be configured for: Permissive tripping Intertripping Blocking / non-blocking Tee-lines (normal or inverse) Security, dependability and transmission speed programmable as per requirements Continuous performance monitoring for each command channel 4 x protection signals per 64 kbit/s channel Trip transmission time measurement

An 8 bit command addressing scheme ensures correct cross connection and the very fast 1+1 switchover in case of link failure ensures highest reliability of the communication channel.
An wrongly rerouted channel will be detected by means of the SFC address

TEBIT

TEBIT

TEBIT

FOX 515 Network


TEBIT TEBIT TEBIT

SFCs addressing scheme prevents false tripping due to rerouted channels

TEBIT architecture The TEBIT is part of a large complement of interface modules which can be plugged into a FOX515 shelf. Like all FOX515 modules TEBIT is: powered from the FOX515 shelf configured by UCST and supervised by FOXMAN-Management system Two front connectors provide access to the teleprotection and binary inputs and outputs. Alarm states are displayed by LEDs. TEBIT includes a non volatile event recorder with an outstanding accuracy, synchronizable with the GPS system and trip counter. Cyclic loop tests allow permanent channel monitoring, and add / drop features allow efficient use of bandwidth. All Teleprotection inputs and outputs are galvanically isolated and provide highest EMC immunity for harsh environment. The TEBIT has an integrated cross connect with drop and insert functionality for single commands.

Binary data channels 8 x opto-coupler inputs 24 to 60 VDC 8 x solid-state relay outputs All inputs and outputs galvanically isolated Cross-connect and drop-and-insert facilities for each binary signal Point-to-multipoint operation Transmission of slow data up to 20 bd 1+1 path protection Integrated galvanically isolated 24 V auxiliary supply 8 x binary signals per 64 kbit/s channel

2 TEBIT for FOX515/512

TEBIT optimised teleprotection solution

It is possible to protect more than one power line using one TEBIT module (e.g. if only two commands are used per power line). Station C of the picture below shows such a configuration. Station A, B and C are connected in a Tee-line configu-

ration. Trip signals (Trip signal 1 and 2) are broadcast to the two opposite stations. Trip-signal 3 and 4 are configured in a point-to-point connection. A GPS receiver provides an accurate time reference for the event recorder.

FOX515

FOX515

Power Line
Trip 1 Trip 2 Trip 3 Trip 4 Powerline

Tee-line

GPS receiver

Binary 1

Binary 2

Binary 3

FOX FOX515

FOX515

B
Binary 2

Trip 1 Trip 2

TEBIT FOX 515 FOX 515 TEBIT


Trip 1 Trip 2

FOX515

TEBIT
Binary 1

Trip 1 Trip 2 Trip 3 Trip 4

TEBIT
Binary 3

Trip 3 Trip 4

FOX515

TEBIT in Tee-off configuration

The TEBIT module provides two different operation modes which should be chosen depending on the protection scheme. Table 1 and 2 show the applicable delay times. Operation mode Speed optimized Recommended for use with teleprotection schemes: Permissive tripping (blocking/unblocking) Delay times for point-to-point transmission (excluding line propagation delay): min. Input voltage Trip immunity time Transmission delay time Propagation delay time 24 125 V 0.5 ms 1.9 ms 2.4 ms 220/250 V 1.4 ms 1.9 ms 3.3 ms typ. 24 125 V 0.7 ms 2.4 ms 3.1ms 220/250 V 1.6 ms 2.4 ms 4.0 ms max. 24 125 V 1.0 ms 3.1 ms 4.1 ms 220/250 V 1.8 ms 3.1 ms 4.9 ms

Table 1: Delay times operation mode speed optimized

Operation mode Security optimized Recommended for use with teleprotection schemes: Intertripping (direct transfer tripping) Delay times for point-to-point transmission (excluding line propagation delay): min. Input voltage Trip immunity time Transmission delay time Propagation delay time 24 125 V 1.5 ms 3.0 ms 4.5 ms 220/250 V 2.4 ms 3.0 ms 5.4 ms typ. 24 125 V 2.1 ms 3.6 ms 5.7 ms 220/250 V 3.0 ms 3.6 ms 6.6 ms max. 24 125 V 3.0 ms 3.8 ms 6.8 ms 220/250 V 4.8 ms 3.8 ms 7.8 ms

Table 2: Delay times operation mode security optimized


TEBIT for FOX515/512 3

Technical data

Teleprotection inputs / outputs Command inputs Nominal input voltage Threshold Command outputs Tripping command Continuous command Aux. outputs Contact load 4 24 VDC up to 250 VDC configurable with UCST 60% of nominal input voltage 250 VDC, 2 A, Ton/Toff 1/3; Ton 5 min 250 VDC; 1 A 2 relays, NO/NC contacts 16 ... 250 VAC or DC; max. 150 W 10 A (max. 100 ms) 50 A (max. 1 ms) 2 A continuous Typical 3.5 ms (optimized for speed 24 ... 125 VDC) IEC 608341 8 (Opto coupler) 24, 48, 60 VDC; low -72 ... +9 VDC; high +18 ... +72 VDC low 1.5 mA; high 3 ... 12.5 mA 8 (PhotoMOS, normally open) 24, 48, 60 VDC low 1.5 mA; 0.5 A for max. 100 ms; 0.2 A continuous On-resistance Aux. voltage supply GPS synchronization input Isolation 6 24 VDC +5% ... -20% 40 mA continuous, short circuit protected IRIG-B DC-level (unmodulated) 3,000 Vrms 1 min between protection circuit and equipment 1,500 Vrms 1 min between protection circuits and earth 708 Vrms 1 min for binary circuits 500 Vrms 1 min for aux voltage IEC61000-4-2 / 3 / 4 / 5 / 6 / 12 IEC01255-5 / -22-1
List of abbreviations GPS NC NO SFC UCST WAN Global Positioning System Normally closed Normally open Secure Frame Concept Configuration tool for FOX515/512 Wide Area Network
1KHA - 000 590 - SEN 1000 - 06/11 - Printed in Switzerland ABB Switzerland Ltd. June 2011. The right to modifications or deviations due to technical progress is reserved.

4 (PowerMosFET normally open)

Propagation delay time Standard compliance Binary signal inputs / outputs Binary inputs Nominal input voltage Input current Binary outputs Nominal output voltage Contact load

EMC

For more information please contact: ABB Switzerland Ltd. Power Systems Brown Boveri Strasse 6 5400 Baden, Switzerland Phone: +41 58 589 37 35 or +41 844 845 845 (Call Center) Fax: +41 58 585 16 88 E-Mail: utilitycommunications@ch.abb.com www.abb.com/utilitycommunications