The FIOD series products add digital capability to your PLC / SCADA. FIOD 0016 model has 16 relay / transistor (PNP/NPN) outputs. The outputs are isolated from the host device. It has one (2 Wire RS485) communication port. The COM port is used to connect any modbus master device (PLC / SCADA / Operator Interface device). This module supports Modbus RTU (Slave) protocol.
support@renuelectronics.com
Website:
www.renuelectronics.com
70.
00
35
.00
100.00
support@renuelectronics.com
Website:
www.renuelectronics.com
3. 4. 5. 6. 7. 8. 9.
Communication Port I/O Terminals Operating Temperature Storage Temperature Humidity Mounting Dimensions (DIN rail)
: : : : : : :
: 230V AC; 2 Amp. / 30V DC; 2 Amp. Coil Voltage: 24VDC For Transistor output (PNP/NPN): 500 mA; Supply Voltage: 24VDC 2 Wire RS-485 Pluggable terminals. 0OC to 60OC -20OC to 80OC 10% to 90% (Non condensing) DIN rail mounting 70 X 100 X 35 mm
Communication Parameters And Modbus Tag Definition Unit supports MODBUS driver for communication with Master device. COM Port Setting:
1 2 3 4 5 6 7 8 9 10
support@renuelectronics.com
Website:
www.renuelectronics.com
UNIT ID 1 2 . . . . 64
ADDR6 0 0
ADDR5 0 0
ADDR4 0 0
ADDR3 0 0
ADDR2 0 0
ADDR1 0 1
BAUD2 0 0 1 1
BAUD1 0 1 0 1
PARITY2 0 0 1
PARITY1 0 1 0
support@renuelectronics.com
Website:
www.renuelectronics.com
Default
40070
Communication Timeout for own frame Communication timeout for ideal communication line
Retentive 0
40071
Retentive 0
Retentive 0
1 or 0
Holds the communication timeout value. If unit doesnt reveive its own frame within this timeout period, it declares communication break. Holds the communication timeout value. If communication line is completely ideal (No frame from master for other slaves also) within this timeout period, unit declares communication break. If 1, timeout value from 40070 is selected If 0, timeout value from 40071 is selected
Note: The default timeout is 10sec. In case of communication break with the host all the outputs are switched OFF after the timeout period is over. Renu Electronics Private Limited
Survey No. 2/6, Baner Road, Pune 411 045 Maharashtra, INDIA Tel: +91 20 2729 2840 Fax: +91 20 2729 2839 E-mail:
support@renuelectronics.com
Website:
www.renuelectronics.com
GND GND B A
TERM TERM REST REST
GND B A
M A S T E R
NC DC+ DCDC-
support@renuelectronics.com
Website:
www.renuelectronics.com
FIOD Unit 1
B A
FIOD Unit 2
FIOD Unit n
GND GND B A
TERM TERM REST REST
EARTH
Renu Electronics Private Limited
Survey No. 2/6, Baner Road, Pune 411 045 Maharashtra, INDIA Tel: +91 20 2729 2840 Fax: +91 20 2729 2839 E-mail:
support@renuelectronics.com
Website:
www.renuelectronics.com
L1
L2
L3
L4
N 230 VAC
N 230 VAC RLY POLE 2 Y4 (NO) Y5 (NO) Y6 (NO) Y7 (NO) P L9 L10 L11 L12
N 230 VAC RLY POLE 3 Y8 (NO) Y9 (NO) Y10(NO) Y11 (NO) P L13 N 230 VAC RLY POLE 4 Y12 (NO) Y13 (NO) Y14 (NO) Y15 (NO) L14 L15 L16
support@renuelectronics.com
Website:
www.renuelectronics.com
For FIOD-0016-C-B
FIOD-0016-C-B FIOD-0808-C-B
24 VDC Y0 INTERNAL CIRCUIT
LOAD
Max 500mA
+ 24 VDC -
OP COM
For FIOD-0016-P-B
FIOD-0016-P-B FIOD-0808-P-B
24 VDC
+ 24 VDC -
LOAD
Max 500mA
support@renuelectronics.com
Website:
www.renuelectronics.com
MANUAL REVISION If you contact us in reference to this manual, please include the following document number Name : User Manual For FIOD0016 Part Number : URML401 Document : UMAN\FIOD-0016\1106 Revision : 3
Revision Number Rev 1 Rev 2 Rev 3 Document Number Date Description Panel dimensions and port details are added. Power supply, multidropping wiring added. Communication timeout register is added.
support@renuelectronics.com
Website:
www.renuelectronics.com