Sunteți pe pagina 1din 4

Text-Based Integration: Step by Step Procedure

To illustrate the needs for text-based integration in LabVIEW, consider an equation used to convert the resistance of a thermistor to the appropriate temperature in degrees Celsius.

Figure 1. Formula Used to Convert Resistance of a Thermistor to Temperature

You can see that this is a complex polynomial equation that requires many mathematical operations. While possible, this is something that can quickly become cluttered in LabVIEW and difcult to follow as seen in Figure 2:

Figure 2. Native LabVIEW Functions for Thermistor Formula

Figure 3 is an example of how the formula could be represented in a traditional text-based language such as C. This is a lot easier to understand, and it resembles closely the actual equation. Now look at how to implement this using the Formula Node and MathScript Node.

Figure 3. Text-Based Code Representation of Thermistor Formula

ni.com/students/learnlabview

LabVIEW Formula Node


Before starting this procedure, you need to complete the exercise and use the solution in the Taking a Measurement module. You can also create a numeric control to simulate the data acquisition input. Note: If you are not using a DAQ Assistant to acquire resistance data and convert to temperature, skip ahead to step 2 and use a numeric control in place of the DAQ Assistant. 1. Congure the voltage input DAQ Assistant to the input resistance from the digital multimeter (DMM) terminals a. Double-click the existing DAQ Assistant to edit the conguration b. Right-click the Voltage channel in the Channel Settings list box and select Remove from Task c. Click the blue plus (+) sign to add a channel to the task and select Resistance d. Select Dev1 (NI myDAQ) >> dmm e. Ensure Iex Source is set to Internal f. Ensure Acquisition Mode is set to 1 Sample (On Demand) g. Press OK to apply settings a. Right-click the block diagram and select Mathematics >> Scripts & Formulas >> Formula Node b. Paste the following equation into the Formula Node window and resize accordingly oat64 M; M=ln(R/10000); T=(1/(A+B*M+C*M*M+D*M*M*M))273.15; 3. Add inputs to the Formula Node for all input variables in the equation a. Right-click the left border and select Add Input b. Enter R0 to relate the input to the R0 variable in the equation c. Repeat this procedure for A, B, C, and D d. Right-click inputs A, B, C, D, and R0 and select Create >> Control e. A=0.0039083; B=5.775E-7; C=1.63214E-6; D=7 .1922E-8; R0=1000 f. Wire the Data output from the DAQ Assistant to the R input of the Formula Node a. Right-click the border and select Add Output b. Enter T to relate the output to the T variable in the equation c. Wire this output to the input of the graph indicator a. Right-click the block diagram and select Programming >> Structures >> While Loop b. Left-click and drag to encompass all of the code c. Right-click the conditional terminal and select Create >> Control

2. Place a Formula Node on the block diagram to convert resistance to degrees Celsius

4. Add output for Temperature (C) to display on the chart indicator

5. Add a While Loop to run the VI continuously

ni.com/students/learnlabview

6. Create the stop condition to include when the Stop button is pressed or an error is detected a. Unwire the Conditional Terminal from the Stopped output terminal of the analog input DAQ Assistant b. Right-click the block diagram and select Programming >> Boolean >> Or c. Wire the output from the Stop button control to the bottom input of the Or Boolean function d.  Right-click the block diagram and select Programming >> Cluster, Class, & Variant >> Unbundle by Name and place this to the right of the analog input DAQ Assistant e.  Wire the Error Out output terminal of the analog input DAQ Assistant to the input of the Unbundle by Name function and ensure Status is selected to be unbundled f. Wire the output of the Unbundle by Name function to the top input of the Or function g. Wire the output of the Or function to the input of the Conditional Terminal

7 . Run the VI and observe the result Get more help with the Formula Node and obtain a list of Formula Node Functions.

MathScript Node
You can also use the MathScript Node to run preexisting .m le scripts as well as develop .m les in LabVIEW for signal processing. Before starting this procedure, you need to complete the exercise and use the solution in the Taking a Measurement module. You can also create a numeric control to simulate the data acquisition input. Note: If you are not using a DAQ Assistant to acquire resistance data and convert to temperature, skip ahead to step 2 and use a numeric control in place of the DAQ assistant. 1. Congure the voltage input DAQ Assistant to the input resistance from the DMM terminals a. Double-click the existing DAQ Assistant to edit the conguration b. Right-click the Voltage channel in the Channel Settings list box and select Remove from Task c. Click the blue plus (+) sign to add a channel to the task and select Resistance d. Select Dev1 (NI myDAQ) >> dmm e. Ensure Iex Source is set to Internal f. Ensure Acquisition Mode is set to 1 Sample (On Demand) g. Press OK to apply settings a. Right-click the block diagram and select Mathematics >> Scripts & Formulas >> MathScript Node b. Paste the following script into the MathScript Node window and resize accordingly

2. Place a MathScript Node on the block diagram to convert resistance to degrees Celsius

double M; M=log(R/10000); T=(1/(A+B*M*M+C*M*M+D*M*M*M)); T=T273.15;

ni.com/students/learnlabview

3. Add inputs to the Formula Node for all input variables in the equation a. Right-click the left border and select Add Input b. Enter R to relate the input to the R variable in the equation c. Wire the Data output from the DAQ Assistant to the R input of the MathScript Node d. Repeat for variables A, B, C, and D e. Right-click inputs A, B, C, D, and R0 and select Create >> Control f. A=0.0039083; B=5.775E-7; C=1.63214E-6; D=7 .1922E-8; R0=1000 g. Wire the Data output from the DAQ Assistant to the R input of the MathScript Node a. Right-click the border and select Add Output b. Enter T to relate the output to the T variable in the equation c. Wire this output to the input of the graph indicator a. Right-click the block diagram and select Programming >> Structures >> While Loop b. Left-click and drag to encompass all of the code c. Right-click the conditional terminal and select Create >> Control a. Unwire the Conditional Terminal from the Stopped output terminal of the analog input DAQ Assistant b. Right-click the block diagram and select Programming >> Boolean >> Or c. Wire the output from the Stop button control to the bottom input of the Or Boolean function d.  Right-click the block diagram and select Programming >> Cluster, Class, & Variant >> Unbundle by Name and place this to the right of the analog input DAQ Assistant e.  Wire the Error Out output terminal of the analog input DAQ Assistant to the input of the Unbundle by Name function and ensure Status is selected to be unbundled f. Wire the output of the Unbundle by Name function to the top input of the Or function g. Wire the output of the Or function to the input of the Conditional Terminal

4. Add output for Temperature (C) to display on the chart indicator

5. Add a While Loop to run the VI continuously

6. Create the stop condition to include when the Stop button is pressed or an error is detected

7 . Run the VI and observe the result Get more help with the LabVIEW MathScript RT Module. You can convert your DAQ Assistant Express VIs into low-level NI-DAQmx functions by right-clicking the DAQ Assistant and selecting Generate NI-DAQmx Code. The low-level NI-DAQmx API exposes more functionality and customization options for programming.

2011 National Instruments. All rights reserved. LabVIEW, National Instruments, NI, and ni.com are trademarks of National Instruments. Other product and company names listed are trademarks or trade names of their respective companies.

ni.com/students/learnlabview