Cooling Plant Sizing Summary for HOTEL SEDA

HOTEL SEDA 9-18-13


ecoSolutions, Inc.

09/21/2013
12:05PM

1. Plant Information:
Plant Name ............................................................................... HOTEL SEDA
Plant Type .................................................................. Generic Chilled Water
Design Weather ............................................................... Manila, Philippines
2. Cooling Plant Sizing Data:
Maximum Plant Load ............................................................................ 4530.8 kW
Load occurs at ................................................................................ Jul 1800
m/kW ......................................................................................................... 5.4 m/kW
Floor area served by plant .................................................................. 24497.5 m
3. Coincident Air System Cooling Loads for Jul 1800

Air System Name


2 Ballrooms
2 Business Center
2 Chinese Restaurant
2 Exhibit Space
2 FT Exhibit
2 Kitchen
2 Meeting Rm 1
2 Meeting Rm 2
2 Meeting Rm 3
2 Meeting Rm 4
2 Meeting Rm 5
2 Meeting Rm 6
2 MT Exhibit
2 Pre Function
21 Corridor/Lobby
21 L Suite Room
21 SE lobby
21 Standard Rm 1
21 Standard Rm 2
21 Standard Rm 3
21 Standard Rm 4
21 Standard Rm 5
21 Standard Rm 6
21 Standard Rm 8
21 Standard Rm 9
21 Suite Room 2
21 Suite Room 3
21 Suite Room 4
21 Suite Room 5
22 Corridor
22 E. Lounge FT
22 E. Lounge MT
22 Elev lobby
22 Executive Lounge
22 Kit
22 Lobby at toilet
22 Meeting Room
22 Private Lounge
22 SE lobby
22 Standard Rm 1
22 Standard Rm 10
22 Standard Rm 11
22 Standard Rm 12
Hourly Analysis Program v4.51

Mult.
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

System
Cooling
Coil Load
( kW )
475.5
5.5
178.1
57.5
1.8
17.4
10.6
10.7
12.6
12.8
33.4
27.4
1.2
60.0
7.3
19.7
1.1
4.1
4.1
4.1
4.1
4.1
4.1
4.1
4.1
9.8
8.1
6.0
11.5
2.7
1.2
1.2
1.4
49.3
6.7
1.3
10.4
9.4
1.1
8.1
4.8
4.8
5.4
Page 1 of 12

Cooling Plant Sizing Summary for HOTEL SEDA


HOTEL SEDA 9-18-13
ecoSolutions, Inc.

Air System Name


22 Standard Rm 2
22 Standard Rm 3
22 Standard Rm 4
22 Standard Rm 5
22 Standard Rm 6
22 Standard Rm 7
22 Standard Rm 8
22 Standard Rm 9
22 Suite Room 1
22 Suite Room 2
23 Bar
23 Corridor/Lobby
23 FT
23 Kit
23 MT
23 SE lobby
23 Storage
2M Admin Office
2M Corridor/Lobby
2M FT
2M MT
2M Office 1
2M Office 2
3 Corridor/Lobby
3 FT
3 Gym
3 MT
3 Pantry
3 Part Of Gym
3 Preparation Area
3 Salon
3 SPA
4-20 Corridor/Lobby
4-20 SE lobby
4-20 Standard Rm 1
4-20 Standard Rm 10
4-20 Standard Rm 11
4-20 Standard Rm 12
4-20 Standard Rm 13
4-20 Standard Rm 14
4-20 Standard Rm 15
4-20 Standard Rm 16
4-20 Standard Rm 17
4-20 Standard Rm 18
4-20 Standard Rm 19
4-20 Standard Rm 2
4-20 Standard Rm 3
4-20 Standard Rm 4
4-20 Standard Rm 5
4-20 Standard Rm 6
4-20 Standard Rm 7
4-20 Standard Rm 8
4-20 Standard Rm 9
4-20 Suite Rm 1

Hourly Analysis Program v4.51

09/21/2013
12:05PM

Mult.
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17
17

System
Cooling
Coil Load
( kW )
8.1
8.1
8.1
8.1
8.1
8.1
5.4
4.8
21.6
15.8
122.8
13.3
2.9
25.8
2.0
1.1
11.5
34.1
5.0
0.6
0.6
4.8
9.3
8.3
1.2
124.6
1.7
5.2
10.7
3.4
29.9
84.1
7.1
1.1
4.1
4.1
4.1
4.1
4.1
6.0
6.1
4.7
4.7
4.2
4.2
4.1
4.1
4.1
4.1
4.1
4.1
4.1
4.1
13.4

Page 2 of 12

Cooling Plant Sizing Summary for HOTEL SEDA


HOTEL SEDA 9-18-13
ecoSolutions, Inc.

Air System Name


4-20 Suite Rm 2
4-20 Suite Rm 3
4-20 Suite Rm 4
B1 Carpet/ Linen
B1 Corridor
B1 Engineering Dept
B1 F Changing Room
B1 FCC Room
B1 General Store
B1 Housekeeping Dept
B1 HR Director
B1 Human Resource Dept
B1 IT/Data rm
B1 Laundry
B1 M Changing Room
B1 Nurse Station
B1 Office Corridor
B1 Part Engineering Dept
B1 Payroll Office
B1 Purchasing/Rcv office
B1 SE
B1 Security Office
B1 Skycable/Telco
B1 Staff Dining Room
B1 Store Man. Office
B1 Training Room
G All Day Dine
G FT All Day Dine
G FT Lobby
G General Office
G Japanese Resto
G Kitchen
G Main Lobby
G MT All Day Dine
G MT Lobby

09/21/2013
12:05PM

Mult.
17
17
17
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

System
Cooling
Coil Load
( kW )
9.8
8.1
6.0
3.2
12.3
6.6
6.4
1.4
3.5
11.1
2.8
7.4
9.2
11.9
6.7
2.7
1.7
7.8
2.3
2.8
1.6
5.8
9.8
26.4
1.7
9.0
225.0
1.5
1.3
24.4
58.2
22.9
143.6
1.2
1.0

System loads are for coils whose cooling source is ' Chilled Water ' or ' Any ' .

Hourly Analysis Program v4.51

Page 3 of 12

Hourly Chiller Load Profiles for HOTEL SEDA


HOTEL SEDA 9-18-13
ecoSolutions, Inc.

09/21/2013
12:05PM

1. Plant Information:
Plant Name ............................................................................... HOTEL SEDA
Plant Type .................................................................. Generic Chilled Water
Design Weather ............................................................... Manila, Philippines
2. Chiller Load Profiles from January to December :

Hour
0000
0100
0200
0300
0400
0500
0600
0700
0800
0900
1000
1100
1200
1300
1400
1500
1600
1700
1800
1900
2000
2100
2200
2300

DESIGN MONTH: JANUARY


DESIGN MONTH: FEBRUARY
DESIGN MONTH: MARCH
OA
TOTAL
OA
TOTAL
OA
TOTAL
TEMP
COOLING
TEMP
COOLING
TEMP
COOLING
( C )
( kW )
( C )
( kW )
( C )
( kW )
22.2
1211.6
23.4
1381.2
25.0
1622.5
21.8
1105.6
22.9
1279.6
24.6
1523.1
21.4
969.8
22.5
1123.7
24.1
1382.1
21.0
918.8
22.1
1054.6
23.8
1293.3
20.8
811.5
21.9
971.9
23.5
1200.8
20.7
478.0
21.8
549.3
23.4
666.2
20.8
473.1
22.0
536.0
23.6
677.5
21.3
906.4
22.4
1061.6
24.1
1290.1
22.1
1122.0
23.2
1253.8
24.8
1497.8
23.2
1157.8
24.3
1349.0
26.0
1599.7
24.5
1307.0
25.6
1457.6
27.3
1700.1
26.0
1487.5
27.1
1616.5
28.8
1826.2
27.4
1584.8
28.5
1706.1
30.2
1914.2
28.5
1540.6
29.6
1652.9
31.3
1862.1
29.2
1519.0
30.3
1632.1
32.0
1844.3
29.4
3244.3
30.6
3541.7
32.2
3951.7
29.2
3234.6
30.3
3540.4
32.0
3956.1
28.6
3249.1
29.7
3587.7
31.3
3986.8
27.6
3337.7
28.7
3619.7
30.4
4054.2
26.5
2796.4
27.6
3089.2
29.2
3497.2
25.3
2582.7
26.4
2819.2
28.1
3230.9
24.4
2111.4
25.5
2395.0
27.1
2736.9
23.5
1820.5
24.6
2077.2
26.3
2455.7
22.8
1319.2
23.9
1500.2
25.6
1724.9
Total Ton-hrs
40289.5
44796.2
51494.2

Hourly Analysis Program v4.51

Page 4 of 12

Hourly Chiller Load Profiles for HOTEL SEDA


HOTEL SEDA 9-18-13
ecoSolutions, Inc.

Hour
0000
0100
0200
0300
0400
0500
0600
0700
0800
0900
1000
1100
1200
1300
1400
1500
1600
1700
1800
1900
2000
2100
2200
2300

DESIGN MONTH: APRIL


DESIGN MONTH: MAY
OA
TOTAL
OA
TEMP
COOLING
TEMP
( C )
( kW )
( C )
25.6
1752.9
26.1
25.1
1608.0
25.7
24.7
1480.8
25.3
24.4
1392.6
24.9
24.1
1305.6
24.6
24.0
716.9
24.6
24.2
752.3
24.7
24.6
1386.5
25.2
25.4
1589.9
26.0
26.5
1715.7
27.1
27.9
1829.2
28.4
29.4
1953.1
29.9
30.8
2020.0
31.3
31.8
1978.4
32.4
32.5
1932.9
33.1
32.8
4120.6
33.3
32.5
4113.3
33.1
31.9
4125.1
32.5
30.9
4189.0
31.5
29.8
3640.8
30.3
28.7
3410.6
29.2
27.7
2932.4
28.2
26.8
2613.6
27.4
26.1
1847.3
26.7
Total Ton-hrs
54407.7

Hourly Analysis Program v4.51

09/21/2013
12:05PM

TOTAL
COOLING
( kW )
1853.1
1721.9
1569.6
1479.2
1375.4
752.7
800.4
1474.1
1688.8
1799.9
1922.6
2050.7
2105.8
2077.7
2048.2
4245.0
4219.2
4249.2
4311.4
3766.1
3555.3
3123.7
2778.3
1970.7
56939.1

DESIGN MONTH: JUNE


OA
TEMP
( C )
27.2
26.8
26.4
26.0
25.8
25.7
25.8
26.3
27.1
28.2
29.5
31.0
32.4
33.5
34.2
34.4
34.2
33.6
32.6
31.5
30.3
29.4
28.5
27.8

TOTAL
COOLING
( kW )
1992.4
1849.3
1716.3
1593.4
1520.8
816.5
845.5
1563.7
1755.0
1898.7
2028.6
2137.9
2212.0
2166.5
2132.7
4399.0
4374.9
4417.6
4493.7
3934.6
3708.3
3328.5
2977.1
2113.0
59975.9

Page 5 of 12

Hourly Chiller Load Profiles for HOTEL SEDA


HOTEL SEDA 9-18-13
ecoSolutions, Inc.

Hour
0000
0100
0200
0300
0400
0500
0600
0700
0800
0900
1000
1100
1200
1300
1400
1500
1600
1700
1800
1900
2000
2100
2200
2300

Hour
0000
0100
0200
0300
0400
0500
0600
0700
0800
0900
1000
1100
1200
1300
1400
1500
1600
1700
1800
1900
2000
2100
2200
2300

DESIGN MONTH: JULY


OA
TEMP
( C )
27.8
27.4
26.9
26.6
26.3
26.2
26.4
26.8
27.6
28.8
30.1
31.6
33.0
34.0
34.7
35.0
34.7
34.1
33.2
32.0
30.9
29.9
29.0
28.3
Total Ton-hrs

09/21/2013
12:05PM

TOTAL
COOLING
( kW )
2031.4
1897.3
1742.1
1653.2
1546.4
826.7
835.1
1570.4
1772.2
1906.8
2027.7
2147.7
2221.0
2158.8
2157.4
4427.4
4418.8
4472.2
4530.8
3972.9
3755.3
3365.0
3034.8
2137.8
60609.0

DESIGN MONTH: AUGUST


DESIGN MONTH: SEPTEMBER
OA
TOTAL
OA
TOTAL
TEMP
COOLING
TEMP
COOLING
( C )
( kW )
( C )
( kW )
27.8
1994.5
26.7
1789.7
27.4
1861.1
26.3
1708.5
26.9
1713.9
25.8
1540.8
26.6
1617.2
25.5
1451.9
26.3
1526.0
25.2
1386.0
26.2
825.6
25.1
751.8
26.4
816.5
25.3
769.1
26.8
1544.0
25.7
1431.5
27.6
1759.3
26.5
1630.5
28.8
1870.7
27.7
1741.5
30.1
2003.4
29.0
1854.0
31.6
2123.0
30.5
1982.0
33.0
2203.0
31.9
2073.3
34.0
2140.0
32.9
2026.9
34.7
2133.2
33.6
2005.8
35.0
4404.9
33.9
4209.9
34.7
4398.2
33.6
4191.1
34.1
4427.4
33.0
4171.2
33.2
4515.5
32.0
4283.9
32.0
3948.6
30.9
3747.3
30.9
3734.6
29.8
3505.9
29.9
3337.1
28.8
3022.0
29.0
2965.1
27.9
2700.7
28.3
2108.3
27.2
1913.8
59971.2
55889.2

DESIGN MONTH: OCTOBER


DESIGN MONTH: NOVEMBER
DESIGN MONTH: DECEMBER
OA
TOTAL
OA
TOTAL
OA
TOTAL
TEMP
COOLING
TEMP
COOLING
TEMP
COOLING
( C )
( kW )
( C )
( kW )
( C )
( kW )
25.6
1646.4
23.9
1443.7
22.8
1253.4
25.1
1553.4
23.5
1335.4
22.4
1144.7
24.7
1411.6
23.0
1164.3
21.9
1030.8
24.4
1335.4
22.7
1090.5
21.6
949.7
24.1
1226.2
22.4
1000.7
21.3
851.3
24.0
692.7
22.3
566.8
21.2
504.2
24.2
714.6
22.5
575.6
21.4
503.2
24.6
1310.3
22.9
1085.9
21.8
962.0
25.4
1509.2
23.7
1331.8
22.6
1154.8
26.5
1596.9
24.9
1424.6
23.8
1260.0
27.9
1714.8
26.2
1529.9
25.1
1382.3
29.4
1874.1
27.7
1708.0
26.6
1544.4
30.8
1948.6
29.1
1805.1
28.0
1642.6
31.8
1914.0
30.1
1763.2
29.0
1608.4
32.5
1876.9
30.8
1730.0
29.7
1575.1
32.8
3994.7
31.1
3641.1
30.0
3334.3
32.5
3956.1
30.8
3603.0
29.7
3302.0
31.9
3916.7
30.2
3601.4
29.1
3328.8
30.9
4026.9
29.3
3704.9
28.2
3409.4
29.8
3478.0
28.1
3154.3
27.0
2875.1
28.7
3216.5
27.0
2944.3
25.9
2653.9
27.7
2783.0
26.0
2470.1
24.9
2216.4
26.8
2455.7
25.1
2191.7
24.0
1907.5
26.1
1753.4
24.4
1536.6
23.3
1345.4
Total Ton-hrs
51906.2
46402.8
41739.5

Hourly Analysis Program v4.51

Page 6 of 12

Chiller Design Day Loads for HOTEL SEDA


HOTEL SEDA 9-18-13
ecoSolutions, Inc.

09/21/2013
12:05PM

Data for January

3000

Chiller Load (kW)

2500
2000
1500
1000
500
0
00

02
01

04
03

06
05

08
07

10
09

12
14
16
18
20
22
11
13
15
17
19
21
23
Hour of Day

Data for February


3500

Chiller Load (kW)

3000
2500
2000
1500
1000
500
0
00

02
01

Hourly Analysis Program v4.51

04
03

06
05

08
07

10
09

12
14
16
18
20
22
11
13
15
17
19
21
23
Hour of Day

Page 7 of 12

Chiller Design Day Loads for HOTEL SEDA


HOTEL SEDA 9-18-13
ecoSolutions, Inc.

09/21/2013
12:05PM

Data for March


4000
3500

Chiller Load (kW)

3000
2500
2000
1500
1000
500
0
00

02
01

04
03

06
05

08
07

10
09

12
14
16
18
20
22
11
13
15
17
19
21
23
Hour of Day

Data for April


4000

Chiller Load (kW)

3500
3000
2500
2000
1500
1000
500
0
00

02
01

Hourly Analysis Program v4.51

04
03

06
05

08
07

10
09

12
14
16
18
20
22
11
13
15
17
19
21
23
Hour of Day

Page 8 of 12

Chiller Design Day Loads for HOTEL SEDA


HOTEL SEDA 9-18-13
ecoSolutions, Inc.

09/21/2013
12:05PM

Data for May


4000

Chiller Load (kW)

3500
3000
2500
2000
1500
1000
500
0
00

02
01

04
03

06
05

08
07

10
09

12
14
16
18
20
22
11
13
15
17
19
21
23
Hour of Day

Data for June


4500
4000

Chiller Load (kW)

3500
3000
2500
2000
1500
1000
500
0
00

02
01

Hourly Analysis Program v4.51

04
03

06
05

08
07

10
09

12
14
16
18
20
22
11
13
15
17
19
21
23
Hour of Day

Page 9 of 12

Chiller Design Day Loads for HOTEL SEDA


HOTEL SEDA 9-18-13
ecoSolutions, Inc.

09/21/2013
12:05PM

Data for July


4500
4000

Chiller Load (kW)

3500
3000
2500
2000
1500
1000
500
0
00

02
01

04
03

06
05

08
07

10
09

12
14
16
18
20
22
11
13
15
17
19
21
23
Hour of Day

Data for August


4500
4000

Chiller Load (kW)

3500
3000
2500
2000
1500
1000
500
0
00

02
01

Hourly Analysis Program v4.51

04
03

06
05

08
07

10
09

12
14
16
18
20
22
11
13
15
17
19
21
23
Hour of Day

Page 10 of 12

Chiller Design Day Loads for HOTEL SEDA


HOTEL SEDA 9-18-13
ecoSolutions, Inc.

09/21/2013
12:05PM

Data for September


4000

Chiller Load (kW)

3500
3000
2500
2000
1500
1000
500
0
00

02
01

04
03

06
05

08
07

10
09

12
14
16
18
20
22
11
13
15
17
19
21
23
Hour of Day

Data for October


4000
3500

Chiller Load (kW)

3000
2500
2000
1500
1000
500
0
00

02
01

Hourly Analysis Program v4.51

04
03

06
05

08
07

10
09

12
14
16
18
20
22
11
13
15
17
19
21
23
Hour of Day

Page 11 of 12

Chiller Design Day Loads for HOTEL SEDA


HOTEL SEDA 9-18-13
ecoSolutions, Inc.

09/21/2013
12:05PM

Data for November


3500

Chiller Load (kW)

3000
2500
2000
1500
1000
500
0
00

02
01

04
03

06
05

08
07

10
09

12
14
16
18
20
22
11
13
15
17
19
21
23
Hour of Day

Data for December


3500

Chiller Load (kW)

3000
2500
2000
1500
1000
500
0
00

02
01

Hourly Analysis Program v4.51

04
03

06
05

08
07

10
09

12
14
16
18
20
22
11
13
15
17
19
21
23
Hour of Day

Page 12 of 12

S-ar putea să vă placă și