Sunteți pe pagina 1din 53

Across the line contactors Type A, B & EH

B9 B75, A95 A110


EH145 EH800

AC 1000 2/97

CONTACTORS:

Maximum UL/CSA horsepower ratings Maximum UL/CSA horsepower ratings Includes NEMA sizes 00 - 3 Includes NEMA sizes 3 - 7 CE mark CE mark Compact space saving design Double break contact design with magnetic Standard auxiliary contact configurations: arc chamber extinguishes arc in shortest B9 B25 1 N.O. or 1 N.C. possible time B30 2 N.O. & 2 N.C. High quality plastic for sizes EH145 EH300 B40 B75 1 N.O. & 1 N.C. Die cast aluminum frame, EH450 EH800 A95 A110 1 N.O. & 1 N.C. High temperature encapsulated coil Additional auxiliary contact blocks are 1 N.O. & 1 N.C. auxiliary contacts are available standard and up to 6 additional auxiliary D.C. ratings & D.C. control operation contacts may be added to provide a total of available 8 (4 N.O. & 4 N.C.) Fast, snap-on DIN rail mounting Early make & late break auxiliary contacts Double break contact design available Snap-on front mounted accessories D.C. ratings and D.C. control operation include mechanical latch, pneumatic available timer, and 1 & 4 pole auxiliary contact Easy removal of arc chute for quick blocks inspection and change of contacts Easy coil change Mechanical latch available for all sizes Captive terminal screws Can be mounted in any position NEMA, UL, IEC, CSA, VDE and most Operates over an extended voltage range other international standards of 85% to 110% of rated control voltage UL File No: E39231 (B9 B75) NEMA, UL, IEC, CSA, VDE and most other UL File No: E79416 (A95 A110) international standards CSA File No: LR56745 (B9 B75) UL File No: E79416 CSA File No: LR19700 (A95 A110) CSA File No: LR19700 Touch safe design: All connection CSA approved for elevator service terminals are protected against accidental New withdrawable coil for EH175 300 !! w touch Ne Terminals supplied open for ease of wiring Operates over an extended voltage range Index of 85% to 110% of rated control voltage Across the line contactors Screwdriver guide holes Features ............................................ 1.1 Description ............................... 1.2 - 1.3 Non-reversing ........................... 1.4 - 1.5 Mechanically interlocked ................... 1.6 Reversing .......................................... 1.7 Accessories ............................ 1.8 - 1.20 Renewal parts ................................. 1.21 Technical data UL/CSA ........................... 1.22 - 1.23 IEC .................................. 1.24 - 1.35 Approximate dimensions ..... 1.36 - 1.49
Renewal parts: 1.21 Technical data: 1.22 - 1.35 Approximate dimensions: 1.36 - 1.49

Selection: 1.4 - 1.7

Accessories: 1.8 - 1.20

1.1

Across the line contactors Type A, B, BC & BE Description


Application
3 and 4-pole contactors A, B, BC, BE are mainly used for controlling three phase motors and for controlling power circuits up to 600VAC and 500VDC, in accordance with their characteristics and utilization data.
G

BE types, d.c. operated, with laminated electro-magnet, double wound coil fed from d.c. supply via an insertion contact (type CDL 7) with normally closed lagging contact and varistor. Contactors with 4 pole auxiliary block Same width as standard contactor of same ratings Contactors for specific application : UB and UB R types for 3-phase capacitor switching. 4-pole types with N/C main poles. TBC types with large coil voltage range. d.c. operated.

Construction details
A95 & A110, B9 B75, BC9 BC30, BE40 BE75 All the contactors can be side by side mounted.
G G

Standard contactors : A & B types, a.c. operated, with laminated electro-magnet, coil directly fed from an a.c. supply. BC types, d.c. operated, with solid core electro-magnet, coil directly fed from a d.c. supply.

1
G Mounting holes for screw mounting. Distances between holes comply with EN 50003 (screws not supplied). G Dove tail for mounting of surge suppressor.
HZ 50 0 40 60

G Fast mounting on DIN rail according to IEC

715 and EN 50022 : 35 x 7.5 mm 35 x 15 mm

G Terminal marking acc. to EN 50012/NEMA. G Space for identification marker or surge

G Location for side mounted accessories.

Same facilities on right handside.

suppressor.
G Attachment-system for front-mounted

accessories.
G Connecting point on main terminals for control G Posidrive (+, ) screw-heads and self lifting

leads.

G Location for side mounted accessories.

Coil part with voltage and frequency in clear text.

cable clamps.
B(C) 9 B(C)30

Same on right side.


G Fast mounting on DIN rail

G Terminals delivered in open position, with captive screws (It is recommended to tighten the screws of unused terminals).

35 x 15 mm acc. to IEC 715 and EN50022 B40 75 75 mm acc. to IEC 715 and EN 50023 B40 75 A95 110
G Location for :

1L1

3L2

5L3

All the connection terminals provide protection against unintentional direct touch of live parts according to VDE 0106. Screw-driver guide holes allow the use of powered screw-drivers.

G Space for identification marker or surge

suppressor. aux. contact block left side mounted on 3-pole contactor types A(E)95 110, B(E)40 to 75 economizing contact mounted on DC operated contactors : right side for 3-pole types A(E)95 110, BE40 to BE75. left side for 4-pole types BE50-40.
G Mounting holes for screw mounting. Distances

G 4th pole of contactor types B(E) 50, factory

mounted on the right side. Same technical characteristics as the other 3 main poles.
6T3 4T2 2T1

G Terminal marking acc. to EN 50012/NEMA.

B(E)40 B(E)75 A(E)95 A(E)110

between holes comply with EN 50003 (screws not supplied).


G Slotted screw-heads and connectors 13 x 10

mm. B40 B75 contactors.


G Socket head screws for A95 A110. AC 1000 2/97

CONTACTORS:

Selection: 1.4 - 1.7

Accessories: 1.8 - 1.20

Renewal parts: 1.21

Technical data: 1.22 - 1.35

Approximate dimensions: 1.36 - 1.49

1.2

Across the line contactors Type EH & EK Description


Application
3-pole Type EH contactors are mainly used for controlling three phase motors and for controlling power circuits up to 600VAC and 500VDC at their corresponding rated operating currrents as indicated in the tables of characteristics and utilization data. 4-pole Type EK contactors are mainly used for switching of emergency circuits and all distribution circuits where neutral needs to be broken.

Construction details
EH145 EH800 and EK110 EK550. Complete closing in one operation is ensured, even at the lowest limit value of the operating voltage, by the patented spring system. Coil encapsulated in glass-fiber reinforced and temperature resistant thermoplastic. G 3-pole Type EH contactors and 4-pole Type EK contactors can be supplied: AC operated types with laminated electro-magnet, coil directly fed from an AC supply. 1 NO and 1 NC auxiliary standard. DC operated types with laminated electro-magnet, coil fed from DC supply via an economizing resistor inserted by an auxiliary contact block with normally closed lagging contact. 1 NO and 1 NC auxiliary contact can be added to left side of contactor.
G Screw, nut and washer are supplied for every main terminal. Terminal clamps for either copper or aluminium cables can be ordered separately. G Holes for M4 self tapping screws. Power take-off screw on L1 & L2 G Main contacts with contact coatings that combine high conductivity with low tendency to oxidation. G Separate arc contacts on EH450 .... 800 with contact plates having high melting point, low tendency to weld and hard material. G Arc shield of glass-fiber reinforced polyester. G Terminal marking complying with EN 50005, EN 50012 and NEMA. Phase terminals and phase wiring with clearly readable markings. G Coil part with voltage and frequency clearly marked. Clamp terminals protected against accidental contact (IP 20). EH175 - EH300 contactors have a withdrawable coil on top.

G Ground screw M10 for EH450 800. Can also be located at the bottom.
G Dampers for EH450 800 are

supplied, c/w screw & washers.


G Body of glass-fiber reinforced

polyester for EH145 300, pressured die-cast light alloy for EH450 800.
G Quick-release clip for removing
1-L1 3-L2 5-L3

of arc-shield.
G Existing auxiliary contact block. G Clamp-terminals protected
6-T3
4-T2

against accidental contact (IP 20)


G Alternative grounding screw

2-T1

position.

EH145 EH800

G Ground screw M10 for EK450

G Screw, nut and washer are supplied for every

and EK550. Can also be fitted at the bottom.


G Dampers for EK550 are

main terminal. Terminal clamps for either copper or aluminium cables can be ordered separately.
G Holes for M4 self tapping screws. Power

supplied, c/w screws & washers.

take-off screw on L1 & L2


G Main contacts with contact coatings that

G Quick-release clip for

removing of arc-shield.
G Existing auxiliary contact
1-L1 3-L2 5-L3

combine high conductivity with low tendency to oxidation.


7-L4

G Separate arc contacts on EK450 and 550

block.
G Clamp-terminals protected

with contact plates having high melting point, low tendency to weld and hard material.
G Economizing contact block with economizing
8-T4 6-T3
4-T2

against accidental contact (IP 20)


2-T1

resistor on DC operated contactors.


G Arc shield of fiberglass reinforced polyester. G Terminal marking complying with EN 50005,

G Alternative grounding screw

position.

EN 50012 and NEMA. Phase terminals and phase wiring with clearly readable markings.
AC 1000 2/97 G Coil with voltage and frequency shown. EK110 EK550

CONTACTORS:

Clamp terminals protected against accidental contact (IP 20). EK175 & EK210 contactors have a withdrawable coil on top.
Technical data: 1.22 - 1.35 Approximate dimensions: 1.36 - 1.49

Selection: 1.4 - 1.7

Accessories: 1.8 - 1.20

Renewal parts: 1.21

1.3

Across the line contactors Non-reversing, 3 pole

B12C-1

B50C-1

EH260C-1

3 Pole, A.C., Open

General purpose current

Maximum motor horsepower ratings 200V 230V 460/480V 575/600V

AC operated Catalog number List price

DC operated Catalog number List price

AC1 21 21 21 33 45 55 65 85 105 125 140 170 190 230 300 350 525 600 715 900

AC3 9 11 17 28 32 41 52 65 80 80 105 130 156 192 242 302 420 480 602 810 2 3 5 7.5 10 10 15 20 25 30 30 40 50 60 75 100 125 150 200 250 2 3 5 10 10 15 20 25 30 30 40 50 60 75 100 100 150 200 250 300 5 7.5 10 20 20 30 40 50 60 60 75 100 125 150 200 250 350 400 500 600

UL rated 7.5 10 15 25 30 40 50 50 75 75 100 125 150 200 250 250 400 500 600 700 NEMA rated B9C-1 B12C-1 B16C-1 B25C-1 B30C-1 B40C-1 B50C-1 B63C-1 B75C-1 A95C-1 A110C-1 EH145C-1 EH175C-1 EH210C-1 EH260C-1 EH300C-1 EH450C-1 EH550C-1 EH700C-1 EH800C-1 $ 52 56 68 122 168 198 220 248 275 300 320 600 920 1150 1300 1400 2200 3100 4800 5000 BC9C-P BC16C-P BC25C-P BC30C-P BE40C-P BE50C-P BE63C-P BE75C-P AE95C-P AE110C-P EH145C-P EH175C-P EH210C-P EH260C-P EH300C-P EH450C-P EH550C-P EH700C-P EH800C-P $ 82 98 152 198 228 250 318 345 370 460 740 1090 1320 1490 1590 2440 3430 5130 5330

NEMA Size

Continuous current

00 0 1 2 3 4 5 6 7

9 18 27 45 90 135 270 540 810

1.5 3 7.5 10 25 40 75 150

1.5 3 7.5 15 30 50 100 200 300

2 5 10 25 50 100 200 400 600

2 5 10 25 50 100 200 400 600

BN9C-1 BN16C-1 BN25C-1 BN50C-1 BN75C-1 EHN145C-1 EHN260C-1 EHN550C-1 EHN800C-1

$ 75 108 148 220 275 600 1300 3100 5000

BCN9C-P BCN16C-P BCN25C-P BEN50C-P BEN75C-P EHN145C-P EHN260C-P EHN550C-P EHN800C-P

$ 105 138 178 250 345 740 1490 3430 5330

Coil voltage selection


All AC operated catalog numbers include a 120VAC coil. All DC operated catalog numbers include a 110VDC coil. To select other coil voltages, substitute the code from the Coil Voltage Selection chart for the first digit after the dash in the catalog number.

Auxiliary contacts as standard


Frame size Number of contacts Mounting

Coil voltage selection chart


Contr. type 60 A,B,EH 50 A,B 50 EH DC A,B,EH Hz 24 F F N Y Volts 48 110 120 125 208 220 240 277 380 415 440 480 500 600 G 1 B 2 C Z 3 4 6 1 2 3 4 6 1 J 3 M 5 W P Q R T

B(C)9 B(C)25 1 N.O. Internal B(C)30 2 N.O. & 2 N.C. Top B(E)40 EH800 1 N.O. & 1 N.C. Side A(E)95 A(E)110 1 N.O. & 1 N.C. Side Additional auxiliary contacts are available for all contactor sizes. See Accessories.

EH Contactors are supplied with lugs


If terminal lugs are not required, subtract the terminal kit price shown on page 1.13. Add the "L" suffix as the last digit in the catalog number. Example: EH145C-1L, $575

For other voltages, consult factory. 24 & 48VAC coils are not available for sizes EH450 EH800. For these applications, use an interposing control relay. AC 1000 2/97

Frame size B(C)9 - 25 contactors can be supplied with 1 N.C. auxiliary contact as standard. Add suffix "01" after the coil voltage suffix. Price is the same.

CONTACTORS:

Selection: 1.4 - 1.7

Accessories: 1.8 - 1.20

Renewal parts: 1.21

Technical data: 1.22 - 1.35

Approximate dimensions: 1.36 - 1.49

1.4

Type A Discount schedule AA Type B Discount schedule BA Type EH Discount schedule EA

Across the line contactors Non-reversing, 4-pole UL rated

B12C4P-1

B25C4P-1

EK175C4P-1

4 Pole A.C., Open


UL general purpose current AC operated Catalog number List price DC operated Catalog number List price

10 15 20 30 40 60 85 105 150 200 250 300 400 600

B9C4P-1 B12C4P-1 B16C4P-1 B25C4P-1 B40C4P-1 B50C4P-1 B63C4P-1 B75C4P-1 EK110C4P-1L EK150C4P-1L EK175C4P-1L EK210C4P-1L EK370C4P-1L EK550C4P-1L

$ 80 90 110 152 240 275 300 350 495 675 1175 1350 3100 4340

BC9C4P-P BC16C4P-P BC25C4P-P BE40C4P-P BE50C4P-P BE63C4P-P BE75C4P-P EK110C4P-PL EK150C4P-PL EK175C4P-PL EK210C4P-PL EK370C4P-PL EK550C4P-PL

$ 110 140 182 270 315 330 380 635 825 1325 1520 3340 4670

4 Pole, A.C., Open 2 N.O. & 2 N.C. Power Poles


UL general purpose current AC operated Catalog number List price DC operated Catalog number List price

20A 30A

B12C4P22-1 B25C4P22-1

$ 76 142

BC25C4P22-P

$ 172

Coil voltage selection


All AC operated catalog numbers include a 120VAC coil. All DC operated catalog numbers include a 110VDC coil. To select other coil voltages, substitute the code from the Coil Voltage Selection chart for the first digit after the dash in the catalog number.

Auxiliary contacts as standard


Frame size Number of contacts Mounting

Coil voltage selection chart


Contr. type 60 A,B,EH 50 A,B 50 EH DC A,B,EH Hz 24 F F N Y Volts 48 110 120 125 208 220 240 277 380 415 440 480 500 600 G 1 B 2 C Z 3 4 6 1 2 3 4 6 1 J 3 M 5 W P Q R T

B(C)9 B(C)25 1 N.O. Internal B(C)30 2 N.O. & 2 N.C. Top B(E)40 EH800 1 N.O. & 1 N.C. Side A(E)95 A(E)110 1 N.O. & 1 N.C. Side Additional auxiliary contacts are available for all contactor sizes. See Accessories.

EK Contactors are supplied without lugs


Lug kits can be ordered for EK contactors. See page 1.13. Subtract the terminal kit price shown on page 1.13 and add the "L" suffix as the last digit in the catalog number. EX: EK110C4P-1L

For other voltages, consult factory. 24 & 48VAC coils are not available for sizes EH450 EH800. For these applications, use an interposing control relay.

AC 1000 2/97

Frame size B(C)9 - 25 contactors can be supplied with 1 N.C. auxiliary contact as standard. Add suffix "01" after the coil voltage suffix. Price is the same.

CONTACTORS:

Selection: 1.4 - 1.7

Accessories: 1.8 - 1.20

Renewal parts: 1.21

Technical data: 1.22 - 1.35

Approximate dimensions: 1.36 - 1.49

Discount schedule BA Type B Discount schedule EA Type EK

1.5

Across the line contactors Mechanically interlocked, 3 pole

B25M-1

B63M-1

EH450M-1

3 Pole, A.C., Open

General purpose current

Maximum motor horsepower ratings 200V 230V 460/480V 575/600V

AC operated Catalog number

List price

DC operated Catalog List number price

AC1 21 21 21 33 45 55 65 85 105 125 140 170 190 230 300 350 525 600 715 900

AC3 9 11 17 28 32 41 52 65 80 80 105 130 156 192 242 302 420 480 602 810 2 3 5 7.5 10 10 15 20 25 30 30 40 50 60 75 100 125 150 200 250 2 3 5 10 10 15 20 25 30 30 40 50 60 75 100 100 150 200 250 300 5 7.5 10 20 20 30 40 50 60 60 75 100 125 150 200 250 350 400 500 600

UL rated 7.5 10 15 25 30 40 50 50 75 75 100 125 150 200 250 250 400 500 600 700 NEMA rated B9M-1 B12M-1 B16M-1 B25M-1 B30M-1 B40M-1 B50M-1 B63M-1 B75M-1 A95M-1 A110M-1 EH145M-1 EH175M-1 EH210M-1 EH260M-1 EH300M-1 EH450M-1 EH550M-1 EH700M-1 EH800M-1 $ 170 210 230 270 365 426 475 580 770 820 910 1490 2240 2690 2990 3640 3990 8190 11,590 12,490 BC9M-P BC16M-P BC25M-P BC30M-P BE40M-P BE50M-P BE63M-P BE75M-P AE95M-P AE110M-P EH145M-P EH175M-P EH210M-P EH260M-P EH300M-P EH450M-P EH550M-P EH700M-P EH800M-P $ 230 290 330 445 506 535 720 910 960 1190 1770 2580 3030 3370 4020 4470 8850 12,250 13,150

NEMA Size

Continuous Current

00 0 1 2 3 4 5 6 7

9 18 27 45 90 135 270 540 810

1.5 3 7.5 10 25 40 75 150

1.5 3 7.5 15 30 50 100 200 300

2 5 10 25 50 100 200 400 600

2 5 10 25 50 100 200 400 600

BN9M-1 BN16M-1 BN25M-1 BN50M-1 BN75M-1 EHN145M-1 EHN260M-1 EHN550M-1 EHN800M-1

$ 170 230 270 475 770 1490 2990 8190 12,490

BCN9M-P BCN16M-P BCN25M-P BEN50M-P BEN75M-P EHN145M-P EHN260M-P EHN550M-P EHN800M-P

$ 230 290 330 535 910 1770 3370 8850 13,150

Description
Mechanically interlocked contactors are designed for reversing, 2speed, reduced voltage, etc. type starter applications. The complete assembly consists of two mechanically and electrically interlocked contactors mounted as follows with line and load terminals:
B9 - B16 mounted on 35mm DIN rail B25 - EH800 mounted on common baseplate Control and power wiring are not included

Coil voltage selection


All AC operated catalog numbers include a 120VAC coil. All DC operated catalog numbers include a 110VDC coil. To select other coil voltages, substitute the code from the Coil Voltage Selection chart for the first digit after the dash in the catalog number.

Coil voltage selection chart


Contr. type 60 A,B,EH 50 A,B 50 EH DC A,B,EH Hz 24 F F N Y Volts 48 110 120 125 208 220 240 277 380 415 440 480 500 600 G 1 B 2 C Z 3 4 6 1 2 3 4 6 1 J 3 M 5 W P Q R T

Auxiliary contacts as standard


Frame size Number of contacts Mounting

B(C)9 B(C)25 B(C)30 B(E)40 EH800 A(E)95 A(E)110

1 N.O. 2 N.O. & 2 N.C. 1 N.O. & 1 N.C. 1 N.O. & 1 N.C.

Internal Top Side Side

For other voltages, consult factory. 24 & 48VAC coils are not available for sizes EH450 EH800. For these applications, use an interposing control relay.

EH Contactors supplied less lugs


Lug kits can be ordered for EH contactors. Subtract the terminal kit price shown on page 15 and add the "L" suffix as the last digit in the catalog number. EX: EH145M-1L
Technical data: 1.22 - 1.35 Approximate dimensions: 1.36 - 1.49

AC 1000 2/97

Additional auxiliary contacts are available for all contactor sizes. See Accessories.
CONTACTORS:
Selection: 1.4 - 1.7 Accessories: 1.8 - 1.20

Renewal parts: 1.21

1.6

Type A Discount schedule AA Type B Discount schedule BA Type EH Discount schedule EA

Across the line contactors Reversing, 3 pole

B9R-1

B50R-1

EH260R-1

3 Pole, A.C., Open


General purpose current Maximum motor horsepower ratings 200V 230V 460/480V 575/600V AC operated Catalog number List price DC operated Catalog List number price

AC1 21 21 21 33 45 55 65 85 105 125 140 170 190 230 300 350 525 600 715 900

AC3 9 11 17 28 32 41 52 65 80 80 105 130 156 192 242 302 420 480 602 810 2 3 5 7.5 10 10 15 20 25 30 30 40 50 60 75 100 125 150 200 250 2 3 5 10 10 15 20 25 30 30 40 50 60 75 100 100 150 200 250 300 5 7.5 10 20 20 30 40 50 60 60 75 100 125 150 200 250 350 400 500 600

UL rated 7.5 10 15 25 30 40 50 50 75 75 100 125 150 200 250 250 400 500 600 700 NEMA rated B9R-1 B12R-1 B16R-1 B25R-1 B30R-1 B40R-1 B50R-1 B63R-1 B75R-1 A95R-1 A110R-1 EH145R-1 EH175R-1 EH210R-1 EH260R-1 EH300R-1 EH450R-1 EH550R-1 EH700R-1 EH800R-1 $ 210 250 275 320 375 500 540 675 865 950 1085 1500 2250 2700 3000 3650 4000 8200 11,600 12,500 BC9R-P BC16R-P BC25R-P BC30R-P BE40R-P BE50R-P BE63R-P BE75R-P AE95R-P AE110R-P EH145R-P EH175R-P EH210R-P EH260R-P EH300R-P EH450R-P EH550R-P EH700R-P EH800R-P $ 270 335 380 435 580 620 715 905 1090 1200 1780 2590 3040 3380 4030 4480 8860 12,260 13,160

NEMA Size

Continuous Current

00 0 1 2 3 4 5 6 7

9 18 27 45 90 135 270 540 810

1.5 3 7.5 10 25 40 75 150

1.5 3 7.5 15 30 50 100 200 300

2 5 10 25 50 100 200 400 600

2 5 10 25 50 100 200 400 600

BN9R-1 BN16R-1 BN25R-1 BN50R-1 BN75R-1 EHN145R-1 EHN260R-1 EHN550R-1 EHN800R-1

$ 210 275 320 540 865 1500 3000 8200 12,500

BCN9R-P BCN16R-P BCN25R-P BEN50R-P BEN75R-P EHN145R-P EHN260R-P EHN550R-P EHN800R-P

$ 270 335 380 620 905 1780 3380 8860 13,160

Description
Reversing contactors are designed for reversing, 2-speed, reduced voltage, etc. type starter applications. The complete assembly consists of two mechanically and electrically interlocked contactors mounted as follows with line and load terminals: B9 - B16 mounted on 35mm DIN rail B25 - EH800 mounted on common baseplate Control and power wiring are included.

Coil voltage selection


All AC operated catalog numbers include a 120VAC coil. All DC operated catalog numbers include a 110VDC coil. To select other coil voltages, substitute the code from the Coil Voltage Selection chart for the first digit after the dash in the catalog number.

Coil voltage selection chart


Contr. type 60 A,B,EH 50 A,B 50 EH DC A,B,EH Hz 24 F F N Y Volts 48 110 120 125 208 220 240 277 380 415 440 G 1 B 2 C Z 3 1 2 3 4 1 J 3 M W P Q R T 480 500 600 4 6 6 5

Auxiliary contacts as standard


Frame size Number of contacts Mounting

B(C)9 B(C)25 B(C)30 B(E)40 EH800 A(E)95 A(E)110


AC 1000 2/97

1 N.O. 2 N.O. & 2 N.C. 1 N.O. & 1 N.C. 1 N.O. & 1 N.C.

Internal Top Side Side

For other voltages, consult factory. 24 & 48VAC coils are not available for sizes EH450 EH800. For these applications, use an interposing control relay.

Additional auxiliary contacts are available for all contactor sizes. See Accessories.

EH Contactors supplied less lugs


Lug kits can be ordered for EH contactors. Subtract the terminal kit price shown on page 15 and add the "L" suffix as the last digit in the catalog number. EX: EH145R-1L

CONTACTORS:

Selection: 1.4 - 1.7

Accessories: 1.8 - 1.20

Renewal parts: 1.21

Technical data: 1.22 - 1.35

Approximate dimensions: 1.36 - 1.49

Discount schedule AA Type A Discount schedule BA Type B Discount schedule EA Type EK

1.7

Accessories for across the line contactors Auxiliary contact blocks


Auxiliary contact blocks for A & B Contactors
Contactor size Description Mounting position Catalog number List price

K(C) & B9 B75

1 N.C. 1 N.O. N.O. Leading N.C. Lagging Impulse N.O. Impulse N.C. 1 N.C. 1 N.O. 1 N.O./1N.C. Overlapping 1 N.O./1 N.C. Overlapping 4 N.O. 3 N.O. & 1 N.C. 2 N.O. & 2 N.C. 4 N.O. 2 N.O. & 2 N.C. 4 N.O. 2 N.O. & 2 N.C. 4 N.C. 4 N.C. 3 N.O. & 1 N.C. 2 N.O. & 2 N.C. 1 N.O. & 1 N.C. 1 N.O. & 1 N.C.

Top

CA7-01 CA7-10 CC7-10 CC7-01 CB7-10 CB7-01 CA5-10 CA5-01 CA7-11/11E CA7-11/11M CA7-40E CA7-31E CA7-22E CA5-40E CA5-22E CA7-40K CA7-22K CA7-04K CA7-04M CA7-31M CA7-22M CAL7-11 CAL5-11

$ 10

CA7-10

A(E)95 110 B(E)40 B(E)75 B(C)9B(C)25, B(C)30 B(C)9 B(C)25 (4 pole) B(C)30 A(E)95 110

Top Top

20

Top

1
CA7- 40 E

Top

40

K(C) B(E)40 B(E)75

Top

B(C)9 B(C)25 B(E)40 B(E)75 A(E)95 110

Top Side Side

20

Auxiliary contact blocks for EH contactors


Description

Terminal Markings NO NC

Catalog number

List price

CB7-10

Standard 1 N.O. & 1 N.C. Standard 1 N.O. & 1 N.C. Standard 1 N.O. & 1 N.C. Standard 1 N.O. & 1 N.C. Late break 1 N.O. & 1 N.C. Mechanical interlock auxiliary, N.O. (VH80-VH300) Mechanical interlock auxiliary, N.C. (VH80-VH300)

13, 14 43, 44 53, 54 83, 84 47, 48 93, 94

21, 22 31, 32 61, 62 71, 72 35, 36 91, 92

CAL16-11A CAL16-11B CAL16-11C CAL16-11D CAL16-11E CA16-10 CA16-01

$ 44 44 44 44 50 22 22

Auxiliary contacts are available in various versions single pole, two pole and four pole blocks. Types CA : instantaneous normally open and normally closed. CC : normally open leading and normally closed lagging. CB : impulse, normally open and normally closed.

CAL7 -11

Description CA7, CC7, CD 7, CAL7, CA5, CAL5 offer captive terminal screws and self-lifting cable clamps. The terminal screws are supplied open and are protected against accidental touch. Screwdriver guide holes aid speedy wiring. CAL 16 and CCL16 have self cleaning contacts. They offer captive terminal screws and self lifting cable clamps. They are protected against unintentional direct touch. CB7 impulse contact are mainly used as "start" contact (e.g. across the line starters). They are delivered with built-in terminal leads. (red leads for CB 7-01 and black leads for CB 7-10). All auxiliary contacts provide "positive safety" between N/O and N/ C contacts thus avoiding the overlapping between opposite functions according to regulations (e.g. ZH1/ 457, INRS, SV). This is not applicable to auxiliary contact blocks fitted with leading or lagging or adjustable contacts. Mounting Single pole and four pole blocks : Clip-on the front face of control relays (K & KC) and contactors (B 9 to B75, BC9 to BC30, BE 40 to BE 75, A95, A110). Two pole blocks : on left and right side of the contactors : CAL7- 11 on B and BE40 to 75 clip on the side of the contactor CAL 16 on EH 145 to EH 800 and EK110 to EK550 are screwed on to the side of the contactor CAL5-11 clips on the side of the A95 & A110 contactors.
AC 1000 2/97

CONTACTORS:

Selection: 1.4 - 1.7

Accessories: 1.8 - 1.20

Renewal parts: 1.21

Technical data: 1.22 - 1.35

Approximate dimensions: 1.36 - 1.49

1.8

Discount schedule AB

Accessories for across the line contactors Surge suppressors, mechanical interlocks
Surge suppression devices for B, A and EH contactors
Contactor Coil voltage (AC/DC) Catalog number List price

Varistor type B, BC, BE RC type EH145 EH300 RC type EH450 EH800


RV-BC6/60

24 60V 110 250V 200 420V 24 48V (AC only) 110 415V (AC only) 24 - 125VDC /48 110VAC 220 600V (AC only) 24 50 110 250 24 50 110 250 50V 133V 250V 440V 50V 133V 250V 440V

RV-BC6/60 RV-BC6/250 RV-BC6/380 RC-EH250/48 RC-EH250/415 RC-EH800/110 RC-EH800/600 RC5-2/50 RC5-2/133 RC5-2/250 RC5-2/440 RV5/50 RV5/133 RV5/250 RV5/440 $ 17

RC Type A95 A110

20

Varistor type A95 A110

1
List price

Mechanical interlocks for A & B contactors


RV-BC6/60 For contactor type Current Catalog number

B9 B30 BC9 BC30 A95 A110 B(E)50 B(E)75

AC DC AC & DC AC & DC

VB30 VBC30 VE5-2 VB75

$ 14 18 30 20

Mechanical interlocks are designed to mechanically interlock two contactors or starters, B9, BC9-B75, BE75, A95, A110. They are used on reversing, multispeed, reduced voltage, transfer switch and other applications. The mechanical interlock incorporates a mechanism which will accept two contactors of the same size or two dissimilar size contactors. The beginning stroke of either contact carrier locks the interference mechanism and prevents the contacts on the other contactor from closing. A95 A110 mechanical interlock includes two normally closed contacts for electrical interlock between the contactors.
VH300

Mechanical interlocks Between EH contactors of same sizes


Left contactor size Right contactor size Catalog number List price

EH145 EH175, 210, 260, 300

EH145 EH175, 210, 260, 300

VH145 VH300

$ 70 130

Mechanical interlocks Between EH contactors of different sizes


VH550A Left contactor size Right contactor size Catalog number List price

EH175, 210 EH260, 300 EH450, 550 EH700, 800

EH110, 145 EH175, 210 EH260, 300, 450, 550 EH450, 550, 700, 800

VH210A VH300A VH550A VH800A

$ 172 264 324 384

Mechanical interlocks For use with EH contactors with a mechanical latch


Left contactor size Right contactor size Catalog number List price

EH145 EH175, 210 EH260, 300

EH145 EH145 210 EH175 300

VH145W VH210W VH300W

$ 148 172 204

Mechanical interlocks are designed to mechanically interlock two contactors or starters, EH145 - EH800. They are used on reversing, multispeed, reduced voltage and transfer switch applications. The mechanical interlock incorporates a mechanism which will accept two contactors of the same size or two dissimilar size contactors. The beginning stroke of either contact carrier locks the interference mechanism and prevents the contacts on the other contactor from closing.
AC 1000 2/97

The VH80 - VH300 mechanical interlocks also include (2) N.C. contacts for electrical interlock between the contactors. On top of the mechanical interlock it is also possible to mount an auxiliary contact block, N.O. (CA16-10) or N.C.(CA16-01), one for each contactor.

CONTACTORS:

Selection: 1.4 - 1.7

Accessories: 1.8 - 1.20

Renewal parts: 1.21

Technical data: 1.22 - 1.35

Approximate dimensions: 1.36 - 1.49

Discount schedule AB

1.9

Accessories Mechanical interlocks for A, B, EH & EK contactors


Utilization
A mechanical interlock between two contactors prevents the closing of one of the contactors as long as the other remains closed.

Mechanical interlocks for horizontal mounted contactors (a.c. or d.c. operated)


Catalog number Description Mech. interlock mounting 2 contactors side by side Left Right Contactor mounting

VB30
B25M-1 (2) B25 contactors interlocked by (1) VB30 mechanical interlock

Block type Block type

sideways ; clip-on front side ; clip-on


(free space for 2 aux. contacts CA 7- .. on each contactor)

K, B9 75 K, B9 30 KC, BC9 16 BC25 BC30

K, B9 30 K, B9 75 KC, BC9 16 BC25 BC30

or extra plate or extra plate

VBC30

VB75

Block type Block type Block types


c / w 2 N.C. contacts electrical interlocking of both contactors. Add - on aux. contacts N.O. or N.C. type CA 16 - .. can be fitted as extra. See "Accessories" on following page.

1
VB30

sideways ; clip-on sideways ; clip-on sideways, by-screws

B(E)40 75 A95, 110 EH145 EK110, 150

B(E)40 75 A95, 110 EH145 EK110, 150

or extra plate or extra plate extra plate extra plate

VE5-2 VH145

VH210 A VH300
VBC30

EH175, 210 EH175300 EK175, 210 rear side ; by-screws EH145 EH175, 210 EH260, 300 rear side, by-screws EH450, 550 EH700, 800 EK370, 550

EH145 EH175...300 EK175, 210 EH145 EH145 210 EH175 300 EH300 550 EH450 800 EK370, 550

extra plate extra plate extra plate (the plate is supplied with the mechanism)

VH145W VH210W VH300W VH550 VH800

Base- plate c /w mechanism


These types are adaptable for interlocking of contactors with WH .. latch.

Base- plate c/ w mechanism

VH145

VH170

AC 1000 2/97

VH550

Mounting: depending on their construction details, physical size, contactors can be mounted on din rail on users own baseplate.
Accessories: 1.8 - 1.20 Renewal parts: 1.21 Technical data: 1.22 - 1.35

or on ABB base- plates or directly

CONTACTORS:

Selection: 1.4 - 1.7

Approximate dimensions: 1.36 - 1.49

1.10

Discount schedule AB

Accessories for across the line contactors Mechanical latches for B Contactors

Range
WB 75 for contactors B 9 to B 75, BC 9 to BC 30, BE40 to BE 75 and contactor relays K, KC 1 stack. WH80 WH800 for contactors EH145 EH800 a.c. and d.c. operated. WH80 R WH800 R for mounting on right side contactor of a reversing pair. WH80 L WH800 L for mounting on left side contactor of a reversing pair.

Description
G WB75 is a compact block which comprises a latch mechanism with both electrical and manual de-latching. It can be a.c. or d.c. operated,

but can not withstand continuous supply on either a.c. or d.c. The connection terminals of the latching block are delivered in open position, with captive screws M 3.5 and self-lifting cable-clamps, pozidriv (+, ) screwhead designed for guiding of screwdriver and protected against unintentional direct touch. Operation The contactor closing sets the WB75 in latched position thus holding the contactor in closed position even if the contactor coil is not energized. In this case, the contactor de-latching can be achieved in two ways : electrically, with a short electric impulse to the coil of the latching block; manually, by pushing on the button located at the front of the latching block.

Mechanical latches for B contactors


Contactor Catalog number List price

B, BC, BE # Coil voltage suffix. Refer to Coil Voltage Selection Chart and substitute the desired coil voltage suffix for the #.

WB75-#

$ 56

Coil voltage selection chart Mechanical latches for B contactors


Hz 60 WB75-04 50 DC 24 01 01 01 42 02 02 02 48 03 03 03 110 04 04 04 120 04 Volts 220 06 06 06 240 05 05 277 05 380 07 07 07 415 07 08 08 480 08

AC 1000 2/97

CONTACTORS:

Selection: 1.4 - 1.7

Accessories: 1.8 - 1.20

Renewal parts: 1.21

Technical data: 1.22 - 1.35

Approximate dimensions: 1.36 - 1.49

Discount schedule AB

1.11

Accessories for across the line contactors Mechanical latches for EH contactors

Range
WB75 for contactors B 9 to B 75, BC 9 to BC 30, BE40 to BE 75 and contactor relays K, KC 1 stack. WH145 WH800 for contactors EH145 EH800 a.c. and d.c. operated. WH145 R WH800 R for mounting on right handside contactor of a reversing pair. WH145 L WH800 L for mounting on left handside contactor of a reversing pair.

Description
G WH 145 WH 800 are supplied with a mounting plate. They can be delivered with either a.c. or d.c. coils but cannot withstand continuous supply. They are also available for reversing, and then delivered without mounting plate. Latches can be mounted on one or both contactors. Should contactors of different sizes be used on the same interlocking device, then select the mechanical latch corresponding to the size of the contactor.

Operation The closing of contactor M sets the WH in latched position thus holding the contactor in closed position and automatically opening the coil circuit of the contactor by means of a built-in auxiliary contact of the latch (11-12). However, a separately mounted contactor relay is required for d.c. operated contactors). The contactor de-latching is operated by means of a current pulse to the coil of the on-position latch. For latched d.c. operated contactors, the economizing device of the contactor M has to be removed and the releasing contact (11-12) of the latch has to be connected acc. to the diagram: see opposite page. For d.c. voltages wire two aux. contacts in series with the latching coil. i. e. 13-14 and 43-44.

Mounting
WB75 .................................................... snaps on the front face of the contactor. WH145 WH800 ................................ Contactor and latch have to be mounted on the base plate of the latch. WH145 (R or L) WH800 (R or L) .... Contactors and latches have to be screwed on the interlocking plate. See Transition section for contactors EH80 through EH270.

Mechanical latches One contactor


Contactor size

With AC release coil Catalog List number price

With DC release coil Catalog List number price

EH145 EH175 - EH210 EH260 - EH300 EH450 - EH550 EH700 - EH800

WH145-# WH210-# WH300-# WH550-# WH800-#

$ 144 382 382 444 540

WH145-# WH210-# WH300-# WH550-# WH800-#

$ 174 412 440 494 600

13

CONTACTORS:

13 LATCH 14 12 L 11 A1 M A2

UNLATCH

# Coil voltage suffix. Refer to the Coil voltage selection chart and substitute the desired coil voltage for the #.

14 14 M 13 E2 L E1

Mechanical latches Right mounting on reversing pair


Contactor size With AC release coil Catalog List number price With DC release coil Catalog List number price

EH145 EH175 - EH210 EH260 - EH300 EH450 - EH550 EH700 - EH800

WH145R- # WH210R- # WH300R- # WH550R- # WH800R- #

$ 144 382 382 444 540

WH145R-# WH210R-# WH300R-# WH550R-# WH800R-#

$ 174 412 440 494 600

# Coil voltage suffix. Refer to the Coil voltage selection chart and substitute the desired coil voltage for the #.

Mechanical latches Left mounting on reversing pair


Contactor size With AC release coil Catalog List number price With DC release coil Catalog List number price

EH145 EH175 - EH210 EH260 - EH300 EH450 - EH550 EH700 - EH800

WH145L- # WH210L-# WH300L-# WH550L-# WH800L-#

$ 144 382 382 444 540

WH145L-# WH210L-# WH300L-# WH550L-# WH800L-#

$ 174 412 440 494 600

# Coil voltage suffix. Refer to the Coil voltage selection chart and substitute the desired coil voltage for the #.

Coil voltage selection chart


Contr. type 60 A,B,EH 50 A,B 50 EH DC A,B,EH Hz 24 F F N Y Volts 48 110 120 125 208 220 240 277 G 1 B 2 C 1 2 1 J W P Q R 380 415 440 480 500 600 Z 3 4 6 3 4 6 3 M 5 T

For other voltages, consult factory. 24 & 48VAC coils are not available for sizes EH450 EH800. For these applications, use an interposing control relay.

AC 1000 2/97

Selection: 1.4 - 1.7

Accessories: 1.8 - 1.20

Renewal parts: 1.21

Technical data: 1.22 - 1.35

Approximate dimensions: 1.36 - 1.49

1.12

Discount schedule AB

Accessories for across the line contactors Shorting bars, terminal kits, bus bar kits, power takeoff terminals
Shorting bars for EH contactors
Contactor size Catalog number List price

EH145, EH175, EH210 EH260, EH300 EH450, EH550 EH700, EH800

LY210 LY300 LY550 LY700

$ 12 16 30 34

Copper shorting bars for interconnecting the load terminals are available for EH145 EH800 contactors. Mounting hardware supplied with the contactors may be used to mount the shorting bars.
LY210

Terminal kits for EH contactors


3 pole Contactor size 4 pole Wire size Catalog number List price

EH145 (Cu only) EH175, 210 EH260 EH300, 550 EH450 EH700 EH800

EK150 EK175 EK210 EK370, 550

8 3/0 (Cu only) 6 250 MCM 4-500 MCM 4 500 MCM (2) 4 500 MCM (2) 6 300 MCM (2) 4 500 MCM (3) 2 600 MCM

EHTK145 EHTK210 EHWTK160 EHTK260 EHTK550N EHTK450 EHTK700 EHTK800

$ 25 30 30 45 75 60 100 225

Terminal kit includes a set of three terminals and mounting hardware for mounting the terminals on either the line or the load side of the contactor. All terminals are CU/AL and are UL recognized.
1 3 5

Bus bar kits for B & A contactors


Mechanically interlocked contactor size Phase to phase catalog number List price Reversing catalog number List price

B40 B75 A95 A110

BES75-30 BES110-30

$ 50 60

BEM75-30 BEM110-30

$ 100 120

BES75-30

Bus bar kits for EH contactors


Mechanically interlocked contactor size Phase to phase catalog number List price Reversing catalog number List price

EH145 EH175/210 EH260/300 EH450/500 EH700 EH800

BES145-30 BES210-30 BES300-30 BES550-30 BES700-30 BES800-30

$ 110 150 175 350 400 510

BEM145-30 BEM210-30 BEM300-30 BEM550-30 BEM700-30 BEM800-30

$ 220 300 350 700 800 1020

Two bus bar connector kits are available for EH145 EH800 mechanically interlocked contactors. The phase to phase bus bar kit provides three parallel connections for the line side of two mechanically interlocked contactors. The reversing bus bar kit provides six busbars; three connections for reversing phases A and C on the load side of two mechanically interlocked contactors; and three parallel connections. Mechanically interlocked contactors intended for use on reversing applications require both kits.

Power takeoff terminals for B & A contactors


Contactor sizes Reversing catalog number List price

B40 - B75 A95 - A110

LK75 LK110

$ 10

AC 1000 2/97

For EK contactors, use three lug kits for both line and load sides.

CONTACTORS:

Selection: 1.4 - 1.7

Accessories: 1.8 - 1.20

Renewal parts: 1.21

Technical data: 1.22 - 1.35

Approximate dimensions: 1.36 - 1.49

Discount schedule AB

1.13

Accessories for across the line contactors Mounting rail, end supports, timers, Transparent cover, labels, terminal covers
Mounting rail for B contactors
Contactor Catalog number List price

B, BC, BE

BMR-40

$ 14

Universal mounting rails (35mm DIN type) are available in 39 inch strips (1 meter) and can be cut to desired lengths and attached to panels. Contactors have built in clips which allow for snap-on mounting.

End supports for B contactors


Description Catalog number List price

Set of 2
Mounting rail, BMR-40 & end support, BESK-40

BESK-40

$ 4

Pneumatic timers for B contactors

Timing range (seconds)

Catalog number

List price

TP40D

0.1 40 (On delay) TP40D 10 180 (On delay) TP180D $ 72 0.1 40 (Off delay) TP40I 10 180 (Off delay) TP180I Snaps onto the top of the B contactor. The adjustable timer is equipped with 1 N.O. and 1 N.C. timed contact which operates after the timer coil has energized (on-delay) or after the timer coil has de-energized (off delay). Available in two ranges.

Electronic timers for Wye-Delta starters


Timing range (seconds) Voltage Catalog number List price

1.5 30 (On-delay)

110-240

C461.13-30-2

$ 175

Transparent cover for pneumatic timer


Description Catalog number List price

Snaps onto top of pneumatic timer

BX-TP

$ 10

C461.13-30-2

Identification labels
Description Catalog number List price

Snap-on label holders with labels

BA50

$ 20

Includes 50 non-adhesive labels, 75 self-adhesive labels, 50 label holders and 50 transparent covers.

Terminal covers for EH & EK contactors


Description BX-TP Catalog number List price

EH145 EH210 with terminal kits EH145 EH210 without terminal kits EH260 EH300 with or without terminal kits EH450, EH500 with or without terminal kits EH700 with or without terminal kits EH800 without terminal kits EK110, EK150 with or without terminal kits EK175, EK210 with or without terminal kits EK370, EK550 with or without terminal kits

LT210-EL LT210-EC LT300-E LT550-E LT700-E LT800-E LT150-EK LT210-EK LT550-EK

$ 12 16 24 26 28 30 35 60 60

BA50

AC 1000 2/97

CONTACTORS:

Selection: 1.4 - 1.7

Accessories: 1.8 - 1.20

Renewal parts: 1.21

Technical data: 1.22 - 1.35

Approximate dimensions: 1.36 - 1.49

1.14

Discount schedule AB

Accessories for across the line contactors Interface relays RA30, RA75

Operating voltage

For contactor types V c

Coil voltages

Catalog number

List price

24V.D.C. 24V.D.C.

K, B 9 ... B 30 KC, BC 9 ... BC 30 B 40 ... B 75

24 ... 250 V 50, 60Hz 12 ... 250 V.D.C. 24 ... 250 V 50, 60Hz

RA 30 RA 75

$ 35 50

Utilization
RA 30

Interface relays RA30 and RA75 are controlled from signals delivered by PLC's or any other type of sources characterized by a low rated power on their output side; those signals are then restored with the suitable power required to operate the associated contactors.

Types
RA30 suitable for contactors B(C)9 to B(C)30 and auxiliary contactors K(C). RA75 suitable for contactors B40 to B75.

Description
Interface relays RA30 and RA75 consist of a small electromechanical relay comes with a normally open contact and a 24 V d.c. low consumption coil.The interface relay coil is controlled from the PLC and its normally open contact operates the contactor.The switching of coils (inductive loads) causes voltage surges which are generating disturbances in the electronic devices, burning out the insulators, or shortening life, of the sensitive components. The interface relays RA30 and RA75 are equipped with built-in surge suppressors on : the interface relay coil, via a diode the contactor coil, via a varistor.In addition, interface relays RA30 and RA75 are protected against a reverse polarity energization of their coil, via a diode connected to the incoming terminals E1 and E2.

Connecting
Incoming terminals "E1+" and "E2" must be wired to the "+" and "" PLC outputs respectively. The RA30 type is equipped with two wires to be connected to the contactor coil terminals A1 and A2. Terminal A2 (on contactor coil) and terminal A0 (on the RA30 interface relay) are used for the contactor coil energization. The RA75 type is equipped with two flat connections ("Y" shaped) which fit contactor coil terminals A1 and A2. Both terminals A0 and A2 of the RA75 interface relay, are used for the contactor coil energization.

B 9 contactor + RA 30

Mounting
RA30: on a dovetail, located on the top part of the contactor base. RA75: straight onto contactor terminals A1 and A2.

Wiring diagrams
RA 75

Interface relay RA 30 for contactors K, Interface relay RA75 for contactors B40 B75, B9 B30 and KC, BC9 BC30

PLC output 24 V d.c. A0 RA 30 E2 E1 + +

PLC output Uc 250 V a.c. A0 RA 75 A2 24 V d.c. E2 E1 + +

Uc Uc

250 V a.c. 250 V d.c.

A1 K1 A2

A1 K1 A2

B 75 + RA 75

AC 1000 2/97

CONTACTORS:

Selection: 1.4 - 1.7

Accessories: 1.8 - 1.20

Renewal parts: 1.21

Technical data: 1.22 - 1.35

Approximate dimensions: 1.36 - 1.49

Discount schedule AB

1.15

Accessories for across the line contactors Interface relays RA30, RA75 Technical data
Types RA 30 RA 75 IEC 255-5 VAC 250

General technical data


Standards Rated insulation voltage Vi acc. to VDE 0110 (Gr.C) Permissible ambient temperature: for operation in free air: at Vc (between E1 and E2) = 24V d.c. from 0.85 to 1.1Vc for storage Climatic resistance Mounting positions Operating altitude Fixing Connecting terminals (delivered in open position) Connecting capacity : rigid solid flexible Protection degree

C C C
metres

25 ... + 70 25 ... + 55 40 ... + 70 Same as for associated contactors No limitation 3000 On a dovetail on top part Via connecting parts onto of the contactor base contactor terminals A1 and A2 Cable clamps with pozidrive +, , screw heads M 3.5 18 12 AWG 18 14 AWG Protection against unintentional direct touch of live parts acc. to VDE 0106

2 x AWG 2 x AWG

Construction and operating data


Integrated surge suppression: for contactor coil for interface relay coil Protection against polarity inversion between terminals E1, E2 Utilization for contactors with coils: 24 ... 250V / 50, 60 Hz types 12 ... 250V d.c. types Interface relay operating times ms Total operating times, interface relay + contactor : from energization to : closing of the N.O. contact ms opening of the N.C. contact ms from de-energization to : opening of the N.O. contact ms closing of the N.C. contact ms Varistor Diode Diode K, B9..B18, B26 B25, B30 KC, BC9...BC30 Closing or opening 10 B40 ... B75

18 ... 26 15 ... 23 15 ... 23 17 ... 25

19 ... 29 16 ... 26 15 ... 25 17 ... 27

59 ... 84 54 ... 79 25 ... 40 27 ... 42

19 ... 36 16 ... 32 15 ... 25 18 ... 28

Input electrical data


Coil operating voltage (terminals E1, E2) Vc : rated value max. range Max. coil consumption for Uc = 24V d.c., q = 20 C State "0" (relay in open position) for Vc or I c State "1" (relay in closed position) for Vc Max. voltage drop time VDC VDC W VDC mA VDC ms 250 250 10 million with 1200 ops./h 24 17 ... 30 0.3 2.4 <1 17 4 250 3 million with 600 ops./h

Output electrical data


Switching voltage (terminals A0, A2) Electrical endurance for 220/240V a.c. VDC VDC ops.

AC 1000 2/97

CONTACTORS:

Selection: 1.4 - 1.7

Accessories: 1.8 - 1.20

Renewal parts: 1.21

Technical data: 1.22 - 1.35

Approximate dimensions: 1.36 - 1.49

1.16

Discount schedule AB

Accessories for across the line contactors Coils


Coils for A contactors
Contactor size AC coils catalog number List price DC coils catalog number List price

A 95, A110

ZA110-#

$ 40

ZAE110-#

$ 60

Coils for B contactors


Contactor size AC coils catalog number List price DC coils catalog number List price

KB16-1

B9 B16 B25 B30 B40 B75

KB16-# KB30-# KB75-#

$ 12 20 38

KBC30-# KBC30-# KBE75-#

$ 24 40 76

# Coil voltage suffix. Refer to Coil Voltage Selection Chart and substitute the desired coil voltage suffix for the #. A.C. and D.C. operated contactors DO NOT have the same magnet structure. Therefore, D.C. coils will not fit on an A.C. magnet structure and vice versa.

Coils for EH contactors


Contactor size AC coils catalog number List price DC coils catalog number List price

1
KH145-# KH210-# KH300-# KH550-# KH800-# $ 80 100 120 240 290 KH145-# KH210-# KH300-# KH550-# KH800-# $ 100 130 160 300 350

KH145-1

EH145 EH175, 210 EH260, 300 EH450, 550 EH700, 800

# Coil voltage suffix. Refer to Coil Voltage Selection Chart and substitute the desired coil voltage suffix for the #. A.C. and D.C. operated contactors DO NOT have the same magnet structure. Therefore, D.C. coils will not fit on an A.C. magnet structure and vice versa.

Mechanical latch coils for EH contactors


Contactor size AC coils Catalog number List price DC coils Catalog number List price

EH145 EH800

KX800-#

$ 40

KX800-#

$ 50

# Coil voltage suffix. Refer to Coil Voltage Selection Chart and substitute the desired coil voltage suffix for the #. EH145 - EH800 A.C. and D.C. operated contactors have the same magnet structure except the D.C. coils include a resistor and a normally closed late break auxiliary interlock. KH300-1

Replacement auxiliary contact blocks


Replacement auxiliary contact blocks are identical to the extra auxiliary contact blocks which can be added to the contactor. See Accessories.

Coil voltage selection chart


Contr. type 60 A,B,EH 50 A,B 50 EH DC A,B,EH Hz 24 F F N Y Volts 48 110 120 125 208 220 240 277 380 415 440 480 500 600 G 1 B 2 C Z 3 4 6 1 2 3 4 6 1 J 3 M 5 W P Q R T

KX800

For other voltages, consult factory. 24 & 48VAC coils are not available for sizes EH450 EH800. For these applications, use an interposing control relay.

AC 1000 2/97

CONTACTORS:

Selection: 1.4 - 1.7

Accessories: 1.8 - 1.20

Renewal parts: 1.21

Technical data: 1.22 - 1.35

Approximate dimensions: 1.36 - 1.49

Discount schedule AB

1.17

Accessories for across the line contactors Mounting instructions B(C)9-30, K(C), TKC
1 RV-BC6 2 VB 30

LINE SIDE 1(L1), 3(L2), 5(L5) B9...30

1
8

BC9...30

3 4 5 A 7 B 6 CA7 4 - Pole CA7 1 - Pole ( Max. of 4. max 2 NC on BC 9-25 )

TP ... D; TP...1 VBC 30 ( Allows 2 additional 1-pole CA7 on each contactor. )

T 25 DU

WB 75 ( Allows 1 additional 1-pole CA7 on each side. )

1. Surge suppressor Slide the device onto the ridge located on the contactors line side. Connect leads to the coil terminals A1 and A2. 2.Mechanical interlock for AC operation Tilt the device and slide the bottom feet up into slots on the bottom of the contactor. Push in top of device and snap into place. 3. Auxiliary contact block 1-pole Tilt device and slide it on from the contactors line side, white lever arm should face the line side. When in position the device will snap into place. To dismount device lift up white lever arm and slide it off in reverse from mounting. 4. Auxiliary contact block 4-pole See 3. above for instructions. 5. Pneumatic timer See 3. above for instructions. 6. Mechanical latch for AC / DC release See 3. above for instructions. 7. Overload relay Open terminal 2,4 and 6 on the line side of the contactor. For mounting to contactors, fixed connection pins A. and moving connection pin (middle pin) must be inserted into the contactor (according to wiring diagram) and the plastic hook B. must be hooked into the loop which is provided on the contactor. For mounting to contactors BC 9 and BC 16, the plastic hook must be shortened by 6 mm. when device is fully pushed in, torque terminal screws 2,4 and 6 according to chart below. B(C)9-129 in-lb B(C)16-2512 in-lb B(C)3020 in-lb 8. Mechanical interlock for DC operation See 3. above for instructions. except white lever arm is replaced by black spring tensioned latch. The DC latch comes with a spacer that mounts between the contactors, BC9 -16 only. The spacer slides in from the bottom of the contactor up into the groove located on the side of the contactor. TORQUE CHART Power Terminals B ( C ) 9 -12 B ( C ) 16 -25 B ( C ) 30 9 in-lb + / - 10% 12 in-lb + / - 10% 20 in-lb + / - 10% B9, B12, B16 BC9, BC16

B25

BC25

B30 BC30

T25 DU

T25 DU

T25 DU

T25 DU

Accessory Terminals 7 in-lb + / - 10%

AC 1000 2/97

CONTACTORS:

Selection: 1.4 - 1.7

Accessories: 1.8 - 1.20

Renewal parts: 1.21

Technical data: 1.22 - 1.35

Approximate dimensions: 1.36 - 1.49

1.18

Discount schedule AB

Accessories for across the line contactors Mounting instructions B B(E)40 75, A(E) 95 110

1 RC / RV 4

2 VE5-2 VB75

CP 50

LINE SIDE 1(L1), 3(L2), 5(L3) 3 CAL 5-11 CAL 7-11 BE 40 ... 75

1
5 6 7

B 40 ... 75 CAL 5-11 or CAL 7-11 ( Allows max. 1 CAL 5-11 or CAL 7-11 on each side. ) 8

CA5 & CA7 1 - Pole ( Max. of 6. ) CA5 & CA7 4 - Pole

TP ... D; TP...1

WB 75 ( Allows 2 additional 1-pole CA7 on each side. )

( Allows 1 additional 1-pole CA5 & CA7 on each side. )

1. SURGE SUPPRESSOR SLIDE THE DEVICE ONTO THE RIDGE LOCATED ON THE CONTACTORS LINE SIDE. CONNECT LEADS TO THE COIL TERMINALS A1 AND A2. 2.MECHANICAL INTERLOCK TILT THE DEVICE AND SLIDE THE BOTTOM FEET UP INTO SLOTS ON THE BOTTOM OF THE CONTACTOR. PUSH IN TOP OF DEVICE AND SNAP INTO PLACE. 3. AUXILIARY CONTACT BLOCK SIDE MOUNTED ( INO - INC) SEE 2. ABOVE FOR INSTRUCTIONS. 4. 4TH ADDER POLE FOR B(E) 40 & 50 SNAPS INTO PLACE ON THE RIGHT HAND SIDE OF CONTACTOR AND SECURE WITH SCREW. 4TH POLE CANNOT BE MOUNTED TOGETHER WITH AUX. CONTACT BLOCK. ON A BE 40 & 50 THE STANDARD LEFT HAND SIDE AUX.BLOCK HAS TO BE DELETED AND REPLACED BY AUX.BLOCK(S) MOUNTED ON THE TOP OF THE CONTACTOR. THE STANDARD RIGHT HAND SIDE DC AUX.BLOCK HAS TO BE MOVED OVER TO THE LEFT HAND SIDE OF THE CONTACTOR(SEE WIRING DIAGRAMS). 5. AUXILIARY CONTACT BLOCK 1-POLE TILT DEVICE AND SLIDE IT ON FROM THE CONTACTORS LINE SIDE, WHITE LEVER ARM SHOULD FACE THE LINE SIDE. WHEN IN POSITION THE DEVICE WILL SNAP INTO PLACE. TO DISMOUNT DEVICE LIFT UP WHITE LEVER ARM AND SLIDE IT OFF IN REVERSE FROM MOUNTING. 6. AUXILIARY CONTACT BLOCK 4-POLE SEE 5. ABOVE FOR INSTRUCTIONS. 7. PNEUMATIC TIMER SEE 5. ABOVE FOR INSTRUCTIONS. 8. MECHANICAL LATCH FOR AC / DC RELEASE SEE 5. ABOVE FOR INSTRUCTIONS. 9. OVERLOAD RELAY OPEN TERMINAL 2,4 AND 6 ON THE LINE SIDE OF THE CONTACTOR. INSERT DEVICE STRAIGHT INTO THE CONTACTOR UNTIL THE BOTTOM PART OF THE DEVICE SNAPS INTO PLACE. WHEN DEVICE IS FULLY PUSHED IN, TORQUE TERMINAL SCREWS 2,4 AND 6 TO 40 in - lb.
TORQUE CHART Power Terminals B(E) 40-75 40 in-lb + / - 10% A(E) 95-110 53 in-lb + / - 10% Accessory Terminals

BE40&50
A1

BE40&50 W/CP50
A1

A2

A2

A3

C
35 VAR

A3

C
16 VAR

36

15

AC 1000 2/97

7 in-lb + / - 10%

CONTACTORS:

Selection: 1.4 - 1.7

Accessories: 1.8 - 1.20

Renewal parts: 1.21

Technical data: 1.22 - 1.35

Approximate dimensions: 1.36 - 1.49

Discount schedule AB

1.19

Accessories for across the line contactors Mounting instructions EH145 - 800

EHTK

CAL16-11

EH145...800 DC operated

VH 550, 800 VH145, 260, 300, VH145A, 260A, 300A WH90...800 CAL16-11 (Can be mounted on both sides of the contactor)
1.Terminal kit Mount terminals per the instructions provided in the kits. 2.Auxiliary contact block (1NO-1NC) Mount block onto the side of the contactor with provided hardware, the block screws down on the base of the contactor. A standard contactor comes with one CAL16-11 contact block on the left hand side. 3. Mechanical interlock (EH145-300) The mechanical interlock mounts between the contactors, screwed down in the same holes as used for the contact blocks. Mech.intlk contactors allows two aux.contact blocks on the outside of each contactor. The interlock itself provides one N.C block for each contactor. one additional aux.block CA16-01(NC) or CA16-10(NO) for each contactor can be snapped on top of the interlock. 4.Mechanical latch (AC or DC release) Mount latch on the top of the contactor per the instruction (5309 673-1Y) provided in the latch kit. 5.Overload relay (EH260-800) The T450/900 overload relays mounts on a separate plate attached to contactor base plate. Openings in the current transformer makes it possible for cable or solid busbars to connect to the contactor. 6.Overload relay (EH145-210) The T200(EH145-210) mounts on a separate mounting plate that attaches to the contactor. The relay comes with hardware to connect the contactor and relay terminal bars. 7.Mechanical interlock (EH450-800) The interlock is included in the contactor base plate and provided instructions (5309 674-1Y) shows how to mount the contactors and adjust the interlock.

EH145...800 AC operated

T450DU/SU T900DU/SU

T200DU

T80DU

TORQUE CHART Power Terminals ( T80 / Load only ) 40 IN-LB + / - 10% Accessory Terminals / Coil Terminals 9 IN-LB + / - 10%
AC 1000 2/97

CONTACTORS:

Selection: 1.4 - 1.7

Accessories: 1.8 - 1.20

Renewal parts: 1.21

Technical data: 1.22 - 1.35

Approximate dimensions: 1.36 - 1.49

1.20

Discount schedule AB

Renewal parts for across the line contactors Contact kits, arc shields B, A , EH & EK contactors
Contact kits for B contactors
Contactor Catalog List

3 Pole

B30, B40, B50, B63, B75,

BC30 BE40 BE50 BE63 BE75

KL30 KL40 KL50 KL63 KL75 KLT40 KLT50

$ 60 70 75 90 105 80 100

4 Pole

B/BE 40 B/BE 50

Contact kits for A contactors


Contact kit, KL50 Contactor size Catalog number List price

A95 A110

ZL95 ZL110

$ 150 170

Contact kits for EH & EK contactors


Contactor size Catalog number List price

3 Pole

EH145 EH175 EH210 EH260 EH300 EH450 EH550 EH700 EH800 EK110 EK145, 150 EK175 EK210 EK370 EK550

KZ145 KZ175 KZ210 KZ260 KZ300 KZ370 KZ550 KZ700 KZ800 KZK110 KZK150 KZK175 KZK210 KZK370 KZK550

$ 200 280 350 570 680 855 1140 1425 1710 230 270 375 470 1135 1520

4 Pole
Contact kit, KZ800

Arc shields for EH & EK contactors


Contactor size Catalog number List price

3 Pole

EH145 EH175 EH210 EH260 EH300 EH450 EH550 EH700 EH800 EK110 EK150 EK175 EK210 EK370 EK550

KW145 KW175 KW210 KW260 KW300 KW450 KW550 KW700 KW800 KWK110 KWK150 KWK175 KWK210 KWK370 KWK550

$ 75 85 90 110 120 130 145 190 205 90 100 115 120 175 195

4 Pole

Arc shield, KW260

AC 1000 2/97

CONTACTORS:

Selection: 1.4 - 1.7

Accessories: 1.8 - 1.20

Renewal parts: 1.21

Technical data: 1.22 - 1.35

Approximate dimensions: 1.36 - 1.49

Discount schedule AB

1.21

UL/CSA technical data for across the line contactors B contactors


ABB contactor frame size
NEMA size A.C. rating information NEMA cont. amp rating (thermal current) NEMA maximum H.P ratings (1 phase) 115VAC 230VAC NEMA maximum H.P. ratings (3 phase) 200VAC 230VAC 460/575VAC U.L. general purpose current (40C) U.L. max 3 Ph. switching motor loads, amps U.L. maximum H.P. ratings (1 phase) 115 VAC 230 VAC

B9 00

B12

B16 0

B25 1

B30 1P

B40

B50 2

B63

B75 3

9 1/3 1 1.5 1.5 2 21 9 0.5 1 2 2 5 7.5 15 15

21 11 1 2 3 3 7.5 10

18 1 2 3 3 5 21 17 1.5 3 5 5 10 15 5 10 10 2

27 2 3 7.5 7.5 10 33 28 3 5 7.5 10 20 25 33 33

36 3 5 45 32 3 5 10 10 20 30 35 35 10 20 20 5

55 41 3 7.5 10 15 30 40 65 65

45 3 7.5 10 15 25 65 52 3 7.5 15 20 40 50 65 65 15 30 30 7.5

85 65 5 10 20 25 50 60 85 85

90 25 30 50 105 80 7.5 15 25 30 60 75 85 85 15 30 40 7.5

U.L. maximum H.P. ratings (3 phase) 200 - 208 VAC 220 - 240 VAC 440 - 480 VAC 550 - 600 VAC Lighting-ballast and incand., 600 VAC Resistive heating applications, 600 VAC CSA elevator ratings 220 - 240 VAC, (3 phase) 440 - 480 VAC, (3 phase) 550 - 600 VAC, (3 phase) 230 VAC, (1 phase) Coil operating data A.C. power consumption Inrush 60 Hz, VA Holding 60 Hz, VA Holding 60 Hz, W D.C. power consumption Inrush, cold, W Holding, warm, W A.C. operating time, ms (milliseconds) Closing time, ms Opening time, ms D.C. operating time, ms (milliseconds) Closing time, ms Opening time, ms Auxiliary contacts NEMA Rating, AC AC rated voltage, VAC AC thermal rated current, (Amps) AC maximum volt-ampere making, VA AC maximum volt-ampere breaking, VA NEMA Rating, DC DC rated voltage, VDC DC thermal rated current, Amps DC Maximum make-break, Amps Approximate weight, lbs. Contactor Starter Frequency of operations per hour Maximum (mechanical switching) At full load (electrical switching) Plugging, inching, or jogging Wire range, AWG Number of wires per phase Tightening torque, lb.-in. Maximum short circuit ratings MCP, Amps/kA @ 480 VAC MCCB, Amps/kA @ 480 VAC Fuse, Amps-Type/kA, 600 VAC

80 10 2.4 7 7 9 - 17 5 - 13 50 - 75 15 - 30 A600 600 10 7200 720 P600 600 5 0.2 0.7 1.04 6000 1200 300 18 - 10 2 9

80 10 2.4 9 - 17 5 - 13 A600 600 10 7200 720 P600 600 5 0.2 0.7 1.04 6000 1200 300 18 - 10 2 9

80 10 2.4 7 7 9 - 17 5 - 13 50 - 75 15 - 30 A600 600 10 7200 720 P600 600 5 0.2 0.7 1.04 6000 1200 300 18 - 10 2 12

100 11 3.3 7 7 10 - 20 5 - 15 50 - 75 15 - 30 A600 600 10 7200 720 P600 600 5 0.2 1.01 1.35 3000 1200 300 14 - 10 2 12

100 11 3.3 7 7 10 - 20 5 - 15 50 - 75 15 - 30 A600 600 10 7200 720 P600 600 5 0.2 1.2 1.54 3000 1200 300 12 - 8 2 20

200 20 5.5 200 4 10 - 27 5 - 15 40 - 49 16 - 20 A600 600 10 7200 720 P600 600 5 0.2 2.25 3 3000 1200 300 8-1 1 40

200 20 5.5 200 4 10 - 27 5 - 15 40 - 49 16 - 20 A600 600 10 7200 720 P600 600 5 0.2 2.25 3 3000 1200 300 8-1 1 40

200 20 5.5 200 4 10 - 27 5 - 15 40 - 49 16 - 20 A600 600 10 7200 720 P600 600 5 0.2 2.25 3 3000 1200 300 8-1 1 40

200 20 5.5 200 4 10 - 27 5 - 15 40 - 49 16 - 20 A600 600 10 7200 720 P600 600 5 0.2 2.25 3 3000 1200 300 8-1 1 40

25/18 50/35 35J/50

25/18 50/35 35J/50

25/18 50/35 60J/50

50/18 70/35 100J/50

50/18 100/35 100J/50

100/18 100/35 200J/50

100/18 100/35 200J/50

100/18 100/35 200J/50

100/18 100/35 200J/50

AC 1000 2/97

CONTACTORS:

Selection: 1.4 - 1.7

Accessories: 1.8 - 1.20

Renewal parts: 1.21

Technical data: 1.22 - 1.35

Approximate dimensions: 1.36 - 1.49

1.22

UL/CSA technical data for across the line contactors A, EH contactors


ABB contactor frame size
NEMA Size AC rating information NEMA cont. amp rating (thermal current) NEMA maximum H.P ratings (1 Phase) 115VAC 230VAC NEMA maximum H.P. ratings (3 Phase) 200VAC 230VAC 460/575V U.L. general purpose current (40C) Max. 3 Ph Switching Motor Loads (Amps) U.L. maximum H.P. ratings (1 Phase) 115 VAC 230 VAC U.L. maximum H.P. ratings (3 Phase) 200 - 208 VAC 220 - 240 VAC 440 - 480 VAC 550 - 600 VAC Lighting-Ballast and Incand., 600 VAC Resistive Heating Applications, 600 VAC U.L. definite purpose ratings, 600 VAC RLA current LRA current Make/break data Making capacity 600 VAC, (Amps) Breaking capacity, 240 VAC (Amps) Breaking capacity, 600 VAC (Amps) Coil operating data A.C. power consumption Inrush 60 Hz, VA Holding 60 Hz, VA Holding 60 Hz, W D.C. power consumption Inrush, cold, W Holding, warm, W A.C. operating time, ms (milliseconds) Closing time, ms Opening time, ms D.C. operating time, ms (milliseconds) Closing time, ms Opening time, ms Auxiliary contacts NEMA Rating, AC AC rated voltage, VAC AC thermal rated current, (Amps) AC maximum volt-ampere making, VA AC maximum volt-ampere breaking, VA NEMA Rating, DC DC rated voltage, VDC DC thermal rated current, Amps DC Maximum make-break, Amps Approximate weight, lbs. Contactor Starter Frequency of operations per hour Maximum (mechanical switching) At full load (electrical switching) Plugging, inching, or jogging Terminal wire range, AWG Number of wires per phase Maximum short circuit ratings MCP, Amps/kA @ 480VAC MCCB, Amps/kA @ 480VAC Fuse, Amps-Type/kA, 600VAC 125 80 7.5 20 30 30 60 75 125 125 95 570 140 105 10 25 30 40 75 100 110 660 135 40 50 100 170 130 10 25 40 50 100 125 150 1050 190 156 15 30 50 60 125 150 150 150 175 1150 230 192 40 60 75 150 200 190 190 210 1260 270 75 100 200 300 242 50 75 100 200 250 200 200 270 1800 350 302 100 100 250 250 260 260 325 2350 525 420 125 150 350 400 400 400 520 3120 540 150 200 400 600 480 150 200 400 500 420 420 600 4020 715 602 200 250 500 600 500 500 775 4560 810 300 600 900 810 250 300 600 700 540 540 900 5000

A95

A110

EH145
4

EH175

EH210

EH260
5

EH300

EH450

EH550
6

EH700

EH800
7

900 900 900

900 1000 1000

1200 1000 1000

1700 1700 1700

1700 1700 1700

1700 2500 2500

1700 2500 2500

5200 5400 5400

5200 5400 5400

7000 7600 6900

7000 7600 6900

500 28 9 310 3 20 - 30 7 - 15 20 - 30 10 - 20

500 28 9 310 3 20 - 30 7 - 15 20 - 30 10 - 20

490 35 11 310 22 20 - 30 7 - 15 20 - 30 10 - 20

900 55 22 500 2.5 20 - 30 7 - 15 20 - 30 10 - 20

900 55 25 500 2.5 20 - 30 7 - 15 20 - 30 10 - 20

1200 70 25 630 2.5 20 - 30 7 - 15 20 - 30 10 - 20

1200 70 25 630 2.5 20 - 30 7 - 15 20 - 30 10 - 20

2900 105 44 800 20 30 - 50 10 - 20 60 - 80 10 - 20

2900 105 44 800 20 30 - 50 10 - 20 60 - 80 10 - 20

4000 140 60 1100 20 30 - 50 10 - 20 60 - 80 10 - 20

4000 140 60 1100 20 30 - 50 10 - 20 60 - 80 10 - 20

A600 600 10 7200 720 P600 600 5 0.2

A600 600 10 7200 720 P600 600 5 0.2

A600 600 10 7200 720 P600 600 5 0.2

A600 600 10 7200 720 P600 600 5 0.2

A600 600 10 7200 720 P600 600 5 0.2

A600 600 10 7200 720 P600 600 5 0.2

A600 600 10 7200 720 P600 600 5 0.2

A600 600 10 7200 720 P600 600 5 0.2

A600 600 10 7200 720 P600 600 5 0.2

A600 600 10 7200 720 P600 600 5 0.2

A600 600 10 7200 720 P600 600 5 0.2

3.5 6 3600 600 300 6 - 2/0 1

5 7 3600 600 300 6 - 2/0 1

5 7 3600 600 300 8 - 3/0 1

9.2 11

9.2 11

13 24

13 24

27.3 45

27.3 47

37.7 56

37.7 60 3600 300 120 2-600MCM 3

3600 3600 3600 3600 3600 3600 3600 600 600 600 600 300 300 300 120 120 120 120 120 120 120 8-250MCM 6-250MCM 4-500MCM 4-500MCM 6-300MCM 4-500MCM 4-500MCM 1 1 1 2 2 2 2

150/65 200J/65

250/65 200J/65

225/35 225/35 400J/50

225/35 400/42 400J/65

225/35 400/42 400J/65

400/42 400/42 700L/65

400/42 400/42 700L/65

1200L/100 1200L/100

1200L/100 1200L/100 1200L/100 1200L/100

1200L/100 1200L/100

AC 1000 2/97

CONTACTORS:

Selection: 1.4 - 1.7

Accessories: 1.8 - 1.20

Renewal parts: 1.21

Technical data: 1.22 - 1.35

Approximate dimensions: 1.36 - 1.49

1.23

IEC technical data for across the line contactors B, BC, BE, & A contactors

a.c. operated d.c. operated Number of main poles

Type Type 3 or 4 3 or 4

B9 BC 9 3 or 4

B 12

B 16

B 25 BC 25 3 + 4thp

B 30 BC 30 3 + 4 thp

B 40

B 50

B 63 BE 63 3

B 75 BE 75 3

A 95 AE95 3

A110 AE110 3

BC 16 3 or 4 3

BE 40 BE 50 3 3

Main poles : Characteristics and utilization data


Rated insulation voltage Vi acc. to IEC 947-4- 1 acc. to VDE 0110 (Gr. C), NF C 20-040 (Gr. C) acc. to UL/CSA Impuls withstand voltage Vimp. acc. to IEC 947-4- 1 Rated operating voltage Ve max. V Rated thermal current, conventional Ith acc. to IEC 947-4- 1, open type contactors 40 C A with cable cross-section mm 2 Note : for EH, EK types with prepared cables. Utilization category AC- 1 Rated operating current I e /AC- 1 max. at ambient temperature measured up to the contactor : 690 26 4 690 28 4 690 28 4 V V V 690 750 600 Unless otherwise stated : 6 kV 690 45 6 690 65 10 1000 100 35 1000 125 50 1000 125 50 1000 125 50 1000 750 600 8kV 1000 145 50 1000 160 70

40 C 55 C 70 C

with cross-section Utilization category AC- 3 3-phase, 50/60 Hz, Ambient temperature 55C Rated operating current I e /AC-3 max. at 220-230 V 240 V 380-400 V 415 V Motors M 440 V ~ 500 V 660-690 V 1000 V Max. power rating at 220-230 V 240 V 380-400 V 415 V 440 V 500 V 660-690 V 1000 V Frequency limits Mechanical endurance in million of operations Types : A & B BC/BE A & EH/EK With max. mechanical switching frequency ops./ h Max. electrical switching on AC- 1 ops./ h frequency on AC-3 ops./ h on AC-2, AC-4 ops./ h Rated making capacity AC- 3 acc. to IEC 947-4- 1 Rated breaking capacity AC- 3 acc. to IEC 947-4-1 Max. making capacity (at cos. = 0.35) Max. breaking capacity at 415 V (at cos. = 0.35) at 690 V Short-circuit protection Without thermal O/ L relay, Non-motor circuit Ue 500 V a.c., max. fuse gG (gl) Short time current 1s at 40 C ambient temperature 10 s in free air, from cold condition 30 s 1 min. 15 min. Heat dissipation per pole Ie /AC-1 Ie /AC-3 A A A

A A A mm 2

22 20 17 2.5

24 22 19 2.5

28 25 23 4

45 40 32 6

55 45 36 6

70 60 50 35

100 85 70 50

115 95 80 50

125 105 85 50

145 135 115 50

160 145 130 70

A A A A A A A A kW kW kW kW kW kW kW kW

9 9 9 9 9 7 6 2.2 2.2 4 4 4 4 4 10 10 6000 600 1200 300

12 12 12 12 12 10 8 3 3 5.5 5.5 5.5 5.5 5.5

16 16 16 16 16 13 8 4 4 7.5 7.5 7.5 7.5 5.5

25 25 25 25 20 17 13 6.5 7.5 11 11 11 11 11 10 10 3000 600 1200 300

33 32 30 30 27 23 18 9 9 15 15 15 15 15

40 37 37 37 37 33 25 17 11 11 18.5 18.5 22 22 22 22

53 50 50 50 45 45 35 23 15 15 22 25 25 30 30 30

65 65 65 65 65 55 43 25 18.5 18.5 30 37 37 37 37 33 10 10 3000 600 600 300

75 75 75 72 70 65 46 28 22 22 37 40 40 45 40 37 10 10 10 3000 600 600 300

96 96 96 96 90 80 65 30 25 25 45 45 45 55 55 40 10 3000 600 600 300

110 110 110 110 110 100 82 30 30 30 55 55 55 59 75 40 10 3000 600 600 300

10 10 10 6000 6000 600 600 1200 1200 300 300

Hz 25 400 10 10 10 10 10 10 3000 3000 3000 600 600 600 1200 600 600 300 300 300 10 x I e /AC- 3 8 x Ie /AC-3 700 380 290 800 700 350 1000 1000 490

300 200 120

300 200 120

300 200 120

390 315 210

1000 1000 490

1100 1000 490

1450 1160 1000

1450 1160 1000

A A A A A A W W

25 200 90 50 40 22 0.55 0.10

25 280 130 70 50 24 0.85 0.25

32/35 280 130 70 50 28 1.5 0.4

50 350 200 110 90 45 2.4 0.6

63 400 250 150 120 55 2.2 0.6

80 600 400 225 150 70 3 0.8

100 1000 650 370 250 100 5.5 1.2

125 1000 650 370 250 115 6.5 1.5

160 1000 650 370 250 125 7 2

160 1200 725 440 350 160 6.5 2.7

200 1450 725 440 350 175


AC 1000 2/97

7.5 3.5

CONTACTORS:

Selection: 1.4 - 1.7

Accessories: 1.8 - 1.20

Renewal parts: 1.21

Technical data: 1.22 - 1.35

Approximate dimensions: 1.36 - 1.49

1.24

IEC technical data for across the line contactors EH & EK contactors

Type Type Main poles

EK 110 EH 145 EK 150 EH 175 EH 210 EK 175 EK 210 EH 260 EH 300 EH 450 EK 370 EH 550 EK 550 EH 700 EH 800 EK 110 EH 145 EK 150 EH 175 EH 210 EK 175 EK 210 EH 260 EH 300 EH 450 EK 370 EH 550 EK 550 EH 700 EH 800 4 3 4 3 3 4 4 3 3 3 4 3 4 3 3

Main poles : Characteristics and utilization data


VI V V V Vimp Ve max. I th 40 C cable cross section I e / AC-1 40 C A 55 C A 70 C A cross section mm 2 I e / AC-3 55C 220-230 V A 240 V A 380-400 V A 415 V A 440 V A 500 V A 660-690 V A 1000 V A 220-230 V kW 240 V kW 380-400 V kW 415 V kW 440 V kW 500 V kW 660-690 V kW 1000 V kW Freq. limits A EH/ EK ops./h ops./h ops./h ops./h Hz25 400 10 10 3600 600 600 300 160 145 130 70 230 200 160 120 250 230 200 150 260 230 170 150 300 270 215 185 350 310 250 240 400 340 290 300 445 375 325 300 550 470 400 2 x 185 800 650 575 2 x 240 1000 1000 800 800 720 720 2 x 300 2 x 300 6kVI V A mm 2 1000 160 70 1000 230 120 1000 250 150 1000 260 150 1000 300 185 1000 1000 600 Unless otherwise stated : 8 kV 1000 1000 1000 350 240 400 300 445 300 1000 550 2 x 185 1000 800 2 x 240 1000 1000

1000 1000 2 x 300 2 x 300

110 110 110 110 100 100 82 30 30 55 55 55 55 59 75 40

150 145 145 145 145 145 120 80 45 45 75 75 75 90 110 110

185 185 185 185 185 170 170 94 55 55 90 90 90 110 132 132

210 210 210 210 210 210 210 113 59 59 110 110 110 132 160 160

260 260 260 260 240 240 220 125 80 80 140 140 140 180 200 180

305 305 305 280 280 280 280 140 90 90 160 160 160 200 250 200

400 400 400 400 370 370 370 155 110 110 200 220 220 250 355 220

550 550 550 550 550 550 550 175 160 160 280 315 315 400 500 250

700 700 700 700 700 700 700 220 220 220 370 400 400 480 600 315

750 750 750 720 720 720 720 220 220 220 400 425 450 520 650 315

10 3600 600 600 120 10 x I e /AC-3 8 x Ie /AC- 3 2000 1800 1500 2300 2000 1700 3300 2600 2500 5000 5000 5000

5 3600 300 300 120

415 V 690 V

A A A

1700 1400 1100

1800 1500 1200

5500 5400 5400

7200 7200 6700

7500 7500 6900

A 1s 10 s 30 s 1 min 15 min
AC 1000 2/97

250 1700 900 600 450 210 10 3

250 1800 1200 700 550 250 13 5

355 2000 1600 1000 800 320 14 6

355 2300 1600 1000 800 320 18 9


Renewal parts: 1.21

500 3050 2100 1500 1100 500 35 15

630 5500 5300 3700 3000 1000 40 15

800 5500 5300 3700 3000 1000 60 25

1000 7000 6400 4500 3500 1300 60 25

1000 7000 6400 4500 3500 1300 60 28

A A A A A W W

CONTACTORS:

Selection: 1.4 - 1.7

Accessories: 1.8 - 1.20

Technical data: 1.22 - 1.35

Approximate dimensions: 1.36 - 1.49

1.25

IEC technical data for across the line contactors B, BC, BE contactors

a.c. operated d.c. operated Number of main poles Standards

Type Type

B9 BC 9 3 or 4

B 12 3 or 4

B 16 BC 16 3 or 4

B 25 3 or 4

B 30 3

B 40 BE 40

B 50 BE 50

B 63 BE 63 3

B 75 BE 75 3

BC 25 BC 30

3+4th p 3+4th p

Equipment complies with the major international, European and national standards IEC 158-1, VDE 0660, NF C 63-110, BS 5424, IEC 947-4-1

Permissible ambient temperature for operation in free air : contactor without relay contactor with relay contactor without relay for storage Climatic resistance acc. to DIN 50017 acc. to UTE C 63-100

C C C C

at 0.85 to 1.1 Vc at 0.85 to 1.1 Vc at Vc

: : : :

25 .. +55 25 .. +50 40 .. +70 40 .. +70

condensated water alternating climate KFW, 30 cycles specification II BC types : see page 33 B and BE types (see sketch page 33): Positions 1 to 5 at ambient temp. 55 C : control voltage = 0.85 to 1.1 Vc Positions 1 to 5 at ambient temp. 70 C : control voltage = Vc Position 6 at ambient temp. 55 C : control voltage = 0.95 to 1.1 Vc Position 6 at ambient temp. 70 C
C1

Mounting positions :

Shock resistance in standard mounting position

ABB

A B

B1

B2

1/2 sinusoidal shock, 10 ms : no change in contact position Contactors in switched-on or switched-off positions Shock directions : C1, C2, A : 20 g B1 : 5 g B2 : 15 g

C2

Mounting

on 35mm DIN rail

acc. to IEC 715 and EN 50 022 35 x 7.5 mm 2xM4 Cable clamps with pozidrive +,, screw heads M 3.5, poz.1 M 4, poz. 2 M 5

acc. to IEC 715 35 x 15 EN 50 022 75 x 25 EN 50 023 2xM6 Connector (13 x 10 mm) With M8 screw slotted srew head

by screws (not supplied) Connection terminals (delivered in open position) Main poles

All the terminals provide protection against unintentional direct touch of live parts acc. to VDE 0106

Coil terminals Built-in aux. terminals Connecting capacity Main conductors (main poles) Rigid solid ( 4 mm2) or rigid stranded ( 6 mm2) Rigid stranded : with cable clamp connector with single cable clamp connector with double cable clamp connector Flexible without cable end With bars or lugs : max. width hole 1 x mm2 2 x mm2 (Cu cables) (AI/ Cu cables) (AI/ Cu cables) 1 x mm2 2 x mm2 mm mm > 1 x mm2 2 x mm2 1 x mm2 2 x mm2

M 3.5 cable clamps with pozidrive 1 +, , screw heads


All the terminals provide protection against unintentional direct touch of live parts acc. to VDE 0106

As main poles
min. max. 14 14

poz. 2

min. max. min.-max. 1.5 6 1.5 6 2.5..10 2.5..10

min. max 6 50 6 25

1 2.5 0.75 2.5 8 3.7 Aux. and coil 14 14 1 2.5 0.75 2.5

4 4 10 4 Aux. Coil 1..4 1..4 1..4 1..4 0.75..4 1..2.5 0.75..4 0.75..2.5

6 6 13 5

6 35 6 16

Auxiliary leads (built-in auxiliary poles + coil terminals) Rigid solid Flexible without cable end Protection degree acc. to IEC 529, IEC 144, DIN 40 050, NF C 20-010

Coil 14 14 1 2.5 0.75 2.5

IP 00 for main terminals IP 20 for coil terminals.


AC 1000 2/97

CONTACTORS:

Selection: 1.4 - 1.7

Accessories: 1.8 - 1.20

Renewal parts: 1.21

Technical data: 1.22 - 1.35

Approximate dimensions: 1.36 - 1.49

1.26

IEC technical data for across the line contactors EH, EK contactors

Type Type Poles

A 95 A 95 3

A110

EH 110 EK 110

EH 145 EH 145 3

EK 150 EK 150 4

EH 175 EH 175 3

EH 210 EH 210 3

EK 175 EK 175 4

EK 210 EK 210 4

EH 260 EH 260 3

EH 300 EH 300 3

EK 370 EK 370 4

EH 450 EH 450 3

EH 550 EH 550 3

EK 550 EK 550 4

EH 700 EH 700 3

EH 800 EH 800 3

A 110 EH 110 EK 110 3 3 4

Equipment complies with the major international, European and national standards IEC 158-1, VDE 0660, NF C 63-110, BS 5 424, IEC 947-4-1

C C C

at 0.85 to 1.1 Uc at 0.85 to 1.1 Uc

: : :

40 .. + 70 25 .. + 55 50 .. + 70

Condensated water alternating climate KFW, 30 cycles Specification I Position 1 : 30 from vertical position Positions 3, 4 and 5 : acceptable Position 6 : acceptable but coil supply within 0.90 1.1 V c

1/2 sinusoidal shock 15 ms : no change in contact position Contactors in switched-on or switched-off positions Shock directions : C1, C2, A : 10 g B1 : 10 g B2 : 10 g

2xM 5 M8 M6

4xM 6 2xM 5

4xM 6 Flat type with screws, nuts and washers M 10

4xM 6

M 3.5 screw, cable clamp with pozidrive +, , screw heads All the terminals provide protection against unintentional direct touch of live parts acc. to VDE 0106

1 x mm2 1 x mm2 2 x mm2

minmax. 6 70

min max. 25 120 10 70

min max. 25 185 35 120

minmax. 70...300 70...300

minmax. 70 300 70 ... 300 35 ... 185

minmax. 95...300 95...300

mm mm Coil 1 x mm 2 2 x mm 2 1 x mm 2 2 x mm 2

30 6

30 10

33 10 0.5 2.5 0.5 2.5 0.5 2.5 0.5 2.5

50 10

55 10

65 10

75 10 x 2

IP 00 for main poles IP 20 for auxiliary terminals


AC 1000 2/97

For larger coil voltage range: please consult us. Screws and damping elements are included. Cable clamps M8 socket head screw.

CONTACTORS:

Selection: 1.4 - 1.7

Accessories: 1.8 - 1.20

Renewal parts: 1.21

Technical data: 1.22 - 1.35

Approximate dimensions: 1.36 - 1.49

1.27

IEC technical data for across the line contactors B, BC, BE contactors
Magnet system
a.c. operated Type B9 d.c. operated Type BC9 Number of main poles Coil operating limits : 0.85 1.10 X Vc Drop-out voltage types B, EH, EK (a.c.) BC, BE, EH, EK (d.c.) Coil consumption (average value) - 50 Hz pull-in VA for a.c. operated contactors - 60 Hz pull-in VA B, A, EH, EK - 50 Hz holding VA/W - 60 Hz holding VA/W for d.c. operated contactors - pull-in, cold W BC, BE, AE, EH, EK - holding, warm W Rated operating voltage Vc for a.c. operated contactors at 50 Hz V B, A, EH, EK at 60 Hz V for d.c. operated contactors BC, BE, EH, EK V Operating times From coil energization to for a.c. oper. contactors - closing of the N.O contact ms B, A, EH, EK - opening of the N.C contact ms From coil de-energization to - opening of the N.O contact ms - closing of the N.C contact ms Operating times From coil energization to for d.c. oper. contactors - closing of the N.O contact ms BC, BE, AE, EH, EK, - opening of the N.C contact ms From coil de-energization to - opening of the N.O contact ms - closing of the N.C contact ms B12 B16 BC16 3 or 4 B18 BC18 B25 B30 B40 B50 B63 B75 BC25 BC30 BE40 BE50 BE63 BE75 3 3 or 4 3 3+ 4th p 3+4 th p 3 55 C approx. 40 60 % of Vc approx. 15 40 % of Vc 85 97 9/ 3 10/3 7 7 24 600 24 550 12 240 10 20 7 17 5 15 7 17 175 195 17/ 5 19/5.7 200 4 B26

65 75 9/ 2.2 9/ 2.2 7 7

12 240 9 17 6 14 5 13 7 15 50 75 45 70 15 30 17 32

12 240 10 27 7 23 5 15 8 18 13 30 10 27 5 15 8 18

Built-in auxiliary contacts (tech. data for add-on aux. contacts


a.c. operated Type B 9 B 12 B 16 B 25 d.c. operated Type BC 9 BC 16 BC 25 Rated insulation voltage Vi acc. to IEC 947-4- 1 V 660/690 acc. to VDE 0110 (Gr C), NF C 20- 040 (Gr C) V 750 acc. to UL/CSA V 600 Impuls withstand voltage Vimp. acc. to IEC 947-4-1 unless otherwise stated : 6 kV Rated operational voltage Ve max. V 690 Conventional free air thermal current Ith A 10 Rated operational current 240 V 50/60 Hz A 4 Ie AC-15 acc. to IEC 947-5-1 415 V 50/60 Hz A 3 500 V 50/60 Hz A 2 660/690 V 50/60 Hz A 2 Ie DC-13 acc. to IEC 947-5- 1 48 V d.c. A/W 4/192 60 V d.c. A/W 2.5/150 110 V d.c. A/W 0.7/77 220 V d.c. A/W 0.3/66 Frequency limits Hz 25 to 400 Max. switching frequency ops./h 3000 Rated making capacity 11 x Ie /AC- 15 or AC 11 Rated breaking capacity 11 x Ie /AC- 15 or AC 11 Fuse protection gG (gI) A 10 Short time current for 1.0 s 50 A for 0.1 s 100 A Insulation resistance at 500 V d.c. after endurance test : 5 M Switching capacity, min. values 24 V/ 5mA Failure rate < 1 per 1 million ops., for terminals voltage drop 500 mV, in clean environment. Non overlapp. time of the cont. betw. N.O. and N.C. ms 2 Heat dissipation per pole at I 10 A W 0.4 CONTACTORS: Selection: 1.4 - 1.7th Accessories: 1.8 - 1.20 Renewal parts: 1.21 Technical data: 1.22 - 1.35
By using surge suppressors, the increase factor of opening time can be rated at 1.1 to 1.5 with varistor types and 4 to 8 with diode types. Ratings also valid for AC 11 respectively DC 11 acc. to IEC 337-1

AC 1000 2/97

Approximate dimensions: 1.36 - 1.49

1.28

IEC technical data for across the line contactors A, EH, EK contactors
Magnet system
Type Type A95 A95 3 A110 EH110 A110 EH110 3 3 EK110 EK110 4 EH145 EH145 3 EK150 EK150 4 EH175 EH175 3 EH210 EK175 EK210 EH260 EH210 EK175 EK210 EH260 3 4 4 3 70 C approx. 45 65 % approx. 15 50 % 1100 1200 52/18 65/22
1) 1) 1) 1) 1)

EH300 EK370 EH300 EK370 3 4

EH450 EH550 EK550 EH450 EH550 EK550 3 3 4

EH700 EH700 3

EH800 EH800 3

(a.c.) (d.c.) VA VA VA/W VA/W W W V V V ms ms ms ms ms ms ms ms


1) 40400 Hz coils with built-in rectifier.

450 500 28/8 28/9 300 3

450 500 28/8 28/ 9 300 3

430 800 490 900 30/10 44/15 35/11 52/18


1)

430 490 30/10 35/11


1)

800 900 44/15 52/18


1)

3500 4000 125/50 140/60 1100 20

2600 2900 90/ 36 105/ 44 800 20

2600 2900 90/36 105/44 800 20 48 500 110 600 24 220 30 60 25 55 10 20 13 23

3500 4000 125/50 140/60 1100 20

330 22

450 3.6

330 22

500 2.5

630 2.5 24 500 48 600

1
24 500 24 600 12 220 20 40 15 35 7 15 10 18 20 30 17 27 30 40 20 30 27 37 17 27 30 40 27 37 10 20 13 23

60 80 55 75

Electrical endurance
AC- 15 acc. to IEC 947-5- 1 (and AC 11 acc. to IEC 337-1) switched on current : 10 x Ie at cos = 0.7 and Ve switched off current : I e at cos = 0.4 and Ve The following curves show the electrical endurances of add-on and built-in auxiliary contacts, depending on the breaking current Ic. The curves are suitable for resistive and inductive loads up to 690 V, 40 60 Hz under the condition the contactor is switched randomly in relation to the phase angle of the network.

Mounting positions

Pos. 6 Pos. 2
30

30

Pos. 4
30 20 10 5

ABB

Pos. 3

Pos. 1

Pos. 1 30 Pos. 5

CAL 16

Million op.

3 2 1 0.5 0.3 0.2 0.1

CA7, CAL 7 ... and built-in aux. contacts

NOTE: BC contactors cannot be mounted in position 5.

AC 1000 2/97

0.02

0.03

0.1

0.2

0.3

0.5

4 5 6

10

Breaking current (A)

CONTACTORS:

Selection: 1.4 - 1.7

Accessories: 1.8 - 1.20

Renewal parts: 1.21

Technical data: 1.22 - 1.35

Approximate dimensions: 1.36 - 1.49

1.29

IEC technical data for across the line contactors Utilization categories and electrical endurances
General information
The following curves show the electrical endurances (contact life) for standard contactors depending-on the switched-off current Ic. These curves are suitable respectively for resistive and inductive loads based on the making and breaking conditions of current as defined in utilization categories AC- 1, AC- 3, AC- 4, specified in the following standards : IEC 947-4-1, IEC 158-1, VDE 0660 and NFC-63110 under the condition the contactor is switched randomly in relation to the phase angle of the network. The table below indicates for the various utilization categories, the relationship between the switched-off current Ic and the rated operating current Ie ( Ie being the current value related respectively to a resistive load or to a motor : full load current In). Utilization category AC- 1 1 x Ie AC- 3 1 x Ie AC- 4 6 x Ie Switched-off curent I c Ic = m x Ie

Electrical endurance curves


For AC-1, AC- 3, AC- 4 the corresponding curves on the following pages quote the electrical endurance depending on the switched-off current Ic. These curves are drawn for 400 V 3-phase circuits. They remain valid up to 690 V, 40 60 Hz providing it is established that, for a quoted operating voltage Ve , the rated operating current Ie does not exceed, "Ie max" on AC1 duty and "Ie max" on AC-3 (AC-4) duty acc. to utilization table page 1.24 or 1.25. The electrical endurance is expressed in million of operations.

Electrical endurance curves for utilization category AC-1. Ambient temperature 55C
Control of non-inductive or slightly inductive loads (P.F. 0.95). Switched-off current I c on AC- 1 equals rated operating current Ie of the load.
A 110 / EK 110

EH 175 / EK 150 EH 210 / EK 175, EH 260 EK 210

EH 450 / EK 370 EH 550 / EK 550

EH 145

EH 300

EH 700

B 25

10

5 3

0.5

Million of operations

EH 800
EK 210

B 16

B 12

B 63 B 75

B 30

B 40

B 50

0.3 0.2

0.1
0 0 0 50 20 30 50 10 20 10 5 30 2 3 10
80 0

A 95

B9

95 10 5

14

Example : Ve = 400 V, Ie = 35 A - AC- 1 Ie = Ic = 35 A Required : N = 2 million of operations. => on AC-1 curves, intersection point " G" : Ie = 35 ; N = 2 leads to select B 50.
CONTACTORS:
Selection: 1.4 - 1.7

85

18

0 23 0 27 0 31 0 34 0 37 5 47 0 65 0

20

22

25

40

45

60

00

AC 1000 2/97

Rated current (A)

Accessories: 1.8 - 1.20

Renewal parts: 1.21

Technical data: 1.22 - 1.35

Approximate dimensions: 1.36 - 1.49

1.30

IEC technical data for across the line contactors Utilization categories and electrical endurances

Details for utilization of the curves


Anticipated electrical endurance and contactor selection for an AC1, AC-3 or AC-4 duty. G Determine load characteristics i.e. : Ve : operating voltage, Ie (1) : operating current, AC- : utilization category, Ic : switched-off current. G Define the required number of operations N. G On the diagram which corresponds to the utilization category, select the contactor of which the curve is immediately above the (I c, N) intersection point.

Anticipated electrical endurance and contactor selection for motor control mixed duty, breaking during running (Ic = Ie) and occasional breaking whereas the "motor is starting" (Ic = m x Ie with m 6). G Determine motor characteristics i.e. : Ve : operating voltage Ie (1) : switched-off current "motor running" = operating current. Ic = m x Ie : switched-off current whereas "motor is starting". K = percentage of operations whereas "motor is starting". G Define the required number of operations N. G On page 1.24 or 1.25, select the first acceptable contactor (lowest rating) according to Ve and Ie (AC-3). G On the AC-4 diagram, retain for the selected contactor : the number of operations A for I c = I e the number of operations B for I c = m x Ie. G Calculate the anticipated total number of operations N' (N' is always <A) : A N' = 1 + 0,01 K (A/B- 1) Should be N' considered as being too low, carry out a second calculation using the nearest upper contactor rating.
(1) Relationship kW to Ie values for motors are shown in the folding front cover of this catalogue.

Electrical endurance curves for utilization category AC-3


Control of squirrel-cage motors : starting, switching-off motors during running. Switched-off current I c on AC- 3 equals rated operating current I e (motor full load current : F.L.C.).

A 110 EH 145

EH 175 EH 210 EH 260 EH 300

EH 700

EH 450

B 25

10

5 3 2

Million of operations

0.5

0.3 0.2

0.1
0 14 5 18 2 5 00 21 0 26 30 0 0 30 5 40 5 0 00 55 0 70 0 0 100 0 75

20

30

50

10

30

37

50

25

63

75

96

10

Example : Motor rating P = 55 kW Ve = 415 V I e acc. to folding front cover 0/0 = 96 A. AC- 3 : Ic = Ie = 96 A. Required : N = 4 million of operations. => on AC-3 curves, intersection G" : CONTACTORS: Selection: 1.4 - 1.7 point " Accessories: 1.8 - 1.20 I e = 96 ; N = 4, leads to select EH 260.

AC 1000 2/97

12

16

Rated current Ic = switched-off current Ie (A)

12

EH 550

EH 800

B 16

B 12

B 63 B 75

B 30

B 40 B 50

A 95

B9

Renewal parts: 1.21

Technical data: 1.22 - 1.35

Approximate dimensions: 1.36 - 1.49

1.31

IEC technical data for across the line contactors Utilization categories and electrical endurances
Electrical endurance curves for utilization category AC-4. Ve 440 V
Control of squirrel cage motors : starting, plugging, inching, switching-off stalled motors or during starting. Switched-off current I c on AC- 4 equals 6 x Ie when I e is the rated operating current (motor full load current : F.L.C.).

A 95 A 110 EH 145 EH 175 EH 210 EH 260 EH 300

10

5 3 2

1
1

0.5 0.3 0.2

0.1

Million of operations

0.05 0.03 0.02

0.01

0.005
2 30 20 0 0 39 0 3 00 45 0 48 0 5 00 70 0 75 0 88 0 10 12 10 00 5 9 0 0 15 00 20 22 00 00 28 00 30 00 38 00 40 0

B 25

EH 550 EH 700 EH 800

EH 450

B 12 B 16

B 30 B 40 B 50 B 63 B 75

B9

10

20

30

54

72 96

15

18

10 0

50

Switched - off current Ic (A) Example : Motor rating P = 45 kW Ve = 400 V I e acc. to folding front cover 0 /0 = 85 A. AC- 4 : Ic = 6 I e = 510 A. Required : N = 0.2 Million of operations. => on AC-4 curves, intersection point "G" : Ic = 510; N = 0.2, leads to select EH 300.

22

50 0 00

440 < Ve 690 V


The table below quotes, for utilization category AC- 4, the I e max. operating current corresponding to the different sizes of contactors for electrical endurances of 100.000 and 30.000 operations. Types
Operating current 100.000 ops - Ie max.A Operating current 30.000 ops - I e max. A

B9 4 5

B12 B16 B25 B30 5.5 7.5 7 9 10 12 14 16

B40 17.5 25

B50 B63 20 33 25 38

B75 28 40

A95 32 54

A110 47 78

EH145 EH175 55 88 66 105

EH210 EH260 EH300 EH450 75 115 90 145 95 155 117 195

EH550 140 235

EH700 185 300

EH800 185
AC 1000 2/97

300

CONTACTORS:

Selection: 1.4 - 1.7

Accessories: 1.8 - 1.20

Renewal parts: 1.21

Technical data: 1.22 - 1.35

Approximate dimensions: 1.36 - 1.49

1.32

IEC technical data for across the line contactors Paralleling of poles Intermittent duty and temporary duty
Purpose : increasing the permissible a.c. resistive load controlled. Paralleling of poles for increasing of a d.c. resistive load is not acceptable. In the table below are quoted the Ie AC-1 max. uprating factors applicable, depending on the number of poles in parallel and for the max. permissible switching frequency : 600 ops./h. for B9 EH300 and EK110 EK210 300 ops./h. for EH450 EH800 and EK370 EK550
L1 L2 L3

L1 L2 L3

L1 L2 L3

1
N

2 poles in // Contactor types a.c. operated d.c. operated B9, B12, B16 B25 BC9, BC16 BC25

3 poles in //

4 poles in //

Uprating factor applicable to rated current I e /AC-1 max. to obtain I e /AC-1 current permissible with "n" poles in parallel. 1.6 1.6 1.6 2.2 2.2 2.2 2.6 2.6

B30 BC30, BE40 B40, B50, B63, B75 BE50, BE63, BE75 B40-40, B50-40 EH145 EH175, EH210 EH260, EH300 EH450, EH550 EH700, EH800 EK110, EK150 EK175, EK210 EK370, EK550 BE40-40, BE50-40

}
}

a.c. and d.c. operated

1.6

2.2

a.c. and d.c. operated

1.6

2.2

2.8

Utilization of contactors B9 to EH800, EK110 to EK550 for intermittent duty and temporary duty In the table below are quoted the Ie /AC-1 max. uprating factors depending on the switching frequency and the current flow duration per cycle, for obtaining
the permissible operating current Ie / AC-1 on intermittent duty.
Operations per hour 120 60 20 6 2 1

Current flow duration per cycle, in secs. 5 10 20 30 40 60

Uprating factor applicable to I e / AC-1 max. to obtain the rated current I e / AC-1 permissible on intermittent duty. 2.8 3.4 4 4.7 5 2.2 2.6 3 3.4 3.7 1.6 2 2.4 2.6 2.7 1.7 2.1 2.2 2.3 1.5 1.9 2.0 2.1 1.7 1.8 1.8

5.2 3.8 2.8 2.4 2.2 1.9

AC 1000 2/97

Example : Contactor B 9 (intermittent duty, resistive load) Rated current Ie / AC-1 max. at 55 C (page 2/ 24) Switching frequency Current flow duration per cycle Factor applicable on current I e / AC-1 max. Permissible current : 2.7 x 20 =

20 A 2 ops./h 20 s 2.7 54 A

CONTACTORS:

Selection: 1.4 - 1.7

Accessories: 1.8 - 1.20

Renewal parts: 1.21

Technical data: 1.22 - 1.35

Approximate dimensions: 1.36 - 1.49

1.33

IEC technical data for across the line contactors DC circuit switching
General :
The arc switching on d.c. is more difficult than on a.c. selecting a contactor it is essential to determine the current and voltage to be switched on and off and the time constant L/R of the controlled load. G For information, typical time constant values are quoted hereafter : non inductive loads such as : resistance furnaces L/R 1 ms inductive loads such as : shunt motors L/R 2 ms series motors L/R 7.5 ms G The addition of a resistor in parallel with the inductive winding helps in the elimination of the arcs. G In case of earthed source, all the poles required for breaking must be connected in series between the load and the source polarity not linked to earth (or chassis). This is the solution we recommend for all connection modes.
G G For

a.c. operated contactors d.c. operated contactors Utilization category DC-1 L/R 1 ms
+

Type Type

B9 BC 9

B 12

B 16 B 25 B 30 B 40 BC 16 BC 25 BC 30 BE 40

B 50 B 63 BE 50 BE 63

GB 75 B 75 BE 75 GBE 75

1
+

72 V 110 V 72 V 110 V 220 V

A A A A A A A A A

9 8 9 9 9 9 9 9 5

11 10 12 12 10 12 12 12 5

12 11 16 14 12 16 16 14 5

20 12 25 20 13 25 25 20 5

25 14 30 25 15 30 30 25 5

35 15 40 35 15 40 40 35 5

50 16 50 50 16 50 50 50 5

63 16 63 63 16 63 63 63 5

75 16 75 75 16 75 75 75 5

100 100 100 100

72 V 110 V 220 V 440 V

Utilization category DC - 3 L/R 2 ms


+

72 V 110 V 72 V 110 V 220 V

A A A A A A A A A

8 2 9 9 6 9 9 9

10 2 12 12 8 12 12 12

11 2 16 14 10 16 16 14

15 2 25 18 10 25 25 20

20 2 30 23 10 30 30 25

35 8 40 32 10 40 40 35

50 10 50 50 12 50 50 50

63 10 63 63 12 63 63 63

75 10 75 75 12 75 75 75

85 85 85 85

72 V 110 V 220 V 440 V

Utilization category DC- 5 L/R 7.5 ms


+

72 V

10

15

35

50

63

75

72 V 110 V 220 V

A A A A A A A

9 8 2 9 9 9

12 10 2 12 12 11

14 12 2 16 16 12

20 14 2 25 20 15

25 20 5 30 25 20

35 30 7 35 35 30

50 50 8 50 50 50

63 63 9 63 63 63

75 75 10 75 75 75

85 85 85 50

72 V 110 V 220 V 440 V

AC 1000 2/97

CONTACTORS:

Selection: 1.4 - 1.7

Accessories: 1.8 - 1.20

Renewal parts: 1.21

Technical data: 1.22 - 1.35

Approximate dimensions: 1.36 - 1.49

1.34

IEC technical data for across the line contactors DC circuit switching
Technical data :
G The

tables indicate for the standard contactors the max. operating currents Ie depending on : the utilization category (i.e. L/R) DC-1, DC-3, DC-5 (as defined in the publication IEC 947-4-1 (see section 7 for more details) the operating voltage Ue the pole coupling details. G Max. switching frequency : 300 ops/h. G For series connection of the poles, use connecting strips LP and LH described in section 4. G For switching higher d.c. ratings, we recommend the use of bar mounted contactors, R series (63 2000 A). G Standard accessories can be fitted.

A.C. & D.C. operated contactors


Type A95 A110 EK 110 EH 145 EK 150 EH 175 EH 210 EK 175 EK 210 EH 260 EH 300 EH 450 EH 550 EH 700 EH 800 Utilization category DC-1 L/R 1 ms 110 V A 120 145 145 175 210 210 210 260 305 370 550 700 750

Consult factory

220 V

Consult factory

200

200

200

260

300

300

300

400

445

550

800

1000

1000

220 V 440 V 600 V 440 V 600 V

A A A A A

200 200

200

200 200

260 170

300 210

300 210 260 260

300 210 300 300

400 270

445 300

550 450 450

800 650 650

1000 800 800

1000 800 800

Utilization category DC-3 L/R 2 ms 72 V A

120

145

145

175

210

210

210

260

305

370

550

700

700

Consult factory

220 V

Consult factory

135

135

135

170

210

210

210

260

300

450

650

800

800

220 V 440 V 600 V 440 V 600 V

A A A A A

135 135

135

135 135

170 170

210 210

210 210 170 170

210 210 210 210

260 260

300 300

450 450 450

650 650 650

800 800 800

800 800 800

Utilization category DC-5 L/R 7.5 ms 220 V A Consult factory Consult factory 135 135 135 170 210 210 210 260 300 450 650 800 800

220 V 440 V 600 V 440 V


AC 1000 2/97

A A A A

135 135

135

135 135

170 170

210 210

210 210 170

210 210 210

260 260

300 300

450 450 450

650 650 650

800 800 800

800 800 800

CONTACTORS:

Selection: 1.4 - 1.7

Accessories: 1.8 - 1.20

Renewal parts: 1.21

Technical data: 1.22 - 1.35

Approximate dimensions: 1.36 - 1.49

1.35

Approximate dimensions for across the line contactors B9 - B75, non-reversing


00.00
00.00

Inches
Millimeters

B9 - B16
1.74
44.0

3.23
82.0

2.99
76.0

1.38
35.0

0.12
3.0

2.72
69.0

2.36 1.89
60.0 48.0

1.34
34.0

1.77
45.0

0.35
9.0

0.16
4.2

0.12
3.0

0.22
5.5

B25
3.23
82.0

1
3.19
81.0

3.18
80.7

0.18
4.5

2.76 2.36 1.97


70.0 60.0 50.0

0.35 2.13
54.0 9.0

1.57
40.0

0.22
5.5

1.77
45.0

B30
5.08
129.0

3.69
93.7 88.0

3.46 0.16
4.2

3.55
90.0

3.15 2.76
80.0 70.0

0.39 2.13
54.0 10.0

1.77
45.0

0.22
5.5

B40 - B75

4.21
107.0

0.24
6.2

3.98
101.0

4.33
110.0

3.94
100.0

3.54
90.0

2.75
70.0

0.39
10.0

3.23
82.0

2.36
60.0

AC 1000 2/97

0.24
6.0

CONTACTORS:

Selection: 1.4 - 1.7

Accessories: 1.8 - 1.20

Renewal parts: 1.21

Technical data: 1.22 - 1.35

Approximate dimensions: 1.36 - 1.49

1.36

Approximate dimensions for across the line contactors BC9 - BE75, DC operated
00.00
00.00

Inches
Millimeters

BC9 - BC16
4.26
108.0

4.48
114.0

0.18
4.5

3.18
81.0

2.76
70.0

2.36
60.0

0.35 1.75
44.0 9.0

1.38
35.0

0.24
5.5

BC25

4.68
119.0

1.77
45.0

2.76 3.34
84.8 70.0

2.36
60.0

0.35 2.12
54.0 9.0

0.24
5.5

BC30
6.34
161.0

4.72

120.0

1.77
45.0

3.15 3.55
90.0 80.0

2.76
70.0

2.13
54.0

BE40 - BE75
101.0

107.0

4.21 0.24
6.2

3.98

3.94
100.0

4.33
110.0

3.54
90.0

2.75

AC 1000 2/97

70.0

0.39
10.0

2.36
60.0

3.71
94.2

0.24
6.0

CONTACTORS:

Selection: 1.4 - 1.7

Accessories: 1.8 - 1.20

Renewal parts: 1.21

Technical data: 1.22 - 1.35

Approximate dimensions: 1.36 - 1.49

1.37

Approximate dimensions for across the line contactors Accessories, B contactors


00.00
00.00

Inches
Millimeters

Single pole auxiliary contact block


A

Four pole auxiliary contact block


B

Pneumatic timer block

On-position latch
C D

Mechanical interlock, D.C. operated


E

TYPES K, B9, B12, B16 B25 B30 B40, B50, B63, B75 KC, BC9, BC16 BC25 BC30 BE40, BE50, BE63, BE75 IN.

A 4.09 4.61

C 5.31

D 6.02 6.22

E -

MM

104.0

117.0

135.0

153.0

IN. IN. IN. IN.

MM MM MM MM

4.29 4.57 5.10 5.35

109.0

4.80 5.08 5.61 5.87

122.0

5.51 5.79 6.32 6.57

140.0

158.0

5.04
128.0

116.0

129.0

147.0

165.0

6.50

129.5 136.0

142.5 149.0

160.5 167.0

7.03 7.28

178.5 185.0 191.0

IN.
MM

5.59
142.0

6.10
155.0

6.81
173.0

7.52 7.76
197.0

5.28
134.0

IN.
MM

5.83
148.0

6.34
161.0

7.05
179.0

5.51
140.0

IN.
MM

5.10
129.5

5.61
142.5

6.32
160.5

7.03
178.5

AC 1000 2/97

CONTACTORS:

Selection: 1.4 - 1.7

Accessories: 1.8 - 1.20

Renewal parts: 1.21

Technical data: 1.22 - 1.35

Approximate dimensions: 1.36 - 1.49

1.38

Approximate dimensions for across the line contactors A95 A110


00.00
00.00

Inches
Millimeters

A95 A110 with additional CA5-10 or CA5-01 1 pole auxiliary contact block
5.90

150.0

5.83
148.0

3.54
90.0

4.01
102.0

A95 A110 with additional 2 pole CAL5-11auxiliary contact block


4.86

123.5

5.83
148.0

3.54
90.0

4.01
102.0

A95 A110 with additional 4 pole CA5-40E or CA5-22E auxiliary contact block

157.0

6.18

5.83
148.0

3.54

AC 1000 2/97

90.0

4.01
102.0

CONTACTORS:

Selection: 1.4 - 1.7

Accessories: 1.8 - 1.20

Renewal parts: 1.21

Technical data: 1.22 - 1.35

Approximate dimensions: 1.36 - 1.49

1.39

Approximate dimensions for across the line contactors EH145 EH260


00.00
00.00

Inches
Millimeters

EH145
5.89
149.6

*
0.44
11.2

NOTE: FOR DC-OPERATED CONTACTORS, THE DC AUXILIARY BLOCK AND ECONOMISING RESISTOR ADD 1.00" TO THE WIDTH OF THE EH CONTACTORS. 5.63
143.0

4.89
124.2

1.65
41.9

0.225
5.7

0.12
3.0

3.57
90.7

*
1
0.79
20.0

5.52
140.2

4.72 6.74
171.2 120.0

4.33
110.0

EH175 & EH210


5.35
136.0

6.65
169.0

1.77
45.0

0.43
11.0

0.19
5.0

4.07
103.5

0.25
6.4

6.14
156.0

7.79
198.0

5.51
140.0

4.72
120.0

EH260

176.0

6.92 0.19
5.0

175.0

6.88

= 0.25
6.4

62.0

2.44

= 0.43
11.0

4.05
102.9

6.14
156.0

207.0

8.14

5.51
140.0

AC 1000 2/97

6.30
160.0

CONTACTORS:

Selection: 1.4 - 1.7

Accessories: 1.8 - 1.20

Renewal parts: 1.21

Technical data: 1.22 - 1.35

Approximate dimensions: 1.36 - 1.49

1.40

Approximate dimensions for across the line contactors EH300 EH550


00.00
00.00

Inches
Millimeters

EH300
2.44

6.92
176.0

6.88
175.0

= 0.25
6.4

= 0.43
11.0

0.19
5.0

4.05
102.9

62.0

6.14
156.0

207.0

8.14

5.51
140.0

1
6.30
160.0

EH450

8.80
223.5

*
= 0.44
11.2

NOTE: FOR DC-OPERATED CONTACTORS, THE DC AUXILIARY BLOCK AND ECONOMISING RESISTOR ADD 1.00" TO THE WIDTH OF THE EH CONTACTORS. = 0.24
6.1

7.80
198.1

2.71
68.8

8.88
225.6

= 0.59 0.20
5.1

5.34
135.6

15.0

224.0

8.82

7.87 10.69
271.5 200.0

0.98
25.0

6.69
170.0

EH550

8.80
223.5

7.80
198.1

*
11.0

NOTE: FOR DC-OPERATED CONTACTORS, THE DC AUXILIARY BLOCK AND ECONOMISING RESISTOR ADD 1.00" TO THE WIDTH OF THE EH CONTACTORS. 8.89
226.0

2.71
68.8

= 0.43 0.23
6.0

= 0.25 5.51
134.0 6.4

*
AC 1000 2/97

10.70
223.0

8.77

272.0

200.0

7.87

6.69
170.0

CONTACTORS:

Selection: 1.4 - 1.7

Accessories: 1.8 - 1.20

Renewal parts: 1.21

Technical data: 1.22 - 1.35

Approximate dimensions: 1.36 - 1.49

1.41

Approximate dimensions for across the line contactors EH700 EH800


00.00
00.00

Inches
Millimeters

EH700

10.61
269.5

*
= 0.44
11.2

NOTE: FOR DC-OPERATED CONTACTORS, THE DC AUXILIARY BLOCK AND ECONOMISING RESISTOR ADD 1.00" TO THE WIDTH OF THE EH CONTACTORS. 8.88
225.5

9.61
244.0

= 0.24
6.1

3.21
81.5

= 0.59 0.24
6.1 135.6

5.34

15.0

8.78
223.0

11.57
294.0

7.87
200.0

40.0

1.57

8.66
220.0

EH800
10.61
269.5

FOR DC-OPERATED CONTACTORS, THE DC AUXILIARY BLOCK AND ECONOMISING RESISTOR ADD 1.00" TO THE WIDTH OF THE EH CONTACTORS. * NOTE: 8.88 D = 0.44
11.2 225.5

9.61
244.0

3.59
91.2

0.24
6.1

5.34
135.6

= 0.24
6.1

= 0.59
15.0

1.36
34.5

18.14

460.8

8.78
223.0

7.87
200.0

13.44
341.4

8.66
220.0

AC 1000 2/97

CONTACTORS:

Selection: 1.4 - 1.7

Accessories: 1.8 - 1.20

Renewal parts: 1.21

Technical data: 1.22 - 1.35

Approximate dimensions: 1.36 - 1.49

1.42

Approximate dimensions for across the line contactors B9 B75, mechanically interlocked & reversing
00.00
00.00

Inches
Millimeters

B9 - B16

5.50
139.7 123.2

4.23
107.4

4.85 0.22 4.09


5.5 104.0

0.79
20.0

0.22
5.5

2.98
76.0

0.12
3.0

2.36
60.0

2.72
70.0

133.4

5.25

1.77
45.0

1.89
48.0

4.63
117.6

0.12 3.91
99.5 3.0

0.22
5.5

0.16
4.2

NOTE: Baseplate for DC ONLY

1.38

35.0

B25
5.25
133.4 115.8

1
4.64
117.9

4.56

0.18 0.22
5.5 4.5

4.26
108.0

0.22
5.5

3.16
80.0

2.36 5.25
133.4

4.64
117.9

3.19
81.0

2.76
70.0

60.0

1.97
50.0

40.0

1.57 1.77
45.0

119.0

4.69

0.79
20 0

B30
133.4

5.25

136.7 129.0

5.48 0.22
5.5 88.0

4.64
117.9

5.08 3.46

0.22
5.5

0.18
4.5

3.15
133.4 3.55 90.0

5.25

80.0

4.64
117.9

2.75
70.0

1.77 4.68
119.0 45.0

0.79
20.0

B40 - B75
6.62
168.1

5.85
148.5

0.22 4.21
107.0 5.5

6.00 0.22 152.4


5.5

3.98
101.0

0.24
6.2

6.50
165.1

3.95 4.33
100.0

5.87
149.1

110.0

3.55
90.0

AC 1000 2/97

6.89

2.36

CONTACTORS:

Selection: 1.4 - 1.7

175.0

Accessories: 1.8 - 1.20

Renewal parts: 1.21

Technical data: 1.22 - 1.35 3.19


81.0

60.0

Approximate dimensions: 1.36 - 1.49

1.43

Approximate dimensions for across the line contactors A95 EH210, mechanically interlocked & reversing
00.00
00.00

Inches
Millimeters

A95 & A110


8.70
221.0

7.91 5.17
131.3 200.1

123.5

4.86

0.24
6.2

8.10
205.7

136.0

5.35 4.96 7.28


185.0

5.82
148.0

126.0

1
7.67
195.0

3.07
78.0 104.1

4.10

EH145

12.56
319.0

12.50 0.51
13.0 146.1 317.5

*
11.50
292.1

5.75

0.31
7.9

NOTE: FOR DC-OPERATED CONTACTORS, THE DC AUXILIARY BLOCK AND ECONOMISING RESISTOR ADD 1.00" TO THE WIDTH OF THE EH CONTACTORS. 0.51 6.25 13.0 158.8 6.42 163.0 0.312 0.16 7.9 4.33
4.1 110.0

203.2

8.00 7.12
180.8

7.12
181.0

0.312
7.9

145.0

5.71

0.50
12.5

11.5
292.1

EH175 & EH210


14.00
355.5

7.55
191.7

13.00
330.2

13.00 6.50
163.0 330.2

0.54 4.94
125.5 13.5

0.31
7.9

0.19
5.0

7.00
178.0

0.312
7.9

6.50
163.0

8.88
225.6

7.79
198.0

7.96
202.0

7.96
202.1

0.312
7.9

6.14
156.0

0.50
12.5

13.00
330.0

AC 1000 2/97

CONTACTORS:

Selection: 1.4 - 1.7

Accessories: 1.8 - 1.20

Renewal parts: 1.21

Technical data: 1.22 - 1.35

Approximate dimensions: 1.36 - 1.49

1.44

Approximate dimensions for across the line contactors EH260 EH450 mechanically interlocked & reversing
00.00
00.00

Inches
Millimeters

EH260

17.53
445.0

7.78 16.34
415.0

0.19
5.0

197.6

16.34 415.0

4.94
125.5

9.06
230.0

8.14
207.0
7.87 200.0 = 0.59 15.0

7.87
200.0

= 0.59
15.0

7.66
194.6

EH300

17.53
445.0

7.78 16.34
415.0

16.34
415.0

0.19
5.0

197.6

4.94
125.5

9.06
230.0

8.14
207.0

7.87
200.0

7.87
200.0

= 0.59
15.0

= 0.59
15.0

7.66
194.6

EH450
19.13
486.0

18.90
480.0

NOTE: FOR DC-OPERATED CONTACTORS, THE DC AUXILIARY BLOCK AND ECONOMISING RESISTOR ADD 1.00" TO THE WIDTH OF THE EH CONTACTORS. 10.67
271.0

17.72
450.0

0.20
5.1

17.72 7.14
181.4 450.0

11.61
295.0

10.69
271.5

10.43
265.0

= 0.59
15.0

= 0.59 AC 1000 2/97


15.0

9.46
240.0

CONTACTORS:

Selection: 1.4 - 1.7

Accessories: 1.8 - 1.20

Renewal parts: 1.21

Technical data: 1.22 - 1.35

Approximate dimensions: 1.36 - 1.49

1.45

Approximate dimensions for across the line contactors EH550 EH800, mechanically interlocked & reversing
00.00
00.00

Inches
Millimeters

EH550
19.16
486.7

10.69
271.5

18.90
480.0

0.23
6.0

*
7.31
185.6

NOTE: FOR DC-OPERATED CONTACTORS, THE DC AUXILIARY BLOCK AND ECONOMISING RESISTOR ADD 1.00" TO THE WIDTH OF THE EH CONTACTORS. 17.72
450.0

11.61
295.0

10.43
265.0

10.77
272.0

10.43
265.0

= 0.59
15.0

9.46
240.0

EH700

22.83
580.0

10.67
271.0

0.24
6.1

7.14
181.4

NOTE: FOR DC-OPERATED CONTACTORS, THE DC AUXILIARY BLOCK AND ECONOMISING RESISTOR ADD 1.00" TO THE WIDTH OF THE EH CONTACTORS. 21.65
550.0

11.61
295.0

*
= 0.59
15.0

11.57
294.0

10.43
265.0

= 0.59
15.0

11.42
290.0

EH800
22.83
580.0

10.67 0.24
6.1 271.0

7.14
181.4

NOTE: FOR DC-OPERATED CONTACTORS, THE DC AUXILIARY BLOCK AND ECONOMISING RESISTOR ADD 1.00" TO THE WIDTH OF THE EH CONTACTORS. 21.65
550.0

18.14
460.8

11.61
295.0

10.43
265.0

13.44
341.4

= 0.59
15.0

= 0.59
15.0

11.42
290.0

AC 1000 2/97

CONTACTORS:

Selection: 1.4 - 1.7

Accessories: 1.8 - 1.20

Renewal parts: 1.21

Technical data: 1.22 - 1.35

Approximate dimensions: 1.36 - 1.49

1.46

Approximate dimensions for across the line contactors EH145 EH800, mechanically latched
00.00
00.00

Inches
Millimeters

EH145 EH800

B1 B G D1 K1 T1

P P1 0.12
3.00

H H1

C1

DIM.. EH 145 EH 175 EH 210 EH 260 EH 300 EH 450 EH 550 EH 700 EH 800 in
mm

B 6.29
160

B1 6.57
167

C 5.51
140

C1 4.72
120

D1 0.26
6.6

F 1.61
41

G 0.59
15

H 5.51
140

H1 6.14
156

K1 0.30
7.5

P 7.88
202

P1 3.58
97

T1 0.16
4

in
mm

7.09
180

7.01
1 78

6.38
162

5.59
142

0.43
11

1.77
45

0.79
20

6.30
160

7.80
198

0.39
10

8.86
225

4.29
109

0.20
5

in
mm

7.09
180

7.01
178

6.38
162

5.59
142

0.43
11

1.77
45

0.79
20

6.30
160

7.80
198

0.39
10

8.86
225

4.29
109

0.20
5

in
mm

9.61
244

9.13
232

8.58
218

5.32
135

0.43
11

2.44
62

0.98
25

6.50
165

8.15
207

0.49
12.5

9.49
241

4.69
119

0.20
5

in
mm

9.61
244

9.13
232

8.58
218

5.32
135

0.43
11

2.44
62

0.98
25

6.50
165

8.15
207

0.49
12.5

9.49
241

4.69
119

0.20
5

in
mm

9.45
240

9.45
240

8.27
210

10.04
255

0.43
11

2.64
67

0.98
25

11.22
285

10.71
272

0.49
12.5

11.65
296

5.77
146.5

0.24
6

in
mm

9.45
240

9.45
240

8.27
210

10.04
255

0.43
11

2.64
67

0.98
25

11.22
285

10.71
272

0.49
12.5

11.65
296

5.77
146.5

0.24
6

in
mm

11.42
290

11.42
290

10.24
260

10.04
255

0.43
11

3.23
82

1.58
40

11.22
285

11.58
294

0.79
20

11.65
296

5.77
146.5

0.24
6

in
mm

11.42
290

11.42
290

10.24
260

10.04
255

0.43
11

3.62
92

1.97
50

11.22
285

13.54
344

0.79
20

11.65
296

5.77
146.5

0.24
6

AC 1000 2/97

CONTACTORS:

Selection: 1.4 - 1.7

Accessories: 1.8 - 1.20

Renewal parts: 1.21

Technical data: 1.22 - 1.35

Approximate dimensions: 1.36 - 1.49

1.47

Approximate dimensions for across the line contactors EH145 EH800, mechanically interlocked, mechanically latched
00.00
00.00

Inches
Millimeters

EH145 EH800
MECHANICAL LATCH IF USED K AA A C G H D DD

J F

1
DIM.. EH 145 EH 175 EH 210 EH 260 EH 300 EH 450 EH 550 EH 700 EH 800 in
mm

A 12.50
317.5

AA 18.00
457.2

B 8.00
203.2

C 6.49
164.8

D 11.50
292.1

DD 17.00
431.8

E 7.12
180.8

F 0.31
7.9

G 4.44
112.8

H 0.08
2

J 1.58
40

K 9.18
233.2

L 0.86
21.8

in
mm

14.00
355.6

18.50
469.9

8.88
225.5

7.51
190.8

13.00
330.2

17.50
444.5

7.97
202.4

0.31
7.9

4.93
125.4

0.11
2.7

0.59
15

10.07
255.8

0.86
21.8

in
mm

14.00
355.6

18.50
469.9

8.88
225.5

7.51
190.8

13.00
330.2

17.50
444.5

7.97
202.4

0.31
7.9

4.93
125.4

0.11
2.7

0.59
15

10.07
255.8

0.86
21.8

in
mm

17.53
445.3

24.73
628.1

9.06
230.1

7.75
196.8

16.34
415

23.60
599.4

7.88
200.2

0.59
15

4.94
125.5

0.11
2.7

1.18
30

10.63
270

0.86
21.8

in
mm

17.53
445.3

24.73
628.1

9.06
230.1

7.75
196.8

16.34
415

23.60
599.4

7.88
200.2

0.59
15

4.94
125.5

0.11
2.7

1.18
30

10.63
270

0.86
21.8

in
mm

19.13
486

30.00
762

11.61
294.8

10.87
276

17.72
450

29.00
736.6

10.43
264.9

0.59
15

7.48
190

0.12
3

1.58
40

12.93
328.4

1.96
50

in
mm

19.13
486

30.00
762

11.61
294.8

10.87
276

17.72
450

29.00
736.6

10.43
264.9

0.59
15

7.48
190

0.12
3

1.58
40

12.93
328.4

1.96
50

in
mm

22.83
580

30.00
762

11.61
294.8

10.87
276

21.65
550

29.00
736.6

10.43
264.9

0.59
15

7.48
190

0.12
3

1.58
40

12.93
328.4

1.96
50

in
mm

22.83
580

30.00
762

11.61
294.8

10.87
276

21.65
550

29.00
736.6

10.43
264.9

0.59
15

7.48
190

0.12
3

1.58
40

12.93
328.4

1.96
50

AC 1000 2/97

CONTACTORS:

Selection: 1.4 - 1.7

Accessories: 1.8 - 1.20

Renewal parts: 1.21

Technical data: 1.22 - 1.35

Approximate dimensions: 1.36 - 1.49

1.48

Approximate dimensions for across the line contactors EK110 EK550, 4 pole, non-reversing
00.00
00.00

Inches
Millimeters

EK110 EK550

B G B1 D T1

P P1 T PE

F1

H1

C1

E M6 F M4 C K1 C2

1
K1
0.30 7.5 0.39 10 0.39 10 0.39 10 0.49 12.5 0.49 12.5

EK 110 EK 150 EK 175 EK 210 EK 370 EK 550

mm mm mm mm mm mm

in in in in in in

B 6.50
165

B1
5.35 136 5.35 136 6.93 176 6.93 1 76 9.61 244 9.61 1 76

C
4.72 120 4.72 120 6.30 160 6.30 160 8.66 220 8.66 220

C1
5.51 140 5.51 140 5.51 140 5.51 140 7.87 200 7.87 200

D
0.26 6.6 0.43 11 0.43 11 0.43 11 0.43 11 0.43 11

E
1,57 40 1.57 40 0.59 15 0.59 15 1.57 40 1.57 40

F
1.61 41 1.65 42 1.77 45 1.77 45

F1
1.69 43 1.65 42 2.64 67 2.64 67 2.76 70 2.76 70

6.50
165

7.91
201

7.91
201

10.51
267

2.64
67

10.51
267

2.64
67

G 0.59 15 0.79 20 0.79 20 0.79 20 0.98 25 0.98 25

H
6.14 156 6.14 156 6.14 156 6.14 156 8.78 223 8.78 223

H1
6.14 156 6.77 172 7.80 198 7.80 198 10.71 272 10.71 272

P
6.08 154.5 6.08 154.5 6.77 172 6.77 172 8.88 225.5 8.88 225.5

P1
4.03 102.3 4.03 102.3 4.20 106.7 4.20 106.7 5.49 139.5 5.49 139.5

T
0.39 10 0.39 10 0.39 10 0.39 10 0.91 23 0.91 23

T1
0.16 4 0.16 4 0.20 5 0.20 5 0.24 6 0.24 6

AC 1000 2/97

CONTACTORS:

Selection: 1.4 - 1.7

Accessories: 1.8 - 1.20

Renewal parts: 1.21

Technical data: 1.22 - 1.35

Approximate dimensions: 1.36 - 1.49

1.49

Notes
00.00
00.00

Inches
Millimeters

AC 1000 2/97

CONTACTORS:

Selection: 1.4 - 1.7

Accessories: 1.8 - 1.20

Renewal parts: 1.21

Technical data: 1.22 - 1.35

Approximate dimensions: 1.36 - 1.49

1.50

Bar contactors

Description
Variable number and type of main poles, (N.O., N.C.) Large number and type of auxiliary contacts Extremely versatile and easily accessible for maintenance Main poles maximum operating voltage: A.C. switching up to 500 V, Type IOR A.C. switching up to 1200V, Type IOR - MT D.C. switching up to 440V, Type IOR D.C. switching up to 750V, Type IOR - CC Specific construction available as standard: Contactors with N.O./N.C. main poles, with or without overlapping Contactors wtih magnetic latch or mechanical latch

Applications
Bar mounted contactors are largely used in the iron and steel industry for traction (rolling stock), electrolysis and hoisting equipment for applications from 63A to 5000A.

, tion a m for ! n i l ona call us i t i add lease r o p F

AC 1000 2/97

Discount schedule IA

1.51

Notes

AC 1000 2/97

1.52

Discount schedule IA

This information is provided by:

Gross Automation 1725 S. Johnson Rd. New Berlin, WI 53146-1240 (877) 268-3700 Fax: (877) 268-9700