High Voltage

IEC 60282-1 and VDE 0670 T4

Fuse-links according to

Ferraz Shawmut is now

product guide

High Voltage fuse-links


The Limitor high voltage fuse-links line by Mersen is designed, manufactured and tested as per a Quality Management System certified to the ISO 9001:2000 International standard. The Mersen high voltage fuse-links are made of pure materials. Some parts of them and some manufacturing processes are patented. The Limitor high voltage fuse-links line by Mersen encompasses 6 different product ranges as per the following table:
Additional Thermal striker function Additional Controlled Power Dissipation function

Product Range Name

Standard

General Purpose category

Back-up category

Striker

Switch-fuse combination dedication

Limitor-G Limitor-P Limitor-PT Limitor-PD Limitor-PTD Limitor-PTS

IEC 60282-1 VDE 0670 T4 IEC 60282-1 VDE 0670 T4 IEC 60282-1 VDE 0670 T4 IEC 60282-1 VDE 0670 T402 IEC 60282-1 VDE 0670 T402 IEC 60282-1 VDE 0670 T402

p. 7 p. 8

p. 11 p. 14

p. 16

p. 20

Catalog Numbering for Limitor high voltage fuse-links

4 5 D B 1 2 0 V 5 0 P T S
45 mm diameter of contact caps D for DIN B for Back-up G for General purpose Voltage rating in V/100 Current rating in A P for striker S for VDE 0670 T402 and dedicated switch-fuse combination D for VDE 0670 T402 T for Thermal Striker or Controlled Power Dissipation D for VDE 0670 T402

General information
HV fuse-links have been used for reliable protection in high voltage switchgear and controlgear and systems for decades. They protect apparatus and equipment against the thermal and dynamic effects of short-circuits. The outstanding features of Limitor HV fuse-links by Mersen are: High breaking capacity High current limitation Low switching voltage Quick breaking Non-ageing Limitor HV fuse-links conform to the following standards:  IEC 60282-1: High voltage fuses - Part 1: current-limiting fuses. This international standard is identical to the German standard VDE 0670 T4. VDE 0670 T402: Selection of curent-limiting fuse-links for transformer circuits. IEC 60787: Application guide for the selection of high voltage fuse-links for transformer circuit applications. VDE 0671 T105/IEC 62271-105: High voltage switchgear and controlgear - Part 105: Alternating switch-fuse combinations. DIN 43 625: DIN 43625: High voltage fuses; rated voltages 3,6 to 36kV (fuse-links dimensions). DIN 43 624: High voltage fuse-links, rated voltages 3/3,6 to 30/36kV (single-pole fuse-bases). The quality management system of Mersen is certified to the international standard DIN EN ISO 9001. Mersen operates a certified environment management system. Mersen manufactures HV fuse-links with dimensions conforming to DIN 43 625 with striker for indoor and outdoor use, where the striker serves for actuating a trip-free mechanism as well as an indicator due to its red colour.

Terms and definitions


General purpose fuse-links range
Mersen General purpose fuse-links have an extended operating range for low currents. The fuse-links are capable of interrupting all currents from a current that causes the fuse-link to melt within a time not less than 1 hour up to the maximum rated breaking current (l1). These fuse-links are therefore also able to reliably interrupt low fault currents.

HV fuse-links

ln
Current

l3

l1
breaking current
Maximum rated

rating

Melting current with melting

time 1h

Back-up fuse-links have a rated minimum breaking current from which the fuse-links are able to interrupt current. Back-up fuse-links are not supposed to operate below their minimum breaking current (below l3). Their operating range is from l3 to the maximum rated breaking current (l1). For the assignment of back-up fuse-links, it is important to note that the lowest short-circuit current is higher at the site of the HV back-up fuse-link than l3 (IKmin > I3). If the short-circuit current is lower than the minimum breaking current, additional protection must be provided.

Back-up fuse-links ranges

ln
Current

l3
breaking current
Minimum rated

l1
breaking current
Maximum rated

rating

The CPD designed by Mersen controls the power dissipation of the fuse-link according to Ohms law and fits both Limitor-PD and -PTD ranges. The striker of all the Limitor high voltage fuse-links published here are of medium type (80Nclass) as per the IEC 60282-1 standard (strikers are ranked as per the energy they release between two specified points during their trip). As the back-up fuse-link is combined with a switch the CPD operates the switch before a too high power level is dissipated by the fuse-link.

Back-up fuse-links ranges with CPD (Controlled Power Dissipation)

Back-up fuse-links ranges with thermal striker

The thermal striker patented by Mersen fits the Limitor-PTS range. The Limitor-PTS range is dedicated to switch-fuse combination.

Striker

The striker of HV fuse-links in this product list has an effective length of 30 mm and is a medium type. This classification results from the energy released by the striker between the points A andB (within the first 20 mm of the operating distance). The initial force is about 80N, the force at the end of free movement is about 15N. The striker serves for actuation of the trip-free mechanism of the switch (figure 1).

Terms and definitions


Rated voltage range
It is important for HV fuse-links that they must be operated at the voltage for which they have been rated. Accordingly, the operating voltage corresponds to the maximum rated voltage of the fuse-link. Owing to the switching voltage occurring during arcing, the fuse-link cannot be used at lower voltages without limitation. A lower operating voltage at which the fuse-link can still be used without exceeding the system insulation level during extinction must therefore be taken into account. From these two values results the permissible voltage range of the fuse-link, which is shown on the fuse-link or in the technical data, e.g. 10/24kV.

HV fuse-links

The breaking capacity is also referred to as the rated maximum breaking current. This clearly indicates that this is the maximum current which can be interrupted by the fuse-link. I1 of the fuse-link must be greater than the maximum short-circuit current at the site of the fuse-link (I1 > IKmax).
Fig. 1

Breaking capacity I1

The minimum breaking current is referred to as the rated minimum breaking current. This value must be specified for back-up fuse-links. From this current, back-up fuse-links are capable to breaking fault currents. The fuse-links must be assigned to the system so that no fault current below I3 can occur at the site of the fuse-link (due to the system parameters or other protective devices).

Minimum breaking current I3

Power dissipation of a fuse-link Pwarm

The power dissipation of a HV fuse-link is specified at the rated current of the fuse-link. For protection with HV fuse-links, it should be noted that the operating current is normally half the rated current. Because of the physical relationships, the actual power dissipation is less than a quarter of the value Pwarm for HV fuse-links shown in the technical data table.

Time-current characteristic (I/t characteristic)

The time-current characteristic shows the correlation between current and time up to the melting of a fuse-element. The virtual time (tvs) is specified to enable a comparison of the l/t characteristics of fuse-links below 100ms. For co-ordination with other protective devices, e.g. load interrupter switches or circuit breakers, the melting integral I2t must be referred to for melting times below 100ms.

Current limitation

At high short-circuit currents, HV fuse-links interrupt current within several milliseconds that means, the sinusoidal current does not reach its peak value and that HV fuse-links are current limiting devices. This is a significant advantage compared to mechanical switches whose contacts take longer to open and interrupt currents at natural zero. During this time, the peak short-circuit current is able to freely develop its dynamic force. By using HV fuse-links, this surge current is limited within several ms to a fraction of its peak value and the design of the subsequent system can be reduced in terms of dynamic forces.

Switching voltage

So that HV fuse-links perform a current-limiting action, the short-circuit current must be limited and reduced as it increases. This requires a switching voltage that exceeds the driving system voltage and forces the current to zero. This switching voltage must not exceed the specified permissible value of 2,2 times the peak value of the maximum rated voltage. Limitor HV fuse-links are within this limit.

Terms and definitions


Dimensions
HV fuse-links in this product list conform to DIN 43 625. The contact cap dimensions defined in this standard are shown in Fig. 2. The dimension e varies depending on the rated voltage of HV fuse-links, which is shown as a dimension for fuse-links in the technical data tables. The diameter d also varies with the rated current, whereby this dimension is also shown in the tables.

HV fuse-links

Fig. 2

d= 88 max

Dimensions acc. to DIN 43 625 in mm.

Protection of transformers

The following should be observed for HV fuse-link selection: a) Transformer ratings Service voltage (U) Rated output (S) Relative short-circuit voltage (Uk %) Inrush current (factor 8...12 In) b) Time-current characteristic of HV fuse-links c) Secondary devices/selectivity

Procedure based on an example:

A 630kVA transformer has a transformer rated current of 18,2A at a service voltage of 20kV. The relative short-circuit voltage is 4% and the inrush current is 12 x In. The short-circuit current on secondary terminal short-circuit is given from the relative short-circuit voltage. The transformer must be designed to withstand this current for 2 seconds. This condition results in point b) in Fig. 3. HV fuse-links must interrupt this current within 2 seconds. In Fig. 3, the fuse-link F4 must not be used for this transformer, as the fuse-link will require longer than 2 seconds to melt at this short-circuit current.

The inrush current is plotted for a duration of 0,1 seconds, resulting in point a). This inrush current must not melt the fuse-link, for which reason the fuse-link F1 cannot be used for this transformer. The fuse-links F2 and F3 can be used for this transformer, since their time-current characteristics are between the points a) and b). A transformer can thus be assigned several HV fuse-links for various rated currents. Decisive for selection of the correct fuse-link is the time-current characteristic and not the rated current of the HV fuse-link.

Fig. 3 F1 F4) Time-current characteristics of HV fuse-links a) Inrush current b) lowest short-circuit current of transformer

Limitor-G General Purpose fuse-links according to IEC 60282-1


Selection table
Rated voltage range of fuse-link [kV] Service voltage of transformer [kV] 6/12 6 6/12 10 10/24 20 Table 5 Mode of protection Rated current of fuse-link [A] Transformer rated current [A] Rated current of fuse-link [A Transformer rated current [A] Rated current of fuse-link [A] Transformer rated current [A] Rated current of fuse-link [A] Transformer output [kVA] rel. short-circuit voltage 50 4,8 6,3 2,9 6,3 1,5 100 9,6 16 5,8 6,3-10 2,9 4 125 12 16 7,2 10 3,6 4-6,3 160 15,4 16-25 9,2 16 4,6 6,3 200 19,2 25 11,5 16 5,8 6,3-10 250 24,1 25-40 14,4 16-25 7,2 10 UK = 4% 315 30,3 40 18,2 25 9,1 16 400 38,5 40-50 23,1 25-40 11,5 16 500 48,1 50 28,9 40 14,4 16 630 60,6 50 36,4 40-50 18,2 25 UK = 5% 800 77,1 46,2 50 23,1 25 1000

HV fuse-links

96,3 57,7 50 28,9 25

Catalog Number 45DG120V6,3P 45DG120V10P 45DG120V16P 45DG120V25P 45DG120V40P 45DG120V50P 45DG240V4P 45DG240V6,3P 45DG240V10P 45DG240V16P 45DG240V25P

Reference Number W1000151A X1000152A Y1000153A Z1000154A A1000155A B1000156A C1000157A D1000158A E1000159A F1000160A G1000161A

Range General Purpose, striker General Purpose, striker General Purpose, striker General Purpose, striker General Purpose, striker General Purpose, striker General Purpose, striker General Purpose, striker General Purpose, striker General Purpose, striker General Purpose, striker

Un (kV) 6/12 6/12 6/12 6/12 6/12 6/12 10/24 10/24 10/24 10/24 10/24

In (A) 6,3 10 16 25 40 50 4 6,3 10 16 25

L (mm) 292 292 292 292 292 292 442 442 442 442 442

D (mm) 65 65 65 65 78 88 78 78 78 78 88

I1 (kA) 40 40 40 40 40 40 40 40 40 40 40

R (m) 128 70 35 20,5 12,2 9,9 280 256,5 135 70,3 41,2

P (W) 6 8 10 15 24 31 5 11 15 21 31

It (kAs) 2 3,8 14 36 110 150 1,8 2 3,6 14 39

Weight (kg) 2,3 2,3 2,3 2,3 3,1 3,7 4,1 4,1 4,1 4,1 4,5

Time-current characterictics

Fig. 13 6/12 kV

Fig.14 10/24 kV

High voltage alternating current switch-fuse according to IEC

62271-105 and VDE 0671 T105


Back-up fuse-links

HV fuse-links

In order to increase the utilization range of a switch, it is combined with current limiting HV fuse-links. This combination unit offers short-circuit protection in addition to load switching capacity. HV fuse-links provide short-circuit protection, while the switch interrupts the currents below the take-over current of the combination unit. In addition to the inrush current, short-circuit current on secondary terminal short-circuits and low voltage selectivity, the following switch characteristics should be taken into account: Rated transfer current (ltransfer) Fuse-initiated opening time of the switch (t0) Fig. 9 shows the rated transfer current (ltransfer) as a vertical line. The fuse-initiated opening time (t0) must be multiplied by 0,9 (procedure according to IEC 62271-105 and VDE 0671 T105) and a horizontal line be drawn. This results in an intersection that is characteristic to the switch and must be established for each switch individually.

Fig. 9: Selection of HV fuse-links acc. to IEC62 271-105 and VDE 0671 T105

This switch intersection divides the sheet into four quadrants (see Fig. 9). Suitable for the switch-fuse combination are HV fuse-links only with a time-current characteristic that does not pass through quadrant IV (forbidden area). Generally suitable for use in switch-fuse combinations according to IEC 62271-105 and VDE0671T105 are all HV fuse-links with striker which meet this criterion. Mersen has assigned HV fuse-links to the switch-fuse combination and the transformers of all major manufactures. These documents are available on request.

Limitor-P&-PT back-up fuse-links


according to IEC
Selection table
Rated voltage range of fuse-link [kV] Service voltage of transformer [kV] Transformer rated current [A] Rel. short-circuit voltage 3/7,2 6 Transformer rated current [A] 6/12 10 Transformer rated current [A] 10/24 20 Transformer rated current [A]

with and without controlled power dissipation CPD

60282-1

20/36 30

HV fuse-links

Rated current of fuse-link [A]

Rated current of fuse-link [A]

Rated current of fuse-link [A]

50 100 125 160 200 UK = 4% 250 315 400 500 630 800 UK = 5% UK = 6% 1000 1250 1600

4,8 9,6 12 15,4 19,2 24,1 30,3 38,5 48,1 60,6 77,1 96,3 120,3 154

1620 2031,5 2540 31,550 4063 4080 50100 63125 80160 100200 125200 125160 160200 200

2,9 5,8 7,2 9,2 11,5 14,4 18,2 23,1 28,9 36,4 46,2 57,7 72,2 92,4

10 1620 2025 2031,5 2540 31,550 4063 4080 50100 63100 80125 100160 125200 125200

1,5 2,9 3,6 4,6 5,8 7,2 9,1 11,5 14,4 18,2 23,1 28,9 36,1 46,2

4 10 1016 1620 1620 2025 2031,5 2540 31,550 4063 4063 5080 63100 80100

0,96 1,9 2,4 3,1 3,8 4,8 6,1 7,7 9,6 12,1 15,4 19,2 24,1 30,8

26,3 6,310 10 10 1016 1620 1625 2025 2031,5 2540 31,540 4050 4050 5063

Table 1 Bold typed figures are preferred values

Limitor-P back-up fuse-links


Catalog Number 45DB72V2P 45DB72V4P 45DB72V6,3PD 45DB72V10PD 45DB72V16PD 45DB72V20PD 45DB72V25PD 45DB72V32PD 45DB72V40PD 45DB72V50PD 45DB72V63P 45DB72V80P 45DB72V100P 45DB72V125PD 45DB72V160P 45DB72V200P Reference Number N1000098A P1000099A S209293A T209294A V209295A W209296A X209297A Y209298A Z209299A A209300A B209301A C209302A D209303A Q1000100A R1000101A S1000102A Range Back-up with striker Back-up with striker Back-up with striker Back-up with striker Back-up with striker Back-up with striker Back-up with striker Back-up with striker Back-up with striker Back-up with striker Back-up with striker Back-up with striker Back-up with striker Back-up with striker Back-up with striker Back-up with striker Un (kV) 3/7,2 3/7,2 3/7,2 3/7,2 3/7,2 3/7,2 3/7,2 3/7,2 3/7,2 3/7,2 3/7,2 3/7,2 3/7,2 3/7,2 3/7,2 3/7,2 In (A) 2 4 6,3 10 16 20 25 31,5 40 50 63 80 100 125 160 200 L (mm) 192 192 192 192 192 192 192 192 192 192 192 192 192 192 192 192 D (mm) 56 56 56 56 56 56 56 56 56 56 65 65 65 88 88 88 I1 (kA) 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63

without controlled power dissipation CPD


I3 (A) 15 20 20 35 64 80 95 110 134 190 220 300 350 435 500 610 R (m) 256 256 256 144 41 32 25 19 12,5 9,25 8,75 6,25 5 3 2,9 2,5 P (W) 1,8 5 11 19 13 14,5 20 23 30 35 60 85 96 75 120 200 It (kAs) 0,6 0,8 0,8 3 2,34 3,9 4,9 7 14 25,3 41,2 84 93,6 440 500 654 Weight (kg) 1,1 1,1 1,1 1,1 1,1 1,1 1,1 1,1 1,1 1,1 1,4 1,4 1,4 2,4 2,4 2,4

Rated current of fuse-link [A]

Transformer output [kVA]

Limitor-P back-up fuse-links


according to IEC
Catalog Number 45DB120V1P Reference Number T1000103A V1000104A W1000105A F209305A G209306A H209307A J209308A K209309A L209310A M209311A N209312A P209313A Q209314A R209315A X1000106A Y1000107A Z1000108A V1000564A W1000565A X1000566A Y1000567A Z1000568A A1000569A B1000570A C1000571A D1000572A E1000573A F1000574A A1000109A B1000110A C1000111A S209339A T209340A V209341A W209342A X209343A Y209344A Z209345A A209346A B209347A C209348A D209349A D1000112A E1000113A F1000114A G1000115A H1000116A S209362A T209363A V209364A W209365A X209366A Y209367A Z209368A J1000117A K1000118A

without controlled power dissipation CPD

60282-1
Un (kV) 6/12 6/12 6/12 6/12 6/12 6/12 6/12 6/12 6/12 6/12 6/12 6/12 6/12 6/12 6/12 6/12 6/12 In (A) 1 2 4 6,3 10 16 20 25 31,5 40 50 63 80 100 125 160 200

Range Back-up with striker Back-up with striker Back-up with striker Back-up with striker Back-up with striker Back-up with striker Back-up with striker Back-up with striker Back-up with striker Back-up with striker Back-up with striker Back-up with striker Back-up with striker Back-up with striker Back-up with striker Back-up with striker Back-up with striker Back-up with striker Back-up with striker Back-up with striker Back-up with striker Back-up with striker Back-up with striker Back-up with striker Back-up with striker Back-up with striker Back-up with striker Back-up with striker Back-up with striker Back-up with striker Back-up with striker Back-up with striker Back-up with striker Back-up with striker Back-up with striker Back-up with striker Back-up with striker Back-up with striker Back-up with striker Back-up with striker Back-up with striker Back-up with striker Back-up with striker Back-up with striker Back-up with striker Back-up with striker Back-up with striker Back-up with striker Back-up with striker Back-up with striker Back-up with striker Back-up with striker Back-up with striker Back-up with striker Back-up with striker Back-up with striker

L (mm) 292 292 292 292 292 292 292 292 292 292 292 292 292 292 292 292 292 367 367 367 367 367 367 367 367 367 367 367 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 537 537 537 537 537 537 537 537 537 537 537

D (mm) 56 56 56 56 56 56 56 56 56 56 56 56 65 65 88 88 88 56 56 56 56 56 56 56 56 56 65 88 56 56 56 56 56 56 56 56 56 56 56 56 65 78 88 88 88 56 56 56 56 56 56 56 65 65 88 88

I1 (kA) 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 40 31,5 31,5 31,5 31,5 31,5 31,5 31,5 31,5 31,5 31,5 20 20 20

I3 (A) 14 16 22 30 42 54 73 93 105 125 160 230 350 500 480 560 610 30 43 54 73 93 105 125 205 280 350 500 14 16 23 30 43 54 73 93 105 125 205 280 310 430 760 900 1050 15 20 20 33 66 95 110 135 200 220 280

R (m) 1400 500 340 185 138 107 71 52 42 22,5 18 12,8 10,6 8,5 4,75 4,25 3,75 245 180 150 102 78 59 33,8 26 18,4 15 13 2170 800 545 297 220 197 132 96 78 45 35 24 20 18 11,7 9,45 7 755 755 827 463 210 147 125 85 65 42 35

P (W) 1,6 2,2 6 9 17 38 38 46 65 54 70 85 115 156 117 217 333 11 22 53 56 73 95 79 106 130 180 280 2,2 3,4 10 13 26 73 76 89 127 114 147 170 233 400 117 217 333 9 32 39 65 67 84 100 119 176 183 271

It (kAs) 0,2 0,4 0,7 1 1,5 2 4 6 10 30 50 100 150 200 440 500 654 1 1,5 2 4 6 10 30 50 100 150 200 0,2 0,4 0,7 1 1,5 2 4 6 10 30 50 100 150 200 350 500 730 0,6 0,8 0,6 2 2,34 3,9 6,5 7 14,2 40 61,7

Weight (kg) 1,7 1,7 1,7 1,7 1,7 1,7 1,7 1,7 1,7 1,7 1,7 1,7 2,1 3,1 3,7 3,7 3,7 2,1 2,1 2,1 2,1 2,1 2,1 2,1 2,1 2,1 2,6 3,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 3,1 4,2 5,9 5,9 5,9 2,7 2,7 2,7 2,7 2,7 2,7 2,7 3,7 3,7 6,5 6,5

HV fuse-links

45DB120V2P 45DB120V4P 45DB120V6,3P 45DB120V10P 45DB120V16P 45DB120V20P 45DB120V25P 45DB120V32P 45DB120V40P 45DB120V50P 45DB120V63P 45DB120V80P 45DB120V100P 45DB120V125P 45DB120V160P 45DB120V200P 45DB175V6,3P 45DB175V10P 45DB175V16P 45DB175V20P 45DB175V25P 45DB175V32P 45DB175V40P 45DB175V50P 45DB175V63P 45DB175V80P 45DB175V100P 45DB240V1P 45DB240V2P 45DB240V4P 45DB240V6,3P 45DB240V10P 45DB240V16P 45DB240V20P 45DB240V25P 45DB240V32P 45DB240V40P 45DB240V50P 45DB240V63P 45DB240V80P 45DB240V100P 45DB240V125P 45DB240V160P 45DB240V200P 45DB360V2P 45DB360V4P 45DB360V6,3PD 45DB360V10PD 45DB360V16PD 45DB360V20PD 45DB360V25PD 45DB360V32PD 45DB360V40PD 45DB360V50PD 45DB360V63PD
10

10/17,5 6,3 10/17,5 10 10/17,5 16 10/17,5 20 10/17,5 25 10/17,5 31,5 10/17,5 40 10/17,5 50 10/17,5 63 10/17,5 80 10/17,5 100 10/24 10/24 10/24 10/24 10/24 10/24 10/24 10/24 10/24 10/24 10/24 10/24 10/24 10/24 10/24 10/24 10/24 20/36 20/36 20/36 20/36 20/36 20/36 20/36 20/36 20/36 20/36 20/36 1 2 4 6,3 10 16 20 25 31,5 40 50 63 80 100 125 160 200 2 4 6,3 10 16 20 25 31,5 40 50 63

with controlled power dissipation CPD


Application

Limitor-PT back-up fuse-links meet the requirements of IEC 60282-1

Limitor HV fuse-links type CPD meet the requirements of IEC 60282-1 and were specifically developed to be installed in compact sized enclosed SF6 insulated substations. In these substations HV fuse-links are enclosed in narrow fuse compartments which on the one hand prevent efficient cooling of the fuse-links and on the other hand have a limited thermal power acceptance themselves. Overheating of fuse compartments in such enclosures is, however, not to be expected, if the fuse-links have been properly selected by their rated current according to the transformer to be protected (see table 3) and if the melting elements of the fuse-links are in faultless condition (Fig. 8). One or more of the melting elements connected in parallel may, however, be interrupted by transient currents caused by transformer inrush or lightning strikes. Fuse-links having one or more of the paralleled melting elements interrupted, dissipate significantly more heat than faultless fuse-links. There is a certain risk that the limited power acceptance of fuse compartments may be exceeded at or even below rated transformer current. HV back-up fuse-links type CPD prevent such potential overheating when installed in conjunction with a transformer switch having trip-free mechanism

HV fuse-links

The CPD striker system controls the power dissipation of the fuse-link according to Ohms law (CPD means controlled power dissipation). The striker pin is released depending on the voltage drop across the fuse-link and, therefore depending on the power dissipation. The release voltage of the CPD striker system has been selected so that the fuse carrying the operating current IB does not exceed the limiting value. The CPD striker system controls the power dissipation of the fuse-link and releases the transformer switch before the permissible power acceptance of the fuse compartment will be exceeded (Fig. 8).

Function mode

Power dissipation acc.to perm.value of the switch gear

Fig. 8 Controlled power dissipation

Voltage drop acc.to the release of the HV Fuse-link


11

Limitor-PT back-up fuse-links


with controlled power dissipation CPD according to IEC

60282-1

HV fuse-links

Catalogue Number 45DB120V1PT 45DB120V2PT 45DB120V4PT 45DB120V6,3PT 45DB120V10PT 45DB120V16PT 45DB120V20PT 45DB120V25PT 45DB120V32PT 45DB120V40PT 45DB120V50PT 45DB120V63PT 45DB120V80PT 45DB120V100PT 45DB120V125PT 45DB120V160PT 45DB120V200PT 45DB240V1PT 45DB240V2PT 45DB240V4PT 45DB240V6,3PT 45DB240V10PT 45DB240V16PT 45DB240V20PT 45DB240V25PT 45DB240V32PT 45DB240V40PT 45DB240V50PT 45DB240V63PT 45DB240V80PT 45DB240V100PT 45DB240V125PT

Reference Number L1000119A M1000120A N1000121A P1000122A Q1000123A R1000124A S1000125A T1000126A V1000127A W1000128A X1000129A Y1000130A Z1000131A A1000132A B1000133A C1000134A D1000135A E1000136A F1000137A G1000138A H1000139A J1000140A K1000141A L1000142A M1000143A N1000144A P1000145A Q1000146A R1000147A S1000148A T1000149A V1000150A

Range Back-up, striker, CPD Back-up, striker, CPD Back-up, striker, CPD Back-up, striker, CPD Back-up, striker, CPD Back-up, striker, CPD Back-up, striker, CPD Back-up, striker, CPD Back-up, striker, CPD Back-up, striker, CPD Back-up, striker, CPD Back-up, striker, CPD Back-up, striker, CPD Back-up, striker, CPD Back-up, striker, CPD Back-up, striker, CPD Back-up, striker, CPD Back-up, striker, CPD Back-up, striker, CPD Back-up, striker, CPD Back-up, striker, CPD Back-up, striker, CPD Back-up, striker, CPD Back-up, striker, CPD Back-up, striker, CPD Back-up, striker, CPD Back-up, striker, CPD Back-up, striker, CPD Back-up, striker, CPD Back-up, striker, CPD Back-up, striker, CPD Back-up, striker, CPD

Un (kV) 6/12 6/12 6/12 6/12 6/12 6/12 6/12 6/12 6/12 6/12 6/12 6/12 6/12 6/12 6/12 6/12 6/12 10/24 10/24 10/24 10/24 10/24 10/24 10/24 10/24 10/24 10/24 10/24 10/24 10/24 10/24 10/24

In (A) 1 2 4 6,3 10 16 20 25 31,5 40 50 63 80 100 125 160 200 1 2 4 6,3 10 16 20 25 31,5 40 50 63 80 100 125

L (mm) 292 292 292 292 292 292 292 292 292 292 292 292 292 292 292 292 292 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442

D (mm) 56 56 56 56 56 56 56 56 56 56 56 56 65 65 88 88 88 56 56 56 56 56 56 56 56 56 56 56 56 65 78 88

I1 (kA) 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 40

I3 (A) 14 16 22 30 42 54 73 93 105 125 160 230 350 500 480 560 610 14 16 23 30 43 54 73 93 105 125 205 280 310 430 760

R (m) 1500 510 338 190 139 107 71 52 43 23 18 12 10,6 8,5 4 4,3 3,8 2100 800 550 300 220 197 134 96 79 45 35 24 20,5 18 11,7

P (W) 1,6 2 6 8 16 38 38 46 65 54 70 85 114 156 117 217 333 2 3 10 13 26 73 76 89 127 114 147 170 233 400 117

It (kAs) 0,09 0,28 0,5 0,6 1,15 1,29 3,2 5,2 7,2 23,3 34,9 58,3 90 140 440 500 654 0,09 0,34 0,45 0,53 0,94 1,4 3,1 4,5 5,9 18,8 33,5 59,6 84 93,6 350

Weight (kg) 1,6 1,6 1,6 1,6 1,6 1,6 1,6 1,6 1,6 1,6 1,6 1,6 2,1 2,1 3,7 3,7 3,7 2,3 2,3 2,3 2,3 2,3 2,3 2,3 2,3 2,3 2,3 2,3 2,3 3,1 4,1 5,9

12

Limitor-P&-PT back-up fuse-links


according to

with and without controlled power dissipation CPD

IEC 60282-1

HV fuse-links

Time-current characterictics

Fig.4 3/7,2 kV

Fig.5 6/12 kV

Fig.6 10/24 kV

Fig.7 20/36 kV

13

Limitor-PD back-up fuse-links


according to VDE

without controlled power dissipation CPD

0670 T402

HV fuse-links

Selection table
Rated voltage range of fuse-link [kV] Service voltage of transformer [kV] Transformer output [kVA] Mode of protection Rated current of fuse-link [A] rel. short-circuit voltage 50 4,8 16 2,9 10 1,5 6,3 1 100 9,6 20-25 20-25 5,8 16 16 2,9 10 10 1,9 6,3 6,3 125 12 25-31,5 25-31,5 7,2 16 16 3,6 10 10 2,4 10 10 160 15,4 200 19,2 250 24,1 50-63 50-63 14,4 31,5-40 31,5-40 7,2 16-25 16-25 4,8 16-20 16-20 UK = 4% 315 30,3 63-80 63-80 18,2 40-50 40-50 9,1 25 25 6,1 20-25 20-25 400 38,5 80-100 80-100 23,1 50-63 50-63 11,5 25-31,5 25-31,5 7,7 25 25 500 48,1 630 60,6 800 77,1 160 160 46,2 100-125 100-125 23,1 63 63 15,4 40-50 40-50 UK = 5% 1000 96,3 160 160 57,7 100-125 125-160 28,9 63 63-80 19,2 40-50 40-50

3/7,2

Transformer rated current [A] with NH gG

31,5-40 40-50 31,5-40 40-50 9,2 20-25 20-25 4,6 16 16 3,1 10 10 11,5 25-31,5 25-31,5 5,8 16 16 3,8 16 16

100-125 125-160 100-125 125-160 28,9 63-80 63-80 14,4 31,5-40 31,5-40 9,6 25-31,5 25-31,5 36,4 80-100 80-100 18,2 40-50 40-50 12,1 31,5-40 31,5-40

with NH gTr Transformer rated current [A] with NH gG

6/12

10

with NH gTr Transformer rated current [A] with NH gG

10/24

20

with NH gTr Transformer rated current [A] with NH gG

20/36

30

with NH gTr

Table 1 Bold typed figures are preferred values

14

without controlled power dissipation CPD according to VDE

Limitor-PD back-up fuse-links 0670 T402

HV fuse-links

Catalogue Number 45DB72V6,3PD 45DB72V10PD 45DB72V16PD 45DB72V20PD 45DB72V25PD 45DB72V32PD 45DB72V40PD 45DB72V50PD 45DB72V63PD 45DB72V80PD 45DB72V100PD 45DB72V125PD 45DB72V160PD 45DB120V6,3PD 45DB120V10PD 45DB120V16PD 45DB120V20PD 45DB120V25PD 45DB120V32PD 45DB120V40PD 45DB120V50PD 45DB120V63PD 45DB120V80PD 45DB120V100PD 45DB120V125PD 45DB120V160PD 45DB240V6,3PD 45DB240V10PD 45DB240V16PD 45DB240V20PD 45DB240V25PD 45DB240V32PD 45DB240V40PD 45DB240V50PD 45DB240V63PD 45DB240V80PD 45DB240V100PD 45DB360V6,3PD 45DB360V10PD 45DB360V16PD 45DB360V20PD 45DB360V25PD 45DB360V32PD 45DB360V40PD 45DB360V50PD 45DB360V63PD Table 2

Reference Number S209293A T209294A V209295A W209296A X209297A Y209298A Z209299A A209300A M1000235A N1000236A P1000237A Q1000100A Q1000238A R1000239A S1000240A T1000241A V1000242A W1000243A X1000244A Y1000245A Z1000246A A1000247A B1000248A C1000249A D1000250A E1000251A F1000252A G1000253A H1000254A J1000255A K1000256A L1000257A M1000258A N1000259A P1000260A Q1000261A R1000262A S209362A T209363A V209364A W209365A X209366A Y209367A Z209368A J1000117A K1000118A

Range Outdoor with striker Outdoor with striker Outdoor with striker Outdoor with striker Outdoor with striker Outdoor with striker Outdoor with striker Outdoor with striker Outdoor with striker Outdoor with striker Outdoor with striker Outdoor with striker Outdoor with striker Outdoor with striker Outdoor with striker Outdoor with striker Outdoor with striker Outdoor with striker Outdoor with striker Outdoor with striker Outdoor with striker Outdoor with striker Outdoor with striker Outdoor with striker Outdoor with striker Outdoor with striker Outdoor with striker Outdoor with striker Outdoor with striker Outdoor with striker Outdoor with striker Outdoor with striker Outdoor with striker Outdoor with striker Outdoor with striker Outdoor with striker Outdoor with striker Outdoor with striker Outdoor with striker Outdoor with striker Outdoor with striker Outdoor with striker Outdoor with striker Outdoor with striker Outdoor with striker Outdoor with striker

Un (kV) 3/7,2 3/7,2 3/7,2 3/7,2 3/7,2 3/7,2 3/7,2 3/7,2 3/7,2 3/7,2 3/7,2 3/7,2 3/7,2 6/12 6/12 6/12 6/12 6/12 6/12 6/12 6/12 6/12 6/12 6/12 6/12 6/12 10/24 10/24 10/24 10/24 10/24 10/24 10/24 10/24 10/24 10/24 10/24 20/36 20/36 20/36 20/36 20/36 20/36 20/36 20/36 20/36

In (A) 6,3 10 16 20 25 31,5 40 50 63 80 100 125 160 6,3 10 16 20 25 31,5 40 50 63 80 100 125 160 6,3 10 16 20 25 31,5 40 50 63 80 100 6,3 10 16 20 25 31,5 40 50 63

L (mm) 192 192 192 192 192 192 192 192 192 192 192 192 192 292 292 292 292 292 292 292 292 292 292 292 292 292 442 442 442 442 442 442 442 442 442 442 442 537 537 537 537 537 537 537 537 537

D (mm) 56 56 56 56 56 56 56 56 65 65 78 88 88 56 56 56 56 56 56 56 56 65 65 78 88 88 56 56 56 56 56 56 56 65 65 65 88 56 56 56 56 56 65 65 88 88

I1 (kA) 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 31,5 31,5 31,5 31,5 31,5 31,5 20 20 20

I3 (A) 21 38 65 92 110 123 140 194 220 300 440 440 610 23 35 64 90 95 110 134 190 220 345 400 480 610 23 36 73 91 116 125 161 230 350 460 420 23 34 70 100 110 135 200 220 280

R (m) 256 144 41 32 25 19 12,5 9,25 7 5,2 4 3 2,3 409 231 69 53 41 31 20 16,7 11,7 8,7 6,7 4,9 3,8 640 386 127 97 74 61 43 35 25 19 14 827 463 210 147 125 85 65 42 35

P (W) 11 19 13 14,5 20 23 30 35 60 85 96 75 120 19 29 21 25 31 39 46 62 60 82 96 117 175 32 48 43 53 64 85 103 116 163 196 279 39 65 67 84 100 119 176 183 271

It (kAs) 0,8 3 2,34 3,9 4,9 7 14 25,3 61,7 87,4 180 440 654 0,8 3 3,7 4,7 4,92 7 14 25,3 63 87 180 440 654 0,8 2 2,34 3,9 6,5 7 14,2 24,2 46,4 104 140 0,6 2 2,34 3,9 6,5 7 14,2 40 61,7

Weight (kg) 1,1 1,1 1,1 1,1 1,1 1,1 1,1 1,1 1,4 1,4 2 2,4 2,4 1,6 1,6 1,6 1,6 1,6 1,6 1,6 1,6 2,1 2,1 3,1 3,7 3,7 2,3 2,3 2,3 2,3 2,3 2,3 2,3 3,1 3,1 3,1 4,1 2,7 2,7 2,7 2,7 2,7 3,7 3,7 6,5 6,5

15

with controlled power dissipation CPD according to VDE


Application

Limitor-PTD back-up fuse-links 0670 T402

HV fuse-links

Limitor HV fuse-links type CPD meet the requirements of VDE 0670 T402 and were specifically developed to be installed in compact sized enclosed SF6 insulated sub-stations. In these substations HV fuse-links are enclosed in narrow fuse compartments which on the one hand prevent efficient cooling of the fuse-links and on the other hand have a limited thermal power acceptance themselves(as a rule about 75 W). Overheating of fuse compartments in such enclosures is, however, not to be expected, if the fuse-links have been properly selected by their rated current according to the transformer to be protected (see table 3) and if the melting elements of the fuse-links are in faultless condition (Fig. 9). One or more of the melting elements connected in parallel may, however, be interrupted by transient currents caused by transformer inrush or lightning strikes. Fuse-links having one or more of the paralleled melting elements interrupted, dissipate significantly more heat than faultless fuse-links. There is a certain risk that the limited power acceptance of fuse compartments may be exceeded at or even below rated transformer current. HV back-up fuse-links type CPD prevent such potential overheating when installed in conjunction with a transformer switch having trip-free mechanism. Transformer operating current to rating current IB/IN
Fig. 9 Power dissipation of HV fuse-links 40 A and 50 A for a 20 kV, 630 kVA transformer

Power dissipation Pa of HV fuse-link [W]

As a rule, the power acceptance of fuse compartments in SF6 insulated switchgear is limited, to e.g. 75 W. In order to prevent thermal overheating, the power dissipation Pa of the fuse-link must not exceed this value: Pa 75 W. The CPD striker system controls the power dissipation of the fuse-link according to Ohms law (CPD means controlled power dissipation). The striker pin is released depending on the voltage drop across the fuse-link and, therefore depending on the power dissipation: Ua = R IB Ua IB = Pa 75 W 630 kVA-Transformer; 40 A fuse-link The release voltage Ua of the CPD striker system has been selected so that the fuse carrying the operating current IB does not exceed the limiting value, e.g. 75 W, when the resistance R of the fuse-link increases because of interrupted melting elements. In this case the CPD striker system controls the power dissipation of the fuse-link and releases the transformer switch before the permissible power acceptance of the fuse compartment will be exceeded (Fig. 10). Power dissipation acc.to perm.value of the switch gear

Function mode

Fig. 10 Controlled power dissipation at 1.3 times transformer rated current

16

Voltage drop acc.to the release of the HV Fuse-link

with controlled power dissipation CPD according to VDE

Limitor-PTD back-up fuse-links 0670 T402

Benefits of thermal protection of the fuse compartment by CPD: CPD controls the power dissipation of the fuse-links CPD is based on Ohms law CPD works independent on the mounting position of the fuse-links CPD releases the striker, before an overheating is reached CPD mechanism is non-ageing

HV fuse-links

Selection table
Rated voltage range of fuse-link [kV] Service voltage of transformer [kV] Transformer output [kVA] Mode of protection Rated current of fuse-link [A] Transformer rated current [A] Rated current of fuse-link [A] 10 Power dissipation of HV fuse-links at rated current of transformer [W] Transformer rated current [A] Rated current of fuse-link [A] 20 Power dissipation of HV fuse-links at rated current of transformer [W] Transformer rated current [A] Rated current of fuse-link [A] 30 Power dissipation of HV fuse-links at rated current of transformer [W] rel. short-circuit voltage 100 125 5,8 16 7,2 16 160 9,2 20 200 11,4 25 250 14,4 31,5 315 18,2 40 UK = 4% 400 23,1 50 500 28,9 63 630 36,4 80 800 46,2 100 UK = 5% 1000 57,7 125

6/12

2,4

3,6

4,5

5,3

6,7

8,6

10,7

10,4

13,1

20,8

18,3

10/24

2,9 10

3,6 10

4,6 16

5,8 16

7,2 16 25 7,2 3,8 4,8 16

9,1 25

11,6 25 31 10,2 8,3 7,7 25

14,4 31,5

18,2 40

23,1 63

28,9 63

3,3

2,9

4,6

6,2

13

15,2

14

22,7

20/36

1,9 6,3

2,4 10

3,1 10

3,8 16

6,1 20

9,6 25

12,1 31,5

15,4 40

19,2 40 50 27,6 17,3

2,8

4,7

4,5

5,6

6,5

10

12,3

16,9

Table 3

17

with controlled power dissipation CPD according to VDE

Limitor-PTD back-up fuse-links 0670 T402


Un (kV) 6/12 6/12 6/12 6/12 6/12 6/12 6/12 6/12 6/12 6/12 6/12 6/12 10/24 10/24 10/24 10/24 10/24 10/24 10/24 10/24 10/24 10/24 10/24 20/36 20/36 20/36 20/36 20/36 20/36 20/36 20/36 In (A) 10 16 20 25 31,5 40 50 63 80 100 125 160 6,3 10 16 20 25 31,5 40 50 63 80 100 6,3 10 16 20 25 31,5 40 50 L (mm) 292 292 292 292 292 292 292 292 292 292 292 292 442 442 442 442 442 442 442 442 442 442 442 537 537 537 537 537 537 537 537

HV fuse-links

Catalogue Number 45DB120V10PTD 45DB120V16PTD 45DB120V20PTD 45DB120V25PTD 45DB120V32PTD 45DB120V40PTD 45DB120V50PTD 45DB120V63PTD 45DB120V80PTD 45DB120V100PTD 45DB120V125PTD 45DB120V160PTD 45DB240V6,3PTD 45DB240V10PTD 45DB240V16PTD 45DB240V20PTD 45DB240V25PTD 45DB240V32PTD 45DB240V40PTD 45DB240V50PTD 45DB240V63PTD 45DB240V80PTD 45DB240V100PTD 45DB360V6,3PTD 45DB360V10PTD 45DB360V16PTD 45DB360V20PTD 45DB360V25PTD 45DB360V32PTD 45DB360V40PTD 45DB360V50PTD

Reference Number S1000263A T1000264A V1000265A W1000266A X1000267A Y1000268A Z1000269A A1000270A B1000271A C1000272A D1000273A E1000274A F1000275A G1000276A H1000277A J1000278A K1000279A L1000280A M1000281A N1000282A P1000283A Q1000284A R1000285A S1000286A T1000287A V1000288A W1000289A X1000290A Y1000291A Z1000292A A1000293A

Range Back-up, striker, CPD Back-up, striker, CPD Back-up, striker, CPD Back-up, striker, CPD Back-up, striker, CPD Back-up, striker, CPD Back-up, striker, CPD Back-up, striker, CPD Back-up, striker, CPD Back-up, striker, CPD Back-up, striker, CPD Back-up, striker, CPD Back-up, striker, CPD Back-up, striker, CPD Back-up, striker, CPD Back-up, striker, CPD Back-up, striker, CPD Back-up, striker, CPD Back-up, striker, CPD Back-up, striker, CPD Back-up, striker, CPD Back-up, striker, CPD Back-up, striker, CPD Back-up, striker, CPD Back-up, striker, CPD Back-up, striker, CPD Back-up, striker, CPD Back-up, striker, CPD Back-up, striker, CPD Back-up, striker, CPD Back-up, striker, CPD

D (mm) 56 56 56 56 56 56 56 65 65 65 88 88 56 56 56 56 56 56 56 65 65 65 78 56 56 56 56 56 65 65 88

I1 (kA) 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 31.5 31.5 31.5 31.5 31.5 31.5 20 20

I3 (A) 35 64 90 95 110 134 190 220 345 500 480 610 23 36 73 91 116 125 161 230 350 460 420 23 34 70 100 110 135 205 220

R (m) 227 66 51 40 30 20 15 12 8,7 8,1 4,5 4 640 386 127 97 73 57 41 35 24 19 14 889 529 190 153 118 82 63 41

P (W) 29 21 25 29 39 46 62 62 85 152 117 175 31 48 42 53 60 84 96 146 163 196 279 39 66 67 84 100 119 176 183

It (kAs) 3 3,7 4,7 4,9 7 14 25 63 87 140 430 670 0,8 2 2,3 3,9 6,5 7 14,2 24,2 46,4 104 140 0,6 2 2,35 3,9 6,5 7 14,2 40

Weight (kg) 1,6 1,6 1,6 1,6 1,6 1,6 1,6 2,1 2,1 2,1 3,7 3,7 2,3 2,3 2,3 2,3 2,3 2,3 2,3 3,1 3,1 3,1 4,1 2,7 2,7 2,7 2,7 2,7 3,7 3,7 6,5

Table 2

18

with and without controlled power dissipation CPD according to VDE

Limitor-PD&-PTD back-up fuse-links 0670 T402

Time-current characterictics

HV fuse-links

Fig.4 3/7,2 kV

Fig.5 6/12 kV

Fig.6 10/24 kV 6,3 A-40 A

Fig.7 10/24 kV 50 A-100 A

Fig.8 20/36 kV
19

Limitor-PTS back-up fuse-links


for switch-fuse combination according to VDE

0670 T402

Limitor-PTS is a series of DIN high voltage fuse-links designed with low power losses meeting high voltage switch-fuse combination. Limitor-PTS is designed for protecting transformers in conjunction with air and gas-insulated switchgear up to 3 MVA transformer power. This series is a good solution for high ratings. They are designed with monobloc fuse-elements and with a built-in thermal striker. Because of the new thermal striker patented by Mersen, the Limitor-PTS prevent overheating in the fuse compartment when installed with switchfuse combination. The new thermal striker releases before the permissible power acceptance is exceeded.

HV fuse-links

Features

Monobloc fuse-elements structure Built-in thermal striker (30mm release) patented by Mersen Extension adaptor New caps design for easier maintenance

Benefits

No overheating Compact switchgear Energy efficiency

New caps

Ratings Up to 160A for 12kV Up to 125A for 24kV Up to 80A for 36kV Standards IEC 60282-1 IEC 62271-105 VDE 0670 T402

20

Limitor-PTS back-up fuse-links


for switch-fuse combination according to VDE
Selection table
Rated voltage range of fuse-link [kV] Service voltage of transformer [kV] Transformer output [kVA] Mode of protection Rated current of fuse-link [A] Transformer rated current [A] Rated current of fuse-link [A] 10 Power dissipation of HV fuse-links at rated current of transformer [W] Transformer rated current [A] Rated current of fuse-link [A] 20 Power dissipation of HV fuse-links at rated current of transformer [W] Transformer rated current [A] Rated current of fuse-link [A] 30 Power dissipation of HV fuse-links at rated current of transformer [W] rel. short-circuit voltage 100 125 5,8 16 7,2 16 160 9,2 20 200 11,4 25 250 14,4 31,5 315 18,2 40 UK = 4% 400 23,1 50 500 28,9 63 630 36,4 80 800 46,2 100 UK = 5% 1000 57,7 125

0670 T402
HV fuse-links

6/12

2,4

3,6

4,5

5,3

6,7

8,6

10,7

10,4

13,1

20,8

18,3

10/24

2,9 10

3,6 10

4,6 16

5,8 16

7,2 16 25 7,2 3,8 4,8 16

9,1 25

11,6 25 31 10,2 8,3 7,7 25

14,4 31,5

18,2 40

23,1 63

28,9 63

3,3

2,9

4,6

6,2

13

15,2

14

22,7

20/36

1,9 6,3

2,4 10

3,1 10

3,8 16

6,1 20

9,6 25

12,1 31,5

15,4 40

19,2 40 50 27,6 17,3

2,8

4,7

4,5

5,6

6,5

10

12,3

16,9

Table 3

21

Limitor-PTS back-up fuse-links


for switch-fuse combination according to VDE
Catalogue Number 45DB120V10PTS2 45DB120V16PTS2 45DB120V20PTS2 45DB120V25PTS2 45DB120V32PTS2 45DB120V40PTS2 45DB120V50PTS2 45DB120V63PTS2 45DB120V80PTS2 45DB120V100PTS2 45DB120V125PTS2 45DB120V100PTS3 45DB120V125PTS3 45DB120V160PTS3 45DB240V10PTS 45DB240V16PTS 45DB240V20PTS 45DB240V25PTS 45DB240V32PTS 45DB240V40PTS 45DB240V50PTS 45DB240V63PTS 45DB240V80PTS 45DB240V100PTS 45DB240V125PTS 45DB360V10PTS 45DB360V16PTS 45DB360V20PTS 45DB360V25PTS 45DB360V32PTS 45DB360V40PTS 45DB360V50PTS 45DB360V63PTS 45DB360V80PTS Reference Number R1032945A S1032946A T1032947A V1032948A W1032949A X1032950A Y1032951A M1018313A N1018314A P1018315A Q1018316A R1018317A S1018318A V1018320A Z1032952A A1032953A B1032954A C1032955A D1032956A E1032957A X1018322A Y1018323A Z1018324A A1018325A B1018326A F1032958A G1032959A H1032960A J1032961A K1032962A L1032963A M1032964A C1018327A F1018330A Range Back-up, th. striker, CPD, S Back-up, th. striker, CPD, S Back-up, th. striker, CPD, S Back-up, th. striker, CPD, S Back-up, th. striker, CPD, S Back-up, th. striker, CPD, S Back-up, th. striker, CPD, S Back-up, th. striker, CPD, S Back-up, th. striker, CPD, S Back-up, th. striker, CPD, S Back-up, th. striker, CPD, S Back-up, th. striker, CPD, S Back-up, th. striker, CPD, S Back-up, th. striker, CPD, S Back-up, th. striker, CPD, S Back-up, th. striker, CPD, S Back-up, th. striker, CPD, S Back-up, th. striker, CPD, S Back-up, th. striker, CPD, S Back-up, th. striker, CPD, S Back-up, th. striker, CPD, S Back-up, th. striker, CPD, S Back-up, th. striker, CPD, S Back-up, th. striker, CPD, S Back-up, th. striker, CPD, S Back-up, th. striker, CPD, S Back-up, th. striker, CPD, S Back-up, th. striker, CPD, S Back-up, th. striker, CPD, S Back-up, th. striker, CPD, S Back-up, th. striker, CPD, S Back-up, th. striker, CPD, S Back-up, th. striker, CPD, S Back-up, th. striker, CPD, S

0670 T402
Un (kV) 6/12 6/12 6/12 6/12 6/12 6/12 6/12 6/12 6/12 6/12 6/12 6/12 6/12 6/12 10/24 10/24 10/24 10/24 10/24 10/24 10/24 10/24 10/24 10/24 10/24 20/36 20/36 20/36 20/36 20/36 20/36 20/36 20/36 20/36 In (A) 10 16 20 25 31,5 40 50 63 80 100 125 100 125 160 10 16 20 25 31,5 40 50 63 80 100 125 10 16 20 25 31,5 40 50 63 80 L (mm) 292 292 292 292 292 292 292 292 292 292 292 442 442 442 442 442 442 442 442 442 442 442 442 442 442 537 537 537 537 537 537 537 537 537 D (mm) 56 56 56 56 56 56 56 65 65 78 88 78 78 78 56 56 56 56 56 56 65 78 78 88 88 56 56 56 56 65 65 88 88 88 I1 (kA) 65 65 65 65 65 65 65 80 80 80 80 80 80 80 65 65 65 65 65 65 65 65 65 65 65 31,5 31,5 31,5 31,5 20 20 20 36 36 I3 (A) 35 64 90 95 110 134 190 260 280 350 440 350 440 600 36 73 91 113 125 161 230 250 280 350 440 34 66 95 110 135 200 220 260 350 R (m) 227 66 51 40 30 20 15 11,9 9,6 7,5 5,3 7,5 5,4 4,1 386 127 97 73 57 41 27,4 21,6 17,3 13,6 10,1 529 190 153 118 82 63 40 31,9 24,2 P (W) 29 21 25 29 39 46 62 58 82 105 110 95 105 145 48 42 53 60 84 96 82 102 153 200 254 66 67 84 100 119 176 183 165 230 Total It Weight (KAs) (kg) 3 3,7 4,7 4,92 7 14 25,3 57 90 145 296 150 300 500 0,8 2 2,34 3,9 6,5 7 39 63 99 159 290 2 2,34 3,9 6,5 7 14,2 40 65 11,2 1,6 1,6 1,6 1,6 1,6 1,6 1,6 2,1 2,1 2,3 2,5 3,3 3,3 3,3 2,3 2,3 2,3 2,3 2,3 2,3 3,1 3,3 3,3 4,1 4,1 2,7 2,7 2,7 2,7 3,7 3,7 6,5 6,5 6,5

HV fuse-links
22

Limitor-PTS back-up fuse-links


for switch-fuse combination according to VDE

0670 T402
HV fuse-links

Time-current characterictics
12 kV - 292mm 12 kV - 442mm

Actual prearcing time (s)

rms value of prearc current (A) +/- 10%

Actual prearcing time (s)

rms value of prearc current (A) +/- 10%

24 kV

36 kV

Actual prearcing time (s)

rms value of prearc current (A) +/- 10%

Actual prearcing time (s)

rms value of prearc current (A) +/- 10%

23

Limitor fuse-links dimensions


HV fuse-links
Dimensions in mm

Un (kV) 3 / 7,2 6 / 12 10 / 17,5 10 / 24 20 / 36

e 192 292 367 442 537

24

Limitor fuse-links accessories Clips


Size MR 45 + spring MR 45 without connection lug Reference Number L096472A S210236B Catalog Number MR45R MR55R Packaging 1 2

HV fuse-links

Bases
Voltage (kV) 7,2 12 17,5 24 36 12 17,5 24 36 Size SI 7,2/192 SI 12/292 SI 17,5/292 SI 24/442 SI 36/537 SE 12/292 SE 17,5/292 SE 24/442 SE 36/537 Use Indoor Indoor Indoor Indoor Indoor Outdoor Outdoor Outdoor Outdoor Reference Number G209421A H209422A J209423A K209424A M209426A S210328A T210329A V210330A W210331A Catalog Number SI72V192 SI120V292 SI175V292 SI240V442 SI360V537 SE120V292 SE175V292 SE240V442 SE360V537 Packaging 1 1 1 1 1 1 1 1 1

Dimensions in mm

Voltage (kV) 7,2 12 17,5 24 36 12 17,5 24 36

Length of fuse L (mm) 192 292 292 442 537 292 292 442 537

Dielectric withstand (phase to ground) Size SI 7,2/192 SI 12/292 SI 17,5/292 SI 24/442 SI 36/537 SE 12/292 SE 17,5/292 SE 24/442 SE 36/537 50Hz-1mn Kv Rms 20 28 38 50 70 28 38 50 70 1,2/50s peak voltage 60 75 95 125 170 75 95 125 170

Dimensions (mm)

A
400 424 424 576 670 424 424 576 670

B
226 324 324 476 570 324 324 476 570

C
322 200 200 270 350 200 200 270 350

D
347 445 445 597 691 445 445 597 691

E
175 175 220 270 354 261 261 309 381

F
270 270 315 365 449 356 356 404 476

Weight (kg) 3,8 4,1 5,1 5,5 7,7 7,5 7,5 8,8 13,2

25

Indicating devices
Voltage (kV) 12/36 12/36 Number of contacts 1 NO/NF 2 NO/NF Length of flexible part (mm) 550 550 L (mm) 710 710 Reference Number E092855A F092856A Catalog Number MC1-5NFLEXQS500 MC1-9NFLEXQS500 Packaging 1 1

HV fuse-links

Neutral conductors
Lenght (mm) 292 442 Reference Number J1006419A L1006421A Catalog Number 45DB292NEUTRAL 45DB442NEUTRAL Packaging 1 1

Dimensions in mm

External adaptor 292/442mm


Reference Number H1026244A Catalog Number ADAPTOR292/442 Packaging 1

Dimensions in mm

26

Notes

27

Main production sites Industrial or commercial branch

A WORLD LEADER
in safety & reliability for electrical power

A GLOBAL PLAYER
Global expert in materials and equipment for extreme environments and in the safety  and reliability of electrical equipment.  Mersen designs innovative solutions to address its clients specific needs to enable them to optimize  their manufacturing process in sectors such as Energy, Transportation, Electronics, Chemical, Pharmaceutical and Process Industries.

Mersen France SB S.A.S. Rue Jacques de Vaucanson F-69720 Saint-Bonnet-de-Mure Tel : + 33 4 72 22 66 11 www.mersen.com

MERSEN Shanghai Co. Ltd. No.55-A6. Shu Shan Road, Songjiang 201611 Shanghai Tel: +8621 67602388 www.mersen.com www.mersen.com

MERSEN USA Newburyport-MA L.L.C. 374 Merrimac Street Newburyport, MA 01950 Phone: 978-462-6662 www.mersen.com

- 7418 - 02-2012