Sunteți pe pagina 1din 14

S7-200 Data Sheets

A.2

CPU 212 DC Power Supply, DC Inputs, DC Outputs

Order Number: 6ES7 2121AA010XB0


General Features Physical size (L x W x D) Weight Power dissipation User program size/storage User data size/storage Data retention Local I/O1 Maximum number of expansion modules Digital I/O supported Analog I/O supported Boolean execution speed Internal memory bits Timers Counters High-speed counters 160 x 80 x 62 mm (6.3 x 3.15 x 2.44 in.) 0.3 kg (0.7 lbs.) 5 W at 1.75 A load 512 words/EEPROM 512 words/RAM 50 hr typical (8 hr minimum at 40 C) 8 inputs/6 outputs 2 64 inputs/64 outputs 16 inputs/16 outputs 1.2 s/instruction 128 64 timers 64 counters 1 software (2 KHz max.) 1 UL 508 CSA C22.2 142 FM Class I, Division 2 VDE 0160 compliant CE compliant UL/CSA rating Holdup time Inrush current Sourcing transistor 20.4 VDC to 28.8 VDC 0 to 40 C 0.75 A 1.00 A 2.25 A 55 C2 0.50 A 0.75 A 1.75 A Fusing (non-replaceable) 5 VDC current Isolated DC Sensor Supply Voltage range Ripple/noise (<10MHz) 24 VDC available current Short-circuit current limit Isolated 16.4 to 28.8 VDC Same as supplied voltage 180 mA < 600 mA No Optical isolation Short circuit protection Input Points Input type (IEC 11312) ON state range ON state nominal OFF state maximum Response time I0.0 to I0.7 Optical isolation Power Supply Voltage range Input current 20.4 to 28.8 VDC 60 mA typical, CPU only 500 mA maximum load 50 VA 10 ms minimum from 24 VDC 10 A peak at 28.8 VDC 1 A, 125 V, slow blow 260 mA for CPU 340 mA for expansion I/O No Type 1 sinking 1530 VDC, 4 mA minimum 35 VDC, 500 ms surge 24 VDC, 7 mA 5 VDC, 1 mA 0.3 ms maximum 500 VAC, 1 min Output Points (continued) Switching delay Surge current Voltage drop 25 s ON, 120 s OFF 4 A, 100 ms 1.8 V maximum at maximum current 500 VAC, 1 min None

Analog adjustments Standards compliance

Output Points Output type Voltage range Maximum load current Per single point Per 2 adjacent points All points total Inductive load clamping Single pulse Repetitive Leakage current
1 2

(per common) 2A L/R = 10 ms 1A L/R = 100 ms 1 W energy dissipation (1/2 Li2 x switch rate t 1 W) 100 A

The CPU reserves 8 process-image input and 8 process-image output image register points for local I/O. Linear derate 40 to 55 C Vertical mount derate 10 C.

A-6

S7-200 Programmable Controller System Manual C79000G7076C23002

S7-200 Data Sheets

Outputs (20.4 to 28.8 VDC)

Power supply

DC 24V OUTPUTS

L+

0.0

0.1

0.2

0.3

0.4

0.5

L+

DC 24V

36V 36V 470 Note: 1. Actual component values may vary. 2. DC circuit grounds are optional.

3.3K
DC 24V INPUTS 1M 0.0 0.1 0.2 0.3 2M 0.4 0.5 0.6 0.7 M L+ DC SENSOR SUPPLY

+
Inputs (15 VDC to 30 VDC)

24 VDC power for input sensors or expansion mdules (180 mA)

Figure A-2

Connector Terminal Identification for CPU 212 DC/DC/DC

S7-200 Programmable Controller System Manual C79000G7076C23002

A-7

S7-200 Data Sheets

A.3

CPU 212 AC Power Supply, DC Inputs, Relay Outputs

Order Number: 6ES7 2121BA010XB0


General Features Physical size (L x W x D) Weight Power dissipation User program size/storage User data size/storage Data retention Local I/O1 Maximum number of expansion modules Digital I/O supported Analog I/O supported Boolean execution speed Internal memory bits Timers Counters High-speed counters 160 x 80 x 62 mm (6.3 x 3.15 x 2.44 in.) 0.4 kg (0.9 lbs.) 6W 512 words/EEPROM 512 words/RAM 50 hr typical (8 hr minimum at 40 C) 8 inputs/6 outputs 2 64 inputs/64 outputs 16 inputs/16 outputs 1.2 s/instruction 128 64 timers 64 counters 1 software (2 KHz max.) 1 UL 508 CSA C22.2 142 FM Class I, Division 2 VDE 0160 compliant CE compliant Isolated DC Sensor Supply Voltage range Ripple/noise (<10MHz) 24 VDC available current Short circuit current limit Isolated 20.4 to 28.8 VDC 1 V peak-to-peak maximum 180 mA < 600 mA No ON state nominal OFF state maximum Response time I0.0 to I0.7 Optical isolation Power Supply Voltage/frequency range Input current Holdup time Inrush current Fusing (non-replaceable) 5 VDC current 85 to 264 VAC at 47 to 63 Hz 4 VA typical, CPU only 50 VA maximum load 20 ms minimum from 110 VAC 20 A peak at 264 VAC 2 A, 250 V, slow blow 260 mA for CPU 340 mA for expansion I/O Yes. Transformer, 1500 VAC, 1 min Input Points Input type (IEC 11312) ON state range Type 1 sinking 1530 VDC, 4 mA minimum 35 VDC, 500 ms surge 24 VDC, 7 mA 5 VDC, 1 mA 0.3 ms maximum 500 VAC, 1 min

Analog adjustments Standards compliance

Output Points Output type Voltage range Maximum load current Overcurrent surge Isolation resistance Switching delay Lifetime Contact resistance Isolation coil to contact contact to contact (between open contacts) Short circuit protection 1 Relay, dry contact 5 to 30 VDC/250 VAC 2 A/point, 6 A/common 7 A with contacts closed 100 MW minimum (new) 10 ms maximum 10,000,000 mechanical 100,000 with rated load 200 mW maximum (new) 1500 VAC, 1 min 750 VAC, 1 min None

The CPU reserves 8 process-image input and 8 process-image output image register points for local I/O.

A-8

S7-200 Programmable Controller System Manual C79000G7076C23002

S7-200 Data Sheets

Outputs (30 VDC/250 VAC) N () L (+) N () L (+)

Power supply

RELAY OUTPUTS

1L

0.0

0.1

0.2

2L

0.3

0.4

0.5

L1

VAC 85264

470 3.3 K

Note: 1. Actual component values may vary. 2. Connect AC line to the L terminal. 3. DC circuit grounds are optional.

DC 24V INPUTS

1M

0.0

0.1

0.2

0.3

2M

0.4

0.5

0.6

0.7

L+

DC SENSOR SUPPLY

24 VDC power for input sensors or expansion modules (180 mA)

+
Inputs (15 VDC to 30 VDC)

Figure A-3

Connector Terminal Identification for CPU 212 AC/DC/Relay

S7-200 Programmable Controller System Manual C79000G7076C23002

A-9

S7-200 Data Sheets

A.4

CPU 212 24 VAC Power Supply, DC Inputs, Relay Outputs

Order Number: 6ES7 2121FA010XB0


General Features Physical size (L x W x D) Weight Power dissipation User program size/storage User data size/storage Data retention Local I/O1 Maximum number of expansion modules Digital I/O supported Analog I/O supported Boolean execution speed Internal memory bits Timers Counters High-speed counters 160 x 80 x 62 mm (6.3 x 3.15 x 2.44 in.) 0.4 kg (0.9 lbs.) 6W 512 words/EEPROM 512 words/RAM 50 hr typical (8 hr minimum at 40 C) 8 inputs/6 outputs 2 64 inputs/64 outputs 16 inputs/16 outputs 1.2 s/instruction 128 64 timers 64 counters 1 software (2 KHz max.) 1 UL 508 CSA C22.2 142 FM Class I, Division 2 VDE 0160 compliant CE compliant Isolated DC Sensor Supply Voltage range Ripple/noise (<10MHz) 24 VDC available current Short circuit current limit Isolated 20.4 to 28.8 VDC 1 V peak-to-peak maximum 180 mA < 600 mA No ON state nominal OFF state maximum Response time I0.0 to I0.7 Optical isolation Power Supply Voltage/frequency range Input current Holdup time Inrush current Fusing (non-replaceable) 5 VDC current 20 to 29 VAC at 47 to 63 Hz 4 VA typical, CPU only 50 VA maximum load 20 ms minimum from 24 VAC 20 A peak at 29 VAC 2 A, 250 V, slow blow 260 mA for CPU 340 mA for expansion I/O Yes. Transformer, 500 VAC, 1 min Input Points Input type (IEC 11312) ON state range Type 1 sinking 1530 VDC, 4 mA minimum 35 VDC, 500 ms surge 24 VDC, 7 mA 5 VDC, 1 mA 0.3 ms maximum 500 VAC, 1 min

Analog adjustments Standards compliance

Output Points Output type Voltage range Maximum load current Overcurrent surge Isolation resistance Switching delay Lifetime Contact resistance Isolation coil to contact contact to contact (between open contacts) Short circuit protection 1 Relay, dry contact 5 to 30 VDC/250 VAC 2 A /point, 6 A /common 7 A with contacts closed 100 MW minimum (new) 10 ms maximum 10,000,000 mechanical 100,000 with rated load 200 mW maximum (new) 1500 VAC, 1 min 750 VAC, 1 min None

The CPU reserves 8 process-image input and 8 process-image output image register points for local I/O.

A-10

S7-200 Programmable Controller System Manual C79000G7076C23002

S7-200 Data Sheets

Outputs (30 VDC/250 VAC) N () L (+) N () L (+)

Power supply

RELAY OUTPUTS

1L

0.0

0.1

0.2

2L

0.3

0.4

0.5

L1

VAC 2029

470 3.3 K

Note: 1. Actual component values may vary. 2. Connect AC line to the L terminal. 3. DC circuit grounds are optional.

DC 24V INPUTS

1M

0.0

0.1

0.2

0.3

2M

0.4

0.5

0.6

0.7

L+

DC SENSOR SUPPLY

24 VDC power for input sensors or expansion modules (180 mA)

+
Inputs (15 VDC to 30 VDC)

Figure A-4

Connector Terminal Identification for CPU 212 24 VAC/DC/Relay

S7-200 Programmable Controller System Manual C79000G7076C23002

A-11

S7-200 Data Sheets

A.5

CPU 212 AC Power Supply, AC Inputs, AC Outputs

Order Number: 6ES7 2121CA010XB0


General Features Physical size (L x W x D) Weight Power dissipation User program size/storage User data size/storage Data retention Local I/O1 Maximum number of expansion modules Digital I/O supported Analog I/O supported Boolean execution speed Internal memory bits Timers Counters High-speed counters 160 x 80 x 62 mm (6.3 x 3.15 x 2.44 in.) 0.4 kg (0.9 lbs.) 7 W at 2.5 A load 512 words/EEPROM 512 words/RAM 50 hr typical (8 hr minimum at 40 C) 8 inputs/6 outputs 2 64 inputs/64 outputs 16 inputs/16 outputs 1.2 s/instruction 128 64 timers 64 counters 1 software (50 Hz max.) 1 UL 508 CSA C22.2 142 FM Class I, Division 2 CE compliant ON state nominal OFF state maximum Response time Optical isolation Power Supply Voltage/frequency range Input current Holdup time Inrush current Triac, zero-crossing 20 to 264 VAC, 47 to 63 Hz 0.3 to 1.0 MOV 275 V working voltage 0 to 40 C 1.20 A 1.50 A 3.50 A 30 mA 1.5 mA, 120 VAC/2.0 mA, 240 VAC 55 C2 1.00 A 1.25 A 2.50 A DC Sensor Supply Voltage range Ripple/noise (<10MHz) 24 VDC available current Short circuit current limit Isolated 20.4 to 28.8 VDC 1 V peak-to-peak maximum 180 mA < 600 mA No Fusing (non-replaceable) 5 VDC current Isolated 85 to 264 VAC at 47 to 63 Hz 4 VA typical, CPU only 50 VA maximum load 20 ms minimum from 110 VAC 20 A peak at 264 VAC 2 A, 250 V, slow blow 320 mA for CPU 280 mA for expansion I/O Yes. Transformer, 1500 VAC, 1 min 120 VAC, 60 Hz, 7 mA 20 VAC, 1 mA 10 ms typical, 15 ms max. 1500 VAC, 1 min Optical isolation Short circuit protection Input Points Input type (IEC 11312) ON state range Type 1 sinking 79 to 135 VAC, 47 to 63 Hz, 4 mA minimum Voltage drop Output Points (continued) Switching delay Surge current 1/2 cycle 30 A peak, 1 cycle / 10 A peak, 5 cycle 1.5 V maximum at maximum current 1500 VAC, 1 min None

Analog adjustments Standards compliance

Output Points Output type Voltage/frequency range Load circuit power factor Inductive load clamping Maximum load current per single point per 2 adjacent points all points total* Minimum load current Leakage current

1 2

The CPU reserves 8 process-image input and 8 process-image output register points for local I/O. Linear derate 40 to 55 C. Vertical mount derate 10 C.

A-12

S7-200 Programmable Controller System Manual C79000G7076C23002

S7-200 Data Sheets

Outputs (20 VAC to 264 VAC)

Power supply

AC OUTPUTS

1L

0.0

0.1

0.2

2L

0.3

0.4

0.5

L1

VAC 85264

275V MOV 0.0068 F 10

390 3.3 K 0.15 F 470 K

Note: Actual component values may vary.

AC 120V INPUTS

0.0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

L+

DC SENSOR SUPPLY

24 VDC power for input sensors or expansion modules (180 mA) Inputs (79 VAC to 135 VAC)

Figure A-5

Connector Terminal Identification for CPU 212 AC/AC/AC

S7-200 Programmable Controller System Manual C79000G7076C23002

A-13

S7-200 Data Sheets

A.6

CPU 212 AC Power Supply, Sourcing DC Inputs, Relay Outputs

Order Number: 6ES7 2121BA100XB0


General Features Physical size (L x W x D) Weight Power dissipation User program size/storage User data size/storage Data retention Local I/O1 Maximum number of expansion modules Digital I/O supported Analog I/O supported Boolean execution speed Internal memory bits Timers Counters High-speed counters Analog adjustments Standards compliance 160 x 80 x 62 mm (6.3 x 3.15 x 2.44 in.) 0.4 kg (0.9 lbs.) 6W 512 words/EEPROM 512 words/RAM 50 hr typical (8 hr minimum at 40 C) 8 inputs/6 outputs 2 64 inputs/64 outputs 16 inputs/16 outputs 1.2 s/instruction 128 64 timers 64 counters 1 software (2 KHz max.) 1 UL 508 CSA C22.2 142 FM Class I, Division 2 VDE 0160 compliant CE compliant Inrush current Fusing (non-replaceable) 5 VDC available current Isolated DC Sensor Supply Voltage range Ripple/noise (<10MHz) 24 VDC available current short circuit current limit Isolated 20.4 to 28.8 VDC 1 V peak-to-peak maximum 180 mA < 600 mA No ON state OFF state Response time I0.0 to I0.7 Optical isolation 4 mA minimum 1 mA maximum 0.3 ms maximum 500 VAC, 1 min Input Points Type Input voltage range Sourcing 15 to 30 VDC, 35 VDC for 500 ms

Power Supply Voltage/frequency range Input current Holdup time 85 to 264 VAC at 47 to 63 Hz 4 VA typical, CPU only 50 VA maximum load 20 ms minimum from 110 VAC 20 A peak at 264 VAC 2 A, 250 V, slow blow 260 mA for CPU 340 mA for expansion I/O Yes. Transformer, 1500 VAC, 1 min

A
Output Points Output type Voltage range Maximum load current Overcurrent surge Isolation resistance Switching delay Lifetime Contact resistance Isolation coil to contact contact to contact (between open contacts) Short circuit protection
1

Relay, dry contact 5 to 30 VDC/250 VAC 2 A /point, 6 A/common 7 A with contacts closed 100 MW minimum (new) 10 ms maximum 10,000,000 mechanical 100,000 with rated load 200 mW maximum (new) 1500 VAC, 1 min 750 VAC, 1 min None

The CPU reserves 8 process-image input and 8 process-image output register points for local I/O.

A-14

S7-200 Programmable Controller System Manual C79000G7076C23002

S7-200 Data Sheets

Outputs (30 VDC/250 VAC) N () L (+) N () L (+)

Power supply

RELAY OUTPUTS

1L

0.0

0.1

0.2

2L

0.3

0.4

0.5

L1

VAC 85264

Note: 1. Actual component values may vary. 2. Connect AC line to the L terminal. 3. Input circuit ground is optional. 470 3.3 K

DC 24V INPUTS

1L

0.0

0.1

0.2

0.3

2L

0.4

0.5

0.6

0.7

L+

DC SENSOR SUPPLY

24 VDC power for input sensors or expansion modules (180 mA)

Inputs (15 VDC to 30 VDC)

Figure A-6

Connector Terminal Identification for CPU 212 AC/Sourcing DC/Relay

S7-200 Programmable Controller System Manual C79000G7076C23002

A-15

S7-200 Data Sheets

A.7

CPU 212 AC Power Supply, 24 VAC Inputs, AC Outputs

Order Number: 6ES7 2121DA010XB0


General Features Physical size (L x W x D) Weight Power dissipation User program size/storage User sata size/storage Data retention Local I/O1 Maximum number of expansion modules Digital I/O supported Analog I/O supported Boolean execution speed Internal memory bits Timers Counters High-speed counters 160 x 80 x 62 mm (6.3 x 3.15 x 2.44 in.) 0.4 kg (0.9 lbs.) 7 W at 2.5 A load 512 words/EEPROM 512 words/RAM 50 hr typical (8 hr minimum at 40 C) 8 inputs/6 outputs 2 64 inputs/64 outputs 16 inputs/16 outputs 1.2 s/instruction 128 64 timers 64 counters 1 software (50 Hz max.) 1 UL 508 CSA C22.2 142 FM Class I, Division 2 CE compliant ON state nominal OFF state maximum Response time Optical isolation Power Supply Voltage/frequency range Input current Holdup time Inrush current Triac, zero-crossing 20 to 264 VAC, 47 to 63 Hz 0.3 to 1.0 MOV 275 V working voltage 0 to 40 C 1.20 A 1.50 A 3.50 A 30 mA 1.5 mA, 120 VAC/2.0 mA, 240 VAC 55 C 2 1.00 A 1.25 A 2.50 A DC Sensor Supply Voltage range Ripple/noise (<10MHz) 24 VDC available current Short circuit current limit Isolated 20.4 to 28.8 VDC 1 V peak-to-peak maximum 180 mA < 600 mA No Fusing (non-replaceable) 5 VDC current Isolated 85 to 264 VAC at 47 to 63 Hz 4 VA typical, CPU only 50 VA maximum load 20 ms minimum from 110 VAC 20 A peak at 264 VAC 2 A, 250 V, slow blow 320 mA for CPU 280 mA for expansion I/O Yes. Transformer, 1500 VAC, 1 min 24 VAC, 60 Hz, 7 mA 5 VAC, 1 mA 10 ms typical, 15 ms max. 1500 VAC, 1 min Optical isolation Short circuit protection Input Points Input type (IEC 11312) ON state range Type 1 sinking 15 to 30 VAC, 47 to 63 Hz, 4 mA minimum Voltage drop Output Points (continued) Switching delay Surge current 1/2 cycle 30 A peak, 1 cycle / 10 A peak, 5 cycle 1.5 V maximum at maximum current 1500 VAC, 1 min None

Analog adjustments Standards compliance

Output Points Output type Voltage/frequency range Load circuit power factor Inductive load clamping Maximum load current per single point per 2 adjacent points all points total Minimum load current Leakage current

1 2

The CPU reserves 8 process-image input and 8 process-image output register points for local I/O. Linear derate 40 to 55 C. Vertical mount derate 10 C

A-16

S7-200 Programmable Controller System Manual C79000G7076C23002

S7-200 Data Sheets

Outputs (20 VAC to 264 VAC)

Power supply

AC OUTPUTS

1L

0.0

0.1

0.2

2L

0.3

0.4

0.5

L1

VAC 85264

275V MOV 0.0068 F 10 Note: Actual component values may vary. 390 3.3 K

AC 24V INPUTS

0.0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

L+

DC SENSOR SUPPLY

24 VDC power for input sensors or expansion modules (180 mA) Inputs (15 VAC to 30 VAC)

Figure A-7

Connector Terminal Identification for CPU 212 AC/AC/AC

S7-200 Programmable Controller System Manual C79000G7076C23002

A-17

S7-200 Data Sheets

A.8

CPU 212 AC Power Supply, AC Inputs, Relay Outputs

Order Number: 6ES7 2121GA010XB0


General Features Physical Size (L x W x D) Weight Power Dissipation User program size/storage User data size/storage Data retention Local I/O1 Maximum Number of Expansion Modules Digital I/O Supported Analog I/O Supported Boolean Execution Speed Internal Memory Bits Timers Counters High-speed counters 160 x 80 x 62 mm (6.3 x 3.15 x 2.44 in.) 0.4 kg (0.9 lbs.) 6W 512 Words / EEPROM 512 Words / RAM 50 hr typical (8 hr minimum at 40 C) 8 Inputs / 6 Outputs 2 64 Inputs / 64 Outputs 16 Inputs / 16 Outputs 1.2 s/instruction 128 64 Timers 64 Counters 1 Software (2 KHz max.) 1 UL 508 CSA C22.2 142 FM Class I, Division 2 VDE 0160 compliant CE compliant DC Sensor Supply Voltage Range Ripple/noise (<10Mhz) 24 VDC Available Current Short Circuit Current Limit Relay, dry contact 5 to 30 VDC / 250 VAC 2 A/point 7 A with contacts closed 100 MW minimum (new) 10 ms maximum 10,000,000 Mechanical 100,000 with Rated Load 200 mW maximum (new) 1500 VAC, 1 minute 1000 VAC, 1 minute None Isolated 20.4 to 28.8 VDC 1 V peak-to-peak maximum 180 mA < 600 mA No Isolated Hold Up Time Inrush Current Fusing (non-replaceable) 5 VDC Current ON State Nominal OFF State Maximum Response Time Optical Isolation Power Supply Voltage/frequency Range Input Current 85 to 264 VAC at 47 to 63 Hz 4 VA typical, CPU only 50 VA maximum load 20 ms minimum from 110 VAC 20 A peak at 264 VAC 2 A, 250 V, Slow Blow 260 mA for CPU 340 mA for expansion I/O Yes. Transformer, 1500 VAC, 1 minute Input Points Input Type (IEC 11312) ON State Range Type 1 Sinking 79 to 135 VAC, 47 to 63 Hz. 4 mA minimum 120 VAC, 60 Hz, 7mA 20 VAC, 1 mA 10 ms typical, 15 ms max. 1500 VAC, 1 minute

Analog Adjustments Standards Compliance

Output Points Output Type Voltage Range Maximum Load Current Overcurrent Surge Isolation Resistance Switching Delay Lifetime Contact Resistance Isolation Coil to Contact Contact to Contact Short Circuit Protection
1

The CPU reserves 8 input and 8 output image register points for local I/O.

A-18

S7-200 Programmable Controller System Manual C79000G7076C23002

S7-200 Data Sheets

Outputs (30 VDC / 250 VAC) N () L (+) N () L (+)

Power Supply

RELAY OUTPUTS

1L

0.0

0.1

0.2

2L

0.3

0.4

0.5

L1

VAC 85264

0.0068 F

Note: 1. Actual component values may vary. 2. Connect AC line to the L terminal.

390 ohms 3.3K ohms 0.15 F 470K ohms

AC 120V INPUTS

0.0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

L+

DC SENSOR SUPPLY

24 VDC Power for Input Sensors or Expansion Modules (180 mA) Inputs (79 to 135 VAC)

Figure A-8

Connector Terminal Identification for CPU 212 AC/AC/Relay

S7-200 Programmable Controller System Manual C79000G7076C23002

A-19